19334-e-0-100kwlowspeeddatasheet
TRANSCRIPT
-
8/4/2019 19334-E-0-100kWlowspeedDataSheet
1/4
Liquid Cooled Gas Generators100 kW 60Hz
www.sea.siemens.com/generators
Data Sheet
Standard EquipmentJ All input connections in one single areaJ High coolant temperature shutdownJ Low oil pressure shutdownJ Low coolant level automatic shutdownJ Low fuel pressureJ Overspeed automatic shutdownJ Adjustable cranking timerJ Adjustable exercise timer
J Oil drain extensionJ Cool ow radiator
J Closed coolant recovery systemJ UV/Ozone resistant hosesJ Watertight state of the art electrical connectorsJ Mainline circuit breakerJ Oil drain extension to frame railJ Radiator drain extensionJ Battery charge alternatorJ 10 Amp static battery chargerJ Battery and battery cablesJ Battery rackJ Fan and belt guardsJ Isochronous governorJ Coolant heater
FeaturesJ Innovative design and fully prototype testedJ UL2200 ListedJ Solid state frequency compensated digital voltage
regulatorJ Dynamic and static battery chargerJ Sound attenuated acoustically designed enclosureJ Quiet test for low noise level exerciseJ Acoustically designed engine cooling systemJ High ow low noise factory engineered exhaust
systemJ State of the art digital control system with H-100
microprocessor control panelJ Built-in kW, kVAR and power factor metersJ Watertight electrical connectorsJ Rodent proof constructionJ High efciency, low distortion Generac designed
alternatorJ Vibration isolated from mounting baseJ Matching Siemens transfer switches engineered and
tested to work as a systemJ Electrostatically applied powder paint
6.8L EngineNaturally AspiratedGaseous FueledGear Drive
-
8/4/2019 19334-E-0-100kWlowspeedDataSheet
2/4
Generator Specifications
Type Synchronous
Rotor Insulation Class H
Stator Insulation Class H
Total Harmonic Distortion
-
8/4/2019 19334-E-0-100kWlowspeedDataSheet
3/4
kW Rating 100
Engine Size 2.4 Liter Inline 4
Generator Output Voltage/kW - 60Hz120/240V, 1-phase, 1.0 pf120/208V, 3-phase, 0.8 pf120/208V, 3-phase, 0.8 pf277/480V, 3-phase, 0.8 pf
600V, 3-phase, 0.8 pf
kW Amp CB Size100 417 500100 300 350100 347 400100 150 175100 120 150
Generator Locked Rotor KVAAvailable @ Voltage Dip of 35%
Single phase or 208 3-phase480V 3-phase
200240
Engine Fuel Consumption (Natural Gas) (Propane)
Exercise cycle25% of rated load50% of rated load
75% of rated load100% of rated load
Natural Gas Propane(ft3/hr) (gal/hr) (cu ft/hr)
130 1.42 52.3371 4.06 149.4713 7.81 287.4
994 10.88 400.41260 13.80 507.8
Engine CoolingAir flow (inlet air including alternator and combusiton air) ft3/min.System coolant capacity US gal.Heat rejection to coolant BTU/hr.Max. operating air temp. on radiator C (F)Max. ambient temperature C (F)
5,5004.5
342,00060 (150)50 (140)
Combustion Air RequirementsFlow at rated power 60 Hz cfm
262
Sound Emissions in DBAExercising at 7 metersNormal operation at 7 meters
6172
ExhaustExhaust flow at rated output 60 Hz cfmExhaust temp. at muffler outlet F
888960
Engine ParametersRated sychronous RPM 60 HzHP at rated kW 60 Hz
2300168
Power Adjustment For Ambient ConditionsTemperature Deration
3% for every 10 C above - C1.65% for every 10 F above - F
Altitude Deration1% for every 100 m above - m
3% for every 1000 ft. above - ft.
2577
183600
Operating Data100kW Liquid Cooled
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply
to installations served by a reliable utility source. The standyb rating is applicable to varying loads for the duration of a power outage. There is no overload
capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
-
8/4/2019 19334-E-0-100kWlowspeedDataSheet
4/4
Transfer Switch
H100 Control Panel Utility In
Gen
LoadOut
GeneratorConnectionBox
15 Amp 120Volt BattChargerCircuit
2 Wire Shielded CableW/Ground To TransferSW. GRDD @ GENSETOnly.
Stub-Up AreaSee Detail f or DimensionsReference Installation Dwg.0G1408 - Enclosed Set0G1541 - Open Set
Ground Level
To Generator Control Panel
2 Wire ShieldedCable W/GroundTo Generator
ToAlternator
CIRCUIT BREAKER SIZEKW VOLTS CB AMPS LUG SIZE100 240 1 500 3-2/0 to 400 mcm
100 240 3 350 2-3/0 to 500 mcm100 208 3 400 (1) 600 MCM or (2) 1/0)100 480 3 175 #6 to 300 mcm100 600 3 150 #6 to 350 mcm
Interconnections100kW Liquid Cooled
Installation Layout100kW Liquid Cooled
. .
-
.--
Note:Door accessfrom both sides
Door
Siemens Energy & Automation, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-964-4114
2008 Siemens Energy & Automation, In
All Rights Reserved. Siemens is a register
trademark of Siemens AG. Product names
mentioned may be trademarks or registe
trademarks of their respective companies
Specifications are subject to change with
notice.
RPFL-QT100-0908 (New) 0908POD
www.sea.siemens.com/generato