  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    505E WOODWARD DIGITAL GOVERNOR CONTROL

    By : IsmailPT PUPUK KALTIM BONTANG

  • 505E DIGITAL GOVERNOR UNTUK EXTRACTION STEAM TURBINE

    Berbasis 32 bit Microprocessor

    Dapat di program , Satu desain

    Berdiri sendiri / di hubungkan dengan alat lain

    Umum

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Serial

    Serial atau Hard wire

    Komputer untuk konfigurasi

    Serial

  • Integrated dalam satu paket

    2 Line (masing-masing 24 karakter )

    30 fungsi tombol

    Operator Control Panel ( OCP )

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Speed ( Load )

    Extraction/Admission Pressure ( Flow )

    Turbine Control Parameter

    2 Modbus Port (RS 232, 422, 485)

    Hardwire Connection

    Komunikasi

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • First Out Trip

    Critical speed (2 speed Band)

    Auto Start Seq. (Hot & Cold)

    Peak Speed Indikasi (Overspeed trip)

    Fitur Tambahan

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Program Mode

    Run Mode

    Service Mode

    Normal Operating Mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Password

    Program Mode : 1113

    Service Mode : 1111

  • Program Mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Program Mode digunakan untuk memilih opsi-opsi yang diperlukan untuk mengkonfigurasi control spesifik turbin aplikasi.

  • Run Mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Run Mode digunakan untuk memonitor parameter parameter operasional saat turbine beroperasi dari start-up dan proses shutdown.

    Service ModeService Mode digunakan untuk meningkatkan kinerja sistem operasi sementara unit sedang berjalan.

  • 2 Speed Input

    6 Analog Input

    12 Contact Input

    4 Function Key

    Control Input

    Terminasi

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Dedicated

  • Dua Actuator Output

    Enam 4 20 mA Output

    Enam Relay Output

    Control Output

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Service Panel dan Key Pad

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol Scroll

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol Select

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol Adjust

    Tombol Run

    Sebagai perintah start ketika unit dalam kondisi Ready to Start

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol Stop

    Tombol Reset

    Untuk mereset Run Mode alarm dan shutdown. Denganmenekan ini akan mengembalikan control ke status (Controlling Parameter/Push Run or Program) saat shutdown

    Memberi perintah control turbine shutdown (Run Mode), Perintah stop dapat di disable melalui Setting Service Mode (dibawah key option)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 2/ACTR (Actuator) Memasukan angka 2 atau posisi actuator (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 3/CONT (Control) Memasukan angka 3 atau menampilkan parameter yang

    sedang di kontrol (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 4/CAS (Cascade) Memasukan angka 4 atau menampilkan informasi Cascade

    kontrol (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 5/RMT (Remote) Memasukan angka 5 atau menampilkan informasi Remote

    Speed Setpoint (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 6/LMTR (Limiter) Memasukan angka 6 atau menampilkan informasi valve limiter (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 7/SPEED Memasukan angka 7 atau menampilkan informasi speed

    control (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 8/AUX (Auxiliary) Memasukan angka 8 atau menampilkan informasi auxiliary

    control (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol 9/KW (Load) Memasukan angka 9 atau menampilkan KW/Load atauinformasi first stage pressure (Run Mode)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol CLEAR Untuk Masuk atau Keluar ke/dari suatu Mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol ENTER Memasukan nilai baru dalam program mode, dan

    memasukan secara langsung spesifik nilai setpoint dalan run mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol DYNAMIC (+/-) Mengakses dynamic setting kontrol parameter dalam posisi

    Run Mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol ALARM (F1) Menampilkan sebuah kondisi alarm ketika indikator LED

    tombol menyala (tekan tombol scroll untuk melihat alarm lainnya)

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol OVERSPEED TEST ENABLE (F2) Mengijinkan speed reference di naikan melebihi maksimum

    kontrol speed setpoint untuk melakukan test electrical ataumekanikal overspeed test.

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Tombol F3 dan F4 (Function Key) Tombol yang dapat diprogram untuk fungsi yang lain

    Tombol EMERGENCY SHUTDOWN Memberikan perintah Emergency Shutdown ke Kontrol

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • KOLOM KONFIGURASI UTAMA

    Turbine Start Start mode, Idle/rated,Auto start sequence Speed Control MPU dan Speed control dynamic setting Speed Setpoint Value Speed setpoint, overspeed Trip

    setpoint, Remote setpoint dan Critical band Operating Parameter Aplikasi generator, Local/Remote Extraction/Adm Cntrl. Extraction/adm Control Driver Configuration Driver Output (ACT) Turbine Performance Value Ratio/Limiter, Steam Map Analog Input Analog Input Option Contact Input Contact input option

    Worksheet

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • KOLOM KONFIGURASI TAMBAHAN

    Function Key F3 dan F4 Function Key Auxiliary Control Auxiliary Control Cascade Control Cascade control Read Outs Analog Read Out Relay Relay Function Communication Modbus Comminication

    Worksheet

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • RESTROKE ACTUATOR

    Syarat

    Control harus kondisi shutdown (Emergency shutdown swicth close)

    Yakinkan TTV harus kondisi Close

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • RESTROKE ACTUATOR

    Ketentuan

    Arus Maksimum actuator tidak dapat di adjust di bawahdari pada arus minimum actuator

    Arus Minimum actuator tidak dapat di adjust lebih besardari pada arus maksimum actuator.

    Driver 20-160 mA range 4-20 mA range

    Over current 217 mA 26 mA

    Under Current 5 mA 0.6 mA

    Max Output Current range 10-200 mA 2-24 mA

    Max Output Impedance 45 ohms 360 ohms

    Min Stop Adjust Range 10-80 mA 2-20 mA

    Max Stop Adjust Range 100-200 mA 10-24 mA

    Restroke

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • TURBINE START MODE

    Manual start mode Semi automatic start mode Automatic start mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    STRAT PERMISSIVE

    Sebuah contact input dapat diprogram sebagai sebuahStart permissive bila diperlukan

    Setelah di tekan RUN maka contact start permissive tidakdiperlukan lagi

    Biasanya diambil dari contact limit switch TTV

  • ZERO SPEED SIGNAL OVERRIDE

    505E dapat di konfigurasi manual atau auto Bila auto maka lamanya zero override berdasarkan timer Status logic zero override dapat ditampilkan di service

    mode

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • START TURBINE

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Contact external shutdown harus close Contact permissive start harus close (bila di konfigurasi)

  • TURBINE START MODE

    Mode Manual Start

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • TURBINE START MODE

    Mode semi Auto Start

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • TURBINE START MODE

    Mode Auto Start

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Critical Speed Avoidance

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    2 range critical speed

    Speed setpoint tidak dapat di stop bila ada di critical speed

    Idle / Rated

    Setpoint akan ramp ke nilai idle speed set point

    Setpoint akan ramp ke rated speed setpoint jika perintahrated di berikan

  • AUTOMATIC START SEQUENCE

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • AUTOMATIC START SEQUENCE

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Hot start ramp rate dan Hold time di pakai jika perintah RUN diberikan dan turbine telah shutdown dengan waktu lebih kecildari setting waktu HOT START

    Cold start ramp rate dan Hold time dipakai jika perintah RUN diberikan dan turbine telah shutdown dengan waktu lebih lama dari setting waktu COLD START

    Bila perintah RUN di berikan dan lamanya shutdown di antarasetting waktu HOT START dan COLD START, maka kontrol akanmenetukan starting rate dan hold time diluar setting

    Work sheet

  • AUTOMATIC START SEQUENCE

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Cold Start ( > xx HRS ) = 22 HRSHot Start ( < xx HRS ) = 2 HRSLow Idle Setpt = 1000 RPMLow Idle Delay ( Cold ) = 30 MINLow Idle Delay ( Hot ) = 10 MINHi Idle Stpt = 2000 RPMRate To Hi Idle ( Cold ) = 5 RPM/SECRate To Hi Idle ( Hot ) = 15 RPM/SECHi Idle Delay Time ( Cold ) = 30 MINHi Idle Delay Time ( Hot ) = 20 MINRate To Rated ( Cold ) = 10 RPMRate To Rated ( Hot ) = 20 RPMRated Setpt = 3400 RPM

  • AUTOMATIC START SEQUENCE

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Apabila unit telah trip selama 12 Jam, 505E akan menambah parameter diantara Hot dan Cold dan memakai rate dan delay seperti berikut ini :

    Low Idle Delay = 20 MINRate To Hi Idle = 10 RPM/SECHi Idle Delay = 10 MINRate To Rated = 15 RPM/SECHours Since Trip ( HRS ) = 12 HRS

  • Speed Control

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Extraction Control

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • Mengaktifkan Extraction Control

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Manual Enable/Disable

    Automatic Enable/Disable

  • TURBINE START

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • STEAM MAP

    Steam map adalah sebuah bentuk grafik yang mewakiliuntuk range operasi dan pembatas pada sebuah ekstraksidan atau Admission steam turbin.

    Saat turbin normal operasi dia harus berada didalamgaris steam amplop.

    Ketentuan

    Sebuah Map harus linear (semua garis harus lurus) Garis ekstraksi/admission flow = 0% dan

    ekstaksi/admission flow = 100% harus di parallel, dangaris LP valve = 0% dan LP valve 100% harus diparallel.

    PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    RATIONING / LIMITER

    HP = K1.S + K2.P + K3

    LP = K4.S + K5.P + K6

    Typical extraction steam map

  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    Nilai MAX POWER adalah beban dimana S = 100 garis silang pada sumbu S (sekitar 13498 KW dalam contoh gambar diatas.

    Nilai MAX HP FLOW adalah flow dimana HP = 100 garis silang pada sumbu HP (sekitar 95 T/H).

    Titik A adalah dimana perpotongan garis P = 0 dan LP = 100 (MAX POWER @ MIN EXTRACTION ; HP FLOW @ MIN EXTRACTION).

    Titik B adalah dimana perpotongan garis LP = 0 dan P = 100 (MIN POWER @ MAX EXTRACTION ; HP FLOW @ MAX EXTRACTION).

    Titik C adalah dimana perpotongan garis LP = 0 dan P = 0 (MIN POWER @ MIN EXTRACTION ; MIN HP FLOW @ MIN EXTRACTION ).

  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    PENGETESAN STEAM MAP

  • PELATIHAN DIGITAL GOVERNOR CONTROLPOKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010

    A : Input S = and P = HP = LP =

    B : Input S = and P =HP = LP =

    C : Input S = and P =HP = LP =

    D : Input S = and P =HP = LP =

    E : Input S = and P =HP = LP =

    F : Input S = and P =HP = LP =

    G : Input S = and P =HP = LP =

    H : Input S = and P =HP = LP =