10.discovery detectors data sheet

Upload: abdelsonia

Post on 03-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 10.Discovery Detectors Data Sheet

    1/2

    The Discovery range

    Using well established sensing

    technologies, the Discovery range

    includes ionisation and optical smoke

    detectors, plus a temperature

    detector. Additionally, a multi-sensor

    detector combining optical smoke and

    temperature sensing has been

    developed. A manual call point

    incorporating Discovery technology is

    also available.

    Features

    Multi-sensor detector

    Five response modes for changing

    environments

    Drift compensation for constant

    sensitivity

    Non-volatile memory for user data

    Alarm flag for fast alarm reporting

    Compatible with Apollo XP95 Vega

    fire control panel

    Sensitivity selection

    Discovery offers five sensitivity bands.

    Detectors are factory-set to a mid-range sensitivity which can be altered

    as appropriate. For example, a

    detector in a clean room might be set

    to a higher sensitivity than one in an

    office. Or different sensitivities might

    be selected for day and night use. This

    system enhances detection reliability

    whilst mitigating against false alarms.

    The multi-sensor detector may be

    operated as a smoke detector, a heat

    detector or a combination of both.

    Drift compensation

    Discovery incorporates an algorithm to

    ensure that the analogue count

    reported to the panel is not affected

    by extraneous factors such as

    contamination which could lead to

    drift. If the count moves from its

    normal clean air value it is, within

    permitted limits, compensated back to

    reduce unwanted alarms.

    Non-volatile memory

    Discovery has a non-volatile memory

    that may be accessed by the control

    panel. This records unchanging

    information, such as the month of

    manufacture and information undercontrol of the panel such as the

    sensitivity setting. Self changing data,

    such as the degree of drift

    D I S C O V E R YA n a l o g u e a d d r e s s a b l e f i r e d e t e c t o r s

    Exciting and innovative, Discovery takes the advanced features of XP95 and

    adds new dimensions of sophistication giving you total reassurance in

    installations where adaptability to changing conditions and protection against

    unwanted alarms are paramount.

  • 7/28/2019 10.Discovery Detectors Data Sheet

    2/2

    Compatibility

    To access the benefits of Discovery, the

    Vega fire control equipment must be

    used.

    The mounting bases are identical to

    those of XP95, featuring the patented

    XPERT card addressing system that has

    proved so simple, reliable and

    effective.

    Existing XP95 isolators and interfaces

    can be used with all Discovery fire

    detectors.

    compensation, is also held in the

    memory, but a significant amount of

    memory is reserved for customers to

    use freely. This part four bytes of

    data may be used to record any data

    required, eg, commissioning date, last

    service date, site reference number,

    project number or whatever is

    important to the customer.

    Kidde Fire ProtectionUK Sales Office Head OfficeThame Park Road, Thame, Oxfordshire OX9 3RT, UK.Tel: +44 (0)1844 265003. Fax: +44 (0)1844 256156. E-mail: [email protected] Web: www.kfp.co.ukUK Sales Office

    Unit 12, Atley Way, North Nelson Industrial Estate, Cramlington, Northumberland NE23 1WA UKTel: +44 (0)1670 713455. Fax: +44 (0)1670 735553International OfficesDubai: Tel: +971 4 337 2498. Fax: +971 4 337 5088Hong Kong: Tel: +852 2195 3688. Fax: +852 2743 7477Singapore: Tel: +65 424 7979. Fax: +65 424 7978Australia: Tel: +61 3 9765 3850. Fax: +61 3 9765 3800E9832-328 01/02

    Optical Smoke Detector

    Part No. 23900-K098

    Multi-Sensor Detector

    Part No. 23900-K102

    Temperature Detector

    Part No. 23900-K097

    Ionisation Smoke Detector

    Part No. 23900-K099

    Manual Call Point

    Part No. 23900-K100 (Flush)

    23900-K101 (Surface)

    Base (inc Xpert card)

    Part No. 23900-H05

    D I S C O V E R Y2