Page 1 of 6

TRF No. IECEN60335_2_40C

Test Report issued under the responsibility of:

NCB TÜ V SÜ D Product Service GmbH

Ridlerstr. 65

D – 80339 München

Germany

TEST REPORT

IEC 60335-2-40 / EN 60335-2-40 Safety of household and similar electrical appliances

Part 2: Particular requirements for electrical heat pumps, air conditioners and dehumidifier

Report Reference No. ..................... : 077-225780-100

Date of issue..................................... : 2010-07-12

Total number of pages ...................... 6 pages

Appendix to Test Report Reference No.: 077-225780-000

Modification to the appliance ............ : Change of model names

Modification to clause ....................... : 7

Page concerned ............................... : 1-5; 7-8; 13

CB/CCA Testing Laboratory ......... : TÜ V SÜ D Korea Laboratory (TKL)

Address .................................... : #315 and 316, MARIO Tower, 222-12, Guro-Dong, Guro-Gu, 152-050, Seoul, Korea

Applicant’s name ............................ : Samsung Electronics Co., Ltd.

Address ............................................ : 416, Maetan 3-Dong, Yeongtong-Gu, Suwon-City, Kyunggi-Do 442-742, Republic of Korea

Test specification:

Standard ........................................... : IEC 60335-2-40:2002 (Edition 4) + A1:2005 + A2:2005 with IEC 60335-1:2001 (incl. Corrigendum 1:2002)+A1:2004+A2:2006 and/or EN 60335-2-40:2003 + A11:2004 + A12: 2005 + A1:2006 with EN 60335-1:2002 + A11:2004 + A1:2004 + A12:2006 +A2:2006 and EN 50366:2003+A1:2006

Test procedure ................................. : CB-Scheme

Non-standard test method…………..: N/A

Test Report Form No. ..................... : IECEN60335_2_40C

Test Report Form(s) Originator ........ : TÜ V SÜ D Product Service GmbH

Master TRF ...................................... : Dated 2008-11

Copyright © 2008 IEC System for Conformity Testing and Certification of Electrical Equipment

(IECEE), Geneva, Switzerland. All rights reserved.

This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from

the reader's interpretation of the reproduced material due to its placement and context.If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended

to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

Page 2 of 6 Report Ref. No.: 077-225780-100

TRF No. IECEN60335_2_40C

Test item description ..................... : Split Type Room Air-Conditioner (Indoor Unit)

Trade Mark ....................................... : SAMSUNG

Manufacturer .................................... : Samsung Electronics Co., Ltd. (18219)

416, Maetan3-Dong,Yeongtong-Gu, Suwon-City, Kyunggi-Do

442-742, Republic of Korea

Model/Type reference ....................... : AVXWVH056EA, NH056VHXEA, AVXWVH071EA, NH071VHXEA, MH052FVEA

Ratings ............................................. : 220-240 V~; 50 Hz; max. 50 W; max. 0,30 A; Class I

Testing procedure and testing location:

CB/CCA Testing Laboratory: TÜ V SÜ D Korea Laboratory (TKL)

Testing location/ address ...................... : #315 and 316, MARIO Tower, 222-12, Guro-Dong, Guro-Gu, 152-050, Seoul, Korea

Associated CB Laboratory: N/A

Testing location/ address ...................... : N/A

Tested by (name + signature) ..... : Chris, Seo

Approved by (+ signature) ........... : Brian, Cha

Testing procedure: TMP

Tested by (name + signature) ..... : N/A

Approved by (+ signature) ............ : N/A

Testing location/ address ...................... : N/A

Testing procedure: WMT

Tested by (name + signature) ..... : N/A

Witnessed by (+ signature) .......... : N/A

Approved by (+ signature) ........... : N/A

Testing location/ address ...................... : N/A

Testing procedure: SMT

Tested by (name + signature) ..... : N/A

Approved by (+ signature) ............ : N/A

Supervised by (+ signature) ........ : N/A

Testing location/ address ................ : N/A

Testing procedure: RMT

Tested by (name + signature) ..... : N/A

Approved by (+ signature) ............ : N/A

Supervised by (+ signature) ........ : N/A

Testing location/ address ...................... : N/A

Page 3 of 6 Report Ref. No.: 077-225780-100

TRF No. IECEN60335_2_40C

Summary of testing:

- The item tested was found to be in compliance with the test standards of IEC 60335-2-40:2002 + A1:2005

+ A2:2005 used in conjunction with IEC 60335-1:2001 (incl. Corrigendum 1:2002) + A1:2004 + A2:2006,

EN 60335-2-40:2003 + A11:2004 + A12: 2005 + A1:2006 used in conjunction with EN 60335-1:2002 +

A11:2004 + A1:2004 + A12:2006 + A2:2006 + A13:2008 and EN 62233:2008.

Tests performed (name of test and test clause):

Cl. 7.14 Marking and instructions

Testing location:

TÜ V SÜ D Korea Laboratory (TKL) #315 and 316, MARIO Tower, 222-12, Guro-Dong, Guro-Gu, 152-050, Seoul, Korea

Summary of compliance with National Differences: N/A

Page 4 of 6 Report Ref. No.: 077-225780-100

TRF No. IECEN60335_2_40C

Copy of marking plate:

―The above labels are draft of an artwork for marking plate pending approval by National Certification Bodies and it shall not be affixed to products prior to such an approval.‖

Page 5 of 6 Report. Ref. No.: 077-225780-100

TRF No. IECEN60335_2_40C

Test item particulars .................................................. : Split type room air conditioner (indoor unit)

Classification of installation and use ............................ : Fixed appliance

Supply Connection........................................................ : Interconnection to outdoor unit

...................................................................................... :

Possible test case verdicts:

- test case does not apply to the test object .................. : N/A

- test object does meet the requirement ....................... : P (Pass)

- test object does not meet the requirement ................. : F (Fail)

Testing .......................................................................... :

Date of receipt of test item ............................................ : N/A

Date (s) of performance of tests ................................... : N/A

General remarks:

The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(See Enclosure #)" refers to additional information appended to the report. "(See appended table)" refers to a table appended to the report.

Note: EN Group Differences together with National Differences and Special National Conditions, if

any, are in the Appendix to the main body of this TRF. Throughout this report a comma is used as the decimal separator.

Note: The Requirements of IEC 60335-2-40 and EN 60335-2-40 in clause 15 are by ident ical content

dif ferent numbered. For better handling the column "Clause" contains an addit ional Information

" IEC" or "EN" .

General product information:

- This test report was modified from 077-225780-000 because of change of model names(NH056NHXEA NH056VHXEA, NH071NHXEA NH071VHXEA)

- This appliance should be installed according to national electrical wiring regulation.

- Model name designation: AVXWVH056EA, NH056VHXEA, AVXWVH071EA, NH071VHXEA, MH052FVEA

1) Model AVXWVH056EA is identical to model AVXWVH071EA except for the micom program which does not have an effect on the safety.

2) Model MH052FVEA is identical to model AVXWVH056EA except for model name and design option.

3) Model NH056VHXEA is identical to model AVXWVH056EA except for model designation.

4) Model NH071VHXEA is identical to model AVXWVH071EA except for model designation.

- Factory information;

1) Samsung Gwangju Electronics Co., Ltd. Air Conditioner Div.(54180) 271, Oseon-Dong, Gwangsan-Gu, Gwangju-City, 506-723, Republic of Korea

2) Suzhou Samsung Electronics Co., Ltd. Air Conditioner Div.(57505) 501, Suhong East Road Suzhou, 215021 Jiangsu, People’s Republic of China

3) Suzhou Samsung Electronics Co., Ltd. Air Conditioner Div.(69062) 218, Jiepu Road, Industry Park, 215400, Suzhou, Jiangsu, People’s Republic of China

Page 6 of 6 Report. Ref. No.: 077-225780-100

TRF No. IECEN60335_2_40C

IEC / EN 60335-2-40

Clause Requirement – Test Result Verdict

7 MARKING AND INSTRUCTIONS

——

7.1 Rated voltage or voltage range (V) .......................... : 220-240 V P

Symbol for nature of supply including number of phases, unless for single phase operation (IEC/EN 60335-2-40) ......... :

~ P

Rated frequency (Hz) ............................................... : 50 Hz P

Rated power input (W) ............................................. : Max. 50 W P

Rated current (A) ..................................................... : Max. 0,30 A P

Manufacturer's or responsible vendor's name, trademark or identification mark .............................. :

SAMSUNG P

Model or type reference ........................................... : AVXWVH056EA, NH056VHXEA, AVXWVH071EA, NH071VHXEA, MH052FVEA

P

Symbol 5172 of IEC 60417, for Class II appliances

Class I N/A

Symbol IEC 60417-5036, for the enclosure of electrically-operated water valves in external hose-sets for connection of an appliance to the water mains (IEC/EN 60335-1/A1)

N/A

Mass of the refrigerant or of each refrigerant in a blend (except for azeotropic type) (IEC/EN 60335-2-40):

N/A

Refrigerant identification (IEC/EN 60335-2-40)

N/A

Permissible excessive operating pressure for sanitary hot water heat pumps (IEC/EN 60335-2-40):

N/A

the maximum operating pressure for the heat exchanger for hydronic fan coil/air handling units; (IEC 60335-2-40/A2) .... :

N/A

Excessive operating pressure of the refrigerant circuit for suction and discharge, if they differ (IEC/EN 60335-2-40) ....... :

N/A

Symbol for degree of protection against ingress of water, other than IPX0 (IEC/EN 60335-2-40):

IPX0 N/A

Separate marking of the appliances with all the rated characteristics of the supplementary heaters (IEC/EN 60335-2-40):

N/A

Marking of the direction of the fluid flow (IEC/EN 60335-2-40):

N/A

7.14 Marking clearly legible and durable P

- The end of test report -