1. performance test of a cooling tower
DESCRIPTION
performance test of a cooling towerTRANSCRIPT
-
ME 404
Group No. :
Experiment No. : 01
Experiment Name:
Date of Performance: 12-05-2015
Date of Submission: 13-05-2015
Name: Nahian Hyder
Department: ME
Roll No.: 0910108
Section: B
-
Objective:
To observe different parts of a cooling tower.
To observe the set-up of cooling tower.
To analyse the performance of the cooling tower.
Line Diagram:
Apparatus:
Hygrometer
Manometer
o manometer for water flow measurement
o Water manometer for air flow measurement
Thermometer
Condenser
Tower Air
Blower
Water Pump
Valve
Orifice
-
Data Sheet
1. Physical dimensions:
a. Cooling tower
i. Length, = 2.00
ii. Breadth, = 1.88
iii. Height, = 2.61
iv. Fill of the tower = 2 1.88 2.61 = 9.8136
b. Air duct
i. Duct diameter, = 0.482
ii. Orifice diameter, = 0.216
c. Water pipe:
i. Pipe diameter, = 0.076
ii. Orifice diameter, = 0.032
2. Atmospheric conditions during experiment
a. Atmospheric pressure, = 760
b. Dry bulb temperature, = 26
c. Wet bulb temperature, = 24
3. Operating condition during experiment
No.
of
Obs.
Water Flow Data Air Flow Data
()
()
()
()
()
()
1 40 31.6 27.3
17
29 22
2 35 34 27.8 30 29
3 25 36.8 27.9 31 30
4 15 39.7 28.2 33 31
5 10 43.5 28.7 32 31
-
Calculation Sheet
No. of Obs. 1. 2. 3. 4. 5.
Density of air (/ ) 1.18
Air flow rate, (/) 0.445
Water flow rate ( ) 1.602 1.498 1.266 0.981 0.801
Water Air Ratio / 3.598 3.365 2.844 2.203 1.799
Sp. Humidity of Inlet Air ( . . ) 0.018 0.018 0.018 0.018 0.018
Sp. Humidity of Outlet Air ( . . ) 0.020 0.024 0.029 0.029 0.030
( . . ) 0.002 0.006 0.011 0.011 0.012
Make-up Water () 0.001 0.003 0.005 0.005 0.005
% Make-up 0.042 0.178 0.369 0.499 0.639
Actual Cooling Range () 4.300 6.200 8.900 11.500 14.800
Theoretical Cooling Range () 7.600 10.000 12.800 15.700 19.500
Cooling Efficiency 56.579 62.000 69.531 73.248 75.897
Heat of Incoming Hot Water () 212.212 213.523 195.276 163.966 145.919
Heat of Outgoing Hot Water () 183.420 174.705 148.182 116.012 96.397
Heat of Dry Inlet Air () 133.795
Heat of water vapour in Air at Inlet () 24.493
Heat of Dry Outlet Air () 135.138 135.585 136.033 136.928 136.480
Heat of Water Vapour in Air at Outlet () 26.583 32.737 38.899 39.630 40.289
Unaccounted Heat () 30.134 40.608 49.332 51.086 52.206
-
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0
10
20
30
40
50
60
70
80
1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5
% M
ake
-up
Wat
er
Co
olin
g E
ffic
ien
cy
Water-Air Ratio
Cooling Efficiency vs % make-up water and Water-Air Ratio
Efficiency vs Water-Air Ratio % make-up vs Water-Air Ratio
-
Discussion