1. performance test of a cooling tower

6
  E 404 roup No. :  Experiment No. : 01 Experiment Name: Date of Performance:  12-05-2015  Date of Submission:  13-05-2015 Name:  Nahian Hyder Department:  ME Roll No.:  0910108 Section: B

Upload: mahmud-hasan

Post on 02-Nov-2015

215 views

Category:

Documents


0 download

DESCRIPTION

performance test of a cooling tower

TRANSCRIPT

  • ME 404

    Group No. :

    Experiment No. : 01

    Experiment Name:

    Date of Performance: 12-05-2015

    Date of Submission: 13-05-2015

    Name: Nahian Hyder

    Department: ME

    Roll No.: 0910108

    Section: B

  • Objective:

    To observe different parts of a cooling tower.

    To observe the set-up of cooling tower.

    To analyse the performance of the cooling tower.

    Line Diagram:

    Apparatus:

    Hygrometer

    Manometer

    o manometer for water flow measurement

    o Water manometer for air flow measurement

    Thermometer

    Condenser

    Tower Air

    Blower

    Water Pump

    Valve

    Orifice

  • Data Sheet

    1. Physical dimensions:

    a. Cooling tower

    i. Length, = 2.00

    ii. Breadth, = 1.88

    iii. Height, = 2.61

    iv. Fill of the tower = 2 1.88 2.61 = 9.8136

    b. Air duct

    i. Duct diameter, = 0.482

    ii. Orifice diameter, = 0.216

    c. Water pipe:

    i. Pipe diameter, = 0.076

    ii. Orifice diameter, = 0.032

    2. Atmospheric conditions during experiment

    a. Atmospheric pressure, = 760

    b. Dry bulb temperature, = 26

    c. Wet bulb temperature, = 24

    3. Operating condition during experiment

    No.

    of

    Obs.

    Water Flow Data Air Flow Data

    ()

    ()

    ()

    ()

    ()

    ()

    1 40 31.6 27.3

    17

    29 22

    2 35 34 27.8 30 29

    3 25 36.8 27.9 31 30

    4 15 39.7 28.2 33 31

    5 10 43.5 28.7 32 31

  • Calculation Sheet

    No. of Obs. 1. 2. 3. 4. 5.

    Density of air (/ ) 1.18

    Air flow rate, (/) 0.445

    Water flow rate ( ) 1.602 1.498 1.266 0.981 0.801

    Water Air Ratio / 3.598 3.365 2.844 2.203 1.799

    Sp. Humidity of Inlet Air ( . . ) 0.018 0.018 0.018 0.018 0.018

    Sp. Humidity of Outlet Air ( . . ) 0.020 0.024 0.029 0.029 0.030

    ( . . ) 0.002 0.006 0.011 0.011 0.012

    Make-up Water () 0.001 0.003 0.005 0.005 0.005

    % Make-up 0.042 0.178 0.369 0.499 0.639

    Actual Cooling Range () 4.300 6.200 8.900 11.500 14.800

    Theoretical Cooling Range () 7.600 10.000 12.800 15.700 19.500

    Cooling Efficiency 56.579 62.000 69.531 73.248 75.897

    Heat of Incoming Hot Water () 212.212 213.523 195.276 163.966 145.919

    Heat of Outgoing Hot Water () 183.420 174.705 148.182 116.012 96.397

    Heat of Dry Inlet Air () 133.795

    Heat of water vapour in Air at Inlet () 24.493

    Heat of Dry Outlet Air () 135.138 135.585 136.033 136.928 136.480

    Heat of Water Vapour in Air at Outlet () 26.583 32.737 38.899 39.630 40.289

    Unaccounted Heat () 30.134 40.608 49.332 51.086 52.206

  • 0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0

    10

    20

    30

    40

    50

    60

    70

    80

    1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5

    % M

    ake

    -up

    Wat

    er

    Co

    olin

    g E

    ffic

    ien

    cy

    Water-Air Ratio

    Cooling Efficiency vs % make-up water and Water-Air Ratio

    Efficiency vs Water-Air Ratio % make-up vs Water-Air Ratio

  • Discussion