© 2002 eaton corporation. all rights reserved. interface cabling options for 9910-p13 & p14 ups...
TRANSCRIPT
![Page 1: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/1.jpg)
© 2002 Eaton Corporation. All rights reserved.
Interface Cabling Options for 9910-P13 & P14 UPS
i5-iSeries and p5-pSeriesand Windows
Selecting Which Interface (Communication) Option is Best for You
![Page 2: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/2.jpg)
2
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Receiving the UPS
UPS will be installed on floor Connections that need to be completed
Power• UPS to utility (mains)
• UPS to Devices
Interface (communications)• UPS to server(s)
![Page 3: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/3.jpg)
3
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Getting Acquainted
UPS must installed near devices to be protected• Communication and power connections made at rear of UPS
What a P13 and P141 UPS looks like from the rear
P13
P14
1 P14 includes three (3) IEC-320-C13 toIEC-320-C14 1.8 m power cords
![Page 4: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/4.jpg)
4
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Communication Options
Software Suite AS/400 InterfaceApplication CD & Serial Cable Cable
IBM i5/iSeriesServer - X
IBM p5/pSeries, OpenPoweror xSeries Server with SingleSerial (TTY) connection X -
IBM p5/pSeries, OpenPoweror xSeries Server and/or Network(WebServer) connection(UPS as a node) X -
IBM p5/pSeries, OpenPowerwith Logical Partitions (LPARs) Not Supported
![Page 5: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/5.jpg)
5
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
i5 Interface Overview
To connect the UPS to an i5 you need:
A Powerware-supplied interface cable (labeled 05146792)
An IBM-supplied interface cable (labeled 1827), included with the server
Connect the cables as shown in Figure 1
![Page 6: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/6.jpg)
6
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
iSeries Interface Overview
To connect the UPS to an iSeries or AS/400 you need:
A Powerware-supplied interface cable (labeled 05146792)
Connect the cable as shown in Figure 2
![Page 7: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/7.jpg)
7
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
UPS Monitoring on the i5, iSeries and AS/4001. Set the QUPSDLYTIM system value for the UPS monitoring
feature.
2. UPS monitoring is a standard feature of the i5-iSeries-AS/400 operating system. QUPSDLYTIM is a time that tells the system how long to run on UPS power before shutting down. Each system is initially assigned a default value for QUPSDLYTIM. A complete description of QUPSDLYTIM is proved on the AS/400 Information Center
Internet Site at: http://publib.boulder.ibm.com/pubs/html/as400ic2924/info/index.htm Select System Administration and MaintenanceCAUTION
The *NOMAX value tells the AS/400 to use customized shutdown software, and if non is available it will begin shutdown immediately when utility power fails.
![Page 8: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/8.jpg)
8
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Serial (TTY) Interface Overview To serially (TTY) connect the UPS to a p5, pSeries, RS/6000,
OpenPower, or other system you need: A Powerware-supplied serial interface cable (labeled 60420064-002 or
124102022), included with the UPS Powerware LanSafe Power Management Software from the Software
Suite CD, included with the UPS
For p5 installations you also need: An IBM-supplied 2-port Asynchronous EIA adapter (FC 5723) installed
(the pSeries does not require an EIA adapter) An IBM-supplied maintenance package 5200-05 for AIX 5.2L V5.2
(APAR IY66260); or, the maintenance package 5300-01 for AIX 5.3L V5.3 (APAR IY62267)
Follow the software installation instructions contained on the Software Suite CD to install LanSafe Software.
Connect the serial cable as shown in Figure 3
![Page 9: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/9.jpg)
9
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Serial (TTY) Interface Overview
![Page 10: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/10.jpg)
10
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
p5 or pSeries with LPARs
The UPS does not support Logical Partitions. LPARs are supported on UPS models 9910-P22, P23, P30, P33, P64 or P65 with the ConnectUPS X-Slot Web/SNMP Card (FC 2934)
![Page 11: © 2002 Eaton Corporation. All rights reserved. Interface Cabling Options for 9910-P13 & P14 UPS i5-iSeries and p5-pSeries and Windows Selecting Which Interface](https://reader036.vdocuments.site/reader036/viewer/2022072014/56649eb35503460f94bbac35/html5/thumbnails/11.jpg)
11
9910-UPS Training
Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Completing Start-Up
You have finished the power and connectivity installation process
Continue with Start-up instructions in User’s Manuals
Questions? Contact: The local IBM office supporting your account Eaton Power Quality Global Services