Page 1: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Annex 9 – Schedules of Guaranteed CharacteristicsKENYA - UGANDA INTERCONNECTION

400 kV DOUBLE CIRCUIT – LINE (OPERATED INITIALLY AS A 220 kV OHTL)

(Revision 2)

Page 2: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Table of Contents

Conductor............................................................................................................................................ 3

Steel Overhead Ground Wire..............................................................................................................4

Optic Overhead Ground Wire (OPGW)...............................................................................................5

Suspension Insulator String/Set........................................................................................................6

Tension Insulator String/Set...............................................................................................................7

Jumper Support Insulator String/Set.................................................................................................7

Transposition Suspension Insulator String/Set................................................................................8

Hardware and Fittings......................................................................................................................... 9

Suspension Clamps for Conductor....................................................................................................9

Suspension Clamps for GSW.............................................................................................................9

Suspension Clamps for OPGW..........................................................................................................9

Tension Clamps for Conductor (Full Tension)................................................................................10

Tension Clamps for GSW (Full Tension).........................................................................................10

Tension Clamps for OPGW...............................................................................................................10

Arcing Horns...................................................................................................................................... 10

Joint Sleeves (Full Tension).............................................................................................................11

Joint Boxes and Splices for OPGW.................................................................................................11

Terminations for OPGW.................................................................................................................... 11

Armour Rods for Conductor.............................................................................................................12

Armour Rods for GSW...................................................................................................................... 12

Armour Rods for OPGW.................................................................................................................... 12

Repair Sleeve for Conductor............................................................................................................13

Repair Sleeve for GSW...................................................................................................................... 13

Repair Sleeve for OPGW................................................................................................................... 13

Spacers............................................................................................................................................... 14

Vibration Dampers for Conductor....................................................................................................14

Vibration Dampers for GSW..............................................................................................................14

Vibration Dampers for OPGW...........................................................................................................15

Hold Down Weights........................................................................................................................... 15

Aviation Warning Devices................................................................................................................. 15

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 2 of 16

Page 3: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 3 of 16

Page 4: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Conductor

Description Unit Requested Provided

Manufacturer

TypeAAAC

All Aluminum Alloy Conductor

Code Word FLINT

Standard ASTM B 399IEC 61089

Construction:

a) Aluminium wires No. 37b) Aluminium wire diameter mm 3.59

c) Aluminium alloy round aluminum-alloy 6201-T81

Total Sectional Area: mm2 375.5 Overall diameter: mm 25.17 Unit weight: N/m 10.15

kg/km 1028

Rated strength (ultimate tensile strength): kN 108.54 Modulus of elasticity:

Initial, minimum kN/mm2 46.2 Initial, maximum kN/mm2 55.8 Final kN/mm2 60.7

Coefficient of linear expansion: x10-6/°C 23.04 Direction of outermost layer Right (z) Every day stress N/mm2 70 Current rating at 25°C ambient: kA 790 DC resistance at 20°C: Ω/km 0.0892 Aluminium wire minimum conductivity at 20°C % IACS 52.5%

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 4 of 16

Page 5: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Steel Overhead Ground Wire

Description Unit Requested Provided

Manufacturer

Type GSW 70

Standard ASTM A 363IEC 60888

Material Galvanized steel Coating Zinc coating Minimum zinc coating weight

Construction No. of wires per strand 7 Nominal wire diameter 3.68 Helical form concentric left lay

Total Area: mm2 97 Overall diameter: mm 11.11 Unit weight: kg/km 595 Ultimate tensile strength (minimum): kN 88 Every day stress N/mm2 180 Galvanised steel wire minimum tensile strength N/mm2 1314 Galvanised steel wire minimum elongation in

250mm % 1.0

Galvanised steel wire minimum stress at 1% elongation N/mm2 1200

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 5 of 16

Page 6: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Optic Overhead Ground Wire (OPGW)

Description Unit Required ProvidedProperties of optical fibers contained inside OPGW cableManufacturer

Material Silica

Index profile Single-mode NZDS

Standard ITU-T G.655

Number of fiber glass cores 96

Concentricity error at 1550m (core to cladding) μm < 1

Cladding diameter μm 125 ±1

Mode field diameter at 1550 nm (MFD) μm 8 – 11 ± 0.6

Attenuation at wave length 1550 nm dB/km < 0.25

Attenuation at wave length 1625 nm dB/km < 0.27

Chromatic dispersion at W.L. 1530 to 1565 nm ps/(nm.km) 2.0 – 6.15

Chromatic dispersion at W.L. 1565 to 1625 nm ps/(nm.km) 4.5 – 12.4

Polarization Mode Dispersion (PMD) ps/sqrt km < 0.5

Average splicing loss dB/joint 0.05

Maximum splicing loss dB/joint 0.10

Construction and properties of OPGW cableManufacturer

International Standards IEEE 1138IEC 60793

IEC 60794-4

Material of conductor Aluminum clad steel wireIEC 61232

Number and diameter of wires No./ mm

Conductor overall diameter, nominal mm 21

Tolerance of overall diameter %

Cross-section area, total mm²

Stranding direction (outer layer) Right-hand

Standard mass kg/km < 820

Rated Ultimate Tensile Strength (UTS), IEEE 1138 kN > 85

Maximum recommended load kN

Every day stress (20% UTS) N/mm2

Maximum load in worst climatic condition (40% UTS) N/mm2

Standard resistance at 20 ºC Ω/km

Minimum short circuit current capacity (0.5 sec) kA 31.5 (min. 496 kA2s)

DC resistance at 20°C Ω/km 0.15

Operating temperature ºC -30 to + 70

Minimum bending radius mm

Minimum length of conductor on drum km 4

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 6 of 16

Page 7: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Suspension Insulator String/SetSuspension Composite Insulator String/Set (note 1)

Description Unit Requested Provided

Applicable voltage (maximum system voltage) kV 420

Overall length of set, including all fittings mm < 4500

Creepage path per string (leakage distance) mm 8400

Dry power frequency withstand voltage kV 900

Wet power frequency withstand voltage (1 min.) kV 710

Dry lightning impulse withstand voltage kV 1060

Corona test voltage kV 290

Radio noise level, insulator set dB 45

Short circuit current capacity, any part of insulator set (0.5 sec)

kA 31.5

Mechanical failing load, single insulator string kN 1 x 120

Overall weight, single insulator string kg

Mechanical failing load, double insulator string kN 2 x 120

Overall weight, double insulator string kg

Note 1: Electrical values to be given for insulator equipped with required arcing rings.

Suspension Composite Insulator (note 1)

Description Unit Requested Provided

Manufacturer

TypeLong rod, composite

ANSI Class or IEC C29.11/ C29.12

Material, weathersheds and housing Material, core

silicone rubberFRP (fiberglass

reinforced plastic)

Grading rings Applied, line end and ground end

Overall length mm < 3900

No. of sheds (large/ small) /

Ball and socket size (IEC 60120) mm

Weight kg

Arcing gap mm 3300

Creepage path (leakage distance) mm 8400

Mechanical failing load kN 120

Mechanical routine test load kN 60

Power frequency flashover (dry) kV 1150

Power frequency flashover (wet) kV 1050

Critical Impulse Flashover voltage, positive kV 2050

Critical Impulse Flashover voltage, negative kV 2150

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 7 of 16

Page 8: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Tension Insulator String/SetTension Composite Insulator String/Set (note 1)

Description Unit Requested Provided

Applicable voltage (maximum system voltage) kV 420

Number of insulators per string 3

Mechanical failing load kN 3 x 120

Overall length of set, including all fittings mm < 4500

Creepage path per string (leakage distance) mm 8400

Dry power frequency withstand voltage kV 900

Wet power frequency withstand voltage (1 min.) kV 710

Dry lightning impulse withstand voltage kV 1060

Corona test voltage kV 290

Radio noise level, insulator set dB 45

Short circuit current capacity, any part of insulator set (0.5 sec)

kA 31.5

Overall weight, complete insulator string kg

Note 1: Electrical values to be given for insulator equipped with required arcing rings.

Tension Composite Insulator (note 1)

Description Unit Requested Provided

Manufacturer

TypeLong rod, composite

ANSI Class or IEC C29.11/ C29.12

Material, weathersheds and housing Material, core

silicone rubberFRP (fiberglass

reinforced plastic)

Grading rings Applied, line end and ground end

Overall length mm < 3900

No. of sheds (large/ small) /

Ball and socket size (IEC 60120) mm

Weight kg

Arcing gap mm 3300

Creepage path (leakage distance) mm 8400

Mechanical failing load kN 120

Mechanical routine test load kN 60

Power frequency flashover (dry) kV 1150

Power frequency flashover (wet) kV 1050

Critical Impulse Flashover voltage, positive kV 2050

Critical Impulse Flashover voltage, negative kV 2150

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 8 of 16

Page 9: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Jumper Support Insulator String/Set

Description Unit Requested Provided

Applicable voltage (maximum system voltage) kV 420

Number of insulators per string 1

Mechanical failing load kN 1 x 120

Overall length of set, including all fittings mm < 4500

No. of sheds (large/ small) /

Ball and socket size (IEC 60120) mm

Creepage path per string (leakage distance) mm 8400

Dry power frequency withstand voltage kV 900

Wet power frequency withstand voltage (1 min.) kV 710

Dry lightning impulse withstand voltage kV 1060

Corona test voltage kV 290

Radio noise level, insulator set dB 45

Short circuit current capacity, any part of insulator set (0.5 sec)

kA 31.5

Overall weight, complete insulator string kg

Note 1: Electrical values to be given for insulator equipped with required arcing rings.

Transposition Suspension Insulator String/Set

Description Unit Requested Provided

Applicable voltage (maximum system voltage) kV 420

Number of insulators per string 1

Mechanical failing load kN 1 x 120

Overall length of set, including all fittings mm < 4500

No. of sheds (large/ small) /

Ball and socket size (IEC 60120) mm

Creepage path per string (leakage distance) mm 8400

Dry power frequency withstand voltage kV 900

Wet power frequency withstand voltage (1 min.) kV 710

Dry lightning impulse withstand voltage kV 1060

Corona test voltage kV 290

Radio noise level, insulator set dB 45

Short circuit current capacity, any part of insulator set (0.5 sec)

kA 31.5

Overall weight, complete insulator string kg

Note 1: Electrical values to be given for insulator equipped with required arcing rings.

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 9 of 16

Page 10: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Hardware and FittingsGenerally the composition of insulator hardware shall be of that specified in the drawings, but not limited thereto, and the ultimate strength of the hardware for tension insulator strings shall be not less than 360 kN, and for single suspension and double suspension strings not less than 120 kN and 240 kN respectively.

Suspension Clamps for Conductor

Description Unit Requested Provided

Material of body Aluminium

Applied conductorFLINT

(AAAC)

Ultimate body strength kN 11.5

Armour rods Applied

Galvanising, if applicable BS 729

Suspension Clamps for GSW

Description Unit Requested Provided

Material of body Steel

Applied conductor GSW 70

Ultimate body strength kN 7.5

Armour rods Not applicable

Galvanising, if applicable BS 729

Suspension Clamps for OPGW

Description Unit Requested Provided

Material of body Steel

Applied conductor OPGW 96

Ultimate body strength kN 7.0

Armour rods Applied

Galvanising, if applicable BS 729

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 10 of 16

Page 11: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Tension Clamps for Conductor (Full Tension)

Description Unit Requested Provided

Type Compression

Material of body Aluminium

Applied conductorFLINT

(AAAC)

Ultimate breaking strength kN 82.7

Galvanising, if applicable BS 729

Tension Clamps for GSW (Full Tension)

Description Unit Requested Provided

TypeBolted or

Compression

Material of body Steel

Applied conductor GSW 70

Ultimate breaking strength kN 85

Galvanising, if applicable BS 729

Tension Clamps for OPGW

Description Unit Requested Provided

Type Preformed dead-end

Material of body Steel

Applied conductor OPGW 96

Ultimate breaking strength kN 44.7

Galvanising, if applicable BS 729

Arcing Horns

Description Unit Requested Provided

Type

Material of body Steel

Mechanical load withstand kN 1.5

Galvanising, if applicable BS 729

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 11 of 16

Page 12: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Joint Sleeves (Full Tension)

Description Unit Requested Provided

For conductor tensile strength kN 82.7

For GSW tensile strength kN 85

Joint Boxes and Splices for OPGW

Description Unit Requested Provided

Optical losses dBNo more than 0.1 db

per splice, average 0.05 db

Terminations for OPGW

Description Unit Requested Provided

Optical losses dBNo more than 0.1 db

per splice, average 0.05 db

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 12 of 16

Page 13: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Armour Rods for Conductor

Description Unit Requested Provided

Type Helical preformed

Material Aluminium alloy

Applied conductorFLINT

(AAAC)

Colour code

Rod diameter mm

Direction of lay

Length mm

Number of rods No

Armour Rods for GSW

Description Unit Requested Provided

Type Helical preformed

Material Aluminium alloy

Applied conductor GSW

Colour code

Rod diameter mm

Direction of lay

Length mm

Number of rods No

Armour Rods for OPGW

Description Unit Requested Provided

Type Helical preformed

MaterialAnti-corrosion

Aluminium alloy

Applied conductor OPGW 96

Colour code

Rod diameter mm

Direction of lay

Length mm

Number of rods No

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 13 of 16

Page 14: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Repair Sleeve for Conductor

Description Unit Requested Provided

Type Compression

Material Aluminium alloy

Applied conductorFLINT

(AAAC)

Length mm

Repair Sleeve for GSW

Description Unit Requested Provided

Type Compression

Material Aluminium alloy

Applied conductor GSW

Length mm

Repair Sleeve for OPGW

Description Unit Requested Provided

Type Helical preformed

MaterialAnti-corrosion

Aluminium alloy

Applied conductor OPGW 96

Length mm

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 14 of 16

Page 15: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Spacers

Description Unit Requested Provided

Type Cushion - grip Material of body Aluminium/ rubber

Applied conductorFLINT

(AAAC) Thermal rating (continuous) °C 125 Slip strength kN 12.3 Galvanising, if applicable BS 729

Vibration Dampers for Conductor

Description Unit Requested Provided

Type Clamp-grip Material of body Galvanized Steel

Applied conductorFLINT

(AAAC) Thermal rating (continuous) 125 Slip strength Galvanising, if applicable BS 729

Vibration Dampers for GSW

Description Unit Requested Provided

Type Clamp-grip Material of body Galvanized Steel Applied conductor GSW 70 Thermal rating (continuous) 125 Slip strength Galvanising, if applicable BS 729

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 15 of 16

Page 16: Web viewDry power frequency withstand voltage. kV. 900. Wet power frequency withstand voltage ... Ball and socket size (IEC 60120) mm. Creepage path per string (leakage

Nile Basin Initiative – Nile Equatorial Lakes Subsidiary Action ProgramInterconnection of Electric Grids of Nile Equatorial Lakes CountriesTender Documents – Lot A: 400 kV Transmission Line for Kenya-Uganda Power Interconnection (Lessos – Uganda Border)

Vibration Dampers for OPGW

Description Unit Requested Provided

Type Clamp-grip Material of body Aluminium alloy Applied conductor OPGW 96 Thermal rating (continuous) 125 Slip strength Galvanising, if applicable BS 729

Hold Down Weights

Description Unit Requested Provided

Type

Material of bodyCast iron hot dip

galvanized

Applied conductorFLINT

(AAAC)

Galvanising, if applicable BS 729

Aviation Warning Devices

Description Unit Requested Provided

Type

Day marking sphere approved by ICAO

and CAA

Material of sphereFibre reinforced polyester (FRP)

Material of clamp Aluminium/steel

Diameter mm 600

Colour code

Applied conductor GSW 70

Colour of sphere White/red

Fade resistant kN 6.4

Slip strength No

Galvanising, if applicable BS 729

Part 2 : Section VI – Employer’s RequirementsAnnex 9 – Schedule of Guaranteed Characteristics, 400kV Line, rev 2 Page 16 of 16