! warning tem is not correctly wired. such voltage …...turn power off before any troubleshooting...
TRANSCRIPT
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
50A55 INTEGRATED FURNACE CONTROL MODULEQualifiedServiceman’sTroubleshootingGuideTROUBLESHOOTING PROCEDUREIfthelightonthemoduleisoncontinuously,thefaultislikelytobeinternaltothemodule.Tomakesure,interruptlineor24voltthermostatpowerforafewsecondsandthenrestore.Ifinternalfaultisindicatedagain,andflamesensorisnotshortedtoground,replacecontrol.Aflashinglightindicatestheproblemismostlikelyintheexternal components or wiring. Proceed as follows:
WARNING!Failure to read and follow all instructions carefully before in-stalling or operating this control, could cause personal injury and/or property damage.
WARNING!Turn power off before any troubleshooting or servicing begins.Line voltage (120 VAC) could be present on the surface of the ignitor, if the sys-tem is not correctly wired. Such voltage can cause serious injury or death.
Thefollowingstepsmustbeperformedfirstbeforeanytroubleshootingbegins.1)Disconnectelectricpowertosystematmainfuseorcircuitbreaker.2)Visuallyinspectequipmentforapparentdamage.Checkwiringforloose connections.3)Checkforpropergroundingandreversedpolarity. A. CheckcontinuityforCterminalonmoduletoelectricalservicegroundand connectionatthefurnacejunctionbox.Ifgroundconnectionisopen,check module ground connection and the electrical service ground connection. Repair and retest. B. Re-connect electric power to system. C. Checkforvoltagebetweenthelineneutralterminalandfurnaceground.If voltage exists, the main power supply lines are improperly connected to the furnace (REVERSED POLARITY). Again disconnect electric power to system; then reverse incoming supply leads to furnace. Repeat step. D. Rechecksystemforproperoperation.
If neither apparent damage, loose connection nor reversed polarity is the problem, proceed to troubleshooting chart or fault index chart that is suggested by the actualcondition.
NOTE: This troubleshooting guide is not for 50A55-4XX modules found on Trane equipmentor50A55-1XXmodulesfoundonLennoxequipment.
FAULT INDEX CHARTNo manual fan ............................................ 1A - 1KPower supply and voltage .......................... 1C - 1GNo fan at cooling speed .............................. 2A - 2LNo induced draft motor ............................... 3A - 3HLEDflashing2Xwithoutinducer................. 3ELEDflashing3Xwithinducer...................... 3I - 3OIgnitor does not glow .................................. 4A - 4DBurner does not stay lit ............................... 4E - 4NGas supply problem.................................... 4F - 4KNo outlet pressure ...................................... 4H - 4JGas valve does not energize ...................... 4L - 4NFlame sensor fault ...................................... 5A - 5PBurner ground............................................. 5KPolaritycheck ............................................. 5L - 5MIgnitor stays on after burner ignition ........... 5B - 5C
TEC
HN
ICA
L H
ELP
www.white-rodgers.com 189
Placethermostat
fan switch inthe ON
position.
Return fanswitch to
AUTO position.
Indoor BlowerCheck
Does indoorblower run atHEAT speed?
YES
YES
NO
NO
YES
NO
YES
NO
YES
NO
Indoor blowerfault. Repair orreplace. Check
operation.
Is 24Vpresent at
controlterminalsG & C?
Is 120Vpresent at
control terminalsCOOL & CIRNEUTRAL?
Is 24Vpresent at
controlterminalsR & C?
Does LEDflash 1 time
when disconnectis turned
ON?
Is 120Vpresent across
primary of controltransformer?
Is 24Vpresent acrosssecondary oftransformer?
Is 24Vpresent
across 12-pinconnector pins TH
& TR on thecontrol?
Is 120Vpresent at
control terminalsXFMR & XFMR
NEUTRAL?
Is 120Vpresent across
control terminalsLINE & LINENEUTRAL?
Repair wiringfrom control to
thermostat. Checkoperation.
Repair wiringand/or plug
connection. Checkoperation.
Replacetransformer. Check
operation.
Repair wiring totransformer. Check
operation.
Correct 120Vpower supply. Check
operation.
Replace control.Check operation.
Replace control.Check operation.
1A 1B
1E1D1C 1F
1I1H1G 1J 1K
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
CHART 1
WARNING!If diagnostic indicator (LED)
shows continuous flashing, turn off gas supply at source before disconnecting electrical power!
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
www.white-rodgers.com190
TEC
HN
ICA
L H
ELP
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
Place thermostatsystem switch in
cooling mode and fanswitch in AUTOposition. Lower
temperature selectionlever to call for a
cooling cycle. R & Ycontacts close.
Return thermostatto desired
setting.
With doorswitch closed,jumper control
terminalsR & Y.
CoolingCycleCheck
Does indoorblower energize
at coolingfan speed?
YES
YES
NO
NO
YES
NO
YES
NO
Repair lowvoltage wiring to
thermostat. Checkoperation.
Doesindoor blowerenergize atcooling fan
speed?
Isthermostat terminal
Y connected to furnaceterminal Y?
Doesindoor blowerenergize atheating fan
speed?
Is 120V presentat primary oftransformer?
Is 24Vpresent at
control terminalsG & C?
Is 24Vpresent across
control terminalsY & C?
Replace control.Check operation.
Replacetransformer.
Check operation.
Repair wiringbetween control and
transformerprimary. Check
operation.
Correct 120Vpower supply tocontrol. Check
operation.
Repair lowvoltage wiring to
thermostat.Check operation.
Correct wiringfrom thermostat
terminal Y to Y onfurnace. Check
operation.
YESIndoor blowerfault. Repair orreplace motor.
Check operation.
NO
Is 120Vpresent at
control terminalsCOOL & CIRNEUTRAL?
2A 2B
2E2D2C 2F
2H
2K2J
2G
YES
NO
YESYES
YES
NO
NO
Is 120Vpresent at
control terminalsLINE & LINENEUTRAL?
2L
YES
Repair lowvoltage wiring
from transformer tocontrol. Check
operation.
NOIs 24V
present atcontrol terminals
R & C?
2I
NO
CHART 2
WARNING!If diagnostic indicator (LED)
shows continuous flashing, turn off gas supply at source before disconnecting electrical power!
TEC
HN
ICA
L H
ELP
www.white-rodgers.com 191
Inducer Draft Motorand
Pressure SwitchCheck
Is induceddraft motorenergized?
YES
YESNO
Is diagnosticLED flashing 3
times?
Call for heat.Thermostat
contactsR & W close.
Jumperpressureswitch.
Disconnectelectric power
at fuse orcircuit breaker.
Is pressureswitch welded
closed?
Correct blockedor incorrectlyinstalled vent.
Check operation.
Repair leaks ininducer assembly or
replace induceddraft motor. Check
operation.
Check inducerwiring. If OK,
repair or replaceinducer motor.
Check operation.
Replace pressureswitch. Energizesystem. Check
operation.
NO
YES
NO
NO
3A 3F
Is diagnosticLED flashing 2
times?
3B
3C
3D
3G
3H
3E
3I
3J
3L
YES
NO
Ispressure
greater thanpressure switch
specs?
YES
Replace pressureswitch. Check
operation.
NO
Ispressure
greater thanpressure switch
specs?
YES
YES
NODoes ignitorglow?
Test forcontinuity acrosspressure switch.
Place inclinemanometer in
series withpressure switch
tubing.
Remove ventconnector
from furnaceflue collar.
3K
CHART 3
WARNING!If diagnostic indicator (LED)
shows continuous flashing, turn off gas supply at source before disconnecting electrical power!
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
www.white-rodgers.com192
TEC
HN
ICA
L H
ELP
Main BurnerIgnition Check.
Inducer ON.
Does ignitorwarm up and
glow?
YES YES
NONO
Does burnerignite?
Turn power OFF to furnace.Unplug ignitor from wire
harness. Connect voltmeteracross ignitor wiringharness leads fromcontrol. Energize
system.
Turn manual knob toOFF position. Connectmanometer to outlet
pressure tap. Turn knobto ON position.
Energize system.
Is 120Vpresent at
control terminalsIGN & IGNNEUTRAL?
Replace controlmodule. Check
operation.
Replace gasvalve. Energizesystem. Check
operation.
NO
YES
NO
Repair orreplace broken
leads to gas valve.Check operation.
4A 4E
4B
YES
Is gasvalve manualknob in ONposition?
4F
4C
4G
4H
4K
4N
4I
4L
4M
YES
YES
Is 24Vdetected
across gasvalve leads after
ignitor warm-up time?
Is 24Vpresent
across controlMV terminals after
ignitor warm-up time?
Replace control.Check operation.
NO
YES
NO
Purge system ofair. Energize
system. Checkoperation.
Adjust manifoldto required
pressure setting.Check operation.
Restore gassupply at source.Check operation.
Replace ignitor.Check operation.
Replace broken ordefective wiring.Check operation.
NO NO
YES
Is outletpressure
detected afterignitor warm-
up time?
YES
Is gas atsource?
Is 120Vpresent at
ignitor leads?
4D
4JIs manifoldpressure
adjusted torequiredsetting?
YES
NO
Turn manual knobto ON position.
Check operation.
NO
Refer to servicefacts or installer’sguide for proper
pressure settings.
Connect voltmeterto gas valve
leads. Energizesystem.
CHART 4
WARNING!If diagnostic indicator (LED)
shows continuous flashing, turn off gas supply at source before disconnecting electrical power!
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
TEC
HN
ICA
L H
ELP
www.white-rodgers.com 193
FlameSensorCheck
Does mainburner remain
lit?
YES NO
YESNO
Is blowerat heat speed
within 1 minuteof burner ignition?
Does ignitor remainenergized withflame present?
De-energize system.Disconnect 12-pin
connector. Connectohmmeter from flame
sensor pin FP toburner GROUND.
Replace sensor.Energize system.Check operation.
NO
Replace control.Check operation.
YES
5A 5C5B
5E
5G
Disconnect flamesensor from wire.
Measure continuity fromwire end to FP pin
on 12-pin connector.
5IDisconnect AC power tosystem at main fuse orcircuit breaker. Connectvoltmeter from control
terminal LINE NEUTRALto BURNER GROUND.
Energize module.
5L
NO
NO
Is 120Vpresent at
control terminalsHEAT & CIRNEUTRAL?
5D
5K
5O
5H
YES
YES
Is resistanceless than
50 megohms?
Is 1 microampor morepresent?
Replace flamesensor lead. Check
operation.
NOYES
NO
Replace controlmodule. Check
operation.
Clean surface offlame sensor with
fine steel wool.Reinstall. Check
operation.
Reverse 120VLINE & NEUTRALwires. Energizesystem. Check
operation.
Repair orreplace wire.
Energize system.Check operation.
Connect groundwire from burner to12-pin connector
terminal GROUND.Check operation.
NOYES
YES
YES
Iscontrol
ground wireconnected to
burnerground?
5J
NO NO
Is sensorlead good?
Disconnect leadfrom flame sensor.Connect ohmmeter
from sensor toburner ground.
5NConnect a microammeter
in series with flamesensor and sensor
lead. Energize system.Measure current when
burner ignites.
5F
Is resistanceless than
50 megohms(50,000,000
Ohms)?
5M
Is 120Vpresent at
burner ground?
NO
5PRemovesensor.
Does sensorhave carbon ordust buildup?
YES
Repair wiringand/or replaceindoor blowermotor. Check
operation.
System isfunctioning
properly.
YES
CHART 5
WARNING!If diagnostic indicator (LED)
shows continuous flashing, turn off gas supply at source before disconnecting electrical power!
INTEGRATED FURNACECONTROL MODULE
TROUBLESHOOTINGGUIDE
www.white-rodgers.com194
TEC
HN
ICA
L H
ELP