07 transformer

Upload: nilushkaa

Post on 05-Apr-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 07 Transformer

    1/81

    TRANSFORMER PROTECTION

    Slide 1Issue A

  • 7/31/2019 07 Transformer

    2/81

    Slide 2Issue A

    Causes of failure:

    Environment

    System

    Mal operation

    Wrong design

    Manufacture

    Material

    Maintenance

  • 7/31/2019 07 Transformer

    3/81

  • 7/31/2019 07 Transformer

    4/81

    2. External failure2. External failure2. External failure2. External failure

    Causes:Causes:Causes:Causes:

    Issue A Slide 4

    -Abnormal operating conditionAbnormal operating conditionAbnormal operating conditionAbnormal operating condition

    - sustained or unclear faultssustained or unclear faultssustained or unclear faultssustained or unclear faults

    Transformer failures classification :Transformer failures classification :Transformer failures classification :Transformer failures classification :

  • 7/31/2019 07 Transformer

    5/81

    Issue A Slide 5

    Vector GroupsVector GroupsVector GroupsVector Groups

    Phase displacementPhase displacementPhase displacementPhase displacement0000

    Group 1Group 1Group 1Group 1

    Phase displacementPhase displacementPhase displacementPhase displacement180180180180

    Group 2Group 2Group 2Group 2

    Lag phase displacementLag phase displacementLag phase displacementLag phase displacement30303030

    Group 3Group 3Group 3Group 3

    Lead phase displacementLead phase displacementLead phase displacementLead phase displacement30303030

    Group 4Group 4Group 4Group 4

    Yy0Yy0Yy0Yy0Dd0Dd0Dd0Dd0Zd0Zd0Zd0Zd0

    Yy6Yy6Yy6Yy6Dd6Dd6Dd6Dd6Dz6Dz6Dz6Dz6

    Yd1Yd1Yd1Yd1

    Dy1Dy1Dy1Dy1Yz1Yz1Yz1Yz1

    Yd11Yd11Yd11Yd11Dy11Dy11Dy11Dy11

    Yz11Yz11Yz11Yz11

  • 7/31/2019 07 Transformer

    6/81

    Slide 10Issue A

    Fault current distribution

    Earth fault on Transformer winding

    V2

    R

    T 2 T 1

    V1

    X

    Fig.3 If

    Fig.N

  • 7/31/2019 07 Transformer

    7/81

  • 7/31/2019 07 Transformer

    8/81

    Slide 13Issue A

    Differential

    Basic Protection

    Restricted Earthfault

    Overfluxing

    Overcurrent & Earthfault

  • 7/31/2019 07 Transformer

    9/81

    Slide 14Issue A

    Differential Protection

    Where protection co-ordination is difficult /notpossible using time delayed elements

    For fast fault clearance

    Applied

    Works on Merz-price current comparisonprinciple

    Relays with bias characteristic should only beused

    For zone of protection

  • 7/31/2019 07 Transformer

    10/81

    Slide 15Issue A

    Differential Protection

    Consideration for applying differential

    protection

    Phase correction

    Filtering of zero sequence currents

    Ratio correction

    Magnetizing inrush during energisation

    Overfluxing

  • 7/31/2019 07 Transformer

    11/81

    Slide 16Issue A

    Differential Protection - Principle

    R I diff = 0I diff = 0I diff = 0I diff = 0

    Nominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipment

    I Diff = 0 :I Diff = 0 :I Diff = 0 :I Diff = 0 : No trippingNo trippingNo trippingNo tripping

  • 7/31/2019 07 Transformer

    12/81

    Slide 17Issue A

    Differential Protection -

    Principle Through fault currentThrough fault currentThrough fault currentThrough fault current

    I Diff = 0 :I Diff = 0 :I Diff = 0 :I Diff = 0 : No trippingNo trippingNo trippingNo tripping

    R I diff = 0I diff = 0I diff = 0I diff = 0

  • 7/31/2019 07 Transformer

    13/81

    Slide 18Issue A

    Differential Protection -

    Principle

    TrippingTrippingTrippingTripping

    Internal FaultInternal FaultInternal FaultInternal Fault

    I Diff = 0 :I Diff = 0 :I Diff = 0 :I Diff = 0 :

    R I diff = 0I diff = 0I diff = 0I diff = 0

  • 7/31/2019 07 Transformer

    14/81

    Slide 19Issue A

    Biased differential protection

    Fast operation

    Adjustable characteristic

    High through fault stability

    CT ratio compensation

    Magnetising inrush restraint

    Overfluxing 5th harmonic restraint

  • 7/31/2019 07 Transformer

    15/81

    Slide 20Issue A

    Biased differential protection

    1 A

    100/50 KV100 / 1 200 / 1

    1 A

    0 A

    LOAD

    = 200 A

    Why bias characteristic ?

    OLTC Setting is at mid tap

    R

    I1I2

  • 7/31/2019 07 Transformer

    16/81

    Slide 21Issue A

    Biased differential protection100/50 KV100 / 1 200 / 1

    0.9 A 1 A

    0.1 A

    Relay pickup setting = O.2 A, So the Relay restrains

    LOAD= 200 A

    OLTC SETTING IS AT 10%

    Differential current = 0.1 A

    R

  • 7/31/2019 07 Transformer

    17/81

    Slide 22Issue A

    Biased differential protection

    100/50 KV100 / 1 200 / 1

    9 A10 A

    1 A

    Relay Pickup Setting is O.2 AOLTC SETTING IS AT 10%

    2000 A

    R

    OperatesSo the Relay

  • 7/31/2019 07 Transformer

    18/81

  • 7/31/2019 07 Transformer

    19/81

    Slide 24Issue A

    Based on Current operated relay with an external stabilising resBased on Current operated relay with an external stabilising resBased on Current operated relay with an external stabilising resBased on Current operated relay with an external stabilising resistoristoristoristor

    Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,typically class X or equivalenttypically class X or equivalenttypically class X or equivalenttypically class X or equivalent

    Equal CT ratiosEqual CT ratiosEqual CT ratiosEqual CT ratios NonNonNonNon----linear resistor may be required to limit voltage across relaylinear resistor may be required to limit voltage across relaylinear resistor may be required to limit voltage across relaylinear resistor may be required to limit voltage across relaycircuit during internal faultscircuit during internal faultscircuit during internal faultscircuit during internal faults

    Suitable for zones up to 200Suitable for zones up to 200Suitable for zones up to 200Suitable for zones up to 200 ---- 300 metres (typically)300 metres (typically)300 metres (typically)300 metres (typically)

    High Impedance Principle

  • 7/31/2019 07 Transformer

    20/81

    Slide 25Issue A

    High Impedance Principle

    TC satur

    M

    RCT

    ZM

    RCT2RL 2RL

    A

    M

    ZM

    RCT

    2RL

    2RL

    RCT

  • 7/31/2019 07 Transformer

    21/81

    Slide 26Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/31/2019 07 Transformer

    22/81

    Slide 27Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TC satur

    A

    M

    M

  • 7/31/2019 07 Transformer

    23/81

    Slide 28Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/31/2019 07 Transformer

    24/81

    Slide 29Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TC satur

    A

    M

    M

  • 7/31/2019 07 Transformer

    25/81

    Slide 30Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/31/2019 07 Transformer

    26/81

    Slide 31Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TCsatur

    A

    M

    M

  • 7/31/2019 07 Transformer

    27/81

    Slide 32Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    M

    MCT Saturation

    False tripping

  • 7/31/2019 07 Transformer

    28/81

    Slide 33Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

  • 7/31/2019 07 Transformer

    29/81

    Slide 34Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

    Stabilising resistorStabilising resistorStabilising resistorStabilising resistor

  • 7/31/2019 07 Transformer

    30/81

    Slide 35Issue A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    RS

    M

    M

    RCT

    2RL

    2RL

    RCT Vset

    High Impedance Principle

  • 7/31/2019 07 Transformer

    31/81

    Slide 36Issue A

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

    ZM = 0(CT "shortcircuited" )

    Vset

    High Impedance Principle

  • 7/31/2019 07 Transformer

    32/81

    Slide 37Issue A

    A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    2RL

    RCT

    2RL

    RCT

    RS

    M

    M

    Vset

    High Impedance Principle

  • 7/31/2019 07 Transformer

    33/81

    Slide 38Issue A

    High Impedance Principle

    2RL

    RCT

    2RL

    RCT

    M

    Vset

    A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    RS

    M

  • 7/31/2019 07 Transformer

    34/81

    Slide 39Issue A

    High Impedance Principle

    M

    A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    RS

    M

    Vset

    MetrosilMetrosilMetrosilMetrosil may bemay bemay bemay berequired for voltagerequired for voltagerequired for voltagerequired for voltage

    limitationlimitationlimitationlimitation2RL

    RCT

    2RL

    RCT

    M

    f

  • 7/31/2019 07 Transformer

    35/81

    Slide 40Issue A

    Restricted Earthfault

    Protection

    Increased sensitivity for earth faults

    REF elements for each transformer winding

    CTs may be shared with differential element

    Uses high impedance principle

    6464

    64

    R t i t d E thf lt P t ti

  • 7/31/2019 07 Transformer

    36/81

    Slide 41Issue A

    Restricted Earthfault Protection

    P1P1P1P1

    S1S1S1S1

    P2P2P2P2

    S2S2S2S2P1P1P1P1

    S1S1S1S1

    P2P2P2P2

    S2S2S2S2

    P1P1P1P1S1S1S1S1

    P2P2P2P2S2S2S2S2

    P1P1P1P1

    P2P2P2P2

    S1S1S1S1

    S2S2S2S2

    Stability level : usually maximum through fault level of tranStability level : usually maximum through fault level of tranStability level : usually maximum through fault level of tranStability level : usually maximum through fault level of transformersformersformersformerREF Case I : Normal Condition

    Under normal conditions no current flows thro Relay

    So, No Operation

  • 7/31/2019 07 Transformer

    37/81

    Slide 42Issue A

    Restricted Earthfault Protection

    REF Case II : External Earth Fault

    External earth fault - Current circulates between the phase & neutral CTs;

    no current thro the relay

    So, No Operation

  • 7/31/2019 07 Transformer

    38/81

    Issue ASlide 43

    Issue A

    Restricted Earthfault Protection

    REF Case III : Internal Earth Fault

    For an internal earth fault the unbalanced current flows thro the relay

    So, Relay Operates

  • 7/31/2019 07 Transformer

    39/81

    Slide 44Issue A

    Restricted Earthfault Protection

    Restricted Earth Fault Protection SettingRestricted Earth Fault Protection SettingRestricted Earth Fault Protection SettingRestricted Earth Fault Protection Setting

    1MVA(5%)11000V 415V

    1600/1RCT = 4.9

    80MVA

    RS1600/1RCT = 4.8

    MCAG14IS = 0.1

    Amp2 Core 7/0.67mm(7.41/km)100m Long

    Setting will requireSetting will requireSetting will requireSetting will requirecalculation of :calculation of :calculation of :calculation of :

    1)1)1)1) Setting stabilitySetting stabilitySetting stabilitySetting stabilityvoltage (Vvoltage (Vvoltage (Vvoltage (V

    SSSS))))

    2)2)2)2) Value of stabilisingValue of stabilisingValue of stabilisingValue of stabilisingresistor requiredresistor requiredresistor requiredresistor required

    3)3)3)3) Peak voltagePeak voltagePeak voltagePeak voltage

    developed bydeveloped bydeveloped bydeveloped by CTCTCTCTssssfor internal faultfor internal faultfor internal faultfor internal fault

    i d hf l i

  • 7/31/2019 07 Transformer

    40/81

    Slide 45Issue A

    Restricted Earthfault Protection

    Example : Earth fault calculation :Example : Earth fault calculation :Example : Earth fault calculation :Example : Earth fault calculation :----

    Using 80MVA baseUsing 80MVA baseUsing 80MVA baseUsing 80MVA base

    Source impedance = 1 p.u.Source impedance = 1 p.u.Source impedance = 1 p.u.Source impedance = 1 p.u.

    Transformer impedance = 0.05 x 80 = 4 p.u.Transformer impedance = 0.05 x 80 = 4 p.u.Transformer impedance = 0.05 x 80 = 4 p.u.Transformer impedance = 0.05 x 80 = 4 p.u.1111

    Total impedance = 14 p.u.Total impedance = 14 p.u.Total impedance = 14 p.u.Total impedance = 14 p.u.

    I1111 = 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u.14141414

    Base current = 80 x 10Base current = 80 x 10Base current = 80 x 10Base current = 80 x 106666

    3 x 4153 x 4153 x 4153 x 415

    = 111296 Amps= 111296 Amps= 111296 Amps= 111296 Amps IFFFF = 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296

    = 23840 Amps (primary)= 23840 Amps (primary)= 23840 Amps (primary)= 23840 Amps (primary)= 14.9 Amps (secondary)= 14.9 Amps (secondary)= 14.9 Amps (secondary)= 14.9 Amps (secondary)

    1 P.U.1 4

    I1

    4

    I2

    4

    I0

    1

    1

    R i d E hf l P i

  • 7/31/2019 07 Transformer

    41/81

    Slide 46Issue A

    Restricted Earthfault Protection

    (1)(1)(1)(1) Setting voltageSetting voltageSetting voltageSetting voltage

    VVVVSSSS ==== IFFFF (R(R(R(RCTCTCTCT + 2+ 2+ 2+ 2RLRLRLRL))))

    AssumingAssumingAssumingAssuming earthearthearthearth CT saturates,CT saturates,CT saturates,CT saturates,

    RRRRCTCTCTCT = 4.8 ohms= 4.8 ohms= 4.8 ohms= 4.8 ohms

    2222RLRLRLRL = 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10----3333 = 1.482 ohms= 1.482 ohms= 1.482 ohms= 1.482 ohms

    Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)

    = 93.6 Volts= 93.6 Volts= 93.6 Volts= 93.6 Volts

    (2)(2)(2)(2) Stabilising Resistor (RStabilising Resistor (RStabilising Resistor (RStabilising Resistor (RSSSS))))

    RRRRSSSS ==== {Vs - [VA/(Is^2)]} /Is

    WhereWhereWhereWhere ISSSS = relay current setting= relay current setting= relay current setting= relay current setting RRRRSSSS = {93.6= {93.6= {93.6= {93.6 ---- [[[[ 1/0.1^2]}/0.1 = 836 ohms1/0.1^2]}/0.1 = 836 ohms1/0.1^2]}/0.1 = 836 ohms1/0.1^2]}/0.1 = 836 ohms

    R t i t d E thf lt P t ti

  • 7/31/2019 07 Transformer

    42/81

    Slide 47Issue A

    Restricted Earthfault Protection

    3)3)3)3) Peak voltage = 2Peak voltage = 2Peak voltage = 2Peak voltage = 22222 VVVVKKKK(V(V(V(VFFFF ---- VVVVKKKK))))

    VVVVFFFF = 14.9 x V= 14.9 x V= 14.9 x V= 14.9 x VSSSS = 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 VoltsISSSS

    ForForForFor EarthEarthEarthEarth CT, VCT, VCT, VCT, VKKKK = 1.4 x 236 = 330 Volts (from= 1.4 x 236 = 330 Volts (from= 1.4 x 236 = 330 Volts (from= 1.4 x 236 = 330 Volts (fromgraph)graph)graph)graph)

    VVVVPEAKPEAKPEAKPEAK = 2= 2= 2= 22222 330 (13946330 (13946330 (13946330 (13946 ---- 330)330)330)330)

    = 6kV= 6kV= 6kV= 6kV

    Thus,Thus,Thus,Thus, metrosilmetrosilmetrosilmetrosil voltage limiter will be required.voltage limiter will be required.voltage limiter will be required.voltage limiter will be required.

  • 7/31/2019 07 Transformer

    43/81

    Slide 48Issue A

    Magnetising Inrush

    Transient condition - occurs when a

    transformer is energised

    Normal operating flux of a transformer is close to saturation

    level

    Residual flux can increase the mag-current

    In the case of three phase transformer, the point-on-wave at

    switch-on differs for each phase and hence, also the inrush

    currents

  • 7/31/2019 07 Transformer

    44/81

    Slide 49Issue A

    Transformer Magnetising CharacteristicTransformer Magnetising CharacteristicTransformer Magnetising CharacteristicTransformer Magnetising Characteristic

    TwiceTwiceTwiceTwiceNormal FluxNormal FluxNormal FluxNormal Flux

    NormalNormalNormalNormalFluxFluxFluxFlux

    NormalNormalNormalNormalNo Load CurrentNo Load CurrentNo Load CurrentNo Load Current

    No Load Current atNo Load Current atNo Load Current atNo Load Current atTwice Normal FluxTwice Normal FluxTwice Normal FluxTwice Normal Flux

    Magnetising Inrush

  • 7/31/2019 07 Transformer

    45/81

    Slide 50Issue A

    Magnetising Inrush

    m+

    SWITCH ON AT VOLTAGE

    ZERO - NO RESIDUAL FLUX

    m-

    m2

    STEADY STATE

    V

    mI

    mI

    V

    Inrush Current

  • 7/31/2019 07 Transformer

    46/81

  • 7/31/2019 07 Transformer

    47/81

    Slide 52Issue A

    Magnetising Inrush

    Appears on one side of transformer only

    - Seen as fault by differential relay

    - Transient magnetising inrush could cause

    relay to operate

    Makes CT transient saturation

    - Can make mal-operation of Zero sequence

    relay at primary

    Effect of magnetising currentEffect of magnetising currentEffect of magnetising currentEffect of magnetising current

  • 7/31/2019 07 Transformer

    48/81

    Slide 53Issue A

    P1P1P1P1

    S1S1S1S1

    P2P2P2P2

    S2S2S2S2P1P1P1P1

    S1S1S1S1

    P2P2P2P2

    S2S2S2S2P1P1P1P1

    S1S1S1S1

    P2P2P2P2

    S2S2S2S2

    IRIRIRIR

    ISISISIS

    ITITITIT

    IR + IS + IT = 3Io = 0IR + IS + IT = 3Io = 0IR + IS + IT = 3Io = 0IR + IS + IT = 3Io = 0

    Magnetising Inrush

    M i i I h

  • 7/31/2019 07 Transformer

    49/81

    Slide 54Issue A

    Effect of magnetising currentEffect of magnetising currentEffect of magnetising currentEffect of magnetising current

    Example ofExample ofExample ofExample of disurbancedisurbancedisurbancedisurbance recordsrecordsrecordsrecordswith detailwith detailwith detailwith detail

    Magnetising Inrush

    M ti i I h R t i

  • 7/31/2019 07 Transformer

    50/81

    Slide 55Issue A

    2nd (and 5th) harmonic restraint2nd (and 5th) harmonic restraint2nd (and 5th) harmonic restraint2nd (and 5th) harmonic restraint

    Makes relay immune to magnetisinginrush

    Slow operation may result for genuine

    transformer faults if CT saturationoccurs

    Magnetising Inrush Restrain

    O fl i B i Th

  • 7/31/2019 07 Transformer

    51/81

    Slide 57Issue A

    Overfluxing - Basic Theory

    Low frequency High voltage

    Geomagnetic disturbances

    Causes

    Overfluxing = V/F

  • 7/31/2019 07 Transformer

    52/81

  • 7/31/2019 07 Transformer

    53/81

    Overfluxing Protection

  • 7/31/2019 07 Transformer

    54/81

    Slide 60Issue A

    V Kf

    Trip and alarm outputs for clearing prolonged overfluxing

    Alarm : Definite time characteristic to initiate correctiveaction

    Trip : IT or DT characteristic to clear overfluxing condition

    Overfluxing - Protection

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    55/81

    Slide 60Issue A

    Oil conservatorOil conservatorOil conservatorOil conservator

    BucholzBucholzBucholzBucholz RelayRelayRelayRelay

    BUCCHOLZ PROTECTION

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    56/81

    Slide 60Issue A

    Buchholz Relay InstallationBuchholz Relay InstallationBuchholz Relay InstallationBuchholz Relay Installation

    5 x internal pipe5 x internal pipe5 x internal pipe5 x internal pipediameter (minimum)diameter (minimum)diameter (minimum)diameter (minimum)

    3 x internal pipe3 x internal pipe3 x internal pipe3 x internal pipediameter (minimum)diameter (minimum)diameter (minimum)diameter (minimum)

    TransformerTransformerTransformerTransformer

    76 mm typical76 mm typical76 mm typical76 mm typical

    To oil conservatorTo oil conservatorTo oil conservatorTo oil conservator

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    57/81

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    58/81

    Slide 60Issue A

    Accumulation of gazAccumulation of gazAccumulation of gazAccumulation of gazOilOilOilOil LeakageLeakageLeakageLeakageSevereSevereSevereSevere windingwindingwindingwinding faultsfaultsfaultsfaults

    BuccholzBuccholzBuccholzBuccholz Protection ApplicationProtection ApplicationProtection ApplicationProtection Application

    BUCCHOLZ PROTECTION

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    59/81

    Slide 60Issue A

    InterturnInterturnInterturnInterturn faultsfaultsfaultsfaults

    WindingWindingWindingWinding faultsfaultsfaultsfaults totototo earthearthearthearth withwithwithwith lowlowlowlow

    power (power (power (power (faultfaultfaultfault close toclose toclose toclose to neutralneutralneutralneutral forforforforexampleexampleexampleexample))))

    Accumulation of GazAccumulation of GazAccumulation of GazAccumulation of Gaz

    BUCCHOLZ PROTECTION

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    60/81

    Slide 60Issue A

    Inter-Turn Fault

    Nominal turns ratio

    Fault turns ratioCurrent ratio

    : 11,000 / 240

    : 11,000 / 1: 1 / 11,000

    Shortedturn

    Load

    Primary Secondary

    CTCTCTCTEEEE

    BUCCHOLZ PROTECTION

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    61/81

    Slide 60Issue A

    Nominal turns ratio

    Fault turns ratioCurrent ratio

    : 11,000 / 240

    : 11,000 / 1: 1 / 11,000

    CTCTCTCTEEEE

    Shortedturn

    Primary Secondary

    Inter-Turn Fault

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    62/81

    Slide 60Issue A

    Interturn Fault Current / Numberof Turns Short Circuited

    5555 10101010 15151515 20202020 25252525

    Turn shortTurn shortTurn shortTurn short----circuitedcircuitedcircuitedcircuited(percentage of(percentage of(percentage of(percentage ofwinding)winding)winding)winding)

    Primary currentPrimary currentPrimary currentPrimary current(multiples of(multiples of(multiples of(multiples ofrated current)rated current)rated current)rated current)

    Fault currentFault currentFault currentFault current(multiples of(multiples of(multiples of(multiples ofrated current)rated current)rated current)rated current)

    100100100100

    80808080

    60606060

    40404040

    20202020

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    63/81

    Slide 60Issue A

    Interturn Fault Current / Numberof Turns Short Circuited

    5 10 15 20 25

    Primary current

    (multiples of

    rated current)

    Fault current

    (multiples of

    rated current)

    100

    80

    60

    40

    20

    Fault current very high

    Primary phase current very low

    Detected by Bucholz relay

    Not detected by current

    operated relays

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    64/81

    Slide 60Issue A

    InterturnInterturnInterturnInterturn faultsfaultsfaultsfaults

    WindingWindingWindingWinding faultsfaultsfaultsfaults totototo earthearthearthearth withwithwithwith lowlowlowlow

    power (power (power (power (faultfaultfaultfault close toclose toclose toclose to neutralneutralneutralneutral forforforforexampleexampleexampleexample))))

    Accumulation of GazAccumulation of GazAccumulation of GazAccumulation of Gaz

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    65/81

    Slide 60Issue A

    Earth Fault Current / Number ofEarth Fault Current / Number ofEarth Fault Current / Number ofEarth Fault Current / Number ofTurns Short CircuitedTurns Short CircuitedTurns Short CircuitedTurns Short Circuited

    5555 10101010 15151515 20202020 25252525

    Turn shortTurn shortTurn shortTurn short----circuitedcircuitedcircuitedcircuited(percentage of(percentage of(percentage of(percentage ofwinding)winding)winding)winding)

    Primary currentPrimary currentPrimary currentPrimary current

    Fault currentFault currentFault currentFault current

    100100100100

    80808080

    60606060

    40404040

    20202020

    multiples ofmultiples ofmultiples ofmultiples ofmax fault currentmax fault currentmax fault currentmax fault current

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    66/81

    Slide 60Issue A

    OperatingOperatingOperatingOperating principleprincipleprincipleprinciple

    Accumulation of GazAccumulation of GazAccumulation of GazAccumulation of Gaz

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    67/81

    Slide 60Issue A

    Buchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    AccumulationAccumulationAccumulationAccumulationofofofof gazgazgazgaz

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    68/81

    Slide 60Issue A

    AccumulationAccumulationAccumulationAccumulationofofofof gazgazgazgaz

    Buchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    69/81

    Slide 60Issue A

    AccumulationAccumulationAccumulationAccumulationofofofof gazgazgazgaz

    Buchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    70/81

    Slide 60Issue A

    ColorColorColorColor ofofofof gazgazgazgaz indicatesindicatesindicatesindicatesthe type of faultthe type of faultthe type of faultthe type of fault

    White or Yellow :White or Yellow :White or Yellow :White or Yellow :Insulation burntInsulation burntInsulation burntInsulation burnt

    Grey :Grey :Grey :Grey :Dissociated oilDissociated oilDissociated oilDissociated oil

    AccumulationAccumulationAccumulationAccumulationofofofof gazgazgazgaz

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    71/81

    Slide 60Issue A

    AccumulationAccumulationAccumulationAccumulation

    ofofofof gazgazgazgaz

    GazGazGazGaz can be extracted fcan be extracted fcan be extracted fcan be extracted fdetailleddetailleddetailleddetailled analysisanalysisanalysisanalysis

    Buchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    72/81

    Slide 60Issue A

    After oil maintenance, falsetripping may occur because Oil

    aeration

    Effects of Oil MaintenanceEffects of Oil MaintenanceEffects of Oil MaintenanceEffects of Oil Maintenance

    BucholzBucholzBucholzBucholz relay tripping inhibited duringrelay tripping inhibited duringrelay tripping inhibited duringrelay tripping inhibited duringsuitable periodsuitable periodsuitable periodsuitable period

    Need of electrical protectionNeed of electrical protectionNeed of electrical protectionNeed of electrical protection

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    73/81

    Slide 60Issue A

    Accumulation of gazAccumulation of gazAccumulation of gazAccumulation of gazOilOilOilOil LeakageLeakageLeakageLeakageSevereSevereSevereSevere windingwindingwindingwinding faultsfaultsfaultsfaults

    BucholtzBucholtzBucholtzBucholtz Protection ApplicationProtection ApplicationProtection ApplicationProtection Application

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    74/81

    Slide 60Issue A

    Oil LeakageOil LeakageOil LeakageOil LeakageBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    75/81

    Slide 60Issue A

    Oil LeakageOil LeakageOil LeakageOil LeakageBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    76/81

    Slide 60Issue A

    Oil LeakageOil LeakageOil LeakageOil LeakageBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    77/81

    Slide 60Issue A

    Oil LeakageOil LeakageOil LeakageOil LeakageBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    78/81

    Slide 60Issue A

    Accumulation of gazAccumulation of gazAccumulation of gazAccumulation of gazOilOilOilOil LeakageLeakageLeakageLeakageSevereSevereSevereSevere windingwindingwindingwinding faultsfaultsfaultsfaults

    BuccholzBuccholzBuccholzBuccholz Protection ApplicationProtection ApplicationProtection ApplicationProtection Application

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    79/81

    Slide 60Issue A

    Severe winding faultSevere winding faultSevere winding faultSevere winding faultBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay

  • 7/31/2019 07 Transformer

    80/81

    BUCCHOLZ PROTECTION

  • 7/31/2019 07 Transformer

    81/81

    Slide 60Issue A

    Severe winding faultSevere winding faultSevere winding faultSevere winding faultBuchholz RelayBuchholz RelayBuchholz RelayBuchholz Relay