144135416-sinamics-v20-drive.pdf

22
SINAMICS V20 DRIVE

Upload: ravindra-angal

Post on 12-Jan-2016

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 144135416-Sinamics-v20-Drive.pdf

SINAMICS V20 DRIVE

Page 2: 144135416-Sinamics-v20-Drive.pdf

V20-The versatile Inverter for Basic

Demands

• Power Range

0.12KW to 15KW

• Voltage Range

1 AC 200V … 240V(+/- 10%)

3 AC 380V … 480V(+10% /-15%)

• Control Modes

V/f, v^2/f, FCC

• Supply frequency

• 50Hz/60Hz

Page 3: 144135416-Sinamics-v20-Drive.pdf

Signal Inputs and Outputs

• Analog Inputs - AI1:bipolar current/voltage mode

-AI2 :unipolar current /voltage mode

(can be used as digital inputs)

• Analog Outputs -AO:0 … 20mA

• Digital Inputs - DI1-DI4,optically isolated PNP/NPN selectable

by terminal

• Digital Outputs -DO1:transistor output

-DO2: relay output

-250V AC 0.5A with resistive load

- 30V DC 0.5A with resistive load

Page 4: 144135416-Sinamics-v20-Drive.pdf

CONNECTION DIAGRAM

Page 5: 144135416-Sinamics-v20-Drive.pdf

BUILT IN BOP

Page 6: 144135416-Sinamics-v20-Drive.pdf

RESTORING TO DEFAULTS

Page 7: 144135416-Sinamics-v20-Drive.pdf

QUICK COMMISIONING THROUGH PARAMETERS

PARAMETER FUNCTION SETTING

P0003 User access level =0(user defined parameter list) =1(standard) =2(extended) =3(expert) =4(service)

P0010 Commissioning parameter

=1(quick commissioning)

P0100 50/60Hz selection =0(50Hz,KW in Europe) =1(60Hz,hp in north America) =2(60Hz, KW in north America)

P0304[0] Rated motor voltage[V]

Range 10…..2000

P0305[0] Rated motor current[A]

Range 0.01….10000

P0307[0] Rated motor power [KW/Hp]

Range 0.01…2000.0

Page 8: 144135416-Sinamics-v20-Drive.pdf

PARAMETER FUNCTION SETTING

P0308[0] Rated motor power factor Range 0.000…..1.000

P0310[0] Rated motor frequency(Hz) Range 12….599

P0311[0] Rated motor speed(RPM) Range 0…40000

P0700[0..2] Selection of command source

=0(Factory default setting) =1(Operator panel) =2(Terminal) =5(USS/MODBUS on RS485)

P1000[0] Selection of frequency set point

Range 0…77(factory default 1) =0(no main set point) =1(MOP set point) =2(analog set point) =3(fixed frequency) =5(USS on RS485) =7(analog set point 2)

P1080[0] Minimum frequency[Hz] Range 0…599(factory default=0)

QUICK COMMISIONING THROUGH PARAMETERS

Page 9: 144135416-Sinamics-v20-Drive.pdf

PARAMETER FUNCTION SETTING

P1082[0] Maximum frequency[Hz] Range 0…599

P1120[0] Ramp up time[s] Range 0.00…650.00(factory default=10)

P1121[0] Ramp down time[s] Range 0.00…650.00(factory default=10)

P3900 End of commissioning Note: After completion of calculation, P3900 and P0010 are automatically reset to their original value 0. The inverter displays "8.8.8.8.8" which indicates that it is busy with internal data processing.

=0(no quick commissioning)-factory default =1(end of quick commissioning with factory reset) =2(end quick commissioning) =3(end of quick commissioning only for motor data)

QUICK COMMISIONING THROUGH PARAMETERS

Page 10: 144135416-Sinamics-v20-Drive.pdf

P0700[1]-OPERATOR PANEL

• Start

• Stop

• Multi-function button

• Hand/jog/auto

• Forward and reverse motor direction

• Speed up and speed down motor

Page 11: 144135416-Sinamics-v20-Drive.pdf

PO700[2]-TERMINALS

Parameter Description Range Factory default Acc. level

P0701[0...2] Function of

digital input 1

0 - 99 0 2

0 Digital input

disabled

16 Fixed frequency

selector bit1

1 ON / OFF1 17 Fixed frequency

selector bit2

2 ON reverse/OFF1 18 Fixed frequency

selector bit3

3 OFF2-coast to

standstill

22 Quick stop

source1

4 OFF3-quick

ramp down

23 Quick stop

source2

9 Fault

acknowledge

24 Quick stop

override

Page 12: 144135416-Sinamics-v20-Drive.pdf

PO700[2]- TERMINALS

Parameter Description Range Factory

default

Acc. level

9 Fault

acknowledge

24 Quick stop

override

10 JOG right 25 DC brake enable

11 JOG left 27 Enable PID

12 Reverse 29 External trip

13 MOP

down(increase

frequency)

33 Disable

additional freq

set point

14 MOP

down(decrease

frequency)

99 Enable BICO

parameterization

15 Fixed

frequency

selector bit0

Page 13: 144135416-Sinamics-v20-Drive.pdf

PO700[2]- TERMINALS

Parameter Description Range Fa0ctory

defa0ult

Acc. level

P0702[0...2] Function of

digital input 2

0 - 99 0 2

P0703[0...2] Function of

digital input 3

0 - 99 9 2

P0704[0...2] Function of

digital input 4

0 - 99 15 2

P0712 [0...2] Analog / digital

input 1

0 - 99 0 2

P0713[0...2] Analog / digital

input 2

0 - 99 0 2

Page 14: 144135416-Sinamics-v20-Drive.pdf

FIXED FREQUENCY

SELECTION • P1000=3(fixed frequency)

• P1016[0..2](Fixed frequency mode)

=1(direct selection)

=2(binary selection)

If P1016=1

• P0701=15(Fixed frequency selector bit 0)

• P0702=16(Fixed frequency selector bit 1)

• P0703=17(Fixed frequency selector bit 2)

• P0704=18(Fixed frequency selector bit 3)

Frequency selected from-P1001 to P1004

If P1016=2

• P1020[0]:DI1

• P1021[0]:DI2

• P1022[0]:DI3

• P1023[0]:DI4

Assigning frequency to each input-

P1001:Fixed frequency 1(Hz)…..

P1015:Fixed frequency 15(Hz)

Page 15: 144135416-Sinamics-v20-Drive.pdf

ANALOG PARAMETERS

P1000=2(Analog set point)

Analog operation through BOP(P0700=1)

P1000=12(analog set point + MOP set point)

P1000=21(MOP set point + analog set point)

Analog operation through Terminals(P0700=2)

P1000=23(fixed frequency + analog set point)

Page 16: 144135416-Sinamics-v20-Drive.pdf

MACROS

DEFINITION:

• CONNECTION MACROS

• APPLICATION MACROS

Page 17: 144135416-Sinamics-v20-Drive.pdf

CONNECTION MACRO

Page 18: 144135416-Sinamics-v20-Drive.pdf

APPLICATION MACROS

Page 19: 144135416-Sinamics-v20-Drive.pdf

Ease of Use

• Energy consumption monitoring

• Automatic restart

• Parameter cloning

• USS/MODBUS communication

• Connection and application macro

• Customized default values

Page 20: 144135416-Sinamics-v20-Drive.pdf

APPLICATION

• Hibernation mode

• Slip compensation

• Keep running mode

• Kinetic buffering

• Flying start

• Motor staging

• BICO function

• Dual ramp

• Wobble function

• PID Controller

• Super torque mode

• Hammer start

• Blockage clearing mode

Page 21: 144135416-Sinamics-v20-Drive.pdf
Page 22: 144135416-Sinamics-v20-Drive.pdf

THANK YOU