1 electrical circuit et 201 become familiar with the operation of a three phase generator and the...
TRANSCRIPT
![Page 1: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/1.jpg)
1
ELECTRICAL CIRCUIT ET 201
Become familiar with the operation of a three phase generator and the magnitude and phase relationship.
Be able to calculate the voltages and currents for a three phase Wye and Delta connected generator and load.
![Page 2: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/2.jpg)
2
THREE PHASE THREE PHASE SYSTEMSSYSTEMS
![Page 3: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/3.jpg)
3
23.1 – IntroductionIf the number of coils on the rotor is increased
in a specified manner, the result is a polyphase ac generator, which develops more than one ac phase voltage per rotation of the rotor
An ac generator designed to develop a single sinusoidal voltage for each rotation of the shaft (rotor) is referred to as a single-phase ac generator
In general, three-phase systems are preferred over single-phase systems for the transmission of power for many reasons, including the following:
![Page 4: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/4.jpg)
4
Introduction1. Thinner conductors can be used to transmit the same kVA
at the same voltage, which reduces the amount of copper required (typically about 25% less) and in turn reduces construction and maintenance costs.
2. The lighter lines are easier to install, and the supporting structures can be less massive and farther apart.
3. Three-phase equipment and motors have preferred running and starting characteristics compared to single-phase systems because of a more even flow of power to the transducer than can be delivered with a single-phase supply.
4. In general, most larger motors are three phase because they are essentially self-starting and do not require a special design or additional starting circuitry.
![Page 5: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/5.jpg)
5
IntroductionThe frequency generated is determined by the
number of poles on the rotor (the rotating part of the generator) and the speed with which the shaft is turned.
Throughout the United States the line frequency is 60 Hz, whereas in Europe (incl. Malaysia) the chosen standard is 50 Hz.
On aircraft and ships the demand levels permit the use of a 400 Hz line frequency.
The three-phase system is used by almost all commercial electric generators.
![Page 6: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/6.jpg)
6
IntroductionMost small emergency generators, such as the
gasoline type, are one-phased generating systems.The two-phase system is commonly used in
servomechanisms, which are self-correcting control systems capable of detecting and adjusting their own operation.
Servomechanisms are used in ships and aircraft to keep them on course automatically, or, in simpler devices such as a thermostatic circuit, to regulate heat output.
The number of phase voltages that can be produced by a polyphase generator is not limited to three. Any number of phases can be obtained by spacing the windings for each phase at the proper angular position around the stator.
![Page 7: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/7.jpg)
7
23.2 – Three-Phase Generator
The three-phase generator has three induction coils placed 120° apart on the stator.
The three coils have an equal number of turns, the voltage induced across each coil will have the same peak value, shape and frequency.
![Page 8: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/8.jpg)
8
Three-Phase GeneratorAt any instant of time, the algebraic sum of
the three phase voltages of a three-phase generator is zero.
![Page 9: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/9.jpg)
9
Three-Phase GeneratorThe sinusoidal expression for each of the
induced voltage is:
![Page 10: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/10.jpg)
10
Phase expression
• In phase expression:
• Where:
EM : peak value
EA, EB and EC : rms value
02
EE M
A 1202
EE M
B 1202
EE M
C
![Page 11: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/11.jpg)
11
Connection in Three Phase System
• A 3-phase system is equivalent to three single phase circuit
• Two possible configurations in three phase system:
1. Y-connection (star connection)
2. ∆-connection (delta connection)
![Page 12: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/12.jpg)
12
Three-phase Voltages Source
Y-connected source ∆-connected source
![Page 13: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/13.jpg)
13
Three-phase Load
Y-connected load ∆-connected load
![Page 14: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/14.jpg)
14
23.3 – Y-Connected GeneratorIf the three terminals denoted N are connected
together, the generator is referred to as a Y-connected three-phase generator.
![Page 15: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/15.jpg)
15
Y-Connected Generator
The point at which all the terminals are connected is called the neutral point.
Two type of Y-connected generator:
1. Y-connected, three-phase, three-wire generator
(a conductor is not attached from this point to the load)
2. Y-connected, three-phase, four-wire generator
(the neutral is connected)
The three conductors connected from A, B and C to the load are called lines.
![Page 16: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/16.jpg)
16
Y-connected, 3-phase, 3-wire generator
![Page 17: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/17.jpg)
17
Y-connected, 3-phase, 4-wire generator
![Page 18: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/18.jpg)
18
Y-Connected GeneratorThe voltage from one line to another is called
a line voltage The magnitude of the line voltage of a
Y-connected generator is:
![Page 19: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/19.jpg)
19
Definition of Phase Voltage
• In 3-phase system, for Y-connected, the voltage from line to neutral point is called a phase voltage.
EAN – phase A voltage
EBN – phase B voltage
ECN – phase C voltage
![Page 20: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/20.jpg)
20
Definition of Line Voltage
• In 3-phase system, for Y-connected, the voltage from one line to another is called a line voltage.
EAB – voltage between line A and B
EBC – voltage between line B and C
ECA – voltage between line C and A
![Page 21: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/21.jpg)
21
Y-connected system
• Line voltage:
VAB ; VBC ; VCA
• Phase voltage:
VAN ; VBN ; VCN
![Page 22: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/22.jpg)
22
Voltage in Y-connected system
For 3-phase Y-connected system, if the phase voltage VAN is taken as the reference, so
0VV ANAN
012VV BNBN
012VV CNCN
![Page 23: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/23.jpg)
23
Voltage in Y-connected system
• By applying Kirchhoff’s Voltage Law, the line voltage can be written as
)30(1.732V
j0.866)(1.5V
j0.866))0.5(j0)((1V
)12010(1V
120V0V
VVV
AN
AN
AN
AN
BNAN
BNANAB
30V3V ANAB
![Page 24: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/24.jpg)
24
Voltage in Y-connected system• With the same method,
and
• The relationship between the line voltage and the phase voltage can be represented as
VL : line voltage Vφ : phase voltage
90V3
VVV
BN
CNBNBC
150V3
VVV
CN
ANCNCA
30V3VL φ
![Page 25: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/25.jpg)
25
Current in Y-connected system• For the Y-connected system, it should be
obvious that the line current equals the phase current for each phase; that is
IL : line current Iφ : phase
current
φIIL
![Page 26: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/26.jpg)
26
23.4 – Phase Sequence (Y-Connected Generator)
The phase sequence can be determined by the order in which the phasors representing the phase voltages pass through a fixed point on the phasor diagram if the phasors are rotated in a counterclockwise direction.
![Page 27: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/27.jpg)
27
3.4 – Phase Sequence (Y-Connected Generator)
In phasor notation,
Line voltage:
Phase voltage:
120VV
120VV
)reference(0VV
CACA
BCBC
ABAB
120VV
120VV
)reference(0VV
CNCN
BNBN
ANAN
![Page 28: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/28.jpg)
28
23.5 – Y-Connected Generator with a Y-Connected Load
Loads connected with three-phase supplies are of two types: the Y and the ∆.
If a Y-connected load is connected to a Y-connected generator, the system is symbolically represented by Y-Y.
![Page 29: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/29.jpg)
29
Y-Connected Generator with a Y-Connected Load
If the load is balanced, the neutral connection can be removed without affecting the circuit in any manner; that is, if Z1 = Z2 = Z3 , then IN will be zero, IN = 0 .
Since IL = V / Z the magnitude of the current in each phase will be equal for a balanced load and unequal for an unbalanced load. In either case, the line voltage is
![Page 30: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/30.jpg)
30
EXAMPLE 1• Calculate the line currents in the three-wire Y-Y
system as shown below.
![Page 31: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/31.jpg)
31
Solution:Single Phase Equivalent Circuit
Phase ‘a’ equivalent circuit
![Page 32: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/32.jpg)
32
21.86.8121.816.155
0110I
8.21155.16)810()25(Z;Z
VI
Aa
TT
ANAa jj
A2.986.811.8266.81
024II
A141.86.81
120II
AaCc
AaBb
![Page 33: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/33.jpg)
33
23.6 – Y-Connected Generator with a ∆-Connected Load
There is no neutral connection for the Y-∆ system shown below.
Any variation in the impedance of a phase that produces an unbalanced system will simply vary the line and phase currents of the system.
![Page 34: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/34.jpg)
34
Y-Connected Generator with a ∆-Connected Load
For a balanced load, Z1 = Z2 = Z3. The voltage across each phase of the load is equal to the line
voltage of the generator for a balanced or an unbalanced load: V = EL.
![Page 35: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/35.jpg)
35
Y-Connected Generator with a ∆-Connected Load
Kirchhoff’s current law is employed instead of Kirchhoff’s voltage law.The results obtained are:
The phase angle between a line current and the nearest phase current is 30°.
![Page 36: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/36.jpg)
36
EXAMPLE 2
A balanced positive sequence Y-connected source with VAN=10010 V is connected to a -connected balanced load (8+j4) per phase. Calculate the phase and line currents.
![Page 37: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/37.jpg)
37
Solution: Balanced WYE source, VAN = 10010 V
Balanced DELTA load, Z = 8 + j4
Phase and line currents = ??
![Page 38: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/38.jpg)
38
Phase Currents
A 43.1336.19j48
40173.2I
V 402.731V
30V 3V
Z
VI
ab
ab
ANAB
Δ
abab
Vab= voltage across Z = VAB= source line voltage
![Page 39: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/39.jpg)
39
Phase Currents
A 43.13336.19I
12043.1336.19I
A 57.10636.19I
12043.13II
A 43.1336.19I
ca
ca
bc
abbc
ab
![Page 40: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/40.jpg)
40
Line Currents
A 43.103 53.33120 II
A 57.136 53.33120 II
A 57.16 53.33I
3043.13 (19.36) 3
30 I 3I
AaCc
AaBb
Aa
abAa
![Page 41: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/41.jpg)
41
23.7 – ∆-Connected Generator
In the figure below, if we rearrange the coils of the generator in (a) as shown in (b), the system is referred to as a three-phase, three-wire.
![Page 42: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/42.jpg)
42
∆-Connected Generator∆-connected ac generator
In this system, the phase and line voltages are equivalent and equal to the voltage induced across each coil of the generator:
or EL = Eg
Only one voltage (magnitude) is available instead of the two in the Y-Connected system.
)120sin(2 and
)120sin(2 and
sin2 and
tEeEE
tEeEE
tEeEE
CNCNCNCA
BNBNBNBC
ANANANAB
![Page 43: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/43.jpg)
43
∆-Connected Generator Unlike the line current for the Y-connected generator, the
line current for the ∆-connected system is not equal to the phase current. The relationship between the two can be found by applying Kirchhoff’s current law at one of the nodes and solving for the line current in terms of the phase current; that is, at node A,
IBA = IAa + IAC
or
IAa = IBA - IAC = IBA + ICA
![Page 44: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/44.jpg)
44
∆-Connected GeneratorThe phasor diagram is shown below for a balanced load.In general, line current is:
![Page 45: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/45.jpg)
45
Definition of Phase Current
• In 3-phase system, for ∆-connected, the current that flow from one phase to another is called a phase current.
IBA – phase A current
ICB – phase B current
IAC – phase C current
![Page 46: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/46.jpg)
46
Definition of Line Current
• In 3-phase system, for ∆-connected, the current that flow through the line is called a line current.
IAa – line A current
IBb – line B current
ICc – line C current
![Page 47: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/47.jpg)
47
∆-connected system (generator)
• Line current:
IAa ; IBb ; ICc
• Phase current:
for generator:
IBA ; IAC ; ICB
![Page 48: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/48.jpg)
48
∆-connected system (load)
• Line current:
IAa ; IBb ; ICc
• Phase current:
for load:
Iab ; Ibc ; Ica
![Page 49: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/49.jpg)
49
Current in ∆-connected system (Generator side)
For 3-phase ∆-connected system (generator), if the phase current IBA is taken as the reference, so
0II BABA
012II CBCB
012II ACAC
![Page 50: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/50.jpg)
50
Current in ∆-connected system (Generator side)
• By applying Kirchhoff’s Current Law, the line current can be written as
)30(1.732I
j0.866)(1.5I
j0.866))0.5(j0(1I
)12010(1I
120I0I
III
BA
BA
BA
BA
BABA
ACBAAa
A 30I3I BAAa
![Page 51: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/51.jpg)
51
• With the same method,
and
Current in ∆-connected system (Generator side)
150I3
III
CB
BACBBb
90I3
III
AC
CBACCc
![Page 52: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/52.jpg)
52
Current in ∆-connected system (Load side)
For 3-phase ∆-connected system (load), if the phase current Iab is taken as the reference, so
0II abab
012II bcbc
012II caca
![Page 53: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/53.jpg)
53
Current in ∆-connected system (Load side)
• By applying Kirchhoff’s Current Law, the line current can be written as
)30(1.732I
j0.866)(1.5I
j0.866))0.5(j0(1I
)12010(1I
120I0I
III
ab
ab
ab
ab
abab
caabAa
A 30I3I abAa
![Page 54: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/54.jpg)
54
• With the same method,
and
Current in ∆-connected system (Load side)
150I3
III
bc
abbcBb
90I3
III
ca
bccaCc
![Page 55: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/55.jpg)
55
• The relationship between the line current and the phase current can be represented as
Where;
IL : line current Iφ : phase current
Relationship between the phase current and the line current
(∆-connected system)
30I3IL φ
![Page 56: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/56.jpg)
56
Voltage in ∆-connected system• For the ∆-connected system, it should be obvious
that the line voltage equals the phase voltage for each phase; that is
VL : line voltage
V : phase voltage
φVVL
![Page 57: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/57.jpg)
57
23.8 – Phase Sequence (∆- Connected Generator)
Even though the line and phase voltages of a ∆ -connected system are the same, it is standard practice to describe the phase sequence in terms of the line voltages
In drawing such a diagram, one must take care to have the sequence of the first and second subscripts the same
In phasor notation,
VAB = VAB 0o
VBC = VBC 120o
VCA = VCA 120o
![Page 58: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/58.jpg)
58
23.9 - ∆-Connected Generator with a ∆-Connected Load
![Page 59: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/59.jpg)
59
EXAMPLE 3
A balanced delta connected load having an impedance 20 - j15 is connected to a delta connected, positive sequence generator having VAB = 3300 V. Calculate the phase currents of the load and the line currents.
![Page 60: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/60.jpg)
60
Solution:
V 0330V
87.3625 j1520Z
AB
Δ
![Page 61: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/61.jpg)
61
Phase Currents
A87.15613.2120II
A13.83-13.2120II
A36.8713.238.8725
0330
Z
VI
abca
abbc
Δ
abab
![Page 62: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/62.jpg)
62
A 87.12686.22120II
A 13.311-86.22120II
A 87.686.22
30336.8713.2
303II
AaCc
AaBb
abAa
Line Currents
![Page 63: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/63.jpg)
63
23.9 - ∆-Connected Generator with a Y-Connected Load
![Page 64: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/64.jpg)
64
EXAMPLE 4
• A balanced Y-connected load with a phase impedance 40 + j25 is supplied by a balanced, positive-sequence Δ-connected source with a line voltage of 210 V. Calculate the phase currents. Use VAB as reference.
![Page 65: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/65.jpg)
65
Solution:
• the load impedance, ZY and the source voltage, VAB are
V 0210V
3217.47 j2540Z
AB
Y
![Page 66: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/66.jpg)
66
Solution:
• When the ∆-connected source is transformed to a Y-connected source,
V 30-121.2
3013
0210
303
VV AB
an
![Page 67: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/67.jpg)
67
Solution:
• The line currents are
A 582.57120II
A 182-2.57120II
A 62-2.573247.17
03121.2
Z
VI
AaCc
AaBb
Y
anAa
![Page 68: 1 ELECTRICAL CIRCUIT ET 201 Become familiar with the operation of a three phase generator and the magnitude and phase relationship. Be able to calculate](https://reader030.vdocuments.site/reader030/viewer/2022032709/56649ec95503460f94bd7095/html5/thumbnails/68.jpg)
68
Summary of Relationships in Y and ∆-connections
Y-connection ∆-connection
Voltage magnitudes
Current magnitudes
Phase sequence
VL leads Vφ by 30° IL lags Iφ by 30°
φV3VL φVVL
φI3IL φIIL