1 fire alarm system initiating devices chapter 12 page 357
TRANSCRIPT
![Page 1: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/1.jpg)
1
Fire Alarm System Initiating Devices
Chapter 12
Page 357
![Page 2: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/2.jpg)
2
Objectives• List and compare the available types of
manually operated fire alarm devices• Discuss the methodology used to increase
the reliability of a fire alarm system• Evaluate the differences between the
available types of heat detectors• Compare the capabilities of the various
types of smoke detectors2
![Page 3: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/3.jpg)
3
Objectives
• Define stratification and explain how it can be predicted
• Propose a methodology for detecting a fire where stratification is predicted
• Discuss the “pressure sandwich,” and explain how this principle is accomplished by a fire detection system
3
![Page 4: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/4.jpg)
4
Objectives
• Compare and contrast flame detectors and their applications
• Give examples of where gas detectors and pressure detectors are appropriate for use
• List and discuss the fire protection system supervisory functions that can be provided by a fire alarm system 4
![Page 5: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/5.jpg)
5
Manually Operated Devices
• Manually operated fire alarm devices: require the action of an individual to initiate a fire alarm signal
• Manual pull stations: used by building occupants to electronically notify others of a fire
5
![Page 6: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/6.jpg)
6
Manually Operated Devices
• Coded manual stations: send a set of unique time-pulsed signals to the fire alarm control unit three or more times, indicating location of the manual station
• Non-coded manual stations: do not deliver a distinctive signal– Grouped on a circuit so the control unit can
indicate activation
6
![Page 7: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/7.jpg)
7
Manually Operated Devices
• Presignal and General Alarm Manual Stations
• Single-Action and Double-Action Manual Stations
• Breakglass and Nonbreakglass Manual Stations
• Addressable Manual Stations7
![Page 8: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/8.jpg)
8
Automatic Fire Detectors• Reliability Methodology for Detectors• Methods of ensuring the reliability of an
automatic fire detection system:– Protection– Wiring– Support– Ceiling jet interaction– Testing accessibility
8
![Page 9: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/9.jpg)
9
Automatic Fire Detectors (con’t.)
Figure 12-2. Detection system support
![Page 10: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/10.jpg)
10
Automatic Fire Detectors (con’t.)
• Methods of ensuring the reliability of an automatic fire detection system (con’t.):– Enclosure evaluation– Specific points of hazard– Anticipated fire– Detection zones
• Addressable Detectors
10
![Page 11: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/11.jpg)
11
Automatic Fire Detector Overview and Comparison
• Automatic fire detectors are composed of– Heat-sensing fire detectors– Smoke-sensing fire detectors– Flame-sensing radiant energy fire detectors– Gas-sensing detectors– Pressure detectors– Non-fire detectors (cold detectors, video
surveillance systems)11
![Page 12: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/12.jpg)
12
Automatic Fire Detector Overview and Comparison
(con’t.)
Table 12-1. Comparison of automatic fire detectors
![Page 13: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/13.jpg)
13
Spot-Type Heat-Sensing Fire Detectors
• Spot-Type Pneumatic Rate-of-Rise Heat Detectors
• Spot-Type Thermocouple Rate-of-Rise Heat Detectors
• Spot-Type Fixed Temperature Heat Detectors
• Spot-Type Rate-Compensated Heat Detectors 1
3
![Page 14: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/14.jpg)
14
Spot-Type Heat-Sensing Fire Detectors (con’t.)
Figure 12-5. Spot-type pneumatic rate-of-rise heat detector
![Page 15: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/15.jpg)
15
Spot-Type Heat-Sensing Fire Detectors (con’t.)
Figure 12-6. Bimetallic fixed temperature heat detectors
![Page 16: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/16.jpg)
16
Spot-Type Heat-Sensing Fire Detectors
• Spot-Type Electronic Thermistor Heat Detectors
• Spot-Type Analog Heat Detectors• Spot-Type Combination Heat Detectors
16
![Page 17: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/17.jpg)
17
Line-Type Heat-Sensing Devices
• Electric or pneumatic • Can be selected to detect either a fixed-
temperature or rate-of-temperature rise anywhere along the length of the detector
• Well suited for linear or elongated hazards such as conveyors and electric cable trays
17
![Page 18: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/18.jpg)
18
Smoke-Sensing Fire Detectors• Spot-Type Ionization Smoke Detectors• Spot-Type Photoelectric Light-Scattering
Detectors• Spot-Type Photoelectric Light Obscuration
Smoke Detectors• Air-Sampling or Air-Aspirated Smoke
Detectors• Laser-Based Air Sampling Smoke
Detectors 18
![Page 19: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/19.jpg)
19
Smoke-Sensing Fire Detectors
Figure 12-10. Line-type heat-sensing device: applications (Note: These detectors are ideal for linear or elongated hazards such as conveyors
and cable trays) 19
![Page 20: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/20.jpg)
20
Smoke-Sensing Fire Detectors
• Linear Beam Smoke Detectors
• Air-Duct Smoke Detectors• Analog Smoke Detectors
20
![Page 21: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/21.jpg)
21
Flame-Sensing Radiant Fire Detectors
• Ultraviolet (UV) Flame Detectors• Infrared (IR) Flame Detectors• Combination Ultraviolet/Infrared (UV/IR)
Detectors• Selecting a Flame Detection System• Radiation Spectrum for Flame Detectors• Inverse Square Law for Flame Detectors• Spark/Ember Detectors 2
1
![Page 22: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/22.jpg)
22
Flame-Sensing Radiant Fire Detectors (con’t.)
Figure 12-22. Radiation spectrum
![Page 23: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/23.jpg)
23
Multi-Sensor Detectors
• Multi-sensor detectors: increases reliability by combining heat and smoke sensing, heat and carbon monoxide sensing, heat/co/smoke sensing, or ionization plus photoelectric sensing
• Multi-sensor detectors contain algorithms for discerning sources of nuisance alarms
23
![Page 24: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/24.jpg)
24
Gas-Sensing Detectors
• A gas-sensing detector can be chosen to detect the release of a flammable gas before it reaches ignitable concentration
• Gas-sensing detectors: detect the release of a flammable gas before it reaches ignitable concentration
24
![Page 25: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/25.jpg)
25
Pressure-Sensing Fire Detectors
• In tightly enclosed rooms or enclosures where personnel are not present, a fire increases the pressure in the enclosure
• Pressure-sensing fire detector: plate that depresses when the enclosure pressure increases to a predetermined level and activates a signal to the FACU
25
![Page 26: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/26.jpg)
26
Fire Protection System Flow And Supervisory Switches
• Sprinkler System Waterflow Switches• Fire Suppression System Releasing
Switches• Fire Suppression System Supervisory
Switches
26
![Page 27: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/27.jpg)
27
Summary
• Initiating devices on a fire alarm system are watchdogs that supervise essential equipment and report fire conditions to the fire alarm control unit (FACU)
• Initiating devices must be– Protected– Properly wired and supported– Placed within the ceiling jet boundary
27
![Page 28: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/28.jpg)
28
Summary
• Initiating devices must (con’t.):– Tested frequently and suitable in the
enclosure conditions to which it is exposed– Installed for specific points of hazard– Selected correctly for the anticipated fire– Zoned wisely
28
![Page 29: 1 Fire Alarm System Initiating Devices Chapter 12 Page 357](https://reader034.vdocuments.site/reader034/viewer/2022051820/56649de75503460f94ae094e/html5/thumbnails/29.jpg)
29
Summary
• Detectors types– Heat-sensing– Smoke-sensing– Particle-sensing– Flame-sensing– Gas-sensing– Pressure-sensing
29