wireless data logger for humidity and temperature … · wireless data loggers for humidity and...

6
Wireless systems WIRELESS DATA LOGGERS FOR HUMIDITY AND TEMPERATURE • HygroClip2 probes for humidity and temperature measurement • Wireless frequency: 433.92 or 915 MHz (USA) for optimized communication • Highest possible measuring accuracy: ±0.8 %RH and 0.1 °C • Outstanding repeatability • Battery life up to 6 years • Large storage capacity of up to 500,000 measured values • Transmission distance up to 300 meters • With USB or Ethernet receiver WIRELESS DATA LOGGER FOR HUMIDITY AND TEMPERATURE PROBES.

Upload: phungthuy

Post on 06-May-2018

229 views

Category:

Documents


4 download

TRANSCRIPT

Wireless systems

W I R E L E S S d ATA L O g g E R S F O R H u M I d I T Y A N d T E M p E R AT u R E

• HygroClip2probesforhumidityandtemperaturemeasurement

• Wirelessfrequency:433.92or915MHz(USA)

foroptimizedcommunication

• Highestpossiblemeasuringaccuracy:±0.8%RHand0.1°C

• Outstandingrepeatability

• Batterylifeupto6years

• Largestoragecapacityofupto500,000measuredvalues

• Transmissiondistanceupto300meters

• WithUSBorEthernetreceiver

WIRELESS dATA LOggER FOR HuMIdITY ANd TEMpERATuRE pRObES.

Dan Macey
1

WIRELESS SYSTEMWIRELESS SYSTEM

433/915MHz

433/915MHz

SYSTEM OvERvIEW

The wireless data loggers are suitable for a wide range of humidity and temperature monitoring tasks. Wireless transmission - possible over distances of up to 300 m - saves the user wiring costs and the data can be collected and recorded from inaccessible points quickly and easily. Thanks to the combination of wireless transmission and data logging, the greatest possible reliability against failure is insured. Up to 100 devices can be connected and configured via HW4 software using an Ethernet or an USB receiver.

The wireless data loggers are suitable for a wide range of monitoring tasks in meteorology, the food industry, build-ing services equipment, museums, environmental and laboratory technology climate chambers, clean rooms re-search and development, the pharmaceutical and chemical industries, logistics and the textile industry.

bE pREcISE:THE MAIN AdvANTAgES AT A gLANcE.

Receiver

Transmitter

Transmitter

Receiver

WirelessUSBnetwork

WirelessLANnetwork

WIRELESS SYSTEM

REcEIvERS

LAN interfaceApplications

Using an existing Ethernet infrastructure, the LAN interface serves as

an interface between the wireless network and the PC.

Features

• Managesupto100digitalwirelessdataloggers

• ImprovedreceptionperformancecomparedwiththeUSB

wirelessadapter

• Networkconnection:100MBitEthernetLAN(RJ-45)

• Communication:viaTCP/IPprotocol

• Wireless:connectionofexternalSMAantennapossible

• Configurableviawebbrowser

• Housingmaterial:aluminum

• Powersupply:ACmainsadapter

Order code Device type

LAN-INTERFACE LANinterface433.92MHz

LAN-INTERFACE-US LANinterface915MHz(USversion)

Compatible

• Wirelessdataloggers

• Groundplaneantenna

Included

• Shortinstructionmanual

• Standardantenna

• ACmainsadapter

USBwirelessadapter

Applications

TheUSBwirelessadapterservesasaninterfacebetweenthewirelessnetworkandthePC.

Features

• Managesupto100digitalwirelessdataloggers

• Wireless:connectionofexternalSMAantennapossible

• Plug&Play

Order code Device type

LOG-DS-EXT USBwirelessadapter433.92MHz

LOG-DS-EXT-US USBwirelessadapter915MHz(USversion)

Compatible

• Wirelessdataloggers

• Groundplaneantenna

Included

• Shortinstructionmanual

• Standardantenna

WIRELESS SYSTEMWIRELESS SYSTEM

pRObES FOR THE LOg-Hc2.TheHygroClip2probescomeinvariousversions.Youcanfindexactlytheprobeyouneed:fromsimplepluginprobesforhandheldinstruments

anddataloggerstohighlydevelopedcableprobesforhightemperatureandhighpressureapplications.Commontoallisthehighprecisionthe

probesofferthankstoourpatentedAirChip3000.Thistechnologyisexactlywhatmakeseveryprobeinourrangeahigh-endproductfornormal

andindustrialapplications.

Wirelesshumidity/temperaturedataloggers

Thankstothedataloggingfunction,thedataarenotlostintheeventofaninterruptioninwireless

transmissionandcanberetrievedatanytime.

Features

• DigitalprobeinputforconnectionofallROTRONICHygroClip2probes

• Probescanbeinterchangedwithoutfurtheradjustment

• Transmissiondistance:upto300m

• Operatingrange:-40to85°C

• Highstoragecapacity:upto500,000measuredvalueswithserialnumber,timeanddate

• Flashmemoryfordatasecurityinthecaseofpowerfailures

• Long-termrecordingupto6yearswithoutbatteryreplacement

• Datasecurity:PINforactivationanddataaccess

• Plastichousing,white,IP65

Order code Device type

LOG-HC2-RC Wirelesshumidity/temperaturelogger433.92MHz

LOG-HC2-RC-US Wirelesshumidity/temperaturelogger915MHz(USversion)

Contact us if you need assistance in selecting the most suitable probe for your application, we will be pleased to advise you.

Standardclimateprobe

Probe with maximum accuracy for all

climatemeasurements.

Operatingrange-50…100°C,0…100%RH.

Miniprobes

4 and 5 mm probes for measurements in

confinedspacessuchaspackagingetc.and

forbuildingmaterialtests.

Operatingrange-40…85°C,0…100%RH.

Industrialprobe

Probeforprocessapplications

Operatingrange0…100%RH,

-100…200°Cand0…100bar.

Alsoavailableasscrew-inprobe.

Probewithmaximumaccuracy

forallclimatemeasurements.

TRANSMITTERS

WIRELESS SYSTEM

Wirelesstemperaturedataloggers

PT1000temperatureprobeintegratedorremotewith30cmcable

Features

• Accuracy:±0.1Kat0°C

• Temperatureoperatingrange:-40to+85°C

• Highstoragecapacity:upto500,000measuredvalueswithserialnumber,

timeanddate

• Flashmemoryfordatasecurityintheeventofpowerfailures

• Long-termrecordingupto6yearswithoutbatteryreplacement

• Transmissiondistance:upto300m(freefield)withremoteprobe,

100mwithintegratedtemperatureprobe

• Datasecurity:PINforactivationanddataaccess

• Plastichousing,white,IP69(submersible)

Order code Device type

LOG-PT1000-RC Wirelesstemperaturelogger433.92MHz

LOG-PT1000-RC-US Wirelesstemperaturelogger915MHz(USversion)

LOG-PT1000-ET030-RC Wirelesstemperatureloggerwithremoteprobe433.92MHz

LOG-PT1000-30-RC-US Wirelesstemperatureloggerwithremoteprobe915MHz(USversion)

AccESSORY433MHzgroundplaneantenna

Features

• Industrialantennaforimprovedreception

• Suitableforbothindoorandoutdooruse

• Incl.2.5mcoaxialcable(50ohms)andSMAconnector

• Dimensions(ØxH):190mmx460mm

Order code Device type

LOG-AN-GP433 433MHzGroundplaneantenna,cablelength2.5m

LOG-PT1000-RCLOG-PT1000-RC-US

LOG-PT1000-ET030-RCLOG-PT1000-30-RC-US

WIRELESS SYSTEM

5902

6E/2

012-

12

You can find detailed information on our probes at www.rotronic.com. We will also be glad to advise you on the telephone or in our showroom.

ROTRONIC AG, Grindelstrasse 6, CH -

TEcHNIcAL INFORMATION.Radio frequencies.There are two radio frequencies available for

transmissionofthedata:915MHzfortheUSA

and433.92MHzforEuropeandtherestofthe

world. These frequencies are ideal for optimal

datatransmission.

Range.Dependingonthetypeoftransmitterandtypeof

building,rangesofupto300meters.

Data logging/Transmission.Upto500,000measuredvaluescanbestored

inthewirelessdatalogger.Thedataistransmit-

ted and recorded continuously as long as the

wirelessdataloggerislocatedinthevicinityof

areceiver(LANinterface,USBwirelessadapter).

Ifthedistancebetweenthetransmitterandre-

ceiver is too large or the wireless connection is

lost, thedata isnevertheless recorded. In this

wayitisensuredthatnodataislost.

Subj

ectt

ote

chni

calc

hang

ew

ithou

tnot

ice.

Pri

ntin

gan

dot

here

rror

sre

serv

ed.

LOG-HC2-RC-(US) LOG-PT1000-RC-(US) LOG-PT1000-ET030-RC-LOG-PT1000-30-RS-US

Type Digital input for HC2 probes (UART)

Pt1000 temperature probe Pt1000 temperature probewith remote probe

Accuracy Probe dependent ± 0.1 K at 0 °C

Radio frequency 433.92 MHz (US: 915 MHz)

Storage capacity Up to 500,000 measured values

Logging interval 1 min. to 12 h

Power supply Lithium (Li-SOCl2) battery 2400 mAh

Battery life Up to 6 years depending on logging interval

Battery status indicator Via software, recording of battery voltage and internal temperature

Transmission distance Max. 100 m (free field) Max. 300 m (free field)

Data security 4-digit PIN (access code for activation/reading)

Dimensions without probe 140 mm x Ø 20 mm

Software HW4 V3.2 or higher

Order code LOG-HC2-RC LOG-PT1000-RC LOG-PT1000-ET030-RC

Order code (US) LOG-HC2-RC-US LOG-PT1000-RC-US LOG-PT1000-ET-RC-US

LAN interface-(US) USB wireless adapter-(US)

Type 100 MBit Ethernet LAN interface

Local readout device for data logger to PC

Radio frequency 433.92 MHz (US: 915 MHz)

Power supply Via AC adapter, 5 V, min. 200 mA, included in the delivery package

USB power supply via PC

Dimensions 30 mm x 130 mm x 80 mm 15 mm x 77 mm x 20 mm

Software HW4 V3.2 or higher

Order code LAN-INTERFACE LOG-DS-EXT

Order code (US) LAN-INTERFACE-US LOG-DS-EXT-US

Dan Macey