04_sanitary drainage system
TRANSCRIPT
-
7/28/2019 04_sanitary Drainage System
1/3
1BUILDING UTILITIES 1: PLUMBING
SANITARY DRAINAGE SYSTEM
GENERAL RULES IN DESIGNING THE SANITARY SYSTEM
The pipes should take the shortest possible route to the house sewer or the terminating point ofthe sanitary system
Control components such as clean-outs, traps, and vents, should be located strategically so asto ensure efficient circulation
SUBSYSTEMS OF SANITARY DRAINAGE SYSTEM
1.Waste Collection System2. Ventilation System
ESSENTIAL PARTS
WASTE PIPE
Conveys only wastewater or liquid waste free of fecal matter.
VENT PIPE
used for ensuring the circulation of air in a plumbing system and for relieving the negative pressure
exerted on trap seals.
TRAP
a fitting or device designed and constructed to provide, when properly vented, a liquid seal which
prevents the backflow of foul air or methane gas without materially affecting the flow of sewage or
wastewater through it.
STACK
The vertical main of a system of soil, waste or vent pipings extending through one or more stories and
extended thru the roof.
BRANCH
Any part of the piping system other than a main, riser or stack.
HOUSE/ BUILDING DRAIN
Part of the lowest horizontal piping of a plumbing system which receives the discharges from the soil,
waste and other drainage pipes inside of a building and conveys it to the house sewer outside of the
building.HOUSE/ BUILDING SEWER
Extends from the house drain at a point 0.60 meters from the outside face of the foundation wall of a
building to the junction with the street sewer or to any point of discharge, and conveying the drainage
of one building site.
CHANGES IN DIRECTION IN SANITARY DRAINAGE LINES
Horizontal to horizontal change
use 45 wye branches, combination wye 1/8 bend branches, or other approved fittings ofequivalent sweep
Vertical to horizontal change
45 wye branches or other approved fittings of equivalent sweepHorizontal to vertical change of direction
use 45 or 60 wye branches, combination wye -1/8 bend branches, sanitary tee or sanitarytapped tee branches, or other approved fittings of equivalent sweeps.
No fitting having more than one inlet at the same level shall be used (i.e., sanitary cross) Double sanitary tees may be used when the barrel of the fitting is at least two pipe (2) sizes
larger than the largest inlet, (pipe sizes recognized for this purpose are 51, 64, 76, 89, 102, 114,
127, & 152 mm dia.)
-
7/28/2019 04_sanitary Drainage System
2/3
2BUILDING UTILITIES 1: PLUMBING
UNIT OF MEASUREMENT OF SIZES OF SANITARY DRAINAGE LINES
The size of waste pipes or soil pipes depend on the amount of waste it carries.
A lavatory discharges 0.47 liters/sec or 28.3 liters/min (7.5 gallons per min or 1 cu ft per min), which is
equivalent to the Fixture Unit (F.U.)
The F.U. rating of plumbing fixtures is based on the size of required trap.
Minimum slope of sanitary drainage lines
Minimum slope or pitch of horizontal drainage pipe 2% or 20mm/m ( per foot). Exception: Where it is impracticable due to depth of street sewer, adverse structural features
and irregular building plans, pipes 102 mm dia or larger may have a slope of not less than 1% or
10mm/m (1/8 per foot), approved by the Administrative Authority
-
7/28/2019 04_sanitary Drainage System
3/3
3BUILDING UTILITIES 1: PLUMBING
TRAPS REQUIRED
Each plumbing fixture, except those with integral traps, shall be separately trapped with anapproved-type water seal trap.
Only one trap shall be permitted on a trap arm (portion of a fixture drain between a trap andthe vent)
One trap, centrally located, may serve three single compartment sinks or laundry tubs orlavatories, adjacent to each other and in the same room, where their waste outlets are not
more than 0.75 m apart.
The trap shall be the same size as the trap arm to which it is connected. Each fixture trap shall have a trap seal of water of not less than 51 mm and not more than 102
mm (except where a deeper seal is found necessary by the Administrative Authority for special
conditions.