14: power in ac circuits
TRANSCRIPT
![Page 1: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/1.jpg)
14: Power in AC Circuits
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 1 / 11
![Page 2: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/2.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
![Page 3: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/3.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
![Page 4: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/4.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
![Page 5: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/5.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt
![Page 6: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/6.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt
![Page 7: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/7.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt=
〈v2(t)〉R
![Page 8: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/8.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt=
〈v2(t)〉R⟨
v2(t)⟩
is the value of v2(t) averaged over time
![Page 9: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/9.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt=
〈v2(t)〉R⟨
v2(t)⟩
is the value of v2(t) averaged over time
We define the RMS Voltage (Root Mean Square): Vrms ,√〈v2(t)〉
![Page 10: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/10.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt=
〈v2(t)〉R⟨
v2(t)⟩
is the value of v2(t) averaged over time
We define the RMS Voltage (Root Mean Square): Vrms ,√〈v2(t)〉
The average power dissipated in R is P =〈v2(t)〉
R= (Vrms)
2
R
Vrms is the DC voltage that would cause R to dissipate the same power.
![Page 11: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/11.jpg)
Average Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 2 / 11
Intantaneous Power dissipated in R: p(t) = v2(t)R
Average Power dissipated in R:
P = 1T
∫ T
0p(t)dt= 1
R× 1
T
∫ T
0v2(t)dt=
〈v2(t)〉R⟨
v2(t)⟩
is the value of v2(t) averaged over time
We define the RMS Voltage (Root Mean Square): Vrms ,√〈v2(t)〉
The average power dissipated in R is P =〈v2(t)〉
R= (Vrms)
2
R
Vrms is the DC voltage that would cause R to dissipate the same power.
We use small letters for time-varying voltages and capital letters fortime-invariant values.
![Page 12: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/12.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
![Page 13: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/13.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
![Page 14: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/14.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
Mean Square Voltage:⟨v2⟩= V 2
2 since cos 2ωt averages to zero.
![Page 15: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/15.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
Mean Square Voltage:⟨v2⟩= V 2
2 since cos 2ωt averages to zero.
![Page 16: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/16.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
Mean Square Voltage:⟨v2⟩= V 2
2 since cos 2ωt averages to zero.
RMS Voltage: Vrms =√〈v2〉 = 1√
2V = 3.54V
![Page 17: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/17.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
Mean Square Voltage:⟨v2⟩= V 2
2 since cos 2ωt averages to zero.
RMS Voltage: Vrms =√〈v2〉 = 1√
2V = 3.54V
Note: Power engineers always use RMS voltages and currents exclusivelyand omit the “rms” subscript.For example UK Mains voltage = 230 V rms = 325 V peak.
![Page 18: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/18.jpg)
Cosine Wave RMS
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 3 / 11
Cosine Wave: v(t) = 5 cosωt. Amplitude is V = 5V.
Squared Voltage: v2(t) = V 2 cos2 ωt = V 2(12 + 1
2 cos 2ωt)
Mean Square Voltage:⟨v2⟩= V 2
2 since cos 2ωt averages to zero.
RMS Voltage: Vrms =√〈v2〉 = 1√
2V = 3.54V= V
Note: Power engineers always use RMS voltages and currents exclusivelyand omit the “rms” subscript.For example UK Mains voltage = 230 V rms = 325 V peak.
In this lecture course only, a ~ overbar means ÷√2: thus V = 1√
2V .
![Page 19: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/19.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθVI = |I| ejθI
![Page 20: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/20.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
![Page 21: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/21.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
![Page 22: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/22.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
![Page 23: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/23.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
![Page 24: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/24.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
![Page 25: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/25.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
![Page 26: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/26.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
Average power: P = 12 |V | |I| cos (φ) where φ = θV − θI
![Page 27: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/27.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
Average power: P = 12 |V | |I| cos (φ) where φ = θV − θI
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ cos (φ)
![Page 28: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/28.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
Average power: P = 12 |V | |I| cos (φ) where φ = θV − θI
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ cos (φ) cosφ is the power factor
![Page 29: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/29.jpg)
Power Factor +
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 4 / 11
Suppose voltage and current phasors are:V = |V | ejθV ⇔ v(t) = |V | cos (ωt+ θV )
I = |I| ejθI ⇔ i(t) = |I| cos (ωt+ θI)
Power dissipated in load Z isp(t) = v(t)i(t) = |V | |I| cos (ωt+ θV ) cos (ωt+ θI)
= |V | |I|(12 cos (2ωt+ θV + θI) +
12 cos (θV − θI)
)
= 12 |V | |I| cos (θV − θI) +
12 |V | |I| cos (2ωt+ θV + θI)
Average power: P = 12 |V | |I| cos (φ) where φ = θV − θI
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ cos (φ) cosφ is the power factor
φ > 0 ⇔ a lagging power factor (normal case: Current lags Voltage)φ < 0 ⇔ a leading power factor (rare case: Current leads Voltage)
![Page 30: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/30.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
![Page 31: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/31.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI
![Page 32: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/32.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
![Page 33: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/33.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ
![Page 34: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/34.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
![Page 35: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/35.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
![Page 36: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/36.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
![Page 37: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/37.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
![Page 38: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/38.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
![Page 39: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/39.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
Average Power: P , ℜ (S) measured in Watts (W)
![Page 40: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/40.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
Average Power: P , ℜ (S) measured in Watts (W)Reactive Power: Q , ℑ (S) Measured in Volt-Amps Reactive (VAR)
![Page 41: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/41.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
Average Power: P , ℜ (S) measured in Watts (W)Reactive Power: Q , ℑ (S) Measured in Volt-Amps Reactive (VAR)
Power Factor: cosφ , cos(∠V − ∠I
)= P
|S|
![Page 42: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/42.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
Average Power: P , ℜ (S) measured in Watts (W)Reactive Power: Q , ℑ (S) Measured in Volt-Amps Reactive (VAR)
Power Factor: cosφ , cos(∠V − ∠I
)= P
|S|
Machines and transformers have capacity limits and power losses that areindependent of cosφ; their ratings are always given in apparent power.
![Page 43: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/43.jpg)
Complex Power
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 5 / 11
If V = 1√2|V | ejθV and I = 1√
2|I| ejθI
The complex power absorbed by Z is S , V × I∗
where * means complex conjugate.
V × I∗ =∣∣∣V
∣∣∣ ejθV ×∣∣∣I∣∣∣ e−jθI =
∣∣∣V∣∣∣∣∣∣I∣∣∣ ej(θV −θI)
=∣∣∣V
∣∣∣∣∣∣I∣∣∣ ejφ =
∣∣∣V∣∣∣∣∣∣I∣∣∣ cosφ+ j
∣∣∣V∣∣∣∣∣∣I∣∣∣ sinφ
= P + jQ
Complex Power: S , V I∗ = P + jQ measured in Volt-Amps (VA)
Apparent Power: |S| ,∣∣∣V
∣∣∣∣∣∣I∣∣∣ measured in Volt-Amps (VA)
Average Power: P , ℜ (S) measured in Watts (W)Reactive Power: Q , ℑ (S) Measured in Volt-Amps Reactive (VAR)
Power Factor: cosφ , cos(∠V − ∠I
)= P
|S|
Machines and transformers have capacity limits and power losses that areindependent of cosφ; their ratings are always given in apparent power.Power Company: Costs ∝ apparent power, Revenue ∝ average power.
![Page 44: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/44.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
![Page 45: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/45.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
![Page 46: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/46.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Resistor: S =∣∣∣I∣∣∣2
R =|V |2R
φ = 0
Absorbs average power, no VARs (Q = 0)
![Page 47: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/47.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Resistor: S =∣∣∣I∣∣∣2
R =|V |2R
φ = 0
Absorbs average power, no VARs (Q = 0)
Inductor: S = j∣∣∣I∣∣∣2
ωL = j|V |2ωL
φ = +90
No average power, Absorbs VARs (Q > 0)
![Page 48: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/48.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Resistor: S =∣∣∣I∣∣∣2
R =|V |2R
φ = 0
Absorbs average power, no VARs (Q = 0)
Inductor: S = j∣∣∣I∣∣∣2
ωL = j|V |2ωL
φ = +90
No average power, Absorbs VARs (Q > 0)
Capacitor: S = −j|I|2ωC
= −j∣∣∣V
∣∣∣2
ωC φ = −90
No average power, Generates VARs (Q < 0)
![Page 49: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/49.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Resistor: S =∣∣∣I∣∣∣2
R =|V |2R
φ = 0
Absorbs average power, no VARs (Q = 0)
Inductor: S = j∣∣∣I∣∣∣2
ωL = j|V |2ωL
φ = +90
No average power, Absorbs VARs (Q > 0)
Capacitor: S = −j|I|2ωC
= −j∣∣∣V
∣∣∣2
ωC φ = −90
No average power, Generates VARs (Q < 0)
VARs are generated by capacitors and absorbed by inductors
![Page 50: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/50.jpg)
Power in R, L, C
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 6 / 11
For any impedance, Z, complex power absorbed: S = V I∗ = P + jQ
Using (a) V = IZ (b) I × I∗ =∣∣∣I∣∣∣2
we get S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Resistor: S =∣∣∣I∣∣∣2
R =|V |2R
φ = 0
Absorbs average power, no VARs (Q = 0)
Inductor: S = j∣∣∣I∣∣∣2
ωL = j|V |2ωL
φ = +90
No average power, Absorbs VARs (Q > 0)
Capacitor: S = −j|I|2ωC
= −j∣∣∣V
∣∣∣2
ωC φ = −90
No average power, Generates VARs (Q < 0)
VARs are generated by capacitors and absorbed by inductorsThe phase, φ, of the absorbed power, S, equals the phase of Z
![Page 51: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/51.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
![Page 52: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/52.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
![Page 53: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/53.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
![Page 54: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/54.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
![Page 55: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/55.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
![Page 56: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/56.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
Tellegen:∑
b VbI∗b =
∑b
∑n abnxnI
∗b
![Page 57: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/57.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
Tellegen:∑
b VbI∗b =
∑b
∑n abnxnI
∗b
=∑
n
∑b abnI
∗b xn
![Page 58: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/58.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
Tellegen:∑
b VbI∗b =
∑b
∑n abnxnI
∗b
=∑
n
∑b abnI
∗b xn=
∑n xn
∑b abnI
∗b
![Page 59: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/59.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
Tellegen:∑
b VbI∗b =
∑b
∑n abnxnI
∗b
=∑
n
∑b abnI
∗b xn=
∑n xn
∑b abnI
∗b =
∑n xn × 0
![Page 60: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/60.jpg)
Tellegen’s Theorem
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 7 / 11
Tellegen’s Theorem: The complex power, S, dissipated in any circuit’scomponents sums to zero.
xn = voltage at node n
Vb, Ib = voltage/current in branch b
(obeying passive sign convention)
abn ,
−1 if Vb starts from node n
+1 if Vb ends at node n
0 else
e.g. branch 4 goes from 2 to 3 ⇒ a4∗ = [0, −1, 1]
Branch voltages: Vb =∑
n abnxn (e.g. V4 = x3 − x2)
KCL @ node n:∑
b abnIb = 0 ⇒∑
b abnI∗b = 0
Tellegen:∑
b VbI∗b =
∑b
∑n abnxnI
∗b
=∑
n
∑b abnI
∗b xn=
∑n xn
∑b abnI
∗b =
∑n xn × 0
Note:∑
b Sb = 0 ⇒∑
b Pb = 0 and also∑
b Qb = 0.
![Page 61: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/61.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
![Page 62: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/62.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A
![Page 63: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/63.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
![Page 64: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/64.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA
![Page 65: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/65.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVA
![Page 66: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/66.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
![Page 67: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/67.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:
![Page 68: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/68.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω
![Page 69: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/69.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
![Page 70: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/70.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
![Page 71: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/71.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
![Page 72: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/72.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA
![Page 73: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/73.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVA
![Page 74: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/74.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVAcosφ = P
|S| = cos 14 = 0.97
![Page 75: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/75.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVAcosφ = P
|S| = cos 14 = 0.97
Average power to motor, P , is 10.6 kW in both cases.
![Page 76: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/76.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVAcosφ = P
|S| = cos 14 = 0.97
Average power to motor, P , is 10.6 kW in both cases.∣∣∣I∣∣∣, reduced from 56.5 ց 47A (−16%) ⇒ lower losses.
![Page 77: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/77.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVAcosφ = P
|S| = cos 14 = 0.97
Average power to motor, P , is 10.6 kW in both cases.∣∣∣I∣∣∣, reduced from 56.5 ց 47A (−16%) ⇒ lower losses.
Effect of C : VARs = 7.6 ց 2.6 kVAR
![Page 78: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/78.jpg)
Power Factor Correction
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 8 / 11
V = 230. Motor modelled as 5||7j Ω.
I = VR+ V
ZL
= 46− j32.9A= 56.5∠− 36
S = V I∗ = 10.6 + j7.6 kVA= 13∠36 kVAcosφ = P
|S| = cos 36 = 0.81
Add parallel capacitor of 300µF:ZC = 1
jωC= −10.6j Ω⇒ IC = 21.7j A
I = 46− j11.2A = 47∠− 14 A
SC = V I∗C = −j5 kVA
S = V I∗ = 10.6 + j2.6 kVA= 10.9∠14 kVAcosφ = P
|S| = cos 14 = 0.97
Average power to motor, P , is 10.6 kW in both cases.∣∣∣I∣∣∣, reduced from 56.5 ց 47A (−16%) ⇒ lower losses.
Effect of C : VARs = 7.6 ց 2.6 kVAR , power factor = 0.81 ր 0.97.
![Page 79: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/79.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
![Page 80: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/80.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.
![Page 81: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/81.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
![Page 82: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/82.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
![Page 83: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/83.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
![Page 84: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/84.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
These two equations allow you to solve circuits and alsoimply that
∑Si = 0.
![Page 85: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/85.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
These two equations allow you to solve circuits and alsoimply that
∑Si = 0.
Special Case:
![Page 86: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/86.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
These two equations allow you to solve circuits and alsoimply that
∑Si = 0.
Special Case:
For a 2-winding transformer this simplifies toV2 = N2
N1
V1 and IL = −I2 = N1
N2
I1
![Page 87: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/87.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
These two equations allow you to solve circuits and alsoimply that
∑Si = 0.
Special Case:
For a 2-winding transformer this simplifies toV2 = N2
N1
V1 and IL = −I2 = N1
N2
I1
Hence V1
I1=
(N1
N2
)2V2
IL=
(N1
N2
)2
Z
![Page 88: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/88.jpg)
Ideal Transformer
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 9 / 11
A transformer has ≥ 2 windings on the same magneticcore.
Ampère’s law:∑
NrIr = lΦµA
; Faraday’s law: Vr
Nr
= dΦdt
.N1 : N2 +N3 shows the turns ratio between the windings.The • indicates the voltage polarity of each winding.
Since Φ is the same for all windings, V1
N1
= V2
N2
= V3
N3
.
Assume µ → ∞ ⇒ N1I1 +N2I2 +N3I3 = 0
These two equations allow you to solve circuits and alsoimply that
∑Si = 0.
Special Case:
For a 2-winding transformer this simplifies toV2 = N2
N1
V1 and IL = −I2 = N1
N2
I1
Hence V1
I1=
(N1
N2
)2V2
IL=
(N1
N2
)2
Z
Equivalent to a reflected impedance of(
N1
N2
)2
Z
![Page 89: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/89.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
![Page 90: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/90.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
Power Transmission
Suppose a power transmission cable has 1Ω resistance.100 kVA@ 1 kV = 100A ⇒ I2R = 10 kW losses.
![Page 91: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/91.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
Power Transmission
Suppose a power transmission cable has 1Ω resistance.100 kVA@ 1 kV = 100A ⇒ I2R = 10 kW losses.100 kVA@ 100 kV = 1A ⇒ I2R = 1W losses.
![Page 92: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/92.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
Power Transmission
Suppose a power transmission cable has 1Ω resistance.100 kVA@ 1 kV = 100A ⇒ I2R = 10 kW losses.100 kVA@ 100 kV = 1A ⇒ I2R = 1W losses.
Voltage Conversion
Electronic equipment requires ≤ 20V but mains voltage is 240V ∼.
![Page 93: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/93.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
Power Transmission
Suppose a power transmission cable has 1Ω resistance.100 kVA@ 1 kV = 100A ⇒ I2R = 10 kW losses.100 kVA@ 100 kV = 1A ⇒ I2R = 1W losses.
Voltage Conversion
Electronic equipment requires ≤ 20V but mains voltage is 240V ∼.
Interference protection
Microphone on long cable is susceptible to interference from nearbymains cables. An N : 1 transformer reduces the microphone voltageby N but reduces interference by N2.
![Page 94: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/94.jpg)
Transformer Applications
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 10 / 11
Power Transmission
Suppose a power transmission cable has 1Ω resistance.100 kVA@ 1 kV = 100A ⇒ I2R = 10 kW losses.100 kVA@ 100 kV = 1A ⇒ I2R = 1W losses.
Voltage Conversion
Electronic equipment requires ≤ 20V but mains voltage is 240V ∼.
Interference protection
Microphone on long cable is susceptible to interference from nearbymains cables. An N : 1 transformer reduces the microphone voltageby N but reduces interference by N2.
Isolation
There is no electrical connection between the windings of a transformerso circuitry (or people) on one side will not be endangered by a failurethat results in high voltages on the other side.
![Page 95: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/95.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
![Page 96: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/96.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
![Page 97: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/97.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
![Page 98: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/98.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
![Page 99: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/99.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
Power engineers always use V and I and omit the ~.
![Page 100: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/100.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
Power engineers always use V and I and omit the ~.
• Tellegen: In any circuit∑
b Sb = 0 ⇒ ∑b Pb =
∑b Qb = 0
![Page 101: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/101.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
Power engineers always use V and I and omit the ~.
• Tellegen: In any circuit∑
b Sb = 0 ⇒ ∑b Pb =
∑b Qb = 0
• Power Factor Correction: add parallel C to generate extra VARs
![Page 102: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/102.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
Power engineers always use V and I and omit the ~.
• Tellegen: In any circuit∑
b Sb = 0 ⇒ ∑b Pb =
∑b Qb = 0
• Power Factor Correction: add parallel C to generate extra VARs
• Ideal Transformer: Vi ∝ Ni and∑
NiIi = 0 (implies∑
Si = 0)
![Page 103: 14: Power in AC Circuits](https://reader031.vdocuments.site/reader031/viewer/2022021815/585aa8281a28ab6e3291f09f/html5/thumbnails/103.jpg)
Summary
14: Power in AC Circuits
• Average Power
• Cosine Wave RMS
• Power Factor +
• Complex Power
• Power in R, L, C
• Tellegen’s Theorem
• Power Factor Correction
• Ideal Transformer
• Transformer Applications
• Summary
E1.1 Analysis of Circuits (2017-10213) AC Power: 14 – 11 / 11
• Complex Power: S = V I∗ = P + jQ where V = Vrms =1√2V .
For an impedance Z: S =∣∣∣I∣∣∣2
Z =|V |2Z∗
Apparent Power: |S| =∣∣∣V
∣∣∣∣∣∣I∣∣∣ used for machine ratings.
Average Power: P = ℜ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ cosφ (in Watts)
Reactive Power: Q = ℑ (S) =∣∣∣V
∣∣∣∣∣∣I∣∣∣ sinφ (in VARs)
Power engineers always use V and I and omit the ~.
• Tellegen: In any circuit∑
b Sb = 0 ⇒ ∑b Pb =
∑b Qb = 0
• Power Factor Correction: add parallel C to generate extra VARs
• Ideal Transformer: Vi ∝ Ni and∑
NiIi = 0 (implies∑
Si = 0)
For further details see Hayt Ch 11 or Irwin Ch 9.