1000 watts ups circuit diagram

24
Greegoo Electric 5.2008 http://www.greegoo.com 1 1-1 Power Supply Uninterruptible Power Supply Following the popularity of computer networks and the continual upgrades of information processing technology, there is now virtually no limits for network information transmissions. Undoubtedly, the server is the soul of a computer network which processes numerous network data day in and day out and is naturally more demanding in terms of power requirements computers in general. Any increase of power network load, excessively low voltage, unstable frequency or even a sudden power-off can interrupt normal network operations! In line with the power requirements for network system, GREEGOO has developed a new generation of on- line intelligent UPS, tieds UPS, UPS battery backup---GOLD Series 1K, 2K, 3K UPS. Its uses the Motorola microprocessor with robust processing power which is capable of detecting and controlling quickly and accurately all movements of the UPS to ensure high product reliability. In addition to providing the network with power protection for virtually zero interruption, regulated voltage and regulated frequency, interference- resistant capability and filtering of noisy signals, under normal conditions, utility power obtains via AC-DC circuit the DC bus voltage which is then converted to 220V AC output via the inverter, so as to safeguard the data over the entire network. Therefore, the power used by the load is the purified sine wave power via regulated voltage and regulated frequency with noisy signals filtered. Furthermore, GREEGOO GOLD Series 1K, 2K, 3K UPS, tieds UPS, UPS battery backup are connected through the RS232 communication port to GREEGOO Power Management software for power detection and power monitoring, to integrate UPS and the network server into one entity with power status available at any time. Moreover, it achieves the intelligent functions such as timer-controlled self-inspection, automatic disk-saving, automatic timer-controlled power- on and power-off and record of power status etc., to achieve the zero distance of communication between the user and UPS. Whenever utility power supply is interrupted, the UPS, tieds UPS, UPS battery backup will inform the server immediately and gets ready for switching off the unit and saving automatically all data before performing the normal power-off instruction. Even in an unattended network environment, the UPS can still ensure data safety of the network system. High frequency on line UPS (1KVA-3KVA) Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom... Key features True on-line double conversion technology with advanced microprocessor control; Wide input voltage range; Zero transfer time; Protection against all type of power problems; Self test while start of the UPS; Site wiring fault warning; On-battery power-on function; Smart RS232 communication interface; Intelligent slot available; Sealed lead-acid, maintenance free battery. Application tieds UPS, UPS battery backup

Upload: muhammad-salman-khan

Post on 20-Feb-2015

868 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

1

1-1Power SupplyUninterruptible Power Supply

Following the popularity of computer networks and the continual upgrades of information processing technology, there is now virtually no limits for network information transmissions. Undoubtedly, the server is the soul of a computer network which processes numerous network data day in and day out and is naturally more demanding in terms of power requirements computers in general. Any increase of power network load, excessively low voltage, unstable frequency or even a sudden power-off can interrupt normal network operations!

In line with the power requirements for network system, GREEGOO has developed a new generation of on-line intelligent UPS, tieds UPS, UPS battery backup---GOLD Series 1K, 2K, 3K UPS. Its uses the Motorola microprocessor with robust processing power which is capable of detecting and controlling quickly and accurately all movements of the UPS to ensure high product reliability. In addition to providing the network with power protection for virtually zero interruption, regulated voltage and regulated frequency, interference-resistant capability and filtering of noisy signals, under normal conditions, utility power obtains via AC-DC circuit the DC bus voltage which is then converted to 220V AC output via the inverter, so as to safeguard the data over the entire network. Therefore, the power used by the load is the purified sine wave power via regulated voltage and regulated frequency with noisy signals filtered. Furthermore, GREEGOO GOLD Series 1K, 2K, 3K UPS, tieds UPS, UPS battery backup are connected through the RS232 communication port to GREEGOO Power Management software for power detection and power monitoring, to integrate UPS and the network server into one entity with power status available at any time. Moreover, it achieves the intelligent functions such as timer-controlled self-inspection, automatic disk-saving, automatic timer-controlled power-on and power-off and record of power status etc., to achieve the zero distance of communication between the user and UPS. Whenever utility power supply is interrupted, the UPS, tieds UPS, UPS battery backup will inform the server immediately and gets ready for switching off the unit and saving automatically all data before performing the normal power-off instruction. Even in an unattended network environment, the UPS can still ensure data safety of the network system.

High frequency on line UPS (1KVA-3KVA)

■ Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom...

Key features■ True on-line double conversion technology with advanced microprocessor control;■ Wide input voltage range;■ Zero transfer time;■ Protection against all type of power problems;■ Self test while start of the UPS;■ Site wiring fault warning;■ On-battery power-on function;■ Smart RS232 communication interface;■ Intelligent slot available;■ Sealed lead-acid, maintenance free battery.

Application

tieds UPS, UPS battery backup

Page 2: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

1

1-�

Uninterruptible Power Supply

High frequency on line UPS (1KVA-3KVA)

Technical specifications

Product Series GOLDModel G1K G2K G3KRated Power VA/W 1kVA / 0.7kW 2kVA / 1.4kW 3kVA / 2.1kWInput Nominal Voltage 220VAC

Voltage Range 115 ~ 300VACFrequency Range 46~54Hz(default), user adjustable within 40~60HzPower Factor 0.97Connection IEC320-10A inlet IEC320-16A inlet

Output Voltage 220VAC ± 2%Frequency 46~54Hz or 50Hz ± 0.2Hz (Line mode)

50Hz ± 0.2Hz ( Battery mode)Waveform Sine WaveDistortion 3% 4%Overload Capability 108%~150% for 30 sec., ≥150% for 300 msCurrent Crest Ratio 3:1Connections IEC320 * 4 IEC320 * 6 IEC320 * 3 and

Terminal BlockBattery Type Sealed, Maintenance free, Lead-Acid (Panasonic)

Quantity 3 pieces 8 piecesBack-up Time (Full load) 5 min 9 min 5 minRecharge Time 5 hrs to 90% of capacity after full load discharge

Bypass Automatic Transfer on overload and UPS failureBefore UPS Power-on Default “NO”, user adjustable to “YES”Voltage Range 80~264VAC (Default), user adjustable within 80~286VAC

Transfer Time 0 ms; less than 4 ms from inverter to bypass and vice versaLED Indicators Status Load level/Battery level, Battery, Utility Power, Inverter, Bypass, Overload, FaultAudible Alarm Bypass, On battery mode, Battery low, Overload, FaultAcoustic Noise At 1 meter distance 45 dBA 50 dBACommunications DB-9 Port RS-232 Serial Interface

Intelligent Slot Options: WebPower, AS400 Card or WinPower CMCNetwork Surge Protection RJ45 I/O port available for network or Fax/ModemEnvironmental Operating Temperature 0˚C~ 40˚C

Operating Humidity 20 ~ 90% non-condensingWeight Net (Kg) 13 31.5 32Dimensions W x D x H (mm) 145 x 400 x 220 192 x 460 x 348

G1KS, G2KS & G3KS for longer Backup time with additional Battery Packs are available, please consult local distributors.

Page 3: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

1

1-3Power SupplyUninterruptible Power Supply

High frequency on line UPS (6KVA-10KVA)

■ Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom...

Key features■ True online double conversion technology;■ Wide input voltage range;■ Zero transfer time;■ Protection against all types of power problems;■ No add-on CNTL unit required for parallel connection;■ Low initial investment and flexible for future expansion;■ Highest reliability and maximum performance for power sharing and redundancy;■ Equipped with Maintenance Bypass Switch;■ Smart RS232 and Intelligent slot interface;■ Sealed lead-acid, maintenance free battery.

Application

Technical specifications

Model G6KN G10KNRated Power VA/W 6kVA/4.2kW 10kVA/7kWInput Nominal Voltage 220VAC

Voltage Range 176 ~ 276VACFrequency Range 46 ~ 54HzPower Factor 0.98Connection Hardwired

Output Voltage 220VAC ±1%Frequency 50Hz ±0.1% ( Battery mode)Waveform Sine WavePower factor 0.7Voltage Distortion ≤ 2% under linear loadOverload Capability 105% ~ 130% for 10 min., ≥130% for 1 min.Current Crest Ratio 3:1 max.Connection Hardwired

Battery Type Sealed, Maintenance free, Lead-Acid (Panasonic)Quantity 20 piecesBack-up time (full load) 7 min 5 minRecharge time 8 hrs to 90% of capacity after full load discharge

Transfer time 0 msMaintenance Bypass Switch YesLED indicators Status Load level/Battery level, Battery , Utility power, Inverter, Bypass, Overload, FaultAudible alarm Bypass Alarm beeps every two minutes

Battery discharge Alarm beeps every four seconds, every second if battery lowOverload Alarm beeps two for every secondFault Alarm beeps continuously

Acoustic noise At 1 meter distance £ 55 dBADB-9 Port RS232 serial interfaceIntelligent Slot Options: WebPower, AS400 or WinPower CMC

Parallel Port up to three units in parallel for power redundancy and load sharingEnvironmental Operating temperature 0˚C~ 40˚C

Operating humidity 20% ~ 90% non-condensingWeight Net (kg) 84 93Dimensions W x D x H (mm) 260 x 570 x 717

Page 4: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

1

1-�

Uninterruptible Power Supply

High frequency on line UPS (6KVA-10KVA)

Technical specifications

Model G6KNS G10KNSRated Power Volt-Amps/Watts 6kVA/4.2kW 10kVA/7kWInput Nominal Voltage 220VAC

Voltage Range 176 ~ 276VACFrequency Range 46 ~ 54HzPower Factor 0.98Connection Hardwired

Output Voltage 220VAC ±1%Frequency 50Hz ±0.1% ( Battery mode)Waveform Sine WavePower factor 0.7Voltage Distortion ≤ 2% under linear loadOverload Capability 105% ~ 130% for 10 min., ≥130% for 1 min.Current Crest Ratio 3:1 max.Connection Hardwired

Battery Type Sealed, Maintenance free, Lead-Acid (Panasonic)Nominal DC Voltage 240VDCBack-up time Depends on the capacity of the external battery bankConnection External Battery Socket

Transfer time 0 msMaintenance Bypass Switch YesLED indicators Status Load level/Battery level, Battery , Utility power, Inverter, Bypass, Overload,

FaultAudible alarm Bypass Alarm beeps every two minutes

Battery discharge Alarm beeps every four seconds, every second if battery lowOverload Alarm beeps two for every secondFault Alarm beeps continuously

Acoustic noise At 1 meter distance £ 55 dBACommunications DB-9 Port RS232 serial interface

Intelligent Slot Options: WebPower, AS400 or WinPower CMCParallel Port up to three units in parallel for power redundancy and load sharingEnvironmental Operating temperature 0˚C~ 40˚C

Operating humidity 20% ~ 90% non-condensingWeight Net (kg) 35 38Dimensions W x D x H (mm) 260 x 570 x 717

Page 5: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

1

1-�Power SupplyUninterruptible Power Supply

High frequency on line UPS (10KVA-�0KVA)

■ Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom...

Key features■ True online double conversion technology;■ Wide input voltage range;■ Zero transfer time;■ Protection against all types of power problems;■ No add-on CNTL unit required for parallel connection;■ Low initial investment and flexible for future expansion;■ Highest reliability and maximum performance for power sharing and redundancy;■ Equipped with Maintenance Bypass Switch;■ Smart RS232 and Intelligent slot interface.

Application

Technical specificationsModel 3G10KNS 3G15KNS 3G20KNSRated Power VA/W 10kVA/7kW 15kVA/10.5kW 20kVA/14kWInput Nominal Voltage 380VAC

Voltage Range 304 ~ 478VACPhase 3 phase (4 wires plus ground)Frequency Range 46 ~ 54HzPower Factor 0.95Connection Ha rdwired

Output Voltage 220VAC ±1%, Single phaseFrequency 50Hz ±0.1% ( Battery mode)Waveform Sine WavePower factor 0.7Voltage Distortion ≤ 2% under linear loadOverload Capability 105% ~ 130% for 10 min., ≥130% for 1 min.Current Crest Ratio 3:1 max.

Battery Type Sealed, Maintenance free, Lead-AcidNominal DC Voltage 240VDCBack-up time (full load) Depends on the capacity of the external battery capacityConnection External Battery Socket Hardwired

Transfer time 0 msMaintenance Bypass Switch YesLED indicators Status Load level/Battery level, Battery , Utility power, Inverter, Bypass, Overload, FaultAudible alarm Bypass Alarm beeps every two minutes

Battery discharge Alarm beeps every four seconds, every second if battery lowOverload Alarm beeps two for every secondFault Alarm beeps continuously

Acoustic noise At 1 meter distance ≤ 55 dBA ≤ 60 dBACommunications DB-9 Port RS232 serial interface

Intelligent Slot Options: WebPower, As400 or WinPower CMCParallel Port up to three units in parallel for power redundancy and load sharingEnvironmental Operating temperature 0˚C~ 40˚C

Operating humidity 20% ~ 90% non-condensingWeight Net (kg) 38.5 55Dimensions W x D x H (mm) 260 x 570 x 717

Page 6: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

1

1-6

Uninterruptible Power Supply

High frequency on line UPS (LCD UPS 1KVA-10KVA)

■ 1KVA ~ 10KVA ( IP/OP:220Vac/230Vac/240Vac ).

Key features■ Microprocessor Control Guarantees High Reliability;■ Comprehensive Self-Protection Design;■ Audible Alarm Mute;■ Cold Start Function;■ Auto Self-Testing System while Turning On UPS;■ Wide Input Voltage Range;■ Maintenance Bypass Switch for 6K/ 10K;■ N+X Parallel Redundancy and Capacity Expansion for 6K/ 10K.

Application

Technical specificationsMODEL G1KD G1KDS G2KD G2KDS G3KD G3KDSCapacity VA/W 1000VA/700W 2000VA/1400W 3000VA/2100WInput Phase Single Phase with Ground

Frequency Range 50Hz:46~54Hz

Power Factor >=0.97

Voltage Range Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer 160VAC/140VAC/120VAC/110VAC± 5VAC

Line Low Comeback 175VAC ± 5VAC

Line High Transfer 300VAC± 5VAC

Line High Comeback 285VAC± 5VAC

Output Phase Single

Voltage 220VAC/230VAC/240VAC

Voltage Regulation ± 2%

Frequency 46~54Hz

( Synchronized Range)

Frequency 50 ± 0.2 Hz

( Battery Mode)

Current Crest Ratio 3:01

Harmonic Distortion ?3% THD <4% THD ( Linear Load)

( Linear Load) <7% THD ( Non-Linear Load)

?6% THD

( Non-Linear Load)

Output Waveform Pure Sinewave

Efficiency To AC Mode 85% 85% 85%

To Battery Mode 83% 83% 83%

Battery Battery Type 12V/7.2Ah Depending onthe capacity of external batteries

12V/7.2Ah Depending on the capacity of external batteries

12V/7.2Ah Depending on the capacity of external batteries

Numbers of Batteries 3 8 8

Backup Time >5 minutes >9 minutes >5 minutes

(Full Load)

Recharge Time 5 hours to 90% 5 hours to 90% 5 hours to 90%

Charging Current (Max.) 1.0A 7A 1.0A 8A+/-1A 1.0A 8A+/-1A

Charging Voltage 41.1Vdc ± 0.6V 110Vdc ± 0.4V

External Battery type N/A 12V/7.2AH *3 N/A 12V/7.2AH *8 N/A 12V/7.2AH *8

Transfer time

AC to DC Zero

Inverter to Bypass 2.5ms (Typical )

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)

LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Audible alarm

Battery Mode Sounding every 4 seconds

Low Battery Sounding every second

Overload Sounding twice every second

Fault Continuously Sounding

Dimension UPS Case D x W x H (mm) 400x145x220 460x192x340

Battery Case D x W x H N/A 400*145*220 N/A 460*192*340 N/A 460*192*340

Weight Net Weight(kgs) 14 7 34.5 15 35.5 16

Enviro Operating Environment 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)

Nment Noise Level <45dB @ 1 Meter 50dB @ 1 Meter

Interface Smart RS-232 Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, and MAC

SNMP (option) Power management from SNMP manager and web browser

Page 7: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

1

1-�Power SupplyUninterruptible Power Supply

MODEL G1KD G6KND G6KNDS G10KND G10KNDSCapacity VA/W 1000VA/700W 6000VA/4200W 10000VA/7000WInput Phase Single Phase with Ground

Frequency Range 50Hz:46~54HzPower Factor >=0.98Voltage Range Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer 176 ±3% VACLine Low Comeback 185 ± 3% VACLine High Transfer 276 ± 3% VACLine High Comeback 266 ± 3% VAC

Output Phase SingleVoltage 220VAC/230VAC/240VACVoltage Regulation ± 1%Frequency 46~54Hz( Synchronized Range)Frequency 50Hz ± 0.05Hz( Battery Mode)Current Crest Ratio 3:1Harmonic Distortion ?2% THD (Linear Load)

?6% THD (Non-Linear Load)Output Waveform Pure Sinewave

Efficiency To AC Mode > 88%To Battery Mode > 88%

Battery Battery Type 12V/7.2AH Depending on the capacity of external batteries

12V/9Ah Depending on the capacity of external batteries

Numbers of Batteries 20 20Backup Time 8 minutes 5 minutes(Full Load)Recharge Time 7 hours to 90% 8 hours to 90%Charging Current (Max.) 2.0A 4.2A 2.0A 4.2ACharging Voltage 274Vdc ± 1%VExternal Battery type N/A 12V/7.2AH *20 N/A 12V/9AH *20

Transfer time AC to DC ZeroInverter to Bypass 2.5ms (Typical )

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Audible alarm Battery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously Sounding

Dimension UPS Case D x W x H (mm) 570x260x717Battery Case D x W x H 570*260*717

Weight Net Weight(kgs) 84 35 93 38Enviro Operating Environment 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)Nment Noise Level <55dB @ 1 meter <55dB @ 1 meterInterface Smart RS-232 Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX,

FreeBSD, HP-UX, and MAC

SNMP (option) Power management from SNMP manager and web browser

High frequency on line UPS (LCD UPS 1KVA-10KVA)

Technical specifications

Please consult the factory or the distributors for further information of "S" models.

Page 8: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

1

1-8

Uninterruptible Power Supply

High frequency on line UPS (LCD UPS 10KVA-�0KVA)

■ 10KVA ~ 20KVA ( IP/OP: 220VAC/380Vac)

Key features■ Microprocessor Control Guarantees High Reliability;■ Comprehensive Self-Protection Design;■ Audible Alarm Mute;■ Cold Start Function;■ Auto Self-Testing System while Turning On UPS;■ Wide Input Voltage Range.

Application

Technical specificationsMODEL 3G10KNDS 3G15KNDS 3G20KNDSCapacity VA/W 10000VA/7000W 15000VA/10500W 20000VA/14000WInput Phase Three Phase with Ground

Frequency Range 46~54HzPower Factor >=0.95Acceptable Voltage 60~138 VacVoltage Range

Line Low Transfer 304VAC +/- 3VACLine Low Comeback 322VAC +/- 3VACLine High Transfer 478VAC +/- 3VACLine High Comeback 361VAC +/- 3VAC

Output Phase SingleVoltage 380VAC/220VAC/230VAC/240VACVoltage Regulation ± 1%Frequency 46~54Hz( Synchronized Range)Frequency ( Battery Mode) 50 ± 0.05 HzCurrent Crest Ratio 3:01Harmonic Distortion <2% THD ( Linear Load) /

<6% THD ( Non-Linear Load)Output Waveform Pure Sinewave

Efficiency To AC Mode 88%To Battery Mode

Battery Battery Type Depending on the capacity of external batteries.Numbers of BatteriesBackup Time (Full Load)Recharge TimeCharging Current (Max.) 4.2ACharging Voltage 274Vdc ± 1%V

Transfer time AC to DC ZeroInverter to Bypass Zero

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage

setAudible alarm Battery Mode Sounding every 4 seconds

Low Battery Sounding every secondOverload Sounding twice every secondFault Continuously Sounding

Dimension UPS Case 570x260x717D x W x H (mm)

Weight Net Weight(kgs) 38.5 55 55Environment Operating Temperature 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)

Noise Level <60dB @ 1 MeterInterface Smart RS-232 Windows 98/NT/2000/XP/2003/ME, Linux, Sun Solaris, IBM Aix, Compaq

True64, SGI IRIX, FreeBSD, HP-UX, amd MACSNMP (option) Power management from SNMP manager and web browser

Please consult the factory or the distributors for further information of "S" models.

Page 9: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

1

1-9Power SupplyUninterruptible Power Supply

High frequency on line UPS (UPS �0KVA-80KVA)

■ 3/3G20KXL~3/3G80KXL (IP/OP:380Vac)

Key features■ True Galvanic Isolation ■ Advanced technology DSP, IGBT, and switching components ■ Plug and Play Modular Design■ Cold Start Function ■ Multi-CPU design and software/hardware cooperate control ■ Defense to miss-operation ■ Input Protection ■ Software and Hardware Redundant Design ■ Intelligent charger and battery testing system ■ Emergent Stop is Available ■ Variety of Accessories / Options

Application

Technical specificationsPHASE 3-Phase Input / 3-Phase Output 3-Phase Input/1-Phase OutputCAPACITY KVA 20 30 40 50 60 80 20 30 40 50Input Voltage 220Vac / 380Vac / 460Vac , 208Vac / 380Vac / 400Vac /415Vac

Voltage range ± 20% (>± 20% IS AVAILABLE UPON REQUEST)Frequency 50 / 60 Hz ± 7%Power walk in 0% - 100% : 20 SECONDSEfficiency ALMOST 98%Voltage ± 1%Regulation

Battery Battery type/pcs MAINTENANCE FREE LEAD-ACID BATTERIES / 12V X 29 PCSMaximum charge current adc (selectable)

10 15 20 25 30 40 10 15 20 25

Battery start YES, UPS CAN BE STARTED WITHOUT AC SOURCE.Output Voltage 220Vac / 380Vac / 460Vac , 208Vac / 380Vac / 400Vac

/415Vac ± 1%220/230/240, 1F2? OR 3?

Waveform SINEWAVEPower factor 0.8Frequency lock range 45-55 Hz / 55-65 HzFrequency 50 / 60 Hz ± 0.1 Hz(Free running)Phase shift under 100% unbalance load

< 0.5°

Thd (linear load) < 2%Overload protection

<110% CONTINUOUS110-125% 15 MINUTES125-150% 10 MINUTES>150% 1 MINUTE

Efficiency (100% load) 93% 93% 93.50% 93.50% 94% 94.50% 93% 93% 93.50% 93.50%STatic switch Voltage range 173-277 VAC (L-N)

Mains<-->inverter 0 MSOperationInterface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Overallcharacteristics

Overall efficiency 91% 91% 91.50% 92% 92% 92.50% 91% 91% 91.50% 92%Maximum heat dissipation (kw) 1.3 1.9 2.6 3 3.5 4.6 1.3 1.9 2.6 3Dimention (hxwxd) mm 1600X550X800 1600X550X800Weight (kg w/o bat.) for standard input 380v y

300 400 480 550 680 820 300 400 480 550

Audible noise@1m <65 dBA <67dBA <65 dBA

Please consult the factory or the distributors for further information of "S" models.

Page 10: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-1Power SupplyUninterruptible Power Supply

Rack Mount On Line UPS (UPS 1KVA-6KVA)

■ Servers, Data centers, Critical network devices, Sensitive electronic equipment Telecom...

Key features■ True on-line double conversion technology with advanced microprocessor control;■ Wide input voltage range;■ Zero transfer time;■ Protection against all type of power problems;■ Self test while start of the UPS;■ Site wiring fault warning;■ On-battery power-on function;■ Smart RS232 communication interface;■ Intelligent slot available;■ Sealed lead-acid, maintenance free battery.

Application

Technical specificationsProduct Series Rack Mount 1~6kVAModel G1KR G2KR G3KR G6KRRated Power VA/W 1kVA / 0.7kW 2kVA / 1.4kW 3kVA / 2.1kW 6kVA/4.2kWInput Nominal Voltage 220VAC

Voltage Range 115 ~ 300VAC 176 ~ 276VACFrequency Range 46 ~ 54Hz(default), user adjustable within 40~60Hz 46 ~ 54HzPower Factor 0.97 0.98Connection IEC320-10A inlet IEC320-16A inlet Terminal Block

Output Voltage 220VAC ± 2% 220VAC ± 1%Frequency 46~54Hz or 50Hz ± 0.2Hz (Line mode) 46~54Hz (Line mode)

50Hz ± 0.2Hz ( Battery mode) 50Hz ± 0.05Hz ( Battery mode)Waveform Sine WaveOverload Capability 108%~150% for 30 sec., ≥150% for 300 ms 105%~130% for 10 min., ≥130% for 1

min.Current Crest Ratio 3:01

Bypass Automatic Transfer on overload and UPS failureBefore UPS Power-on Default “NO”, user adjustable to “YES” YesVoltage Range 80~264VAC (Default), user adjustable within

80~286VAC176 ~ 261VAC

Output Connections IEC320 -10A * 4 IEC320-10A * 4 IEC320-10A and IEC320-10A * 4 and Terminal BlockTerminal Block

Transfer Time 0 ms; less than 4 ms from inverter to bypass and vice versa

Zero

LED indica-tors

Status Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm Bypass, On battery mode, Battery low, Overload, FaultCommunications RS-232 Serial Interface

Intelligent Slot;OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)

Network Surge Protection RJ45 I/O port available for network or Fax/ModemEnvironmental Operating Temperature 0˚C~ 40˚C

Operating Humidity 20 ~ 90% non-condensingMain Unit Net Weight (Kg) 15.3 10.3 11.2 18.3

Dimensions (W x D x H) mm 482.6 x 450 x 88 (2U) 482.6 x 600 x 130 (3U)Battery Pack Type Internal Batteries External Battery Pack

Nominal DC Voltage 36VDC 96VDC 240VDCBackup Time (Full load) 5 min 9 min 5 min 7 min

(with 1 BP) (with 1 BP) (with 1 BP)Net Weight (Kg) -- 25.3 58.2Dimensions (W x D x H) mm -- 482.6 x 450 x 88 (2U) 482.6 x 600 x 130 (3U)

Notes:G1KRS, G2KRS, G3KRS & G6KRS for longer Backup time with additional Battery Packs are available, please consult local distributors.

Page 11: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

�-�

Uninterruptible Power Supply

Rack Mount On Line UPS (UPS 1KVA-3KVA 110Vac)

Key features

■ Comprehensive Self-Protection Design;■ Audible Alarm Mute;■ Cold Start Function;■ Auto Self-Testing System while Turning On UPS;

Products SpecificationMODEL GR1KD GR1KDS GR2KD GR2KDS GR3KD GR3KDSCapacity VA/W 1000VA/700W 1500VA/1050W 3000VA/2100WInput Phase Single Phase with Ground

Frequency Range 50Hz: 46~54Hz / 60Hz : 56~64HzPower Factor >=0.95Acceptable Voltage 60~138 VacVoltage Range

Base on load percentage (100%-70% / 70%-60% / 60%-50% / 50%-40% / 40% - 0%)Line Low 80VAC/70VAC/70VAC/60VAC/60VACTransferLine Low 85VAC/85VAC/75VAC/75VAC/65VACComebackLine High Transfer 138VACLine High Comeback 133VAC

Output Phase SingleVoltage 110VAC/115VAC/120VACVoltage Regulation ± 2%Frequency 50Hz : 46~54Hz / 60Hz : 56~64Hz

( SynchronizedRange)Frequency 50/60Hz / ± 0.2 Hz( Battery Mode)Current Crest Ratio 3:01Harmonic Distortion 5% THD ( Linear Load) /

10% THD ( Non-Linear Load)Output Waveform Pure Sinewave

Efficiency To AC Mode 85% 83% 86%To Battery Mode 83% 82% 83%

Battery Battery Type 12V/7.2Ah Depending on the capacity

12V/7.2Ah Depending on the capacity

12V/7.2AH D e p e nding o n t h e capacity

Numbers of 3 of external 4 of external batteries

8 of external batteries

Batteries batteriesBackup Time >5 minutes >5 minutes >5 minutes(Full Load)Recharge Time 8 hours to 90% 8 hours to 90% 8 hours to 90%Charging Current (Max.) 1.0A 7.8A 1.0A 7.8A 1.0A 7.8ACharging Voltage 41.1Vdc / ±0.6V 54.9Vdc / ±0.4V 110Vdc / ±0.4VExternal Battery N/A 12V / 7.2

AH * 6N/A 12V / 7.2

AH *8N/A 12V / 7.2 AH * 8

TypeTransfer time

AC to DC ZeroInverter to Bypass 2.5ms (Typical ) Zero

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Audible alarm

Battery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously Sounding

Dimension UPS Case 400x145x220 465x145x220 465x192x340D x W x H (mm)Battery Case N/A 400x145x220 N/A 465x145x220 N/A 465x192x340D x W x H (mm)

Weight Net Weight(kgs) 13(w. Battery) 7 1 7 . 5 ( w . Battery)

9 33(w. Battery) 12

Environment Operating Temperature 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)Noise Level <45dB @ 1 Meter <45dB @ 1 Meter <50dB @ 1 Meter

Interface Smart RS-232 Windows 98/NT/2000/XP/2003/ME, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, amd MAC

SNMP (option) Power management from SNMP manager and web browser

■ Wide Input Voltage Range;■ Tower and Rack Mount Available;■ 19" Rack Mount Available.

Page 12: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-3Power SupplyUninterruptible Power Supply

Rack Mount On Line UPS (UPS 1KVA-6KVA ��0Vac)

Key features

■ Microprocessor Control Guarantees High Reliability;■ Comprehensive Self-Protection Design;■ Audible Alarm Mute;■ Cold Start Function;■ Auto Self-Testing System while Turning On UPS;■ Wide Input Voltage Range;■ Tower and Rack Mount Available;■ 19" Rack Mount Available.

MODEL GR1KD GR1KDS GR2KDS GR2KDS GR3KD GR3KDSCapacity VA/W 1000VA/700W 2000VA/1400W 3000VA/2100WInput Phase Single Phase with Ground

Frequency Range 50Hz:46~54HzPower Factor >=0.97Voltage Range Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer 160VAC/140VAC/120VAC/110VAC± 5VACLine Low Comeback 175VAC ± 5VACLine High Transfer 300VAC± 5VACLine High Comeback 285VAC± 5VAC

Output Phase SingleVoltage 220VAC/230VAC/240VACVoltage Regulation ± 2%Frequency 46~54Hz( Synchronized Range)Frequency 50 ± 0.2 Hz( Battery Mode)Current Crest Ratio 3:01Harmonic Distortion <3% THD <4% THD ( Linear Load)

( Linear Load) <7% THD ( Non-Linear Load)<6% THD( Non-Linear Load)

Output Waveform Pure SinewaveEfficiency To AC Mode 85% 85% 85%

To Battery Mode 83% 83% 83%Battery Battery Type 12V/7.2Ah Depending on

the capacity of external batteries

12V/7.2Ah Depending on the capacity of external batteries

12V/7.2Ah Depending on the capacity of external batteries

Numbers of Batteries 3 8 8Backup Time >5 minutes >9 minutes >5 minutes(Full Load)Recharge Time 5 hours to 90% 5 hours to 90% 5 hours to 90%Charging Current (Max.) 1.0A 7A 1.0A 8A+/-1A 1.0A 8A+/-1ACharging Voltage 41.1Vdc ± 0.6V 110Vdc ± 0.4VExternal Battery type N/A 12V/7.2AH *6 N/A 12V/7.2AH *8 N/A 12V/7.2AH *8

Transfer time

AC to DC ZeroInverter to Bypass 2.5ms (Typical )

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Audible alarm

Battery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously Sounding

Dimension UPS Case D x W x H (mm) 400x145x220 460x192x340Battery Case D x W x H N/A 400*145*220 N/A 460*192*340 N/A 460*192*340

Weight Net Weight(kgs) 14(w / battery) 7 34.5(w / Battery)

15 35.5(W / Battery)

16

Enviro Operating Environment 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)Nment Noise Level <45dB @ 1 Meter 50dB @ 1 MeterInterface Smart RS-232 Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX,

FreeBSD, HP-UX, and MACSNMP (option) Power management from SNMP manager and web browser

Products Specification

Page 13: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

�-�

Uninterruptible Power Supply

Rack Mount On Line UPS (UPS 1KVA-6KVA ��0Vac)

Products SpecificationMODEL GR6KD GR6KDSCapacity VA/W 6000VA/4200WInput Phase Single Phase with Ground

Frequency Range 50Hz:46~54HzPower Factor >=0.98Voltage Range Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer 176 ±3% VACLine Low Comeback 185 ± 3% VACLine High Transfer 276 ± 3% VACLine High Comeback 266 ± 3% VAC

Output Phase SingleVoltage 220VAC/230VAC/240VACVoltage Regulation ± 1%Frequency 46~54Hz( Synchronized Range)Frequency 50Hz ± 0.05Hz( Battery Mode)Current Crest Ratio 3:1Harmonic Distortion <2% THD (Linear Load)

<6% THD (Non-Linear Load)Output Waveform Pure Sinewave

Efficiency To AC Mode > 88%To Battery Mode > 88%

Battery Battery Type 12V/7.2AH Depending on the capacity of external batteriesNumbers of Batteries 20Backup Time 8 minutes(Full Load)Recharge Time 7 hours to 90%Charging Current (Max.) 2.0A 4.2ACharging Voltage 274Vdc ± 1%VExternal Battery type N/A 12V/7.2AH *20

Transfer time

AC to DC ZeroInverter to Bypass Zero

Operation interface

LED Indicator Normal (green),warning(yellow),Fault(red)LCD Indicator Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

Audible alarm

Battery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously Sounding

Dimension UPS Case D x W x H (mm) 570x260x717Battery Case D x W x H 570*260*717

Weight Net Weight(kgs) 84(W / Battery) 35Enviro Operating Environment 0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)Nment Noise Level <55dB @ 1 meterInterface Smart RS-232 Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX,

FreeBSD, HP-UX, and MACSNMP (option) Power management from SNMP manager and web browser

Page 14: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

3

3-1Power SupplyUninterruptible Power Supply

Line interactive UPS

■ 3/3G20KXL~3/3G80KXL (IP/OP:380Vac).

Key features■ Controlled By Twin Microprocessor;■ Line-Interactive Design. Pure sin wave output.;■ AC startup with no Battery avoid spike when connect batteries;■ Hot-Swap Batteries;■ DC-Start mode (cold-start);■ Voltage Sensitivity adjust button;■ Three-stage AVR (auto voltage regulation) Auto Buck/Boost mode;■ Speed Controlled Fan;■ High Input Voltage Range (145Vac~290Vac);■ High Input frequency range (66HZ to 44HZ);■ High Voltage & Overload & Short circuit Protections, RJ-45 surge Protection;■ Load Level & Battery Level Monitor on Front Panel;■ LCD panel (optional);■ Long Backup Time (XL type);■ True RS232/Dry Contact two way computer interface, RUPS protocol;■ SNMP Slot (optional), USB interface (optional);■ Specially designed for PC users, Servers, Workstations, Critical network devices , Data-Center & Telecom equipment ...etc;■ Bondle Monitor software support Win98/NT/2000/XP & Linux/FreeBSD/Netware;■ Optional Monitor software support all UNIX system.

Application

Functions■ Smart Intelligent Battery Management system means longer battery lifeImproved reliability results from a precision Smart Battery Charging System, and automatic true-load battery tests. Redundant overcharge protection and continuous, nonplused charging also contribute to longer battery life.

■ Sine - wave outputA-Smart UPS sine-wave output provides assurance of compatibility with all loads.

■ Line-interactive design delivers unmatched performance and reliability Innovative line-interactive design uses the DC to AC power inverter "in reverse" as a battery charger during normal operation providing greater performance, filtering inefficiency. F-ewer components under stress results in greater reliability than inefficient double conversion, on-line UPS units. Line-interactive topology is approximately. 98% efficient, which leads to extremely high reliability. In contrast most online operate at approximately 70% efficiency, which produces life-cycle costs 30% higher. Worse, the excess energy from an on-line UPS becomes heat which damages batteries and decreases reliability.

■ Line-interactive design delivers Network Interface Port adds automatic safe system shutdown Once installed, an A-Smart UPS will interface with your network via serial port to perform automated safe shutdown. Power failures can occur at night, on weekends, or while the system administrator is out of the building, which makes automated safe shut-down critical. A-Smart UPS communications port means the ability to coordinate a safe shutdown with most popular operating systems by Novell, IBM, Microsoft, Banyan, UNIX, and others. You can also manage UPS power and diagnose power problems using Upsilon2000 UPS monitor software.

■ SNMP SLOT adds completely UPS Networks ManagementA-Smart UPS includes SNMP Slot that you can Install internal SNMP Card(Optional) for up-rade A-Smart UPS Management of networks.(also can install external SNMP Box via UPS communication port)

■ ONLINE Hot-Swap user Friendly, Hot swappable battery replacement SystemSaves the time and expense of returning the UPS to the factory for Battery service, And allows safe and easy replacement of batteries while your system is up and running. Replacement battery kits ship in a reusable box for convenient return of exhausted batteries to a recycling center or to Netion.

Page 15: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

3

3-�

Uninterruptible Power Supply

Line interactive UPS

■ Lightning and surge protection shields hardwarewhen measured via IEEE 62.41 Category "A" tests, the suppression performance of the A-Smart UPS is superior to virtually all separate surge suppressors.

■ Network-grade line conditioning prevents glitchesFull time EMI/RFI filters prevent line noise from causing data errors, A-Smart UPS meets Novell and Microsoft's approval for network protection, without the need for additional external conditioners.

■ Super-Boost automatically corrects brownout conditionsAllows you to work through brownouts without unnecessary battery drain. Super Boost automatically Two-stage up low voltage to safe output levels.

■ Smart-Back Trim automatically corrects overvoltage conditions Allows you to work through overvoltages without unnecessary battery drain. Smart-Back Trim automatically steps down high voltage to safe output levels.

Protect

■ Battery Replacement Warning prevents downtime A-Smart UPS automatically performs a self-test every two weeks. This ensures you will be alerted to degraded batteries before they wear out. Through software, or the push of a button, you may perform self-tests anytime.

■ Informative LED Display provides status at a glance Instantly assess the status of your power and the A-Smart UPS without even pushing a button. Bar meters and status indicators are simple to use and easy to understand. Visible and audible alarms alert you to fault conditions.

■ Load and Battery Meters keep you in controlThe Load Meter prevents you from exceeding UPS capacity. The battery Meter reports battery capacity, allowing you to gauge how much time you have before batteries are depleted. An alarm sounds when batteries are low, allowing you time to save data and shutdown the system.

Messages

Page 16: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

3

3-3Power SupplyUninterruptible Power Supply

Diagram of net agent UPS networks monitor:

For UPS Network Monitor completely, you can use Net Agent internal card or external boxNet Agent Feature: 1.provide SNMP MIB to monitor & control UPS 2.Auto-sense 10 Base-T/100M Fast Ethernet 3.Support TCP/IP, UDP, SNMP, Telnet, SNTP,PPP,HTTP,SMTP Protocol 4.Providing easy setup and upgrade tools via MS-Windows, no more traditional RS232 complicated setting nightmare 5.Sending TRAP and E-mail for events notifications simultaneously 6.Auto email daily UPS history report 7.environment Measurement (Optional) 8.External modem dial in/out via PPP protocol (Optional)

Line interactive UPS

Diagram of net agent use in UPS networks monitor:

Page 17: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

3

3-�

Uninterruptible Power Supply

SpecificationModel Name A-Smart 1000(XL) A-Smart 2000(XL) A-Smart 3000(XL) A-Smart 6000(XL)

1KVA 2KVA 3KVA 6KVAInputvoltagetype

120Vac 230Vac 120Vac 230Vac 120Vac 230Vac 120Vac 230Vac

Allowablerange

80~132Vac

145~290Vac

80~132Vac

145~290Vac

80~132Vac

145~290Vac

80~132Vac

145~290Vac

Inputprotection

Circuit Breaker Circuit Breaker Circuit Breaker Circuit Breaker

Boost/Buck 120Vac  92~103Vac(2 stage)/132~150Vac(1 stage)Range 230Vac  184~206Vac(2 stage)/264~300Vac(1 stage)Inputfrequency

50/60Hz(Auto Selectable)

Transfertime

2~3.5ms(Normal Load) Max:<10ms

Outputvoltage(Inverter)

120V±5% 230V±5% 120V±5% 230V±5% 120V±5% 230V±5% 120V±5% 230V±5%

Outputfrequency(Inverter)

50/60Hz±0.1Hz 50/60Hz±0.1Hz 50/60Hz±0.1Hz 50/60Hz±0.1Hz

Outputwaveform(Inverter)

Pure sinewave Pure sinewave Pure sinewave Pure sinewave

Outputcapacity

1000VA/660W(700W) 2000VA/1400W 3000VA/2100W 6000VA/4200W

Characteristics True Line-Interactive designProtections High Voltage & Overload & Short Circuit & Low BatteryTotal 24Vdc/36Vdc/ 48Vac 48Vac 48VacBattery (48Vac)VoltageRechargetime

3~8 Hours(24 Hours) 12 Hours(24 Hours) 12 Hours(24 Hours) 18 Hours(24 Hours)

Backuptime

Full 6/10 min 20min(2.5...hr) 10min(2...hr) 12min(2...hr)Load (2/4/6...hr)Half 12/20min 40min(5...hr) 20min(4...hr) 25min(4...hr)Load (4/8/12...hr)

Auto 12/20/30min 12/20/30min 12/20/30min 12/20/30minturn on (2/4/6hr) (2/4/6hr) (2/4/6hr) (2/4/6hr)Comm.interface

Ture RS232 / Dry Relay Contact two way

Userinterface

LED Display LCD(optional)

LEDdisplays

Front : Battery Charge, Load Level ,On-Line, Over Load,Buck, Boost, On-Battery, Battery weakBack : Voltage Sensitivity(Generator Mode),Site Fault

Audiblesound

40dBA 50dBA 50dBA 50dBA

Operatingtemperature

0~40℃ 0~40℃ 0~40℃ 0~40℃

Storetemperature

-15℃ ~ +45℃ -15℃ ~ +45℃ -15℃ ~ +45℃ -15℃ ~ +45℃

Surgeprotectionapprovals

IEEE C62.41 CATEGORY A

Safetyapprovals

UL/TUV

EMI approvals CISPER22 CLASS B  FCC CLASS BDimension(H*W*D)(mm)

216*170.5*380 432*196*546 432*196*546 432*196*546

Net Weight 18.5Kg(15.5Kg) 46.8Kg(32Kg) 50.3Kg(38Kg) 91.8Kg(71Kg)

Line interactive UPS

Please consult the factory or the distributors for further information of "S" models.

Page 18: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

3

3-�Power SupplyUninterruptible Power Supply

Blazer (modified sine wave output waveform)

■ PCs, Workstations, Small servers, POS systems, Critical electronic devices

Application

■ Microprocessor control guarantees high reliability;■ Equipped with AVR to stabilize output voltage;■ Wide input voltage range;■ Generator Compatible;■ Auto charging even though the UPS is off;■ Auto restart while AC recovery;■ On-battery power-on function without AC input;■ RJ11 Modem/Phoneline surge protection;■ Full protection against over-discharge, overcharge, overload;■ Smart RS232 and USB communication interfaces;■ Sealed lead-acid, maintenance free battery.

Key features

Technical specificationsProduct Series BLAZERModel BLAZER 600 BLAZER 800 BLAZER1000 BLAZER1400 BLAZER2000Rated Power VA/W 600/360 800/480 1000/600 1400/840 2000/1080Input Nominal Voltage 220VAC

Voltage Range 162 ~ 268VACNominal Frequency 50HzProtection Fuse Non-Fuse breakerConnection IEC320-10A inlet

Output Voltage 220VACRegulation ±10% on battery voltage regulation; ±15% on utility voltage regulationFrequency 50Hz ±1Hz ( Battery mode)Overload Capability 110% for 5 min., 120% immediate shutdownConnections IEC320-10A * 3 IEC320-10A * 4

Battery Type Sealed Lead-Acid, Maintenance freeBackup Time 20 min.(a PC with

15” monitor)30 min.(a PC with 15” monitor)

23 min. 25 min.(two PCs with 15” monitors)

(two PCs with 15” monitors)

Recharge Time 8 hours to 90% capacity after full load dischargeLED indicators Line Mode Green LED lighting The 1st green LED lighting; the 2nd to 5th green LEDs

indicating load levelBattery Mode Green LED flashing The 1st green LED flashing; the 2nd to 5th green LEDs

indicating battery capacity levelFault -- Red LED lighting

Audible Alarm Battery Mode Beeping every 10 secondsBattery Low Beeping every second Overload Beeping every 0.5 secondsFault Beeping continuously

Acoustic Noise £ 45 dBAData Line Surge Protection RJ11 I/O jacksCommunications RS232 and USB portsEnvironmental Temperature 0˚C~ 40˚C

Humidity 20% ~ 90% non-condensingWeight Net (kg) 6 6.5 13.8 14.2 16Dimensions W x D x H (mm) 100 x 330 x 140 140.2 x 368.3 x 180.4

Page 19: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-1Power SupplyUninterruptible Power Supply

GREEGOO GP11 series UPS is single Phase Input and Single Phase Output and the capacity from 8KVA to 20KVA; GP31 series UPS is three phases input & single phase output and the capacity is from 10KVA to 30KVA. They can use in parallel or separately against different request. They suitable for large machine room, data management center, manufacture industry, petrify system, metallurgical industry, power system etc. important area.

Low Frequency On Line UPS 8KVA-30KVA(1Ph Out)

High Reliable■ Adopt twin change on line technology, sequester extraneous interference;■ Favorable overload ability and protection;■ Design with 100% unbalance protection;■ 100% Non linear load ability;■ IGBT, PWM inverter together with digital .

logic power control technology■ Industrial grade UPS.

Super Safety■ The output isolate transformer can avoid the destruction of abnormal signal & lightning stroke;■ With static bypass, repair bypass, battery maintain bypass;■ Cold start.

Smart■ Different loading have different use way. Single UPS, 1+1 or N+1 etc;■ Modular design, easy to repair;■ Intelligent management for battery pack.

Economic■ The efficiency of complete system more than 90%, it will be up to 95% or more if ECO mode.

Easy operation■ LED/LCD display, it’s easy to operate.

Intelligent■ It can remote management and TVSS through the offered RS232()RS422, optional SNMP Card, RJ45 etc. communicate port.

APPLIANCE ■ Data management equipment and system;■ Automatic control systems;■ Hospital;■ Mini office system;■ Telecommunication systems;■ Bank.

FEATURES

Page 20: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

�-�

Uninterruptible Power Supply

UPS 8KVA-30KVA(1Ph Out)

Technical specifications

Model GP1108 GP1110 GP1115 GP1120 GP3110 GP3115 GP3120 GP3130Capacity 8KVA 10KVA 15KVA 20KVA 10KVA 15KVA 20KVA 30KVAInput Voltage 220VAC±25% (Single phase 2 wires + G) 220/380VAC±20% (Three phases 4 wires + G)

Frequency 50Hz ± 10%Power Factor 0.8 ( 0.95 if UPS with filter )

Output Voltage 220VAC±1% (steady state) 220VAC±2% (steady state)Frequency Free synchronized to main (AC Power Mode); 50Hz±0.5%(Battery Mode)Power Factor 0.8 (lagging)Wave Form Sine WaveDistortion £ 3% (linear load), £ 5% (non linear load)Crest Factor 3:01Transitory Voltage 220VAC ± 4% 220VAC ± 5%Efficiency ³90%

Battery Type 12VDC Sealed lead acid battery, maintenance freeNominal Voltage 192VDC (16 PCS) 384VDC (32 PCS)Backup Time As per the request of customerRecharge Time 7 ~ 10 hours up to 90% capacityCharge Current 10~25A (Adjustable)

Transfer Time 0 ms ( AC to DC or DC to AC); < 4 ms (Bypass to Inverter or Inverter to Bypass)LCD Display UPS work situation, AC power situation, Battery situation, automatic turn to bypass,

overloadOverload Ability 150% for 30 seconds, 125% for 10 minutesProtection Over Voltage, Under Voltage, Over Load, Over Temperature, Short Circuit, Lightning

Stroke etc.Alarm Over Temperature, Battery, Bypass, AC Power Abnormal, Over Load, Over VoltageNoise ( 1 m distance) £55dBCommunicate Interface RS232 (or RS422), SNMP Card (Optional), RJ45Ambient Temperature 0˚C ~ 40˚C

Humidity 10% ~ 90% (no dewfall)Elevation < 2000m

Size (mm) 1140x560x800N.W. (kg) 125 140 175 225 181 235 285 320EMC IEC62040-2, EN50091,GB9254Ability of Antijamming IEC61000-4Protection Degree IP20

Page 21: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-3Power SupplyUninterruptible Power Supply

GREEGOO GP33 series low frequency on line UPS, champion UPS, industrial UPS from 10KVA to 300KVA. It’s designed special for data management center, manufacture industry, petrify system, metallurgical industry, power system etc. It’s adopted twin changing online design, intelligent IGBT module, PWM pulse-width modulation and several CPU, champion UPS, industrial UPS control technology. It’s the best protection equipment for various kinds of important equipments. It can enlarge the capacity up to 8 units UPS use in parallel.

Low Frequency On Line UPS 10KVA-300KVA(3Ph out)

High Reliable■ Adopt twin change on line technology,sequester extraneous interference;■ Favorable overload ability and protection;■ Design with 100% unbalance protection;■ 100% Non linear load ability;■ IGBT, PWM inverter together with digital .

logic power control technology■ Industrial grade UPS.

Super Safety■ The output isolate transformer can avoid the destruction of abnormal signal & lightning stroke;■ With static bypass, repair bypass, battery maintain bypass;■ Cold start champion UPS, industrial UPS.

Smart■ Different loading have different use way. Single UPS, 1+1 or N+1 etc;■ Modular design, easy to repair;■ Intelligent management for battery pack.

Economic■ The efficiency of complete system more than 90%, it will be up to 95% or more if ECO mode.

Easy operation■ LED/LCD display, it’s easy to operate.

Intelligent■ It can remote management and TVSS through the offered RS232()RS422, optional SNMP Card, RJ45 etc. communicate port.

APPLIANCE ■ Data management equipment and system;■ Automatic control systems;■ Hospital;■ Mini office system;■ Telecommunication systems;■ Bank champion UPS, industrial UPS.

FEATURES

Page 22: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008htt

p:/

/ww

w.g

reegoo.c

om

Power Supply

�-�

Uninterruptible Power Supply

UPS 10KVA-300KVA(3Ph out)

Technical specifications Model GP3310 GP3315 GP3320 GP3330 GP3340 GP3360Capacity 10KVA 15KVA 20KVA 30KVA 40KVA 60KVAInput Voltage 220/380VAC±20% (Three phases +N + G)

Frequency 50Hz ± 10%Power Factor 0.8 (0.95 if lagging)Bypass Phase Qty. Three phases 4 wires + G

Voltage 380V ± 15%Frequency 50Hz ± 2%

Output Voltage 380VAC±1% (steady state)Frequency 50Hz±5% (AC Power Mode); 50Hz±0.1%(Battery Mode)Power Factor 0.8 (lagging)Wave Form Sine WaveDistortion = 3% (linear load), = 5% (non linear load)Transitory Voltage of dynamic load

±5% (0 ~ 100% Decrease step by step)

Transitory recover time < 10ms (±5%)Unbalance Voltage < 3%, <1%( balanced load)Overload Ability 150% for 1 minute, 125% for 10 minutes, more than 150% for 200msCrest Factor 3:1Efficiency > 90%, 95% (ECO mode)

Battery Type 12VDC Sealed lead acid battery, maintenance freeNominal Voltage 384VDC (32PCS)Recharge Time < 10 hours up to 90% capacityCharge Current 10~25A (Adjustable)

Transfer time 0 ms ( AC to DC or DC to AC); < 4 ms (Bypass to Inverter or Inverter to Bypass)LCD Display UPS work situation, AC power situation, Battery situation, automatic turn to bypass, overloadProtection Over Voltage, Under Voltage, Over Load, Over Temperature, Short Circuit, Lightning Stroke etc.Alarm Over Temperature, Battery, Bypass, AC Power Abnormal, Over Load, Over VoltageNoise ( 1 m distance) < 50dB < 55dB < 65dBCommunicate Interface RS232 (or RS422), SNMP Card (Optional), RJ45Cooling way FanAmbient Temperature 0 ? ~ 40 ?

Humidity 10% ~ 90% (no dewfall)Elevation < 2000m

Size (mm) 700x520x1100 800x600x1200 900x660×x1500

N.W. (kg) 210 258 350 400 480 650EMC IEC62040-2, EN50091-2, GB9254Ability of Antijamming IEC61000-4Protection Degree IP20

Page 23: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-�Power SupplyUninterruptible Power Supply

UPS 10KVA-300KVA(3Ph out)

Technical specifications Model GP3380 GP33100 GP33120 GP33140 GP33160 GP33200 GP33250 GP33300

Capacity 80KVA 100KVA 120KVA 140KVA 160KVA 200KVA 250KVA 300KVAInput Voltage 220/380VAC±20% (Three phases +N + G)

Frequency 50Hz ± 10%Power Factor 0.8 (0.95 if lagging)Bypass Phase Qty. Three phases 4 wires + G

Voltage 380V ± 15%Frequency 50Hz ± 2%

Output Voltage 380VAC±1% (steady state)Frequency 50Hz±5% (AC Power Mode); 50Hz±0.1%(Battery Mode)Power Factor 0.8 (lagging)Wave Form Sine WaveDistortion = 3% (linear load), = 5% (non linear load)Transitory Voltage of dynamic load

±5% (0 ~ 100% Decrease step by step)

Transitory recover time

< 10ms (±5%)

Unbalance Voltage < 3%, <1%( balanced load)Overload Ability 150% for 1 minute, 125% for 10 minutes, more than 150% for 200msCrest Factor 3:1Efficiency > 90%, 95% (ECO mode)

Battery Type 12VDC Sealed lead acid battery, maintenance freeNominal Voltage 384VDC

(32PCS)396VDC(33PCS)

Recharge Time < 10 hours up to 90% capacityCharge Current 10~25A (Adjustable)

Transfer time 0 ms ( AC to DC or DC to AC); < 4 ms (Bypass to Inverter or Inverter to Bypass)LCD Display UPS work situation, AC power situation, Battery situation, automatic turn to bypass, overloadProtection Over Voltage, Under Voltage, Over Load, Over Temperature, Short Circuit, Lightning Stroke etc.Alarm Over Temperature, Battery, Bypass, AC Power Abnormal, Over Load, Over VoltageNoise ( 1 m distance) < 65dB < 68dBCommunicate Interface RS232 (or RS422), SNMP Card (Optional), RJ45Cooling way FanAmbient Temperature 0˚C~ 40˚C

Humidity 10% ~ 90% (no dewfall)Elevation < 2000m

Size (mm) 1250x900x1600 2000x900x1800 2400x900x1800N.W. (kg) 900 1100 1200 1250 1380 1520 1650 1800EMC IEC62040-2, EN50091-2, GB9254Ability of Antijamming IEC61000-4Protection Degree IP20

Page 24: 1000 Watts Ups Circuit Diagram

Greegoo Electric 5.2008 htt

p:/

/ww

w.g

reegoo.c

om

�-1Power SupplyUninterruptible Power Supply

Battery Cabinet

Technical parameter

Name ModelNo.

Specification Battery Weight(KGS)

Packing Measure(LxWxH)mm

Battery Cabinet A1 462x200x295 100Ah 1 PC 5 480x220x330Battery Cabinet A2 458x382x294 100Ah 2 PCS 8 480x390x280Battery Cabinet A3 617x470x305 100Ah 3 PCS 13 600x450x210Battery Cabinet A4 500x420x613 100Ah 4 PCS 17 640x490x210Battery Cabinet A6 617x470x613 100Ah 6 PCS 21 640x490x210Battery Cabinet A8 780x470x632 100Ah 8 PCS 24 800x490x210Battery Cabinet A10 959x470x632 100Ah 10 PCS 30 980x490x200Battery Cabinet A12 780x470x915 100Ah 12 PCS 34 800x490x330Battery Cabinet A16 780x470x1210 100Ah 16 PCS 45 800x490x220Battery Cabinet 1180x490x90Battery Cabinet A20 959x470x1210 100Ah 20 PCS 53 980x490x230Battery Cabinet 1180x490x90Battery Cabinet B7081 482.6x450x88 7Ah 8 PCS 26.5 600x600x265

Notes:1.The above weight without including the weight of battery.2.The package is one package for one set of battery group.3. The space of 100Ah battery cabinet 1 nos is equal to 24Ah 3 nos, 38Ah battery 2 nos and 65Ah battery 1 nos.