HURRICANE ENGINEERING & TESTING INC. ISO 17025 Accredited Computer Controlled Product Testing Wind Load Design, Analysis & Evaluation 6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 1/6 Salt Spray (Prohesion) Testing (ASTM G 85-11 Annex A5) April 7, 2016 REPORT NUMBER: HETI-16-S300 CLIENT: PrimeSource Building Products, Inc. 1321 Greenway Drive, Irving, Texas 75038. TEST LOCATION: Hurricane Engineering & Testing Inc. 6120 NW 97 th Avenue, Doral, Florida, 33178 NOTIFICATION NUMBER: HETI16005 (MIAMI-DADE COUNTY, FLORIDA) LAB. CERTIFICATION No.: 15-1216.04 (MIAMI-DADE COUNTY, FLORIDA) IAS. CERTIFICATION No.: TL-296 (ISO 17025-05) FBC ORGANIZATION No: TST1691 FBPE Certificate of Authorization Number: 6905 PRODUCT: 1-¼” x 0.120” Ring Shank 15 o Wire Weld Coil Collated Roofing Nail BATCH IDENTIFICATION: P.O. #: 81-043294; I.D. Code: R04, Electrogalvanized Class 1. PRODUCT SIZE: 0.119” x 1.19” x 0.361” Head Diameter x 25 Rings/Inch. MAJOR/MINOR DIAMETER: Major: 0.119”, Minor: 0.113”. TEST WITNESSED BY Syed Waqar Ali, Ph. D. (HETI) Dr. Nasreen K. Ali. (HETI) Mr. Eugenio Rivera (HETI) Mr. Rafael E. Droz-Seda, P.E. (HETI) Coated 1-¼” x .120” Ring Shank 15 o Wire Weld Coil Non-coated 1-¼” x .120” Ring Shank 15 o Wire Weld Coil

Upload: others

Post on 29-Jul-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

HURRICANE ENGINEERING & TESTING INC. ISO 17025 Accredited Computer Controlled Product Testing Wind Load Design, Analysis & Evaluation

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 1/6

Salt Spray (Prohesion) Testing (ASTM G 85-11 Annex A5)

April 7, 2016 REPORT NUMBER: HETI-16-S300 CLIENT: PrimeSource Building Products, Inc.

1321 Greenway Drive, Irving, Texas 75038.

TEST LOCATION: Hurricane Engineering & Testing Inc. 6120 NW 97th Avenue, Doral, Florida, 33178 NOTIFICATION NUMBER: HETI16005 (MIAMI-DADE COUNTY, FLORIDA) LAB. CERTIFICATION No.: 15-1216.04 (MIAMI-DADE COUNTY, FLORIDA) IAS. CERTIFICATION No.: TL-296 (ISO 17025-05) FBC ORGANIZATION No: TST1691 FBPE Certificate of Authorization Number: 6905 PRODUCT: 1-¼” x 0.120” Ring Shank 15o Wire Weld Coil Collated Roofing Nail BATCH IDENTIFICATION: P.O. #: 81-043294; I.D. Code: R04, Electrogalvanized Class 1. PRODUCT SIZE: 0.119” x 1.19” x 0.361” Head Diameter x 25 Rings/Inch. MAJOR/MINOR DIAMETER: Major: 0.119”, Minor: 0.113”. TEST WITNESSED BY Syed Waqar Ali, Ph. D. (HETI) Dr. Nasreen K. Ali. (HETI) Mr. Eugenio Rivera (HETI) Mr. Rafael E. Droz-Seda, P.E. (HETI)

Coated 1-¼” x .120” Ring Shank 15o Wire Weld Coil Non-coated 1-¼” x .120” Ring Shank 15o Wire Weld Coil

Page 2: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 2/6

The coated 1-¼” x .120” Ring Shank 15o Wire Weld Coil samples were delivered by Miami-Dade Product Control to HETI on March 23, 2016. The non-coated Roofing nails were delivered via DHL Directly to Hurricane Engineering & Testing, Inc. on April 4, 2016 from Qingdao Golden Sunshine Metal at Products Co Ltd, Jiaobei Industrial Park Jiaozhou Ingdao China.

Microscope Photos

Microscope Photos at 400x Resolution (Coated Roofing Nails)

Microscope Photos at 400x Resolution (Non-coated Roofing Nails)

duncans
Rectangle
duncans
Rectangle
Page 3: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 3/6

Product Description

Coating Thickness Analysis

Attribute Units Value Nail Shaft Length cm 3.04 Nail Shaft Diameter cm 0.29 Nail Surface Area cm2 0.42 Nails per Coil - 120 Average Weight per Coated Nail Coil. (average of 5) g 221 AverageWeight per Bare Nail Coil. (average of 5) g 220 Coating Weight per Coil g 1 Coating Weight per Nail µg 8333 Coating Density g/cm3 5.58 Coating Surface Density µg/cm2 19840 Maximum Coating Thickness (using measured coating weight) µm 34 Maximum Coating Thickness. (using Microscopic analysis) µm --- Maximum Coating Thickness using XRF Analysis µm 30 Minimum Coating Thickness using XRF Analysis µm 10 Average Coating Thickness. (ASTM E376 using microprobe)* µm 24 Maximum Coating Thickness. (ASTM E376 using microprobe)* µm 35 Minimum Coating Thickness. (ASTM E376 using microprobe)* µm 15 *: Measurement made on the nail head using n=100.

Nail Material Composition

The nail material composition was determined by XRF analysis as per ASTM E1621–13.

Analyte Result %

(Std.Dev.) Proc.-Calc. Line Int

cps/uA Fe 99.331 0.146 Quan-FP FeKα 178.9861 Mn 0.353 0.013 Quan-FP MnKα 0.6933 Si 0.152 0.012 Quan-FP SiKα 0.0149 Cr 0.109 0.006 Quan-FP CrKα 0.3242 S 0.054 0.003 Quan-FP S Kα 0.0234

Page 4: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 4/6

Double Shear Strength Results Unexposed Coated 1-1/4” x .120” Ring Shank 15o Wire Weld Coil

(Test Reference HETI-16-M509)

Sample No. Maximum Force (lb) No. 1 1206 No. 2 1284 No. 3 1116 No. 4 1299 No. 5 1206 No. 6 1092 No. 7 1225 No. 8 1330 No. 9 1371

No. 10 1177 Average 1231

S.D. 90 % COV. 7.35

Load-Position

0200400600800

100012001400160018002000

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2in

lb

Salt Spray Exposed (280 Hours) Coated 1-1/4” x .120” Ring Shank 15o Wire Weld Coil

(Test Reference HETI-16-M510 Fiberglass Base Mounted ) Sample No. Maximum Force (lb)

No. 1 1251 No. 2 1303 No. 3 1445 No. 4 1353 No. 5 1411

Average 1353 S.D. 79

% COV. 5.82

Load-Position

0200400600800

100012001400160018002000

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2in

lb

Page 5: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 5/6

TEST DESCRIPTION The samples were tested to meet Miami-Dade County requirements per checklist #0195 for corrosion resistance per ASTM G 85, Annex 5, and 140 cycles as detailed in TAS 114, Appendix E. A group of five samples was mounted in a fiber glass plate, placed in the bottom channel and were placed in the chamber. Samples were delivered by Miami-Dade Product Control to HETI on March 23, 2016.

TEST PARAMETERS

1. Fog: 250 C, 1:00 hour. 2. Dry: 350 C, 1:00 hour. 3. Solution: 0.05% Sodium Chloride & 0.35% Ammonium Sulfate. 4. pH: 5.0-5.4. 5. Fog Decomposition Rate: 1 to 2 milliliters/hour (Min 16 hour collection Time) 6. Spray Pressure: 14 psi 7. Flow Rate: 0.3 liters/hour pray Pressure 8. Exposure Required: 280 Hour 9. Number of Samples: 5 10. Solution Specific Gravity 1.004 Test Equipment: Q-FOG CCT-600 by Q-Panel Lab Products, HETI-0985. Test Start and End Dates: March 23, 2016 – April 4, 2016 Fiberglass Base Setup

Hours Elapsed

Chamber Temperature oC %Corrosion

Observed Corrosion Observed

Fog Deposition Rate ml/hr

Collected Solution

pH Collected Solution Specific Gravity

Interruption time (min) Fog Dry

0 25 34 0 No --- --- --- --- 168 25 34 <5 Yes 2.0 5.1 1.01 5 280 24 34 <5 Yes 2.0 5.1 1.01 5

*All nails were tested by being installed onto a fiberglass base.

Samples at 0 Hours Samples at 280 Hours

Page 6: 16-S300-PRIME SOURCE-Salt Spray - Grip-Rite · Microsoft Word - 16-S300-PRIME SOURCE-Salt Spray Author: Nasreen Created Date: 4/7/2016 3:46:48 PM

6120 NW 97th Avenue, Doral, Florida, 33178 • Phone 305-597-5590 • Fax 305-597-7023 Report No. HETI-16-S300, Page 6/6

Conclusion

The samples of Ring Shank 150 wire weld Coil Roofing Nails were tested in accordance with Florida Building Code TAS114 Appendix E Section 2 ASTM G 85, Annex A5. The samples were examined after 140 cycles (280 hours) and were found to have less than 5% surface corrosion, meeting the requirement of TAS 114 Appendix E section 2.6.1.1 of Florida Building Code for High Velocity Hurricane Zone. NOTE: The above results were obtained using the designated test methods, which indicates compliance with the performance requirements of the referenced specifications. This report does not constitute certification of the specimens tested. STATEMENT OF INDEPENDENCE The Hurricane Engineering & Testing, Inc., does not have, nor does it intend to acquire or will acquire, a financial interest in any company manufacturing or distributing products tested or labeled by the Hurricane Engineering & Testing, Inc. Hurricane Engineering & Testing, Inc., is not owned, operated or controlled by any company manufacturing or distributing products it test or labels. _______________________ ______________________ Dr. Nasreen K. Ali Mr. Rafael E. Droz-Seda, P.E. Vice President Resident Engineer