xlpe cable amps rating

38
X XL PR F W E XL LPE Insula RODU Federal Pow Lot 8, Jln Rag 40702 S W Tel (603 Fax Website: http:// Email: commer Designed b LP ated Pow UCT CA wer Sdn Bhd gum 15/17, P.O Shah Alam, Sel West Malaysia 3) 5518 3600/6 (603) 5512 27 (603) 5519 80 /www.federalpo rcial@federalpo by : Information Sy PE wer Cables ATALO d (17892 -V) O.Box 7016 langor 601/602 730 020 ower.com.my ower.com.my ystems Dept s OG FEDERAL L POWER TM

Upload: uthaya-kumar

Post on 03-Oct-2014

579 views

Category:

Documents


16 download

TRANSCRIPT

Page 1: Xlpe Cable Amps Rating

X XL

PR

F

WE

X LLPE Insula

RODU

Federal PowLot 8, Jln Rag

40702 SW

Tel (603Fax

Website: http://Email: commer

Designed b

L Pated Pow

UCT CA

wer Sdn Bhdgum 15/17, P.OShah Alam, SelWest Malaysia3) 5518 3600/6 (603) 5512 27 (603) 5519 80

/www.federalporcial@federalpo

by : Information Sy

P Ewer Cables

ATALO

d (17892 -V) O.Box 7016 langor

601/602 730 020 ower.com.my ower.com.my

ystems Dept

s

OG

FEDERALL POWERTM

Page 2: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY

1

Conductor

Conductor shelding

(Semi-conducting layer) Insulation

Insulation shielding

(Semi-conducting layer) Metallic shielding

Fillers

Binder tape

Outer sheath

Conductor

Insulation Fillers

Binder tape

Outer sheath

Conductor

Insulation Fillers

Binder tape

Separation sheath

Steel wire armour

Outer sheath

Conductor

Conductor shielding (Semi-conducting layer) Insulation Insulation shielding (Semi-conducting layer)

Metallic shielding Fillers

Binder tape

Separate sheath

Steel wire armour

Outer sheath

600/1000V XLPE/PVC Power Cable

3.6/6-18/30 kV XLPE/PVC Power Cable

600/1000V XLPE/SWA/PVC Power Cable 3.6/6-18/30 kV XLPE/SWA/PVC Power Cable

Notes: SWA : Steel wire armoured

CONSTRUCTION XLPE

Single core Three core

Page 3: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY

2

CONSTRUCTION XLPE

Conductor; Hard drawn aluminium

Conductor shielding Insulation: XLPE Insulation shielding Metallic shielding: Copper tape Fillers Binder tape Bedding: Black polyethylene Armour : Galvanized steel wire

Outer sheath: Black polyethylene

Conductor Conductor shielding Insulation Insulation shielding Metallic shielding Binder tape Sheath: Black HDPE Messenger wire : Galvanized steel wire

11kV up to 33kV AI-XLPE/SWA/PE Cable

11kV up to 33kV AI-XLPE/PE Aerial Cable

Page 4: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 3

CONSTRUCTION XLPE

Conductor: Hard drawn aluminium, sector shape Insulation: XLPE

Fillers: Polypropylene yarn Binder tape: Plastic tape Bedding: Black polyethylene Armour: Galvanized steel wire Outer sheath: Black-termite repellent polyethylene

Core identification : Core identification shall be made by coloured insulation compound. Cable identification : Outer sheath shall be embossed.

Conductor : Hard drawn aluminium

Conductor shielding Insulation : XLPE

Insulation shielding: Metallic shielding: Annealed copper tape Sheath: Black HDPE Messenger wire: Galvanized steel wire

Conductor: Hard drawn aluminium

Conductor shielding Insulation: XLPE Insulation shielding Metallic shielding Fillers: Polypropylene yarn Binder tape Bedding: Black polyethylene Armour: Galvanized steel wire Binder tape Outer Sheath: Black termite repellent polyethylene

Cross-section of 11 kV up to 33 kV AI-XLPE/SWA/PE Cable

Cross-section of 11 kV up to 33 kV AI-XLPE/PE Aerial Cable

Cross-section of 600/1000 V AI-XLPE/SWA/PE Cable

Page 5: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 4

XLPE 11kV up to 161kV XLPE/PE Cable with Copper wire screen

CONDUCTOR (Copper or aluminium)

CONDUCTOR SHIELD

INSULATION (XLPE)

INSULATION SHIELD

SWELLABLE TAPE

BINDING TAPE

OUTER SHEATH

METALLIC SCREEN (Copper wires)

Page 6: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 5

XLPE 11kV up to 132kV XLPE/LC/PE or PVC cable with lead sheathed

CONDUCTOR (Copper or aluminium)

CONDUCTOR SHIELD

INSULATION (XLPE)

INSULATION SHIELD

LEAD SHEATH

OUTER SHEATH

Page 7: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 6

XLPE 11kV up to 132kV XLPE/AWA/PE or PVC cable with Aluminium wire screen

CONDUCTOR (Copper or aluminium)

CONDUCTOR SHIELD

INSULATION (XLPE)

INSULATION SHIELD

SWELLABLE TAPE

BINDING TAPE

OUTER SHEATH

METALLIC SCREEN (Aluminium wires)

Page 8: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 7

CONTINUOUS CURRENT CARRYING CAPACITY The tabulated current rating have been calculated in accordance with IEC 287. They are for single circuit with the standard conditions as follow:- i) Maximum permissable conductor temperature at continuous operation is 90 deg. C ii) Ground temperature is 25 deg.C iii) Ambient temperature is 40 deg.C iv) Ground thermal resistivity is 1.2 Km/W v) Cables laying depth is ground:-

- cable’s voltage up to 1kV……500mm - cable’s voltage above 1kv……800mm

vi) Spacing between cables:- -In flat formation…….2 times of the cable overall diameter. -In trefoil formation….cables touching. vii) Cable’s sheath or armour solidly bonded at both ends viii) Cables shielded from direct sun rays For conditions of operation different from those on which the continuous current carrying capacity tables are based, ratings can be determined by application of “Rating Factor” in table below.

Rating Factor

Rating Factor For Cables In Air

Ambient air temperature 10 15 20 25 30 35 40 45 50 55 60

Rating Factor 1.26 1.22 1.18 1.14 1.10 1.05 1.00 0.95 0.89 0.84 0.78

Rating Factor For Ground Temperature

Ground temperature 10 15 20 25 30 35 40 45 50 55 60

Rating Factor 1.11 1.07 1.04 1.00 0.96 0.92 0.88 0.83 0.78 0.73 0.68

Rating Factor For Thermal Resistivity of Ground

Conductor size (mm2) Thermal Resistivity (K.m/W)

0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0

Single Core Cable Up to 150 From 185 to 400 From 500 to 1200 Multicore cables Up to 16 From 25 to 150 From 185 to 400

1.16 1.17 1.18 1.09 1.14 1.16

1.11 1.12 1.13 1.06 1.10 1.11

1.07 1.07 1.08 1.04 1.07 1.07

1.0 1.0 1.0 1.0 1.0 1.0

0.91 0.90 0.90 0.95 0.93 0.92

0.81 0.80 0.79 0.86 0.84 0.82

0.73 0.72 0.71 0.79 0.76 0.74

0.67 0.66 0.65 0.74 0.70 0.68

Rating Factor For Depth of Laying

Depth of laying (m)

0.6 / 1 kV cables 1.9 / 3.3 kV to 19 / 33 kV cables

up to 50mm2 70mm2 to 300m2 above 300mm2 up to 300mm2 above 300mm2

0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.0 or more

1.00 0.99 0.97 0.95 0.94 0.93 0.92 0.91 0.90 0.89

1.00 0.98 0.96 0.94 0.92 0.91 0.89 0.88 0.87 0.86

1.00 0.97 0.94 0.92 0.90 0.89 0.87 0.86 0.85 0.83

- - 1.00 0.98 0.96 0.95 0.94 0.92 0.91 0.90

- - 1.00 0.97 0.95 0.94 0.92 0.90 0.89 0.88

XLPE Technical Data

Page 9: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 8

Derating Factors for groups of cables installed in air

Number vertically 1 2

Number of cable horizontally 1 2 3 6 7-20 2 3 4 5 6 7 8-20

Spacing S = d S = 2d S = 3d

1.00 1.00 1.00

0.85 0.95 1.00

0.80 0.95 1.00

0.70 0.80 0.95

0.70 0.80

-

0.70 0.90 0.95

0.60 0.90 0.95

0.60 0.85 0.90

0.56 0.73

-

0.53 0.72

-

0.51 0.71

-

0.50 0.70

-

Number vertically 3 Number of cables horizontally 3 4 5 6 7 8 9-10 11-12 13-15 16-19 20 N/A

Spacing S = d S = d2 S = 3d

0.48 0.80 0.85

0.41 0.80 0.85

0.37 0.68

-

0.34 0.66

-

0.32 0.65

-

0.31 0.65

-

0.30 0.64

-

0.30 0.63

-

0.30 0.62

-

0.30 0.61

-

0.30 0.60

-

Number vertically

Derating Factors for groups of cables laid direct in ground

Cable Voltage

(kV)

Number of

circuit

Spacing of circuit (between centres of cables groups) Touching

0.15m* 0.3m 0.45m 0.6m Trefoil Laid flat

0.6/1

2 3 4 5 6

0.77 0.66 0.59 0.55 0.52

0.80 0.68 0.63 0.58 0.56

0.82 0.72 0.67 0.63 0.60

0.88 0.79 0.75 0.72 0.70

0.90 0.83 0.81 0.78 0.77

0.93 0.87 0.85 0.83 0.82

1.9/3.3 to 12.7/22

2 3 4 5 6

0.78 0.66 0.60 0.55 0.52

0.80 0.69 0.63 0.58 0.55

0.81 0.71 0.65 0.61 0.58

0.85 0.76 0.72 0.68 0.66

0.88 0.80 0.76 0.73 0.72

0.90 0.83 0.80 0.77 0.76

19/33

2 3 4 5 6

0.79 0.67 0.62 0.57 0.54

0.81 0.70 0.65 0.60 0.57

0.81 0.71 0.65 0.60 0.57

0.85 0.76 0.72 0.68 0.66

0.88 0.80 0.76 0.73 0.72

0.90 0.83 0.80 0.76 0.76

* This spacing will not be possible for some of the larger diameter cables.

Derating Factors for groups of cables laid direct in ground

Cable Voltage

(kV)

Number Of

circuits

Spacing of circuits (between centres of cable groups)

Touching 0.15m* 0.3m 0.45m 0.6m

0.6/1

2 3 4 5 6

0.81 0.70 0.63 0.59 0.55

0.87 0.78 0.74 0.70 0.67

0.91 0.84 0.81 0.78 0.76

0.93 0.87 0.86 0.83 0.82

0.94 0.90 0.89 0.87 0.86

1.9/3.3 to 12.7/22

2 3 4 5 6

0.80 0.69 0.63 0.57 0.55

0.85 0.75 0.70 0.66 0.63

0.89 0.80 0.77 0.73 0.71

0.90 0.84 0.80 0.78 0.76

0.92 0.86 0.84 0.81 0.80

19/33

2 3 4 5 6

0.80 0.70 0.64 0.59 0.56

0.83 0.73 0.68 0.63 0.60

0.87 0.78 0.74 0.70 0.68

0.89 0.82 0.78 0.75 0.74

0.91 0.85 0.82 0.79 0.78

* This spacing will not be possible for some of the larger diameter cables.

Number of cables horizontally

d S

SS+

+ +

+ +

+

XLPE Group Derating Factors

Multiple circuits

Three single core cables in trefoil and laid flat touching, horizontal formation

Multicore cables in horizontal formation

Page 10: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 9

1. Minimum bending radius and permissible maximum pulling tension.

For safety installation without damaging electrical and physical properties, the following minimum bending radius and permissible maximum pulling tension must be observed.

Minimum bending radius D: Overall dia. Of cable

Number of core

Type of cable

Single core Multi core

Round conductor Four segmental stranded conductor

600 V cable 10D 12D 8D

3,300 V cable and higher 10D 12D 8D

Triplex type cable - - 8D

Corrugated metal armoured cable 10D 12D 8D

Flat tape armoured cable 10D 12D 8D

Wire armoured cable 10D 12D 10D

Lead sheathed cable 10D 12D 10D

Permissble maximum pulling tension

Pulling tool Material of conductor Permissible maximum pulling tension (kg)

Pulling eye

Copper 7 x (Number of core) x (Core-sectional area of conductor)

Aluminium 4 x (Number of core) x (Core-sectional area of conductor)

Cable grip Copper & aluminium

The same as using the pulling eye, but the minimum tension should be less than two tons

Note : When cable grip is used it should cover more than 500 mm in length of end be bound to the cable sheath. 2. Side wall pressure to cable 3. Removal of sheath or tape Special care must be taken not to harm the insulation

Permissible maximum side wall pressure to the cable at when removing the sheath or tapes with knife otherwise bending point during installation is 500 kg/m. it may results in a dielectric breakdown. Note : pulling tension (kg) = T 4. Cleaning the surface of insulation Side wall pressure to cable The surface of insulation should be cleaned to avoid a

bending radius (m) R flash over at the cable termination or joint. 5. Applying of self-adhesive tape When applying a self-adhesive tape after joint or terminating of XLPE cable, stretch it properly about 1.2 times as long as the original one. If it is over-stretched crack may occur on the tape will not be adhered between each layer. 6. Water proof treatment for out-door termination For out-door termination water proof treatment is necessary to avoid the water penetrating into the cable end and special care must be taken to apply tapes and terminals. It is desirable to use a compression to solder type terminal.

Handling and installation of XLPE cable

XLPE

T : Pulling tension (kg) R : Bending Radius (m)

R

T

Side wall pressure

Page 11: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 10

For Aluminium and Copper Conductor

600/1000 V XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core

Nominal Shape thickness Thickness Approximate Approx. Approx. cross sectional Diameter of of overall cable weight weight

area sheath sheath diameter (Cu) (AL) sqmm mm mm mm mm kg/km kg/km

16 4.7 0.7 1.5 16 400 300 25 5.9 0.9 1.5 17 510 350 35 7.0 0.9 1.5 19 630 400 50 8.0 1.0 1.6 20 790 470 70 9.7 1.1 1.6 21 1010 570 95 11.4 1.1 1.7 23 1280 680

120 Compact 12.8 1.2 1.8 25 1540 790 150 round 14.3 1.4 1.8 26 1860 910 185 stranded 15.8 1.6 1.9 28 2210 1050 240 18.3 1.7 1.9 31 2790 1280 300 20.5 1.8 2.0 34 3420 1530 400 23.3 2.0 2.1 37 4430 1550 500 26.4 2.1 2.3 41 5460 2300 630 30.2 2.4 2.4 45 6760 2780 800 34.8 2.6 2.6 50 8450 3400

1000 39.0 2.8 2.7 54 10410 4100

600/1000V Multi-core XLPE/PE Power Cable, Type XLPE/PE Conductor Nominal Three core Four core

Nom. Cross Thickness Thickness Approx. Approx. Approx. Thickness Approx. Approx Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (copper) (alu) sheath diameter (copper) (alu) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 0.7 1.8 18 670 360 1.8 19 890 480 25 5.9 0.9 1.8 22 990 510 1.8 23 1320 670 35 7.0 0.9 1.8 24 1320 640 1.8 26 1750 850 50 8.0 1.0 1.8 27 1810 840 1.8 29 2370 1080 70 9.7 1.1 1.9 31 2450 1100 2.0 34 3230 1430 95 11.4 1.1 2.0 35 3220 1390 2.1 38 4260 1820

120 Compact 12.8 1.2 2.1 38 4000 1690 2.3 43 5320 2230 150 round 14.3 1.4 2.3 43 5000 2070 2.4 47 6590 2730 185 stranded 15.8 1.6 2.4 47 6070 2500 2.6 52 8070 3310 240 18.3 1.7 2.6 53 7780 3150 2.8 59 10340 4160 300 20.5 1.8 2.7 59 9620 3830 3.0 66 12780 5060 400 23.3 2.0 3.0 66 12670 4930 3.2 74 16800 6510 500 26.4 2.2 3.3 74 15720 6070 3.5 83 20890 8020 630 30.2 2.4 3.7 84 19720 7560 3.8 94 - 9960 800 34.8 2.6 4.0 95 24920 9480 4.2 106 - 12490

1000 39.0 2.8 4.4 106 - 11650 - - - -

XLPE DIMENSIONAL TABLE XLPE / PE or PVC

Page 12: Xlpe Cable Amps Rating

`

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 11

DIMENSIONAL TABLE, XLPE / PE or PVC XLPE

0.6/1 kV-XLPE/PE.LV-Continuous Current Rating Factor (100%-Load)

Conduc- in-air at 400C in-ground at 300C in-duct conductor

tor Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Core 4 Core 4 Core 4 Core 4 Core 4 Core 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

mm (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

16 95 85 75 125 105 100 90 90 85 115 110 110 80 80 60 105 100 80 1.5 2.3

25 130 130 100 165 145 130 115 115 110 150 145 140 105 100 80 135 130 105 2.3 3.5

35 160 160 125 200 175 160 140 135 130 180 170 170 125 120 95 160 155 125 3.3 4.9

50 190 190 150 240 210 195 160 160 155 210 205 200 145 140 115 185 185 150 4.7 7.0

70 235 235 190 305 265 245 200 195 190 255 250 245 180 175 140 230 225 185 6.7 9.9

95 290 290 235 370 320 300 235 230 235 305 295 295 220 220 170 285 280 220 9.1 13.4

120 335 335 270 430 370 345 270 260 260 345 335 335 255 250 195 325 320 250 11.4 17.0

150 385 385 305 500 430 395 300 295 290 390 380 375 285 280 220 370 360 285 14.3 21.2

185 445 445 350 570 495 450 340 330 330 440 425 420 325 320 250 420 410 320 17.7 26.2

240 530 530 415 680 585 530 395 385 380 510 490 485 380 370 305 485 475 390 22.9 34.0

300 605 605 475 780 670 605 450 435 425 575 555 545 425 420 345 550 535 435 28.7 42.5

400 710 710 555 910 780 695 515 495 490 660 630 615 490 480 395 630 610 500 38.3 56.7

500 835 835 640 1060 900 795 590 565 555 750 710 690 565 545 455 715 690 560 47.0 70.9

630 980 980 740 1235 1040 900 675 645 630 855 800 770 645 625 515 815 775 630 60.6 89.4

800 1140 1140 845 1425 1190 1010 775 730 710 965 890 845 735 705 580 920 865 695 76.6 113

1000 1320 1320 945 1620 1345 1105 875 815 780 1075 980 915 830 790 640 1020 945 750 95.7 141.9

Page 13: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 12

1.9/3.3 kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core

Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 2.0 1.4 15 370 270 1.9 28 1060 750 25 5.9 2.0 1.5 16 480 320 1.9 32 1400 920 35 7.0 2.0 1.5 17 590 370 2.0 33 1770 1090 50 8.0 2.0 1.5 19 750 430 2.1 36 2270 1310 70 9.7 2.0 1.6 20 970 530 2.2 40 2980 1630 95 11.4 2.0 1.7 22 1240 640 2.4 43 3830 2000

120 Compact 12.8 2.0 1.7 24 1500 740 2.5 47 4660 2350 150 round 14.3 2.0 1.8 25 1810 860 2.6 50 5650 2750 185 stranded 15.8 2.0 1.8 27 2160 1000 2.7 53 6780 3210 240 18.3 2.0 1.9 30 2730 1210 2.9 59 8590 3950 300 20.5 2.0 2.0 32 3330 1430 3.0 64 10510 4720 400 23.3 2.0 2.1 35 4310 1780 3.2 71 13630 5910 500 26.4 2.2 2.2 39 5530 2170 3.5 79 16920 7270 630 30.2 2.4 2.3 43 6640 2670 3.8 88 21190 9030 800 34.8 2.6 2.5 49 8350 3310 4.2 100 - 11330

1000 39.0 2.8 2.7 54 10340 4030 4.6 111 - 13890

3.8/6.6 kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core

Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 2.5 1.5 16 400 300 1.9 30 1160 580 25 5.9 2.5 1.5 17 510 350 2.0 33 1510 1030 35 7.0 2.5 1.5 19 630 400 2.0 35 1890 1210 50 8.0 2.5 1.6 20 790 470 2.1 38 2400 1430 70 9.7 2.5 1.6 21 1010 570 2.3 42 3120 1760 95 11.4 2.5 1.7 23 1280 680 2.4 46 3980 2150

120 Compact 12.8 2.5 1.8 25 1540 790 2.5 49 4820 2500 150 round 14.3 2.5 1.8 26 1860 910 2.6 52 5820 2920 185 stranded 15.8 2.5 1.9 28 2210 1050 2.8 56 6960 3390 240 18.3 2.6 1.9 31 2790 1280 3.0 63 8820 4190 300 20.5 2.8 2.0 34 3420 1530 3.2 69 10860 5060 400 23.3 3.0 2.1 37 4430 1550 3.4 76 14110 6390 500 26.4 3.2 2.3 41 5460 2300 3.7 84 17450 7800 630 30.2 3.2 2.4 45 6760 2780 3.9 92 21380 9410 800 34.8 3.2 2.6 50 8450 3400 4.3 103 - 11720

1000 39.0 3.2 2.7 54 10410 4100 4.6 113 - 14170

DIMENSIONAL TABLE, XLPE / PE or PVC XLPE

Page 14: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 13

3.6/6 kV XLPE/PE.MV-Continuous Current Rating Factor (100%-Load)

Condu- in-air at 400C in-ground at 300C in-duct conductor

ctor Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

(mm2) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

25 126 136 87 162 175 113 112 109 87 144 140 113 98 96 64 126 82 2.36 3.58 3.58

35 152 164 108 195 211 140 132 129 108 170 166 139 116 114 81 148 146 104 3.31 5.01

50 183 199 132 235 255 170 165 153 129 200 196 167 136 134 97 174 172 125 4.72 7.15

70 228 247 158 291 316 204 189 185 152 241 237 196 165 163 115 210 209 148 6.61 10

95 276 300 197 347 382 254 223 219 186 283 279 240 195 193 141 247 246 181 8.98 13.6

120 329 354 278 422 456 357 261 255 253 335 328 325 228 224 193 293 289 248 11.34 17.2

150 371 401 312 477 517 402 291 284 281 374 366 362 254 250 215 326 323 278 14.2 21.5

185 427 461 356 546 592 457 329 322 317 420 413 407 287 283 244 367 363 313 17.5 26.5

240 508 548 427 646 702 547 380 373 371 484 478 474 332 328 286 422 420 366 22.7 34.3

300 587 635 476 743 810 608 429 422 413 542 538 528 373 370 319 472 473 407 28.4 42.9

325 615 666 517 772 842 653 446 439 437 559 556 552 418 415 338 524 526 428 30.7 46.5

400 686 743 581 858 940 734 488 483 480 610 610 607 458 457 374 572 577 472 37.8 57.2

500 793 846 665 977 1080 829 552 55 545 679 687 680 517 520 446 636 649 556 47.2 71.5

630 899 1010 779 1087 1243 956 621 625 623 749 768 765 581 589 510 701 725 626 59.5 90.1

800 1045 1164 885 1237 1406 1066 689 702 698 813 847 841 643 660 573 759 797 690 75.6 114.5

1000 1160 1307 1026 1344 1548 1211 750 774 782 866 916 923 698 727 639 806 860 754 94.5 143.1

XLPE DIMENSIONAL TABLE XLPE / PE or PVC

Page 15: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 14

DIMENSIONAL TABLE, XLPE / PE or PVC XLPE

6.35/11 kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core

Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 3.4 1.5 18 450 350 2 34 1360 1050 25 5.9 3.4 1.6 19 570 410 2.1 37 1730 1240 35 7.0 3.4 1.6 21 690 470 2.1 39 2120 1440 50 8.0 3.4 1.6 22 850 540 2.3 42 2640 1670 70 9.7 3.4 1.7 23 1080 640 2.4 46 3380 2030 95 11.4 3.4 1.8 25 1360 760 2.5 50 4270 2430

120 Compact 12.8 3.4 1.8 27 1630 870 2.7 53 5130 2810 150 round 14.3 3.4 1.9 28 1940 1000 2.8 56 61400 3250 185 stranded 15.8 3.4 1.9 30 2300 1140 2.9 60 7300 3730 240 18.3 3.4 2.0 33 2880 1360 3.1 66 9160 4520 300 20.5 3.4 2.1 35 3490 1600 3.2 71 11130 5330 400 23.3 3.4 2.2 38 4480 1960 3.5 77 14310 6580 500 26.4 3.4 2.3 41 5490 2330 3.7 84 17550 7900 630 30.2 3.4 2.4 45 6790 2820 4.0 93 21780 9620 800 34.8 3.4 2.5 50 8490 3440 4.3 104 - 11850

1000 39.0 3.4 2.6 55 10440 4130 4.6 114 - 14320

8.7/15kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core

Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 4.5 1.6 21 530 430 2.2 40 1630 1320 25 5.9 4.5 1.6 22 650 490 2.3 42 2020 1540 35 7.0 4.5 1.7 23 780 560 2.4 45 2430 1750 50 8.0 4.5 1.7 24 940 630 2.5 47 2970 2000 70 9.7 4.5 1.8 26 1180 740 2.6 51 3740 2380 95 11.4 4.5 1.8 28 1460 860 2.7 55 4650 2820

120 Compact 12.8 4.5 1.9 29 1730 989 2.8 58 5530 3210 150 round 14.3 4.5 1.9 31 2060 1110 2.9 61 6570 3670 185 stranded 15.8 4.5 2.0 32 2120 1260 3.0 65 7750 4180 240 18.3 4.5 2.1 35 3000 1490 3.2 71 9650 5020 300 20.5 4.5 2.2 37 3630 1730 3.4 76 11650 5860 400 23.3 4.5 2.3 40 4630 2110 3.6 82 14880 7150 500 26.4 4.5 2.4 44 5650 2490 3.9 89 18170 8520 630 30.2 4.5 2.5 48 6960 2990 4.1 98 22460 10290 800 34.8 4.5 2.7 53 8670 3630 4.5 109 - 12600

1000 39.0 4.5 2.8 57 10650 4340 - - - -

Page 16: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 15

DIMENSIONAL TABLE, XLPE / PE or PVC XLPE

12.7/22 kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core

Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 5.5 1.7 23 610 510 2.4 44 1740 1430 25 5.9 5.5 1.7 24 730 580 2.5 47 2120 1630 35 7.0 5.5 1.8 25 860 640 2.5 49 2510 1830 50 8.0 5.5 1.8 25 1030 720 2.6 52 3020 2070 70 9.7 5.5 1.9 28 1280 830 2.8 55 3770 2420 95 11.4 5.5 1.9 30 1560 960 2.9 60 4650 2810

120 Compact 12.8 5.5 2.0 31 1840 1080 3.0 63 5500 3180 150 round 14.3 5.5 2.0 33 2170 1220 3.1 66 6500 3600 185 stranded 15.8 5.5 2.0 34 2540 1370 3.2 69 7640 4060 240 18.3 5.5 2.1 37 3130 1620 3.4 75 9450 4820 300 20.5 5.5 2.2 40 3760 1860 3.6 80 11380 5580 400 23.3 5.5 2.3 42 4770 2250 3.8 87 14490 6760 500 26.4 5.5 2.4 46 5800 2640 4.1 94 17640 7990 630 30.2 5.5 2.6 50 7120 3150 4.3 103 21730 9570 800 34.8 5.5 2.7 55 8850 3820 4.6 114 - 11600

1000 39.0 5.5 2.9 60 10840 4530 - - - -

19/33kV XLPE/PE Power Cable, Type XLPE/PE

Conductor Nominal Single core Three core Nom. cross thickness Thickness Approx. Approx. Approx. Thickness Approx Approx. Approx.

sectional Shape Diameter of of overall cable weight weight of overall

cable weight weight

area insulation sheath diameter (Cu) (AL.) sheath diameter (Cu) (AL.) sqmm mm mm mm mm kg/km kg/km mm mm kg/km kg/km

16 4.7 8.0 1.9 29 840 730 2.8 40 2420 2110 25 5.9 8.0 2.0 30 970 810 2.9 42 2830 2340 35 7.0 8.0 2.0 31 1110 890 3.0 45 3250 2570 50 8.0 8.0 2.0 32 1290 970 3.1 47 3800 2830 70 9.7 8.0 2.1 34 1540 1100 3.2 51 4580 3230 95 11.4 8.0 2.1 36 1840 1240 3.3 55 5500 3670

120 Compact 12.8 8.0 2.1 37 2130 1370 3.4 58 6390 4070 150 round 14.3 8.0 2.2 39 2470 1520 3.6 61 7430 4530 185 stranded 15.8 8.0 2.2 40 2860 1690 3.7 65 8610 5040 240 18.3 8.0 2.3 43 3470 1950 3.8 71 10490 5860 300 20.5 8.0 2.4 46 4110 2220 4.0 76 12480 6680 400 23.3 8.0 2.5 49 5150 2630 4.1 82 15660 7940 500 26.4 8.0 2.6 53 6200 3050 4.3 89 18900 9250 630 30.2 8.0 2.7 57 7560 3590 - - - - 800 34.8 8.0 2.8 62 9330 4280 - - - -

1000 39.0 8.0 3.0 67 11350 5040 - - - -

Page 17: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 16

6.35/11kV to 19/33 kV-XLPE/PE.MV-Continuous Current Rating Factor (100%-Load)

Cond- uctor in-air at 400C in-ground at 300C in-duct conductor

Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

mm (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

16 130 115 110 100 90 85 115 110 110 90 895 85 105 105 85 80 80 70 2.3 1.5

25 170 140 135 130 118 110 150 145 145 115 110 110 135 135 115 105 105 90 3.5 2.3

35 210 185 175 160 145 135 180 170 170 135 135 135 160 160 135 125 125 105 4.9 3.3

50 245 220 210 190 170 160 210 200 200 160 155 155 190 190 160 150 145 125 7.0 4.7

70 310 275 260 240 210 200 255 250 245 200 190 190 230 230 195 180 175 150 9.9 6.7

95 375 335 310 290 260 240 305 300 295 235 230 225 290 280 240 225 220 185 13.4 9.1

120 430 385 355 335 300 275 345 335 330 270 260 260 325 320 275 255 250 210 17.0 11.4

150 495 440 375 385 340 315 390 380 375 300 290 290 365 360 310 290 285 240 21.2 14.3

185 565 500 460 440 390 355 440 426 420 340 330 325 410 410 345 330 320 270 26.2 17.7

240 670 595 540 520 460 420 510 490 485 395 385 380 480 475 400 380 370 310 34.0 22.9

300 770 680 625 600 530 485 580 555 550 450 435 430 540 535 455 430 420 355 42.5 28.7

325 613 662 413 769 839 523 446 440 408 559 556 516 418 416 298 524 526 377 30.7 46.5

400 895 790 720 700 620 565 660 630 625 515 495 495 615 610 515 495 480 405 56.7 38.3

500 1040 910 810 820 720 645 750 720 705 590 570 560 695 680 580 556 530 465 70.9 47.0

630 1210 1050 940 960 840 755 850 810 795 680 650 640 785 770 655 650 630 530 89.4 60.6

800 1395 1200 1035 1115 975 855 970 905 875 775 735 720 875 845 720 735 710 595 113.0 76.6

1000 1590 1350 1125 1290 1115 960 1080 995 950 875 825 800 960 915 785 830 795 660 141.9 95.7

DIMENSIONAL TABLE, XLPE / PE or PVC XLPE

Page 18: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 17

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

600/1000 V Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.)

sectional insulation sheath wire wire sheath diameter

area

sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 0.7 1.0 19 1.6 1.8 28 1650 1340

25 5.9 0.9 1.1 22 1.6 1.9 31 2140 1660

35 7.0 0.9 1.1 25 1.6 2.0 34 2590 1920

50 Compact 8.0 1.0 1.1 28 2.0 2.1 38 3450 2490

70 round 9.7 1.1 1.2 32 2.0 2.3 42 4370 3020

95 stranded 11.4 1.1 1.3 36 2.5 2.4 48 5800 3960

120 12.8 1.2 1.4 39 2.5 2.6 51 6870 4550

150 14.3 1.4 1.5 44 2.5 2.7 56 8150 5250

185 15.8 1.6 1.5 48 2.5 2.8 61 9560 5990

240 18.3 1.7 1.7 54 2.5 3.1 67 11850 7210

300 20.5 1.8 1.8 59 2.5 3.3 73 14130 8340

400 23.3 2.0 1.9 66 3.15 3.5 82 18700 10980

500 26.4 2.1 2.0 74 3.15 3.8 90 22530 12870

630 30.2 2.4 2.2 84 3.15 4.2 100 27540 15490

For Aluminium and Copper Conductor

Page 19: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 18

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

0.6/1 Kv-XLPE/SWA/PE or PVC.LV-Continuous Current Rating Factor (100%-Load)

Conduc- in-air at 400C in-ground at 300C in-duct conductor

tor Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Core 4 Core 4 Core 4 Core 4 Core 4 Core 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

mm (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

16 95 85 75 125 105 100 90 90 85 115 110 110 80 80 60 105 100 80 1.5 2.3

25 130 130 100 165 145 130 115 115 110 150 145 140 105 100 80 135 130 105 2.3 3.5

35 160 160 125 200 175 160 140 135 130 180 170 170 125 120 95 160 155 125 3.3 4.9

50 190 190 150 240 210 195 160 160 155 210 205 200 145 140 115 185 185 150 4.7 7.0

70 235 235 190 305 265 245 200 195 190 255 250 245 180 175 140 230 225 185 6.7 9.9

95 290 290 235 370 320 300 235 230 235 305 295 295 220 220 170 285 280 220 9.1 13.4

120 335 335 270 430 370 345 270 260 260 345 335 335 255 250 195 325 320 250 11.4 17.0

150 385 385 305 500 430 395 300 295 290 390 380 375 285 280 220 370 360 285 14.3 21.2

185 445 445 350 570 495 450 340 330 330 440 425 420 325 320 250 420 410 320 17.7 26.2

240 530 530 415 680 585 530 395 385 380 510 490 485 380 370 305 485 475 390 22.9 34.0

300 605 605 475 780 670 605 450 435 425 575 555 545 425 420 345 550 535 435 28.7 42.5

400 710 710 555 910 780 695 515 495 490 660 630 615 490 480 395 630 610 500 38.3 56.7

500 835 835 640 1060 900 795 590 565 555 750 710 690 565 545 455 715 690 560 47.0 70.9

630 980 980 740 1235 1040 900 675 645 630 855 800 770 645 625 515 815 775 630 60.6 89.4

800 1140 1140 845 1425 1190 1010 775 730 710 965 890 845 735 705 580 920 865 695 76.6 113

1000 1320 1320 945 1620 1345 1105 875 815 780 1075 980 915 830 790 640 1020 945 750 95.7 141.9

Page 20: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 19

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

1.9/3.3 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 2.0 1.1 27 2.0 2.1 37 2360 2050 25 5.9 2.0 1.1 30 2.0 2.2 40 2780 2300 35 7.0 2.0 1.2 32 2.0 2.3 43 3290 2610 50 8.0 2.0 1.2 34 2.0 2.3 45 3890 2930 70 9.7 2.0 1.3 38 2.5 2.5 50 5190 3840 95 Compact 11.4 2.0 1.4 42 2.5 2.6 54 6320 4480

120 round 12.8 2.0 1.4 45 2.5 2.8 58 7290 4980 150 stranded 14.3 2.0 1.5 48 2.5 2.9 61 8490 5590 185 15.8 2.0 1.6 52 2.5 3.0 65 9830 6260 240 18.3 2.0 1.7 57 2.5 3.2 71 12000 7370 300 20.5 2.0 1.8 62 3.15 3.4 77 14260 8470 400 23.3 2.0 1.9 69 3.15 3.6 84 18700 11000 500 26.4 2.2 2.0 76 3.15 3.9 93 22520 12920 630 30.2 2.4 2.2 86 3.15 4.2 103 - 15890

800 34.8 2.6 2.4 97 3.15 4.5 112 - 18680

3.8/6.6 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 2.5 1.1 29 2.0 2.2 39 2540 2230 25 5.9 2.5 1.2 32 2.0 2.3 42 3030 2550 35 7.0 2.5 1.2 34 2.0 2.3 45 3510 2830 50 8.0 2.5 1.3 37 2.5 2.5 48 4160 3190 70 9.7 2.5 1.4 40 2.5 2.6 53 5500 4140 95 Compact 11.4 2.5 1.4 44 2.5 2.7 57 6550 4700

120 round 12.8 2.5 1.5 47 2.5 2.8 60 7620 5310 150 stranded 14.3 2.5 1.6 51 2.5 2.9 64 8830 5940 185 15.8 2.5 1.6 54 2.5 3.1 67 10160 6590 240 18.3 2.6 1.7 60 2.5 3.3 74 12390 7760 300 20.5 2.8 1.8 66 3.15 3.5 81 15710 9910 400 23.3 3.0 2.0 73 3.15 3.8 89 19540 11820 500 26.4 3.2 2.1 81 3.15 4.1 97 23470 13820 630 30.2 3.2 2.3 90 3.15 4.4 107 - 16290

800 34.8 3.2 2.5 100 3.15 4.7 118 - 19290

Page 21: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 20

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

3.6/6 kV XLPE/SWA/PE or PVC MV-Continuous Current Rating Factor (100%-Load)

Conduc- in-air at 400C in-ground at 300C in-duct conductor

tor Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

mm (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

25 126 136 87 162 175 113 112 109 87 144 140 113 98 96 64 126 82 2.36 3.58 3.58

35 152 164 108 195 211 140 132 129 108 170 166 139 116 114 81 148 146 104 3.31 5.01

50 183 199 132 235 255 170 165 153 129 200 196 167 136 134 97 174 172 125 4.72 7.15

70 228 247 158 291 316 204 189 185 152 241 237 196 165 163 115 210 209 148 6.61 10

95 276 300 197 347 382 254 223 219 186 283 279 240 195 193 141 217 246 181 8.98 13.6

120 329 354 278 422 456 357 261 255 253 335 328 325 228 224 193 293 289 248 11.34 17.2

150 371 401 312 477 517 402 291 284 281 374 366 362 254 250 215 326 323 278 14.2 21.5

185 427 461 356 546 592 457 329 322 317 420 413 407 287 283 244 367 363 313 17.5 26.5

240 508 548 427 646 702 547 380 373 371 484 478 474 332 328 286 422 420 366 22.7 34.3

300 587 635 476 743 810 608 429 422 413 542 538 528 373 370 319 472 473 407 28.4 42.9

325 615 666 517 772 842 653 446 439 437 559 556 552 418 415 338 524 526 428 30.7 46.5

400 686 743 581 858 940 734 488 483 480 610 610 607 458 457 374 572 577 472 37.8 57.2

500 793 846 665 977 1080 829 552 550 545 679 687 680 517 520 446 636 649 556 47.2 71.5

630 899 1010 779 1087 1243 956 621 625 623 749 768 765 581 589 510 701 725 626 59.5 90.1

800 1045 1164 885 1237 1406 1066 689 702 698 813 847 841 643 660 573 759 797 690 75.6 114.5

1000 1160 1307 1026 1344 1548 1211 750 774 782 866 916 923 698 727 639 806 860 754 94.5 143.1

Page 22: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 21

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

6.35/11 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 3.4 1.2 33 2.0 2.3 44 2950 2640 25 5.9 3.4 1.3 36 2.5 2.4 48 3460 2980 35 7.0 3.4 1.3 38 2.5 2.5 50 4350 3670 50 8.0 3.4 1.4 41 2.5 2.6 53 5030 4070 70 9.7 3.4 1.4 44 2.5 2.7 57 6020 4670 95 Compact 11.4 3.4 1.5 48 2.5 2.9 61 7120 5290

120 round 12.8 3.4 1.6 51 2.5 3.0 64 8190 5880 150 stranded 14.3 3.4 1.6 55 2.5 3.1 68 9430 6530 185 15.8 3.4 1.7 58 2.5 3.2 71 10810 7230 240 18.3 3.4 1.8 64 3.15 3.4 79 13860 9230 300 20.5 3.4 1.9 69 3.15 3.6 84 16220 10420 400 23.3 3.4 2.0 75 3.15 3.8 91 19920 12200 500 26.4 3.4 2.2 82 3.15 4.1 98 23700 14050 630 30.2 3.4 2.3 90 3.15 4.4 107 - 16430

8.5/15 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 4.5 1.3 38 2.5 2.5 50 3850 3540 25 5.9 4.5 1.4 41 2.5 2.6 53 4400 3920 35 7.0 4.5 1.4 43 2.5 2.7 56 4960 4280 50 8.0 4.5 1.5 45 2.5 2.8 58 5660 4700 70 9.7 4.5 1.5 49 2.5 2.9 62 6640 5290 95 Compact 11.4 4.5 1.6 53 2.5 3.0 66 7810 5980

120 round 12.8 4.5 1.7 56 2.5 3.1 70 8910 6590 150 stranded 14.3 4.5 1.7 60 2.5 3.3 73 10140 7240 185 15.8 4.5 1.8 63 3.15 3.4 78 12380 8810 240 18.3 4.5 1.9 69 3.15 3.6 84 14720 10090 300 20.5 4.5 2.0 74 3.15 3.8 89 17080 11290 400 23.3 4.5 2.1 80 3.15 4.0 96 20790 13070 500 26.4 4.5 2.2 87 3.15 4.3 104 - 15040 630 30.2 4.5 2.4 95 3.15 4.6 113 - 17600

Page 23: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 22

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

12.7/ 22 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 5.5 1.4 43 2.5 2.7 55 4410 4100 25 5.9 5.5 1.4 45 2.5 2.8 58 5000 4520 35 7.0 5.5 1.5 48 2.5 2.8 60 5600 4920 50 8.0 5.5 1.5 50 2.5 2.9 63 6230 5260 70 9.7 5.5 1.6 54 2.5 3.1 67 7300 5950 95 Compact 11.4 5.5 1.7 58 2.5 3.2 71 8490 6660

120 round 12.8 5.5 1.7 61 3.15 3.3 76 9550 7230 150 stranded 14.3 5.5 1.8 64 3.15 3.5 79 11760 8860 185 15.8 5.5 1.9 68 3.15 3.6 83 13220 9650 240 18.3 5.5 2.0 73 3.15 3.8 89 15570 10140 300 20.5 5.5 2.1 78 3.15 4.0 94 18040 12240 400 23.3 5.5 2.2 84 3.15 4.2 101 21800 14080 500 26.4 5.5 2.3 91 3.15 4.4 108 - 15990

19/33 kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power cable, Type XLPE/SWA/PVC

Conductor Nominal Thickness Approx. Diameter Thickness Approx. Approx. Approx.

Nominal Shape Diameter thickness of cable diameter of of overall weight weight

cross of separation under armour outer cable (Cu) (AL.) sectional insulation sheath wire wire sheath diameter

area sqmm mm mm mm mm mm mm mm kg/km kg/km

16 4.7 8.0 1.6 54 2.5 3.1 67 5960 5650 25 5.9 8.0 1.7 57 2.5 3.2 70 6520 6040 35 7.0 8.0 1.7 59 2.5 3.2 72 7100 6430 50 8.0 8.0 1.8 61 3.15 3.4 76 7830 6800 70 9.7 8.0 1.8 65 3.15 3.5 80 9870 8510 95 Compact 11.4 8.0 1.9 69 3.15 3.6 84 11150 9320

120 round 12.8 8.0 2.0 72 3.15 3.7 88 12360 10040 150 stranded 14.3 8.0 2.0 75 3.15 3.9 91 13730 10840 185 15.8 8.0 2.1 79 3.15 4.0 95 15210 11640 240 18.3 8.0 2.2 84 3.15 4.2 101 17660 13030 300 20.5 8.0 2.3 89 3.15 4.3 106 21210 14420 400 23.3 8.0 2.4 96 3.15 4.6 113 - 16350

Page 24: Xlpe Cable Amps Rating

1

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 23

DIMENSIONAL TABLE, XLPE / SWA/PVC or PE

XLPE

6.35/11 19/33 kV-XLPE/SWA/PE.MV or PVC-Continuous Current Rating Factor (100%-Load)

Conduc- in-air at 400C in-ground at 300C in-duct conductor

tor Aluminium Copper Aluminium Copper Aluminium Copper Alu- minium Copper

3 3 3 3 3 3

Size Single or Single or Single or Single or Single or Single or 1 Sec. 1 Sec.

Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4 Isolated 4

Core Core Core Core Core Core fault fault

Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable Flat Trefoil Cable current current

mm (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (kA) (kA)

16 130 115 110 100 90 85 115 110 110 90 895 85 105 105 85 80 80 70 2.3 1.5

25 170 140 135 130 118 110 150 145 145 115 110 110 135 135 115 105 105 90 3.5 2.3

35 210 185 175 160 145 135 180 170 170 135 135 135 160 160 135 125 125 105 4.9 3.3

50 245 220 210 190 170 160 210 200 200 160 155 155 190 190 160 150 145 125 7.0 4.7

70 310 275 260 240 210 200 255 250 245 200 190 190 230 230 195 180 175 150 9.9 6.7

95 375 335 310 290 260 240 305 300 295 235 230 225 290 280 240 225 220 185 13.4 9.1

120 430 385 355 335 300 275 345 335 330 270 260 260 325 320 275 255 250 210 17.0 11.4

150 495 440 375 385 340 315 390 380 375 300 290 290 365 360 310 290 285 240 21.2 14.3

185 565 500 460 440 390 355 440 426 420 340 330 325 410 410 345 330 320 270 26.2 17.7

240 670 595 540 520 460 420 510 490 485 395 385 380 480 475 400 380 370 310 34.0 22.9

300 770 680 625 600 530 485 580 555 550 450 435 430 540 535 455 430 420 355 42.5 28.7

325 613 662 413 769 839 523 446 440 408 559 556 516 418 416 298 524 526 377 30.7 46.5

400 895 790 720 700 620 565 660 630 625 515 495 495 615 610 515 495 480 405 56.7 38.3

500 1040 910 810 820 720 645 750 720 705 590 570 560 695 680 580 556 530 465 70.9 47.0

630 1210 1050 940 960 840 755 850 810 795 680 650 640 785 770 655 650 630 530 89.4 60.6

800 1395 1200 1035 1115 975 855 970 905 875 775 735 720 875 845 720 735 710 595 113.0 76.6

1000 1590 1350 1125 1290 1115 960 1080 995 950 875 825 800 960 915 785 830 795 660 141.9 95.7

Page 25: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 24

DIMENSIONAL TABLE, Copper Conductor, XLPE / CWS/PE or PVC

XLPE

38/66 kV XLPE INSULATED POWER CABLE

Copper Conductor, XLPE/CWS/PE or PVC

Conductor Nominal Thickness

of jacket (mm)

Outside Weight

of cable

(kg/km)

DC resistance

(Ω /km)

Electro-static

capacity (µF/km)

thickness diameter Conductor Shape Diameter of of cable

size (Approx insulation (Approx (mm2) mm) (mm) mm)

300 20.8 9.5 2.88 58 8110 0.0601 0.262 400 Compact 23.3 9.5 2.97 61 9165 0.0470 0.283 500 Round 26.4 9.5 3.08 65 10255 0.0366 0.309 630 Stranded 30.2 9.5 3.21 68 12290 0.0283 0.340

800 34.8 9.5 3.37 73 14110 0.0221 0.376

Four 1000 Segmental 38.0 9.5 3.48 76 16445 0.0176 0.404 1200 Stranded 41.7 9.5 3.61 80 18495 0.0151 0.434

Aluminium conductor,XLPE/PE or PVC Conductor Nominal

Thickness of

jacket (mm)

Outside Weight

of cable

(kg/km)

DC resistance

(Ω /km)

Electro-static

capacity (µF/km)

thickness diameter Conductor Shape Diameter of of cable

size (Approx insulation (Approx (mm2) mm) (mm) mm)

300 20.8 9.5 2.88 58 7145 0.1000 0.262 400 Compact 23.3 9.5 2.97 61 7560 0.0778 0.283 500 Round 26.4 9.5 3.08 65 8015 0.0605 0.309 630 Stranded 30.2 9.5 3.21 68 8590 0.0469 0.340

800 34.8 9.5 3.37 73 9330 0.0367 0.376

Four 1000 Segmental 38.0 9.5 3.48 76 10070 0.0291 0.404 1200 Stranded 41.7 9.5 3.61 80 10845 0.0247 0.434

Page 26: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 25

DIMENSIONAL TABLE, XLPE / CWS/ PE or PVC

XLPE

76/132kV XLPE Insulated Power Cable with Copper Wire screen

Aluminium Conductor, XLPE/CWS/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness of

jacket (mm)

Outside diameter of cable (Approx

mm)

Weight of

cable (kg/km)

DC resistance

(Ω /km)

Electro-static

capacity (µF/km) Shape

Conductor Diameter size (Approx

(mm2) mm)

300 20.8 21 3.71 84 9875 0.1000 0.151 400 Compact 23.3 21 3.80 87 10390 0.0778 0.161 500 Round 26.4 21 3.90 89 10965 0.0605 0.173 630 Stranded 30.2 21 4.04 94 11695 0.0469 0.187

800 34.8 21 4.20 98 12615 0.0367 0.205

Four 1000 Segmental 38.0 21 4.31 102 13485 0.0291 0.217 1200 Stranded 41.7 21 4.45 107 14405 0.0247 0.231

Continuous current ratings (load factor = 100%)

Conductor Size (mm2)

In ground In air In duct Conductor

1 sec Fault current

rating (kA)

3 sec Fault

current rating (kA)

Trefoil Flat Trefoil Flat Trefoil Flat

(A) (A) (A) (A) (A) (A)

Aluminium cond. 300 448 487 578 663 437 442 28.3 16.4 400 522 543 683 763 555 571 37.8 21.8 500 613 644 791 868 580 597 47.2 27.2 630 702 754 889 943 592 631 59.5 34.4 800 786 828 954 1037 660 705 75.6 43.6

1000 889 971 1011 1175 785 853 94.5 54.6 1200 919 1029 1144 1220 859 949 113.4 65.5

Page 27: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 26

DIMENSIONAL TABLE, XLPE / CWS/ PE or PVC

XLPE

76/132kV XLPE Insulated Power Cable with Copper wire screen

Copper conductor , XLPE/CWS/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness of

jacket (mm)

Outside diameter of cable (Approx

mm)

Weight of

cable (kg/km)

DC resistance

( Ω/km)

`Electro-static

capacity (µ F/km) Shape

Conductor Diameter size (Approx

(mm2) mm)

300 20.8 21 3.71 84 11790 0.0601 0.151 400 Compact 23.3 21 3.80 87 13230 0.0470 0.161 500 Round 26.4 21 3.90 89 14155 0.0366 0.173 630 Stranded 30.2 21 4.04 94 15710 0.0283 0.187 800 34.8 21 4.20 98 17715 0.0221 0.205

Four 1000 Segmental 38.0 21 4.31 102 19860 0.0176 0.217 1200 Stranded 41.7 21 4.45 107 22060 0.0151 0.231

Continuous current ratings (load factor = 100%)

Conductor Size (mm2)

In ground In air In duct Conductor

1 sec Fault

current rating (kA)

3 sec Fault

current rating (kA)

Trefoil Flat Trefoil Flat Trefoil Flat

(A) (A) (A) (A) (A) (A)

Copper cond. 300 549 591 678 763 537 566 42.9 24.8 400 618 659 779 854 598 632 57.2 33.0 500 710 757 894 987 685 686 71.5 41.3 630 819 854 992 1063 793 833 90.1 52.0 800 894 941 1047 1246 849 893 114.5 66.1

1000 996 1067 1214 1367 896 947 143.0 82.6 1200 1021 1157 1349 1394 952 996 171.7 99.1

Page 28: Xlpe Cable Amps Rating

27

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY

93/161 kV XLPE insulated Power Cable with Copper wire screen. Copper Conductor , XLPE/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness

of jacket (mm)

Outside diameter of cable (Approx

mm)

Weight

of cable

(kg/km)

DC resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

25 25 25 25 25

4.20 4.20 4.20 4.20 4.20

94 97 99

103 108

15305 16470 17690 19260 21270

0.0601 0.0470 0.0366 0.0283 0.0221

0.135 0.144 0.154 0.166 0.182

1000 1200

Four

Segmental Stranded

38.0 41.7

25 25

4.20 4.20

111 115

23420 25615

0.0176 0.0151

0.192 0.204

Continuous current ratings (load factor = 100%)

Conductor Size (mm²)

In ground In air In duct Conductor

Trefoil

(A)

Flat (A)

Trefoil

(A)

Flat (A)

Trefoil

(A)

Flat (A)

1 sec Fault current rating (kA)

3 sec Fault current rating (kA)

Copper cond.

300 400 500 630 800

1000 1200

555 633 709 822 910

1015 1091

596 664 762 859 946

1072 1162

678 779 896 997

1044 1209 1340

767 851 992

1068 1251 1372 1399

542 603 690 798 854 901 957

571 637 691 838 798 952

1001

42.9 57.2 71.5 90.1

114.5 143.0 171.7

24.8 33.0 41.3 52.0 66.1 82.6 99.1

XLPE DIMENSIONAL TABLE XLPE/PE or PVC

Page 29: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 28

38/66 kV Lead Sheathed Cable

Copper Conductor, XLPE/LC/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness

of jacket (mm)

Thickness

of lead

sheathed (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

9.5 9.5 9.5 9.5 9.5

3.85 3.94 4.05 4.20 4.37

2.21 2.28 2.38 2.50 2.63

59 62 65 69 75

8340 9795

11320 13335 15840

0.0601 0.0470 0.0366 0.0283 0.0221

0.262 0.283 0.309 0.340 0.376

1000 1200

Four

Segmental Stranded

38.0 41.7

9.5 9.5

4.49 4.62

2.72 2.83

79 83

18395 21090

0.0176 0.0151

0.404 0.434

Continuous current ratings (load factor = 100%)

Conductor Size (mm²)

In ground In air In duct Conductor

Trefoil (A)

Flat (A)

Trefoil (A)

Flat (A)

Trefoil (A)

Flat (A)

1 sec Fault current

rating (kA)

3 sec Fault current

rating (kA)

Copper cond.

300 400 500 630 800

1000 1200

457 516 681 752 920

1105 1212

531 603 704 856 987

1175 1294

593 698 787 912

1071 1218 1347

642 741 873

1011 1176 1347 1507

423 502 658 761 898

1093 1186

499 584 693 823 955

1142 1254

42.9 57.2 71.5 90.1

114.5 143.0 171.7

24.8 33.0 41.3 52.0 66.1 82.6 99.1

XLPE DIMENSIONAL TABLE XLPE/LC/PE or PVC

Page 30: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 29

38/66 kV XLPE Insulated Lead Sheathed Cable Aluminium conductor, XLPE/LC/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness

of jacket (mm)

Thickness

of lead

sheathed (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

9.5 9.5 9.5 9.5 9.5

3.85 3.94 4.05 4.20 4.37

2.21 2.28 2.38 2.49 2.63

59 62 65 70 75

6510 7265 8155 9300

10770

0.1000 0.0778 0.0605 0.0469 0.0367

0.262 0.283 0.309 0.340 0.376

1000 1200

Four

Segmental Stranded

38.0 41.7

9.5 9.5

4.49 4.62

2.72 2.83

79 83

18395 21090

0.0291

-

0.404 0.434

Continuous current ratings (load factor = 100%)

Conductor Size (mm²)

In ground In air In duct Conductor

Trefoil

(A)

Flat (A)

Trefoil

(A)

Flat (A)

Trefoil

(A)

Flat (A)

1 sec Fault current

rating (kA)

3 sec Fault current

rating (kA)

Copper cond.

300 400 500 630 800

1000 1200

332 406 478 545 664 789 841

394 485 546 602 698 842 995

579 684 792 891 958

1011 1143

663 765 877 951

1043 1182 1217

313 396 457 521 656 778 824

331 410 498 577 666 821 945

28.3 37.8 47.2 59.5 75.6 94.5

113.4

16.4 21.8 27.2 34.4 43.6 54.6 65.5

XLPE DIMENSIONAL TABLE XLPE/PE or PVC

Page 31: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 30

76/132 kV XLPE Insulated Lead Sheathed Cable

Copper conductor, XLPE/LC/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness

of jacket (mm)

Thickness

of lead

sheathed (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

21 21 21 21 21

4.74 4.84 4.95 5.09 5.26

2.93 3.01 3.10 3.22 3.35

87 89 93 97

102

14840 16470 18290 20625 23610

0.0601 0.0470 0.0366 0.0283 0.0221

0.151 0.161 0.173 0.187 0.205

1000 1200

Four

Segmental Stranded

38.0 41.7

21 21

5.38 5.52

3.45 3.56

106 110

26465 29515

0.0176 0.0151

0.217 0.231

Aluminium conductor, XLPE/LC/PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Thickness

of jacket (mm)

Thickness

of lead

sheathed (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

21 21 21 21 21

4.74 4.84 4.95 5.09 5.26

2.93 3.01 3.10 3.22 3.35

87 89 93 97

102

12925 13920 15105 16605 18510

0.1000 0.0778 0.0605 0.0469 0.0367

0.151 0.161 0.173 0.187 0.205

1000 1200

Four

Segmental Stranded

38.0 41.7

21 21

5.38 5.52

3.45 3.56

106 110

20090 21865

0.0291 0.0247

0.217 0.231

XLPE DIMENSIONAL TABLE XLPE/PE or PVC

Page 32: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 31

38/66 kV XLPE Insulated Power Cable Aluminium Wire Screen

Copper conductor, XLPE/ AWA /PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Diameter & number of aluminium

wire (mm x N)

Thickness

of jacket (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape Diameter

(Approx mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

9.5 9.5 9.5 9.5 9.5

2.5 x 52 2.5 x 54 2.5 x 58 2.5 x 62 2.5 x 67

2.88 2.97 3.08 3.21 3.37

59 61 64 69 74

5625 6730 7885 9370

11285

0.0601 0.0470 0.0366 0.0283 0.0221

0.262 0.283 0.309 0.340 0.376

1000 1200

Four

Segmental Stranded

38.0 41.7

9.5 9.5

2.5 x 70 2.5 x 74

3.48 3.61

77 81

13370 15495

0.0176 0.0151

0.404 0.434

Aluminium conductor, XLPE/ AWA / PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Diameter & number of aluminium

wire (mm x N)

Thickness

of jacket (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

9.5 9.5 9.5 9.5 9.5

2.5 x 52 2.5 x 54 2.5 x 58 2.5 x 62 2.5 x 67

2.88 2.97 3.08 3.21 3.37

59 61 64 69 74

3715 4180 4695 5350 6185

0.1000 0.0778 0.0605 0.0469 0.0367

0.262 0.283 0.309 0.340 0.376

1000 1200

Four

Segmental Stranded

38.0 41.7

9.5 9.5

2.5 x 70 2.5 x 74

3.48 3.61

77 81

6995 7845

0.0291 0.0247

0.404 0.434

XLPE DIMENSIONAL TABLE XLPE/PE or PVC

Page 33: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 32

63/132 kV XLPE Insulated Power Cable with Aluminium Wire Screen

Copper conductor, XLPE/ AWA /PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Diameter & number of aluminium

wire (mm x N)

Thickness

of jacket (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

(mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

21 21 21 21 21

2.5 x 80 2.5 x 80 2.5 x 80 2.5 x 80 2.5 x 80

3.72 3.80 3.91 4.04 4.21

84 87 90 94 99

8670 9825

11035 12590 14595

0.0601 0.0470 0.0366 0.0283 0.0221

0.151 0.161 0.173 0.187 0.205

1000 1200

Four

Segmental Stranded

38.0 41.7

21 21

2.5 x 80 2.5 x 80

4.32 4.45

102 106

16740 18940

0.0176 0.0151

0.217 0.231

Aluminium conductor, XLPE/ AWA / PE or PVC

Conductor Nominal thickness

of insulation

(mm)

Diameter & number of aluminium

wire (mm x N)

Thickness

of jacket (mm)

Outside diameter of cable (Approx

mm

Weight

of cable

(kg/km)

DC

resistance

(Ω/km)

Electro-static

capacity (µF/km)

Conductor size

(mm²) Shape

Diameter (Approx

mm)

300 400 500 630 800

Compact Round

Stranded

20.8 23.3 26.4 30.2 34.8

21 21 21 21 21

2.5 x 80 2.5 x 80 2.5 x 80 2.5 x 80 2.5 x 80

3.72 3.80 3.91 4.04 4.21

84 87 90 94 99

6755 7275 7850 8575 9495

0.1000 0.0778 0.0605 0.0469 0.0367

0.262 0.283 0.309 0.340 0.376

1000 1200

Four

Segmental Stranded

38.0 41.7

21 21

2.5 x 80 2.5 x 80

4.32 4.45

102 106

10365 11290

0.0291 0.0247

0.404 0.434

XLPE DIMENSIONAL TABLE XLPE/PE or PVC

Page 34: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 33

Some Of The Various Utility Specified Cables

XLPE

600/1000 V Four Core XLPE/SWA/PVC, Steel Wire Armoured Power Cable, Type XLPE/SWA/PVC Conductor Nominal

thickness of

insulation mm

Thickness of

separation sheath

mm

Approx. cable diameter

under wire mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx. weight (Cu)

kg/km

Approx. weight (AL)

kg/km

Nom. Cross

Shape Diameter mm

sectional area sqmm

25 5.9 1.1 1.0 22.1 1.6 1.9 31 3230 2590 35 7.0 1.1 1.1 24.9 1.6 2.0 34 3880 2980 50 8.0 1.2 1.1 27.9 2.0 2.1 38 4350 3070 70 9.7 1.3 1.2 32.7 2.0 2.3 43 5550 3740 95 Compact 11.4 1.3 1.3 37.0 2.5 2.5 49 6450 4010

120 round 12.8 1.4 1.4 41.0 2.5 2.6 53 7750 4660 150 stranded 14.3 1.6 1.5 45.8 2.5 2.8 58 9350 5480 185 15.8 1.8 1.6 50.6 2.5 2.9 63 11100 6340 240 18.3 1.9 1.7 57.4 2.5 3.2 71 13840 7660 300 20.5 2.0 1.8 63.4 3.15 3.4 79 16140 8420

400 23.3 2.3 2.0 72.0 3.15 3.7 88 20780 10480 6.35/11kV Three Core XLPE/SWA/PVC, Steel Wire Armoured Power Cable, Type XLPE/SWA/PVC

Conductor Nominal thickness

of insulation

mm

Thickness of

separation sheath

mm

Approx. cable diameter

under wire mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx. weight (Cu)

kg/km

Approx. weight (AL)

kg/km

Nom. Cross Shape

Diameter

mm

sectional

area sqmm

25 5.9 3.6 1.3 40 2.5 2.6 52 3640 3160 35 7.0 3.6 1.4 42 2.5 2.7 55 4140 3470 50 8.0 3.6 1.4 44 2.5 2.8 57 4740 3770 70 9.7 3.6 1.5 48 2.5 2.9 61 5660 4310 95 Compact 11.4 3.6 1.6 52 2.5 3.00 65 6730 4900

120 round 12.8 3.6 1.6 55 2.5 3.1 68 7700 5380 150 stranded 14.3 3.6 1.7 59 2.5 3.3 72 8860 5970 185 15.8 3.6 1.8 62 3.15 3.4 77 9600 6030 240 18.3 3.6 1.9 68 3.15 3.6 83 11640 7010 300 20.5 3.6 2.0 72 3.15 3.8 88 13800 8000

400 23.3 3.6 2.1 79 3.15 4.0 95 17200 9480 19/33 kV Three Core XLPE/SWA/PVC, Wire Armoured Power Cable, Type XLPE/SWA/PVC

Conductor Nominal thickness

of insulation

mm

Thickness of

separation sheath

mm

Approx. cable diameter

under wire mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx. weight (Cu)

kg/km

Approx. weight (AL)

kg/km

Nom. Cross Shape

Diameter

mm

sectional area sqmm

25 5.9 8.2 1.7 60 3.15 3.4 75 5470 4980 35 7.0 8.2 1.8 63 3.15 3.5 78 6000 5330 50 8.0 8.2 1.8 65 3.15 3.5 80 6660 5700 70 9.7 8.2 1.9 69 3.15 3.7 85 7660 6310 95 Compact 11.4 8.2 2.0 73 3.15 3.8 89 8770 6940

120 round 12.8 8.2 2.0 76 3.15 3.9 92 9840 7520 150 stranded 14.3 8.2 2.1 79 3.15 4.0 96 11100 8210 185 15.8 8.2 2.2 83 3.15 4.1 99 12470 8210 240 18.3 8.2 2.3 88 3.15 4.3 105 14680 10050

300 205 8.2 2.4 93 3.15 4.5 110 16990 11190

Page 35: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 34

Some Of The Various Utility Specified Cables

XLPE

600/1000 V Four Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC

Conductor Nom. thickness

of insulation

mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.)

kg/km

Nom. Cross

sectional area

sqmm

Shape

Diameter

mm

25

Compact round

stranded

5.9 1.1 1.0 1.4 1.1 28.1 2.0 2.1 37 3820 3180 35 7.0 1.1 1.1 1.5 1.2 31.2 2.0 2.2 40 4640 3740 50 8.0 1.2 1.1 1.6 1.2 34.5 2.0 2.4 44 5730 4450 70 9.7 1.3 1.2 1.7 1.3 39.8 2.5 2.6 50 7730 5940 95 11.4 1.3 1.3 1.8 1.4 44.5 2.5 2.7 55 9550 7120

120 12.8 1.4 1.4 2.0 1.5 49.0 2.5 2.9 60 10480 8040 150 14.3 1.6 1.5 2.1 1.6 54.2 2.5 3.1 66 13680 9840 185 15.8 1.8 1.6 2.2 1.7 59.5 2.5 3.3 71 16200 11460 240 18.3 1.9 1.7 2.5 1.9 67.0 3.15 3.6 81 20900 14760 300 20.5 2.0 1.8 2.6 2.0 73.6 3.15 3.8 88 25020 17330

400 23.3 2.3 2.0 2.9 2.2 83.1 3.15 4.1 98 - 21360 6.35/11 kV Three Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC

Conductor Nom. thickness

of insulation

mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.)

kg/km

Nom. Cross

sectional area

sqmm

Shape

Diameter

mm

25

Compact

round stranded

5.9 3.6 1.3 1.9 1.5 45.9 2.5 2.8 57 7390 6910 35 7.0 3.6 1.4 1.9 1.5 48.6 2.5 2.9 60 8230 7560 50 8.0 3.6 1.4 2.0 1.6 51.1 2.5 3.0 63 9220 8260 70 9.7 3.6 1.5 2.1 1.6 55.3 2.5 3.1 67 10780 9430 95 11.4 3.6 1.6 2.2 1.7 59.50 2.5 3.3 72 12490 10660

120 12.8 3.6 1.6 2.3 1.8 62.9 3.15 3.5 77 14080 11780 150 14.3 3.6 1.7 2.4 1.9 66.7 3.15 3.6 81 16710 13820 185 15.8 3.6 1.8 2.5 1.9 70.4 3.15 3.7 85 18740 15170 240 18.3 3.6 1.9 2.7 2.0 76.6 3.15 3.9 92 22100 17470 300 20.5 3.6 2.0 2.9 2.2 82.0 3.15 4.1 97 25500 19710

400 23.3 3.6 2.1 3.0 2.3 88.9 3.15 4.1 105 - 22860 19/33 kV Three Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC

Conductor Nominal thickness

of insulation

mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.)

kg/km

Nom. Cross

sectional area

sqmm

Shape

Diameter

mm

25

Compact round

stranded

5.9 8.3 1.7 2.5 1.9 69.1 3.15 3.7 84 14370 13380 35 7.0 8.3 1.8 2.6 2.0 71.9 3.15 3.8 87 15470 14790 50 8.0 8.3 1.8 2.7 2.0 74.3 3.15 3.9 89 16660 15690 70 9.7 8.3 1.9 2.8 2.1 78.5 3.15 4.0 94 18600 17250 95 11.4 8.3 2.0 2.9 2.2 82.8 3.15 4.1 98 20730 18900

120 12.8 8.3 2.0 3.0 2.2 86.2 3.15 4.3 102 22630 20300 150 14.3 8.3 2.1 3.1 2.3 89.9 3.15 4.4 106 24770 21870

185 15.8 8.3 2.2 3.2 2.4 93.7 3.15 4.5 110 27080 23500

Page 36: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 35

Some Of The Various Utility Specified Cables

XLPE

6.35/11 kV Single Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC Conductor Nom.

thickness of

insulation mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.) kg/km

Nom. cross

sectional area

sqmm

Shape Diameter mm

25

Compact round

stranded

5.9 3.6 0.9 1.3 1.0 23.4 1.6 2.0 31 2620 2460

50 8.0 3.6 1.0 1.3 1.1 25.8 2.0 2.1 35 3400 3090

95 11.4 3.6 1.0 1.4 1.1 29.7 2.0 2.2 39 4480 3880

150 14.3 3.6 1.1 1.5 1.2 33.0 2.0 2.3 43 5590 4650

240 18.3 3.6 1.2 1.7 1.3 37.6 2.5 2.5 49 7680 6170

400 23.3 3.6 1.3 1.8 1.4 43.3 2.5 2.7 55 10400 7880

630 30.2 3.6 1.4 2.0 1.6 51.2 2.5 3.0 63 14400 10430

1000 39.0 3.6 1.6 2.3 1.8 61.3 3.15 3.4 75 21300 14990

12.7/22 kV Single Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC

Conductor Nom. thickness

of insulation

mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.) kg/km

Nom. cross

sectional area

sqmm

Shape Diameter mm

25

Compact round

stranded

5.9 5.7 1.0 1.4 1.1 28.2 2.0 2.2 37 3630 2460

50 8.0 5.7 1.1 1.5 1.2 30.6 2.0 2.2 40 4300 3090

95 11.4 5.7 1.1 1.6 1.2 34.5 2.0 2.4 44 5460 3880

150 14.3 5.7 1.2 1.7 1.3 37.8 2.5 2.5 49 7000 4650

240 18.3 5.7 1.3 1.8 1.4 42.4 2.5 2.7 54 8860 6170

400 23.3 5.7 1.4 1.9 1.5 48.1 2.5 2.9 60 11700 7880

630 30.2 5.7 1.5 2.2 1.7 56.0 2.5 3.2 68 15900 10430

1000 39.0 5.7 1.7 2.4 1.8 66.1 3.15 3.6 80 23040 14990

19/33 kV Single Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC

Conductor Nom. thickness

of insulation

mm

Thickness of

separation sheath

mm

Thickness of

lead sheath

mm

Thickness of

separation sheath

mm

Approx cable

diameter under

armour mm

Diameter of

armour wire mm

Thickness of

outer sheath

mm

Approx. overall cable

diameter mm

Approx weight (Cu)

kg/km

Approx. weight (AL.) kg/km

Nom. cross

sectional area

sqmm

Shape Diameter mm

25

Compact

round stranded

5.9 8.3 1.1 1.6 1.2 34.1 2.0 2.4 44 4830 4670

50 8.0 8.3 1.2 1.6 1.3 36.6 2.5 2.5 47 5900 5600

95 11.4 8.3 1.2 1.7 1.4 40.4 2.5 2.6 52 7200 6600

150 14.3 8.3 1.3 1.8 1.4 43.8 2.5 2.7 55 8470 7530

240 18.3 8.3 1.4 1.9 1.5 48.4 2.5 2.9 60 10450 8940

400 23.3 8.3 1.5 2.1 1.6 54.1 2.5 3.1 66 13480 10960

630 30.2 8.3 1.6 2.3 1.8 62.0 3.15 3.4 76 18640 14670

1000 39.0 8.3 1.8 2.6 2.0 72.1 3.15 3.8 87 25340 19030

Page 37: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 36

Some Of The Various Utility Specified Cables

XLPE

6.35/11 kV Single Core XLPE/LC/DWA/PVC, Double Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/DWA/PVC Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km

25 5.9 3.6 0.9 1.3 1.0 23.4 1.6 2.1 35 2660 2500

50 8.0 3.6 1.0 1.3 1.1 25.8 2.0 2.2 39 3490 3170

95 11.4 3.6 1.0 1.4 1.1 29.7 2.0 2.3 43 4570 3970

150 Compact 14.3 3.6 1.1 1.5 1.2 33.0 2.0 2.5 47 5690 4740

240 round 18.3 3.6 1.2 1.7 1.3 37.6 2.5 2.7 54 7800 6280

400 stranded 23.3 3.6 1.3 1.8 1.4 43.3 2.5 2.9 60 10540 8020

630 30.2 3.6 1.4 2.0 1.6 51.2 2.5 3.2 68 14610 10640

1000 39.0 3.6 1.6 2.3 1.8 61.3 3.15 3.6 82 21630 15320

12.7/22 kV Single Core XLPE/LC/DWA/PVC, Double Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/DWA/PVC Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km

25 5.9 5.7 1.0 1.4 1.1 28.2 2.0 2.3 42 3700 3540

50 8.0 5.7 1.1 1.5 1.2 30.6 2.0 2.4 44 4380 4060

95 11.4 5.7 1.1 1.6 1.2 34.5 2.0 2.5 48 5550 4950

150 Compact 14.3 5.7 1.2 1.7 1.3 37.8 2.5 2.7 54 7160 6210

240 round 18.3 5.7 1.3 1.8 1.4 42.4 2.5 2.9 59 9000 7490

400 stranded 23.3 5.7 1.4 1.9 1.5 48.1 2.5 3.1 65 11880 9350

630 30.2 5.7 1.5 2.2 1.7 56.0 2.5 3.3 74 16110 12140

1000 39.0 5.7 1.7 2.4 1.8 66.1 3.15 3.8 87 23360 17060

19/33 kV Single Core XLPE/LC/SWA/PVC, Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/SWA/PVC Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km

25 5.9 8.3 1.1 1.6 1.2 34.1 2.0 2.5 48 4890 4750

50 8.0 8.3 1.2 1.6 1.3 36.6 2.5 2.7 53 6030 5710

95 11.4 8.3 1.2 1.7 1.4 40.4 2.5 2.8 57 7350 6750

150 Compact 14.3 8.3 1.3 1.8 1.4 43.8 2.5 2.9 60 8660 7710

240 round 18.3 8.3 1.4 1.9 1.5 48.4 2.5 3.1 65 10630 9110

400 stranded 23.3 8.3 1.5 2.1 1.6 54.1 2.5 3.3 72 13650 11130

630 30.2 8.3 1.6 2.3 1.8 62.0 3.15 3.6 83 18980 15000

1000 39.0 8.3 1.8 2.6 2.0 72.1 3.15 4.0 94 25720 19410

Page 38: Xlpe Cable Amps Rating

FEDERAL POWER SDN BHD | WWW.FEDERALPOWER.COM.MY 37

Some Of The Various Utility Specified Cables

XLPE

600/1000 V Four Core XLPE/LC/DWA/PVC, Double Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/DWA/PVC

Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km 25 5.9 1.1 1.0 1.4 1.1 28.1 2.0 2.3 41 4000 3360

35 7.0 1.1 1.1 1.5 1.2 31.2 2.0 2.4 44 4840 3940

50 8.0 1.2 1.1 1.6 1.2 34.5 2.0 2.5 48 5940 46660

70 Compact 9.7 1.3 1.2 1.7 1.3 39.8 2.5 2.8 56 8010 6220

95 round 11.4 1.3 1.3 1.8 1.4 44.5 2.5 2.9 61 9870 7440

120 stranded 12.8 1.4 1.4 2.0 1.5 49.0 2.5 3.1 66 11710 8640

150 14.3 1.6 1.5 2.1 1.6 54.2 2.5 3.3 71 14000 10160

185 15.8 1.8 1.6 2.2 1.7 59.5 2.5 3.4 77 16600 11860

240 18.3 1.9 1.7 2.5 1.9 67.0 3.15 3.8 88 21420 12570

300 20.5 2.0 1.8 2.6 2.0 73.6 3.15 4.0 95 25600 17900

400 23.3 2.3 2.0 2.9 2.2 83.1 3.15 4.4 105 - 21990 6.35/11 kV Three Core XLPE/LC/DWA/PVC, Double Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/DWA/PVC

Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km 25 5.9 3.6 1.3 1.9 1.5 45.9 2.5 3.0 63 7730 7250

35 7.0 3.6 1.4 1.9 1.5 48.6 2.5 3.1 66 8650 7980

50 8.0 3.6 1.4 2.0 1.6 51.1 2.5 3.2 68 9650 8680

70 Compact 9.7 3.6 1.5 2.1 1.6 55.3 2.5 3.3 73 11200 9860

95 round 11.4 3.6 1.6 2.2 1.7 59.5 2.5 3.5 77 12960 11130

120 stranded 12.8 3.6 1.6 2.3 1.8 62.9 3.15 3.7 84 15400 13070

150 14.3 3.6 1.7 2.4 1.9 66.7 3.15 3.8 88 17300 14400

185 15.8 3.6 1.8 2.5 1.9 70.4 3.15 3.9 92 19330 15760

240 18.3 3.6 1.9 2.7 2.0 76.6 3.15 4.2 98 22770 18130

300 20.5 3.6 2.0 2.9 2.2 82.0 3.15 4.3 104 - 20380

400 23.3 3.6 2.1 3.0 2.3 88.9 3.15 4.6 112 - 23600

19/33 kV Three Core XLPE/LC/DWA/PVC, Double Wire Armoured,Lead Covered Power Cable, Type XLPE/LC/DWA/PVC

Conductor Nom. Thickness Thickness Thickness Approx cable Diameter Thickness Approx. Approx Approx.

Nom. cross thickness of of of diameter of of overall weight weight

sectional Diameter of separation lead separation under armour outer cable (Cu) (AL.) area Shape insulation sheath sheath sheath armour wire sheath diameter

sqmm mm mm mm mm mm mm mm mm mm kg/km kg/km 25 5.9 8.3 1.7 2.5 1.9 69.1 3.15 3.9 90 14960 14480

35 7.0 8.3 1.8 2.6 2.0 71.9 3.15 4.0 93 16130 15450

50 Compact 8.0 8.3 1.8 2.7 2.0 74.3 3.15 4.1 96 17320 16350

70 round 9.7 8.3 1.9 2.8 2.1 78.5 3.15 4.2 100 19270 17920

95 stranded 11.4 8.3 2.0 2.9 2.2 82.8 3.15 4.4 105 21400 19570

120 12.8 8.3 2.0 3.0 2.2 86.2 3.15 4.5 109 23300 20990

150 14.3 8.3 2.1 3.1 2.3 89.9 3.15 4.6 113 25500 22600