© siemens ag 2010. all rights reserved. zone selective interlocking (zsi) functionality and...

5
© Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well Application Guide

Upload: mandy-cliff

Post on 11-Dec-2015

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: © Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well

© Siemens AG 2010. All Rights Reserved.

Zone Selective Interlocking (ZSI)

Functionality and Structure of ZSIFor short circuit and ground fault as well

Application Guide

Page 2: © Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well

© Siemens AG 2010. All Rights Reserved.

Industry SectorPage 2

ZSI

ZSI

ZSI

ZSI

ZSI

ZSI

tZSI = 50 ms

tsd = 200 ms

tsd = 300 ms

ZSI

ZSI

ZSI

ZSI

ZSI

tZSI = 50 ms

tsd = 300 ms

A) B)

Example: ZSI function in the event of a short-circuit

ZSI OUT

ZSI OUT

ZSI IN

ZSI IN

ZSI OUT

ZSI OUT

ZSI IN

ZSI OUT

ZSI

ZSI

Page 3: © Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well

© Siemens AG 2010. All Rights Reserved.

Industry SectorPage 3

ZSI

ZSI

ZSI

ZSI

ZSI

ZSI

tZSI = 100 ms

tg = 400 ms

tg = 500 ms

ZSI

ZSI

ZSI

ZSI

ZSI

tZSI = 100 ms

tg = 500 ms

A) B)

Example: ZSI function in the event of a ground fault

ZSI OUT

ZSI OUT

ZSI IN

ZSI IN

ZSI OUT

ZSI OUT

ZSI IN

ZSI OUT

ZSI

ZSI

Page 4: © Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well

© Siemens AG 2010. All Rights Reserved.

Industry SectorPage 4

tsd = 200 ms

ZSI

ZSI

ZSI

ZSI

ZSI

tZSI = 50 ms

tsd = 300 ms

Example: ZSI function in the event of a short-circuit

ZSI OUT

ZSI IN

ZSI OUT

tsd = 100 ms

ZSITrip

tsd = 0 ms

tsd = 100 msTrip

With ZSI and without ZSI function in grading level 3

1

2

3

Page 5: © Siemens AG 2010. All Rights Reserved. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSI For short circuit and ground fault as well

© Siemens AG 2010. All Rights Reserved.

Rainer HuentemeierProductmanagerI BT LV GC MCCB

V2.0 2010

Thank you for your attention!

Zone Selective Interlocking (ZSI)