Electrical Machines
LSEGG216A9080V
![Page 2: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/2.jpg)
TransformerTransformerLosses & EfficiencyLosses & Efficiency
Week 3Week 3
![Page 3: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/3.jpg)
ObjectiveObjectivess1. Describe the power losses which occur in a transformer
2. Describe the tests which allow the power losses of a transformer to be calculated
3. Calculate transformer losses and efficiency using test results
4. Define the all day efficiency of a transformer5. Calculate the all day efficiency of a transformer
6. Describe the relationship between transformer cooling and rating
![Page 4: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/4.jpg)
5. Calculate the all day efficiency of a transformer
6. Describe the relationship between transformer cooling and rating
7. Describe the methods of cooling
8. List the properties of transformer oil
9. Describe the tests conducted on transformer oil
Objectives
![Page 5: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/5.jpg)
Transformer RatingsTransformer RatingsTransformers are rated to supply a given output in
Volt Ampsor
VAat a specified frequency and terminal voltage.
![Page 6: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/6.jpg)
Transformer RatingsTransformer RatingsThey are NOT rated in Watts
The load power factor is unknown
IVS PFSPower
PF
PowerS
![Page 7: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/7.jpg)
Transformer RatingsTransformer RatingsThey are NOT rated in Watts
The load power factor is unknown
![Page 8: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/8.jpg)
Problem
V1 = 6,351 V
V2 = 230 V
S = 2 kVA
Power output at unity PF ?
P = 2 kVA x 1
P = 2 kW
Power = S x PF
![Page 9: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/9.jpg)
Problem
PFVS
I
V1 = 6,351 V
V2 = 230 V
S = 2 kVA
Full load secondary current at 0.8 PF ?
I = 10.87 A
0.82302000
I
![Page 10: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/10.jpg)
Student Exercise 1
![Page 11: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/11.jpg)
PFSPower
V2 = 200 VV1 = 1270 V
S = 20 kVA
0.1000,20 P
P = 20 kW
(a) Power output at unity power factor
![Page 12: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/12.jpg)
PFSPower
V2 = 200 VV1 = 1270 V
S = 20 kVA
8.0000,20 P
P = 16 kW
(b) Power output at 0.8 power factor
![Page 13: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/13.jpg)
VxPFS
I
V2 = 200 VV1 = 1270 V
S = 20 kVA
I = 100 A
(c) Full-load secondary current at unity power factor
200x1.020,000
I
![Page 14: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/14.jpg)
VxPFS
I
V2 = 200 VV1 = 1270 V
S = 20 kVA
I = 62.5 A
(d) Secondary current when transformer supplies 10 kW at 0.8 power factor
200x0.810,000
I
![Page 15: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/15.jpg)
Efficiency
PowerInputPowerOutput
η
LossesOutputInput
LossesPowerOutput
PowerOutputη
Ratio between Input power and Output Power
PowerInputLossesPowerInput
η
![Page 16: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/16.jpg)
Efficiency
100PowerInputPowerOutput
η%
Efficiency is normally expressed as a percentage
![Page 17: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/17.jpg)
Transformer Efficiency
PowerIn
PowerOut
OvercomeIron
Losses
Overcome Copper Losses
Some Poweris used to:
η = 100%η = 95%η = 90%
![Page 18: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/18.jpg)
Student Exercise 2
![Page 19: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/19.jpg)
PFSPower
V1 = 230 V V2 = 32 V
S = 20 kVA
η = 90% PF = 0.85
(a) Power output of transformer
0.85100P
P = 85 W
![Page 20: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/20.jpg)
InOut
η
V1 = 230 V V2 = 32 V
S = 20 kVA
η = 90% PF = 0.85
(b) Power input
P = 94.4 W
ηOut
In
0.9W 85
In
![Page 21: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/21.jpg)
LossesOutIn
V1 = 230 V V2 = 32 V
S = 20 kVA
η = 90% PF = 0.85
(c) Losses
P = 9.4W
Losses8594.4
![Page 22: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/22.jpg)
Transformer Losses
Copper Losses (Cu)
•Varies with load current
•Produces HEAT •Created by resistance of windings
•Short circuit test supplies copper losses
![Page 23: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/23.jpg)
Short Circuit TestCopper Losses
(Cu)
SecondaryShort
Circuited
Limited
Supply Voltage ≈ 5-10 %
Wattmeter indicates Copper Losses (Cu)
![Page 24: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/24.jpg)
Short Circuit Test
1000.5lossCopper 2
Copper Losses (Cu)•Finds Cooper losses at full load
•Copper losses vary with the square of the load Full load Cu loss = 100
WTransformer loaded at 50%
PCu = 25 W
1000.25lossCopper
![Page 25: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/25.jpg)
0102030405060708090
100110120130140150
0 10 20 30 40 50 60 70 80 90 100 110
Copper Losses (Cu)
% Load
Cu
Losses (
W)
![Page 26: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/26.jpg)
Transformer LossesIron Losses
(Fe)•Fixed
•Always present
•Related to transformers construction
Eddy Currents
Reduced by laminations
Produces HEAT
Hysteresis
Reduced by using special steels in laminations
![Page 27: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/27.jpg)
Open Circuit TestFinds Iron Losses
(Fe)
Full Supply Voltage
SecondaryOpen Circuit
Wattmeter indicates Iron Losses (Fe)
![Page 28: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/28.jpg)
Transformer Efficiency
Student Exercise 3
100PowerInput
PowerOutputη%
LossesCuLoadFullload 2%Cu Losses
![Page 29: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/29.jpg)
100PowerInput
PowerOutputη%
Sout = 30 kVA Fe = 220 WCu FL= 840 W
Calculate η%at Full Load
100Losses Output
PowerOutputη%
100k 0.22k 84k 30
k 30η%
.0
η% = 96.6%
![Page 30: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/30.jpg)
100Losses Output
PowerOutputη%
Sout = 30 kVA Fe = 220 WCu FL= 840 W
Calculate η%at 75%Load
1000.220.75 22.5
22.5η% 2
84.0
η% = 97%
1000.220.4725 22.5
22.5η%
5.223075.0 outS
5.47284075.0 2 75%Cu
![Page 31: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/31.jpg)
100Losses Output
PowerOutputη%
Sout = 30 kVA Fe = 220 WCu FL= 840 W
Calculate η%at 50%Load
1000.220.5 15
15η% 2
84.0
η% = 97.21%
1000.220.21 15
15η%
15305.0 outS
![Page 32: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/32.jpg)
100Losses Output
PowerOutputη%
Sout = 30 kVA Fe = 220 WCu FL= 840 W
Calculate η%at 25%Load
1000.220.25 7.5
7.5η% 2
84.0
η% = 96.49%
1000.220.0525 7.5
7.5η%
5.73025.0 outS
![Page 33: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/33.jpg)
100% η = 96.6%75% η = 97%50% η = 97.21%25% η = 96.49%
![Page 34: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/34.jpg)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0 10 20 30 40 50 60 70 80 90 100 110
96.00
97.00
% Load
Losses (
W)
η%
Cu Losses
Fe Losses
η%
Fe = Cu =Max η
![Page 35: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/35.jpg)
Maximum Efficiency
Fe = Cu =Max η
CuLoadFe 2
2LoadCuFe
LoadCuFe
Load840220
Fe = 220
Cu = 840
Load %= 51.18%
1000.220.5118 300.5118
300.5118η% 2
84.0
1000.22
15.35η%
22.035.15
η%= 97.21%
![Page 36: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/36.jpg)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0 10 20 30 40 50 60 70 80 90 100 110
96.00
97.00
![Page 37: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/37.jpg)
All Day Efficiency
• Most Transformers are connected permanently
• The time that the transformer has to be calculated when determining efficiency
• Able to determine the best transformer for the application
by its efficiency
![Page 38: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/38.jpg)
All Day EfficiencyTransformer A
Sout = 300 kVA Fe = 1.25 kVA Cu = 3.75 kVAHours Load kW kWh % Load Cu Loss Cu kWh Fe kWh Losses kWh Input kWh
1.00 6.00 5 100 500.0 33.33 0.42 2.08 6.25 8.33 508.336.00 7.00 1 200 200.0 66.67 1.67 1.67 1.25 2.92 202.927.00 8.00 1 300 300.0 100.00 3.75 3.75 1.25 5.00 305.008.00 9.00 1 360 360.0 120.00 5.40 5.40 1.25 6.65 366.659.00 12.00 3 300 900.0 100.00 3.75 11.25 3.75 15.00 915.0012.00 14.00 2 280 560.0 93.33 3.27 6.53 2.50 9.03 569.0314.00 18.00 4 300 1200.0 100.00 3.75 15.00 5.00 20.00 1220.0018.00 20.00 2 360 720.0 120.00 5.40 10.80 2.50 13.30 733.3020.00 22.00 2 280 560.0 93.33 3.27 6.53 2.50 9.03 569.0322.00 1.00 3 200 600.0 66.67 1.67 5.00 3.75 8.75 608.75
5900.0 5998.02
98.37
Time Period
P out kWh = P in kWh =
% Eff =
![Page 39: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/39.jpg)
All Day EfficiencyTransformer B
Sout = 300 kVA Fe = 2.5 kVA Cu = 2.5 kVA
Hours Load kW kWh % Load Cu Loss Cu kWh Fe kWh Losses kWh Input kWh1.00 6.00 5 100 500.0 33.33 0.28 1.39 12.50 13.89 513.896.00 7.00 1 200 200.0 66.67 1.11 1.11 2.50 3.61 203.617.00 8.00 1 300 300.0 100.00 2.50 2.50 2.50 5.00 305.008.00 9.00 1 360 360.0 120.00 3.60 3.60 2.50 6.10 366.109.00 12.00 3 300 900.0 100.00 2.50 7.50 7.50 15.00 915.0012.00 14.00 2 280 560.0 93.33 2.18 4.36 5.00 9.36 569.3614.00 18.00 4 300 1200.0 100.00 2.50 10.00 10.00 20.00 1220.0018.00 20.00 2 360 720.0 120.00 3.60 7.20 5.00 12.20 732.2020.00 22.00 2 280 560.0 93.33 2.18 4.36 5.00 9.36 569.3622.00 1.00 3 200 600.0 66.67 1.11 3.33 7.50 10.83 610.83
5900.0 6005.34
98.25% Eff =
Time Period
P out kWh = P in kWh =
![Page 40: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/40.jpg)
Transformer Cooling• Transformer ratings can be increased if their windings are cooled
by some external means
• The most common cooling mediums are in direct with transformer windings;
and/orAir Oil• The most common methods of circulation are
Forced
and/or Natural
![Page 41: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/41.jpg)
![Page 42: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/42.jpg)
Transformer Classification• Transformers are allocated symbols which indicate the type of
cooling used• Can consist of up to 4 letters indicating the cooling system
1st Letter 2nd Letter 3rd Letter 4th Letter
The cooling medium in contact with the windings
The cooling medium in contact with the external cooling
system
Kind of Medium
Circulation type
Kind of Medium
Circulation type
![Page 43: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/43.jpg)
Transformer Classification
Type AN
Dry Transformer withNatural Air Flow
Air Natural
![Page 44: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/44.jpg)
Transformer Classification
Type AFDry Transformer with
Forced Air Flow
Air Forced
![Page 45: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/45.jpg)
Transformer Classification
Type ONAN
Oil Tank Cooling Natural Oil Flow - Natural Air Flow
Oil Natural Air Natural
![Page 46: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/46.jpg)
Transformer Classification
Type ONAF
Oil Tank Cooling Natural Oil Flow - Forced Air Flow
Oil Natural Air Forced
![Page 47: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/47.jpg)
Transformer ClassificationType OFAF
Oil Tank Cooling Forced Oil Flow – Forced Air Flow
Oil Forced Air Forced
![Page 48: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/48.jpg)
Transformer Oil
• Low Viscosity
• High Flash point
• Chemically inert
• Good insulator
Acts as Coolant & Insulator
![Page 49: 03 Transformer Losses & Efficiency](https://reader033.vdocuments.site/reader033/viewer/2022061309/55250b384a7959f90c8b46ec/html5/thumbnails/49.jpg)
Transformer Oil Tests
• Dielectric Strength• Acidity • Power factor • Interfacial tension • Dissolved Gas