PROJECT TEAM
PROJECT NAME
PROJECT ADDRESS
© 2018 Kirksey
KIRKSEY PROJECT NO.
RENDERING FOR ARTISTIC REPRESENTATION ONLY
1/9
/20
19
4:3
9:1
2 P
MC
:\U
se
rs\m
ich
ae
ll\D
ocum
en
ts\A
RC
H_
20
17
18
7_
CO
MM
ON
S_B
LD
G_
mic
ha
ell.
rvt
PERMIT & BIDJAN 09 2019
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
St. Anne Catholic Community2140 Westheimer Road
Macdonald Engineering, LLCCIVIL ENGINEER
Walter P Moore1301 McKinney, Suite 1100
ME Engineers, Inc.MEP ENGINEER
Commons & Parking Garage
*
OWNER
1604 Woodhead Street
STRUCTURAL ENGINEER
4550 Post Oak Place, Suite 334
Kudela & WeinheimerLANDSCAPE ARCHITECT
7155 Old Katy Road
SLR ConsultingACOUSTIC ENGINEER
6001 Savoy Drive, Suite 215
Houston, Texas 77098
www.saintanne.org
Houston, Texas 77019
macdonaldengineering.com
Houston, Texas 77010
walterpmoore.com
Houston, Texas 77027
me-engineers.com
Houston, Texas 77024
kwtexas.com
Houston, Texas 77036
slrconsulting.com
SACC - COMMONS BLDG & GARAGE
REG
IS
TERED ARCHITECT
STATE OF TEXAS
JA
NIS BRACKETT
17459
09 JANUARY 2019
F
FA FIRE ALARM
FC FIRE CODE
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER, BRACKET
FEC FIRE EXTINGUISHER, CABINET
FG ENTRANCE FLOOR GRILLES
FH FIRE HYDRANT
FIN FINISH/FINISHED
FIXT FIXTURE
FLRG FLOORING
FLR FLOOR
FLSHG FLASHING
F.P.W. FLOOD PROTECTION WALL
FL FLOW LINE
FM FACTORY MUTUAL
FND FOUNDATION
FR GL FRITTED GLASS
FRP FIBER REINFORCED PLASTIC
FRPF FIREPROOF(ING)
FSEC FOOD SERVICE EQUIPMENT CONTRACTOR
FS FULL SIZE
FTG FOOTING
FT FOOT (FEET)
FURN FURNISH
FURR FURRED/FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALL COVERING
FWP FABRIC WRAPPED WALL PANELS
GGALV GALVANIZED
GAL GALLON
GA GAUGE
GC GENERAL CONTRACTOR
GD GUARD
GEN GENERAL
GF GLASS FILM
GI GALVANIZED IRON
GL GLASS, GLAZING
GL BLK GLASS BLOCK
GMP GUARANTEED MAXIMUM PRICE
GR GRADE, GRADING
GRP GRAVEL
GRT GROUT
GSF GLAZING SURFACE FILM
GSF GROSS SQUARE FOOT
GYP GYPSUM
HHB HOSE BIBB
HC HOLLOW CORE
HDCP HANDICAPPED
HDWR HARDWARE
HD HEAD
HFS HALF FULL SIZE
HLB HORIZONTAL LOUVER BLINDS
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HR HOUR
HT HEIGHT
HVAC HEATING/VENTILATING/
AIR CONDITIONING
HW HOT WATER
HYD HYDRANT
IID INSIDE DIAMETER
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
IN INCH
IPS INSIDE PIPE SIZE
JJAN JANITOR
JST JOIST
JT JOINT
LLAM LAMINATE(D)
LAV LAVATORY
LGTH LENGTH
LH LEFT HAND
LV LEVEL
LIN LINEAR
LL LIVE LOAD
LT LIGHT
LVR LOUVER
LWT LIGHTWEIGHT
MM METER
MM MILLIMETER
MACH MACHINE
MAINT MAINTENCE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEJ MASONRY EXPANSION JOINT
MEP MECHANICAL, ELECTRICAL
PLUMBING
MF METAL FINISHES
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOULDING
MO MASONRY OPENING
MR MOISTURE RESISTANT
MSV MANUFACTURED STONE VENEER
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MWP METAL WALL PANEL
NNIC NOT IN CONTRACT
NOM NOMINAL
NO. OR # NUMBER
NRA NET RENTABLE SQUARE FOOT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OOA OVERALL
OC ON CENTER(S)
OCD OVERHEAD COILING DOOR
OCG OVERHEAD COILING GRILLES
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED/
CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED/
OWNER INSTALLED
OH OVERHEAD
OP OPERABLE PARTITION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
O.S. OVERFLOW SCUPPER
O/A OUTSIDE AIR
P
PAC ARCHITECTURAL PRECAST CONCRETE
PART PARTITION
PC POLISHED CONCRETE
PCF POUNDS PER CUBIC FOOT
PDP PREFINISHED DECORATIVE
PANELS
PERF PERFORATED
PLAST PLASTER
PLAS PLASTIC
PLBG PLUMBING
PLWD PLYWOOD
PNL PANEL
POL POLISHED
PRKG PARKING
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PTD PAINTED
PTS PAINTED
PVC POLYVINYL CHLORIDE
PVG PAVING
PVMT PAVEMENT
P.L. PROPERTY LINE
PL PLASTIC LAMINATE
P/C PRECAST
PFP PREFINISHED PANEL
QQT QUARRY TILE
RR RISER
RAD RADIUS
RBA RESILIENT BASE AND ACCESSORY
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING BAR
RECEPT RECEPTION
RECEP RECEPTACLE
RECOM RECOMMENDATION
REC RECESSED
REG REGULATION
REINF REINFORCED
REQD REQUIRED
RET RETURN
REV REVISION
RE REFER TO
RF RESINOUS FLOORING
RFG ROOFING
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RS ROLLER SHADE
RSF RESILIENT SHEET FLOORING
RSF RENTABLE SQUARE FOOT
RTF RESILIENT TILE FLOORING
R/AG RETURN AIR GRILLE
R/A RETURN AIR
S
SAWU SOUND ABSORBING WALL UNITS
SCHED SCHEDULE(D)
SC STAINED CONCRETE
SECT SECTION
SF SQUARE FEET
SHLV SHELVES/SHELVING
SHTHG SHEATHING
SHT SHEET
SIM SIMILAR
SKY SKYLIGHT
SMV STONE MASONRY VENEER
SPEC SPECIFICATION
SQ SQUARE
SS SOILD SURFACE
SSTL STAINLESS STEEL
STA STATION
STAB STABILIZE(D)
STC SOUND TRANSMISSION
COEFFICIENT
STC STONE COUNTERTOP
STF STONE FACING
STL STEEL
STOR STORAGE
STRUCT STRUCTURE/STRUCTURAL
SUSP SUSPENDED
SW SWITCH
S/AD SUPPLY AIR DIFFUSER
TT TREAD
TA TOILET ACCESSORY
TCOC TEXTURE COATING ON CONCRETE
TC TRAFFIC COATING
TEL TELEPHONE
TEMP TEMPERED
THK THICK(NESS)
THRES THRESHOLD
TKBD TACK BOARD
T.O. TOP OF
TOS TOP OF STEEL
TOSS TOP OF STRUCTURAL SLAB
TR TRIM (METAL EDGE TRIM)
TRANS TRANSFORMER
TS TUBE STEEL
TTC TELEPHONE TERMINAL CABINET
TUC TILT-UP CONCRETE
TV TELEVISION
TYP TYPICAL
UUL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPH UPHOLSTERY
UR URINAL
VVAC VACUUM
VERT VERTICAL
VEST VESTIBULE
VLB VERTICAL LOUVER BLINDS
WWC WALL COVERING
WCD WALL COVERING - DRY ERASE
WDW WINDOW
WD WOOD
WDV WOOD VENEER
WF WIDE FLANGE
WFA WOOD ATHLETIC FLOORING
WFE ENGINEERED WOOD PLANK FLOORINGWH WALL HUNG
WI WROUGHT IRON
WP WALL PROTECTION
WR WATER REPELLENTS
WWF WELDED WIRE FRABIC
W.P. WORK POINT
W/I WITHIN
W/O WITHOUT
W/ WITH
XXFMR TRANSFORMER
AAB ANCHOR BOLT
AC ACOUSTICAL SEALANT
ACC ARCHITECTURAL CAST IN PLACE
CONCRETE
ACM ALUMINUM COMPOSITE METAL
ACOUS ACOUSTICAL
ADJUST ADJUSTABLE
ADJ ADJACENT
AD ACCESS DOOR
AF ACCESS FLOORING
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANG ANGLE
ANOD ANODIZED
APPROX APPROXIMATELY
APC ACOUSTICAL PANEL CEILING
ARCH ARCHITECT/ARCHITECTURAL
ASPH ASPHALT
ATC ACRYLIC TEXTURED COATING
ATN ATTENUATION/ATTENUATING
AUTO AUTOMATIC
AUX AUXILIARY
AVE AVENUE
AVG AVERAGE
A/C AIR CONDITIONING
A/V AUDIO VISUAL
BB BASE
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BLK BLOCK
BM BEAM
BOT BOTTOM
B.O. BOTTOM OF
BR BICYCLE RACK
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BTW BETWEEN
B&B BALLED & BUR LAPPED
B-B BACK TO BACK
B.M. BENCH MARK
B/F BOTH FACES
CCAB CABINET
CB CATCH BASIN
CCTV CLOSED CIRCUIT TELEVISION
CEM CEMENT
CER CERAMIC
CFMF COLD FORMED METAL FRAMING
CFT CORK FLOOR TILE
CIP CAST IN PLACE CONCRETE
CJ CONTROL JOINT
CKBD CHALKBOARD
CLG CEILING
CLR CLEAR(ANCE)
CL CLOSET
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
COL COLUMN
COMPRESS COMPRESSIBLE
COMP COMPOSITION
CONC CONCRETE
COND CONDITION
CONF CONFERENCE
CONST CONSTRUCTION
CONTR CONTRACTOR
CONT CONTINUOUS
CORRU CORRUGATED
CORR CORRIDOR
CPS CARPET SHEET
CPT CARPET TILE
CSM CAST STONE MASONRY
CSMT CASEMENT
CTR CENTER
CTSK COUNTERSUNK
CU FT CUBIC FOOT (FEET)
CU YD CUBIC YARD
CW COLD/CHILLED WATER
C-C CENTER TO CENTER
C.O. CASED OPENING
D
D DEEP/DEPTH
DBL DOUBLE
DEFL DEFLECTION
DEFS DECORATIVE EXTERIOR FINISH
DF DRINKING FOUNTAIN
DGL DECORATIVE GLASS
DIAG DIAGONAL
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DISP DISPENSER
DL DEAD LOAD
DN DOWN
DR DOOR
DS DOWNSPOUT
DSC DIMENSIONAL STONE CLADDING
DTL DETAIL
DWG(S) DRAWING(S)
EEA EACH
EFOB EXTERIOR FACE OF BUILDING
EJ EXPANSION JOINT
ELAS ELASTIC (ELASTOMERIC)
ELEC ELECTRICAL
ELEV ELEVATOR
EL ELEVATION
ELAST ELASTOMERIC
EM ENTRANCE FLOOR MATS
EMER EMERGENCY
EP EXPLOSION PROOF
EQUIP EQUIPMENT
EQ EQUAL
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EW EACH WAY
EXH EXHAUST
EXIST EXISTING
EXPAN EXPANSION
EXP EXPOSED
EXT EXTERIOR
S.### SHEET NOTE - SITE
P.###
SHEET NOTE - FLOOR PLAN
R.### SHEET NOTE - REFLECTED CEILING PLAN
PW.### SHEET NOTE - POWER PLAN
F.###
SHEET NOTE - FINISH PLAN
D.### SHEET NOTE - DEMO PLAN
FN.### SHEET NOTE - FURNITURE PLAN
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
These drawings have been prepared as one coordinated set of drawings and are complimentary. What is required by one drawing is required by all of the drawings, even if a detail or component part is not identified on every sheet. Any user’s
reliance on a single or select few sheet(s) of the drawings without consideration for the information included in the entire set of drawings will be at the user’s sole risk and shall not form the basis for a request for additional compensation or time.
© 2018 Kirksey
1/9
/20
19
4:5
5:1
5 P
MC
:\U
se
rs\S
teven
\Do
cu
me
nts
\AR
CH
_2
01
71
87
_C
OM
MO
NS
_B
LD
G_
ste
ve
n@
kirksey.c
om
.rvt
A0.11
ABBREVIATIONS
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1 JAN 09 2019 PERMIT & BID
REG
IS
TERED ARCHITECT
STATE OF TEXAS
JA
NIS BRACKETT
17459
09 JANUARY 2019
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
These drawings have been prepared as one coordinated set of drawings and are complimentary. What is required by one drawing is required by all of the drawings, even if a detail or component part is not identified on every sheet. Any user’s
reliance on a single or select few sheet(s) of the drawings without consideration for the information included in the entire set of drawings will be at the user’s sole risk and shall not form the basis for a request for additional compensation or time.
1/9
/20
19
5:2
6:4
3 P
MC
:\U
se
rs\S
teven
\Do
cu
me
nts
\AR
CH
_2
01
71
87
_C
OM
MO
NS
_B
LD
G_
ste
ve
n@
kirksey.c
om
.rvt
A0.12
SHEET INDEX
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
© 2017 Kirksey
# SHEET NAME DATE REVISION
P6.00 PLUMBING DETAILS JAN 09 2019 PERMIT & BID
P6.01 PLUMBING DETAILS JAN 09 2019 PERMIT & BID
P7.00 PLUMBING SCHEDULES JAN 09 2019 PERMIT & BID
PLUMBING - COMMONS BLDG.
1-P2.00 PLUMBING LEVEL 1 UNDERFLOOR PLAN JAN 09 2019 PERMIT & BID
1-P2.01 PLUMBING LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
1-P2.02 PLUMBING LEVEL 2 MEZZANINE FLOOR PLAN JAN 09 2019 PERMIT & BID
1-P2.03 PLUMBING ROOF PLAN JAN 09 2019 PERMIT & BID
PLUMBING - GARAGE
2-P2.00 PLUMBING LEVEL 1 UNDERFLOOR PLAN JAN 09 2019 PERMIT & BID
2-P2.01 PLUMBING LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-P2.02 PLUMBING LEVEL 2 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-P2.03 PLUMBING LEVEL 3 FLOOR PLAN JAN 09 2019 PERMIT & BID
FIRE PROTECTION
FP0.00 FIRE PROTECTION LEGEND AND DETAILS JAN 09 2019 PERMIT & BID
FIRE PROTECTION - COMMONS BLDG.
1-FP2.01 FIRE PROTECTION LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
1-FP2.02 FIRE PROTECTION LEVEL 2 MEZZANINE FLOOR PLAN JAN 09 2019 PERMIT & BID
FIRE PROTECTION - GARAGE
2-FP2.01 FIRE PROTECTION LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-FP2.02 FIRE PROTECTION MEZZANINE FLOOR PLAN JAN 09 2019 PERMIT & BID
2-FP2.03 FIRE PROTECTION LEVEL 2 FLOOR PLAN JAN 09 2019 PERMIT & BID
PARKING
PK1.00 PARKING LOT STRIPING SITE PLAN JAN 09 2019 PERMIT & BID
PK1.01 LEVEL 1 PAVEMENT MARKING PLAN JAN 09 2019 PERMIT & BID
PK1.02 LEVEL 2 PAVEMENT MARKING PLAN JAN 09 2019 PERMIT & BID
PK1.03 LEVEL 3 PAVEMENT MARKING PLAN JAN 09 2019 PERMIT & BID
PK1.20 PAVEMENT MARKING DETAILS JAN 09 2019 PERMIT & BID
PK2.01 LEVEL 1 GRAPHICS PROGRAMMING PLAN JAN 09 2019 PERMIT & BID
PK2.02 LEVEL 2 GRAPHICS PROGRAMMING PLAN JAN 09 2019 PERMIT & BID
PK2.03 LEVEL 3 GRAPHICS PROGRAMMING PLAN JAN 09 2019 PERMIT & BID
PK2.20 SIGNS & GRAPHICS SCHEDULE JAN 09 2019 PERMIT & BID
PK2.21 SIGN FACE DETAILS JAN 09 2019 PERMIT & BID
SIGNAGE
SG1.00 INTERIOR SIGNAGE TYPES JAN 09 2019 PERMIT & BID
TRAFFIC CONTROL
T1.0 KINGSTON ST. TRAFFIC CONTROL PLAN JAN 09 2019 PERMIT & BID
T1.1 SHEPHERD DR. TRAFFIC CONTROL PLAN JAN 09 2019 PERMIT & BID
# SHEET NAME DATE REVISION
2-A4.21 WALL SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A4.22 WALL SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A5.10 EXTERIOR PLAN DETAILS BLDG B JAN 09 2019 PERMIT & BID
2-A5.20 EXTERIOR SECTION DETAILS BLDG B JAN 09 2019 PERMIT & BID
2-A5.21 EXTERIOR SECTION DETAILS BLDG B JAN 09 2019 PERMIT & BID
2-A6.50 WINDOW TYPES AND GLAZING SCHEDULE BLDG B JAN 09 2019 PERMIT & BID
2-A7.10 STAIR PLANS AND SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A7.11 STAIR PLANS AND SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A7.23 STAIR DETAILS BLDG B JAN 09 2019 PERMIT & BID
2-A7.30 ELEVATOR PLANS AND SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A7.31 ELEVATOR DETAILS BLDG B JAN 09 2019 PERMIT & BID
2-A8.10 INTERIOR ELEVATIONS BLDG B JAN 09 2019 PERMIT & BID
ARCHITECTURAL
A6.10 DOOR & FRAME TYPES, DOOR SCHEDULE AND NOTES JAN 09 2019 PERMIT & BID
A6.30 DOOR HARDWARE SPECIFICATIONS JAN 09 2019 PERMIT & BID
A6.31 DOOR HARDWARE SPECIFICATION & SCHEDULE JAN 09 2019 PERMIT & BID
A6.61 PARTITION TYPES JAN 09 2019 PERMIT & BID
A6.62 PARTITION TYPES JAN 09 2019 PERMIT & BID
A9.20 INTERIOR SECTION DETAILS JAN 09 2019 PERMIT & BID
A9.21 INTERIOR SECTION DETAILS JAN 09 2019 PERMIT & BID
A10.10 MILLWORK (LEGEND & SCHEDULES) JAN 09 2019 PERMIT & BID
A10.11 MILLWORK JAN 09 2019 PERMIT & BID
A10.12 MILLWORK JAN 09 2019 PERMIT & BID
STRUCTURAL
S1.00 GENERAL NOTES JAN 09 2019 PERMIT & BID
S1.01 GENERAL NOTES JAN 09 2019 PERMIT & BID
S1.02 SYMBOLS AND NOTATIONS JAN 09 2019 PERMIT & BID
S1.10 CONCRETE COVER AND CONCRETE MATRIX JAN 09 2019 PERMIT & BID
S2.00 FOUNDATION AND LEVEL 1 FLOOR PLAN - COMMONS BUILDING JAN 09 2019 PERMIT & BID
S2.01 MEZZANINE LOW ROOF LEVEL - COMMONS BUILDING JAN 09 2019 PERMIT & BID
S2.02 ROOF PLAN - COMMONS BUILDING JAN 09 2019 PERMIT & BID
S2.10 FOUNDATION LEVEL 1 FLOOR PLAN - GARAGE JAN 09 2019 PERMIT & BID
S2.11 LEVEL 2 FLOOR PLAN - GARAGE JAN 09 2019 PERMIT & BID
S2.12 LEVEL 3 FLOOR PLAN - GARAGE JAN 09 2019 PERMIT & BID
S2.20 PARTIAL PLANS JAN 09 2019 PERMIT & BID
S2.30 ROOF UPLIFT PLAN JAN 09 2019 PERMIT & BID
S3.00 TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.10 FOUNDATION TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.11 FOUNDATION TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.12 FOUNDATION TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.20 PRECAST CONCRETE TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.30 STEEL FRAMING TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.31 STEEL FRAMING TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.32 STEEL FRAMING TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.40 MASONRY TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S3.41 MASONRY TYPICAL DETAILS JAN 09 2019 PERMIT & BID
S4.01 BUILDING SECTIONS AND DETAILS JAN 09 2019 PERMIT & BID
S4.02 BUILDING SECTIONS AND DETAILS JAN 09 2019 PERMIT & BID
S4.03 BUILDING SECTIONS AND DETAILS JAN 09 2019 PERMIT & BID
MECHANICAL
M0.00 MECHANICAL LEGEND JAN 09 2019 PERMIT & BID
M0.01 MECHANICAL GENERAL NOTES JAN 09 2019 PERMIT & BID
M1.00 MECHANICAL SITE PLAN JAN 09 2019 PERMIT & BID
M2.00 MECHANICAL SECTION VIEWS JAN 09 2019 PERMIT & BID
MECHANICAL
1-M2.01 MECHANICAL LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
1-M2.02 MECHANICAL LEVEL 2 MEZZANINEROOF FLOOR PLAN JAN 09 2019 PERMIT & BID
2-M2.01 MECHANICAL LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-M2.02 LEVEL 2 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-M2.03 MECHANICAL LEVEL 3 FLOOR PLAN JAN 09 2019 PERMIT & BID
M6.00 MECHANICAL CONTROL DIAGRAM JAN 09 2019 PERMIT & BID
M6.01 MECHANICAL CONTROL DIAGRAM JAN 09 2019 PERMIT & BID
M6.02 MECHANICAL CONTROL DIAGRAM JAN 09 2019 PERMIT & BID
M7.00 MECHANICAL DETAILS JAN 09 2019 PERMIT & BID
M7.01 MECHANICAL DETAILS JAN 09 2019 PERMIT & BID
M7.02 MECHANICAL CODE COMPLIANCE JAN 09 2019 PERMIT & BID
M8.00 MECHANICAL SCHEDULES JAN 09 2019 PERMIT & BID
M8.01 MECHANICAL SCHEDULES JAN 09 2019 PERMIT & BID
ELECTRICAL
1-E0.01 ELECTRICAL ONE-LINE DIAGRAM & PANEL SCHEDULES JAN 09 2019 PERMIT & BID
1-E0.02 ELECTRICAL LIGHTING CONTROL SCHEDULE & CODE COMPLIANCE JAN 09 2019 PERMIT & BID
1-E5.00 ELECTRICAL SCHEDULES JAN 09 2019 PERMIT & BID
2-E0.01 ELECTRICAL ONE-LINE DIAGRAM & PANEL SCHEDULES JAN 09 2019 PERMIT & BID
2-E0.02 ELECTRICAL LIGHTING CONTROL SCHEDULE & CODE COMPLIANCE JAN 09 2019 PERMIT & BID
2-E4.00 ELECTRICAL ENLARGED PLANS JAN 09 2019 PERMIT & BID
2-E5.00 ELECTRICAL SCHEDULES JAN 09 2019 PERMIT & BID
E0.00 ELECTRICAL LEGEND JAN 09 2019 PERMIT & BID
E1.00 ELECTRICAL SITE PLAN JAN 09 2019 PERMIT & BID
E1.01 ELECTRICAL COMMONS AND GARAGE OVERALL PLAN JAN 09 2019 PERMIT & BID
E5.00 ELECTRICAL DETAILS JAN 09 2019 PERMIT & BID
E6.00 ELECTRICAL DETAILS JAN 09 2019 PERMIT & BID
E6.01 ELECTRICAL DETAILS JAN 09 2019 PERMIT & BID
ELECTRICAL - COMMONS BLDG.
1-E2.01 ELECTRICAL LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
1-E2.02 ELECTRICAL LEVEL 2 MEZZANINE FLOOR PLAN JAN 09 2019 PERMIT & BID
1-E3.01 ELECTRICAL LIGHTING LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
1-E3.02 ELECTRICAL LIGHTING LEVEL 2 MEZZANINE FLOOR PLAN JAN 09 2019 PERMIT & BID
ELECTRICAL - GARAGE
2-E2.01 ELECTRICAL LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-E2.02 ELECTRICAL LEVEL 2 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-E2.03 ELECTRICAL LEVEL 3 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-E3.01 ELECTRICAL LIGHTING LEVEL 1 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-E3.02 ELECTRICAL LIGHTING LEVEL 2 FLOOR PLAN JAN 09 2019 PERMIT & BID
2-E3.03 ELECTRICAL LIGHTING LEVEL 3 FLOOR PLAN JAN 09 2019 PERMIT & BID
PLUMBING
P0.00 PLUMBING LEGEND JAN 09 2019 PERMIT & BID
P4.00 PLUMBING ENLARGED PLANS JAN 09 2019 PERMIT & BID
P5.00 PLUMBING ISOMETRICS JAN 09 2019 PERMIT & BID
P5.01 PLUMBING ISOMETRICS JAN 09 2019 PERMIT & BID
P5.02 PLUMBING ISOMETRICS JAN 09 2019 PERMIT & BID
# SHEET NAME DATE REVISION
GENERAL
A0.00 TITLE SHEET JAN 09 2019 PERMIT & BID
A0.10 GRAPHIC STANDARDS JAN 09 2019 PERMIT & BID
A0.11 ABBREVIATIONS JAN 09 2019 PERMIT & BID
A0.12 SHEET INDEX JAN 09 2019 PERMIT & BID
A0.20 CODE INFORMATION - COMMONS BLDG A JAN 09 2019 PERMIT & BID
A0.21 CODE INFORMATION - GARAGE & MINISTRY BLDG B JAN 09 2019 PERMIT & BID
A0.50 FIRE ASSEMBLY (PARTITIONS) JAN 09 2019 PERMIT & BID
A0.51 FIRE ASSEMBLY (PARTITIONS) JAN 09 2019 PERMIT & BID
A0.60 REFERENCE (MOUNTING HEIGHTS) JAN 09 2019 PERMIT & BID
A0.61 REFERENCE (DOOR MANEUVERING CLEARANCES) JAN 09 2019 PERMIT & BID
A0.70 MASTER SCHEDULE JAN 09 2019 PERMIT & BID
A0.71 MASTER SCHEDULE JAN 09 2019 PERMIT & BID
GENERAL
1-A0.31 LIFE SAFETY PLAN LEVEL 1 BLDG A JAN 09 2019 PERMIT & BID
1-A0.32 LIFE SAFETY PLAN - EQUIPMENT LEVEL BLDG A JAN 09 2019 PERMIT & BID
2-A0.31 LIFE SAFETY PLAN - LEVEL 1 BLDG B JAN 09 2019 PERMIT & BID
2-A0.32 LIFE SAFETY PLAN - LEVEL 2 BLDG B JAN 09 2019 PERMIT & BID
2-A0.33 LIFE SAFETY PLAN - LEVEL 3 BLDG B JAN 09 2019 PERMIT & BID
CIVIL
C0.0 CIVIL OVERALL SITE PLAN JAN 09 2019 PERMIT & BID
C1.0 CIVIL SITE DEMOLITION PLAN JAN 09 2019 PERMIT & BID
C1.1 CIVIL SITE DEMOLITION PLAN JAN 09 2019 PERMIT & BID
C1.2 CIVIL SITE DEMOLITION PLAN JAN 09 2019 PERMIT & BID
C1.3 CIVIL SITE DEMOLITION PLAN JAN 09 2019 PERMIT & BID
C2.0 CIVIL SITE LAYOUT PLAN JAN 09 2019 PERMIT & BID
C2.1 CIVIL SITE LAYOUT PLAN JAN 09 2019 PERMIT & BID
C2.2 CIVIL SITE LAYOUT PLAN JAN 09 2019 PERMIT & BID
C2.3 CIVIL SITE LAYOUT PLAN JAN 09 2019 PERMIT & BID
C3.0 CIVIL SITE GRADING PLAN JAN 09 2019 PERMIT & BID
C3.1 CIVIL SITE GRADING PLAN JAN 09 2019 PERMIT & BID
C3.2 CIVIL SITE GRADING PLAN JAN 09 2019 PERMIT & BID
C3.3 CIVIL SITE GRADING PLAN JAN 09 2019 PERMIT & BID
C4.0 CIVIL SITE UTILITY PLAN JAN 09 2019 PERMIT & BID
C4.1 CIVIL SITE UTILITY PLAN JAN 09 2019 PERMIT & BID
C4.2 CIVIL SITE UTILITY PLAN JAN 09 2019 PERMIT & BID
C4.3 CIVIL SITE UTILITY PLAN JAN 09 2019 PERMIT & BID
C5.0 CIVIL GENERAL NOTES JAN 09 2019 PERMIT & BID
C5.1 CIVIL DETAILS JAN 09 2019 PERMIT & BID
C5.2 CIVIL DETAILS JAN 09 2019 PERMIT & BID
C5.3 CIVIL DETAILS SWQMP DETAILS JAN 09 2019 PERMIT & BID
C5.4 CIVIL DETAILS JAN 09 2019 PERMIT & BID
C6.0 CIVIL SWPPP JAN 09 2019 PERMIT & BID
C6.1 CIVIL SWPPP DETAILS JAN 09 2019 PERMIT & BID
C7.0 CIVIL SITE DRAINAGE AREA MAP JAN 09 2019 PERMIT & BID
C7.1 CIVIL SITE DRAINAGE AREA CALCULATIONS JAN 09 2019 PERMIT & BID
C8.0 CIVIL SWQMP JAN 09 2019 PERMIT & BID
LANDSCAPE
L1.01 LANDSCAPE MATERIALS PLAN JAN 09 2019 PERMIT & BID
L1.02 LANDSCAPE MATERIALS PLAN JAN 09 2019 PERMIT & BID
L1.03 LANDSCAPE MATERIALS PLAN JAN 09 2019 PERMIT & BID
L2.01 CONSTRUCTION DETAIL JAN 09 2019 PERMIT & BID
L2.02 CONSTRUCTION DETAIL JAN 09 2019 PERMIT & BID
L2.03 CONSTRUCTION DETAIL JAN 09 2019 PERMIT & BID
L3.01 LANDSCAPE PLAN JAN 09 2019 PERMIT & BID
L3.02 LANDSCAPE PLAN JAN 09 2019 PERMIT & BID
L3.03 LANDSCAPE PLAN AND DETAILS JAN 09 2019 PERMIT & BID
L3.04 LANDSCAPE PLAN AND DETAILS JAN 09 2019 PERMIT & BID
ARCHITECTURAL - COMMONS BLDG
1-A1.20 OVERALL SITE PLAN JAN 09 2019 PERMIT & BID
1-A2.31 FLOOR PLAN LEVEL 1 BLDG A JAN 09 2019 PERMIT & BID
1-A2.32 FLOOR PLAN EQUIPMENT LEVEL BLDG A JAN 09 2019 PERMIT & BID
1-A2.33 ROOF PLAN BLDG A JAN 09 2019 PERMIT & BID
1-A2.41 REFLECTED CEILING PLAN LEVEL 1 AND EQUIPMENT LEVEL BLDG A JAN 09 2019 PERMIT & BID
1-A2.61 FINISH PLAN BLDG A JAN 09 2019 PERMIT & BID
1-A2.70 ENLARGED PLANS BLDG A JAN 09 2019 PERMIT & BID
1-A2.80 RESTROOM PLANS BLDG A JAN 09 2019 PERMIT & BID
1-A2.81 RESTROOM PLANS BLDG A JAN 09 2019 PERMIT & BID
1-A2.82 RESTROOM PLANS BLDG A JAN 09 2019 PERMIT & BID
1-A2.83 RESTROOM PLANS BLDG A JAN 09 2019 PERMIT & BID
1-A3.10 ELEVATIONS BLDG A JAN 09 2019 PERMIT & BID
1-A3.11 ELEVATIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.10 BUILDING SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.11 BUILDING SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.20 WALL SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.21 WALL SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.22 WALL SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A4.23 WALL SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A5.10 EXTERIOR PLAN DETAILS BLDG A JAN 09 2019 PERMIT & BID
1-A5.20 EXTERIOR SECTION DETAILS BLDG A JAN 09 2019 PERMIT & BID
1-A5.21 EXTERIOR SECTION DETAILS BLDG A JAN 09 2019 PERMIT & BID
1-A5.30 ROOF DETAILS BLDG A JAN 09 2019 PERMIT & BID
1-A6.50 WINDOW TYPES AND GLAZING SCHEDULE BLDG A JAN 09 2019 PERMIT & BID
1-A7.10 STAIR PLANS AND SECTIONS BLDG A JAN 09 2019 PERMIT & BID
1-A7.20 STAIR DETAILS BLDG A JAN 09 2019 PERMIT & BID
1-A8.10 INTERIOR ELEVATIONS BLDG A JAN 09 2019 PERMIT & BID
1-A8.11 INTERIOR ELEVATIONS BLDG A JAN 09 2019 PERMIT & BID
1-A8.12 INTERIOR ELEVATIONS BLDG A JAN 09 2019 PERMIT & BID
1-A9.10 INTERIOR PLAN DETAILS BLDG A JAN 09 2019 PERMIT & BID
ARCHITECTURAL - GARAGE
2-A1.40 SITE CANOPIES PLANS & DETAILS JAN 09 2019 PERMIT & BID
2-A2.31 FLOOR PLAN LEVEL 1 BLDG B JAN 09 2019 PERMIT & BID
2-A2.32 FLOOR PLAN LEVEL 2 BLDG B JAN 09 2019 PERMIT & BID
2-A2.33 FLOOR PLAN LEVEL 3 BLDG B JAN 09 2019 PERMIT & BID
2-A2.41 REFLECTED CEILING PLAN LEVEL 1 BLDG B JAN 09 2019 PERMIT & BID
2-A2.42 REFLECTED CEILING PLAN LEVEL 2 BLDG B JAN 09 2019 PERMIT & BID
2-A2.43 REFLECTED CEILING PLAN LEVEL 3 BLDG B JAN 09 2019 PERMIT & BID
2-A2.61 FINISH PLAN LEVEL 1 BLDG B JAN 09 2019 PERMIT & BID
2-A2.70 ENLARGED FLOOR PLANS BLDG B JAN 09 2019 PERMIT & BID
2-A2.71 ENLARGED RCP & FINISH PLAN BLDG B JAN 09 2019 PERMIT & BID
2-A2.80 RESTROOM PLANS BLDG B JAN 09 2019 PERMIT & BID
2-A3.10 EXTERIOR ELEVATIONS BLDG B JAN 09 2019 PERMIT & BID
2-A3.11 EXTERIOR ELEVATIONS BLDG B JAN 09 2019 PERMIT & BID
2-A4.10 BUILDING SECTIONS BLDG B JAN 09 2019 PERMIT & BID
2-A4.20 WALL SECTIONS BLDG B JAN 09 2019 PERMIT & BID
1 JAN 09 2019 PERMIT & BID
REG
IS
TERED ARCHITECT
STATE OF TEXAS
JA
NIS BRACKETT
17459
09 JANUARY 2019
DUCTWORK
DUCT MOUNTED SMOKE DETECTOR
FIRE DAMPER
SMOKE DAMPER
FIRE/SMOKE DAMPER
MOTORIZED DAMPER
BACKDRAFT DAMPER
TRANSITION:RECTANGULAR TO ROUND
ROUND DUCT UP
CONICAL TAP
RECTANGULAR BRANCH TAP
SECTION NO.
SECTION VIEW SHEET NO.
DETAIL DESIGNATION
POWERED EQUIPMENT DESIGNATION
NON POWERED EQUIPMENT DESIGNATION
BASEBOARD EQUIPMENT DESIGNATION
SHEET KEY NOTES
INDICATES TYPE OF EQUIPMENT
INDICATES UNIT NUMBER WITHIN AREA
BUILDING
C - COMMONSG - GARAGE
PIPING SYMBOLS
PRESSURE/TEMPERATURE PORT TAPS
CONCENTRIC REDUCER
ECCENTRIC REDUCER
EXPANSION JOINT
THERMOMETER W/ THERMOWELL
UNION
AIR VENT
FLEXIBLE PIPE CONNECTOR
FLOW SWITCH
PRESSURE SWITCH
P&T
CR
ER
EJ
U
T
FS
PS
AV
FC
PRESSURE GAUGE W/ GAUGE COCK
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
ISOLATION VALVE, RE: SPECS
PG
IV
OUTSIDE STEM AND YOKE
OS&Y
DRAIN VALVE W/ HOSE END CONNECTION
DV
PIPE CAP OR PLUG
ABBREVIATIONSYMBOL DESCRIPTION
BALL VALVE W/ HOSE CONNECTION
CHECK VALVE WITH INDICATION OF FLOW DIRECTION
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE W/ TEST PORTS
CIRCUIT SETTER OR BALANCING VALVE
GLOBE VALVE (STRAIGHT PATTERN)
GLOBE VALVE (ANGLE PATTERN)
BUTTERFLY VALVE
CV
PRV
FCV
GLV
BFV
CS,BV
GLV
BALL VALVE
AUTOMATIC TEMPERATURE CONTROL VALVE, 2-WAY
AUTOMATIC TEMPERATURE CONTROL VALVE, 3-WAY
BALANCING VALVE
TEMPERATURE/PRESSURE RELIEF VALVE
STRAINER W/ BLOW-OFF & CAPPED HOSE END CONNECTION
BV
TCV
TCV
BV
TMP
STR
STEAM TRAPST
VALVE IN RISER
PIPING TYPES
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSATE DRAIN
HIGH PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM SUPPLY
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
D
HPS
HIGH PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE CONDENSATE RETURN
LOW PRESSURE CONDENSATE RETURN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
CONTROL AIR (PNEUMATIC)
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
D
HPS
HPRHPR
MPRMPR
LPRLPR
RSRS
RLRL
AA
BOILER BLOW DOWN
BDBD
BOILER FEEDBFBF
BLOW OFFBOBO
CHEMICAL FEEDER
CFCF
PROCESS COOLING WATER SUPPLY/RETURN
PCS/RPCS/R
HIGH TEMP. HOT WATER SUPPLY/RETURN
HTWS/RHTWS/R
PRIMARY OR DISTRICT HEATING WATER SUPPLY/RETURN
PHWS/RPHWS/R
PRIMARY OR DISTRICT CHILLED WATER SUPPLY/RETURN
PCHS/RPCHS/R
PUMPED CONDENSATE RETURN
PRPR
EXISTING PIPING(E)(E)
EXISTING PIPING TO BE REMOVED
(E)(E)
REFRIGERANT HOT GAS
RHGRHG
SINGLE LINE PIPING(UP TO 2")
DOUBLE LINE PIPING(2" AND ABOVE)
PIPETYPE
MISCELLANEOUS
SUPPLY DIFFUSER-4-WAY THROW
SUPPLY DIFFUSER-3-WAY THROW
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
UC
POINT OF DISCONNECTION
UNDERCUT DOOR (UNDER ARCH. SECTION)
D/L DOOR LOUVER (UNDER ARCH. SECTION)
L/DLOUVER DOOR FULL HEIGHT. (UNDER ARCH. SECTION)
ARROW INDICATES DIRECTION OF FLOWEXTERIOR WALL LOUVER (UNDER ARCH. SECTION)
SUPPLY DIFFUSER-2-WAY THROW
SUPPLY DIFFUSER-1-WAY THROW
EQUIPMENT DESIGNATION
POINT OF CONN. (CONN. NEW TO EXISTING)
(QTY)
DIFFUSER TYPE
SUPPLY DIFFUSER
ROUND DUCT DOWN
SUPPLY OR OUTSIDE AIR DOWN
NEW DUCTWORK
20"x16"
DUCT DIMENSIONS (WIDTH x HEIGHT)
TURNING VANES
SPLITTER DAMPER
TRANSITION-RECT. TO RECT. OR
ROUND TO ROUND
CONICAL SPIN-IN FITTING W/
MANUAL VOLUME DAMPER
LOW PRESSURE FLEXIBLE DUCT
SUPPLY SLOT DIFFUSER
UP DN
RETURN DIFFUSER
RISE IN DIRECTION OF
AIRFLOWRETURN OR RELIEF AIR UP
EXHAUST AIR UP EXHAUST DIFFUSER
DROP IN DIRECTION OF AIRFLOW
RETURN OR RELIEF AIR DN
EXHAUST AIR DN
FITTINGS:
EJ
FS
PS
SSV SOLENOID VALVE
FC
F
S
F/S
M
B
1
A101
SIM
A
M1-01
AHU
1.01
VAV
1.01
TYPE
LENGTH
12"
AHU
C-1
S
ASIZE
CFM
EXHAUST DIFFUSER
RETURN DIFFUSER
H
CEILING ACCESS PANEL
FLEXIBLE DUCT CONNECTION
HUMIDIFIER
RETURN/EXHAUST AIR FLOW SYMBOL
SUPPLY AIR FLOW SYMBOL
HEAT TRACE
EXISTING DIFFUSER
EXISTING DUCTWORK TO BE REMOVED
EXISTING DUCTWORK
A AIR (COMPRESSED)ABV ABOVEA/C AIR CONDITIONINGAC ALTERNATING CURRENT
AIR COMPRESSORACCH AIR COOLED CHILLERACCU AIR COOLED CONDENSING UNITAD ACCESS DOOR
AREA DRAINADJ ADJUSTABLEAF AIR FILTERAFC ABOVE FINISHED CEILINGAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNITAL ALUMINUMAMB AMBIENTAP ACCESS PANELAPD AIR PRESSURE DROPARI AMERICAN REFRIGERANT INSTITUTEARCH ARCHITECTAS AIR SEPARATORASHRAE AMERICAN SOCIETY OF HEATING AND REFRIGERATION ENGINEERSASME AMERICAN SOCIETY OF MECHANICAL ENGINEERSASTM AMERICAN SOCIETY OF TESTING AND MATERIALSAV ACID VENT
AIR VENTAVG AVERAGEAW ACID WASTEAWS AMERICAN WELDING SOCIETYAUX AUXILIARY
B BOILERBC BELOW COUNTERB/C BACK OF CURBBFV BUTTERFLY VALVEBH BOX HYDRANTBHP BRAKE HORSEPOWERBLDG BUILDINGBM BENCHMARKBOD BOTTOM OF DUCT (AFF)BOF BOTTOM OF FOOTINGBOS BOTTOM OF STRUCTUREBT BATH TUB
BREAK TANKBTU BRITISH THERMAL UNITBV BALL VALVEBWV BACK WATER VALVE
C CELSIUSCAB CABINETCAV CONSTANT AIR VOLUMECB CATCH BASINCC COOLING COILCD CONDENSATE DRAIN LINECFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECFS CUBIC FEET PER SECONDCI CAST IRONCIRC CIRCULATINGCL CENTERLINECLG CEILINGCLR CLEARCMP CORRIGATED METAL PIPECMU CONCRETE MASONRY UNITCPI CAST IRON PIPE INSTITUTECPVC CHLORINATED POLYVINYL CHLORIDECO CLEANOUTCOL COLUMNCOMB COMBINATIONCOMP COMPRESSORCON CONVERTERCONC CONCRETE
CONCENTRICCOND CONDENSER
CONDENSATECONN CONNECTIONCONT CONTINUOUS
CONTINUATIONCONTR CONTROLLER
CONTRACTORCOP COEFFICIENT OF PERFORMANCECRAC COMPUTER ROOM A/C UNITCRT CATHODE RAY TUBECRU CONDENSATE RETURN UNITCT COOLING TOWERCTR CENTERCU COPPERCW COLD WATERCWP CONDENSER WATER PUMPCWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLYCV CONSTANT VOLUME
dB DECIBELDB DRY-BULBDC DOUBLE DUCT CONSTANT VOLUME
DIRECT CURRENTDDC DIRECT DIGITAL CONTROLDESIG DESIGNATIONDEFL DEFLECTIONDTL DETAILDF DRINKING FOUNTAINDIA DIAMETERDIFF DIFFUSERDIM DIMENSIONDISC DISCONNECTDN DOWNDP DISCHARGE PLENUMDPR DAMPERDS DOUNSPOUT
DOUBLE SUCTIONDV DOUBLE DUCT VAVDW DISHWASHERDWG DRAWINGDWH DOMESTIC WATER HEATERDWP DOMESTIC WATER PUMPDX DIRECT EXPANSION
(E) EXISTINGEA EACHEAT ENTERING AIR TEMPERATUREEC ELECTRICAL CONTRACTORECC ECCENTRICEDB ENTERING DRY BULBEDF ELECTRIC DRINKING FOUNTAINEDH ELECTRIC DUCT HEATER
EDR EFFECTIVE DIRECT RADIATIONEER ENERGY EFFICIENCY RATIOEF EXHAUST FANEFF EFFICIENCYEJ EXPANSION JOINTEL ELEVATIONEMRG EMERGENCYENCL ENCLOSUREENGR ENGINEERENT ENTERINGES END SUCTION
EMERGENCY SHOWERESP EXTERNAL STATIC PRESSUREET EXPANSION TANKETR EXISTING TO REMAINEVAP EVAPORATOREWB ENTERING WET BULBEWT ENTERING WATER TEMPERATUREEX EXPLOSION PROOFEXT EXTERNALEXTG EXISTING
F DEGREE FAHRENHEITFBO FURNISHED BY OTHERSFCO FLOOR CLEAN OUTFCS FLOOR CONTROL SWITCHFCU FAN COIL UNITFD FLOOR DRAIN
FIRE DAMPERFDS FIRE DEPARTMENT SIAMESEFDV FIRE DEPARTMENT VALVEFG FIBERGLASSFF FINAL FILTERFH FIRE HYDRANTFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFIXT FIXTUREFLA FULL LOAD AMPSFLEX FLEXIBLEFL FLOW LINESFLR FLOORFP FAN POWERED MIXING BOX
FIRE PUMPFPI FINS PER INCHFPM FEET PER MINUTEFRIC FRICTIONFRZR FREEZERFS FLOW SWITCH
FIRE SPRINKLERFSK FLOOR SINKFT FOOT
FEETFT WC FEET, WATER COLUMNFUT FUTURE
G GASGA GAUGEGAL GALLONGALV GALVANIZEDGC GENERAL CONTRACTORGLV GLOBE VALVEGND GROUNDGPD GALLONS PER DAYGPM GALLONS PER MINUTEGSH GRAND SENSIBLE HEATGV GATE VALVE
HB HOSE BIBBHC HEATING COILHD HEAD
HUB DRAINHF HUMIDIFIERHORIZ HORIZONTALHP HORSEPOWER
HALON PANELHPU HEAT PUMP UNITHKP HOUSEKEEPING PADHSC HORIZONTAL SPLIT CASEHSTAT HUMIDISTATHT HEIGHTHTG HEATINGHTR HEATERHU HUMIDIFIER SECTIONHW HOT WATERHWC HOT WATER CIRCULATORHWP HOT WATER PUMPHWR HOT WATER RETURNHWS HOT WATER SUPPLYHX HEAT EXCHANGERHZ HERTZ
ID INSIDE DIAMTERIE INVERT ELEVATIONIH INFRARED HEATERIN INCHIN WC INCH, WATER COLUMNINSUL INSULATIONINT INTERNAL
INTERIORIW INDIRECT WASTE
JB JUNCTION BOXJP JOCKEY PUMP
KEC KITCHEN EQUIPMENT CONTRACTORKO` KNOCKOUTKVA KILOVOLT AMPSKW KILOWATT
L LENGTHLAT LEAVING AIR TEMPERATURELAV LAVATORYLBS POUNDSLBS/HR POUNDS PER HOURLF LINEAR FEETLP LOW PRESSURELRA LOCKED ROTOR AMPSLVG LEAVINGLVL LEVELLWB LEAVING WET BULBLWCO LOW WATER CUT OFFLWT LEAVING WATER TEMPERATURE
MA MAKE-UP AIRMAT MIXED AIR TEMPERATUREMAX MAXIMUMMBH THOUSAND BTUHMC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCC MOTOR CONTROL CENTERMECH MECHANICALMFR MANUFACTURERMH MANHOLEMI MALLEABLE IRONMIN MINIMUMMOCP MAXIMUM OVER CURRENT PROTECTIONMP MEDIUM PRESSUREMS MOP SINKMTD MOUNTEDMTL METALMU MAKE-UPMUA MAKE-UP AIR UNITMVD MANUAL VOLUME DAMPER
(N) NEWNC NORMALLY CLOSEDNFP NATIONAL FIRE PROTECTION ASSOCIATIONNIC NOT IN CONTRACTNO NORMALLY OPENNO NUMBERNTS NOT TO SCALE
OA OUTSIDE AIROAF OUTSIDE AIR FANOAHU OUTSIDE AIR HANDLING UNITOBD OPPOSED BLADE DAMPEROC ON CENTEROD OUTSIDE DIAMETER
OVERFLOW DRAINOFCU OUTSIDE AIR FAN COIL UNITOPG OPENINGOS&Y OPEN STEM AND YOLK
P PUMPPLUMBING EQUIPMENT
PC PLUMBING CONTRACTORPCR PUMPED CONDENSATE RETURNPD PRESSURE DROP
PLANTER DRAINPF PRE-FILTERPH PHASE
POST HYDRANTPIV POST INDICATOR VALVEPLBG PLUMBINGPNEU PNEUMATICPNL PANELPNTH PENTHOUSEPP POLYPROPYLENEPPM PARTS PER MILLIONPRESS PRESSUREPRI PRIMARYPRS PRIMARY REDUCING STATIONPRV PRESSURE REDUCING VALVEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSIG POUNDS PER SQUARE INCH, GAUGEPT PLUMBING TRIMPV PLUG VALVEPVC POLYVINYL CHLORIDEPWL SOUND POWER LEVEL
QTY QUANTITY
(R) REMOVERELOCATE
RA RETURN AIRRAD REFRIGERATED AIR DRYERRAF RETURN AIR FANRAG RETURN AIR GRILLERAT RETURN AIR TEMPERATURERCP REFLECTED CEILING PLAN
REINFORCED CONCRETE PIPERD ROOF DRAINRE REFERENCE
REFERRECIRC RECIRCULATERED REDUCERREFR REFRIGERATORREG REGISTERREINF REINFORCINGREQD REQUIREDREV REVISION
REVISERF RETURN FANRH RELATIVE HUMIDITYRHG REFRIGERANT HOT GASRKVA RUNNING KILOVOLT AMPSRKW RUNNING KILOWATTSRL REFRIGERANT LIQUIDRLA RUNNING LOAD AMPSRM ROOM
REFRIGERANT MACHINERPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTIONRTU ROOFTOP UNITRV RELIEF VALVE
SA SUPPLY AIRSAF SUPPLY AIR FANSAG SUPPLY AIR GRILLESAN SANITARY SEWERSAR SUPPLY AIR REGISTERSCHED SCHEDULESCFM STANDARD AIR CUBIC FEET PER MINUTESCR SILICON CONTROLLED RECTIFIERSD STORM DRAINSE SEWAGE EJECTORSEC SECONDARYSECT SECTIONSENS SENSIBLESF SQUARE FEET
SFCS SPRINKLER FLOOR CONTROL STATIONSH SHOWERSHT SHEETSIM SIMILARSK SINKSKVA STARTING KILOVOLT AMPSSKW STARTING KILOWATTSSM SHEET METALSP STATIC PRESSURE
SUMP PUMPSPEC SPECIFICATIONSPR SPRINKLERSQ SQUARESS STAINLESS STEEL
SERVICE SINKSSD SUBSURFACE DRAINSSFU SANITARY SEWER FIXTURE UNITSSSSC SOLID STATE SPEED CONTROLSTD STANDARDSTL STEELSTR STRAINERSURF SURFACESUSP SUSPENDSV SANITARY VENTST SOUND TRAP
TC TEMPERATURE CONTROLTD TRENCH DRAINTDH TOTAL DYNAMIC HEADTF TRANSFER FANTG TRANSFER GRILLETH BLK THRUST BLOCKTOD TOP OF DUCT (AFF)TOP TOP OF PIPE (AFF)TP TRAP PRIMERTPD TRAP PRIMER DEVICETSP TOTAL STATIC PRESSURETSTAT THERMOSTATTYP TYPICAL
U URINALU/F UNDERFLOORU/S UNDERSLABUCD UNDERCUT DOORUG UNDERGROUNDUH UNIT HEATERUL UNDERWRITERS LABORATORIESUNO UNLESS NOTED OTHERWISEUTR UP THROUGH ROOF
V VOLT, VENTVA VOLT-AMPEREVAC VACUUMVAV VARIABLE AIR VOLUMEVB VALVE BOX
VACUUM BREAKERVCP VITRIFIED CLAY PIPEVD VOLUME DAMPERVEL VELOCITYVERT VERTICALVFD VARIABLE FREUENCY DRIVEVIB VALVE IN BOXVOV VALVE ON VERTICALVP VACUUM PUMPVR VARIABLE AIR VOLUME REHEATVSD VARIABLE SPEED DRIVEVTR VENT THROUGH ROOF
W WATT, WASTE, WIDTHW/ WITHW/O WITHOUTWB WETBULBWC WATER CLOSETWCO WALL CLEANOUTWF WATER FILTERWH WALL HYDRANTWM WATER METERWP WEATHERPROOFWPD WATER PRESSURE DROPWWF WELDED WIRE FABRICWT WATER TIGHT
WEIGHT
Y YARD HYDRANT
Z ZONE
ABBREVIATIONS:ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
B
A
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Y
Z
EXISTING THERMOSTAT
NEW THERMOSTAT
SPACE TEMPERATURE SENSOR
SPACE HUMIDISTAT
SPACE HUMIDITY SENSOR
SPACE PRESSURE SENSOR
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
(E)T
T
TS
H
HS
PS
CD
CO
NITROGEN DIOXIDE SENSOR ND
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 9
:33
:55
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M0.00
MECHANICAL LEGEND
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
01-09-2019
MECH SHEET LIST
SheetNumber Sheet Name
M0.00 MECHANICAL LEGEND
M0.01 MECHANICAL GENERAL NOTES
M1.00 MECHANICAL SITE PLAN
1-M2.01 MECHANICAL LEVEL 1 FLOOR PLAN
1-M2.02 MECHANICAL LEVEL 2 MEZZANINE/ROOF FLOOR PLAN
2-M2.01 MECHANICAL LEVEL 1 FLOOR PLAN
2-M2.02 MECHANICAL LEVEL 2 FLOOR PLAN
2-M2.03 MECHANICAL LEVEL 3 FLOOR PLAN
M2.00 MECHANICAL SECTION VIEWS
M6.00 MECHANICAL CONTROL DIAGRAM
M6.01 MECHANICAL CONTROL DIAGRAM
M6.02 MECHANICAL CONTROL DIAGRAM
M7.00 MECHANICAL DETAILS
M7.01 MECHANICAL DETAILS
M7.02 MECHANICAL CODE COMPLIANCE
M8.00 MECHANICAL SCHEDULES
M8.01 MECHANICAL SCHEDULES
GENERAL MECHANICAL CONTRACT REQUIREMENTS:
GENERAL:
1. UNLESS OTHERWISE NOTED, THE WORK DESCRIBED ON THE PLANS AND SPECIFICATIONS SHALL INCLUDE THE FURNISHING AND INSTALLATION OF ALL LABOR AND MATERIALS NECESSARY FOR COMPLETE AND OPERATIONAL HVAC, FIRE PROTECTION AND PLUMBING SYSTEMS. CONTRACTOR SHALL FURNISH THESE EVEN IF ITEMS REQUIRED TO ACHIEVE THIS (I.E. OFFSETS, ISOLATION AND BALANCING DEVICES, MAINTENANCE CLEARANCES, ETC.) ARE NOT SPECIFICALLY SHOWN.
2. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO THE ACTUAL CONDITIONS OF THE JOB.
3. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. THEY SHOW CERTAIN PHYSICAL RELATIONSHIPS WHICH MUST BE ESTABLISHED WITHIN THE DIVISION 21,22 AND 23 WORK AND ITS INTERFACE WITH OTHER WORK. ESTABLISHING THIS RELATIONSHIP IN THE FIELD IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR. THIS DIVISION SHALL COORDINATE ITS WORK WITH ALL DIVISIONS OF THE WORK AND ADJUST ITS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF THE PROJECT.
A. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING A BID TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT. NO EXTRAS WILL BE ALLOWED DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS.
B. CERTAIN SYSTEMS REQUIRE ENGINEERING OF INSTALLATION DETAILS BY CONTRACTOR. UNLESS FULLY DETAILED IN THE CONTRACT DOCUMENTS, SUCH ENGINEERING IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR.
C. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE WHERE CLEARANCES ARE LIMITED, AND WHERE INSTALLATION DRAWINGS OR SCHEMATICS, "CONSTRUCTION DRAWINGS", OR COORDINATION DRAWINGS MAY BE REQUIRED IN ACCORDANCE WITH, OR IN EXCESS OF, THOSE REQUIRED BY THE SPECIFICATIONS. THE CONTRACTOR SHALL PREPARE ALL SUCH COORDINATION DRAWINGS AS PART OF THE BASE CONTRACT. SUCH DRAWINGS MAY BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR RECORD AND COMMENT. ANY WORK INSTALLED WITHOUT APPROVED COORDINATION DRAWINGS IS DONE AT THE CONTRACTOR'S RISK.
4. THESE NOTES ONLY SUPPLEMENT, AND DO NOT REPLACE, THE SPECIFICATIONS.
5. DEFINITIONS AND TERMINOLOGY
A. THE DEFINITIONS OF DIVISION 1 AND THE GENERAL CONDITIONS OF THIS SPECIFICATION ALSO APPLY TO THE DIVISION 21,22 AND 23 CONTRACT DOCUMENTS.
B. "CONTRACT DOCUMENTS" CONSTITUTE THE DRAWINGS, SPECIFICATIONS, GENERAL CONDITIONS, PROJECT MANUALS, ETC., PREPARED BY ENGINEER (OR OTHER DESIGN PROFESSIONAL IN ASSOCIATION WITH ENGINEER) FOR CONTRACTOR'S BID OR CONTRACTOR'S NEGOTIATIONS WITH THE OWNER. THE DIVISION 21,22 AND 23 DRAWINGS AND SPECIFICATIONS PREPARED BY THE ENGINEER ARE NOT CONSTRUCTION DOCUMENTS.
C. "CONSTRUCTION DOCUMENTS", "CONSTRUCTION DRAWINGS", AND SIMILAR TERMS FOR DIVISION 21,22 AND 23 WORK REFER TO INSTALLATION DIAGRAMS, SHOP DRAWINGS AND COORDINATION DRAWINGS PREPARED BY THE CONTRACTOR USING THE DESIGN INTENT INDICATED ON THE ENGINEER'S CONTRACT DOCUMENTS. THESE SPECIFICATIONS DETAIL THE CONTRACTOR'S RESPONSIBILITY FOR "ENGINEERING BY CONTRACTOR" AND FOR PREPARATION OF CONSTRUCTION DOCUMENTS.
D. "(N)" INDICATES "NEW" EQUIPMENT TO BE PROVIDED UNDER THIS CONTRACT.
E. "(E)" INDICATES "EXISTING" EQUIPMENT ON SITE WHICH MAY OR MAY NOT NEED TO BE RELOCATED AS A PART OF THIS WORK.
F. "(R)" INDICATES EXISTING EQUIPMENT TO BE RELOCATED AS PART OF THIS WORK.
G. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT.
H. "INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL OPERATIONAL ORDER".
I. "PROVIDE" MEANS TO "FURNISH AND INSTALL".
J. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN ALL SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS SHALL BE AS DETERMINED BY THE ARCHITECT/ENGINEER.
K. "WORK BY OTHER(S) DIVISIONS"; "RE: XX DIVISION", AND SIMILAR EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN HIS/HER SUPPLIERS, SUBCONTRACTORS AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT ARCHITECT/ENGINEER BEFORE SUBMITTING BID.
L. BY INFERENCE, ANY REFERENCE TO A "CONTRACTOR" OR "SUB- CONTRACTOR" MEANS THE ENTITY WHICH HAS CONTRACTED WITH THE OWNER FOR THE WORK OF THE CONTRACT DOCUMENTS.
M. "ENGINEER" MEANS THE DESIGN PROFESSIONAL FIRM WHICH HAS PREPARED THESE CONTRACT DOCUMENTS. ALL QUESTIONS, SUBMITTALS, ETC. OF THIS DIVISION SHALL BE ROUTED THROUGH THE ARCHITECT TO THE ENGINEER (THROUGH PROPER CONTRACTUAL CHANNELS).
EXISTING BUILDING: 1. THE CONTRACTOR'S ATTENTION IS CALLED TO THE FACT THAT THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE HINDERED BY THIS WORK. THE CONTRACTOR SHALL ACCOUNT FOR ALL ADDITIONAL COSTS WHICH MAY BE INCURRED BY HIM DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, DESKS, EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN AREA MAY BE AVAILABLE WHEN SUBMITTING HIS BID.
2. MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. SURRENDER DRAWINGS TO OWNER UPON COMPLETION.
3. ALL CAPACITIES ARE SCHEDULED AT JOBSITE ALTITUDE OF 0 FT. ABOVE SEA LEVEL.
4. COORDINATE ALL PENETRATIONS OF THE FLOOR SLAB PRIOR TO COMMENCING WORK UTILIZE X-RAY AND VISUAL INVESTIGATION OF EXISTING CONDITIONS AS REQUIRED PRIOR TO DRILLING OR CUTTING. COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE WORK. ALL CONTRACTORS ARE INDIVIDUALLY RESPONSIBLE FOR ALL PENETRATIONS REQUIRED BY THEIR DIVISIONS.
ELECTRICAL COORDINATION:
1. VERIFY THE ELECTRICAL SERVICE PROVIDED BY THE ELECTRICAL CONTRACTOR BEFORE ORDERING ANY MECHANICAL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
2. PROVIDE PREMIUM EFFICIENCY MOTORS WITH 1.15 SERVICE FACTOR ON ALL EQUIPMENT, MOTORS SHALL BE CAPABLE OF OPERATING CONTINUOUSLY AT 105°F UNDER JOBSITE CONDITIONS AND ALTITUDE.
3. UNLESS NOTED OTHERWISE, ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH HOA SWITCH AND STARTER COMPATIBLE WITH EQUIPMENT AND BMS SYSTEM. STARTERS SHALL BE PROVIDED BY DIVISION 21,22 AND 23 UNLESS IN A MOTOR CONTROL CENTER. ALL DISCONNECTS SHALL BE FURNISHED BY DIVISION 26.
4. THE ELECTRICAL POWER FOR CERTAIN EQUIPMENT PROVIDED UNDER DIVISION 21,22 AND 23 HAS NOT BEEN SPECIFICALLY INDICATED ON THE ELECTRICAL DRAWINGS AND MUST BE PROVIDED BY AND FIELD COORDINATED BY THE DIVISION 21,22 AND 23 TRADE REQUIRING SUCH POWER.
SUFFICIENT POWER FOR THIS PURPOSE SHALL BE FURNISHED AS "SPARE", DEDICATED CIRCUIT CAPACITY IN DIVISION 26'S PANELBOARDS. ALL WIRING, CONDUIT AND ELECTRICAL DEVICES DOWNSTREAM OF THE PANELBOARDS IS THE RESPONSIBILITY OF THE DIVISION 21,22 AND 23 TRADE REQUIRING THE POWER UNLESS OTHERWISE SHOWN ON THE ELECTRICAL DRAWINGS.
SUCH EQUIPMENT IS HEREBY DEFINED AS:
A. ELECTRICAL HEAT TRACE. REQUIRED HEAT TRACE LOCATIONS, CAPACITIES AND SPECIFICATION ARE SHOWN OR INDICATED ON THE DRAWINGS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
B. FIRE PROTECTION AIR COMPRESSORS, DRY-PIPE CONTROL PANELS AND VALVES. REQUIRED CONNECTIONS ARE INCLUDED IN THE DIVISION 21 WORK, AND WILL BE SHOWN BY THAT CONTRACTOR'S ENGINEERED SYSTEM DESIGN DRAWINGS.
(1) PRE-ACTION SYSTEM INITIATION SIGNALS (SUCH AS SMOKE DETECTORS, OR GENERAL ALARM CONDITIONS IN A PRE-ACTION ZONE) SHALL BE PROVIDED UNDER DIVISION 28 FIRE-ALARM WORK.
(2) DIVISION 21 SHALL PROVIDE PRE-ACTION CONTROL PANEL AND INTERCONNECTION BETWEEN NEAREST SUITABLE FIRE ALARM PANEL AND LOCATION OF PRE-ACTION VALVE(S).
(3) DIVISION 28 SHALL PROVIDE INTERCONNECTION BETWEEN FIRE COMMAND CENTER ALARM PANEL (PROVIDED UNDER DIVISION 28) AND REMOTE COMMUNICATION FIRE ALARM PANEL (PROVIDED UNDER DIVISION 28).
C. TEMPERATURE CONTROL PANELS, CONTROL AIR COMPRESSORS AND LINE VOLTAGE POWER FOR 24V CONTROL TRANSFORMERS. REQUIRED CONNECTION ARE INCLUDED IN DIVISION 230900 AND WILL BE SHOWN BY THAT CONTRACTOR'S CONTROL SUBMITTAL DRAWINGS.
D. IT IS NOT PERMISSIBLE TO UTILIZE "SPARE" POWER FROM ADJACENT POWER CIRCUITS TO SERVE ANY OF THE ABOVE LOADS. ALL POWER MUST COME FROM DEDICATED CIRCUITS.
5. SMOKE DETECTORS:
FOR AIR HANDLING UNITS AND AIR SYSTEMS WITH A CAPACITY EXCEEDING 2000 CFM, PROVIDE UL LISTED SMOKE DETECTORS IN RETURN AIR SYSTEMS IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE AND ELSEWHERE AS SHOWN ON THE DRAWINGS.
SMOKE DETECTORS WILL BE FURNISHED AND SET IN PLACE UNDER THIS DIVISION. DETECTORS WILL BE WIRED UNDER DIVISION 28. SMOKE DETECTORS MUST BE OF THE SAME MANUFACTURER, AND COMPATIBLE WITH THE FIRE FLARM SYSTEM PROVIDED UNDER DIVISION 28 (IF APPLICABLE).
CONNECT RELAY(S) TO FAN CONTROL CIRCUIT TO STOP FAN WHEN SMOKE IS DETECTED.
INSTALLATION:
1. SUSPEND EACH TRADE'S WORK SEPARATELY FROM THE STRUCTURE. DUCTWORK SHALL BE HELD TIGHT TO STRUCTURE EXCEPT WHERE OTHERWISE SHOWN.
2. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY INDICATED OTHERWISE OR WHERE LOCAL CODES OR REGULATIONS TAKE PRECEDENCE.
3. PROVIDE MANUFACTURER'S RECOMMENDED SERVICE CLEARANCE AROUND ALL EQUIPMENT REQUIRING SAME.
4. PROVIDE FOR SAFE CONDUCT OF THE WORK, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS AND PROTECTION OF PROPERTY WHICH IS TO REMAIN UNDISTURBED.
5. PROVIDE ACCESS DOORS FOR ALL EQUIPMENT, VALVES, CLEANOUTS, ACTUATORS AND CONTROLS WHICH REQUIRE ACCESS FOR ADJUSTMENT OR SERVICING AND WHICH ARE LOCATED IN OTHERWISE INACCESSIBLE LOCATIONS.
A. FOR EQUIPMENT LOCATED IN "ACCESSIBLE LOCATIONS" SUCH AS LAY-IN CEILINGS: LOCATE EQUIPMENT TO PROVIDE ADEQUATE SERVICE CLEARANCE FOR NORMAL MAINTENANCE WITHOUT REMOVING ARCHITECTURAL, ELECTRICAL OR STRUCTURAL ELEMENTS SUCH AS THE CEILING SUPPORT SYSTEM, ELECTRICAL FIXTURES, ETC. "NORMAL MAINTENANCE" INCLUDES, BUT IS NOT LIMITED TO:FILTER CHANGING; GREASING OF BEARINGS; USING P/T PORTS FOR PRESSURE OR TEMPERATURE MEASUREMENTS; SERVICING CONTROL VALVES AND SERVICING CONTROL PANELS.
6. ISOLATE ALL PRESSURIZED PIPE (WATER, ETC.) AT EACH RISER, BRANCH, PIECE OF EQUIPMENT, AND AREA SERVED.
7. PROVIDE PRIMERS FOR ALL FLOOR DRAINS AND FLOOR SINKS SHOWN ON DRAWINGS. PRIMERS MAY BE CONNECTED TO FLUSH FIXTURES OR BE STAND ALONE. SEE SPECIFICATIONS.
8. NO DOMESTIC WATER, CHILLED WATER, OR HEATING WATER LINES SHALL BE LOCATED EXPOSED IN FINISHED SPACES OR BELOW THE BUILDING SLAB UNLESS SHOWN OTHERWISE ON THE DRAWINGS.
9. NO GAS LINES SHALL BE LOCATED BELOW BUILDING SLAB.
10. ALL CURBS, ROOF JACKS, ROOF THIMBLES, SANITARY VENTS, ROOF DRAINS, ETC. SHALL BE COMPATIBLE WITH ROOFING SYSTEM TO BE PROVIDED. REFERENCE ARCHITECTURAL DIVISION FOR REQUIRED FLASHING DETAILS.
11. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONCRETE EQUIPMENT PAD DIMENSIONS, BASED ON THE FINAL EQUIPMENT SELECTION, TO THE STRUCTURAL AND GENERAL CONTRACTOR FOR INCLUSION IN THOSE CONTRACTOR'S WORK AS DESCRIBED BY THE GENERAL CONTRACTOR.
12. WARRANTY: AT A MINIMUM, THE ENTIRE MECHANICAL SYSTEM SHALL BE WARRANTED AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR AFTER ACCEPTANCE OF THE SYSTEM BY THE OWNER. REFER TO INDIVIDUAL SPECIFICATION SECTIONS FOR SPECIFIC WARRANTY REQUIREMENTS.
DUCTWORK INSTALLATION:
1. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIR TIGHT WITH SEALANT PER SPECIFICATIONS.
2. DUCT DIMENSIONS ARE INSIDE CLEAR.
3. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE.
4. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH.
5. WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE MITERED ELBOWS WITH TURNING VANES AS FOLLOWS:
A. FOR DUCT WIDTHS OF 36" OR LESS, PROVIDE MANUFACTURED SINGLE WIDTH TURNING VANES, WITH NO TRAILING EDGES AND SPACING IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR "STANDARD SPACING".
B. USE DOUBLE THICKNESS (AIRFOIL) BLADES WITHOUT TRAILING EDGES FOR DUCT WIDTHS GREATER THAN 36".
6. ALL FLEXIBLE DUCTS SHALL NOT BE LESS THAN 4', OR MORE THAN 10' IN LENGTH. INSTALL FLEXIBLE DUCTWORK SUCH THAT:
A. MINIMUM OVERALL LENGTH OF 3D, STRAIGHT INTO NECK OF DIFFUSER.
B. MAXIMUM OF 135° OF TOTAL TURNING IN ENTIRE LENGTH OF FLEXIBLE DUCT.
C. MINIMUM TURNING RADIUM OF R = 1.5D.
D. WHERE: * D = FLEXIBLE DUCT DIAMETER * R = RADIUS OF TURN AS MEASURED TO CENTERLINE OF DUCT.
7. RETURN AIR PLENUM: THE HVAC SYSTEM WILL USE THE SPACE ABOVE THE CEILING AS A RETURN AIR PLENUM. CONTRACTOR SHALL CONFORM TO THE REQUIREMENTS OF NFPA AND LOCAL CODE REQUIREMENTS FOR ALL MATERIAL INSTALLED IN THE RETURN AIR PLENUM.
A. IN ADDITION, THE CONTRACTOR SHALL PROVIDE A COMPLETE RETURN AIR PATH BETWEEN ALL RETURN AIR DEVICES (GRILLES ETC.) AND THEIR RESPECTIVE HVAC UNIT. MAXIMUM VELOCITY OF RETURN AIR IN PLENUM SHALL GENERALLY NOT EXCEED 250 FEET PER MINUTE, NOR EXCEED 750 FEET PER MINUTE AT ANY CROSS-SECTION OF THE RETURN AIR PATH.
8. BRANCH LINES:
A. MAKE ALL TAPS TO ROUND DUCTWORK WITH CONICAL TEES.
B. MAKE ALL TAPS TO RECTANGLE DUCTWORK WITH 45° ENTRY OR CONICAL SPIN IN TO ROUND.
C. INCLUDE DAMPERS AT ALL BRANCH LINES.
9. DUCT SIZES NOT CALLED OUT SHALL BE DETERMINED BASED ON 0.08" S.P. LOSS OR LESS PER 100 FT. OF LENGTH.
10. ASSUME ROUND OR OVAL DUCTS IN EXPOSED AREAS.
11. INCLUDE DAMPERS AT ALL BRANCH LINES, WHERE SHOWN ON THE DRAWINGS, AND WHERE OTHERWISE REQUIRED FOR BALANCING.
PIPE INSTALLATION:
1. ALL PIPING SHALL BE ADEQUATELY SUPPORTED FROM THE BUILDING STRUCTURE TO PREVENT SAGGING, POCKETING, SWAYING OR DISPLACEMENT BY MEANS OF HANGERS AND SUPPORTS. PIPING IS NOT TO BE SUPPORTED BY EQUIPMENT.
2. PROVIDE DIELECTRIC UNIONS BETWEEN DISSIMILAR MATERIALS.
3. PROVIDE MANUAL AIR VENTS AND CAPPED HOSE-END DRAINS WITH ISOLATION VALVES AT PIPING HIGH AND LOW POINTS.
4. WELD PIPE IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. WELDERS SHALL BE CERTIFIED FOR TYPE OF WORK BEING PERFORMED.
5. FLUSH OUT PIPING AND REMOVE CONTROL DEVICES BEFORE PERFORMING PRESSURE TEST. DO NOT USE PIPING SYSTEM VALVES TO ISOLATE SECTIONS WHERE TEST PRESSURE EXCEEDS VALVE PRESSURE RATING. PRESSURIZE PIPING AT 100 PSIG. IF LEAKAGE IS OBSERVED OR IF TEMPERATURE COMPENSATED PRESSURE DROP EXCEEDS 1% OF TEST PRESSURE, REPAIR LEAKS AND RETEST. DO NOT USE AIR PRESSURE TO TEST PLASTIC PIPE.
CONDENSATE DRAINAGE:
1. PROVIDE CONDENSATE DRAINAGE FOR ALL COOLING COILS AND OVERFLOW PANS.
2. ROUTE CONDENSATE PIPING, FULL SIZE OF DRIP PAN CONNECTION, TO NEAREST CODE APPROVED RECEPTACLE. INSULATE WHERE LOCATED ABOVE FINISHED CEILINGS.
3. HEAT TRACE CONDENSATE LINES FROM FOOD SERVICE EQUIPMENT.
LOUVERS:
1. ALL LOUVERS LOCATED ON EXTERIOR WALLS SHALL BE PROVIDED BY ARCHITECTURAL DIVISION. ALL OTHER LOUVERS SHALL BE PROVIDED BY DIVISION 23. REQUIRED LOUVER FREE AREAS ARE INDICATED ON DIVISION 23 AND 23 DRAWINGS. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO CONFIRM THAT THE REQUIRED FREE AREA HAS BEEN PROVIDED, PRIOR TO CONNECTION TO THAT LOUVER. DIVISION 23 SHALL PROVIDE ALL LOUVER PLENUMS.
CUTTING, PATCHING AND DEMOLITION:
1. KEEP DEMOLITION & CUTTING TO MINIMUM REQUIRED FOR PROPER EXECUTION OF WORK.
2. BE RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE COMPLETION OF THE WORK.
3. NO CUTTING (NOT SHOWN ON THE CONTRACT DOCUMENTS) SHALL BE DONE WITHOUT THE APPROVAL OF THE ARCHITECT AS TO LOCATIONS, METHOD AND EXTENT OF THE CUTTING.
4. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE OR FUNCTION.
5. ALL "CAPPED" SANITARY AND VENT LINES SHALL BE RECONNECTED OR RE- ROUTED AS NECESSARY TO PREVENT "DEAD-ENDS" IN THE PIPING. ALL PIPING SHALL DRAIN TO ACTIVE SANITARY WASTE LINES AND ALL BRANCHES WITH TRAPS SHALL BE ADEQUATELY VENTED.
GENERAL PLUMBING CONTRACT REQUIREMENTS:
1. THE GENERAL MECHANICAL REQUIREMENTS PERTAIN TO THE WORK OF THIS DIVISION.
2. PREPARE SHOP DRAWINGS OF ALL NEW WORK (INCLUDING SLEEVE LOCATIONS) TO VERIFY LOCATIONS AND COORDINATION OF WORK BETWEEN TRADES PRIOR TO INSTALLATION.
3. ALL DRAIN GRATES, CLEANOUT COVERS, AND OTHER FINISHED, EXPOSED COMPONENTS SHALL BE PROTECTED FROM DAMAGE. DAMAGED COMPONENTS SHALL BE REPLACED BY CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT.
4. COORDINATE ROUTING OF ALL PLUMBING PIPING BELOW SLAB WITH STRUCTURAL GRADE BEAMS, TIE BEAMS, ETC. ALLOW FOR REROUTING OF PIPING AS REQUIRED.
5. ALL REQUIRED OPENINGS IN CONCRETE BEAMS AND STRUCTURAL WALLS ARE TO BE ACCOMPLISHED USING SLEEVES PROPERLY SIZED FOR THE PIPE THEY SERVE. CORE DRILLING IN BEAMS IS NOT ALLOWED. CORE DRILLING IN PANS IS ALLOWED UPON PRIOR APPROVAL OF ARCHITECT AND STRUCTURAL ENGINEER.
6. HORIZONTAL STORM AND SANITARY PIPING SHALL RUN AT A SLOPE OF 1/4" PER FOOT MINIMUM FOR 3" AND SMALLER PIPING. 4" AND LARGER PIPING SHALL RUN AT 1/8" PER FOOT MINIMUM.
7. NO DOMESTIC WATER LINES SHALL BE LOCATED EXPOSED IN FINISHED SPACES OR BELOW THE BUILDING SLAB UNLESS SHOWN OTHERWISE ON THE DRAWINGS.
8. WHERE SHOWN, MINIMIZE THE NUMBER OF JOINTS ON ANY PRESSURIZED PIPING BELOW CONCRETE SLABS. ALL BELOW GRADE PIPING TO BE PRESSURE TESTED AND WITNESSED BY ARCHITECT BEFORE BACKFILLING.
9. ALL CLEANOUTS FOR HORIZONTAL STORM DRAINAGE SYSTEM SHALL BE PIPE SIZE OR MAXIMUM 6" FOR LARGER PIPE.
10. IN ADDITION TO THE CLEANOUT LOCATIONS SHOWN ON DRAWINGS, PROVIDE ADDITIONAL CLEANOUTS AT:
A. ALL UPPER TERMINALS.
B. EACH RUN OF PIPING WHICH IS MORE THAN 100 FEET IN LENGTH OR FRACTION THEREOF.
C. HORIZONTAL LINES 5 FEET OR MORE.
D. HORIZONTAL LINES FOR EACH AGGREGATE CHANGE OF DIRECTION EXCEEDING 135 DEGREES.
E. AT THE BASE OF ALL WASTE AND VENT RISERS. ALL VERTICAL CLEANOUTS SHALL BE SIZED TO ACCOMMODATE THE LARGEST PIPE ON THAT BRANCH LINE, BUT NEVER LARGER THAN 4".
11. NO GAS LINES SHALL BE LOCATED BELOW BUILDING SLAB. ALL GAS PIPING IN AIR PLENUMS TO BE WELDED.
12. PROVIDE ISOLATION VALVES ON ALL PIPING SERVING HOSE BIBBS.
13. ANY ELECTRICAL SPACE NOT CONSTRUCTED WITH A SUB-ROOF WHICH MAY HAVE PLUMBING PIPING AT THE CEILING OF THESE SPACES SHALL HAVE A DRIP PAN INSTALLED BELOW THE PIPING. DRIP PANS SHALL BE 1.5 TIMES THE WIDTH OF THE PIPING SERVED WITH A MINIMUM OF 2" HIGH SIDES. DRIP PANS SHALL BE SUSPENDED FROM THE PIPING SERVED AND SHALL SLOPE AT A MINIMUM 1/8"/FT. DRIP PANS SHALL DISCHARGE WITH MIN. 1-1/2" DR TO FLOOR DRAINS.
A. DO NOT LOCATE PIPING DIRECTLY ABOVE ANY ELECTRICAL EQUIPMENT IN ELECTRICAL ROOMS.
14. MAINTAIN DESIGNATED PLUMBING FIXTURE HEADER SIZE FOR FULL BANK OF FIXTURES.
15. PROVIDE GAS VENTS EXTENDING CONTINUOUSLY FROM ALL INTERIOR GAS REGULATORS TO THE EXTERIOR OF THE BUILDING. TERMINATE AT AN APPROVED LOCATION. SIZE VENTS SUCH THAT MINIMUM VENT SIZE (FOR VENT WHICH IS 10 FEET OR LESS IN LENGTH) EQUALS RELIEF OUTLET PIPE SIZE. INCREASE VENT PIPE SIZE ONE PIPE SIZE FOR EVERY ADDITIONAL TEN FEET OF VENT PIPE LENGTH.
A. PROVIDE AN ISOLATION VALVE DOWNSTREAM OF EVERY INTERIOR GAS REGULATOR.
STRUCTURE: 1. DO NOT PENETRATE STRUCTURAL MEMBERS. ALL EQUIPMENT SUPPORTS SHALL BE ATTACHED TO THE LOAD BEARING MEMBERS OF STRUCTURAL ELEMENTS. DO NOT OVER-STRESS ANY STRUCTURAL MEMBERS. CONTACT STRUCTURAL ENGINEER FOR ALLOWABLE LOADS FOR SPECIFIC MEMBERS.
2. DO NOT UTILIZE POWER DRIVEN ANCHORS FOR ANY LOCATIONS WHICH REQUIRE THE LOAD TO BE HELD IN TENSION. SEE STRUCTURAL DIVISION FOR ADDITIONAL RESTRICTIONS.
3. SEE ALSO STRUCTURAL DIVISION FOR ACCEPTABLE ANCHORING AND SUPPORT MEANS, METHODS, AND LOCATIONS.
4. PROVIDE FLEXIBLE CONNECTORS, EXPANSION LOOPS, EXPANSION JOINTS, ADDITIONAL FITTINGS OR EQUIVALENT TO ACCOMMODATE THE THERMAL EXPANSION OF THE BUILDING THROUGH STRUCTURAL EXPANSION JOINTS. PROVIDE SUCH FITTING AT EVERY PIPE, DUCT, CONDUIT, ETC. CROSSING OF A STRUCTURAL EXPANSION JOINT.
CONSTRUCTION VENTILATION:
1. WHERE EXISTING OR NEW MECHANICAL SYSTEMS ARE USED FOR TEMPORARY VENTILATION OR CLIMATE CONTROL, MECHANICAL EQUIPMENT INSTALLER SHALL PROVIDE CONSTRUCTION FILTERS, MAINTAIN EQUIPMENT, AND CLEAN, ADJUST AND PUT IN NEW CONDITION BEFORE BUILDING OCCUPANCY. PARTS AND LABOR WARRANTY SHALL NOT BE CONSIDERED TO START UNTIL ACCEPTANCE OF SYSTEM BY OWNER.
2. PROVIDE CONSTRUCTION FILTERS INSTALLED AT ALL AIR MOVING DEVICES THROUGHOUT THE CONSTRUCTION. REMOVE FILTERS ONLY FOR BALANCING AND FINAL TURNOVER. INSPECT ALL NON-CONSTRUCTION FILTERS AND REPLACE ALL THOSE DEEMED NECESSARY BY THE ENGINEER PRIOR TO ACCEPTANCE OF THE SYSTEM BY THE OWNER.
GAS FIRED VENTING REQUIREMENTS:
1. ALL FLUES SERVING GAS FIRED EQUIPMENT SHALL BE DOUBLE WALL TYPE "B" BY METALBESTOS CO. OR EQUAL. TERMINATE FLUES A MINIMUM HEIGHT ABOVE ROOF (AS DETERMINED BY CODE) WITH WEATHER CAP. SLOPE HORIZONTAL RUNS TOWARD POINT OF ORIGINATION AT MINIMUM 1/4" PER 1'.
FIRE PROTECTION NOTES:
1. FIRE PROTECTION NOTES
A. SUBMIT SHOP DRAWINGS SHOWING PROPOSED LAYOUT OF FIRE PROTECTION SYSTEM. DRAWINGS SHALL SHOW ACTUAL EQUIPMENT TO BE USED, DIMENSIONS AND HYDRAULIC CALCULATIONS. SHOP DRAWINGS SHALL BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION PRIOR TO SUBMITTAL TO ENGINEER OR ARCHITECT.
B. SHOW THE CONNECTING MAIN AND BRANCH PIPE SIZES FOR ALL RELOCATED EXISTING SPRINKLER HEADS.
C. CONFORM TO HAZARD OCCUPANCY REQUIREMENTS OF NFPA 13.
2. THE ENTIRE BUILDING SHALL BE SERVED BY A WET PIPE TYPE FIRE SPRINKLER SYSTEM. COORDINATE ELECTRICAL, FIRE PROTECTION AND MECHANICAL SPACE REQUIREMENTS CAREFULLY BEFORE PROCEEDING WITH INSTALLATION.
3. EXTEND THE EXISTING SPRINKLER SYSTEM, RELOCATE EXISTING AND ADD NEW SPRINKLER HEADS IN ACCORDANCE WITH NFPA 13, ALL APPLICABLE CODES AND ORDINANCES AND PROJECT REQUIREMENTS TO COMPLETELY PROTECT THE NEW WORK.
4. SYSTEM SHALL BE INSTALLED COMPLETE AND OPERATIONAL, INCLUDING WATER FLOW INDICATOR, CONNECTIONS TO EXISTING ALARM, DRAIN PIPING, IDENTIFICATION SIGNS, ETC.
5. WORK SHALL BE PERFORMED BY A QUALIFIED FIRE SPRINKLER INSTALLER WITH A MINIMUM OF (5) FIVE YEARS EXPERIENCE IN SIMILAR INSTALLATIONS.
6. COORDINATE ALL WORK WITH ALL OTHER TRADES.
7. SUPPLY OWNER AN EXTRA STOCK OF SIX SPRINKLER HEADS (6), THREE (3) OF EACH TYPE, AND A SPRINKLER WRENCH.
FIRE STOPPING:
1. FIRE STOPPING REQUIREMENT: PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ACCEPTANCE MATERIALS NCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 21,22 AND 230 CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING CONSTRUCTION; GAPS 3M FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICAL CABLE.
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 9
:53
:38
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M0.01
MECHANICAL GENERALNOTES
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
01-09-2019
RE
F.
REF.
UPUPUP
F/S
NEWPARKINGGARAGE
NEWCOMMONSBUILDING
CENTRAL
PLANT
L100
SITE PLAN IS DIAGRAMATIC IN NATURE. MECHANICAL CONTRACTOR TO FIELD VERIFY EXACT ROUTING AND SIZE OF EXISTING CHILLED WATER PIPING. COORDINATE POSSIBLE RELOCATION WITH OWNER'S REQUIREMENTS.
(E) CHS/R
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:59
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M1.00
MECHANICAL SITE PLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1" = 40'-0" 1MECHANICAL SITE PLAN
JAN 09, 2019 PERMIT & BID
01-09-2019
EL.13' - 2"
LEVEL 2
EL.13' - 2"
LEVEL 2
EL.14' - 0"
LEVEL 2 - MECHANICAL
MEZZANINE
12"øSA
12"øSA
18"x18"SA
C-3
VAV
C-4
VAV
26"x10"SA
26"x10"SA
EL.28' - 0"
LEVEL 3
EL.42' - 0"
LEVEL 4
EL.28' - 0"
LEVEL 3
EL.41' - 6"
LEVEL 4
34"øSA
ROUTE DUCT BETWEEN STRUCTURAL MEMBERS AS SHOWN. REFER TO DETAIL 6 SHEET M7.00 FOR DETAILS. TYPICAL OF ALL ROUND DUCT IN GYMNASIUM.
EL.13' - 2"
LEVEL 2
EL.28' - 0"
LEVEL 3
EL.13' - 2"
LEVEL 2
EL.28' - 0"
LEVEL 3
EL.14' - 0"
LEVEL 2 - MECHANICAL
MEZZANINE
EL.28' - 0"
LEVEL 3
22"x44"SA
40"x
36"R
A
40"x36"SA
C-2
AHU
C-1
EDH
40"x36" RELIEF AIR
34"x44" OA
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:59
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M2.00
MECHANICAL SECTIONVIEWS
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
1/4" = 1'-0"1
VAV C-3 AND C-4
1/4" = 1'-0"2
FABRIC DUCT THROUGH STRUCTURE
1/4" = 1'-0"3
AHU C-1
01-09-2019
UP
UPUP
SH
SH
SH
SH
SH
SH
M
M
CA CB CC CD
C1
C2
C3
C4
C4.2
C5
C5.2
CA.3 CC.5
C4.6
LOBBY
C100
STUDIO
C112
MEN
C106
WOMEN
C107
GYMNASIUM
C113
STAGE
C116
GREEN RM
C115
OUTSIDE
STOR.
C117
LOCKER
C121CONF
C120
OFFICE
C122
UCAL STOR
C103
ATHLETIC
STOR
C104
TICKET &
VENDING
C101
P.E. INDOOR
STOR
C105
ADVANCEMENT
STOR
C102
TABLE &
CHAIR STOR.
C114
FAMILY
C109
JAN
C108
GIRLS
LOCKER
C119
BOYS LOCKER
C118
LOGGIA
C124
CHEER
C110ELEC
C111 EAST
CORRIDOR
C123
8"x8"EA
12"x12"EA
200A
8"ø 250A
10"ø
C-1
CU
12"x
12"S
A
32"x26"SA
16"x12"SA12"x10"SA
16"x12"SA
20"x12"SA
16"x12"SA
12"x12"SA
50A
6"ø
200A
8"ø
200A
8"ø C-2
VAV
C-1
VAV
C-5
VAV
C-6
VAV
C-7
VAV
200A
8"ø
50A
6"ø
325A (2)
12"ø
200A (3)
10"ø
150A
8"ø
T
T
T
TT
T
10"x12"EA
12"x12"EA
16"x16"EA
M15
M15
14"x12"EA
M15
M15
M15
M15
(14 SF FREE AREA)
(4 SF FREE AREA)
M11(4 SF FREE AREA)
M12
-42"x18"
E
18"øSA
26"x4"D (6)
200
26"x4"D
200
C-1
AHU
20"øSA20"x14"OA
20"x14"RA
20"x
20"R
A
FIRE RISER
C124
C-1
UH
T
M15 C-8
VAV
T M15
12"øSA
C-1
REF
T
-12"x6"
E
CB CC CD
CD
M20
-18"x10"
E (4)
6"x6"F
100
10"x6"D(4)
200
12"x6"RA
22"x12"RA
-18"x10"
E (4)
(TYP. 3)
-36"x24"
E
-22"x22"
C (2)
C-1
TF12"x12"
D140-
12"x12"F
50"x24"RA
40"x24"RA
12"x24"RA
VAV-4
18"x18"SA
20"x12"SA20"x12"SA
12"x12"SA12"x12"SA
400G (8)
10"ø
T
280G (10)
10"ø
400G (8)
10"ø
VAV-3
40"x24"RA
24"x24"RA
M17
SD
20"x
12"S
A
20"x
12"S
A
14"x12"SA
28"x16"SA
24"x16"SA
M1
M7
1
M2.00
M22M22
M291"DR
48"x
16"S
A
48"x18"SA
36"x30"SA
44"x24"RA
M4
M1
M15
-12"x12"
E(2)
-18"x10"
E
28"x
16"S
A
6"ø
100B
SP
CO2
12"ø
375B
12"ø
375B
6"x6"D
50
6"ø
100B
12"x12"D
150
48"x30"RA
200A (3)
10"ø 10"ø
250B (3)
10"ø
250B (3)
-22"x22"
C
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:54
:13
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
1-M2.01
MECHANICAL LEVEL 1FLOOR PLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1/8" = 1'-0" 1MECHANICAL LEVEL 1 FLOOR PLAN - COMMONS
1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN CODE REQUIRED AREA OF SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC.
3. COORDINATE EQUIPMENT HOUSEKEEPING PAD DIMENSIONS AND LAYOUT WITH THE GENERAL CONTRACTOR BASED ON FINAL EQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERS IN ALL SUPPLY DUCT BRANCH TAPS DOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE TRANSFER "Z" BOOT DUCTS IN FULL HEIGHT WALLS WHERE A PLENUM RETURN SYSTEM IS UTILIZED. BOOTS SHALL BE SIZED TO MAINTAIN A MAXIMUM OF 400 FPM. PROVIDE A GRILLE FOR ALL TRANSFERS IN EXPOSED AREAS. RE: ARCH. OPENINGS OF "Z" BOOT DUCTS SHALL BE AT LEAST 12" CLEAR OF STRUCTURE.
7. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES.
8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW PRIOR TO ROUGH-IN.
9. PROVIDE THROUGH FACE BALANCING FOR ALL DIFFUSERS, REGISTERS, AND GRILLES ABOVE INACCESSIBLE AREAS.
10. PROVIDE TURNING VANES IN ALL 90° DUCT ELBOWS.
11. INSTALL EXPOSED DUCTWORK AS HIGH AS POSSIBLE.
13. ALL DUCT/PIPE PENETRATIONS THROUGH FIRE RATED/SMOKE RATED PARTITIONS SHALL BE CAULKED AND SEALED TO MEET THE RATING REQUIRED. REFER TO LIFE SAFETY DRAWINGS FOR FIRE/SMOKE RATING REQUIREMENTS.
14. PROVIDE ISOLATION VALVES AT EACH BRANCH LINE OFF OF RISER.
15. PROVIDE 3/4" BRANCH PIPING TO ALL TERMINAL UNITS, UNLESS NOTED OTHERWISE.
16. PROVIDE CONDENSATE DRAIN FROM ALL CHILLED WATER COILS AND DX EVAPORATOR COILS TO LAVATORY TAIL PIECE OR MECHANICAL ROOM FLOOR DRAIN. PROVIDE CONDENSATE PUMP FOR WALL MOUNTED UNITS AND CONCEALED UNITS THAT CANNOT BE GRAVITY DRAINED TO TERMINATION LOCATION
GENERAL NOTES:
KEYNOTES
M1 SA DUCT UP.
M4 RA DUCT UP.
M7 EA DUCT UP.
M11 RELIEF AIR LOUVER WITH 18" PLENUM.
M12 REFRIGERANT PIPING TO/FROMFCU/CU. SIZE PER MANUFACTURER'SRECOMMENDATIONS.
M15 T-STAT LOCATED ON WALL BY DIV 23CONTRACTOR. FINAL LOCATION OFT-STAT SHALL BE COORDINATED WITHARCHITECT PRIOR TO INSTALLATION.
M17 ROUTE CONDENSATE FROMAC/AHU/RTU TO TAILPIECE OFLAVATORY AS ALLOWED BY AHJ.
M20 ROUND DOUBLE WALL SPIRAL DUCT INAREAS WITH EXPOSDED DUCTWORK.USE OF FLEX DUCT NOT PERMITED INAREAS WITH EXPOSED DUCTWORK.EXPOSED DUCTWORK SHALL BEPAINTED AND WRAPPED PERARCHITECT'S INSTRUCTIONS.
M22 REFER TO MEZZANINE PLAN FORCONTINUATION.
M29 MECHANICAL CONDENSATE PIPING UP.
JAN 09, 2019 PERMIT & BID
01-09-2019
MECHANICAL
PLATFORM
C127
34" FABRIC DUCT 34" FABRIC DUCT
C-2.2
CU
C-2.1
CU
C-1
EF
-96"x36"
E
(16 SF FREE AREA)
(16 SF FREE AREA)
M13M13
M16
IDF
C128
C-3
AC
C-3
CU
M12
C-1
EDH
34"x44"OA
44"x22"SA
40"x36"SA
40"x36"RA
REFRREFR
2
M2.00
C-3
VAV
C-4
VAV
C-2
EFM16
1"D
R
3/4"DR
M30
M18M18
TCO2SD
18"x18"SAM2
1
M2.00
M23 M23
M25M26
M26
M27
M28 M28
C-2
AHU
3
M2.00
40"x36" RELIEF AIR
M35
C-1
RTU
M5M24
M2M24
T SPM10
M11
M37
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:50
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
1-M2.02
MECHANICAL LEVEL 2MEZZANINE/ROOF FLOORPLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1/8" = 1'-0" 1MECHANICAL LEVEL 2 MEZZANINE - COMMONS
1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN CODE REQUIRED AREA OF SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC.
3. COORDINATE EQUIPMENT HOUSEKEEPING PAD DIMENSIONS AND LAYOUT WITH THE GENERAL CONTRACTOR BASED ON FINAL EQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERS IN ALL SUPPLY DUCT BRANCH TAPS DOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE TRANSFER "Z" BOOT DUCTS IN FULL HEIGHT WALLS WHERE A PLENUM RETURN SYSTEM IS UTILIZED. BOOTS SHALL BE SIZED TO MAINTAIN A MAXIMUM OF 400 FPM. PROVIDE A GRILLE FOR ALL TRANSFERS IN EXPOSED AREAS. RE: ARCH. OPENINGS OF "Z" BOOT DUCTS SHALL BE AT LEAST 12" CLEAR OF STRUCTURE.
7. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES.
8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW PRIOR TO ROUGH-IN.
9. PROVIDE THROUGH FACE BALANCING FOR ALL DIFFUSERS, REGISTERS, AND GRILLES ABOVE INACCESSIBLE AREAS.
10. PROVIDE TURNING VANES IN ALL 90° DUCT ELBOWS.
11. INSTALL EXPOSED DUCTWORK AS HIGH AS POSSIBLE.
13. ALL DUCT/PIPE PENETRATIONS THROUGH FIRE RATED/SMOKE RATED PARTITIONS SHALL BE CAULKED AND SEALED TO MEET THE RATING REQUIRED. REFER TO LIFE SAFETY DRAWINGS FOR FIRE/SMOKE RATING REQUIREMENTS.
14. PROVIDE ISOLATION VALVES AT EACH BRANCH LINE OFF OF RISER.
15. PROVIDE 3/4" BRANCH PIPING TO ALL TERMINAL UNITS, UNLESS NOTED OTHERWISE.
16. PROVIDE CONDENSATE DRAIN FROM ALL CHILLED WATER COILS AND DX EVAPORATOR COILS TO LAVATORY TAIL PIECE OR MECHANICAL ROOM FLOOR DRAIN. PROVIDE CONDENSATE PUMP FOR WALL MOUNTED UNITS AND CONCEALED UNITS THAT CANNOT BE GRAVITY DRAINED TO TERMINATION LOCATION
GENERAL NOTES:
KEYNOTES
M2 SA DUCT DOWN.
M5 RA DUCT DOWN.
M10 OUTSIDE AIR LOUVER WITH 18"PLENUM.
M11 RELIEF AIR LOUVER WITH 18" PLENUM.
M12 REFRIGERANT PIPING TO/FROMFCU/CU. SIZE PER MANUFACTURER'SRECOMMENDATIONS.
M13 CONDENSING UNIT MOUNTED ONROOF. UNIT SHALL BE ANCHORED TOROOF PER STRUCTURAL DETAILS.
M16 UPBLAST ROOF MOUNTED EXHAUSTFAN. FAN TO BE INSTALLED PERSTRUCTURAL DETAILS. EXHAUSTSHALL BE NO LESS THAN 10' CLEAR OFALL AIR INTAKES ANDPROPERTY/BUILDING LINE.
M18 ROUTE CONDENSATE FROMAC/AHU/RTU TO DRAIN AS ALLOWED BYAHJ.
M23 REFER TO FIRST FLOOR PLAN FORCONTINUATION.
M24 TRANSITION TO RTU OPENING ASREQUIRED.
M25 PROVIDE AHU ON 4" HOUSEKEEPINGPAD. REFER TO MECHANICALSCHEDULES FOR MORE INFORMATION.
M26 VAV BOXES TO BE SUPPORTED FROMVERTICAL WALL.
M27 ROUTE REFRIGERANT PIPING HIGH TOSCTRUCTURE. PIPING SHALL NOT BEOVER ANY ELECTRICAL COMPONENTS.
M28 ROUTE FABRIC DUCT THROUGHSTRUCTURE. FABRIC AIR ORIFLOWWITH DISCHARGE POSITIONS AT 4 AND8 O'CLOCK, OR APPROVED EQUAL.PROVIDE INTERNAL SKELETON TOMAINTAIN SHAPE.
M30 MECHANICAL CONDENSATE PIPINGDOWN.
M35 STACKED REFIRGERANT PIPING.
M37 BAS CONTROL PANEL. CONFIRM FINALLOCATION WITH ARCHITECT PRIOR TOINSTALLATION.
JAN 09, 2019 PERMIT & BID
01-09-2019
UP
REF.
RE
F.
UP
F/S
F/S
1 2
A
B
C
4 5 6 7 8 9 10 11 133 12
H.M. STOR
G111
UNISEX
G112
SCOUTS
G116
MEN
G104WOMEN
G105 YOUTH
G117MULTI-PURPOSE
G118
STOR 2
G108
SERVER
G102
SECURITY
G101
LOBBY
G100
S.A.F.
G106
STAIR A
G123
STAIR B
G124
150A
8"ø
G-1
VAV
210A
8"ø
10"x10"SA 12"x12"SA 12"x10"SA 8"x10"SA
G-4
VAV
50A
6"ø
14"x14"SA
20"x14"SA
10"x14"SA
18"x14"SA
375A(8)
12"ø
G-3
VAV G-5
VAV
12"x14"SA
16"x16"SA
G-6
VAV
G-2
VAV
250A
10"ø
200A (2)
8"ø
14"x14"SA
28"x16"SA46"x16"SA
52"x
16"S
A
G-1
AC
10"ø
300B (2)
100A (2)
6"ø
400A (4)
12"ø
G-1
CU
SAF STOR
G107STOR 1
G109
WORK
G110
YOUTH STOR
G113
T T
T
T
T
T
M12
M17
3/4
"DR
M15
T M15
M15
M15
M15 M15 M15
18"x6"EA
M19
M19
(1 SF FREE AREA)
(0.5 SF FREE AREA)
100A
6"ø
CORR - N
G120
CORR - W
G119
150A
8"ø
G-1
UH
T
G-2
EF
G-1
EF
1 2
C3
3 4 5 6 7 8 9 10 11 13
C1C2C5
C5
C4
A
B
C
12
C5.2 C4.2
300G(2)
10"ø
150G
8"ø
12"x6"RA
(TYP. 10)
-12"x6"
E (8)
12"x6"D (2)
110
G-3
EF
M19 (0.5 SF FREE AREA)
M21
JAN.
G129
ELECT.
G121
GIRLS STOR
G114BOY STOR
G115
G-1
TF
-12"x12"
F
48"x12"RA
8"ø
EA
48"x12"RA
(TYP. 2)
M17
44"x20"RA
44"x20"SA
M4
M1
1"DRM29
-C (TYP.)
CO2
M3712"x6"D (3)
110
12"x6"D
11012"x6"
D110
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:53
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
2-M2.01
MECHANICAL LEVEL 1FLOOR PLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1 : 144 1MECHANICAL LEVEL 1 FLOOR PLAN - GARAGE
1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN CODE REQUIRED AREA OF SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC.
3. COORDINATE EQUIPMENT HOUSEKEEPING PAD DIMENSIONS AND LAYOUT WITH THE GENERAL CONTRACTOR BASED ON FINAL EQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERS IN ALL SUPPLY DUCT BRANCH TAPS DOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE TRANSFER "Z" BOOT DUCTS IN FULL HEIGHT WALLS WHERE A PLENUM RETURN SYSTEM IS UTILIZED. BOOTS SHALL BE SIZED TO MAINTAIN A MAXIMUM OF 400 FPM. PROVIDE A GRILLE FOR ALL TRANSFERS IN EXPOSED AREAS. RE: ARCH. OPENINGS OF "Z" BOOT DUCTS SHALL BE AT LEAST 12" CLEAR OF STRUCTURE.
7. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES.
GENERAL NOTES:8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW PRIOR TO ROUGH-IN.
9. PROVIDE THROUGH FACE BALANCING FOR ALL DIFFUSERS, REGISTERS, AND GRILLES ABOVE INACCESSIBLE AREAS.
10. PROVIDE TURNING VANES IN ALL 90° DUCT ELBOWS.
11. INSTALL EXPOSED DUCTWORK AS HIGH AS POSSIBLE.
13. ALL DUCT/PIPE PENETRATIONS THROUGH FIRE RATED/SMOKE RATED PARTITIONS SHALL BE CAULKED AND SEALED TO MEET THE RATING REQUIRED. REFER TO LIFE SAFETY DRAWINGS FOR FIRE/SMOKE RATING REQUIREMENTS.
14. PROVIDE ISOLATION VALVES AT EACH BRANCH LINE OFF OF RISER.
15. PROVIDE 3/4" BRANCH PIPING TO ALL TERMINAL UNITS, UNLESS NOTED OTHERWISE.
16. PROVIDE CONDENSATE DRAIN FROM ALL CHILLED WATER COILS AND DX EVAPORATOR COILS TO LAVATORY TAIL PIECE OR MECHANICAL ROOM FLOOR DRAIN. PROVIDE CONDENSATE PUMP FOR WALL MOUNTED UNITS AND CONCEALED UNITS THAT CANNOT BE GRAVITY DRAINED TO TERMINATION LOCATION
KEYNOTES
M1 SA DUCT UP.
M4 RA DUCT UP.
M12 REFRIGERANT PIPING TO/FROMFCU/CU. SIZE PER MANUFACTURER'SRECOMMENDATIONS.
M15 T-STAT LOCATED ON WALL BY DIV 23CONTRACTOR. FINAL LOCATION OFT-STAT SHALL BE COORDINATED WITHARCHITECT PRIOR TO INSTALLATION.
M17 ROUTE CONDENSATE FROMAC/AHU/RTU TO TAILPIECE OFLAVATORY AS ALLOWED BY AHJ.
M19 EXHAUST AIR LOUVER WITH 18"PLENUM.
M21 CONDENSING UNIT MOUNTED ONWALL. UNIT SHALL BE ANCHORED PERMECHANICAL DETAILS ANDMANUFACTURER'SRECOMMENDATIONS.
M29 MECHANICAL CONDENSATE PIPING UP.
M37 BAS CONTROL PANEL. CONFIRM FINALLOCATION WITH ARCHITECT PRIOR TOINSTALLATION.
JAN 09, 2019 PERMIT & BID
01-09-2019
1 2
A
B
C
4 5 6 7 8 9 10 11 133 121 2
C3
3 4 5 6 7 8 9 10 11 13
C1C2C5
C5
C4
A
B
C
12
C4.2
44"x20"RA
44"x20"SA
1"DR
M3
M6
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:54
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
2-M2.02
MECHANICAL LEVEL 2FLOOR PLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1 : 144 1MECHANICAL LEVEL 2 FLOOR PLAN - GARAGE
JAN 09, 2019 PERMIT & BID
01-09-2019
1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN CODE REQUIRED AREA OF SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC.
3. COORDINATE EQUIPMENT HOUSEKEEPING PAD DIMENSIONS AND LAYOUT WITH THE GENERAL CONTRACTOR BASED ON FINAL EQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERS IN ALL SUPPLY DUCT BRANCH TAPS DOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE TRANSFER "Z" BOOT DUCTS IN FULL HEIGHT WALLS WHERE A PLENUM RETURN SYSTEM IS UTILIZED. BOOTS SHALL BE SIZED TO MAINTAIN A MAXIMUM OF 400 FPM. PROVIDE A GRILLE FOR ALL TRANSFERS IN EXPOSED AREAS. RE: ARCH. OPENINGS OF "Z" BOOT DUCTS SHALL BE AT LEAST 12" CLEAR OF STRUCTURE.
7. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES.
GENERAL NOTES:8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW PRIOR TO ROUGH-IN.
9. PROVIDE THROUGH FACE BALANCING FOR ALL DIFFUSERS, REGISTERS, AND GRILLES ABOVE INACCESSIBLE AREAS.
10. PROVIDE TURNING VANES IN ALL 90° DUCT ELBOWS.
11. INSTALL EXPOSED DUCTWORK AS HIGH AS POSSIBLE.
13. ALL DUCT/PIPE PENETRATIONS THROUGH FIRE RATED/SMOKE RATED PARTITIONS SHALL BE CAULKED AND SEALED TO MEET THE RATING REQUIRED. REFER TO LIFE SAFETY DRAWINGS FOR FIRE/SMOKE RATING REQUIREMENTS.
14. PROVIDE ISOLATION VALVES AT EACH BRANCH LINE OFF OF RISER.
15. PROVIDE 3/4" BRANCH PIPING TO ALL TERMINAL UNITS, UNLESS NOTED OTHERWISE.
16. PROVIDE CONDENSATE DRAIN FROM ALL CHILLED WATER COILS AND DX EVAPORATOR COILS TO LAVATORY TAIL PIECE OR MECHANICAL ROOM FLOOR DRAIN. PROVIDE CONDENSATE PUMP FOR WALL MOUNTED UNITS AND CONCEALED UNITS THAT CANNOT BE GRAVITY DRAINED TO TERMINATION LOCATION
KEYNOTES
M3 SA DUCT UP AND DOWN.
M6 RA DUCT UP AND DOWN.
DN
DN
F/S
F/S
1 2
A
B
C
4 5 6 7 8 9 10 11 133
RAMP DN
TO LVL 1
RAMP UP
TO LVL 3
12
TYP.
1 2
C3
3 4 5 6 7 8 9 10 11 13
C1C2C5
C5
C4
A
B
C
12
SD
44"x20"RA
44"x20"SA
M5
M2
1"DRM30
M31
M32
G-1
RTUM33 M34
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:43
:54
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
2-M2.03
MECHANICAL LEVEL 3FLOOR PLAN
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1 : 144 1MECHANICAL LEVEL 3 FLOOR PLAN - GARAGE
JAN 09, 2019 PERMIT & BID
01-09-2019
1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN CODE REQUIRED AREA OF SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC.
3. COORDINATE EQUIPMENT HOUSEKEEPING PAD DIMENSIONS AND LAYOUT WITH THE GENERAL CONTRACTOR BASED ON FINAL EQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERS IN ALL SUPPLY DUCT BRANCH TAPS DOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE TRANSFER "Z" BOOT DUCTS IN FULL HEIGHT WALLS WHERE A PLENUM RETURN SYSTEM IS UTILIZED. BOOTS SHALL BE SIZED TO MAINTAIN A MAXIMUM OF 400 FPM. PROVIDE A GRILLE FOR ALL TRANSFERS IN EXPOSED AREAS. RE: ARCH. OPENINGS OF "Z" BOOT DUCTS SHALL BE AT LEAST 12" CLEAR OF STRUCTURE.
7. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES.
GENERAL NOTES:8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW PRIOR TO ROUGH-IN.
9. PROVIDE THROUGH FACE BALANCING FOR ALL DIFFUSERS, REGISTERS, AND GRILLES ABOVE INACCESSIBLE AREAS.
10. PROVIDE TURNING VANES IN ALL 90° DUCT ELBOWS.
11. INSTALL EXPOSED DUCTWORK AS HIGH AS POSSIBLE.
13. ALL DUCT/PIPE PENETRATIONS THROUGH FIRE RATED/SMOKE RATED PARTITIONS SHALL BE CAULKED AND SEALED TO MEET THE RATING REQUIRED. REFER TO LIFE SAFETY DRAWINGS FOR FIRE/SMOKE RATING REQUIREMENTS.
14. PROVIDE ISOLATION VALVES AT EACH BRANCH LINE OFF OF RISER.
15. PROVIDE 3/4" BRANCH PIPING TO ALL TERMINAL UNITS, UNLESS NOTED OTHERWISE.
16. PROVIDE CONDENSATE DRAIN FROM ALL CHILLED WATER COILS AND DX EVAPORATOR COILS TO LAVATORY TAIL PIECE OR MECHANICAL ROOM FLOOR DRAIN. PROVIDE CONDENSATE PUMP FOR WALL MOUNTED UNITS AND CONCEALED UNITS THAT CANNOT BE GRAVITY DRAINED TO TERMINATION LOCATION
KEYNOTES
M2 SA DUCT DOWN.
M5 RA DUCT DOWN.
M30 MECHANICAL CONDENSATE PIPINGDOWN.
M31 SUPPLY AIR TO SIDE DISCHARGEPLENUM CURB BELOW ROOF TOPUNIT.
M32 RETURN AIR TO SIDE DISCHARGEPLENUM CURB BELOW ROOF TOPUNIT.
M33 ROOF TOP UNIT ON SPRING ISOLATEDSIDE DISCHARGE PLENUM CURB.
M34 COORDINATE ACCESS TO RTU WITHBOLLARDS.
POINTS LISTSYSTEM: MISCELLANEOUS POINTS
POINT DESCRIPTION
FIRE ALARM
OUTSIDE AIR - DB
OUTSIDE AIR - WB
SUMP PUMPS - HIGH WATER
SUMP PUMPS - STATUS
GENERAL NOTES:
1. NOT ALL VIRTUAL POINTS ARE INDICATED.
2. PROVIDE ALL POINTS REQUIRED TO ACHIEVE SEQUENCE OF OPERATION.
3. COORDINATE COMMUNICATION REQUIREMENTS FOR ELECTRICAL MONITORING WITH ELECTRICAL
TY
PE
DI
AI
AI
DI
DI
GR
AP
HIC
X
X
X
X
X
ALA
RM
H
F
TR
EN
D
CONV
5MIN
5MIN
COV
COV
REMARKS
REFERENCE
REFERENCE
EACH SUMP
EACH SUMP
SEQUENCE OF OPERATION GENERAL NOTES:
A GENERAL NOTES/LEGEND AND SEQUENCE OF OPERATIONNO SCALE
B DX SPLIT SYSTEM & HEAT PUMP CONTROLNO SCALE
D ELECTRIC UNIT HEATER DETAILNO SCALE
C VAV TERMINAL UNIT CONTROLNO SCALE
T
POINTS LISTPOINTS LIST
POINTS LIST
POINT DESCRIPTION
SPACE TEMPERATURE - SET POINT
SPACE TEMPERATURE
GENERAL NOTES:
1. NOT ALL VIRTUAL POINTS ARE INDICATED.
2. PROVIDE ALL POINTS REQUIRED TO ACHIEVE SEQUENCE OF OPERATION.
TY
PE
AI
AI
GR
AP
HIC
X
XA
LA
RM
H/L
TR
EN
D
5MIN
5MIN
REMARKS
FLOAT SWITCH IN DRAIN PAN DI H COV INTERLOCK WITH UNIT FOR SHUT DOWN
SYSTEM:
POINT DESCRIPTION
SPACE TEMPERATURE - SET POINT
SPACE TEMPERATURE
GENERAL NOTES:
1. NOT ALL VIRTUAL POINTS ARE INDICATED.
2. PROVIDE ALL POINTS REQUIRED TO ACHIEVE SEQUENCE OF OPERATION.
TY
PE
AI
AI
GR
AP
HIC
X
X
ALA
RM
H/L
TR
EN
D
5MIN
5MIN
REMARKS
SYSTEM: VAV BOX
POINT DESCRIPTION
ELECTRIC HEATER CONTROLLER
GENERAL NOTES:
1. NOT ALL VIRTUAL POINTS ARE INDICATED.
2. PROVIDE ALL POINTS REQUIRED TO ACHIEVE SEQUENCE OF OPERATION.
TY
PE
AO
AO
AI
GR
AP
HIC
X
X
ALA
RM
TR
EN
D
REMARKS
5MIN
5MIN
DAMPER POSITION INDICATOR
CONTROL DAMPER
SPACE TEMPERATURE AI X H/L 5MIN
X
DISCHARGE TEMPERATURE AI X H/L 5MIN
CONTROL SYMBOL LEGEND
AITESPACESENSORS
CONTROL SEQUENCE
A. THE DX SPLIT SYSTEM SHALL BE OPERATED AND CONTROLLED BY THE MANUFACTURER'S
CONTROLS. THE OWNER SHALL HAVE THE ABILITY TO SET THE SPACE TEMPERATURE SETPOINT
REMOTELY THROUGH THE BMS.THE BMS SHALL MONITOR THE SPACE TEMPERATURE AND
ALARM THE BMS WHEN SPACE TEMPERATURE IS OUT OF RANGE.
A. BMS CONTRACTOR SHALL COORDINATE ALL INTERFACE REQUIREMENTS.
B. ALTHOUGH EACH SEPARATE CONTROL DIAGRAM INDICATES AN OUTDOOR AIR
TEMPERATURE SENSOR AND OUTDOOR AIR HUMIDITY SENSOR, TC CONTRACTOR MAY
UTILIZE ONE OF EACH SENSOR AS A COMMON INPUT TO THE SYSTEM. COORDINATE
LOCATION WITH ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
C. PROVIDE INDIVIDUAL INPUTS OR OUTPUTS FOR EACH POINT LISTED IN THE POINTS LISTS.
PROVIDE ANY ADDITIONAL POINTS NOT LISTED IN THE POINTS LIST, BUT REQUIRED TO
MEET THE SEQUENCES OF OPERATION, AT NO ADDITIONAL COST TO THE OWNER. ALL
ANALOG OUTPUTS SHALL BE 4-20MA, 0-10VDC OR 0-20VDC UNLESS OTHERWISE
INDICATED. AO=ANALOG OUTPUT, AI=ANALOG INPUT, DO=DIGITAL (BINARY)
OUTPUT, DI=DIGITAL (BINARY) INPUT.
C. ALL SETPOINTS SHALL BE FULLY ADJUSTABLE AT THE OPERATOR WORKSTATION.
D. PROVIDE OVERRIDE CONTROL OF ALL POINTS AT THE OPERATOR WORKSTATION.
E. ALL CONTROL DIAGRAMS ARE IN EXTENSION OF THE EXISTING BASE BUILDING BMS.
F. BMS/ATC CONTRACTOR IS RESPONSIBLE FOR UNDERSTANDING ALL OWNER
STANDARDS. ANY MODIFICATIONS REQUIRED IN ORDER TO MEET THE OWNER
STANDARDS AT A LATER DATE SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER
OR THE PROJECT. REFER TO THE SPECIFICATIONS FOR OPERATOR WORKSTATION
REQUIREMENTS.
GENERAL
OCCUPANCY SCHEDULES:
A. THE BUILDING SHALL HAVE OCCUPIED AND UNOCCUPIED MODES THAT CAN BE SCHEDULED ON
A DAILY BASIS.
B. SCHEDULE SHALL BE ABLE TO BE SCHEDULED BY THE OPERATOR.
HIGH PRESSURE STEAM FLOW METER
=CT
DSP =
DPL =
DAT
DP
=
=
AVS =
CURRENT TRANSMITTER
HEAT RECOVERY COILDISCHARGE STATIC PRESSURE SENSOR
DIFFERENTIAL PRESSURE LOW
DISCHARGE AIR TEMPERATURE
DIFFERENTIAL PRESSURE HIGH
HRC =
MAT
OAD OUTSIDE AIR DAMPER
MOTOR STARTER
MIXED AIR TEMPERATURE
=
M =
=
EXHAUST AIR VALVE
FLOW INDICATOR
AIR VELOCITY SENSOR
FI
EAV
=
=
HPSF
HUMIDITY SENSORHS =
=
=
SAV = SUPPLY AIR VALVE
VFV VARIABLE FREQUENCY INPUT VALVE=
RAT
SDPR
S/S
=
=
=
PH = PH METER
RETURN AIR TEMPERATURE
SMOKE DAMPER
START - STOP
ST
SCV
STEAM TEMPERATURE=
STEAM CONTROL VALVE=
FLOW ELEMENTFE =
FLOW TRANSMITTERFT =
HAND OFF AUTOHOA
IT = CURRENT TRANSMITTER
PSH PRESSURE SENSOR HIGH=
SC = SPEED CONTROLER
AO
I/P CURRENT TO PNEUMATIC RELAY
ANALOG INPUT
ANALOG OUTPUT
ELECTRIC TO PNEUMATICEP =
=
AI =
=
DI
DO
DIGITAL INPUT
DIGITAL OUTPUT=
=CO =
CD =
CARBON DIOXIDE SENSOR
CONTROL DAMPER
END SWITCHES =
FLOW METER=FMMOISTURE TRANSMITTERMT =
DIFFERENTIAL PRESSURE INDICATORPDI =
DIFFERENTIAL PRESSURE TRANSMITTERPDT =
PRESSURE SENSOR LOWPSL =
SDD DUCT SMOKE DETECTOR=
2
C = CONTACT
=TE TEMPERATURE ELEMENT
FO FAIL OPEN=
FC FAIL CLOSED=
PRESSURE TRANSMITTER=PT
STATUSS =
RH = REHEAT COIL
CC = COOLING COIL
AFS = AIR FLOW MEASURING STATION
HUMIDITY SENSOR HIGH LIMITHSH =
=CV CONTROL VALVE
F FAULT=
GENERAL EXHAUST VALVEGEV =
HEATING COILHC =
RAD = RETURN AIR DAMPEREPO EMERGENCY POWER OFF=
EC
START/STOP
SF
SA
ELECTRIC UNIT HEATER TEMPERATURE CONTROL
A. THE UNIT HEATER IS CONTROLLED BY A SPACE THERMOSTAT.
B. LOCAL CONTROLLER SHALL CYCLE FAN & ENERGIZE ELECTRIC HEAT TO MAINTAIN SPACE
SETPOINT.
SPACETHERMOSTAT
AI
TE
SA
AI
CD
AO
CD
AITEHC
AO
SPACE TEMPERATURE
A. CONFIGURATION: REFER TO SCHEDULE.
VAV TERMINAL UNIT CONTROL:
B. OCCUPIED MODE: 1. WHEN THE AHU IS IN THE OCCUPIED MODE, THE PRIMARY AIR DAMPER AND ELECTRIC HEAT SHALL
C. UNOCCUPIED MODE: 1. WHEN THE AHU IS IN THE UNOCCUPIED MODE, THE UNIT SHALL BE OFF AND HEATING SHALL BE
MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SETPOINT
DEACTIVATED.
D. NIGHT SETBACK MODE: 1. TERMINAL UNIT SHALL OPERATE NORMALLY WHEN AHU IS IN OPERATIONE. MORNING WARM-UP MODE: 1. PRIMARY AIR VALVES SHALL BE AT MINIMUM POSITION AND ELECTRIC HEAT ACTIVATED. 2. REVERT TO OCCUPIED MODE WHEN ALL SPACE STATS HAVE REACHED OCCUPIED HEATING SETPOINT.F. ELECTRIC HEAT CONTROL: 1. THE HEATING STAGES SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.THE HEATING
SHALL BE DEACTIVATED IF THE PRIMARY AIR DAMPERS ARE OPEN PAST THEIR MINIMUM POSITION. THE HEATINGSHALL BE DEACTIVATED IF THE AHU FAN IS OFF.
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:44
:00
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M6.00
MECHANICAL CONTROLDIAGRAM
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1/8" = 1'-0" 2MEC CONTROLS - Dependent 2
JAN 09, 2019 PERMIT & BID
01-09-2019
EXHAUST FANS:
VAV AIR HANDLING UNIT:
VAV AIR HANDLING UNIT:
B EXHAUST FANS
NO SCALE
A ROOFTOP UNIT CONTROL
NO SCALE
C AHU C-1
NO SCALE
SYSTEM POINTS LIST
EXHAUST FAN
SYSTEM POINT DESCRIPTION
INPUT
ANALOG
OUTPUT
BINARY
INPUT OUTPUT ALARMS
NOTES
SYSTEM POINTS LIST
VAV AIR HANDLER WITH OA TRACKING
SYSTEM POINT DESCRIPTION
ANALOG
INPUT OUTPUT
BINARY
INPUT OUTPUT ALARMS
SYSTEM POINTS LIST
AIR HANDLER WITH OA TRACKING
SYSTEM POINT DESCRIPTION
ANALOG
INPUT OUTPUT
BINARY
INPUT OUTPUT ALARMS
S
T
CO2
T T
EXHAUST FANS
INTERLOCKED DAMPERS (2-POSITION)
GENERAL NOTES:G
RA
PH
IC
X
1. SEE SCHEDULES FOR QUANTITIES
2. POINTS ABOVE ARE NOT NECESSARILY REFLECTED IN CONTROL DIAGRAMS.T
EM
PE
RA
TU
RE
PR
ES
SU
RE
RE
LA
TIV
E H
UM
IDIT
YK
WG
PM
CF
MP
PM
PE
RC
EN
TP
ER
CE
NT
RLA
DD
C (
4-2
0 M
A,
0-1
0 V
DC
)
SE
TP
OIN
T A
DJ.
ST
AT
US
ON
/OF
F
X
ALA
RM
ST
AT
US
ST
AT
US
OP
EN
/CLS
D.
ST
AT
US
RE
LA
Y
TIM
ED
OV
ER
RID
E
OF
F/O
N
X
OP
EN
/CLO
SE
D
X
LO
CK
OU
TE
NA
BLE
/DIS
AB
LE
LIM
IT W
AR
NIN
GH
IGH
AN
ALO
GLO
W A
NA
LO
GB
INA
RY
PR
OO
FS
EN
SO
R F
AIL
FLO
W F
AIL
CO
MM
FA
IL
X
DIA
GN
OS
TIC
SF
LO
W O
VE
RR
IDE
X
3. PROVIDE ADDITIONAL POINTS REQUIRED IN DIAGRAMS OR SEQUENCES.
CONTROL PANEL
SUPPLY AIR FAN
SUPPLY AIR FAN VFD
SUPPLY AIR TEMPERATURE
BUILDING STATIC PRESSURE
COOLING (EACH STAGE)
OA DAMPER
SMOKE DETECTOR CONTACTS
SPACE TEMPERATURE
AHU ALARM STATUS
TIMED OVERRIDE
OUTSIDE AIR TEMPERATURE
RELIEF AIR DAMPER
GENERAL NOTES:
GR
AP
HIC
X
1. SEE SCHEDULES FOR QUANTITIES
TE
MP
ER
AT
UR
E
X
X
X
PR
ES
SU
RE
X
RE
LA
TIV
E H
UM
IDIT
YK
WG
PM
CF
MP
PM
PE
RC
EN
T
X
X
PE
RC
EN
T R
LA
DD
C (
4-2
0 M
A,
0-1
0 V
DC
)
X
X
SE
TP
OIN
T A
DJ.
X
RE
FR
IGE
RA
NT
ST
AT
US
ON
/OF
F
X
FIL
TE
R S
TA
TU
S
ST
AT
US
OP
EN
/CLS
D.
ST
AT
US
ALA
RM
X
2
X
TIM
ED
OV
ER
RID
E
X
OF
F/O
N
X
OP
EN
/CLO
SE
DLO
CK
OU
TE
NA
BLE
/DIS
AB
LE
LIM
IT W
AR
NIN
GH
IGH
AN
ALO
G
X
X
X
LO
W A
NA
LO
G
X
X
X
BIN
AR
Y
2
PR
OO
FS
EN
SO
R F
AIL
X
X
X
X
X
FLO
W F
AIL
CO
MM
FA
IL
X
X
DIA
GN
OS
TIC
S
X
FLO
W O
VE
RR
IDE
X
X
X
X
X
X
X
X
X
X
X
X
2. SMOKE DETECTOR HARD WIRED FOR FAN SHUT-DOWN AND FIRE ALARM.
3. PROVIDE ADDITIONAL POINTS REQUIRED IN DIAGRAM OR SEQUENCE.
NOTIFICATION PER SECTION DIV 23 & 26.
X XX
CARBON DIOXIDE SENSOR XX
X
CONTROL PANEL
SUPPLY FAN
SUPPLY AIR TEMPERATURE
HEATING CONTROLLER
COOLING (EACH STAGE)
OA DAMPER
SPACE TEMPERATURE
AHU ALARM STATUS
TIMED OVERRIDE
OUTSIDE AIR TEMPERATURE
RELIEF AIR DAMPER
GENERAL NOTES:
GR
AP
HIC
X
1. SEE SCHEDULES FOR QUANTITIES
TE
MP
ER
AT
UR
E
X
X
X
PR
ES
SU
RE
RE
LA
TIV
E H
UM
IDIT
YK
WG
PM
CF
MP
PM
PE
RC
EN
T
X
PE
RC
EN
T R
LA
DD
C (
4-2
0 M
A,
0-1
0 V
DC
)
X
SE
TP
OIN
T A
DJ.
X
RE
FR
IGE
RA
NT
ST
AT
US
ON
/OF
F
X
FIL
TE
R S
TA
TU
S
ST
AT
US
OP
EN
/CLS
D.
ST
AT
US
ALA
RM
X
TIM
ED
OV
ER
RID
E
X
OF
F/O
N
OP
EN
/CLO
SE
DLO
CK
OU
TE
NA
BLE
/DIS
AB
LE
LIM
IT W
AR
NIN
GH
IGH
AN
ALO
G
X
X
LO
W A
NA
LO
G
X
X
BIN
AR
YP
RO
OF
SE
NS
OR
FA
IL
X
X
X
X
FLO
W F
AIL
CO
MM
FA
IL
X
X
DIA
GN
OS
TIC
SF
LO
W O
VE
RR
IDE
X
X
X
X
X
X
X
X
X
X
2. SMOKE DETECTOR HARD WIRED FOR FAN SHUT-DOWN AND FIRE ALARM.
3. PROVIDE ADDITIONAL POINTS REQUIRED IN DIAGRAM OR SEQUENCE.
NOTIFICATION PER SECTION DIV 23 & 26.
X
X
X
X
X
X
X
XX XRETURN AIR DAMPER
RELIEF AIR FAN X XX
DUCT STATIC PRESSURE X X X XX
RELIEF AIR FAN
RELIEF AIR FAN VFD X X
X
X X
X
X
X
X
ECONOMIZER MODE DAMPER XX X
FILTER DIFFERENTIAL PRESSURE X X X XX
SUPPLY AIR FLOWRATE X X X X X
OUTSIDE AIR FLOWRATE X X X X X
RELIEF AIR FLOWRATE X X X X X
RTU C-1
UNIT OUTSIDE AIRSETPOINT (CFM)
OUTSIDE AIRSETPOINT (CFM)
MINIMUM
RTU G-1
2,500
1,300
500
400
X
EA
EA
EXHAUST FAN
S/S
CSEN
DI
A. FAN SHALL OPERATE DURING OCCUPIED HOURS. DURING OCCUPIED HOURS,
EXHAUST DAMPER SHALL OPEN AND EXHAUST FAN SHALL BE ENERGIZED. FAN SHALL
DE-ENERGIZE WHEN SYSTEM IS IN UNOCCUPOED MODE.
B. SYSTEM CAN BE MANUALLY ENERGIZED BY MANUAL OVERRIDE SWITCH.
C. MONITORED BY BMS.
DO
M
2-POSITION LOW LEAKDAMPER INTERLOCKEDWITH FAN CIRCUIT.DAMPER(S) ARE OPENWHEN FAN IS ON.
DO
MANUALOVERRIDESWITCH WHEREINDICATED
AI
OA
AO
M
TTA
SF
CSEN
TT
DI
SD
DI AI AO
S
AI
DPT
SPACE
SPT
DI
VFDAO
DI
DO
AI
OUTSIDE AIR
F
AI
SA
HARD WIRE TO FANSTART CIRCUIT
DX
CC
A. CONFIGURATION, RE: SCHEDULE
B. OCCUPIED MODE:
1. WHEN THE AHU IS IN THE OCCUPIED MODE, THE SUPPLY FANS SHALL OPERATE
CONTINUOUSLY. THE SUPPLY FAN VFD SHALL MODULATE TO MAINTAIN THE DUCT STATIC
PRESSURE. DX COOLING AND HOT GAS REHEAT SHALL MODULATE TO MAINTAIN SPACE
TEMPERATURE (ADJ) AND HUMIDITY (ADJ).
C. UNOCCUPIED MODE
1. WHEN THE AHU IS IN THE UNOCCUPIED MODE, THE SUPPLY FANS SHALL BE OFF. THE
OUTSIDE AIR DAMPER SHALL BE CLOSED, AND DX COOLING SHALL BE DE-ENERGIZED.
D. FAN SAFETY CONTROLS:
1. DE-ENGERGIZE THE SUPPLY FANS WHENEVER EITHER SMOKE DETECTOR HAS
TRIPPED OR A FAN STATUS INDICATES A FAILURE (AFTER A TWO MINUTE DELAY). THE
SMOKE DETECTORS AND THE FAN FAILAURES REQUIRE A MANUAL RESET.
2. DE-ENERGIZE THE SUPPLY FANS WHEN THE DISCHARGE STATIC PRESSURE HIGH-LIMIT
REACHES 1.5 INCHES WC (ADJ).
3. ALARM THE BMS WITH THE APPROPRIATE ALARM MESSAGE.
F. TIMED OVERRIDE
1. PROVIDE A TWO HOUR TIMED OVERRIDE VIA SWITCH AT SPACE SENSORS TO RETURN RTU
TO OCCUPIED MODE.
G. ECONOMIZER OPERATION
1. WHEN THE DIFFERENCE BETWEEN THE OA ENTHALPY AND THE REQUIRED SA ENTHALPY IS LESS THANTHE DIFFERENCE BETWEEN RA AND SA ENTHALPY, THE AHU CONTROLS SHALL ENABLE
H. DX COOLING COIL CONTROL
1. THE CONDENSING UNIT SHALL MODULATE TO MAINTAIN THE DAT. THE CONDENSING UNIT
SHALL BE DE-ENERGIZED IF THE AHU IS IN HEATING MODE, THE FANS ARE OFF, OR THE
DISCHARGE AIR SENSORS HAVE FAILED.
M
INTAKE HOOD DAMPER
E. VFD CONTROL
1. WHEN THE SUPPLY FAN IS ENERGIZED, THE VFD SHALL SLOWLY RAMP UP TO SETPOINT AND
MODULATE THE OA DAMPER TO MAINTAIN THE PROPER BUILDING STATIC PRESSURE SETPOINT (0.05",
ADJUSTABLE). REFER TO FLOOR PLANS FOR STATIC PRESSURE SENSOR LOCATIONS.
A0
M
BUILDING STATICPRESSURE SENSOR
THE ECONOMISER MODE. THE BAS SHALL CONTINOUSLY MONITOR THE OA, SA & RA ENTHALPY IN
ORDER TO ACTIVATE THE OPERATING MODE THAT IS MOST ENERGY EFFICIENT.
AITE
SPACE TEMPERATURE
RA
AI
AI
OA
A0
M
TTA
SF
CSEN
TT
DI
SPT
DI
AI
OUTSIDE AIR
F
SA
DX
CC
ELECTRIC
HC
A. CONFIGURATION, RE: SCHEDULE
B. OCCUPIED MODE:
1. WHEN THE FCU IS IN THE OCCUPIED MODE, THE SUPPLY FANS SHALL OPERATE
CONTINUOUSLY. THE SUPPLY FAN VFD SHALL MODULATE TO MAINTAIN THE DUCT STATIC
PRESSURE. DX COOLING SHALL MODULATE TO MAINTAIN SPACE
TEMPERATURE (ADJ) AND HUMIDITY (ADJ). THE ELECTRIC HEATING SHALL
MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE (ADJ). ELECTRIC
HEATING AND DX COOLING SHALL NOT OPERATE SIMULTANEOUSLY.
C. UNOCCUPIED MODE
1. WHEN THE FCU IS IN THE UNOCCUPIED MODE, THE SUPPLY FANS SHALL BE OFF. THE
OUTSIDE AIR DAMPER SHALL BE CLOSED, DX COOLING SHALL BE DE-ENERGIZED, AND
ELECTRIC HEATING SHALL BE DE-ENERGIZED.
D. FAN SAFETY CONTROLS:
1. DE-ENGERGIZE THE SUPPLY FANS WHENEVER EITHER SMOKE DETECTOR HAS
TRIPPED OR A FAN STATUS INDICATES A FAILURE (AFTER A TWO MINUTE DELAY). THE
SMOKE DETECTORS AND THE FAN FAILAURES REQUIRE A MANUAL RESET.
2. DE-ENERGIZE THE SUPPLY FANS WHEN THE DISCHARGE STATIC PRESSURE HIGH-LIMIT
REACHES 1.0 INCHES WC (ADJ).
3. ALARM THE BMS WITH THE APPROPRIATE ALARM MESSAGE.
E. TIMED OVERRIDE
1. PROVIDE A TWO HOUR TIMED OVERRIDE VIA SWITCH AT SPACE SENSORS TO RETURN RTU
TO OCCUPIED MODE.
F. ECONOMIZER OPERATION
1. WHEN THE DIFFERENCE BETWEEN THE OA ENTHALPY AND THE REQUIRED SA ENTHALPY IS LESS THANTHE DIFFERENCE BETWEEN RA AND SA ENTHALPY, THE FCU CONTROLS SHALL ENABLE
G. DX COOLING COIL CONTROL
1. THE CONDENSING UNIT SHALL MODULATE TO MAINTAIN THE DAT. THE CONDENSING UNIT
SHALL BE DE-ENERGIZED IF THE FCU IS IN HEATING MODE, THE FANS ARE OFF, OR THE
DISCHARGE AIR SENSORS HAVE FAILED.
THE ECONOMIZER MODE. THE BAS SHALL CONTINOUSLY MONITOR THE OA, SA & RA ENTHALPY IN
ORDER TO ACTIVATE THE OPERATING MODE THAT IS MOST ENERGY EFFICIENT.
RA
A0
M
EA
A0
M
MIXINGPLENUM
M
AO
RELIEFAIR
M
RELIEFAIR
2. RETURN AIR DAMPER WILL CLOSE AND RELIEF EXHAUST DAMPER SHALL OPEN. RELIEF EXHAUST
FAN SHALL MODULATE TO MAINTAIN PROPER STATIC PRESSURE SETPOINT (0.05", ADJ.).
VFDAO
DI
DO
AI
DP
LOCATE 2_3 OF THE
WAY DOWN THE
LONGEST DUCT RUN.
AI
SPACE TEMPERATURE
AI
AFS
AI
AFS
AI
AFS
I. DEMAND CONTROL VENTILATION.
1. THE CONTROLLER SHALL MONITOR RETURN AIR CO2 CONCENTRATION.
2. IF THE CO2 LEVEL FOR RETURN AIR EXCEED 850 PPM (ADJ.), ALARM THE BMS.
3. INCREASE OUTSIDE AIR QUANTITIES (SUBJECT TO MAINTAINING LEAVING AIR TEMPERATURE) TO
4. IF RETURN AIR CO2 IS BELOW 700 PPM (ADJ.), AND RELIEF DAMPERS ARE NOT CLOSED, MINIMUM
MAINTAIN 850 PPM IN RETURN AIR DUCT.
OUTSIDE AIR SETPOINT SHALL BE INCREMENTALLY REDUCED. SET POINT TO RAISE IF CO2 LEVELS
RISE ABOVE 750 PPM (ADJ.) OR IF SPACE STATIC PRESSURE CANNOT BE MAINTAINED. REFER TO
SCHEDULE BELOW FOR LOWEST MINIMUM OUTSIDE AIR.
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:44
:00
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M6.01
MECHANICAL CONTROLDIAGRAM
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1/8" = 1'-0" 1MEC CONTROLS - Dependent 1
JAN 09, 2019 PERMIT & BID
01-09-2019
VAV AIR HANDLING UNIT:
A AHU C-2
NO SCALE
SYSTEM POINTS LIST
VAV AIR HANDLER WITH OA TRACKING
SYSTEM POINT DESCRIPTION
ANALOG
INPUT OUTPUT
BINARY
INPUT OUTPUT ALARMS
T
CO2
CONTROL PANEL
SUPPLY AIR FAN
SUPPLY AIR FAN VFD
SUPPLY AIR TEMPERATURE
BUILDING STATIC PRESSURE
COOLING (EACH STAGE)
OA DAMPER
SMOKE DETECTOR CONTACTS
SPACE TEMPERATURE
AHU ALARM STATUS
TIMED OVERRIDE
OUTSIDE AIR TEMPERATURE
RETURN AIR DAMPER
GENERAL NOTES:
GR
AP
HIC
X
1. SEE SCHEDULES FOR QUANTITIES
TE
MP
ER
AT
UR
E
X
X
X
PR
ES
SU
RE
X
RE
LA
TIV
E H
UM
IDIT
YK
WG
PM
CF
MP
PM
PE
RC
EN
T
X
X
PE
RC
EN
T R
LA
DD
C (
4-2
0 M
A,
0-1
0 V
DC
)
X
X
SE
TP
OIN
T A
DJ.
X
RE
FR
IGE
RA
NT
ST
AT
US
ON
/OF
F
X
FIL
TE
R S
TA
TU
S
ST
AT
US
OP
EN
/CLS
D.
ST
AT
US
ALA
RM
X
2
X
TIM
ED
OV
ER
RID
E
X
OF
F/O
N
X
OP
EN
/CLO
SE
DLO
CK
OU
TE
NA
BLE
/DIS
AB
LE
LIM
IT W
AR
NIN
GH
IGH
AN
ALO
G
X
X
X
LO
W A
NA
LO
G
X
X
X
BIN
AR
Y
2
PR
OO
FS
EN
SO
R F
AIL
X
X
X
X
X
FLO
W F
AIL
CO
MM
FA
IL
X
X
DIA
GN
OS
TIC
S
X
FLO
W O
VE
RR
IDE
X
X
X
X
X
X
X
X
X
X
X
X
2. SMOKE DETECTOR HARD WIRED FOR FAN SHUT-DOWN AND FIRE ALARM.
3. PROVIDE ADDITIONAL POINTS REQUIRED IN DIAGRAM OR SEQUENCE.
NOTIFICATION PER SECTION DIV 23 & 26.
X XX
X
RETURN AIR FAN
RETURN AIR FAN VFD X X
X
X X
X
X
X
X
ECONOMIZER MODE DAMPER XX X
FILTER DIFFERENTIAL PRESSURE X X X XX
SUPPLY AIR FLOWRATE X X X X X
OUTSIDE AIR FLOWRATE X X X X X
RETURN AIR FLOWRATE X X X X X
AHU C-2
UNIT OUTSIDE AIRSETPOINT (CFM)
OUTSIDE AIRSETPOINT (CFM)
MINIMUM
3,000 600
CARBON DIOXIDE SENSOR XX X
ELECTRIC DUCT HEATER X XX
SUPPLY AIR TEMPERATURE (HEATING) X X X XX
AI
OA
AO
M
TTA
SF
CSEN
TT
DI
SD
DI AI AO
S
AI
DPT
SPACE
VFDAO
DI
DO
AI
OUTSIDE AIR
F
AI
SA
HARD WIRE TO FANSTART CIRCUIT
DX
CC
A. CONFIGURATION, RE: SCHEDULE
B. OCCUPIED MODE:
1. WHEN THE AHU IS IN OCCUPIED MODE, THE SUPPLY AND RETURN FANS SHALL OPERATE
CONTINUOUSLY. THE SUPPLY AND RETURN VFD'S SHALL MODULATE SIMULTANEOUSLY
TO REACH DESIGN FLOW RATE. FANS SHALL RAMP UP SLOWLY. DX COIL SHALL MODULATE TO
MAINTAIN SPACE TEMPERATURE (ADJ.) AND HUMIDITY (ADJ.). ELECTRIC DUCT HEATER SHALL
C. UNOCCUPIED MODE
1. WHEN THE AHU IS IN THE UNOCCUPIED MODE, THE SUPPLY AND RETURN FANS SHALL BE OFF. THE
OUTSIDE AIR DAMPER SHALL BE CLOSED, AND DX COOLING SHALL BE DE-ENERGIZED.
D. FAN SAFETY CONTROLS:
1. DE-ENGERGIZE THE SUPPLY FANS WHENEVER EITHER SMOKE DETECTOR HAS
TRIPPED OR A FAN STATUS INDICATES A FAILURE (AFTER A TWO MINUTE DELAY). THE
SMOKE DETECTORS AND THE FAN FAILAURES REQUIRE A MANUAL RESET.
2. DE-ENERGIZE THE SUPPLY FANS WHEN THE DISCHARGE STATIC PRESSURE HIGH-LIMIT
REACHES 3.0 INCHES WC (ADJ).
3. ALARM THE BMS WITH THE APPROPRIATE ALARM MESSAGE.
F. TIMED OVERRIDE
1. PROVIDE A TWO HOUR TIMED OVERRIDE VIA SWITCH AT SPACE SENSORS TO RETURN RTU
TO OCCUPIED MODE.
G. ECONOMIZER OPERATION
1. WHEN THE DIFFERENCE BETWEEN THE OA ENTHALPY AND THE REQUIRED SA ENTHALPY IS LESS THANTHE DIFFERENCE BETWEEN RA AND SA ENTHALPY, THE AHU CONTROLS SHALL ENABLE
H. DX COOLING COIL CONTROL
1. THE CONDENSING UNIT SHALL MODULATE TO MAINTAIN THE DAT. THE CONDENSING UNIT
SHALL BE DE-ENERGIZED IF THE AHU IS IN HEATING MODE, THE FANS ARE OFF, OR THE
DISCHARGE AIR SENSORS HAVE FAILED.
E. VFD CONTROL
1. WHEN THE SUPPLY AND RETURN FANS ARE ENERGIZED, THE VFD'S SHALL SLOWLY RAMP UP TO SETPOINT AND
MODULATE THE OA DAMPER TO MAINTAIN THE PROPER BUILDING STATIC PRESSURE SETPOINT (0.05",
ADJUSTABLE). REFER TO FLOOR PLANS FOR STATIC PRESSURE SENSOR LOCATIONS.
A0
M
BUILDING STATICPRESSURE SENSOR
THE ECONOMISER MODE. THE BAS SHALL CONTINOUSLY MONITOR THE OA, SA & RA ENTHALPY IN
ORDER TO ACTIVATE THE OPERATING MODE THAT IS MOST ENERGY EFFICIENT.
AITE
SPACE TEMPERATURE
RA
AI
M
AOM
RELIEFAIR
2. RETURN AIR DAMPER WILL CLOSE AND RELIEF EXHAUST DAMPER SHALL OPEN. RELIEF EXHAUST
FAN SHALL MODULATE TO MAINTAIN PROPER STATIC PRESSURE SETPOINT (0.05", ADJ.).
VFDAO
DI
DO
AI
DP
AI
AFS
AI
AFS
RF
I. DEMAND CONTROL VENTILATION.
1. THE CONTROLLER SHALL MONITOR RETURN AIR CO2 CONCENTRATION.
2. IF THE CO2 LEVEL FOR RETURN AIR EXCEED 850 PPM (ADJ.), ALARM THE BMS.
3. INCREASE OUTSIDE AIR QUANTITIES (SUBJECT TO MAINTAINING LEAVING AIR TEMPERATURE) TO
4. IF RETURN AIR CO2 IS BELOW 700 PPM (ADJ.), AND RELIEF DAMPERS ARE NOT CLOSED, MINIMUM
MAINTAIN 850 PPM IN RETURN AIR DUCT.
OUTSIDE AIR SETPOINT SHALL BE INCREMENTALLY REDUCED. SET POINT TO RAISE IF CO2 LEVELS
RISE ABOVE 750 PPM (ADJ.) OR IF SPACE STATIC PRESSURE CANNOT BE MAINTAINED. REFER TO
SCHEDULE BELOW FOR LOWEST MINIMUM OUTSIDE AIR.
ELECTRIC
DUCT HEATER
AI
TT
MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE (ADJ.). ELECTRIC HEATING AND
DX COOLING SHALL NOT OPERATE SIMULTANEOUSLY.
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 9
:23
:49
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M6.02
MECHANICAL CONTROLDIAGRAM
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
01-09-2019
PROVIDE MIN. AIR FLOW & MAINTENANCE ACCESS PER MFR DIRECTIONS:
TYPICAL ALL SIDES & TOP OF UNIT
12
CONDENSING UNIT
COMPRESSOR ACCESS
REFRIGERANT GAUGE CONNECTIONS.
BACK-SEATED REFRIGERANTVALVE.
SIGHT GLASS WITH MOISTURE INDICATOR.
SUCTION LINE WITH INSULATION.
ROOF CAP AND CURB.
CONDUIT - POWER AND CONTROL.
REFRIGERANT LIQUID LINE
FULL PERIMETER ROOF CURB WITH SHEET METAL CAP.
CONDENSER COIL.
FAN GUARD.
VIBRATION ISOLATORS.
FLASH PENETRATION WATER TIGHT SEE DETAIL.
1.
2.
NOTES :
REFRIGERANT LIQUID LINE & SUCTION LINE TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.
PROVIDE OIL TRAPS AT RS LOW POINTS AND/OR PITCH HORIZONTAL PIPING FOR PROPER OIL RETURN.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
23
4
5
9
6
14
78
10
13
11
3
DETAIL NOTES :
REMOTE CEILINGOPERATOR WHERE
DAMPER ISINACCESSIBLE
AIR FLOW
W
DAMPERS SHOULD NOTBE INSTALLED CLOSERTHAN TWO DUCT WIDTHSTO ELBOWS ORINTERSECTIONS
NOTE:
45
L
VOLUME DAMPERPROVIDE CONCEALEDCEILING DAMPERREGULATOR
L=1/4 W (4" MIN.)
NOTE:
1. ACOUSTICAL TILE CEILING SHOWN. GYP. BOARD CEILING SIMILAR.
NOTES:
SHEET METALBAND
ACOUSTICAL TILECEILING
INSULATED FLEXIBLEDUCT. MAX. 7'
VD
FLUORESCENT COLOREDMARKER TAPE
DUCT INSULATION
CLEANOUTS CAP
SLOPE TO NEAREST FLOORDRAIN (MECHANICAL ROOM)JANITORS CLOSET, OR OTHERAPPROVED RECEPTOR
FAN STATIC PRESSURE +1"DRAIN PAN
GIRANDOLE OR FAN COIL
NOTE:
1. INSULATE CONDENSATE DRAIN WHEN ABOVE CEILINGS.
DRAW THROUGH COIL BLOW THROUGH COIL
A B
SEE NOTE 1 SEE NOTE 2 SEE NOTE 1SEE NOTE 2
AB
DRAIN LINE SHALL BE ATLEAST THE SAME SIZE AS
THE NIPPLE ON THE DRAIN PAN
PITCH DOWNTOWARD DRAIN
AIR HANDLING UNIT
DRAIN PAN
NOTES:1. STATIC PRESSURE OF AIR HANDLING UNIT PLUS 1".
2. 2" MINIMUM.
1"B
A 2"
TOOPEN DRAIN
RECEPTOR ORFLOOR SINK
OPEN TO ATMOSPHERE
EXHAUST AIR DUCT
ACCESS DOOR
ROOF
GRAVITY BACKDRAFTDAMPER
SEE ARCH. DWG. FOR FLASHING DETAILS
PRE-FABRICATED ROOF CURB
1. PROVIDE BACKDRAFT DAMPER AT AN DISCHARGE
UPBLAST
NOTE:
TRUSS ANGLES, TOPCHORD
2X2X1/4" STEEL TEE2 1/2" LONG W/1/2"THICK PLATE WELDEDAT TOP AND BOLTEDTO TRUSS W(2) 3/8"DIA. BOLTS
DUCT SUPPORTAT 10'-0" O.C.@ EACH TRUSS
SECTION A-A
A
STEEL TEEW/PLATE AT TRUSS
DUCT 24" DIA. TO 30"
STRAP
A
SECTION/ELEVATION
NOTE:
1. SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION.
1/8" THICK FORMEDGALV. MLT. SADDLE2" W (PLACED OVERSTRAP AND BOLTED
TO TRUSS) W/(2)
16 GA FORMEDGALV METAL BAND1/4" W BOLTED TO
BRACKET & TRUSSW 1/2 DIA. BOLT
4"
SOLDER COUNTER FLASHINGCOLLAR TO COUPLING
FLASHING
MINIMUM 4" OVERLAP
TOP OF ROOFING
ROOF DECK
SEE ARCH. DETAILS FOR ALL FLASHING REQUIREMENTS &MAINTAIN ROOFING WARRANTY
FOR UNITS 5 TONS AND SMALLER
NEOPRENE VIBRATIONISOLATION PAD
OIL TRAP (TYP)
FILTER-DRIER (FORTYPE AND LOCATIONSEE SPEC)
VIBRATION ISOLATOR
SECURE CONDENSINGUNIT TO SUPPORT
EXPANSION VALVE
COOLING COILCONDENSING UNIT
LIFT TRAP (EVERY25 FT. OF RISE) LIQUID SITE GLASS
REVERSE TRAP
SEE PLAN FORCONTINUATIONSLOPE SUCTION LINE
DOWN TOWARDS CONDENSINGUNIT. (TYPICAL)
NOTE:
ROOF
SEE ARCH.DRAWING FORFLASHING AND
ROOFING DETAIL
FACTORYPRE-FABRICATED
LEVELED ROOFCURB
CONTINUOUS UNITSUPPORT MEMBER
EPDM WEATHER SEAL
SPRING ISOLATORHOUSING WITHADJUSTABLE SPRINGSNEOPRENE SPRINGCUPS AND ALLDIRECTIONAL SEISMIC
RESTRAINTS WITH 1/4"THICK NEOPRENEBUSHINGS
CONTINUOUS STEEL RAIL
2x4 WOOD NAILER
STRUCTURAL SUPPORTS(COORDINATE WITHSTRUCTURAL DRAWING)
INSULATION
CONTINUOUSGALVANIZEDSEALER STRIP(TOP AND BOTTOM)
ROOFTOP AC UNIT
CLOSED CELLNEOPRENEAIRSEAL
FOR ANCHORAGEDETAIL, SEE
STRUCTURAL DRAWING
ALLOW FOR ACCESS
BOX OUTLET SIZE
SIZE ON PLAN
CONICAL OR 45°TAP
D
SHEET METAL ELBOW ONLY
2'-0" MAX. STRAIGHT NON-COMPRESSED FLEX DUCT.
ALLOW FOR ACCESS
4'-0" TO FIRST TAKEOFF
4 D
REMOVABLE COREFILTER DRYER
LIQUID DN
HOT GAS
SUCTIONDN
MOISTURE INDICATING SIGHT GLASS
CHARGING/GAUGE/RECOVERY PORT
CONDENSING UNIT
VIBRATION ISOLATION PADS
FULL PERIMETER ROOF CURB W/FLASHING & COUNTER
FLASHING (RE: ARCH. DIV.)
ISOLATION VALVE (TYP)
INSULATE SUCTION LINEPER SPEC.
SIGHT GLASS
DOUBLE RISER ASRECOMMENDED BYMANUFACTURER
ISOLATION VALVE
SEE SPEC. EXPANSION VALVE
SEE SPEC.
EVAPORATOR COIL
INSULATE EXPANSION VALVE BULB
GATE VALVE (TYP)
SIZE AND INSTALL REFRIG. LINESACCORDING TO MANUFACTURER'SSPECIFICATIONS.
1.
2. PROVIDE OIL TRAP AND INVERTED TRAP AT ALL RISERS. ALSO PROVIDEDOUBLE RISER IF NECESSARY FOR PROPER OIL RETURN AT LOWEST STEP OF COMPRESSOR UNLOADING.
PITCH REFRIGERANT LINES INDIRECTION INDICATED @ 1/2" PER 10FT.
3.
ALL CONNECTIONS SHALL BE BRAZEDINCLUDING CONNECTIONS AT COIL AND CONDENSING UNIT.
4.
NOTES:
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:44
:01
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M7.00
MECHANICAL DETAILS
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
NO SCALE1
AIR-COOLED CONDENSING UNIT
NO SCALE2
BRANCH DUCT TAKE-OFF DETAIL
NO SCALE3
CEILING DIFFUSER CONNECTION
NO SCALE4
CONDENSATE DRAIN DETAIL
NO SCALE5
DRAIN AND TRAP FROM AIR HANDALINGUNIT
NO SCALE7
EXHAUST AIR FAN INSTALLATION (FORGENERAL APPLICATION)
NO SCALE6
GYM MAIN DUCT SUPPORT
NO SCALE8
PIPE/ROOF PENETRATION
NO SCALE9
REFRIGERANT PIPING DETAIL
NO SCALE10
ROOFTOP AC UNIT SUPPORT &VIBRATION ISOLATION SYSTEM
NO SCALE11
VAV BOX DETAIL
NO SCALE12
SPLIT SYSTEM AC UNIT DETAIL
JAN 09, 2019 PERMIT & BID
01-09-2019
ROUND OR RECT.DUCT AS SHOWN
ON PLAN
OPPOSED BLADE DAMPERIF SHOWN ON SCHEDULE
MIN 6" BOOT.WITH LINER
SURFACE MOUNTFRAME
SEE SCHEDULEFOR TYPE OFREGISTER/GRILLE
45 INLET
AIRFLOW
ROUND SUPPLY DUCTSEE PLAN FOR SIZE
HORIZONTALLINE
15°
TURN BOOT COLLAR IN TOPROVIDE SMOOTH AIR FLOW
TO GRILLE.
16 GA. BOOT.SECURE TO DUCTAIRTIGHT
SUPPLY GRILLEFOR DETAILSSEE PLANS
OPPOSED BLADEDAMPER
TRANSFER AIR DUCT
RETURN AIR TRANSFER BOOT
1" THICK LINEDDUCT
TRANSFER AIRGRILL (TYP.)
1" THICK LINEDDUCT
SHT. MTL. NOSING OR APPROVEDSEALANT AT EXPOSED EDGES (TYP)
CAULK CONTINUOUS ATWALL PENETRATION (TYP.)
NOTE: OPENING FOR RETURN AIR INTAKE/OUTTAKE SHALL BE AT LEAST 12" CLEAR OF ANY STRUCTURAL MEMBERS.
1-1/2" UNISTRUT
STRUCTURE
CONDENSINGUNIT
PROVIDE 8" CLEARBETWEEN STRUCTUREAND CONDENSER.
GENERAL NOTE:
INLET SIDE OF CONDENSER FAN SHALLBE TOWARDS WALL. DISCHARGE SHALLFACE THE GARAGE OPEN AREA. PROVIDE12" CLEAR BETWEEN INLET OF CONDENSERAND WALL.
DISCHARGE DUCT.
FLEXIBLE CONNECTION.
BACKDRAFT DAMPER
HANGER RODS TO STRUCTURE ABOVE, TYPICAL
SPRING ISOLATORS, TYPICAL.
FLEXIBLE CONNECTION.
TRANSITION WHERE REQUIRED.
INTAKE DUCT.
TRANSITION WHERE REQUIRED.
30° MAXIMUM.
ACCESS DOOR. INSTALL FAN TO ALLOW DOOR TO BE COMPLETELY OPENED.
30° MAXIMUM
1. INSTALL FAN WITH PROPER SERVICE CLEARANCE TO MOTOR AND ALL PARTS FOR PROPER AIR MOVEMENT AS RECOMMENDED BY THE MANUFACTURER.
NOTE:
GAP
PIPE AND INSULATION WITH WATERPROOF ALUMINUM JACKET LONGITUDINAL SEAM AT BOTTOM
HIGH DENSITY INSULATIONWITH PIPE COVERING SHIELD
WALK PAD
PIPE CLAMP OFFSET
4" X 4" REDWOODSET IN MASTIC BED
ROOF
SECTION - A
DUCT SUPPORT DETAIL
2" STRAP
b" ISOMODE PAD
18 GAUGE HAT3"X3"X1" LEG
#10 TEK SCREW(TYPICAL)
NOTE:
1. DUCT WORK AND SUPPORT DESIGNATED FOR PAINTING ON FLOOR PLANS TO HAVE ALL JOINTS AND TAP-INS, E.T.C, SANDED SMOOTH TO A PAINT READY CONDITION FOR PAINTING BY OTHER.
A
-TRUSS#10 TEK SCREW(TYPICAL)
b" ISOMODE PAD
10 OR 18 GAUGERING X2" TOFIT DUCT
SPIRO DUCT26"Ø TO 32"Ø
TRUSS
SPIRO DUCT26"Ø TO 32"Ø
1-1/2"x1-1/2" ANGLESUPPORTS (TYP ALL
SIDES) DO NOT ATTACHTO WALL
10 GA SLEEVE (TYP)
INSULATION WHERENOTED
1/4" MINCLEARANCE
1" MINOVERLAPACCESS DOOR
OPERATOR/ACTUATOR24V OR 120V
TAXIWAY OPERATINGJACK SHAFT
FUSIBLE LINK WITH LOCK
USABLE ROD
INTEGRATOR SPRING
6" MAX (TYP ALL SIDES)
ROOF TOP UNIT
NOTE:
1. MECHANICAL CONTRACTOR TO COORDINATE ALL ROOF TOP UNITS, CURBS, SIZES AND ROOF OPENINGS WITH ROOFING CONTRACTOR.
2. CURB TO BE MINIMUM 18" ABOVE ROOF. PROVIDE SERVICE RAIL AS REQUIRED.
CURB
FLEXIBLE CONNECTION ONSA & RA DUCTS
SA & RA DUCTS. REFER TO ROOF PLAN.
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:47
:14
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M7.01
MECHANICAL DETAILS
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
NO SCALE1
DUCT MOUNTED AIR DEVICE DETAIL
NO SCALE2
DUCT MOUNTED SUPPLY GRILLEDETAIL
NO SCALE3
RETURN AIR TRANSFER BOOT AND AIRDUCT
JAN 09, 2019 PERMIT & BID
NO SCALE4
SUSPENDED CONDENSING UNIT DETAIL
NO SCALE5
INLINE FAN DETAIL
NO SCALE6
PIPE SUPPORT ON ROOF
NO SCALE9
DUCT SUPPORT TYPE "A"
NO SCALE7
COMBINATION FIRE SMOKE DAMPERDETAIL
NO SCALE8
RTU G-1 CURB DETAIL01-09-2019
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:44
:02
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M7.02
MECHANICAL CODECOMPLIANCE
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
01-09-2019
LAUREN BERRY
01/07/2019
LAUREN BERRY 01/07/2019
01-07-2019
DUCT PRESSURE CLASSIFICATION SCHEDULE
DUCT TYPE
MEDIUM PRESSURE SUPPLY
LOW PRESSURE SUPPLY
MEDIUM PRESSURE EXHAUST
LOW PRESSURE EXHAUST
MEDIUM PRESSURE RETURN
LOW PRESSURE RETURN
GENERAL NOTES
1. DUCTWORK SHALL MEET ALL SMACNA REQUIREMENTS.
2. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION AND REQUIREMENTS, INCLUDING ALLOWABLE LEAKAGE.
3. NOTIFY THE ARCHITECT PRIOR TO INSTALLATION IF SYSTEMS ARE NOT SCHEDULED.
SYSTEM
ALL SUPPLY AIR
ALL SUPPLY AIR
ALL EXHAUST AIR
ALL EXHAUST AIR
ALL RETURN AIR
ALL RETURN AIR
SMACNA PRESSURE
CLASSIFICATION
+ 4"
+ 2"
- 4"
- 2"
- 4"
- 2"
INFORMATION
FROM AHU TO SAV, OR VAV
FROM SAV, VAV OR FCU TO GRD
FROM EAV TO FAN
FROM GRD TO EAV OR RAV
FROM RAV TO FAN
FROM GRD TO RAV
REMARKS
ELECTRIC DUCT HEATERCODE
(EDH)
C-1
GENERAL NOTES:
1. PROVIDE OVERCURRENT PROTECTION FOR ANY CIRCUIT OVER 48 AMPS.
2. SCHEDULED DIMENSIONS ARE DUCT DIMENSIONS.
3. PROVIDE AUTOMATIC AND MANUAL RESET THERMAL CUTOUTS.
4. PROVIDE DIFFERENTIAL PRESSURE AIRFLOW SWITCH.
5. PROVIDE CONTROL CIRCUIT TRANSFORMER.
6. TRANSITION DUCT WHERE REQUIRED TO COIL DIMENSIONS.
7. DISCONNECT TO BE PROVIDED BY EQUIPMENT MANUFACTURER.
8. PROVIDE SCR CONTROL.
9. MAINTAIN AT LEAST 4' OF STRAIGHT DUCT UPSTREAM AND DOWNSTREAM OF ELECTRIC COIL.
SERVICE
GYMNASIUM
CFM
16000
KW
150
DIMENSIONS
W" X H"
36X40
STEPS
SCR
EAT
(F)
55
LAT
(F)
85
ELECTRICAL
VOLT
480
PH
3
FLA
180
FUSE
200A FRS-R
DISC.
200A/3P
SECTION 23.05.30
FEEDER
RE: ELEC ONE LINE
REMARKS
ENVIRONMENTAL FAN SCHEDULE
CODE
EF G-1
EF G-2
EF G-3
EF C-1
EF C-2
REF C-1
TF G-1
TF C-1
GENERAL NOTES:
1. DRIVE TYPE: D = DIRECT-PROVIDE RHEOSTAT SPEED CONTROLLER IN FAN HOUSING UNLESS OTHERWISE NOTED.
B = BELT-PROVIDE ADJUSTABLE SHEAVE UNLESS OTHERWISE NOTED.
VFD = VARIABLE FREQUENCY DRIVE.
2. ALL CURBS SHALL BE FACTORY MADE, 14 INCH HIGH INSULATED UNLESS OTHERWISE NOTED.
3. SCHEDULED FAN VALUES (CFM, SP AND HP) ARE ACTUAL AT ALTITUDE. MOTOR HP HAS BEEN ADJUSTED FROM SEA LEVEL CONDITIONS FOR
OPERATION AT JOB SITE ELEVATION. JOB SITE ELEVATION = 0 FT.
4. PROVIDE MAGNETIC STARTER WITH AUXILARY CONTACTS AND HOA SWITCH ON ALL THREE PHASE UNITS EXCEPT WHEN
SERVED FROM MOTOR CONTROL CENTER.
5. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER NEMA STANDARD MG1-2003, TABLES 12-12 AND 12-13.
6. REFER TO SPECIFICATIONS FOR ADDITIONAL MANUFACTURER'S THAT MAY BID AN EQUAL TO THE SCHEDULED BASIS OF DESIGN.
7. PROVIDE FANS WITH MANUFACTURER'S MOTORIZED SHUTOFF DAMPER.
MOUNTING (MTG):
1.PROVIDE WITH FACTORY MANUFACTURED ROOF CURB SUITABLE FOR ROOFING SYSTEM BEING USED. INSTALL
PER MANUFACTURER'S RECOMMENDATIONS. ALSO PROVIDE FACTORY BACKDRAFT DAMPER.
MANUFACTURER/
MODEL NO.
GREENHECK SQ-90-D
GREENHECK SP-A90-130-VG
GREENHECK SP-A90-130-VG
GREENHECK G-099-A
GREENHECK G-123-A
GREENHECK SQ-140-A
GREENHECK SQ-90-D
GREENHECK SQ-90-D
SERVICE
TOILET
TOILET
JANITOR'S CLOSET
TOILET/LOCKEROOM
TOILET/LOCKEROOM
STAGE
TRANSFER AIR
TRANSFER AIR
LOCATION
SIDEWALL/GARAGE LEVEL 1
SIDEWALL/GARAGE LEVEL 1
SIDEWALL/GARAGE LEVEL 1
ROOF
ROOF
STORAGE
ELECTRICAL ROOM
ELECTRICAL ROOM
TYPE
INLNE
CEILING MOUNTED
CEILING MOUNTED
CENT.
CENT.
INLINE
INLINE
INLINE
CFM
600
100
100
950
1600
1850
350
500
ESP
"W.C.
(ALT.)
0.25
0.25
0.25
.75
.75
.25
0.25
0.25
DRIVE
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
ELECTRICAL
HP
1/10
1/4
1/2
1
1/10
1/10
VOLT
115
115
115
115
115
460
115
115
PH
1
1
1
1
1
3
1
1
FLA
5.8
9.8
2.1
DISC.
$ TO
$ TO
$ TO
$ TO
$ TO
30A/3P
$ TO
$ TO
FEEDER
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
(3#12,#12G)3/4"C
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
FUSE
-
-
-
-
-
3A FRS-R
-
-
MTG CTRL REMARKS
GRILLE REGISTER DIFFUSER SCHEDULE
CODE
A
B
C
D
E
F
G
GENERAL NOTES:
1. SEE PLANS FOR CFM AND NECK SIZE.
2. MAXIMUM NOISE CRITERIA (NC) SHALL BE 30 UNLESS OTHERWISE NOTED.
3. COLOR TO BE COORDINATED WITH ARCHITECT.
4. MATERIAL IS STEEL UNLESS OTHERWISE NOTED.
5. BALANCING DEVICE SHALL BE AT SPIN-IN TAP FOR ALL GRD'S UNLESS OTHERWISE NOTED.
6. PROVIDE SURFACE MOUNTING KIT FOR ALL PLAQUE DIFFUSERS LOCATED IN A GYP BOARD CEILING.
7. REFER TO SPECIFICATIONS FOR ALTERNATE MANUFACTURER'S THAT MAY BID AN EQUAL TO THE SCHEDULED BASIS OF DESIGN.
MANUFACTURER/
MODEL NO.
TITUS OMNI
TITUS OMNI
TITUS OMNI
TITUS 300RS
TITUS 301RS
TITUS 301RS
TITUS FL15
SERVICE
SUPPLY
EXHAUST
RETURN
SUPPLY
RETURN
EXHAUST
SUPPLY
TYPE
PLAQUE
PLAQUE
PLAQUE
GRILLE
GRILLE
GRILLE
SLOT
ACCESSORIES
NONE
NONE
NONE
NONE
NONE
NONE
NONE
FACE SIZE
24X24
24X24
24X24
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
REMARKS
LAY-IN
LAY-IN
LAY-IN
SURFACE MOUNT
SURFACE MOUNT
ROOF TOP UNIT SCHEDULE (DX COOLING)
CODE
(RTU)
C-1
G-1
GENERAL NOTES
1. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13.
2. PROVIDE 2", 30% EFFICIENT FILTERS.
3. PROVIDE HIGH EFFICIENT FILTERS.
4. UNIT TO HAVE SINGLE POINT ELECTRICAL CONNECTION.
5. CAPACITY BASED ON 105F AMBIENT TEMPERATURE.
6. PROVIDE FULL PERIMETER MANUFACTURER'S ROOF CURB.
7. PROVIDE MANUFACTURERS RECOMMENDED SERVICE CLEARANCE AROUND ENTIRE UNIT.
8. HEATING AND COOLING CAPACITIES AND FAN STATIC PRESSURES ARE AT JOBSITE ALTITUDE.
9. JOBSITE ELEVATION= 0 FT.
10. PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY AIR OF ALL UNITS 2000 CFM OR GREATER.
11. CONTRACTOR SHALL COORDINATE MANUFACTURER'S ROOF CURB WITH STRUCTURAL ENGINEER.
12. UNIT SHALL COME EQUIPPED WITH ECONOMIZER AND ALL ASSOCIATED SENSORS, CONTROLS, AND DAMPERS FOR CHANGEOVER.
13. REFER TO SPECIFICATIONS FOR ALTERNATE MANUFACTURERS THAT MAY BID AS AN EQUAL TO THE BASIS OF DESIGN.
14. UNIT SHALL BE PROVIDED WITH LEAK DETECTION DEVICE IN DRAIN PAN THAT WILL SHUT OFF UNIT IN THE EVENT THAT THE PRIMARY DRAIN LINE BECOMES RESTRICTED.
15. PROVIDE UNIT WITH THYBAR VIBROCURB III WITH THEATER ACOUSTICS PACKAGE.
16. PROVIDE UNIT WITH SUPPLY FAN VFD INTEGRAL TO RTU BY MANUFACTURER.
17. PROVIDE MODULATING HOT GAS REHEAT.
REMARK NOTES
A. PROVIDE CUSTOM FULL PERIMETER MANUFACTURER'S SPRING ISOLATED ROOF CURB PLENUM FOR SIDE DISCHARGE. REFER TO SHEET M7.01.
MANUFACTURER/
MODEL
TRANE
TRANE
AREA
SERVED
COMMONS
GARAGE
SUPPLY FAN
CFM
10,500
7,700
ESP
(IN.)
2
1.5
FAN
QUANTITY
2
2
HP
(EA.)
5
3
MIN.
OSA
CFM
2,500
1,300
RELIEF AIR FAN
CFM
10,500
7,500
ESP
(IN.)
1
1
FAN
QUANTITY
2
1
HP
(EA.)
7.5
8
COOLING CAPACITY
EAT (F)
DB
80
78.5
WB
67.9
66.7
LAT (F)
DB
53.48
51.59
WB
53.42
51.52
TOTAL
MBH
464.95
335.06
SENS
MBH
303.71
214.22
ELECTRICAL
VOLT
460
460
PH
3
3
MCA
116
86
MOCP
125
100
FUSE
125A FRS-R
100A FRS-R
DISCON.
200A/3P
100A/3P
FEEDER
RE: ELEC ONE-LINE
RE: ELEC ONE-LINE
REMARKS
A
SPLIT SYSTEM SCHEDULEAHU COIL
CODE
AHU C-1
AHU C-2
GENERAL NOTES
1. PROVIDE DRAIN PAN WITH LEAK DETECTION THAT WILL SHUT DOWN UNIT IN THE EVENT THAT THE PRIMARY DRAIN BECOMES RESTRICTED.
2. PROVIDE PERMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13.
3. PROVIDE 2", 30% EFFICIENT FILTERS.
4. PROVIDE HIGH EFFICIENT FILTERS.
5. CAPACITY BASED ON 105F AMBIENT TEMPERATURE.
6. PROVIDE MANUFACTURER'S RECOMMENDED SERVICE CLEARANCE AROUND ENTIRE UNIT.
7. HEATING AND COOLING CAPACITIES AND FAN STATIC PRESSURES ARE AT JOBSITE ALTITUDE.
8. JOBSITE ELEVATION= 0 FT.
9. PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY AIR OF ALL UNITS 2000 CFM OR GREATER.
10. REFER TO SPECIFCATIONS FOR ALTERNATE MANUFACTURERS THAT MAY BID AS AN EQUAL TO THE BASIS OF DESIGN.
11. PROVIDE SINGLE POINT CONNECTION KIT.
REMARKS NOTES:
A. PROVIDE UNIT WITH SUPPLY FAN VFD INTEGRAL TO RTU BY MANUFACTURER.
B. UNIT SHALL BE EQUIPPED WITH ECONOMIZER AND ALL ASSOCIATED SENSORS, CONTROLS, AND DAMPERS FOR CHANGEOVER.
C. MECHANICAL CONTRACTOR TO PROVIDE ALL ASSOCIATED EQUIPMENT, SENSORS, CONTROLS, AND DAMPERS FOR ECONOMIZER OPERATION SEPARATE FROM UNIT.
CONDENSER
CODE
CU C-1
CU C-2.1
CU C-2.2
MANUFACTURER/
MODEL NO.
TRANE
TRANE
TRANE
AREA
SERVED
STAGE
GYM
GYM
SUPPLY FAN
CFM
1850
16000
NO. OF
FANS
1
2
HP
(EACH)
1
7.5
ESP
(IN.)
0.5
2
OA
CFM
450
3000
RETURN FAN
CFM
N/A
16000
NO. OF
FANS
2
HP
(EACH)
5
ESP
(IN.)
0.5
COOLING
ENTERING AIR
T (DB)
80.11
78.5
T (WB)
69.29
67
LEAVING AIR
T (DB)
55
55
T (WB)
55
54.1
COOLING CAPACITY
TOTAL
81.3
640.65
SENS.
49
412.57
ELECTRIC HEAT
ENTERING AIR
T
60
N/A
LEAVING AIR
T
90
CFM
1850
(KW)
TOTAL
20
CU ELECTRICAL
VOLT
-
460
460
PH
-
3
3
MCA
-
63
63
MOCP
-
70
70
FUSE
-
70A FRS-R
70A FRS-R
DISCON.
-
100A/3P
100A/3P
FEEDER
-
RE: ELEC ONE-LINE
RE: ELEC ONE-LINE
AHU ELECTRICAL
VOLT
460
460
460
PH
3
3
3
MCA
40
26.9
17.5
MOCP
-
-
-
FUSE
40A FRS-R
60A FRS-R
30A FRS-R
DISCON.
60A/3P
60A/3P
30A/3P
FEEDER
(3#8,#10G)3/4"C
(3#4,#8G)1"C
(3#10,#10G)3/4"C
REMARKS
C
A, B
VAV BOX SCHEDULE
CODE
(VAV)
C-1
C-2
C-3
C-4
C-5
C-6
C-7
C-8
G-1
G-2
G-3
G-4
G-5
G-6
GENERAL NOTES
1. CONTROLS SHALL BE BY MANUFACTURER OR BY CONTROL MANUFACTURER AND INSTALLED AT THE FACTORY (SEE SPECIFICATIONS).
2. MOUNT WITH 3 STRAIGHT DUCT DIAMETERS UPSTREAM OF THE BOX.
3. MAXIMUM NC LEVELS ARE RADIATED SOUND DATA AND BASED ON THE LISTED COOLING MAXIMUM CFM AND TOTAL APD LISTED.
4. HEATING COIL DISCHARGE TEMPERATURES SHALL NOT EXCEED 90F OR HAVE A TEMPERATURE RISE GREATER THAN 35F.
5. REFER TO SPECIFICATIONS FOR ALTERNATE MANUFACTURERS THAT MAY BID AN EQUAL TO THE SCHEDULED BASIS OF DESIGN.
AREA SERVED
STUDIO C112
RR/MISC
ENTRANCE HALLWAY C100
ENTRANCE HALLWAY C100
STORAGE/CONCESSION
OFFICE
LOCKERS
STUDIO C112
LOBBY
RR/CORRIDOR
MULTIPURPOSE G111
STORAGE MISC
YOUTH G110
SCOUTS G107
MANUFACTURER/
MODEL NO.
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
NAILOR 30RE
DESIGN CFM
COOLING
MAX
1550
640
1600
1600
1000
1000
1200
1400
900
500
1750
1230
1650
1600
HEATING
MAX
700
320
800
800
500
500
600
700
450
250
875
615
825
800
DESIGN
MIN
450
250
540
540
540
350
450
450
300
175
600
400
550
550
CAPACITY (CFM)
MAX.
2050
900
2050
2050
1500
1500
1500
2050
1500
900
2250
1500
2050
2050
MIN.
400
175
400
400
275
275
275
400
275
175
550
275
400
400
HEATING COIL
KW
7.9
3.6
9.0
9.0
5.6
5.6
6.8
7.9
5.1
2.8
9.9
6.9
9.3
9.0
CFM
700
320
800
800
500
500
600
700
450
250
875
615
825
800
EAT
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
LAT
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
90.0
ELECTRICAL
V
480
277
480
480
480
480
480
480
480
277
480
480
480
480
PH
3
1
3
3
3
3
3
3
3
1
3
3
3
3
FLA
9.5
13.0
10.9
10.9
6.8
6.8
8.1
9.5
6.1
10.1
11.9
8.3
11.2
10.9
FUSE
10A FRS-R
-
15A FRS-R
15A FRS-R
10A FRS-R
10A FRS-R
15A FRS-R
15A FRS-R
10A FRS-R
-
15A FRS-R
10A FRS-R
15A FRS-R
15A FRS-R
DISC.
30A/3P
$
30A/3P
30A/3P
30A/3P
30A/3P
30A/3P
30A/3P
30A/3P
$
30A/3P
30A/3P
30A/3P
30A/3P
FEEDER
(3#12,#12G)3/4"C
(2#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(2#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
MAX. NC @
BOX MAX.
30
30
30
30
30
30
30
30
30
30
30
30
30
30
INLET
SIZE
12
8
12
12
10
10
10
12
10
8
14
10
12
12
OUTLET
SIZE
20X12
14X12
16X16
16X16
16X12
16X12
20X12
20X12
14x12
10x10
18X16
14X14
16X16
16X16
TOTAL
APD
(IN.)
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
REMARKS
MINI SPLIT SYSTEM SCHEDULEFAN COIL
CODE
AC C-3
AC G-1
GENERAL NOTES
1. EAT=72F DB/WB.
2. PROVIDE DRAIN PAN WITH LEAK DETECTION THAT WILL SHUT DOWN UNIT IN THE EVENT THAT THE PRIMARY DRAIN BECOMES RESTRICTED.
3. PROVIDE CONDENSATE PUMP WITH ALL WALL MOUNTED AIR CONDITIONING UNITS.
CONDENSER
CODE
CU C-3
CU G-1
MANUFACTURER/
MODEL NO.
TRANE 4TYK6524A10N0B / 4MYW6524A10N0B
TRANE 4TYK612A10N0B / 4MYW6512A10N0B
AREA
SERVED
IDF C128
SERVER G114
SUPPLY FAN
CFM
500
300
COOLING CAP. (MBH)
TOTAL
24
12
SENS.
-
-
ELECTRICAL
VOLT
208
208
PH
1
1
MCA
16
10
MOCP
25
15
FUSE
20A FRN-R
15A FRN-R
DISCON.
30A/2P
30A/2P
FEEDER
(2#12,#12G)3/4"C
(2#12,#12G)3/4"C
REMARKS
UNIT HEATER SCHEDULE (ELECTRIC)CODE
(UH)
C-1
G-1
GENERAL NOTES
REMARK NOTES
A. PROVIDE UNIT MOUNTED CONTROLS.
B. HORIZONTAL DISCHARGE.
MANUFACTURER/
MODEL NO.
MODINE HER30
MODINE HER30
SERVICE
FIRE RISER C105
MECHANICAL G225
OUTPUT
(KW)
3
3
CFM
380
380
EAT
(F)
50
50
LAT
(F)
75
75
VOLT
480
480
PH
3
3
FLA
3.6
3.6
FUSE
5A FRS-R
5A FRS-R
DISCON.
30A/3P
30A/3P
FEEDER
(3#12,#12G)3/4"C
(3#12,#12G)3/4"C
REMARKS
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:54
:13
AM
C:\R
evi
t P
roje
cts\
20
18\M
E-S
t A
nn
e C
om
mo
ns
an
dG
ara
ge
-ME
PT
18
_M
uh
am
ma
d.A
lavi
7P
5A
X.r
vt
M8.00
MECHANICAL SCHEDULES
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
JAN 09, 2019 PERMIT & BID
01-09-2019
0.80
419
450
CFM
CFM
ASHRAE STANDARD 62.1-2013 VENTILATION RATE PROCEDURE CALCULATIONS (PER TABLE 402.1 COH AMENDMENTS TO 2012 UMC) - AHU C-1
ROOM
NUMBER
C114
C115
C116
C117
System Ventilation Efficiency (Ev)
ASHRAE 62.1-2007 Required Outdor Air Intake (Vot)
Outdoor Air Scheduled
ZONE/ROOM NAME
TABLE & CHAIR STOR
GREEN RM
STAGE
OUTSIDE STOR.
ZONE TYPE
PER TABLE 6-1
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
STAGES, STUDIOS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
AREA
(Az)
(SQ.FT.)
215
269
742
358
OUTDOOR
AIRFLOW RATE
PER PERSON
(Rp)
CFM / PERSON
5
5
10
5
OUTDOOR
AIRFLOW RATE
PER UNIT
AREA (Ra)
CFM / SQ.FT.
0.06
0.06
0.06
0.06
OCCUPANT DIVERSITY
ZONE
POPULATION
PEOPLE/1000
SQ.FT.
2
2
70
2
100.0%
ZONE
POPULATION
(Pz)
0
0
24
0
24
OUTDOOR AIR
REQUIRED AT
BREATHING ZONE
CFM (Vbz)
13
16
285
21
335
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
(Ez) TABLE 6-2
0.8
0.8
0.8
0.8
OUTDOOR
AIRFLOW RATE
CFM (Voz)
16
20
356
27
MINIMUM
ZONE
PRIMARY
AIRFLOW
CFM (Vpz)
200
250
1200
200
CRITICAL ZONE Zp
ZONE
PRIMARY
OUTDOOR
FRACTION
(Zp)
0.08
0.08
0.30
0.13
0.30
0.95
2,733
3,000
CFM
CFM
ASHRAE STANDARD 62.1-2013 VENTILATION RATE PROCEDURE CALCULATIONS (PER TABLE 402.1 COH AMENDMENTS TO 2012 UMC) - FCU C.2
ROOM
NUMBER
C113
System Ventilation Efficiency (Ev)
ASHRAE 62.1-2007 Required Outdor Air Intake (Vot)
Outdoor Air Scheduled
ZONE/ROOM NAME
GYMNASIUM
ZONE TYPE
PER TABLE 6-1
GYM, STADIUM (PLAY AREA)
AREA
(Az)
(SQ.FT.)
8656
OUTDOOR
AIRFLOW RATE
PER PERSON
(Rp)
CFM / PERSON
0
OUTDOOR
AIRFLOW RATE
PER UNIT
AREA (Ra)
CFM / SQ.FT.
0.3
OCCUPANT DIVERSITY
ZONE
POPULATION
PEOPLE/1000
SQ.FT.
30
100.0%
ZONE
POPULATION
(Pz)
41
41
OUTDOOR AIR
REQUIRED AT
BREATHING ZONE
CFM (Vbz)
2597
2,597
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
(Ez) TABLE 6-2
0.8
OUTDOOR
AIRFLOW RATE
CFM (Voz)
3246
MINIMUM
ZONE
PRIMARY
AIRFLOW
CFM (Vpz)
16000
CRITICAL ZONE Zp
ZONE
PRIMARY
OUTDOOR
FRACTION
(Zp)
0.20
0.20
0.90
1,418
2,500
CFM
CFM
ASHRAE STANDARD 62.1-2013 VENTILATION RATE PROCEDURE CALCULATIONS (PER TABLE 402.1 COH AMENDMENTS TO 2012 UMC) - RTU C-1
ROOM
NUMBER
C112
C110
C100
C102
C101
C103
C104
C105
C120
C122
C123
C118
C119
System Ventilation Efficiency (Ev)
ASHRAE 62.1-2007 Required Outdor Air Intake (Vot)
Outdoor Air Scheduled
ZONE/ROOM NAME
STUDIO
CHEER
LOBBY
ADVANCEMENT STOR
CONCESSIONS
UCAL STOR
ATHLETIC STOR
P.E. INDOOR STOR
CONF
OFFICE
EAST CORRIDOR
BOYS LOCKER
GIRLS LOCKER
ZONE TYPE
PER TABLE 6-1
STAGES, STUDIOS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
MAIN ENTRY LOBBIES
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
CONFERENCE/MEETING
OFFICE SPACE
CORRIDORS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
AREA
(Az)
(SQ.FT.)
2061
161
2251
130
115
103
350
312
136
299
511
821
815
OUTDOOR
AIRFLOW RATE
PER PERSON
(Rp)
CFM / PERSON
10
5
5
5
5
5
5
5
5
5
0
5
5
OUTDOOR
AIRFLOW RATE
PER UNIT
AREA (Ra)
CFM / SQ.FT.
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
OCCUPANT DIVERSITY
ZONE
POPULATION
PEOPLE/1000
SQ.FT.
70
2
10
2
2
2
2
2
50
5
0
2
2
100.0%
ZONE
POPULATION
(Pz)
41
0
23
0
4
0
4
0
6
4
0
18
18
118
OUTDOOR AIR
REQUIRED AT
BREATHING ZONE
CFM (Vbz)
534
10
248
8
27
6
41
19
38
38
31
139
139
1,276
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
(Ez) TABLE 6-2
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
OUTDOOR
AIRFLOW RATE
CFM (Voz)
667
12
310
10
34
8
51
23
48
47
38
174
174
MINIMUM
ZONE
PRIMARY
AIRFLOW
CFM (Vpz)
2800
140
3200
100
200
100
200
200
200
350
150
700
700
CRITICAL ZONE Zp
ZONE
PRIMARY
OUTDOOR
FRACTION
(Zp)
0.24
0.09
0.10
0.10
0.17
0.08
0.26
0.12
0.24
0.14
0.26
0.25
0.25
0.26
0.90
1,272
1,300
CFM
CFM
ASHRAE STANDARD 62.1-2013 VENTILATION RATE PROCEDURE CALCULATIONS (PER TABLE 402.1 COH AMENDMENTS TO 2012 UMC) - RTU G-1
ROOM
NUMBER
G100
G118
G118
G116
G119
G120
G101
G106
G107
G108
G109
G110
G111
G113
G114
G115
System Ventilation Efficiency (Ev)
ASHRAE 62.1-2007 Required Outdor Air Intake (Vot)
Outdoor Air Scheduled
ZONE/ROOM NAME
LOBBY
MULTI PURPOSE
YOUTH
SCOUTS
CORR-W
CORR-N
SECURITY
S.A.F.
SAF STORY
STOR 2
STOR 1
WORK
H.M. STOR
YOUTH STOR
GIRL STOR
BOY STOR
ZONE TYPE
PER TABLE 6-1
MAIN ENTRY LOBBIES
MULTI-USE ASSEMBLY
MULTI-USE ASSEMBLY
MULTI-USE ASSEMBLY
CORRIDORS
CORRIDORS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
OCCUPIABLE STORAGE ROOMS FOR DRY MATERIALS
AREA
(Az)
(SQ.FT.)
649
1167
1062
1165
660
271
101
194
157
157
160
164
162
167
158
147
OUTDOOR
AIRFLOW RATE
PER PERSON
(Rp)
CFM / PERSON
5
7.5
7.5
7.5
0
0
5
5
5
5
5
5
5
5
5
5
OUTDOOR
AIRFLOW RATE
PER UNIT
AREA (Ra)
CFM / SQ.FT.
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
OCCUPANT DIVERSITY
ZONE
POPULATION
PEOPLE/1000
SQ.FT.
10
100
100
100
0
0
2
2
2
2
2
2
2
2
2
2
100.0%
ZONE
POPULATION
(Pz)
6
32
32
32
0
0
0
0
0
0
0
0
0
0
0
0
102
OUTDOOR AIR
REQUIRED AT
BREATHING ZONE
CFM (Vbz)
71
310
304
310
40
16
6
12
9
9
10
10
10
10
9
9
1,145
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
(Ez) TABLE 6-2
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
OUTDOOR
AIRFLOW RATE
CFM (Voz)
89
388
380
387
50
20
8
15
12
12
12
12
12
13
12
11
MINIMUM
ZONE
PRIMARY
AIRFLOW
CFM (Vpz)
750
1500
1500
1600
200
100
150
210
100
100
100
100
100
100
110
110
CRITICAL ZONE Zp
ZONE
PRIMARY
OUTDOOR
FRACTION
(Zp)
0.12
0.26
0.25
0.24
0.25
0.20
0.05
0.07
0.12
0.12
0.12
0.12
0.12
0.13
0.11
0.10
0.26
OUTSIDE AIR VERSUS EXHAUST AIR
COMMONS
UNIT
FCU-C-1
RTU-C-1
RTU-C-2
TOTAL
GARAGE
UNIT
RTU-G-1
AREA
STAGE
COMMONS
GYM
AREA
GARAGE
OUTSIDE AIR
450
2500
3000
5950
OUTSIDE AIR
1300
EXHAUST AIR
0
2550
0
2550
EXHAUST AIR
800
4550 Post Oak Place, Suite 344
Houston, TX 77027
P: +1.713.621.8690
www.me-engineers.com
1 2 4
D
3
1 2 4 53
C
B
A
D
C
B
A
5
SHEET NUMBER
SHEET TITLE
KEY PLAN
PROJECT NAME
PROJECT ADDRESS
DATE ISSUE
KIRKSEY PROJECT NO.
© 2018 Kirksey
Texas Firm Reg. No. F-10231
1/9
/20
19 8
:44
:03
AM
C:\R
evit P
roje
cts
\20
18\M
E-S
t A
nn
e C
om
mo
ns a
nd
Ga
rage
-ME
PT
18
_M
uh
am
ma
d.A
lavi7
P5A
X.r
vt
M8.01
MECHANICAL SCHEDULES
Commons & Parking Garage
2140 Westheimer RoadHouston, Texas 77098
2017187
1/8" = 1'-0" 1MEP SCHEDULES Copy 1
JAN 09, 2019 PERMIT & BID
01-09-2019