[] off-line ups with zero transfer time using integrated magnetics{1989}[martínez;...]

Upload: mapo-mfa

Post on 02-Mar-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/26/2019 [] Off-line Ups With Zero Transfer Time Using Integrated Magnetics{1989}[Martnez;...]

    1/5

    IEEE TRANSACTIONSON INDUSTRIAL ELECTRONICS VOL. 36, NO. 3, AUGUST 1989

    44 1

    Off-Line Uninterruptible Power Supply with Zero

    Transfer Time Using Integrated Magnetics

    SALVADOR MARTiNEZ, MANUEL CASTRO, MEMBER,EEE,RAFAEL ANTORANZ, AND

    FERNAN DO ,&DANA, SENIOR MEMBER, IEEE

    Abstract-An off-line uninterruptible power supply UPS) r emer-

    gency power system with zero transfer time is presented. The power

    transformer, a tnport-like transformer, acts as an inverter and as a

    voltage stabiliz er with no external load ing coil. It has been mad e with

    commercial

    E l

    scrapless laminations. The battery charging circuit is also

    integrated into the transformer and improves the dynamic output

    response during line-mode operation. The result is a robust, short-circuit-

    proof equipment with a harmonic distortion

    of

    lower than

    3

    percent, a

    static output stab ility better than

    1.5

    percent, and

    a

    very high reliability.

    1. INTRODUCTION

    GREAT effort is being put forth nowadays to implement

    A mall and economic uninterruptible power supplies

    (UPSS ), mainly to feed personal compu ters and systems. The

    most commercialized economic solution is the off-line power

    supply in which the line is normally connected to the critical

    load,

    and when the line fails, an inverter is started and

    connected to the load. The transfer o peration is made with fast

    electromechanical relays resulting in a typical transfer tim e of

    5 ms.

    When no transfer tim e is allowed by the critical load, other

    solutions are available such as the classical rectifier-inverter-

    bypass UPS and the triport

    [

    11, [2].

    The operation of the triport demands an output voltage

    stabilizing device when operating in line m ode, and this d evice

    is made of a nonintegrated coil and a triac in phase-controlled

    working mode.

    This paper shows an off-line UPS with zero transfer time

    built over a triport transformer without an external stabilizing

    coil. In the line-mod e operation, the inverter coil of the triport

    is

    used to stabilize the output voltage, whereas in the battery-

    mode, that coil acts as the inverter primary, which stabilizes

    the output operating in one pulse width control. The change of

    the electrical topology is made of fast electromechanical relays

    with a typical response of 4-6 ms. T he energy stored in the

    output capacitor typically keeps the output wave transient

    between 15 percent of the nominal voltage. This careful

    transfer operation demands keeping the inverter control

    synchronized with the line at all times. In a general sen se, the

    main electromagnetic device can be seen as an integrated

    Manuscript received January 25, 1988; revised December 13, 1988.

    S .

    Martinez and M. Castro are with the Electronic and Control Department,

    R. Antoranz is with Coalba Engergia, Madrid, Spain.

    F. Aldana is with the Electronic Engineering Department, Universidad

    IEEE

    Log

    Number 8928461.

    Universidad Nacional de educaci6n a Distancia, Madrid, Spain.

    Politknica de Madrid, Madrid, Spain.

    magnetics compon ent (concept proposed as defined by

    S .

    Cuk

    (8)).

    A range of three equipm ent powers has been develop ed (500

    VA, lo00 VA, and 1500 VA) intended mainly for operation in

    low-quality utility areas.

    11 POWER IRCUIT

    The power circuit is showed in Fig. 1. With line voltage

    between 15 and 20 percent of the nominal value, relay RE1

    is closed, and relay RE2 is in position 1 , connecting the triac to

    the 8-9 coil of the transformer. The circuit acts as a line

    voltage stabilizer keeping the output voltage between

    k

    1.5

    percent in any static condition. The m agnetic shunts SH1 and

    SH2 are adjusted to obtain an impedan ce of 0 .333

    Zn

    and 0.4

    Zn (Zn = nominal impedance), respectively. Other lower

    values are possible for SHl in case of smaller line voltage

    tolerance, but it results in too high an output short circuit

    current (31 nominal for 0 .333 Zn in SH1 at nominal input

    voltage). Besides, a line failure (short circuit equivalent)

    affects the output voltage to a higher degree, while RE1 is still

    closed.

    The 0.4 Zn value for S H2 has been selected because of the

    results of previous work on inverters. Therefore, less than 3

    percent of total harmonic distortion in the output voltage in

    battery-mode can be obtained. This value also helps keep the

    first peak current in the transistor bridge, in case of output

    short circuit, under 200 percent of the repetitive peak at 100-

    percent load. The inverter control circuit reduces the static

    output short circuit current to 1.6

    In

    In

    =

    nominal output

    current) with the aid of the current transformer (CT).

    The LC output filter resonates to the third harmonic. The

    equivalent circuit at the fundamental frequency is a capacitor

    whose reactive power is 1.66 Pn Pn = nominal power),

    which was also selected because of previous work on

    inverters. The total harmonic distortion in line-mode is also

    less than 3 percent in any condition.

    It is worth while to ensure that, with the elected values for

    the leakage inductances and the o utput capacitor, the circuit is

    able to maintain the output voltage to within 1.5 percent of the

    nominal value in the limit situations that follow:

    Limit Case

    Line voltage 1.15 U ominal

    Output voltage