Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 1

10 INTRODUCTION AND BACKGROUND

This Site Investigation Report has been prepared by Phelps Engineering to present the findings of a subsurface investigation at Connor Homes located on Route 7 in Middlebury Vermont (the site) A Site Location Map is provided as Figure 1 and Site Plan is presented as Exhibit 1 The facility located at 1741 Route 7 South is owned and operated by Connor Homes LLC who purchased the facility from Standard Register Co in 2007 Standard Register Co developed the property in 1965 prior to which it was farmland

A Phase I Environmental Site Assessment (ESA) was completed for the Connor Homes facility by Heindel amp Noyes Inc of Burlington Vermont on behalf of a prospective buyer The Beverage Acquisition Group DBA Green Mountain Beverage The Phase I ESA report dated January 21 2011 identified ldquoRecognized Environmental Conditionsrdquo and ldquoAreas of Potential Environmental Concernrdquo including

bull One existing 15000-gallon fuel oil underground storage tank (UST) bull Three former USTs that were removed in 1987 and 1993 when the facility was owned

by Standard Register Co bull Floor drains present throughout the building and bull A storage area where hazardous waste containers are stored

As a result of the Phase I ESA report recommendations Heindel amp Noyes completed a limited subsurface investigation in January and February 2011 Asbestos and lead surveys of the building were also conducted A boring advanced in the vicinity of the current and former USTs showed no evidence of contamination

Ten borings were advanced through the concrete floor of the production area and office area Soil gas testing soil sampling and groundwater sampling were completed Also samples were collected of some existing residual materials in the floor drain The borings showed evidence of chlorinated solvent contamination in groundwater at concentrations exceeding the Vermont Groundwater Enforcement Standards (VGES) Metals were also detected in soil samples although not at concentrations that exceeded typical background levels in Addison County clay soils Toluene was detected in soil gas samples using a field gas chromatograph and at low concentrations in two groundwater samples Elevated metals and moderate levels of petroleum compounds were detected in samples of residual materials in the floor drain piping Heindel amp Noyes recommended notifying the Agency of Natural Resources (ANR) of the findings of chlorinated solvents exceeding the VGES

On February 22 2011 Phelps Engineering provided a Notice of Release to ANR on behalf of Connor Homes along with a completed Site Investigation Expressway Notification Form This report presents the results of the subsequent Expressway Site Investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 2

20 SITE INVESTIGATION SCOPE OF WORK

The following work was conducted during this investigation

bull Dig Safe was notified to mark out utilities outside the building bull A base map of the facility was developed by adapting from the Heindel amp Noyes Site

Plan an aerial photograph a 1965 site plan of the facility and Town base maps showing existing water and sewer utilities

bull The Verterre Group of Colchester Vermont was subcontracted to provide field services

on March 1 and March 15 2011 including - Clearance of proposed soil boring locations for the presence of utilities inside the

building using Ground Penetrating Radar

- Advancement of soil borings using Geoprobereg Direct Push technology

- Screening of recovered soil samples for the presence of volatile organic compounds (VOCs) using a photoionization detector (PID)

- Installation of temporary and permanent groundwater monitoring wells where directed and

- Subcontracted laboratory analysis of soil and groundwater samples bull The new well locations and top of casing elevations were surveyed bull Water levels were measured in the groundwater monitoring wells bull Indoor and background air samples were collected bull The hazardous waste storage area was visually inspected bull A sensitive receptor survey was conducted bull This report was prepared

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 3

30 SUBSURFACE EXPLORATION AND RESULTS

The subsurface exploration work was completed during two events on March 1 and March 15 2011 A total of eleven soil borings were installed to evaluate the magnitude and extent of VOC contamination in soil and groundwater A groundwater sample was collected from a temporary well installed in one soil boring and permanent groundwater monitoring wells were installed in nine of the soil borings

31 Soil Borings

Verterre advanced a total of eleven soil borings on-site in the locations shown on Exhibit 1 using Verterrersquos Geoprobereg Logs for these borings are presented in Appendix A The borings were advanced to a depth ranging from 94 to 16 feet below ground surface (bgs) until an apparent confining layer (glacial till) was encountered All borings were logged describing soil strata conditions and field screened for VOCs using conventional headspace techniques with a properly-calibrated PID with an 117eV lamp The boring results are summarized in the following table

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-1MW-1 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-3 and the west production area sink

Boring = 12 feet DTW = 8 feet PID = 72 (at 9-10 feet)

SB-2MW-2 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-4

Boring = 12 feet DTW = 8 feet PID = 1009 (at 7-8 feet)

SB-3 3-1-11 Inside building downgradient of floor drain piping

Boring = 11 feet DTW = 8 feet PID = 147 (at 8 feet)

SB-4 3-1-11 Inside building downgradient of floor drain piping and HampN boring C-4

Boring = 94 feet DTW = 7 feet PID = 37 (at 7 feet)

SB-5MW-3 3-1-11 Inside building near storm drain outlet piping downgradient of HampN boring C-3

Boring = 105 feet DTW = 7 feet PID = 36 (at 9-10 feet)

SB-6MW-4 3-1-11 Inside building near west production area sink and floor drain close to HampN boring C-3

Boring = 11 feet DTW = 7 feet PID = 85 (at 8-10 feet)

SB-7MW-5 3-1-11 Inside building near east production area sink and floor drain close to HampN boring C-8

Boring = 11 feet DTW = 7 feet PID = 31 (at 10 feet)

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 4

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-101MW-7 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1 and MW-2

Boring = 12 feet DTW = 8 feet PID = 04

SB-102MW-6 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1

Boring = 12 feet DTW = 75 feet PID = 349 (at 9-10 feet)

SB-103MW-8 3-15-11 Inside building near southeast end of west floor drain system

Boring = 12 feet DTW = 8 feet PID = 44 (at 10-11 feet)

SB-104MW-9 3-15-11 Inside building near southeast end of east floor drain system

Boring = 16 feet DTW = 8 feet PID = 27

Notes 1) Apparent depth to water in boring based on water table indicators such as moisture and free water at the time of drilling

32 Site Geology

The boring logs in Appendix A describe the specific soil strata encountered in each boring location The borings show a typical generalized soil profile as described below

Depth Below Grade

(feet) Soil Description

0 to frac12 Concrete slab floor (inside) or topsoil (outside)

frac12 to 4 Firm dry fill (inside) or firm dry clay (outside)

4 to 10frac12 or 11 Soft moist to wet clay with interbedded layers of silts or fine sands

10frac12 or 11 + Firm dry glacial till

Most of the soil borings fit the generalized profile described above without significant variations with two exceptions

bull The underlying till layer was slightly shallower in boring SB-4 where it was

encountered at 94 feet below grade and bull In SB-104 the glacial till layer was encountered at 14 feet below grade A peat

layer was also encountered at 10 to 11 feet below grade in SB-104 (near the southeast end of the building) which may have been the former ground surface before the land was developed

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 5

Drillersrsquo logs from the ANR mapping website were also reviewed Logs for the nearest wells mapped in the vicinity of the site are included in Appendix B The drillersrsquo logs show that limestone bedrock in the vicinity is typically at least 50 feet below grade

Based on the soil and groundwater conditions encountered and the drillersrsquo logs from the area it appears that the shallow groundwater aquifer beneath the site is confined by a glacial till layer

33 Soil Sampling and Analytical Results

PID screening of soil samples during the subsurface exploration work (during the Phelps Engineering and Heindel amp Noyes site investigations) did not show evidence of significant soil contamination above the shallow water table Elevated PID readings were encountered within the saturated soils in Phelps Engineeringrsquos borings but it appears that soil beneath the water table in the Heindel amp Noyes borings was not screened using a PID

Soil sampling performed by Heindel amp Noyes during their limited subsurface investigation showed some detections of volatile organic compounds by field gas chromatograph and laboratory analysis in borings C-4 and C-8

To supplement the previous Heindel amp Noyes soil testing in the vicinity of the west production area sink the soil with the highest PID reading in boring SB-3 (147 ppmv at 8 feet below grade) was submitted for laboratory analysis The laboratory analytical report is provided in Appendix C No volatile organic compounds were detected above the laboratory method detection limits

34 Site Hydrogeology

On March 9 and March 16 2011 groundwater levels were measured On March 9 depths to water in the monitoring wells ranged from 322 feet below top of casing (btoc) in MW-1 to 400 feet btoc in MW-3 On March 16 after significant snow melt had started to occur depths to water in the monitoring wells ranged from 180 feet btoc in MW-6 to 346 feet btoc in MW-3 Groundwater elevation data is presented in Tables 1 and 1A Groundwater elevation contours are presented on Exhibits 2 and 3 Based on the groundwater contouring hydraulic gradients during the two monitoring events were 0004 feet per foot (on March 9) and 0009 feet per foot (on March 16)

Groundwater generally appears to flow to the southsouthwest toward Route 7 There are some drainageways southsouthwest of the Quesnel farm buildings on the west side of Route 7 that may be the receiving area for drainage in the vicinity of the Connor Homes facility The groundwater contouring from March 16 appears to also show that when water levels are high groundwater flow paths may be influenced by the floor drain conduits beneath the concrete slab creating some components of flow that follow the floor drain and storm drain conduits

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 2: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 2

20 SITE INVESTIGATION SCOPE OF WORK

The following work was conducted during this investigation

bull Dig Safe was notified to mark out utilities outside the building bull A base map of the facility was developed by adapting from the Heindel amp Noyes Site

Plan an aerial photograph a 1965 site plan of the facility and Town base maps showing existing water and sewer utilities

bull The Verterre Group of Colchester Vermont was subcontracted to provide field services

on March 1 and March 15 2011 including - Clearance of proposed soil boring locations for the presence of utilities inside the

building using Ground Penetrating Radar

- Advancement of soil borings using Geoprobereg Direct Push technology

- Screening of recovered soil samples for the presence of volatile organic compounds (VOCs) using a photoionization detector (PID)

- Installation of temporary and permanent groundwater monitoring wells where directed and

- Subcontracted laboratory analysis of soil and groundwater samples bull The new well locations and top of casing elevations were surveyed bull Water levels were measured in the groundwater monitoring wells bull Indoor and background air samples were collected bull The hazardous waste storage area was visually inspected bull A sensitive receptor survey was conducted bull This report was prepared

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 3

30 SUBSURFACE EXPLORATION AND RESULTS

The subsurface exploration work was completed during two events on March 1 and March 15 2011 A total of eleven soil borings were installed to evaluate the magnitude and extent of VOC contamination in soil and groundwater A groundwater sample was collected from a temporary well installed in one soil boring and permanent groundwater monitoring wells were installed in nine of the soil borings

31 Soil Borings

Verterre advanced a total of eleven soil borings on-site in the locations shown on Exhibit 1 using Verterrersquos Geoprobereg Logs for these borings are presented in Appendix A The borings were advanced to a depth ranging from 94 to 16 feet below ground surface (bgs) until an apparent confining layer (glacial till) was encountered All borings were logged describing soil strata conditions and field screened for VOCs using conventional headspace techniques with a properly-calibrated PID with an 117eV lamp The boring results are summarized in the following table

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-1MW-1 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-3 and the west production area sink

Boring = 12 feet DTW = 8 feet PID = 72 (at 9-10 feet)

SB-2MW-2 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-4

Boring = 12 feet DTW = 8 feet PID = 1009 (at 7-8 feet)

SB-3 3-1-11 Inside building downgradient of floor drain piping

Boring = 11 feet DTW = 8 feet PID = 147 (at 8 feet)

SB-4 3-1-11 Inside building downgradient of floor drain piping and HampN boring C-4

Boring = 94 feet DTW = 7 feet PID = 37 (at 7 feet)

SB-5MW-3 3-1-11 Inside building near storm drain outlet piping downgradient of HampN boring C-3

Boring = 105 feet DTW = 7 feet PID = 36 (at 9-10 feet)

SB-6MW-4 3-1-11 Inside building near west production area sink and floor drain close to HampN boring C-3

Boring = 11 feet DTW = 7 feet PID = 85 (at 8-10 feet)

SB-7MW-5 3-1-11 Inside building near east production area sink and floor drain close to HampN boring C-8

Boring = 11 feet DTW = 7 feet PID = 31 (at 10 feet)

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 4

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-101MW-7 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1 and MW-2

Boring = 12 feet DTW = 8 feet PID = 04

SB-102MW-6 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1

Boring = 12 feet DTW = 75 feet PID = 349 (at 9-10 feet)

SB-103MW-8 3-15-11 Inside building near southeast end of west floor drain system

Boring = 12 feet DTW = 8 feet PID = 44 (at 10-11 feet)

SB-104MW-9 3-15-11 Inside building near southeast end of east floor drain system

Boring = 16 feet DTW = 8 feet PID = 27

Notes 1) Apparent depth to water in boring based on water table indicators such as moisture and free water at the time of drilling

32 Site Geology

The boring logs in Appendix A describe the specific soil strata encountered in each boring location The borings show a typical generalized soil profile as described below

Depth Below Grade

(feet) Soil Description

0 to frac12 Concrete slab floor (inside) or topsoil (outside)

frac12 to 4 Firm dry fill (inside) or firm dry clay (outside)

4 to 10frac12 or 11 Soft moist to wet clay with interbedded layers of silts or fine sands

10frac12 or 11 + Firm dry glacial till

Most of the soil borings fit the generalized profile described above without significant variations with two exceptions

bull The underlying till layer was slightly shallower in boring SB-4 where it was

encountered at 94 feet below grade and bull In SB-104 the glacial till layer was encountered at 14 feet below grade A peat

layer was also encountered at 10 to 11 feet below grade in SB-104 (near the southeast end of the building) which may have been the former ground surface before the land was developed

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 5

Drillersrsquo logs from the ANR mapping website were also reviewed Logs for the nearest wells mapped in the vicinity of the site are included in Appendix B The drillersrsquo logs show that limestone bedrock in the vicinity is typically at least 50 feet below grade

Based on the soil and groundwater conditions encountered and the drillersrsquo logs from the area it appears that the shallow groundwater aquifer beneath the site is confined by a glacial till layer

33 Soil Sampling and Analytical Results

PID screening of soil samples during the subsurface exploration work (during the Phelps Engineering and Heindel amp Noyes site investigations) did not show evidence of significant soil contamination above the shallow water table Elevated PID readings were encountered within the saturated soils in Phelps Engineeringrsquos borings but it appears that soil beneath the water table in the Heindel amp Noyes borings was not screened using a PID

Soil sampling performed by Heindel amp Noyes during their limited subsurface investigation showed some detections of volatile organic compounds by field gas chromatograph and laboratory analysis in borings C-4 and C-8

To supplement the previous Heindel amp Noyes soil testing in the vicinity of the west production area sink the soil with the highest PID reading in boring SB-3 (147 ppmv at 8 feet below grade) was submitted for laboratory analysis The laboratory analytical report is provided in Appendix C No volatile organic compounds were detected above the laboratory method detection limits

34 Site Hydrogeology

On March 9 and March 16 2011 groundwater levels were measured On March 9 depths to water in the monitoring wells ranged from 322 feet below top of casing (btoc) in MW-1 to 400 feet btoc in MW-3 On March 16 after significant snow melt had started to occur depths to water in the monitoring wells ranged from 180 feet btoc in MW-6 to 346 feet btoc in MW-3 Groundwater elevation data is presented in Tables 1 and 1A Groundwater elevation contours are presented on Exhibits 2 and 3 Based on the groundwater contouring hydraulic gradients during the two monitoring events were 0004 feet per foot (on March 9) and 0009 feet per foot (on March 16)

Groundwater generally appears to flow to the southsouthwest toward Route 7 There are some drainageways southsouthwest of the Quesnel farm buildings on the west side of Route 7 that may be the receiving area for drainage in the vicinity of the Connor Homes facility The groundwater contouring from March 16 appears to also show that when water levels are high groundwater flow paths may be influenced by the floor drain conduits beneath the concrete slab creating some components of flow that follow the floor drain and storm drain conduits

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 3: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 3

30 SUBSURFACE EXPLORATION AND RESULTS

The subsurface exploration work was completed during two events on March 1 and March 15 2011 A total of eleven soil borings were installed to evaluate the magnitude and extent of VOC contamination in soil and groundwater A groundwater sample was collected from a temporary well installed in one soil boring and permanent groundwater monitoring wells were installed in nine of the soil borings

31 Soil Borings

Verterre advanced a total of eleven soil borings on-site in the locations shown on Exhibit 1 using Verterrersquos Geoprobereg Logs for these borings are presented in Appendix A The borings were advanced to a depth ranging from 94 to 16 feet below ground surface (bgs) until an apparent confining layer (glacial till) was encountered All borings were logged describing soil strata conditions and field screened for VOCs using conventional headspace techniques with a properly-calibrated PID with an 117eV lamp The boring results are summarized in the following table

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-1MW-1 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-3 and the west production area sink

Boring = 12 feet DTW = 8 feet PID = 72 (at 9-10 feet)

SB-2MW-2 3-1-11 Southwest of Connor Homes building (outside) downgradient of HampN boring C-4

Boring = 12 feet DTW = 8 feet PID = 1009 (at 7-8 feet)

SB-3 3-1-11 Inside building downgradient of floor drain piping

Boring = 11 feet DTW = 8 feet PID = 147 (at 8 feet)

SB-4 3-1-11 Inside building downgradient of floor drain piping and HampN boring C-4

Boring = 94 feet DTW = 7 feet PID = 37 (at 7 feet)

SB-5MW-3 3-1-11 Inside building near storm drain outlet piping downgradient of HampN boring C-3

Boring = 105 feet DTW = 7 feet PID = 36 (at 9-10 feet)

SB-6MW-4 3-1-11 Inside building near west production area sink and floor drain close to HampN boring C-3

Boring = 11 feet DTW = 7 feet PID = 85 (at 8-10 feet)

SB-7MW-5 3-1-11 Inside building near east production area sink and floor drain close to HampN boring C-8

Boring = 11 feet DTW = 7 feet PID = 31 (at 10 feet)

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 4

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-101MW-7 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1 and MW-2

Boring = 12 feet DTW = 8 feet PID = 04

SB-102MW-6 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1

Boring = 12 feet DTW = 75 feet PID = 349 (at 9-10 feet)

SB-103MW-8 3-15-11 Inside building near southeast end of west floor drain system

Boring = 12 feet DTW = 8 feet PID = 44 (at 10-11 feet)

SB-104MW-9 3-15-11 Inside building near southeast end of east floor drain system

Boring = 16 feet DTW = 8 feet PID = 27

Notes 1) Apparent depth to water in boring based on water table indicators such as moisture and free water at the time of drilling

32 Site Geology

The boring logs in Appendix A describe the specific soil strata encountered in each boring location The borings show a typical generalized soil profile as described below

Depth Below Grade

(feet) Soil Description

0 to frac12 Concrete slab floor (inside) or topsoil (outside)

frac12 to 4 Firm dry fill (inside) or firm dry clay (outside)

4 to 10frac12 or 11 Soft moist to wet clay with interbedded layers of silts or fine sands

10frac12 or 11 + Firm dry glacial till

Most of the soil borings fit the generalized profile described above without significant variations with two exceptions

bull The underlying till layer was slightly shallower in boring SB-4 where it was

encountered at 94 feet below grade and bull In SB-104 the glacial till layer was encountered at 14 feet below grade A peat

layer was also encountered at 10 to 11 feet below grade in SB-104 (near the southeast end of the building) which may have been the former ground surface before the land was developed

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 5

Drillersrsquo logs from the ANR mapping website were also reviewed Logs for the nearest wells mapped in the vicinity of the site are included in Appendix B The drillersrsquo logs show that limestone bedrock in the vicinity is typically at least 50 feet below grade

Based on the soil and groundwater conditions encountered and the drillersrsquo logs from the area it appears that the shallow groundwater aquifer beneath the site is confined by a glacial till layer

33 Soil Sampling and Analytical Results

PID screening of soil samples during the subsurface exploration work (during the Phelps Engineering and Heindel amp Noyes site investigations) did not show evidence of significant soil contamination above the shallow water table Elevated PID readings were encountered within the saturated soils in Phelps Engineeringrsquos borings but it appears that soil beneath the water table in the Heindel amp Noyes borings was not screened using a PID

Soil sampling performed by Heindel amp Noyes during their limited subsurface investigation showed some detections of volatile organic compounds by field gas chromatograph and laboratory analysis in borings C-4 and C-8

To supplement the previous Heindel amp Noyes soil testing in the vicinity of the west production area sink the soil with the highest PID reading in boring SB-3 (147 ppmv at 8 feet below grade) was submitted for laboratory analysis The laboratory analytical report is provided in Appendix C No volatile organic compounds were detected above the laboratory method detection limits

34 Site Hydrogeology

On March 9 and March 16 2011 groundwater levels were measured On March 9 depths to water in the monitoring wells ranged from 322 feet below top of casing (btoc) in MW-1 to 400 feet btoc in MW-3 On March 16 after significant snow melt had started to occur depths to water in the monitoring wells ranged from 180 feet btoc in MW-6 to 346 feet btoc in MW-3 Groundwater elevation data is presented in Tables 1 and 1A Groundwater elevation contours are presented on Exhibits 2 and 3 Based on the groundwater contouring hydraulic gradients during the two monitoring events were 0004 feet per foot (on March 9) and 0009 feet per foot (on March 16)

Groundwater generally appears to flow to the southsouthwest toward Route 7 There are some drainageways southsouthwest of the Quesnel farm buildings on the west side of Route 7 that may be the receiving area for drainage in the vicinity of the Connor Homes facility The groundwater contouring from March 16 appears to also show that when water levels are high groundwater flow paths may be influenced by the floor drain conduits beneath the concrete slab creating some components of flow that follow the floor drain and storm drain conduits

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 4: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 4

Boring ID

Date Installed

Boring Location

Depth of Boring Depth to Water1

(below grade) Max PID (ppmv)

SB-101MW-7 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1 and MW-2

Boring = 12 feet DTW = 8 feet PID = 04

SB-102MW-6 3-15-11 Southwest of Connor Homes building (outside) near Route 7 right-of-way downgradient of MW-1

Boring = 12 feet DTW = 75 feet PID = 349 (at 9-10 feet)

SB-103MW-8 3-15-11 Inside building near southeast end of west floor drain system

Boring = 12 feet DTW = 8 feet PID = 44 (at 10-11 feet)

SB-104MW-9 3-15-11 Inside building near southeast end of east floor drain system

Boring = 16 feet DTW = 8 feet PID = 27

Notes 1) Apparent depth to water in boring based on water table indicators such as moisture and free water at the time of drilling

32 Site Geology

The boring logs in Appendix A describe the specific soil strata encountered in each boring location The borings show a typical generalized soil profile as described below

Depth Below Grade

(feet) Soil Description

0 to frac12 Concrete slab floor (inside) or topsoil (outside)

frac12 to 4 Firm dry fill (inside) or firm dry clay (outside)

4 to 10frac12 or 11 Soft moist to wet clay with interbedded layers of silts or fine sands

10frac12 or 11 + Firm dry glacial till

Most of the soil borings fit the generalized profile described above without significant variations with two exceptions

bull The underlying till layer was slightly shallower in boring SB-4 where it was

encountered at 94 feet below grade and bull In SB-104 the glacial till layer was encountered at 14 feet below grade A peat

layer was also encountered at 10 to 11 feet below grade in SB-104 (near the southeast end of the building) which may have been the former ground surface before the land was developed

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 5

Drillersrsquo logs from the ANR mapping website were also reviewed Logs for the nearest wells mapped in the vicinity of the site are included in Appendix B The drillersrsquo logs show that limestone bedrock in the vicinity is typically at least 50 feet below grade

Based on the soil and groundwater conditions encountered and the drillersrsquo logs from the area it appears that the shallow groundwater aquifer beneath the site is confined by a glacial till layer

33 Soil Sampling and Analytical Results

PID screening of soil samples during the subsurface exploration work (during the Phelps Engineering and Heindel amp Noyes site investigations) did not show evidence of significant soil contamination above the shallow water table Elevated PID readings were encountered within the saturated soils in Phelps Engineeringrsquos borings but it appears that soil beneath the water table in the Heindel amp Noyes borings was not screened using a PID

Soil sampling performed by Heindel amp Noyes during their limited subsurface investigation showed some detections of volatile organic compounds by field gas chromatograph and laboratory analysis in borings C-4 and C-8

To supplement the previous Heindel amp Noyes soil testing in the vicinity of the west production area sink the soil with the highest PID reading in boring SB-3 (147 ppmv at 8 feet below grade) was submitted for laboratory analysis The laboratory analytical report is provided in Appendix C No volatile organic compounds were detected above the laboratory method detection limits

34 Site Hydrogeology

On March 9 and March 16 2011 groundwater levels were measured On March 9 depths to water in the monitoring wells ranged from 322 feet below top of casing (btoc) in MW-1 to 400 feet btoc in MW-3 On March 16 after significant snow melt had started to occur depths to water in the monitoring wells ranged from 180 feet btoc in MW-6 to 346 feet btoc in MW-3 Groundwater elevation data is presented in Tables 1 and 1A Groundwater elevation contours are presented on Exhibits 2 and 3 Based on the groundwater contouring hydraulic gradients during the two monitoring events were 0004 feet per foot (on March 9) and 0009 feet per foot (on March 16)

Groundwater generally appears to flow to the southsouthwest toward Route 7 There are some drainageways southsouthwest of the Quesnel farm buildings on the west side of Route 7 that may be the receiving area for drainage in the vicinity of the Connor Homes facility The groundwater contouring from March 16 appears to also show that when water levels are high groundwater flow paths may be influenced by the floor drain conduits beneath the concrete slab creating some components of flow that follow the floor drain and storm drain conduits

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 5: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 5

Drillersrsquo logs from the ANR mapping website were also reviewed Logs for the nearest wells mapped in the vicinity of the site are included in Appendix B The drillersrsquo logs show that limestone bedrock in the vicinity is typically at least 50 feet below grade

Based on the soil and groundwater conditions encountered and the drillersrsquo logs from the area it appears that the shallow groundwater aquifer beneath the site is confined by a glacial till layer

33 Soil Sampling and Analytical Results

PID screening of soil samples during the subsurface exploration work (during the Phelps Engineering and Heindel amp Noyes site investigations) did not show evidence of significant soil contamination above the shallow water table Elevated PID readings were encountered within the saturated soils in Phelps Engineeringrsquos borings but it appears that soil beneath the water table in the Heindel amp Noyes borings was not screened using a PID

Soil sampling performed by Heindel amp Noyes during their limited subsurface investigation showed some detections of volatile organic compounds by field gas chromatograph and laboratory analysis in borings C-4 and C-8

To supplement the previous Heindel amp Noyes soil testing in the vicinity of the west production area sink the soil with the highest PID reading in boring SB-3 (147 ppmv at 8 feet below grade) was submitted for laboratory analysis The laboratory analytical report is provided in Appendix C No volatile organic compounds were detected above the laboratory method detection limits

34 Site Hydrogeology

On March 9 and March 16 2011 groundwater levels were measured On March 9 depths to water in the monitoring wells ranged from 322 feet below top of casing (btoc) in MW-1 to 400 feet btoc in MW-3 On March 16 after significant snow melt had started to occur depths to water in the monitoring wells ranged from 180 feet btoc in MW-6 to 346 feet btoc in MW-3 Groundwater elevation data is presented in Tables 1 and 1A Groundwater elevation contours are presented on Exhibits 2 and 3 Based on the groundwater contouring hydraulic gradients during the two monitoring events were 0004 feet per foot (on March 9) and 0009 feet per foot (on March 16)

Groundwater generally appears to flow to the southsouthwest toward Route 7 There are some drainageways southsouthwest of the Quesnel farm buildings on the west side of Route 7 that may be the receiving area for drainage in the vicinity of the Connor Homes facility The groundwater contouring from March 16 appears to also show that when water levels are high groundwater flow paths may be influenced by the floor drain conduits beneath the concrete slab creating some components of flow that follow the floor drain and storm drain conduits

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 6: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 6

35 Groundwater Sampling and Analytical Results

Screened intervals selected for the groundwater monitoring wells installed during the investigation are generally deep (to the top of the glacial till confining layer) because of the known presence of chlorinated solvents (which are more dense than water) The wells were constructed with three to seven feet of screen generally to correspond with the most saturated soils encountered and the highest PID readings measured in the soil borings

Prior to collecting groundwater samples a minimum of three well volumes of water were purged from each monitoring well using a dedicated bailer (unless the well went dry prior to removing three volumes) The wells were then allowed to recharge prior to sampling With the exception of the samples collected from MW-1 and MW-2 on March 15 all of the groundwater samples were collected on the same day that the monitoring well was constructed due to the urgency of the clientrsquos schedule to facilitate a pending real estate closing

The March 1 and March 15 2011 groundwater sampling results are summarized on Table 2 The laboratory analytical reports are provided in Appendix C Wells MW-1 through MW-5 and a temporary well placed in Boring SB-4 were sampled on March 1 PID readings from Boring SB-1 (which were significantly elevated) did not appear to correlate with the groundwater analytical results from the March 1 sampling of MW-1 and the groundwater analytical results from sampling MW-2 on March 1 showed the presence of petroleum compounds that were not detected in other groundwater samples As such MW-1 and MW-2 were re-sampled on March 15 along with four newly installed wells (MW-6 through MW-9)

Petroleum-related compounds including isopropylbenzene trimethylbenzenes (124 and 135) sec-butylbenzene 4-isopropylbenzene and naphthalene were reported above the method detection limits in one well (MW-2) Only one petroleum compound naphthalene was reported (at 46 microgl on March 15) above the applicable VGES (20 microgl)

Chlorinated VOCs including dichlorodifluoromethane vinyl chloride trichlorofluoromethane 11-dichloroethene trans-12-dichloroethene cis-12-dichloroethene and trichloroethylene (TCE) were detected in samples from one or more of the monitoring wells as described below

bull Vinyl chloride (at 4 microgl in MW-5) was reported above the applicable VGES (2

microgl) in only one well bull Trans-12-dichloroethene was reported above the applicable VGES (100 microgl) in

two wells (MW-3 (130 microgl) and MW-4 (220 microgl))

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 7: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 7

bull Cis-12-dichloroethene was reported above the applicable VGES (70 microgl) in four wells (MW-3 (140 microgl) MW-4 (150 microgl) MW-8 (160 microgl) and MW-9 (120 microgl))

bull TCE was reported above the applicable VGES (5 microgl) in six wells (MW-1 (40 to 51

microgl) MW-3 (400 microgl) MW-4 (1300 microgl) MW-5 (260 microgl) MW-8 (18 microgl) and MW-9 (77 microgl))

Based on the laboratory analysis results TCE distribution beneath the site was mapped to describe the horizontal extent of groundwater contamination The TCE distribution is shown on Exhibit 4 The chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES The highest concentrations of chlorinated solvents appear to be centered in the vicinity of the west production area sink where a floor drain is also present Reportedly the east and west production sinks may have been used by Standard Register to wash off solvents that were used in their production processes The floor drain piping beneath the building is likely corroded and the floor drain trap near the west production area sink does not appear to hold water

The source of petroleum contamination detected in well MW-2 is not apparent

36 QAQC Results

The laboratory data was evaluated for the following parameters prior to acceptance in this report

bull Correct sample IDs bull Analysis date within method specified holding times bull Acceptable detection limit multipliers bull Acceptable matrix spike (MS) and matrix spike duplicate (MSD) recoveries where

applicable bull Acceptable relative percent difference (RPD) between the MS and MSD where

applicable and bull Acceptable surrogate recoveries

Surrogate recoveries reported by the laboratory were all within acceptable limits

Field blanks were submitted with the groundwater samples collected on March 1 and March 15 No target compounds were detected in either field blank above the MDLs

All of the samples submitted were preserved with hydrochloric acid however the laboratory reported pH levels greater than two in several samples indicating insufficient sample preservation This may have occurred due to overfilling of the sample vials which sometimes dilutes the sample acidity beyond the desired pH Based on the

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 8: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 8

relatively short turnaround that was provided for the laboratory analysis the pH variance is not likely to have had a measurable effect on the analytical results

Based on an evaluation of the above-described parameters the data was determined to be acceptable

40 RECEPTOR EVALUATION AND RECONNAISSANCE

At the request of the prospective buyer the location designated as a hazardous waste storage area on the site plans in Heindel amp Noyesrsquo report was visually inspected On March 16 the containers stored in this location were all intact and in good condition There was no evidence of staining suggesting that wastes or other materials stored in this area had been spilled or dumped The concrete floor in this location was in good condition but the area is not bermed to contain potential spills The adjacent area outside is paved No evidence of staining or spills was observed on the asphalt

Phelps Engineering also conducted a sensitive receptor review of the property The following summarizes the evaluation results

bull Drinking Water ndash The property and other properties along Route 7 are served by

municipal water Phelps Engineering verified with Middleburyrsquos Director of Public Works that the downgradient Quesnel farm on the west side of Route 7 is served by municipal water The homeowner did not return phone calls made by Phelps Engineering A map of drinking water wells in the area from the ANR website is included in Appendix B The well that is shown on the Connor Homes property is not located correctly in the ANR mapping it is a domestic well that was drilled for David and Sue Roberts on Route 7 They appear to have owned a former nursery at 263 Foote Street in Middlebury so this well is likely located north (upgradient) of the Connor Homes facility Based on the presence of a glacial till layer (likely of substantial thickness) beneath the Connor Homes site and the existing municipal water service to the adjacent properties drinking water in the area does not appear threatened by the contamination at the site

bull Surface Water ndash The nearest surface water receptors are some drainageways

southsouthwest of the Quesnel farm buildings on the west side of Route 7 that are likely the receiving area for drainage in the vicinity of the Connor Homes facility (shown on the map in Appendix B) These drainageways appear to ultimately discharge to Otter Creek Based on the contaminant distribution mapped during this investigation the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore surface water receptors do not appear to be threatened

bull Indoor Air - The building was constructed on a reinforced concrete slab which

generally appears to be in good condition and contaminant concentrations in shallow unsaturated soils do not appear to be significant based on the soil analysis results and

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 9: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 9

PID screening of soils however some of the existing penetrations through the floor can allow air exchange between the indoor air and the subsurface Specifically the existing floor drains whose traps do not hold water can allow air exchanges to occur and there are several indirect drains that are open to the indoor air (where condensate discharge piping discharges to the floor drain system)

Two indoor air samples and one background (outdoor) air sample were collected on

March 16 to evaluate indoor air quality The sample collection procedures and laboratory analytical results are summarized on Table 3 The laboratory analytical report is included in Appendix D To avoid potential confusion as a result of ongoing production activities (sawing and assembly of homes forklift activities etc) and Route 7 traffic the air samples were analyzed by Method TO-15 and only chlorinated solvents were reported

The two indoor air samples were located in the vicinity of what appear to be two

potential ldquosource areasrdquo for the solvent contamination in the subsurface (the two sinks in the production area) Each of the samples was located in the general vicinity of an existing floor drain and an indirect drain where air exchange between the subslab soil and the indoor air is possible

No chlorinated solvents were detected in the background sample collected outside the

building Chlorinated VOCs detected in the indoor air included cis-12-dichloroethene and TCE neither of which exceeds the EPA Region IX Regional Screening Level for Industrial Air

Based on the indoor air sampling results indoor air appears to be affected by the

chlorinated VOC contamination but not at concentrations exceeding the applicable standard

bull Public Utilities ndash The floor drains in the facility are connected to the Middlebury sewer

system Roof drains from Connor Homes are separate from the floor drain system Based on the contaminant distribution the chlorinated solvent and limited petroleum contamination do not appear to be migrating off-site at concentrations exceeding the VGES therefore public utilities along Route 7 which include public water sewer and communications do not appear to be threatened

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 10: 0311 site investigation

Connor Homes Supplemental Site Investigation SMS No 2011-4164

Phelps Engineering Project No 20110501 10

50 SUMMARY AND CONCLUSIONS

Based on the information and analytical data obtained during this investigation Phelps Engineering concludes the following

bull Subsurface investigations conducted by Heindel amp Noyes and Phelps Engineering have

identified the presence of volatile organic compounds in groundwater beneath the site The contamination includes primarily chlorinated VOCs including TCE and some associated breakdown compounds of TCE Petroleum compounds were also detected at fairly low levels in one on-site well

bull The vertical extent of contamination appears to be limited to typically no more than 12

feet below grade by a dense glacial till confining layer bull The contamination does not appear to be migrating off-site at concentrations exceeding

the VGES Groundwater generally flows to the southsouthwest beneath the site toward Route 7 although the existing utility conduits under the concrete slab may also influence groundwater flow paths beneath the building under some conditions

bull Indoor air appears to be the only threatened potential sensitive receptor Chlorinated

VOCs were detected at concentrations below the applicable reference standards for industrial air in two indoor air samples

60 RECOMMENDATIONS

Based on the results of this supplemental investigation a routine groundwater monitoring program should be implemented to monitor seasonal groundwater trends and verify that the groundwater contaminant plume is stable

Possible corrective measures to consider for additional indoor air quality protection could include sealing or re-plumbing the existing floor drains and indirect drains to minimize air exchange with the area beneath the slab

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 11: 0311 site investigation

Figures

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 12: 0311 site investigation

Exhibits

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 13: 0311 site investigation

Tables

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 14: 0311 site investigation

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-18

9921 ND 322 1110 788 9599

MW-2 9910 ND 381 1081 700 9529

MW-3 9972 ND 400 1020 620 9572

MW-4 9958 ND 370 1040 670 9588

MW-5 9984 ND 370 880 510 9614

The average depth to water is 369 feet

March 9 2011

TABLE 1

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 20118 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-030911

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 15: 0311 site investigation

Well Top of Riser Depth to Depth to Depth of Thickness of Water Table

Identification Elevation Product Water Well Water in Well Elev

MW-1 9921 ND 254 1110 856 9667

MW-2 9910 ND 265 1081 816 9645

MW-3 9972 ND 346 1020 674 9626

MW-4 9958 ND 358 1040 682 9600

MW-5 9984 ND 277 880 603 9707

MW-6 9818 ND 180 1083 903 9638

MW-7 9849 ND 226 887 661 9623

MW-8 9973 ND 291 928 637 9682

MW-9 9986 ND 251 1070 819 9735

The average depth to water is 272 feet

TABLE 1A

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Water Table Elevations

March 16 2011

The average depth to water is 272 feet

NOTES

1 Elevation data is referenced to an assumed TBM of 100 feet Units are in feet2 ND - not detected nm - not measured3 NA - not applicable4 Measurements recorded are referenced to a marking on top of PVC riser for each well5 Depth to fluid measurements were obtained using a Solinst Interface Probe6 TOC - Top of casing7 Wells surveyed on March 9 2011

8 Based on PID readings well MW-1 was screened deep (9-12) so groundwater elevations in this well

will not be used for gw contouring because of expected skew from pieziometric rise

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWElev-031611

Compound VGES MW-1 MW-2 MW-3 MW-4 MW-5 SB-4 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 8 lt10 lt2 lt2 lt2

vinyl chloride 20 lt2 lt2 lt2 lt10 4 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt10 6 lt2 lt2

11-dichloroethene 70 lt1 lt1 2 lt5 lt1 lt1 lt1

trans-12-dichloroethene 1000 3 lt2 130 220 5 lt2 lt2

cis-12-dichloroethene 700 15 lt2 140 150 39 lt2 lt2

trichloroethene 50 40 lt2 400 1300 260 lt2 lt2

isopropylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 8 lt4 lt20 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt10 lt2 lt2 lt2

4-isopropyltoluene ne lt2 5 lt2 lt10 lt2 lt2 lt2

naphthalene 200 lt5 8 lt5 lt25 lt5 lt5 lt5

Compound VGES MW-1 MW-2 MW-6 MW-7 MW-8 MW-9 Field Blank

dichlorodifluoromethane 10000 lt2 lt2 lt2 lt2 lt2 11 lt2

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

TABLE 2

Summary of Water Quality

Sampling Date 312011

Connor Homes Former Standard Register

Middlebury Vermont

Sampling Date 3152011

vinyl chloride 20 lt2 lt2 lt2 lt2 lt2 lt2 lt2

trichlorofluoromethane 21000 lt2 lt2 lt2 lt2 lt2 lt2 lt2

11-dichloroethene 70 lt1 lt1 lt1 lt1 1 lt1 lt1

trans-12-dichloroethene 1000 4 lt2 lt2 lt2 23 29 lt2

cis-12-dichloroethene 700 20 lt2 lt2 lt2 160 120 lt2

trichloroethene 50 51 lt2 lt2 lt2 18 77 lt2

isopropylbenzene ne lt2 6 lt2 lt2 lt2 lt2 lt2

135-trimethylbenzene and

124-trimethylbenzene 3500 lt4 15 lt4 lt4 lt4 lt4 lt4

sec-butylbenzene ne lt2 2 lt2 lt2 lt2 lt2 lt2

4-isopropyltoluene ne lt2 4 lt2 lt2 lt2 lt2 lt2

naphthalene 200 lt5 48 lt5 lt5 lt5 lt5 lt5

NOTES

1 VGES -Vermont Groundwater Enforcement Standard2 ne -VGES not established3 Bold and Italic numbers that are highlighted indicate concentrations that exceed VGES4 All samples were analyzed for VOCs via US EPA Method 8260 6 ns - Not sampled nd - not detected7 All units are in micrograms per liter (ugl) or parts per billion

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsGWQ-0311

Compound

EPA Region IX

Regional Screening

Level for Industrial

Air (ugm3)

West Sink Area

(ugm3)

East Sink Area

(ugm3)

Outside Break Room

(Ambient Outdoor Air)

(ugm3)

cis-12-dichloroethene Not Established 056 049 lt016

12-dichloroethene (total) 260 056 049 lt016

trichloroethene 61 24 20 lt021

NOTES

TABLE 3

Connor Homes Former Standard Register

Middlebury Vermont

Summary of Air Sample Analysis Results (Detections Only)

Sampling Date 3162011

NOTES

1 Two air samples were collected inside (for indoor air) and one outside (for background ambient air) 2 Air samples were all collected using Summa canisters (supplied by the laboratory) equipped with laboratory-calibrated regulators to fill the canisters over approximately an 8-hour period 3 Starting interim and ending vacuum levels for each canister were observed and noted All canisters started with -2775 Hgto -300 Hg pressure and ended with -45 Hg to -100 Hg pressure4 Sample times were 8 hours and 1 minute for all three samples5 Canisters were set on bases so that the air inlets were approximately 35 feet above gradefloor 6 Indoor canisters were placed in two areas where chlorinated solvents have been detected in groundwater (beneath the slab)in the vicinity of drains that penetrate the concrete floor near sinks where solvents were reportedly handled during Standard Registers occupancy of the building7 The outdoor canister was placed outside the break room on the west end of the building 8 Analysis included chlorinated solvents only9 RSL shown for 12 dichloroethene (total) is the RSL for trans-12-dichloroethene

PProject Files2011201105 Connor HomesEnvironmentalReport TablesxlsAir-031611

Appendices

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-1doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-1MW-1

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 701 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 lt01 48rdquo recovery 0-48rdquo Brown clay with banded slit layers dry

5____ 50 Moist silt at tip

6____

7____

8____ 8-12 48rdquo recovery 0-7rdquo Fine silt wet

9____ 72 7-11rdquo Clay with banded silt layer wet

10___ 49 tip 11-48rdquo Wet silty till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-2doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-2MW-2

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-35rdquo Brown clay with banded gray silt layers

dry

1____

2____

3____

4____ 4-8 621 48rdquo recovery 0-33rdquo Dense brown clay with gray bands

5____ 1009 33-48rdquo Gray silty clay moist last 2 inches with

thin silt bands moist

6____ 499 tip Strong odor

7____

8____ 8-12 389 35rdquo recovery 0-30rdquo Loose wet silty clay

9____ 78 30-35rdquo Silty till wet Dry till at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-5MW-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 105 ft BORING DEPTH 105 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 55-105 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-55 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 33rdquo recovery 0-14rdquo Medium sand and gravel

1____ 17 14-33rdquo Dense brown clay dry

2____

3____

4____ 4-7 19

29 tip

48rdquo recovery 0-48rdquo Dense brown clay with fine sandy layers

Becoming soft near bottom

5____

6____

7____

8____ 7-105 28 48rdquo recovery 0-29rdquo Mixed layers of soft clay intermixed with

fine sand saturated

9____ 36

35 (tip)

29-48rdquo Soft silty clay with gravel

Dry till at tip

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-6MW-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 18 28rdquo recovery 0-28rdquo Clay mixed with backfill

1____

2____

3____

4____ 4-8 50 22rdquo recovery 0-22rdquo Coarse sandy backfill

5____

6____

7____

8____ 8-11 85 48rdquo recovery 0-25rdquo Sandy backfill

9____ 40 25-37rdquo Soft sandy silt wet

10___ 49 37-48rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-5doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-7MW-5

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH 11 ft BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 6-11 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-6 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 24 32rdquo recovery 0-14rdquo Coarse sand and medium gravel

1____ 14-32rdquo Dense brown clay

2____

3____

4____ 4-8 28 48rdquo recovery 0-48rdquo Dense brown clay

5____

6____

7____

8____ 8-11 25 40rdquo recovery 0-20rdquo Dense brown clay

9____ 31 20-35rdquo Soft silty clay moist to wet

10___ 29 tip 35-40rdquo Dry dense till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-6doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-102MW-6

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 75 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 38rdquo recovery 0-6rdquo Topsoil

1____ 03 6-38rdquo Dry brown clay with banded silt layers

2____ Tip 05

3____

4____ 4-8 16 48rdquo recovery 0-36rdquo Dry brown clay with banded silt layers

5____ 30 36-48rdquo Moist brown clay with large bands of silt

6____

7____

8____ 8-12 149 20rdquo recovery 0-15rdquo Saturated brown clay with lots of silt

9____ 349 15-20rdquo Moist till with clay

10___ Tip Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-7doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-101MW-7

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 39rdquo recovery 0-6rdquo Topsoil

1____ 04 6-39rdquo Brown clay with banded silt layers dry

2____

3____

4____ 4-8 02 48rdquo recovery 0-33rdquo Dry brown clay with banded silt layers

5____ 02 33-48rdquo Moist brown clay with large bands of silt

larger silt layers Wet at tip

6____

7____

8____ 8-12 04 24rdquo recovery 0-7rdquo Medium soft clay

9____ 04 7-22rdquo Wet silt

10___ 04 22-24rdquo Dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-8doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-103MW-8

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 12 ft BORING DEPTH 12 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 7-12 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-7 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 17 16rdquo recovery 0-16rdquo Medium brown sand

1____

2____

3____

4____ 4-8 17 48rdquo recovery 0-4rdquo Medium brown sand

5____ 02 4-48rdquo Medium to dense brown clay with small bands

of silt dry

6____

7____

8____ 8-12 43 35rdquo recovery 0-23rdquo Medium soft brown clay with bands of sand

and gravel wet

9____ 44 23-35rdquo Till mixed with clay decreasing moisture

with depth dry at bottom

10___

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsMW-9doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-104MW-9

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 15 2011 WELL DEPTH 16 ft BORING DEPTH 16 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA 1-inch DEPTH 9-16 ft bgs

SCREEN TYPESIZE 0010rdquo-slot schedule 40 PVC

DRILLING METHOD Geoprobereg Tools RISER TYPE Schedule 40 PVC solid riser

SAMPLING METHOD Macrocore RISER DIA 1-inch DEPTH 0-9 ft bgs

REFERENCE POINT (RP) NA GUARD TYPE Aluminum Roadbox

ELEVATION OF RP NA RISER CAP locking expansion plug

REMARKS Boring was completed as a monitoring well with an aluminum Roadbox

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 35rdquo recovery 0-10rdquo Medium brown sand dry

1____ 13 10-35rdquo Medium density gray clay transitioning to

brown dry

2____

3____

4____ 4-8 22 48rdquo recovery 0-48rdquo Dense brown clay with silt layers dry

5____

6____

7____

8____ 8-12 20 36rdquo recovery 0-7rdquo Dense brown clay with silt layers dry

7-10rdquo Coarse sand and gravel

9____ 25

27 (tip)

10-26rdquo Soft moist banded gray and brown clay

26-36rdquo Soft black what appears to be organics

10___

11___

12___ 12-16 20 33rdquo recovery 0-25rdquo Saturated flowing clays with silt and sand

13___ 23 25-33rdquo Dry till

14___ 27 tip

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-3doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-3

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 11 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 8 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Soil samples were collected boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 26 48rdquo recovery 0-10rdquo Medium sand and gravel

10-48rdquo Dense graybrown clay with little silt

1____ 26 tip

2____

3____

4____ 4-8 57

147 tip

48rdquo recovery 0-48rdquo Dense dry brown clay intermixed with small

layers of fine silty sand

5____

6____

7____

8____ 8-11 25 48rdquo recovery 0-15rdquo Saturated fine silt with gravel till

9____ 15-33rdquo Moistsoft silt with clay and gravel

10___ 18 33-48rdquo Dry silty sand and gravel till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

Page 1 of 1

PProject Files2011201105 Connor HomesEnvironmentalBoring LogsSB-4doc

The Verterre Group

414 Roosevelt Highway Colchester Vermont 05446

(802) 654-8663 FAX (802) 654-8667

MONITORING WELLSOIL BORING LOG

Project Name Connor Homes WELL

BORING ID

SB-4

Location Middlebury Vermont

Verterre Project

SMS

11005

INSTALL DATE March 1 2011 WELL DEPTH NA BORING DEPTH 94 ft

VERTERRE REP Rod Lindsay II DEPTH TO WATER (during drilling) Approximately 7 ft

DRILLING CO Verterre

Colchester VT

SCREEN DIA NA DEPTH NA

SCREEN TYPESIZE NA

DRILLING METHOD Geoprobereg Tools RISER TYPE NA

SAMPLING METHOD Macrocore RISER DIA NA DEPTH NA

REFERENCE POINT (RP) NA GUARD TYPE NA

ELEVATION OF RP NA RISER CAP NA

REMARKS Set temporary well with 5rsquo screen boring was then backfilled with native

material and sand

DEPTH IN

FEET

WELL PROFILE

SAMPLE DEPTH

(FT)

PID (PPMV)

BLOWS6rdquo AND

RECOVERY

SOIL DESCRIPTION AND NOTES

LEGEND

0____ 0-4 29rdquo recovery 0-17rdquo Coarse sand and medium gravel dry

17-29rdquo Dense brown clay dry

1____

2____

3____

4____ 4-7 20 48rdquo recovery 0-23rdquo Dense brown clay dry

5____ 32

37 tip

23-48rdquo Dense brown clay with small layers of fine

silty sand Layers of sand are wet

6____

7____

8____ 7-94 29 48rdquo recovery 0-17rdquo Saturated silty sand with some gravel

9____ 35 17-43rdquo Moistsoft silty sand with little clay and

gravel

10___ 19 43-48rdquo Dense dry till

11___

12___

13___

14___

15___

16___

17___

18___

19___

20___

21___ 22___ 23___ 24___ 25___

GRANULAR SOILS COHESIVE SOILS PROPORTIONS USED NOTES

BLOWSFT DENSITY BLOWSFT DENSITY TRACE 0-10

0-4 VLOOSE lt2 VSOFT LITTLE 10-20

4-10 LOOSE 2-4 SOFT SOME 20-35

10-30 MDENSE 4-8 MSTIFF AND 35-50

30-50 DENSE 8-15 STIFF

gt50 VDENSE 15-30 VSTIFF

gt30 HARD

CEMENT

GROUT

NATIVE

SOIL

BENTONITE

SEAL

SAND

PACK

WELL

SCREEN

RISER

PIPE

HEAD

SPACE HS

WATER LEVEL

(APPROXIMATE)

CONNOR HOMES

Date 3302011

Maps are to be used for display or planning purposes only data is not survey quality and is therefore not to be used as a basis for legal decisions The data layers have been developed from the best available sources at the time of their creation These original sources vary in scale and accuracy which determines the relative map accuracy of the digital data layers For information regarding data layer accuracy or update schedules please check with the Agency of Natural Resources

LEGEND

PRIVATE WELLS

E911 ADDRESS

GPS LOCATION

SCREEN DIGITIZED

WELLDRILLERCLARION

NOT AVAILABLE

Page 1 of 1Connor Homes

3302011httpmapsanrstatevtuseDrillerPrintTemplatesestamphtm

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1650ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-12-dichloroethene 33113 2 SW5030B8260B1 1650ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289cis-12-dichloroethene 331115 2 SW5030B8260B1 1650ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trichloroethene 331140 2 SW5030B8260B1 1650ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1650ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1650ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1140Sampled

21008-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1650ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1650ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1650ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1650 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1650 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1650 LMM86-115 1100289

SPACE

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1421ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1421ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301cis-12-dichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trichloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1421ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1421ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1650Sampled

21008-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301isopropylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301135-trimethylbenzene 34118 2 SW5030B8260B1 1421ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301sec-butylbenzene 34112 2 SW5030B8260B1 1421ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 11003014-isopropyltoluene 34115 2 SW5030B8260B1 1421ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1421ugL LMM 1100301naphthalene 34118 5 SW5030B8260B1 1421ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1421ugL LMM 1100301

dibromofluoromethane SUR 341199 SW5030B8260B1 1421 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411104 SW5030B8260B1 1421 LMM88-110 11003014-bromofluorobenzene SUR 341193 SW5030B8260B1 1421 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 34118 2 SW5030B8260B1 1526ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301vinyl chloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichlorofluoromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1526ugL LMM 110030111-dichloroethene 34112 1 SW5030B8260B1 1526ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-12-dichloroethene 3411130 2 SW5030B8260B1 1526ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301cis-12-dichloroethene 3411140 2 SW5030B8260B1 1526ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trichloroethene 3411400 2 SW5030B8260B1 1526ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1526ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1526ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-3Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1544Sampled

21008-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1526ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1526ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1526ugL LMM 1100301

dibromofluoromethane SUR 3411101 SW5030B8260B1 1526 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341198 SW5030B8260B1 1526 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B1 1526 LMM86-115 1100301

SPACE

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301vinyl chloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichlorofluoromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301diethyl ether 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301acetone 3411lt 250 250 SW5030B8260B5 1601ugL LMM 110030111-dichloroethene 3411lt 5 5 SW5030B8260B5 1601ugL LMM 1100301methylene chloride 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301carbon disulfide 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-12-dichloroethene 3411220 10 SW5030B8260B5 1601ugL LMM 110030111-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-butanone (MEK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 110030122-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301cis-12-dichloroethene 3411150 10 SW5030B8260B5 1601ugL LMM 1100301chloroform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrahydrofuran (THF) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301111-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030111-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301carbon tetrachloride 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301benzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trichloroethene 34111300 10 SW5030B8260B5 1601ugL LMM 110030112-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromodichloromethane 3411lt 3 3 SW5030B8260B5 1601ugL LMM 1100301dibromomethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301cis-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301toluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301trans-13-dichloropropene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-hexanone 3411lt 50 50 SW5030B8260B5 1601ugL LMM 1100301112-trichloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tetrachloroethene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301dibromochloromethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromoethane (EDB) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301chlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011112-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301ethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301mampp-xylenes 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1555Sampled

21008-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301styrene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromoform 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301isopropylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003011122-tetrachloroethane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301123-trichloropropane 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-propylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301bromobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301135-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003012-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-chlorotoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301tert-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trimethylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301sec-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030113-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 11003014-isopropyltoluene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030114-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301n-butylbenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301124-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301hexachlorobutadiene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301naphthalene 3411lt 25 25 SW5030B8260B5 1601ugL LMM 1100301123-trichlorobenzene 3411lt 10 10 SW5030B8260B5 1601ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B5 1601 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 341199 SW5030B8260B5 1601 LMM88-110 11003014-bromofluorobenzene SUR 3411103 SW5030B8260B5 1601 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301vinyl chloride 34114 2 SW5030B8260B1 1454ugL LMM 1100301bromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichlorofluoromethane 34116 2 SW5030B8260B1 1454ugL LMM 1100301diethyl ether 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301acetone 3411lt 50 50 SW5030B8260B1 1454ugL LMM 110030111-dichloroethene 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301methylene chloride 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301carbon disulfide 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301methyl t-butyl ether (MTBE) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-12-dichloroethene 34115 2 SW5030B8260B1 1454ugL LMM 110030111-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-butanone (MEK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 110030122-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301cis-12-dichloroethene 341139 2 SW5030B8260B1 1454ugL LMM 1100301chloroform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrahydrofuran (THF) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301111-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030111-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301carbon tetrachloride 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301benzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trichloroethene 3411260 2 SW5030B8260B1 1454ugL LMM 110030112-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromodichloromethane 3411lt 1 1 SW5030B8260B1 1454ugL LMM 1100301dibromomethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-methyl-2-pentanone (MIBK) 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301cis-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301toluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301trans-13-dichloropropene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-hexanone 3411lt 10 10 SW5030B8260B1 1454ugL LMM 1100301112-trichloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tetrachloroethene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301dibromochloromethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromoethane (EDB) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301chlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011112-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301ethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301mampp-xylenes 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

Connor Homes 11005Project ID21008Job ID

MW-5Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1615Sampled

21008-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301styrene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromoform 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301isopropylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003011122-tetrachloroethane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301123-trichloropropane 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-propylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301bromobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301135-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003012-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-chlorotoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301tert-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trimethylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301sec-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030113-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 11003014-isopropyltoluene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030114-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301n-butylbenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 110030112-dibromo-3-chloropropane (DBCP) 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301124-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301hexachlorobutadiene 3411lt 05 05 SW5030B8260B1 1454ugL LMM 1100301naphthalene 3411lt 5 5 SW5030B8260B1 1454ugL LMM 1100301123-trichlorobenzene 3411lt 2 2 SW5030B8260B1 1454ugL LMM 1100301

dibromofluoromethane SUR 3411102 SW5030B8260B1 1454 LMM78-114Surrogate Recovery Limits

1100301toluene-D8 SUR 3411100 SW5030B8260B1 1454 LMM88-110 11003014-bromofluorobenzene SUR 3411104 SW5030B8260B1 1454 LMM86-115 1100301

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

dichlorodifluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006vinyl chloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromomethane 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006chloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichlorofluoromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006diethyl ether 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006acetone 3311lt 3 3 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methylene chloride 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006carbon disulfide 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006methyl t-butyl ether (MTBE) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-butanone (MEK) 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 400622-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006cis-12-dichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chloroform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrahydrofuran (THF) 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006111-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400611-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006carbon tetrachloride 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006benzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trichloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromodichloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromomethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-methyl-2-pentanone (MIBK) 3311lt 05 05 SW5035A8260B1 1755ugg LMM 3311 4006cis-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006toluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006trans-13-dichloropropene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-hexanone 3311lt 06 06 SW5035A8260B1 1755ugg LMM 3311 4006112-trichloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tetrachloroethene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006dibromochloromethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromoethane (EDB) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006chlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061112-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006ethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006mampp-xylenes 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

Connor Homes 11005Project ID21008Job ID

SB-3Solid

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1300Sampled

21008-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

Percent Dry 751 Results expressed on a dry weight basis

o-xylene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006styrene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromoform 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006isopropylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40061122-tetrachloroethane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006123-trichloropropane 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-propylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006bromobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006135-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40062-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-chlorotoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006tert-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trimethylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006sec-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400613-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 40064-isopropyltoluene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400614-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006n-butylbenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 400612-dibromo-3-chloropropane (DBCP) 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006124-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006hexachlorobutadiene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006naphthalene 3311lt 03 03 SW5035A8260B1 1755ugg LMM 3311 4006123-trichlorobenzene 3311lt 01 01 SW5035A8260B1 1755ugg LMM 3311 4006

dibromofluoromethane SUR 3311101 SW5035A8260B1 1755 LMM 331178-114Surrogate Recovery Limits

4006toluene-D8 SUR 3311100 SW5035A8260B1 1755 LMM 331188-110 40064-bromofluorobenzene SUR 3311100 SW5035A8260B1 1755 LMM 331186-115 4006aaa-trifluorotoluene SUR 3311126 SW5035A8260B1 1755 LMM 331170-130 4006

SPACE

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1900ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1900ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1900ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

SB-4Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1440Sampled

21008-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1900ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1900ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1900ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1900 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 3311100 SW5030B8260B1 1900 LMM88-110 11002894-bromofluorobenzene SUR 3311104 SW5030B8260B1 1900 LMM86-115 1100289

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289vinyl chloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichlorofluoromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289diethyl ether 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289acetone 3311lt 50 50 SW5030B8260B1 1511ugL LMM 110028911-dichloroethene 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289methylene chloride 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289carbon disulfide 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289methyl t-butyl ether (MTBE) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-butanone (MEK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 110028922-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289cis-12-dichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chloroform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrahydrofuran (THF) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289111-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028911-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289carbon tetrachloride 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289benzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trichloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromodichloromethane 3311lt 1 1 SW5030B8260B1 1511ugL LMM 1100289dibromomethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-methyl-2-pentanone (MIBK) 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289cis-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289toluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289trans-13-dichloropropene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-hexanone 3311lt 10 10 SW5030B8260B1 1511ugL LMM 1100289112-trichloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tetrachloroethene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289dibromochloromethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromoethane (EDB) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289chlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891112-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289ethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289mampp-xylenes 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

Connor Homes 11005Project ID21008Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

3111 1030Sampled

21008-008

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289styrene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromoform 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289isopropylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002891122-tetrachloroethane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289123-trichloropropane 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-propylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289bromobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289135-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002892-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-chlorotoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289tert-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trimethylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289sec-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028913-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 11002894-isopropyltoluene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028914-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289n-butylbenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 110028912-dibromo-3-chloropropane (DBCP) 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289124-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289hexachlorobutadiene 3311lt 05 05 SW5030B8260B1 1511ugL LMM 1100289naphthalene 3311lt 5 5 SW5030B8260B1 1511ugL LMM 1100289123-trichlorobenzene 3311lt 2 2 SW5030B8260B1 1511ugL LMM 1100289

dibromofluoromethane SUR 3311103 SW5030B8260B1 1511 LMM78-114Surrogate Recovery Limits

1100289toluene-D8 SUR 331199 SW5030B8260B1 1511 LMM88-110 11002894-bromofluorobenzene SUR 3311101 SW5030B8260B1 1511 LMM86-115 1100289

SPACE

Project Connor Homes 11005si

21088Job IDPO Number None

31711Date Received

Martha Roy

414 Roosevelt HighwaySuite 200

The Verterre Group

Colchester VT 05446

Unless otherwise noted in the attached report the analyses performed met the requirements of AbsoluteResource Associates Quality Assurance Plan The Standard Operating Procedures are based uponUSEPA SW-846 USEPA Methods for Chemical Analysis of Water and Wastewater Standard Methodsfor the Examination of Water and Wastewater and other recognized methodologies The resultscontained in this report pertain only to the samples as indicated on the chain of custody

Absolute Resource Associates maintains certification with the agencies listed below

We appreciate the opportunity to provide laboratory services If you have any questions regarding theenclosed report please contact the laboratory and we will be glad to assist you

Total number of pagesDate of Approval

SincerelyAbsolute Resource Associates

Attached please find results for the analysis of the samples received on the date referenced above

323201116

Sue SylvesterPrincipal General Manager

124 Heritage Avenue 10 Portsmouth NH 03801

124 Heritage Avenue 10 | Portsmouth NH 03801 | 603-436-2001 | absoluteresourceassociatescom

Absolute Resource Associates Certifications

New HampshireMaine NH903

1732 Massachusetts M-NH902

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 914ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-12-dichloroethene 319114 2 SW5030B8260B1 914ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398cis-12-dichloroethene 3191120 2 SW5030B8260B1 914ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trichloroethene 3191151 2 SW5030B8260B1 914ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 914ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 914ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398ethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

2

Connor Homes 11005siProject ID21088Job ID

MW-1Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1410Sampled

21088-001

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398isopropylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-propylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398135-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398sec-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 11003984-isopropyltoluene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 914ugL LMM 1100398naphthalene 31911lt 5 5 SW5030B8260B1 914ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 914ugL LMM 1100398

dibromofluoromethane SUR 31911106 SW5030B8260B1 914 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911105 SW5030B8260B1 914 LMM88-110 11003984-bromofluorobenzene SUR 31911103 SW5030B8260B1 914 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

3

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398vinyl chloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichlorofluoromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398diethyl ether 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398acetone 31911lt 50 50 SW5030B8260B1 809ugL LMM 110039811-dichloroethene 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398methylene chloride 31911lt 5 5 SW5030B8260B1 809ugL LMM 1100398carbon disulfide 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398methyl t-butyl ether (MTBE) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-butanone (MEK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 110039822-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398cis-12-dichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chloroform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrahydrofuran (THF) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398111-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039811-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398carbon tetrachloride 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398benzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trichloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromodichloromethane 31911lt 1 1 SW5030B8260B1 809ugL LMM 1100398dibromomethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-methyl-2-pentanone (MIBK) 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398cis-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398toluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398trans-13-dichloropropene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003982-hexanone 31911lt 10 10 SW5030B8260B1 809ugL LMM 1100398112-trichloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039813-dichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tetrachloroethene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398dibromochloromethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromoethane (EDB) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398chlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003981112-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398ethylbenzene 319112 2 SW5030B8260B1 809ugL LMM 1100398mampp-xylenes 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

4

Connor Homes 11005siProject ID21088Job ID

MW-2Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1414Sampled

21088-002

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398styrene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398bromoform 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398isopropylbenzene 319116 2 SW5030B8260B1 809ugL LMM 11003981122-tetrachloroethane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398123-trichloropropane 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-propylbenzene 319114 2 SW5030B8260B1 809ugL LMM 1100398bromobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398135-trimethylbenzene 3191115 2 SW5030B8260B1 809ugL LMM 11003982-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-chlorotoluene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398tert-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trimethylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398sec-butylbenzene 319112 2 SW5030B8260B1 809ugL LMM 110039813-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 11003984-isopropyltoluene 319114 2 SW5030B8260B1 809ugL LMM 110039814-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398n-butylbenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 110039812-dibromo-3-chloropropane (DBCP) 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398124-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398hexachlorobutadiene 31911lt 05 05 SW5030B8260B1 809ugL LMM 1100398naphthalene 3191148 5 SW5030B8260B1 809ugL LMM 1100398123-trichlorobenzene 31911lt 2 2 SW5030B8260B1 809ugL LMM 1100398

dibromofluoromethane SUR 31911101 SW5030B8260B1 809 LMM78-114Surrogate Recovery Limits

1100398toluene-D8 SUR 31911108 SW5030B8260B1 809 LMM88-110 11003984-bromofluorobenzene SUR 3191193 SW5030B8260B1 809 LMM86-115 1100398

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

5

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2152ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2152ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2152ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

6

Connor Homes 11005siProject ID21088Job ID

MW-6Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1400Sampled

21088-003

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2152ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2152ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2152ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 2152 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 2152 LMM88-110 11003964-bromofluorobenzene SUR 31811102 SW5030B8260B1 2152 LMM86-115 1100396

SPACE

7

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1940ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1940ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1940ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

8

Connor Homes 11005siProject ID21088Job ID

MW-7Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1406Sampled

21088-004

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1940ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1940ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1940ugL LMM 1100396

dibromofluoromethane SUR 31811104 SW5030B8260B1 1940 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 1940 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1940 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

9

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2013ugL LMM 110039611-dichloroethene 318111 1 SW5030B8260B1 2013ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-12-dichloroethene 3181123 2 SW5030B8260B1 2013ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396cis-12-dichloroethene 31811160 2 SW5030B8260B1 2013ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trichloroethene 3181118 2 SW5030B8260B1 2013ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2013ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2013ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

10

Connor Homes 11005siProject ID21088Job ID

MW-8Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1428Sampled

21088-005

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2013ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2013ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2013ugL LMM 1100396

dibromofluoromethane SUR 31811105 SW5030B8260B1 2013 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811108 SW5030B8260B1 2013 LMM88-110 11003964-bromofluorobenzene SUR 31811101 SW5030B8260B1 2013 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationSPACE

11

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 3181111 2 SW5030B8260B1 2225ugL LMMJ 1100396chloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 2225ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-12-dichloroethene 3181129 2 SW5030B8260B1 2225ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396cis-12-dichloroethene 31811120 2 SW5030B8260B1 2225ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trichloroethene 3181177 2 SW5030B8260B1 2225ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 2225ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 2225ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

12

Connor Homes 11005siProject ID21088Job ID

MW-9Water

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1429Sampled

21088-006

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 2225ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 2225ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 2225ugL LMM 1100396

dibromofluoromethane SUR 31811102 SW5030B8260B1 2225 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811107 SW5030B8260B1 2225 LMM88-110 11003964-bromofluorobenzene SUR 31811103 SW5030B8260B1 2225 LMM86-115 1100396

Note The sample pH was greater than 2 indicating inadequate preservationJ = The associated CCV showed recovery above the acceptance criteria The associated LCSD showed acceptable recoveriesSPACE

13

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

dichlorodifluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396vinyl chloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichlorofluoromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396diethyl ether 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396acetone 31811lt 50 50 SW5030B8260B1 1252ugL LMM 110039611-dichloroethene 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396methylene chloride 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396carbon disulfide 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396methyl t-butyl ether (MTBE) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-butanone (MEK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 110039622-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396cis-12-dichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chloroform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrahydrofuran (THF) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396111-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039611-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396carbon tetrachloride 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396benzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trichloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromodichloromethane 31811lt 1 1 SW5030B8260B1 1252ugL LMM 1100396dibromomethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-methyl-2-pentanone (MIBK) 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396cis-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396toluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396trans-13-dichloropropene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-hexanone 31811lt 10 10 SW5030B8260B1 1252ugL LMM 1100396112-trichloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tetrachloroethene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396dibromochloromethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromoethane (EDB) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396chlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961112-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396ethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396mampp-xylenes 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

14

Connor Homes 11005siProject ID21088Job ID

FBWater

Sample IDMatrix

Parameter ResultAnalysis

Date Time

Sample

QuantLimit Reference

31511 1345Sampled

21088-007

AnalystInstr Diln

FactorUnitsPrepDate Batch

o-xylene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396styrene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromoform 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396isopropylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003961122-tetrachloroethane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396123-trichloropropane 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-propylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396bromobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396135-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003962-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-chlorotoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396tert-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trimethylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396sec-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039613-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 11003964-isopropyltoluene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039614-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396n-butylbenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 110039612-dibromo-3-chloropropane (DBCP) 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396124-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396hexachlorobutadiene 31811lt 05 05 SW5030B8260B1 1252ugL LMM 1100396naphthalene 31811lt 5 5 SW5030B8260B1 1252ugL LMM 1100396123-trichlorobenzene 31811lt 2 2 SW5030B8260B1 1252ugL LMM 1100396

dibromofluoromethane SUR 31811103 SW5030B8260B1 1252 LMM78-114Surrogate Recovery Limits

1100396toluene-D8 SUR 31811106 SW5030B8260B1 1252 LMM88-110 11003964-bromofluorobenzene SUR 31811100 SW5030B8260B1 1252 LMM86-115 1100396

SPACE

15

16

ANALYTICAL REPORT

Job Number 200-4287-1

Job Description Connor Homes

ForPhelps Engineering Inc

PO Box 367Middlebury VT 05753

Attention Mr Jonathan Ashley

_____________________________________________

Approved for releaseDon C DawickiProject Manager II3242011 347 PM

Don C DawickiProject Manager II

dondawickitestamericainccom03242011

The test results in this report relate only to sample(s) as received by the laboratory These test results were derivedunder a quality system that adheres to the requirements of NELAC Pursuant to NELAC this report may not beproduced in full without written approval from the laboratory

TestAmerica Laboratories Inc

TestAmerica Burlington 30 Community Drive Suite 11 South Burlington VT 05403

Tel (802) 660-1990 Fax (802) 660-1919 wwwtestamericainccom

Page 1 of 18

CASE NARRATIVE

Client Phelps Engineering Inc

Project Connor Homes

Report Number 200-4287-1

With the exceptions noted as flags or footnotes standard analytical protocols were followed in the analysis of the samples and no problems were encountered or anomalies observed In addition all laboratory quality control samples were within established control limits with any exceptions noted below Each sample was analyzed to achieve the lowest possible reporting limit within the constraints of the method In some cases due to interference or analytes present at high concentrations samples were diluted For diluted samples the reporting limits are adjusted relative to the dilution required

Calculations are performed before rounding to avoid round-off errors in calculated results

All holding times were met and proper preservation noted for the methods performed on these samples unless otherwise detailed in the individual sections below

RECEIPTThe samples were received on 03172011 the samples arrived in good condition

LOW LEVEL VOLATILE ORGANIC COMPOUNDSSamples WEST SINK AREA EAST SINK AREA and OUTSIDE BREAKROOM were analyzed for Low Level Volatile Organic Compounds in accordance with EPA Method TO-15 The samples were analyzed on 03202011

No difficulties were encountered during the Low Level VOC analyses

All quality control parameters were within the acceptance limits

Page 2 of 18

EXECUTIVE SUMMARY - Detections

Client Phelps Engineering Inc Job Number 200-4287-1

Analyte Result Qualifier

Reporting

Limit Units Method

Lab Sample ID Client Sample ID

200-4287-1 WEST SINK AREA

0040 ppb vv TO15 LL014cis-12-Dichloroethene

016 ugm3 TO15 LL056cis-12-Dichloroethene

0040 ppb vv TO15 LL01412-Dichloroethene Total

016 ugm3 TO15 LL05612-Dichloroethene Total

0040 ppb vv TO15 LL044Trichloroethene

021 ugm3 TO15 LL24Trichloroethene

200-4287-2 EAST SINK AREA

0040 ppb vv TO15 LL012cis-12-Dichloroethene

016 ugm3 TO15 LL049cis-12-Dichloroethene

0040 ppb vv TO15 LL01212-Dichloroethene Total

016 ugm3 TO15 LL04912-Dichloroethene Total

0040 ppb vv TO15 LL038Trichloroethene

021 ugm3 TO15 LL20Trichloroethene

TestAmerica Burlington

Page 3 of 18

METHOD SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Preparation MethodMethodLab LocationDescription

Matrix Air

Volatile Organic Compounds in Ambient Air Low

Concentration (GCMS)

TAL BUR EPA TO15 LL

Collection via Summa Canister TAL BUR Summa Canister

Lab References

TAL BUR = TestAmerica Burlington

Method References

EPA = US Environmental Protection Agency

TestAmerica Burlington Page 4 of 18

METHOD ANALYST SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Method Analyst Analyst ID

Desjardins William R WRDEPA TO15 LL

TestAmerica Burlington

Page 5 of 18

SAMPLE SUMMARY

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample IDLab Sample ID Client Matrix Sampled Received

DateTime DateTime

200-4287-1 WEST SINK AREA Air 03162011 1616 03172011 1020

200-4287-2 EAST SINK AREA Air 03162011 1625 03172011 1020

200-4287-3 OUTSIDE BREAKROOM Air 03162011 1633 03172011 1020

TestAmerica Burlington Page 6 of 18

SAMPLE RESULTS

TestAmerica Burlington

Page 7 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

WEST SINK AREA

Client Matrix

200-4287-1

Air

Date Sampled 03162011 1616

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1149

03202011 1149

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf005d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

014 00400040cis-12-Dichloroethene

014 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

044 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

056 016016cis-12-Dichloroethene

056 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

24 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 8 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

EAST SINK AREA

Client Matrix

200-4287-2

Air

Date Sampled 03162011 1625

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1244

03202011 1244

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf006d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

012 00400040cis-12-Dichloroethene

012 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

038 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

049 016016cis-12-Dichloroethene

049 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

20 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 9 of 18

Analytical Data

Client Phelps Engineering Inc Job Number 200-4287-1

Client Sample ID

Lab Sample ID

OUTSIDE BREAKROOM

Client Matrix

200-4287-3

Air

Date Sampled 03162011 1633

Date Received 03172011 1020

TO15 LL Volatile Organic Compounds in Ambient Air Low Concentration (GCMS)

Method

Date Prepared

Date Analyzed

Dilution

Preparation

03202011 1339

03202011 1339

40

TO15 LL Analysis Batch 200-15342

Injection Volume

Final WeightVolume

Initial WeightVolume

Lab File ID

Instrument ID

eejf007d

125 mL

500 mL

500 mL

Summa Canister

Ei

Analyte Result (ppb vv) Qualifier RL RL

0080 U 00800080Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0040 U 00400040111-Trichloroethane

0080 U 0080008012-Dichloroethane

0040 U 00400040Trichloroethene

0040 U 00400040112-Trichloroethane

0040 U 00400040Tetrachloroethene

0040 U 004000401122-Tetrachloroethane

Analyte Result (ugm3) Qualifier RL RL

020 U 020020Vinyl chloride

016 U 01601611-Dichloroethene

016 U 016016trans-12-Dichloroethene

016 U 01601611-Dichloroethane

016 U 016016cis-12-Dichloroethene

016 U 01601612-Dichloroethene Total

022 U 022022111-Trichloroethane

032 U 03203212-Dichloroethane

021 U 021021Trichloroethene

022 U 022022112-Trichloroethane

027 U 027027Tetrachloroethene

027 U 0270271122-Tetrachloroethane

TestAmerica Burlington Page 10 of 18

DATA REPORTING QUALIFIERS

Client Phelps Engineering Inc Job Number 200-4287-1

Lab Section Qualifier Description

Air - GCMS VOA

Indicates the analyte was analyzed for but not detectedU

TestAmerica Burlington

Page 11 of 18

QUALITY CONTROL RESULTS

TestAmerica Burlington

Page 12 of 18

Quality Control Results

Client Phelps Engineering Inc Job Number 200-4287-1

QC Association Summary

Lab Sample ID Client Sample ID Client Matrix Method Prep Batch

Report

Basis

Air - GCMS VOA

Analysis Batch200-15342

Lab Control Sample Air TO15 LLLCS 200-153423 T

Method Blank Air TO15 LLMB 200-153424 T

AirWEST SINK AREA TO15 LL200-4287-1 T

AirEAST SINK AREA TO15 LL200-4287-2 T

AirOUTSIDE BREAKROOM TO15 LL200-4287-3 T

Report Basis

T = Total

TestAmerica Burlington

Page 13 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0020 U 00200020Vinyl chloride

0010 U 0010001011-Dichloroethene

0010 U 00100010trans-12-Dichloroethene

0010 U 0010001011-Dichloroethane

0010 U 00100010cis-12-Dichloroethene

0010 U 0010001012-Dichloroethene Total

0010 U 00100010111-Trichloroethane

0020 U 0020002012-Dichloroethane

0010 U 00100010Trichloroethene

0010 U 00100010112-Trichloroethane

0010 U 00100010Tetrachloroethene

0010 U 001000101122-Tetrachloroethane

AirClient Matrix

10Dilution

Date Analyzed

Lab Sample ID

03202011 0831

Method Blank - Batch 200-15342

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

Analysis Batch 200-15342

Prep Batch NA

03202011 0831

eejf004d

500 mL

500 mL

500 mL

Units ugm3

Method TO15 LL

Preparation Summa Canister

EiMB 200-153424

Analyte Result Qual RL RL

0051 U 00510051Vinyl chloride

0040 U 0040004011-Dichloroethene

0040 U 00400040trans-12-Dichloroethene

0040 U 0040004011-Dichloroethane

0040 U 00400040cis-12-Dichloroethene

0040 U 0040004012-Dichloroethene Total

0055 U 00550055111-Trichloroethane

0081 U 0081008112-Dichloroethane

0054 U 00540054Trichloroethene

0055 U 00550055112-Trichloroethane

0068 U 00680068Tetrachloroethene

0069 U 006900691122-Tetrachloroethane

TestAmerica Burlington Page 14 of 18

Quality Control Results

Job Number 200-4287-1Client Phelps Engineering Inc

Air

10

03202011 0736Date Analyzed

Lab Control Sample - Batch 200-15342

Client Matrix

Lab Sample ID

Dilution

Date Prepared

Instrument ID

Lab File ID

Initial WeightVolume

Final WeightVolume

Injection Volume

eejf003d

03202011 0736

Analysis Batch 200-15342

Prep Batch NA

500 mL

500 mL

500 mL

Units ppb vv

Method TO15 LL

Preparation Summa Canister

EiLCS 200-153423

Analyte QualLimit RecResultSpike Amount

0200 0207 104 70 - 130Vinyl chloride

0200 0177 89 70 - 13011-Dichloroethene

0200 0167 84 70 - 130trans-12-Dichloroethene

0200 0166 83 70 - 13011-Dichloroethane

0200 0180 90 70 - 130cis-12-Dichloroethene

0200 0181 91 70 - 130111-Trichloroethane

0200 0177 89 70 - 13012-Dichloroethane

0200 0166 83 70 - 130Trichloroethene

0200 0169 85 70 - 130112-Trichloroethane

0200 0188 94 70 - 130Tetrachloroethene

0200 0169 85 70 - 1301122-Tetrachloroethane

TestAmerica Burlington Page 15 of 18

Page 16 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 1

NARadioactivity either was not measured or if measured is at or below

background

Lab does not accept radioactive samples

TrueThe coolers custody seal if present is intact 853920 853919

TrueThe cooler or samples do not appear to have been compromised or

tampered with

NASamples were received on ice Thermal preservation not required

TrueCooler Temperature is acceptable

TrueCooler Temperature is recorded AMBIENT

TrueCOC is present

TrueCOC is filled out in ink and legible

TrueCOC is filled out with all pertinent information

TrueIs the Field Samplers name present on COC

TrueThere are no discrepancies between the sample IDs on the containers and

the COC

TrueSamples are received within Holding Time

TrueSample containers have legible labels

TrueContainers are not broken or leaking

TrueSample collection datetimes are provided

TrueAppropriate sample containers are used

TrueSample bottles are completely filled

NASample Preservation Verified

TrueThere is sufficient vol for all requested analyses incl any requested

MSMSDs

NAVOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

NAMultiphasic samples are not present

NASamples do not require splitting or compositing

NAResidual Chlorine Checked Lab does not accept radioactive samples

TestAmerica Burlington Page 17 of 18

Login Sample Receipt Checklist

Client Phelps Engineering Inc Job Number 200-4287-1

Login Number 4287

Question Answer Comment

Creator Marion Greg T

List Source TestAmerica Burlington

List Number 2

Radioactivity either was not measured or if measured is at or below

background

The coolers custody seal if present is intact

The cooler or samples do not appear to have been compromised or

tampered with

Samples were received on ice

Cooler Temperature is acceptable

Cooler Temperature is recorded

COC is present

COC is filled out in ink and legible

COC is filled out with all pertinent information

Is the Field Samplers name present on COC

There are no discrepancies between the sample IDs on the containers and

the COC

Samples are received within Holding Time

Sample containers have legible labels

Containers are not broken or leaking

Sample collection datetimes are provided

Appropriate sample containers are used

Sample bottles are completely filled

Sample Preservation Verified

There is sufficient vol for all requested analyses incl any requested

MSMSDs

VOA sample vials do not have headspace or bubble is lt6mm (14) in

diameter

If necessary staff have been informed of any short hold time or quick TAT

needs

Multiphasic samples are not present

Samples do not require splitting or compositing

TestAmerica Burlington Page 18 of 18

  • Site Investigation Report
  • Figures
  • Site Location Map
  • Exhibits
  • EXH1
  • EXH2
  • EXH3
  • EXH4
  • Tables
  • Table 1
  • Table 1A
  • Table 2
  • Table 3
  • Appendices
  • App A - MW-1
  • App A - MW-2
  • App A - MW-3
  • App A - MW-4
  • App A - MW-5
  • App A - MW-6
  • App A - MW-7
  • App A - MW-8
  • App A - MW-9
  • App A - SB-3
  • App A - SB-4
  • App B Drilled Well Logs
  • Appendix B Map of Drilled Wells
  • Appendix C March 1 Sampling Lab Report
  • Appendix C March 15 Sampling Lab Report
  • Appendix D Air Samples J4287-1 Std_Tal_L2 Final Report
    • Cover Title Page
    • Report Narrative
    • Executive Summary
    • Method Summary
    • Method Analyst Summary
    • Sample Summary
    • Sample Results
    • Sample Datasheets
    • Data Qualifiers
    • QC Results
    • Qc Association Summary
    • Qc Reports
    • Client Chain of Custody
    • Sample Receipt Checklist
Page 16: 0311 site investigation
Page 17: 0311 site investigation
Page 18: 0311 site investigation
Page 19: 0311 site investigation
Page 20: 0311 site investigation
Page 21: 0311 site investigation
Page 22: 0311 site investigation
Page 23: 0311 site investigation
Page 24: 0311 site investigation
Page 25: 0311 site investigation
Page 26: 0311 site investigation
Page 27: 0311 site investigation
Page 28: 0311 site investigation
Page 29: 0311 site investigation
Page 30: 0311 site investigation
Page 31: 0311 site investigation
Page 32: 0311 site investigation
Page 33: 0311 site investigation
Page 34: 0311 site investigation
Page 35: 0311 site investigation
Page 36: 0311 site investigation
Page 37: 0311 site investigation
Page 38: 0311 site investigation
Page 39: 0311 site investigation
Page 40: 0311 site investigation
Page 41: 0311 site investigation
Page 42: 0311 site investigation
Page 43: 0311 site investigation
Page 44: 0311 site investigation
Page 45: 0311 site investigation
Page 46: 0311 site investigation
Page 47: 0311 site investigation
Page 48: 0311 site investigation
Page 49: 0311 site investigation
Page 50: 0311 site investigation
Page 51: 0311 site investigation
Page 52: 0311 site investigation
Page 53: 0311 site investigation
Page 54: 0311 site investigation
Page 55: 0311 site investigation
Page 56: 0311 site investigation
Page 57: 0311 site investigation
Page 58: 0311 site investigation
Page 59: 0311 site investigation
Page 60: 0311 site investigation
Page 61: 0311 site investigation
Page 62: 0311 site investigation
Page 63: 0311 site investigation
Page 64: 0311 site investigation
Page 65: 0311 site investigation
Page 66: 0311 site investigation
Page 67: 0311 site investigation
Page 68: 0311 site investigation
Page 69: 0311 site investigation
Page 70: 0311 site investigation
Page 71: 0311 site investigation
Page 72: 0311 site investigation
Page 73: 0311 site investigation
Page 74: 0311 site investigation
Page 75: 0311 site investigation
Page 76: 0311 site investigation
Page 77: 0311 site investigation
Page 78: 0311 site investigation
Page 79: 0311 site investigation
Page 80: 0311 site investigation