066195 - 25 kv underarm side-break switch, manual and ...€¦ · 25 kv underarm side-break switch,...

29
OH: Switches Rev. #17: 10-15-09 066195 Page 1 of 29 Electric Distribution 066195 Construction, Maintenance, and Operation Function: Asset Type: Issued by: Date: Sam Chang (SKC5) 10-15-09 Rev. #17: This document replaces Document 066195, Rev. #16. For a description of the changes, see Page 29. 25 KV UNDERARM SIDE-BREAK SWITCH, MANUAL AND AUTOMATED Prepared by: EOB1 Purpose and Scope This document specifies the requirements and preferred installation of manual and automated 25 kV underarm side-break switches (U.S. Switch). General Information, Both Manual and Automated Switches 1. The U.S. Switch is required to be designed, manufactured, and tested to meet all applicable ANSI (American National Standards Institute) standards, IEEE (Institute of Electrical and Electronic Engineers) standards, and all requirements shown and described in this document. In addition, the U.S. Switch is required to be tested to meet the CDF (California Department of Forestry) requirements and qualified as exempt electrical equipment. 2. Switch Code 341575 (manual) or switch Code 341497 (automated) are for use in all switch applications and districts, except for 21 kV in AA insulation districts. For 21 kV in AA insulation districts, use switch Code 341576 (manual) or switch Code 341488 (automated). The Cooper/Kearney and the S&C U.S. Switch both use epoxy insulators, and Inertia uses station post silicone rubber insulators. 3. The switch codes shown in this document are for the U.S. Switch. These switches are shipped as tangent 3-wire, and are adaptable to all line configurations; e.g., tangent 4-wire, angle, tangent riser, dead-end riser, alley arm, etc. 4. Caution: The U.S. Switch is designed and manufactured to be installed in the underarm position only. Do not install this switch in the upright position. The bell crank operation will be reversed causing the switch to operate opposite of the normal open/close positions. 5. Non-ceramic dead-end insulators and extension links are not included by the manufacturer of the switch and must be ordered separately. Extension links are required for all installations where dead-ending occurs on the switch arm dead-end bracket. Important : Three extension links are required per phase for the automated switches; i.e., two extension links on the sensor insulator side and one extension link on the opposite side. 6. The U.S. Switch is furnished with terminal paddles for use with fired wedge connectors. Select the appropriate fired wedge connector from Document 066194 by using 397.5 AAC (terminal paddle size) for one groove size, and the line conductor size for the other groove size. The terminal paddle has a normal ampacity rating of 900 amperes. Do not unbolt and reuse paddle assemblies. New assemblies must be used (see Table 9 on Page 9, Code 340361). 7. In order to maintain the 36-inch climbing space for below pole-top installations, the U.S. Switch is manufactured with approximately 24 inches of phase spacing. Limit span lengths to approximately 400 feet with the 24-inch phase spacing. When the switch is mounted at pole top, additional phase spacing can be achieved by moving the center dead-end bracket next to the pole mounting bracket. Moving this center dead-end bracket will allow for span lengths greater than 400 feet and will provide increased raptor protection. 8. Switches are permitted in the working space, but switches, or any part of the switch, must not be installed in the climbing space. 9. Install the switch handle (bottom when opened) or MSO controller (bottom of cabinet) at a minimum of 15 feet above the ground line. 10. Attach the operating numbers to the pole in a vertical configuration below the switch handle or MSO controller. If the numbers cannot be readily seen from the road, install an additional set of numbers at the 9-foot level on the traffic side of the pole.

Upload: others

Post on 21-Sep-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

Rev. #17: 10-15-09 066195 Page 1 of 29

Electric Distribution

066195

Construction, Maintenance, and OperationFunction:Asset Type:

Issued by: Date:Sam Chang (SKC5) 10-15-09

Rev. #17: This document replaces Document 066195, Rev. #16. For a description of the changes, see Page 29.

25 KV UNDERARM SIDE-BREAK SWITCH, MANUAL ANDAUTOMATED

Prepared by: EOB1

Purpose and ScopeThis document specifies the requirements and preferred installation of manual and automated 25 kV underarm side-breakswitches (U.S. Switch).

General Information, Both Manual and Automated Switches

1. The U.S. Switch is required to be designed, manufactured, and tested to meet all applicable ANSI (AmericanNational Standards Institute) standards, IEEE (Institute of Electrical and Electronic Engineers) standards, and allrequirements shown and described in this document. In addition, the U.S. Switch is required to be tested to meetthe CDF (California Department of Forestry) requirements and qualified as exempt electrical equipment.

2. Switch Code 341575 (manual) or switch Code 341497 (automated) are for use in all switch applications anddistricts, except for 21 kV in AA insulation districts. For 21 kV in AA insulation districts, use switch Code341576 (manual) or switch Code 341488 (automated). The Cooper/Kearney and the S&C U.S. Switch bothuse epoxy insulators, and Inertia uses station post silicone rubber insulators.

3. The switch codes shown in this document are for the U.S. Switch. These switches are shipped as tangent3-wire, and are adaptable to all line configurations; e.g., tangent 4-wire, angle, tangent riser, dead-end riser,alley arm, etc.

4. Caution: The U.S. Switch is designed and manufactured to be installed in the underarm position only. Do notinstall this switch in the upright position. The bell crank operation will be reversed causing the switch tooperate opposite of the normal open/close positions.

5. Non-ceramic dead-end insulators and extension links are not included by the manufacturer of the switch andmust be ordered separately. Extension links are required for all installations where dead-ending occurs on theswitch arm dead-end bracket. Important: Three extension links are required per phase for the automatedswitches; i.e., two extension links on the sensor insulator side and one extension link on the opposite side.

6. The U.S. Switch is furnished with terminal paddles for use with fired wedge connectors. Select theappropriate fired wedge connector from Document 066194 by using 397.5 AAC (terminal paddle size) forone groove size, and the line conductor size for the other groove size. The terminal paddle has a normalampacity rating of 900 amperes. Do not unbolt and reuse paddle assemblies. New assemblies must beused (see Table 9 on Page 9, Code 340361).

7. In order to maintain the 36-inch climbing space for below pole-top installations, the U.S. Switch ismanufactured with approximately 24 inches of phase spacing. Limit span lengths to approximately 400 feetwith the 24-inch phase spacing. When the switch is mounted at pole top, additional phase spacing can beachieved by moving the center dead-end bracket next to the pole mounting bracket. Moving this centerdead-end bracket will allow for span lengths greater than 400 feet and will provide increased raptor protection.

8. Switches are permitted in the working space, but switches, or any part of the switch, must not be installed inthe climbing space.

9. Install the switch handle (bottom when opened) or MSO controller (bottom of cabinet) at a minimum of 15 feetabove the ground line.

10. Attach the operating numbers to the pole in a vertical configuration below the switch handle or MSO controller. Ifthe numbers cannot be readily seen from the road, install an additional set of numbers at the 9-foot level on thetraffic side of the pole.

Page 2: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 2 of 29

Installation Instructions

Manual Switch and Switch Portion of Automated Switch

11. The U.S. Switch is unitized and fully adjusted at the factory. The following are the manufacturer’s installationinstructions:A. The U.S. Switch manufacturers apply “Conducto-Lube” switch contact lubrication at the factory. During

installation, do not apply additional contact lubrication or any other product to the contacts. After a few years,a switch may become stiff and difficult to operate. If that occurs, sparingly apply “Conducto-Lube” (Code 495346) to the overhead switch contacts.

B. All Cooper U.S. Switches are furnished with three galvanized steel channels for mounting larger diameterpost-type insulators to the steel crossarm. Note: Tighten the bottom nut and lock washer to the bottom of thesteel crossarm. The phase unit has a large hole for inserting a socket.

C. Mount unitized switch to pole with 3/4-inch bolts at the desired location, using TECO shear plates as shown in“Mounting Detail” on Page 10.

D. Attach eye bolt guides to pole as required and thread 1-inch fiberglass through guides and attach to clampon bell crank.

E. Use only the switch handle that comes with that switch. The manufacturers use different throws, so mixinghandles will not work.

F. Attach control rod to control handle with the control handle and adjusting clevis in position and mount handleto pole with 5/8-inch bolts. Adjust the control rod to have a slight compression load against the switch bellcrank when the switch is in the fully closed position; i.e., there must be a slight bow in the fiberglass controlrod when the switch is in the fully closed position. Use approximately 1-1/4 inches of compression for 30 feetof rod.

G. Remove factory-installed contact blade shipping ties.

H. Check interrupters individually for proper operation. Operate each interrupter by hand. A “slamming action”should occur when testing each one by moving the rod/rocker through its complete arc. A defective loadinterrupter will have a consistent spring tension without the “slamming action.” Simply testing the switch after ithas been installed will not detect this problem.

After testing the interrupters, make sure that each interrupter is cocked (in the correct position for the nextswitch operation). If an interrupter is not properly cocked and latched, a load-break switch operation will mostlikely result in a flashover and a switch failure.

I. Operate the switch several times and check for any difficulties. A compression load should be felt on thecontrol at the end of the closing stroke. Adjustment of load can be made by adjusting clevis as needed.

J. For Cooper Switch

(1) Check to be sure that all phases are fully closed. Ensure that the reliabreak trip arm is passed through thecatch arm in the latched position; if not, adjustment should be made at adjusting clevis. If for some reasononly one or two phases are not fully closed, adjustment should be made at the interphase clamp of that unit.

K. For S&C Switch(1) Check to be sure that all phases are fully closed by visually inspecting that the blades are parallel to the

pole-unit bases. If for some reason only one or two phases are not fully closed, adjustment should bemade at the interphase clamp of that unit. The switch is properly closed when all blades are parallel to thepole-unit base, the operating linkage is in the over-toggle position, and the yellow flag on the top of theinterrupter is not visible.

(2) When reconfiguring a factory-assembled switch to an alley arm switch, follow S&C installation Drawing Number ED-8038 which is shipped with all S&C switches.

L. For Inertia Switch

(1) Verify the switch operation by closing the switch with the minimum force required to fully close at theswitch. The load interrupter flag (LIF) yellow reflector will rotate from the horizontal to the vertical positionindicating a closed and latched switch. If for some reason all phases do not close, loosen the phase crankclamp of the phase that is not closed, manually close the switchblade, and tighten the clamp.

Note: Do not lift switch by main contact during installation.

Page 3: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 3 of 29

Installation Instructions (continued)

12. Operation: The U.S. Switch should be opened or closed with one swift operation. Caution: Do not tease theswitch while opening or closing. After closing the switch, look up to make sure all phases are fully closed. Theswitch blade must be parallel with the phase unit channel. The following are the instructions for making sure thateach of the phase unit interrupters are latched:

A. On the Cooper switch, the worker must look up at the rods on the interrupter to make sure that they arelatched before opening the switch.

B. On the S&C switch, there is a yellow flag on the top of the interrupter to warn the worker if the interrupter isopen or closed. The yellow flag is present when the switch is open. In other words, the worker must look up atthe interrupter to verify that a yellow flag is not present and that the blade assembly is parallel to the pole-unitbase when the switch is closed.

C. On the Inertia switch, there is a reflective yellow flag on the rotating switchblade that is visible when the switchis open or the interrupter is not latched. The worker must look up at the interrupter when closing the switch toverify that the yellow flag is not present. Properly latched interrupter flags can be seen when viewing theswitch on the crossarm pole face from a distance of at least 30 feet.

Automated Switch Only – Inertia Switch and Motor Switch Operator (MSO)

13. Remove the control rods, MSO, and rod splices from the crate. Remove the top boards of the shipping crate andattach hoisting slings to the 5/8” holes in the two outermost phase base channels.

Note: The automated switch is completely unitized on a common steel crossarm at the factory and requires nofield adjustment. The switch is always mounted in the underarm position. Maintain all required clearanceswhen installing this equipment.

14. Install the switch portion of the automated switch as indicated in the “Manual Switch” section. Exception: SeeNote 5 on Page 1 for automated extension link requirement.

15. Drill two MSO mounting holes at 33-1/2” center-to-center distance in line with the switch control rod. Install theMSO, using two 5/8” pole bolts Verify the MSO operating mechanism is in line with the control rod (see Figure 15on Page 24).

16. Install the eyenuts and bolts through the pole and make alignment adjustments so that the control rod makes asmooth transition from the switch bell crank to the MSO output shaft. Tighten the eyenuts and space bolt nuts onthe pole and cut off any excess.

17. Verify that the switch and the MSO are in the closed position. Attach the MSO adjusting screw and control rodclamp to the MSO output shaft and cut the fiberglass control rod as shown in Figure 15 on Page 24.

18. Connect the control rod to the control rod clamp. Adjust the control rod to have a slight compression load (useapproximately 1-1/4 inches of compression for 30 feet of rod) against the switch bell crank when in the fullyclosed (up) position by using the MSO adjusting screw, and/or adjusting the adjusting screw control rod clampposition. Remove the factory-installed shipping ties from the rotating blade/female clips.

19. Check all control rod clamps and mounting hardware for proper torque. Operate the switch slowly several times toverify that the moving switch contact blades fully seat in the female contact clips. The automated switch movingcontact blade is in line with the insulators when the switch is fully closed. Adjust the MSO control rod by adjustingthe nut screw as required, to establish full seating of the contacts. The control rod should be adjusted so that theswitch fully closes with the interrupters latched, when the switch is operated slowly. Note: During manualswitching operations, the automated switch should be operated with rapid and continuous motion from start tofinish. Return the handle and operating motor interlock pin to their storage positions inside the MSO whenadjustments are completed.

20. A control power source of 120 Vac is required as follows.

A. Common Neutral Systems: The supply voltage transformer can be installed on the SCADA switch pole or anadjacent pole. The control, switch arm, and transformer neutral shall all be connected to the pole ground. Thepole ground shall be connected to the common neutral conductor.

B. Non-Common Neutral Systems: The supply voltage transformer can be installed on the SCADA switch pole oran adjacent pole. The supply voltage transformer must be a dedicated transformer; i.e., no other loads,grounds, neutrals, or services are to be connected to this transformer.

Page 4: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 4 of 29

Automated Switch Only – Inertia Switch and Motor Switch Operator (MSO) (continued)

21. Pull the hinged door of the F1 and F2 control fuses in the MSO. Install and connect the 120 Vac leads onto thelanding lugs in the MSO (see Figure 17 on Page 26). Connect the MSO battery leads together and replace thecontrol fuses.

22. Check the MSO on local control with the clutch engaged (coupled position) and the operating pin installed. Verifythe lockout light is not lit and electrically operate the MSO to open the switch. Note that the MSO prevents switchdamage by stopping the motor prior to full open position. Electrically close the switch and verify that the contactsare fully seated. Operate the switch to close a minimum of ten times to verify proper control rod adjustment.

23. Leave the switch in the proper operating position (open or closed) with the MSO door closed and locked. Makesure all control features are cut in or cut out as dictated by switching instructions. Release the switch and MSOfor local electrical operation to the appropriate switching center. Note: Make sure any abnormal control featuresare properly tagged before releasing the unit to the switching center.

References Location DocumentTransformer Connections for Distribution Lines OH: Transformers 015003. . . . . . . . . . . . . . . . . . . . . . . . . . High-Voltage Signs TIL 015070. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dead-End Attachments for Copper Conductors, Distribution and Telephone Lines OH: Conductors 015218. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Moldings, Conduits, and Attachments for Use on Wood Poles and Crossarms OH: Risers/ UG-1: Terminations 021924. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pin, Post, and Dead-End Insulators for Distribution Lines OH: Conductors 022088. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Construction Requirements for Pole Line Guys OH: Guys 022178. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spool and Clevis-Type Insulators−Distribution Lines OH: Conductors 022439. . . . . . . . . . . . . . . . . . . . . . . Guy Hooks, Pole Plates, and Thimbles for Wood Pole Lines ELS 023569. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Insulation Districts for Overhead Lines and Stations OH: General 026300. . . . . . . . . . . . . . . . . . . . . . . . . . Installation of Cable Risers on Wood Poles OH: Risers/UG-1 Terminations 027742. . . . . . . . . . . . . . . . . . Dead-End and Angle Attachments for Aluminum Conductors - Distribution Lines OH: Conductors 028851. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compression-Type Connectors for Overhead Distribution and Transmission OH: Conductors 041010. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vertical and Delta Post-Type Construction 44−115 kV Pole Lines ELS 045707. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PG&E Overhead SCADA and PDAC Installation OH: Switches 054422. . . . . . . . . . . . . . . . . . . . . . . . . . . . Overhead Transformer Installation OH: Transformers 056425. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Numerals for Identification on Distribution Equipment OH: Marking 057352. . . . . . . . . . . . . . . . . . . . . . . . . Miscellaneous Hardware for Overhead Line Construction OH: Framing 058778. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conductors for Overhead Lines OH: Conductors 059626. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fired Wedge Connectors for Primary and Secondary Distribution Lines OH: Conductors 066194. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Framing for Tangent Construction - Distribution Pole Lines OH: Framing 066196. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Equipment Clearances OH: Clearances 066198. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Corporation Padlock TIL 068200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 5 of 29

Electrical and Mechanical Ratings

Table 1 Switch Ratings

Description Rating

Maximum Voltage 25.8 kV

Continuous Current Rating 900 Amps

24-Hour Emergency 1,233 Amps

B.I.L. 150 kV

Momentary Current 40 kA − Asym

Fault Close Rating 20 kA − Asym

Table 2 Interrupter Ratings

Description Amps

Load Dropping − Current 900

Loop − Current 900

Table 3 Approximate Component Weights (pounds)

Description Cooper S&C Inertia

Manual Switch Code341575

Code341576

Code341575

Code341576

Code341575

Code341576

Three-Phase Gang Switch, Total Weight 384 551 442 510 459 467

Single Switch Unit 50 101 78 100 55 58

Crossarm 173 173 173 173 173 173

Shipping Weight With Crate 654 821 760 800 725 733

Automated Switch Code341497

Code341488

Three-Phase Gang Switch With FaultSensing Insulators − − − − 580 588

Motorized Switch Operator (MSO) − − − − 215 215

Single-Phase Switch Assembly − − − − 93 108

Three-Phase Gang Switch With FaultSensing Insulators(shipping weight with crate)

− − − − 1,111 1,119

Page 6: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 6 of 29

Electrical and Mechanical Ratings (continued)

Table 4 Bill of Material for Installing 25 kV Underarm Side-Break Switches 1

Item Description Code Document

1

Manual U.S. Switch for All Applications and Districts, Except AA at 21 kV 341575 −Manual U.S. Switch for AA Insulation Districts at 21 kV 341576 −Automated U.S. Switch for All Applications and Districts, Except AA at 21 kV 341497 −Automated U.S. Switch for AA Insulation Districts at 21 kV 341488 −

2 Non-Ceramic Insulator − 0220883 Extension Link, 14” (see Note 5 on Page 1) 340356 −4 TECO Shear Plate 199017 0587785 Fired Wedge Connector − 0661946 High-Voltage Sign 373038 0150707 Switch Number − 057352

8Dead-End Attachment (as required), Aluminum − 028851Dead-End Attachment (as required), Copper − 015218

9 Bolt, Machine, 3/4” x Length (as required) −

058778

10 Washer, Curved, Steel, Galvanized, Square, for 3/4” Bolt 19529311 Bolt, Machine, 5/8” x Length (as required) −12 Washer, 2-1/4” Square, 5/8” Bolt 19528613 Bolt, Space, 5/8” x Length (as required) −14 Eyenut for 5/8” Bolt 19530815 Padlock 016583 06820016 Insulator, Post-Type (as required) −

02208817 Stud for Insulator, 3/4” x 7-1/2” 18214418 Extension Link, 6” 180050 05877819 Shackle, Anchor 182025 04570720 Dead-End Bracket 340357 −21 Eyelet, for 3/4” Bolt 195304

05877822 Bolt, Machine, 3/4” x 8” 19233923 Washer, Curved, 4” x 4”, for 3/4” Bolt 19529824 Guy Hook, 7500# 186180 02356925 Guy Grip 16M, Alumoweld 186172

02217826 Guy Wire 16M, Alumoweld 10104527 Fiberglass Rod, 1” x 10’ 343128 −28 Washer, Lock, 3/4” Bolt 195232 −29 Washer, Spring Clip 033501 05877830 Insulator, Non-Ceramic, Dead-End Type, 15 kV 310054 02208831 Guy Thimble 186213 02356932 Nut, Square, American Standard, Regular, Galvanized, for 3/4” Bolt 195061 05877833 Splice Coupling for Fiberglass Control Rod 343084 −34 Insulator, Spool and Clevis-Type 315002 02243935 Wire, 600 V 2-#14 AWG Cu Stranded, Outdoor Rated; Color Coded: Black, White 031620 −36 Cable, Al Duplex, #6-6/1 Bare ACSR Neutral and #6 insulated Al, 600 V 294344 059626

1 See Table 9 on Page 9 for codes of replacement parts for the U.S. Switch.

Page 7: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 7 of 29

Table 4 Bill of Material for Installing 25 kV Underarm Side-Break Switches 1 (continued)Item Description Code Document37 Connector, Compression-Type (for use with Items 35 and 36) To Be Coded 04101038 Grip, Preformed, for #6-6/1 Bare ACSR Neutral and #6 Insulation Aluminum 184239 −39 Conduit, Rigid, PVC, 1-1/2” Schedule 80 (supplied in 10 or 20 feet lengths) 360433 −40 Nipple, Conduit, PVC, 1-1/2” (length as required) To Be Coded −41 Bend, 90°, R=5-3/4”, PVC, 1-1/2”, Slip Fit To Be Coded −42 LR-Fitting, PVC, 1-1/2”, Slip Fit, Kralet or Equivalent To Be Coded −43 Molding, U-Shaped, Rigid PVC, 2” 360672 021924

1 See Table 9 on Page 9 for codes of replacement parts for the U.S. Switch.

Table 5 Accessory Equipment

Description Code

Lever Extension for S&C Underarm Switches(see Detail C on Page 25) 375049

G.O. 95 PVC Control Rod Shroud (10 foot) 341504

Page 8: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 8 of 29

Electrical and Mechanical Ratings (continued)

Table 6 Clearances 1

Voltage at Switch4 kV 12 kV 21 kV

Conductor at NextUnrelated Level Vertical Clearance Required

Communications 48 Inches 72 Inches 72 InchesSecondary 48 Inches 48 Inches 48 Inches

4 kV and 12 kV 48 Inches 48 Inches 48 Inches21 kV 48 Inches 48 Inches 48 Inches

1 The minimum clearances from the bottom of the U.S. Switch (including the load-break device) to the next unrelatedlevel of conductor below, must meet the dimensions listed in this table.

Table 7 Communication Equipment − Radios

Description Code

Radio − Utilinet IWR Series III Spread Spectrum 374572

Radio – MDS 9710B, Programmable, Generic Frequency 375050

Radio – MDS 9810, Spread Spectrum 375051

Table 8 Communication Equipment – Accessory Equipment and Replacement PartsDescription Code

Antenna – 15 dB Directional, YAGi TY900 372816Bracket – Antenna, for Directional or Omni 376632Antenna Cable – ¼” x 15’ Heliax With N-Male Connectors 375048Antenna Cable – ¼” x 30’ Heliax With N-Male Connectors 375344Insulator, Analog, Lindsey Dual Shed 25 kV 375028Bulkhead Connector – N-Female to N-Female 545453Polyphaser – Surge Protector 375456Antenna – 5 dB Omnidirectional Whip 375027Antenna Lead Converter Jumper N-Male to SMA-Female – 1/4” x 6” To Be Coded

Page 9: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 9 of 29

Replacement Parts

Table 9 Data and Codes for 25 kV Underarm Side-Break Switch Replacement Parts

DescriptionCooper600 ASwitch

Cooper900 ASwitch

S&C600 A and

900 ASwitch

Inertia900 ASwitch

Manual Switch Code

One Complete Switch Phase for the U.S. Switch, 25 kV 340364 341578 342056 342112

One Complete Switch Phase for the U.S. Switch, 35 kV 340366 341579 342058 342116

One Complete Load-Break Device for the U.S. Switch(includes all hardware) 340360 341584 342059 342117

One Load-Break Device Only for the U.S. Switch 340367 341587 342197 342120

One 25 kV Station Post Insulator for the U.S. Switch 340359 341732 342198 342123

One 35 kV Station Post Insulator for the U.S. Switch 340358 341590 342057 342126

One Terminal Paddle and Anti-Corrosion Pad andAll Terminal Mounting Hardware for the U.S. Switch(minimum order quantities in multiples of 24)

340361 340361 340361 340361

Box of 12 Replacement Indicator Flags − − − 342149

Automated Switch Code

MSO With Sensor Kit and Sensor Cable Assembly forExisting Underarm Side-Break SCADA Retrofit (all districts) − − − 342487

MSO Basic Motor Operator Without Control Module and RTU − − − 342439

MSO With 4 Foot Cable for Existing SCADA Switches andHydraulic SEO Replacements − − − 342440

25 kV, Underarm Switch With Sensor Kit − − − 341499

25 kV, AA Districts Underarm Switch With Sensor Kit − − − 341491

MSO Control Module With RTU − − − 342437

Sensor Cable Harness, 38-Foot (underarm switches only) − − − 342435

Sensor Cable Harness, 4-Foot (used with existing sensors andreplacement of hydraulic operator) − − − 342434

Reliatronics RTU2000 (PG&E 2179 protocol) − − − 375118

Harness, Reliatronics, Status, Control, Analog, Power − − − Uncoded

Battery Pack Assembly, 24 Vdc With Disconnect Plug − − − 375119

MSO Manual Operating Handle − − − Uncoded

MSO Interlock Pin − − − Uncoded

Lamp, 24 Vdc, MSO Operation Panel (package of three) − − − Uncoded

Fuse, 15-Amp (package of three) − − − Uncoded

Fuse, 5-Amp (package of three) − − − Uncoded

Rod Coupling Assembly for MSO to 1” Fiberglass Rod − − − Uncoded

AC Installation Kit − 1” x 36” Superflex ConduitWith Couplings − − − To Be

Coded

Page 10: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 10 of 29

Generic Switch RequirementsNotes

1. Bill of material items shown in this figure are common for the various switch configurations that follow inthis document.

2. The U.S. Switch is furnished with 30 feet of fiberglass control rod and the splices for the fiberglass.3. Install control rod guides at 5-foot (maximum) intervals. Control rod guides may be spaced 5 to 6 feet between the

operating handle to the first eyenut and between the last eyenut to the bell crank connection.4. The U.S. Switch is furnished with a steel arm and three dead-end brackets.

1

2

3

5

6

7

8

11

See Note 9 on Page 1

See Note 3

13 1412

27 See Note 2

See Note 6on Page 1

15

Anti-Split

5”

6”

8” MinimumFrom Pole Top

Mounting Detail

Anti-Split Detail

1010

299

9

2923 4

36”ClimbingSpace(typical)

For Temporary Grounding

16”32

Nut to Make Shear Plate Captive

The CooperU.S. Switch isillustrated on alldocuments. The S&Cand Inertia U.S. Switchis similar.

See Note 11Bon Page 2

Figure 1 Generic Switch Requirements

See Note 5 on Page 1

29

29

33

Page 11: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 11 of 29

3-Wire, Tangent Construction - AlternateNotes

1. See Page 10 for common bill of material requirements.2. The dimensions shown in the figure below are as received from the manufacturer. The S&C and Inertia

dimensions are the same as the Cooper dimensions, except for those shown with an asterisk (*).3. Use the Inertia dimensions. That way, if the Inertia switch is used as a replacement, there will not be a

clearance problem.4. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

22” *

24-3/8”

23”50-1/2”

26”

31”

3”

3”27-1/4” *26-7/16”

120”

Inertia23-1/4” −27-1/4” −

S&C Cooper20-7/8” − 21-15/16” − Code 34157524-7/8” − 25-15/16” − Code 341576 }

24-3/4” *

35” *34”

* = Inertia and S&C dimensions.Figure 2

3-Wire, Tangent Construction - Alternate

Table 6 on Page 8See Note 3 Above and

See Note 4

Page 12: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 12 of 29

3-Wire, Tangent Construction − Preferred (see Note 3)

Notes

1. See Page 10 for common bill of material requirements.

2. For angle construction, the maximum angle is limited by the post insulator strength. For the maximumallowable angle, see Document 066196, table titled “Angle and Span Limitation for Fiberglass BracketConstruction.”

3. This preferred construction shall not be used in the following three conditions:

A. Where raptor protection is a concern. Use the “Alternate Tangent Construction” type of design shown on Page 11.

B. Where the switch is a SCADA switch and the arm is grounded. Use the “Alternate Tangent Construction” typeof design shown on Page 11.

C. Where the angle is greater than that as determined in Note 2 above. Use the “Angle Construction” type ofdesign shown on Page 13.

16

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅÅ

ÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅ

17

Figure 3 3-Wire, Tangent Construction − Preferred

18

Page 13: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 13 of 29

3-Wire, Angle Construction

Notes

1. The U.S. Switch can be installed in any angle installation, up to 35°. The angle can be on either side of theswitch or split.

2. See Page 10 for common bill of material requirements.

3. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

SeeNote 3

19

Figure 4 3-Wire, Angle Construction

Page 14: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 14 of 29

3-Wire, Tangent Riser ConstructionNotes

1. For details on the riser installation, see the “Risers” section of the Electric Overhead Construction Manual.

2. See Page 10 for common bill of material requirements.3. Where the switch is a SCADA switch and the arm is grounded, use Part 3 insulators and cover all three

phases with insulator/line covers.

See Note 1

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅ

ÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

16

ÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

17

Figure 5 3-Wire, Tangent Riser Construction

Page 15: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 15 of 29

3-Wire, Dead-End Riser ConstructionNotes

1. Regarding dead-end riser installations, the preferred construction is to install the U.S. Switch in a normaltangent configuration one span before the riser. This is to eliminate pole “clutter” on the riser pole. If fieldconditions do not allow for a switch to be installed one span before the riser, the U.S. Switch may be installedas a riser switch.

2. For details on the riser installation, see the “Risers” section of the Electric Overhead Construction Manual.3. The U.S. Switch is capable of handling 3,500 pounds per conductor of three-wire dead-end tension.

4. See Page 10 for common bill of material requirements.

5. See the “Guys” section of the Electric Overhead Construction Manual for down guy requirements.6. Where the switch is a SCADA switch and the arm is grounded, use Part 3 insulators and cover all three

phases with insulator/line covers.

16

See Note 2

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ ÅÅ

ÅÅÅÅ

ÅÅÅÅÅÅÅ

21

ÅÅÅÅÅÅÅ

ÅÅ

ÅÅÅÅ

17

Figure 6 3-Wire, Dead-End Riser Construction

Page 16: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 16 of 29

3-Wire, Alley Arm ConstructionNotes

1. See Page 10 for common bill of material requirements.

2. The insulator is only needed for below pole-top installations. A guy thimble is required for all installations.3. The S&C and Inertia dimensions are the same as the Cooper dimensions, except for those shown with an

asterisk (*).4. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

29-3/4”

16-3/4”

19”

29-1/4”

3”

56”

2-1/4”

2825 22

26

21

SeeNote 2

31

7-1/4”

7-1/2”

9 23 2425

30

19”

2-1/2”

InterphaseRod

Detail A

See Detail A

30” *5” *5-1/4”

* = Inertia and S&C dimensions. Figure 7 3-Wire, Alley Arm Construction

SeeNote 4

Page 17: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 17 of 29

4-Wire, Tangent Construction - Alternate

Note

1. See Page 10 for common bill of material requirements.

2. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

16

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅ

17

25-1/2”

31-3/4”

Figure 8 4-Wire, Tangent Construction - Alternate

PrimaryNeutral

SeeNote 2

Page 18: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 18 of 29

4-Wire, Tangent Construction − Preferred (see Note 3)

Notes

1. See Page 10 for common bill of material requirements.

2. For angle construction, the maximum angle is limited by the post insulator strength. For the maximumallowable angle, see Document 066196, table titled “Angle and Span Limitation for Fiberglass BracketConstruction.”

3. This preferred construction shall not be used in the following three conditions:

A. Where raptor protection is a concern. Use the “Alternate Tangent Construction” type of design shown on Page 17.

B. Where the switch is a SCADA switch and the arm is grounded. Use the “Alternate Tangent Construction” typeof design shown on Page 17.

C. Where the angle is greater than that as determined in Note 2 above. Use the “Angle Construction” type ofdesign shown on Page 19.

ÅÅÅÅÅÅ

ÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

Primary Neutral

16

17

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅ

Figure 9 4-Wire, Tangent Construction − Preferred

18

Page 19: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 19 of 29

4-Wire, Angle Construction

Notes

1. The U.S. Switch can be installed in any angle installation, up to 35°.2. See Page 10 for common bill of material requirements.3. For below pole-top installations, the angle must be on the arm side in order to maintain climbing space. For

pole-top installations, the angle can be on either side of the switch or split.4. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

6-3/4”

19

16

25-1/2”

24-3/4”

ÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅ

ÅÅ

ÅÅÅÅ

20

17

Figure 10 4-Wire, Angle Construction

Primary Neutral

SeeNote 4

Page 20: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 20 of 29

4-Wire, Tangent Riser Construction

Notes

1. For details on the riser installation, see the “Risers” section of the Electric Overhead Construction Manual.

2. See Page 10 for common bill of material requirements.3. Where the switch is a SCADA switch and the arm is grounded, use Part 3 insulators and cover all three

phases with insulator/line covers.

ÅÅÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

16

ÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅ

ÅÅ

ÅÅÅÅÅÅ

See Note 1

ÅÅÅÅÅÅÅ

ÅÅÅ

ÅÅÅÅÅÅÅ

17

Figure 11 4-Wire, Tangent Riser Construction

Primary Neutral

Page 21: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 21 of 29

4-Wire, Dead-End Riser Construction

Notes

1. Regarding dead-end riser installations, the preferred construction is to install the U.S. Switch in a normaltangent configuration one span before the riser. This is to eliminate pole “clutter” on the riser pole. If fieldconditions do not allow for a switch to be installed one span before the riser, the U.S. Switch may be installedas a riser switch.

2. For details on the riser installation, see the “Risers” section of the Electric Overhead Construction Manual.

3. The U.S. Switch is capable of handling 3,000 pounds per conductor of four-wire dead-end tension.

4. See Page 10 for common bill of material requirements.

5. See the “Guys” section of the Electric Overhead Construction Manual for down guy requirements.6. Where the switch is a SCADA switch and the arm is grounded, use Part 3 insulators and cover all three

phases with insulator/line covers.

6-3/4”

16

25-1/2”

24-3/4”

20

See Note 2

17

Primary Neutral

ÅÅÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅ

ÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅÅÅÅÅÅ

ÅÅÅÅ

ÅÅ

ÅÅÅÅÅ

Figure 12 4-Wire, Dead-End Riser Construction

Page 22: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 22 of 29

4-Wire, Alley Arm ConstructionNotes

1. See Page 10 for common bill of material requirements.

2. The insulator is only needed for below pole-top installations. A guy thimble is required for all installations.3. The S&C and Inertia dimensions are the same as the Cooper dimensions, except for those shown with an

asterisk (*).

4. Where the switch is a SCADA switch, two links are required on all three line current sensor insulator sides.

29-3/4”

16-3/4”

19”

29-1/4”

3”

56”

2-1/4”

2825 22 2621

SeeNote 2

31

7-1/4”

7-1/2”

9 23 2425

PrimaryNeutral

30

ÅÅÅÅÅÅÅÅ

ÅÅÅÅÅÅ

ÅÅ

ÅÅÅÅÅÅÅ

19”

2-1/2”

InterphaseRod

Detail B

See Detail B

30” *

5” *

5-1/4”

= Inertia and S&C dimensions.* Figure 13 4-Wire, Alley Arm Construction

SeeNote 4

Page 23: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 23 of 29

Automated Switch − General Construction Requirements

39

36” ClimbingSpace atSwitch

Extension Links, 14” (3)

27” Standard31” AA Districts

15” Min.

48” Minimum

TELCO Cable

12” Min.

For switch installation details,see the manual switch sectionof this document.

72” Minimum(see G.O. 95Rule 54.4-Gand 87.4-H forexemptions)

Top of Mounting Bracket

Control Rod PVC ShroudTubing Must Extend a Minimumof 12” Above CommunicationLevel (see Table 5 on Page 7)

See Document 054422For Mounting and CoaxialCable Requirements

Stored EnergyMotorized SwitchOperator (MSO)

See General GroundingDetail Sheet Case Ground9’ 0” Minimum

to Ground

1” Conduit Hold for120 V Supply, SensorCable Connector andN-Style CoaxialConnector Supplied onMSO Cabinet Bottom

Tie Wrap Sensorand Coaxial

Cables to ConduitFigure 14 General Construction Requirements

48” Minimum WithGuard Arm72” WithoutGuard Arm

42

38

3736

35

34

16

12 13

15

43

4140

43

4140

42

120 Vac Option 1For Transformer and Cutout

Installation Details, SeeDocument 056425 and

Note 20 on Page 3.

120 Vac Option 2See Note 20on Page 3

Page 24: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 24 of 29

Automated Switch (continued) − MSO Dimensions

Compression Adjusting Screw

Lifting Point

5/8” Mounting Boltsat 33-1/2” CenterDistance

Motorized SwitchOperator (MSO)

Manual Operating Handle Rotation

Open

Closed

Inertia

MSO

Line Current Sensor

14-3/8”

6”

Figure 15 MSO Dimensions

Rod Cut-Off 24”−25”

Page 25: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 25 of 29

Automated Switch (continued) − MSO Switch Throws

CAUTION!Switch Type Must Be Determined Prior to Installation of Switch Operator on Existing U.S. Switches

Proper Switch Throw Incorrect AutomatedSwitch Throw

Corrected AutomatedSwitch Throw

Close

Open

Remove Supplied Leverand Replace With Extended

Lever (see Table 5on Page 7)

10-1/4” − 10-1/2”

14-1/2” − 14-7/8”

6-3/8” − 7-3/8” 10-1/4”

9” − 10-1/4”14-1/2”

8”

4-1/8”

Figure 16 MSO Switch Throws

Detail C Lever Extension

Inertia and Cooper Switches S&C Switches

Page 26: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 26 of 29

Automated Switch (continued) − 120 Vac Terminations and Grounding

MSOGrounding Lug

Current Sensor

Antenna Connection

Sensor Cable Connection

Grounding Lug

Gas Discharge Surge Arrestors(factory-Installed)

Terminal Block Located BehindControl Panel in Lower Rightof MSO

Grounding Lug on MSOMounting Bracket

Earth

Ground

120 VacNeutral

120 VacLine

See Note 20 on Page 3

Figure 17 120 Vac Terminations and Grounding

Page 27: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 27 of 29

Automated Switch (continued) − Sensor and Telecom Cable Wiring Diagram

MSO

Red White BlueA B C

Sensor Circular Connector(color coded)

Current Sensor

Stainless SteelWire Ties

Excess Cable

Cable Grip

Connector to MSO

Telecom Lease Line Connection Cable

38’ Sensor Cable Assembly

See RTU InstallationGuidefor RTU Terminations

Telecom Lease LineField TerminationCable Breakout

P5-RTUMolex

Connector

See ModemInstallationGuide forInternalTerminations

Sensor ConnectorF1

MSO Module12 Pin MSOConnector

Three-WayBreakout

Red

Red

Red

Orange

Orange/Black

Orange

Orange

Red

Red

Black Black

Black

Black Black

Yellow Yellow

Yellow/Black

Yellow

Brown Brown Blue

Blue

BlueBlue

Purple Purple

Black

Black

Black

Grey Grey

White White

Black

P 5−6

P 5−7

P 5−8

P 5−9

1

3

5

7

A

C

E

H

A

A, B, C Common

C

E

H

K

L

M

N

K

L

M

N

TELCOPigtailCable

IA Phase −

IC Phase −

IB Phase −

9

11

10

12

Ring +

Tip +

Ring −

Tip −

(Blue 8’ 5”)IC Phase + C

(White 4’ 11”)IB Phase + B

(Red 8’ 5”)IA Phase + A

Figure 18 Sensor and Telecom Cable Wiring Diagram

Page 28: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09066195 Page 28 of 29

P1 P2 P3 P4 P5

RS232 Power/EIA585 Inputs Outputs Analog

CaseGround

1,2

3,4

TXRXGND.RTSCTS

RS232-2RS232-3RS232-5RS232-7RS232-8

TB1-1TB1-18

+24 Vdc

−24 Vdc Common Black P1-3Red P1-1

TB1-9

TB1-10TB1-11TB1-12TB1-18

TB1-13

TB1-15TB1-16

TB1-18

Open

Motor Operator Status InputsPurple P3-1

ClosedRemoteMotor Decoupled(-) dc Common

WhiteGreenYellowBlack

P3-2P3-3P3-4

P3-5

P3-8P3-9P3-10

P3-12

BlueOrangeGray

Black

Low Battery LockoutInterlock Pin RemovedPower Supply

(−) dc Common

Current/VoltageSensor Inputs

BlackF1-2

TB1-3 White

ControlModuleSlide-InConnector

12-PinBulkheadConnector

P5-6 Black 1A F-1 AP5-1P5-7P5-2P5-8P5-3P5-9P5-4

Yellow

Brown

Purple Current Common F-7

VA Note 1 F-2

VC

F-3F-4F-5F-6

1C

1BVB

F-8Voltage Common Note 1

BCDEFHJ

RTU Control Outputs

TB1-4P4-1P4-2

P4-3P4-4P4-5P4-6P4-7P4-8P4-9P4-10P4-11P4-12

PurpleWhite

GreenYellow

BlueOrange

Switch Open

Switch Close

Battery Test

TB1-5

TB1-6

TB1- 8Control(−24 Vdc Common)

To RTU Statusand ControlTerminal Points

TerminalBlock 1

1 2 3 4 5 6 7 8 9

10 11 1213 14 15161718

TB1 Verification:Remote SBO ControlPoints Can Be Verifiedby Using a JumperConnection From:TB18 (−24 Vdc) toTB4−TB7.

Status Output PointsCan Be Verified byChecking the VoltageBetween TB17 (+24 Vdc)to TB8-TB15. The StatusIs True When +24 Vdc IsPresent.

Terminal Block 1 (TB1)1. +24 Vdc2. +12 Vdc3. Neutral for 120 Vac4. Control Switch Open5. Control Switch Close6. Spare7. Control Battery Lockout Reset8. Control Common9. Status, Opened Switch

10. Status, Closed Switch11. Status, Local/Remote Toggle (+24 Vdc=Remote True)12. Status, Motor Decoupled13. Status, Battery Lockout14. 12 Vdc Common15. Interlock Pin Removed16. Status, Power Supply (115 Vac Present)17. RTU Wetting Source (+24 Vdc)18. RTU Common (−24 Vdc)

Fuse,115Vac,115-Amp

-F1BussABC-15A

Fuse,24Vdc2-Amp−F2FuseType:BussMDA2

Note 1. Voltage Sensors Not Attached: P5-1: 120 Vac Line Output P5-4: 120 Vac Neutral Input

1,2,3,4,5,6,7,8,9 1,2,3,4 1,2,3,4,5,6,7,8,9 10,11,12,13,14

1,2,3,4,5,6,7,8,9,10,11,12 1,2,3,4,5,6,7,8,9,10

Reliatronics RTU2000

Figure 19 SCADA Control and Status Points

List and Remote Terminal UnitWiring Diagram

Page 29: 066195 - 25 kV Underarm Side-Break Switch, Manual and ...€¦ · 25 kV Underarm Side-Break Switch, Manual and Automated Rev. #17: 10-15-09 066195 Page 3 of 29 Installation Instructions

OH: Switches

25 kV Underarm Side-Break Switch, Manual and Automated

Rev. #17: 10-15-09 066195 Page 29 of 29

Revision Notes

Revision 17 has the following changes:

1. Updated the Reference section on Page 4.

2. Revised the size of the antenna cable and added a new material code in Table 8 on Page 8.

3. Revised Note 3 on Page 10.

4. Changed Item 34 to 33 in Figure 1 on Page 10.

5. Changed Item 12 to 29 in Figure 1 on Page 10.