Australia/Energy/Building and Construction Cables/Multicore/600-1000V/1.5mm, PVC, Armoured VERSION:
ENERGY CABLES
Building &
Construction Circular
PVC
2-20C + E SWA, 1.5mm2
APPLICATION For control circuits unenclosed, enclosed in conduit, buried direct or in underground ducts for commercial, industrial, mining and electricity authority systems mechanical damage may occur.
Suitable for glanding.
STANDARD AS/NZS 5000.1
VOLTAGE 600/1000V
CONDUCTOR Copper 1.5mm2
INSULATION PVC, V-90 White (with markings) & Green/Yellow
SHEATH PVC, 5V-90 Orange or Black
MAX. OPERATING TEMP.
90C
TECHNICAL SPECIFICATIONS
ITEM NUMBER
CONDUCTOR OVERALL DIAMETER APPROX. MASS kg/km
MINIMUM INSTALLED BENDING RADIUS mm
NUMBER OF CORES
mm2 (No./mm) MIN
mm MAX mm
15059xxx 2C + E 1.5 7/0.50 13.8 14.7 370 180 15062xxx 4C + E 1.5 7/0.50 15.6 16.6 445 200 15063xxx 6C + E 1.5 7/0.50 16.5 17.5 510 215 15065xxx 8C + E 1.5 7/0.50 19.4 20.5 715 245 15067xxx 10C + E 1.5 7/0.50 20.6 21.8 790 260 15068xxx 12C + E 1.5 7/0.50 21.8 23.1 875 275 15069xxx 15C + E 1.5 7/0.50 22.7 24.0 970 290 15090xxx 20C + E 1.5 7/0.50 25.3 26.7 1275 320
xxx=016 for Black xxx=131 for Orange
CONDUCTOR CURRENT RATING (a) ELECTRICAL CHARACTERISTICS Number of Cores
Unenclosed In Air
A
BuriedDirect
A
Buried In Ducts
A
Maximum DC Resistance @20C
/km
Maximum AC Resistance @90C
/km
Equivalent Star Reactance
/km
Single Phase Voltage Drop @90C mV/A.m
2C + E 18 21 21 13.6 17.3 0.111 30.0 3 - 20C + E 15 18 18 13.6 17.3 0.111 30.0
(a) Based on 40C ambient air temperature and where applicable, burial depth of 0.5m, soil temperature of 25C and soil resistivity of 1.2C.m/W. Based on 2 to 4 cores fully loaded with the remainder of the cores
-
GENERAL CABLE AUSTRALIA PTY LTD Level 1, 591-595 Blackburn Road Notting Hill VIC 3168 Locked Bag 220, Clayton VIC 3168, Australia Phone: 1300 363 282 FAX: 1300 363 382 EMAIL: [email protected]
Australia/Energy/Building and Construction Cables/Multicore/600-1000V/1.5mm, PVC, Armoured VERSION: 1.5mm2
, PVC, Armoured v020412
TECHNICAL SPECIFICATIONS - Continued ACTIVE / CONDUCTOR EARTH DIAMETER
UNDER ARMOUR
ARMOUR WIRE
NUMBER OF CORES
NUMBER & DIAMETER OF WIRES No/mm
NOMINAL DIAMETER mm
MINIMUM INSULATION THICKNESS mm
NOMINAL AREA. mm
2
NUMBER & DIAMETER OF WIRES No/mm
MINIMUM INSULATION THICKNESS mm
mm NOMINAL DIAMETER mm
2C + E 8.7 0.90 4C + E 10.5 0.90 6C + E 11.4 0.90 8C + E 7/0.50 1.5 0.8 1.5 7/0.50 0.6 13.6 1.25 10C + E 14.9 1.25 12C + E 16.2 1.25 15C + E 17.1 1.25 20C + E 19.0 1.60