Passive House Institute, Jan Steiger, 1 June 2015
PHPP & designPH
Energy efficiency planning at a higher level
-
Passive House Institute, Jan Steiger, 1 June 2015
What is PHPP?
Passive House Planning Package
- Energy balance calculation within a conventional Excel format
- Simple and direct data input - Validated accuracy of results- Continuous further development- Verification tool for Passive House
buildings and EnerPHit retrofits- Includes detailed user manual with
energy efficiency advice- Import/Export data interface for other
programmes
- 3D data entry tool designPH (plug-in for SketchUP)
-
Passive House Institute, Jan Steiger, 1 June 2015
Adjust all sorts of Parameters
AIRTIGHTNESSVENTILATION
(natural/mechanical)
INSULATION THERMALBRIDGES
WINDOWS
SHADING
-
Passive House Institute, Jan Steiger, 1 June 2015
Enter and evaluate all sorts of designs
-
Passive House Institute, Jan Steiger, 1 June 2015
Areas
Windows
Shading
Ground
U-Value
Climate
Ventilation
Annual heating
Heating
no
Heating casecriteria met? yes
Components
Heating load
Additional vent
Verification
SummVent
Passive cooling?
frequencyof overheating
10%
Cooling
Cooling units
Cooling load
Summer
no
yes
yes
no
Optional:Compact
Boiler
District heat
HP
HP Ground
PV
SolarDHW
no yes no yesCooling case criteria met?*
PE valuecriteria met?
Electr. non-res
Aux electricity
PE Value
DHW+Distribution
IHG Non-Res
Use non-res
* Not for EnerPHit
Input required
Entry possibly required
No entry required
Passive House /
EnerPHit
Heating case worksheets
PE- demandworksheets
Cooling caseworksheets
Start
Building envelope
Mechanical systems
Check Variants Comparison
-
Passive House Institute, Jan Steiger, 1 June 2015
PHPP Illustrated by Sarah Lewis :
Step-by-Step approach how to enter building data into PHPP 8
General recommendations for Passive House design
Released by RIBA Publishing
It`s easy!
-
Passive House Institute, Jan Steiger, 1 June 2015
PHPP 9: Calculation results
- Annual heating demand [kWh/(ma)] and maximal heating load [W/m]
- In case of active cooling: annual cooling demand [kWh/(ma)] and maximal cooling load [W/m]
- Comfort in summer through passive cooling: Frequency of overheating [%]
- Annual Primary Energy Renewable and Primary energy demands for all energy services in the entire building [kWh/(ma)]
- Estimation of annual renewable energy gains [kWh/(ma)]
-
Passive House Institute, Jan Steiger, 1 June 2015
PHPP: Validated precision
- Very good compliance of the energy demand calculated with PHPP andthe measured consumption or load detected in monitoring projects
- Compliance of the calculated heating load- The more efficient the building, the lower the deviations- No performance gaps when planning with PHPP - PHPP is the ideal design tool for efficient buildings like - Passive Houses, NZEBs or other efficiency projects !
Monitoring projects:
Comparison ofcalculated demand andmeasured consumption
-
Passive House Institute, Jan Steiger, 1 June 2015
0
50
100
150
1978 1982 1986 1990 1994 1998 2002 2006 2010 2014 2018
P
r
i
m
r
e
n
e
r
g
i
e
/
H
e
i
z
w
r
m
e
b
e
d
a
r
f
[
k
W
h
/
(
m
a
)
]
B
e
z
u
g
a
u
f
N
u
t
z
f
l
c
h
e
/
W
o
h
n
f
l
c
h
e
0
20
40
60
80
100
120
140
160
180
WSchV 77
WSchV 82
Primrenergiebedarf: Heizung, Warmwasser, Hilfsenergie
Heizwrmebedarf
WSchV95EnEV
02/04/07EnEV09
EnEV14
Primrenergie
Heizwrme
0
50
100
150
1978 1982 1986 1990 1994 1998 2002 2006 2010 2014 2018
P
r
i
m
a
r
y
e
n
e
r
g
y
/
H
e
a
t
i
n
g
e
n
e
r
g
y
d
e
m
a
n
d
[
k
W
h
/
(
m
a
)
]
U
s
e
f
u
l
f
l
o
o
r
s
p
a
c
e
/
l
i
v
i
n
g
s
p
a
c
e
0
20
40
60
80
100
120
140
160
180
WSchV 77
WSchV 82
Primary energy demant: Heating, hot water, auxiliary electricity
Heat energy demand
WSchV95EnEV
02/04/07EnEV09
EnEV14
Primary energy
Heat energy
PassivehousePilot project
NZEB?
2021
Passivehouse Promotion by KfW
Source: 17 International Passive House Conference in Frankfurt/M.
Passive Houses have been succsesfullydesigned and build with PHPP since 20 years !
-
Passive House Institute, Jan Steiger, 1 June 2015
90% Reduction of Heating Energy Demand often
morethan90%
P
H
A
v
e
r
a
g
e
e
x
i
s
t
i
n
g
b
u
i
l
d
i
n
g
s
:
f
o
s
s
i
l
e
f
u
e
l
Unterrainer
200 kWh/(ma) 15 kWh/(ma)
Passive House Institute
Calculate the reduction potential with PHPP!.....
-
Passive House Institute, Jan Steiger, 1 June 2015
and enable the transition to high efficiencyto make a sustainable energy supply feasible
Acc. EnEVEfficiency technology
Trend
SustainableEnergy
Avaiable
H
e
a
t
i
n
g
E
n
e
r
g
y
C
o
n
s
u
m
p
t
i
o
n
i
n
D
E
M
r
d
k
W
h
-
Passive House Institute, Jan Steiger, 1 June 2015
PHPP: An international tool
More information: www.passivehouse.com
PHPP* resellers available: Australia | Austria | Belgium | Bulgaria | Canada | Czech Republic | Denmark | England | Estonia | Finland | France | Germany | Greece | Hungary | Ireland | Italy | Japan | Korea | Kosovo | Latvia | Netherlands | Poland | Russia | Serbia | Slovakia | Spain | Sweden | Switzerland | Ukraine | USA PHPP* translations available: Belgian | Bulgarian | Czech | Dutch | English | French | Flemish | German | Hungarian | Italian | Japanese | Korean | Polish | Russian | Spanish | Serbian | Swedish | Slovakian | Ukrainian | * Latest version of PHPP may not be available in all languages
-
Passive House Institute, Jan Steiger, 1 June 2015
For an international standard!
Climate No Region Heating-/Cooling-Region IndicatorHeatingclimate
1 Arctic > 1182 Cold > 53,83 Cool-temperate > 274 Warm-temperate > -45 Warm All others
Coolingclimate
6 Hote > 1187 Very hot > 139,5
1 Arctic
2 Cold
3 Cool, temperate
4 Warm, temperate
5 Warm
6 Hot
7 Very hot
1 Energy recovery
Now including component and certification criteria for 7 international climate zones Passivhaus Institut 2014
Passivhaus Institut 2014
-
Passive House Institute, Jan Steiger, 1 June 2015
Passive House Planning Package 9 (2015)
-
Passive House Institute, Jan Steiger, 1 June 2015
NEW! in PHPP 9
The energy balance and planning tool for efficient buildings and retrofits such as Passive House buildings and NZEBs
- Sustainability evaluation after PER factors- Verification of Passive House classes - International climate zones and EnerPHit criteria- Input for calculation of variants - Cost-efficiency comparison for planning variants- Systematic input assistance and error messages- Extension of calculation fo heat losses for DHW - Comprehensive component categories included- Extension of PHPP additional tools
Passive House Institute
-
Passive House Institute, Jan Steiger, 1 June 2015
The NZEB Challange
Enable sustainable energy supply
Apply highest efficiency and couple itWith renewable energy production
The new Passive House Classes:
Classic - Plus - Premium
-
Passive House Institute, Jan Steiger, 1 June 2015
Evaluation of energy generation
Do not allocate energy generation directly with energy demand!- The plus energy approach leads to erroneous optimisation.- Multi-storey buildings are systematically penalised, since they have less roof or facade areas in comparison to useful area availablePHI evaluation proposal:- Energy generation will be drawn from planned ground area of heated space.- New off-site Incorporate systems
-
Passive House Institute, Jan Steiger, 1 June 2015
Primary Energy Renewable (PER)
Renewable energygains
Energy demand depending on use
Direct use of energy or Energy storage
Passive House Institute 2014
Sustainability evaluation based on a future scenario in which only renewable energies are in operation.
-
Passive House Institute, Jan Steiger, 1 June 2015
Even a Passive House cannot completely be supplied with PV energy in winter! The more storeys, the harder it gets!
Sustainable coverage of energy demand
The winter hole: annual course of energy demand Passivhaus Institut 2014
-
Passive House Institute, Jan Steiger, 1 June 2015
classic
Classic
+ Generation of renewable energy and high energy efficiency
The new Passive House Classes
Plus Premium
Basic requirement Very low heating/cooling demand 15 kWh/(ma)
Efficiency !
-
Passive House Institute, Jan Steiger, 1 June 2015
Renewable Primary Energy Demand: Heating, DHW, Auxhiliary and Appliances
30
3045
60
Renewableenergy production[kWhPER/(mGrund*a)]
60
120
classic
plus
premium
for efficiency and renewables
RenewablePrimary Energy Demand
[kWhPER/(mEBF*a)]
-
Passive House Institute, Jan Steiger, 1 June 2015
Verification of Passive House Classes
Customary verification of PE is still available
Evaluation of efficiency and RES specific to the project
P
E
R
/
P
E
C
r
i
t
e
r
i
a
-
E
f
f
i
c
i
e
n
c
y
-
Passive House Institute, Jan Steiger, 1 June 2015
Practical challenges designing NZEBs
Deal with design design variants andefficiency options
Plan and visualise step-by-step refurbishment processes
Enable economic comparisons ofefficiency options
-
Passive House Institute, Jan Steiger, 1 June 2015
Calculation of variants: what is possible?
Parallel calculation of all variants- Evaluation of planning variants- Determination of modernisation steps- Representation of demand reduction
Active variant
-
Passive House Institute, Jan Steiger, 1 June 2015
Energy balance for stepwise retrofit
25
Variantenberechnung Passivhaus mit PHPP Version 9.1Passivhaus-Reihenendhaus / Klima: PHPP-Standard / EBF: 156 m / Heizen: 19,86 kWh/(ma) / bertemperatur: 0,7 % / PER: 43,8 kWh/(ma)
aktiv
aktive Variante whlen >>
5
-
E
n
e
r
P
H
i
t
B
e
s
t
a
n
d
F
e
n
s
t
e
r
u
n
d
T
r
e
n
A
u
e
n
w
a
n
d
-
d
m
m
u
n
g
D
a
c
h
u
n
d
L
u
f
t
d
i
c
h
t
h
e
i
t
s
-
t
e
s
t
E
n
e
r
P
H
i
t
Ergebnisse Einheit 5 1 2 3 4 5Heizwrmebedarf kWh/(ma) 19,9 174,2 107,1 48,5 27,8 19,9
Heizlast W/m 13,2 71,9 47,3 25,0 16,7 13,2Khl- + Entfeuchtungsbedarf kWh/(ma)
Khllast W/mbertemperaturhufigkeit (> 25 C) % 0,7 0,2 0,2 0,4 0,6 0,7
PER-Bedarf kWh/(ma) 43,8 214,2 140,5 76,0 52,2 43,8Passivhaus Classic? ja / nein nein nein nein nein nein nein
Endenergie - - - - - - Nutzerdefiniert: verknpfte Ergebnisse 0,0 0,0 0,0 0,0 0,0
Eingangsgren Einheit Wert 1 2 3 4 5 Bauteilschichten U-Werte
Strahlungsbilanz Flchen Wrmebrcken Flchen
Fenster und Verschattung Fenster Verschattung Lftung Lftung SommLuft
Wrmeerzeuger PER WP Kompakt Kessel Fernwrme Kompressor-Khlgerte Khlgerte Nutzerdefiniert
0100200300400500
1-Bestand 2-Schlechter
Wrmeschutz
3- Mssiger
Wrmeschutz
4-Passivhaus
mit WP +
Solarthermie
Heating demand [kWh/(ma)]
www.europhit.eu
-
Passive House Institute, Jan Steiger, 1 June 2015
Pre-certification for stepwise retrofits
www.europhit.eu
-
Passive House Institute, Jan Steiger, 1 June 2015
Applicable all over Europe: International component criteria
Verification of EnerPHit criteria according to quality of building components based on climate zone requirements
www.europhit.eu
-
Passive House Institute, Jan Steiger, 1 June 2015
Variant calculation: how it works
Entry of variousefficiency parameters
Varied calculation values will be colour-coded+Applyparametersto the worksheets
-
Passive House Institute, Jan Steiger, 1 June 2015
Cost-efficiency comparison
- Configuration of comparison parameters
- Implemented results diagramme
- Input of boundary conditions
www.europhit.eu
-
Passive House Institute, Jan Steiger, 1 June 2015
Pilot Projects
www.europhit.eu/projects
www.europhit.eu
-
Passive House Institute, Jan Steiger, 1 June 2015
For more information
www.europhit.eu
The sole responsibility for the content of this presentation lieswith the authors. It does not necessarily reflect the opinion of theEuropean Union. Neither the EACI nor the EuropeanCommission are responsible for any use that may be made ofthe information contained therein.
-
Passive House Institute, Jan Steiger, 1 June 2015
Guidance for data entry of NZEBs
Error messages
Plausibility checks
-
Passive House Institute, Jan Steiger, 1 June 2015
Systematic layout + Input assistance
Headline with project data
Error / Information column with input advice and error messages
-
Passive House Institute, Jan Steiger, 1 June 2015
Control worksheet: centralised assistance
Error messages or information about- Incomplete input- Overview of possible input problems in PHPP file
-
Passive House Institute, Jan Steiger, 1 June 2015
Plausibility checks
Es wurde eine sehr kleine Wrmeleitfhigkeit angesetzt
Die Flche des Dachs und die der Bodenplatte weichen stark voneinander ab
Die Flchen nach Osten/Westen bzwNorden/Sden weichen stark voneinander ab
Der Verglasungsanteil am Gesamtgebude (inkl. Dach) ist sehr hoch oder sehr klein
Es gibt sehr geringe U-Werte der Bauteile Es gibt sehr geringe Ug-Werte der Fenster Es wurde ein sehr kleiner Fenstereinbauwert
fr seitlich oder oben eingegeben Es gibt keine Verteilverluste durch
Heizungsrohre, ist das korrekt? Es wurde eine Lftung mit hoher WRG /
hohem Luftwechsel eingegeben Die Flche fr PV / Solarthermie bersteigt
die Dachflche
Which support- Reasonable / corret data entry- Avoiding typing errors
-
Passive House Institute, Jan Steiger, 1 June 2015
Component recommendations
The window traffic-light informs about meeting comfort criterion in winter
Green: achieved
Yellow: acceptable in case of small windows
Red: not achieved, additional radiators are necessary
Component recommendations serve as planning guidelines
-
Passive House Institute, Jan Steiger, 1 June 2015
Component data for entry of NZEBs
Entry of several PV systems
Detailed calculation of DHW distribution
Heat recovery concepts for shower water
-
Passive House Institute, Jan Steiger, 1 June 2015
Input extension for PV systems
Input possibility for- Up to 5 different PV systems- Allocation to building areas- Input of module surfaces
-
Passive House Institute, Jan Steiger, 1 June 2015
DHW+Distribution: Extension of input
Possibility of input for- Several heating and DHW distribution pipes- Inside and outside thermal envelope- Each with consideration of thermal bridges
-
Passive House Institute, Jan Steiger, 1 June 2015
Auxiliary calculation: HR shower water
Input of performance rate of shower HR from certified systemsSeparate consideration of DHW demand for showers and others
Reduction of DHW demand
-
Passive House Institute, Jan Steiger, 1 June 2015
Connectivity and data access
Optimised Import interface
Availibility of components
designPH as 3D data interface
-
Passive House Institute, Jan Steiger, 1 June 2015
Centralisation of all PHPP tools in one file
- Import / Export macro- Import from PHPP 8- Profile settings- Row insertion- Import of component updates
PHPP_V9.1_Tools
-
Passive House Institute, Jan Steiger, 1 June 2015
TodayComponent updatesPeriodical update all Certified Passive House ComponentsImport of component update lists into PHPP9Soon: Copy to Clipboard Feature :Enables copying of specific data from an individual Passive House Components by downloading it from the online component database.
Link to component data base
-
Passive House Institute, Jan Steiger, 1 June 2015
PHPP 9 naturally also with designPH
designPH 1.1: - Data export to PHPP 9- Shading factors relating to the project and current components
-
Passive House Institute, Jan Steiger, 1 June 2015
designPH EDU:- price for students / universities- Low budget licence fees, - Limited features or component availability- Available as bundle with PHPP 8
designPH DEMO:- Free DEMO version- Limited features or component availability- No data export to PHPP - Available as download from www.designph.org
designPH new versions
-
Passive House Institute, Jan Steiger, 1 June 2015
Updates / FAQs / Support Forum
www.designph.org
-
Passive House Institute, Jan Steiger, 1 June 2015
Passive House design made easy!
PHPP & designPH
-
Passive House Institute, Jan Steiger, 1 June 2015
www.passivehouse.com
pbr Planungsbro Rohling | Erich-Kstner-Schule Stadt Leipzig
Congress Center Leipzig
Thursday, 16th of April, 9.00-13.00
- Presentation of new features in PHPP9- Work with design variants or retrofit steps- Presentation of the new Passive House classes- Entry of buildings with cooling requirement
Total of 80 participants. For more PHPP or designPH workshops check
-
Passive House Institute, Jan Steiger, 1 June 2015
FOR YOURATTENTION!
THANK YOU
www.passivehouse.com
www.passipedia.org
www.designph.org
www.passivehouseconference.org
Successful since 1991
The Passive House Concept
High comfort Highly efficient Cost effective Sustainable Approved User friendly NZEB-ready
-
Passive House Institute, Jan Steiger, 1 June 2015
Urheberrechtshinweis:
Bitte beachten Sie folgenden Hinweis zum Urheberrecht: Die vorliegende Foliensammlung wurde zusammengestellt fr die Teilnehmer der untengenannten Veranstaltung. Diese Datei bzw. ein Papierausdruck ist nur zur Informationszweckenund zum persnlichen Gebrauch fr die Teilnehmer dieser Veranstaltung bestimmt. Die berlassung der Datei begrndet kein Recht zur Weitergabe an Dritte oder ein Recht zurVerffentlichung in jedweder Form. Die Inhalte bleiben geistiges Eigentum des Passivhaus Instituts. Insbesondere ist eine weitergehende Verwendung einzelner Inhalte (Folien) ohneausdrckliche Zustimmung seitens des Passivhaus Instituts nicht gestattet.
Please note the following copyright notice: The present collection of slides was assembled for the participants of the seminar denoted below. This file or any printed copy of this file is for information purposes only and intended only for the personal use of the participants of this event. The transferral of this file to a third party or the right to publish it in any form is excluded. The contents are the intellectual property of the Passive House Institute. In particular, further use of individual contents (slides) is not permitted without the express permission of the Passive House Institute.