view™ very intelligent early warning hssd detector data sheet · the view™ is an analogue,...

3
The VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER intelligent fire alarm control panels. The unique design of this sensor uses an extremely bright, tightly focused laser diode, with special lens and mirror optics, combined with enhanced AWACS™ algorithms in the NOTIFIER fire control panel, to achieve a signal‑to‑noise ratio allowing smoke detection sensitivity up to 50 times greater than traditional photoelectric technology. In addition, the light beam and algorithms, allow the system to differentiate between dust and smoke particles. Using these algorithms, the VIEW™ system provides drift compensation, three levels of maintenance alert, selection of nine alarm levels and nine pre‑alarm levels. The system includes a self‑learn sensitivity adjustment to set the pre‑alarm level just above the peak levels sensed over extended periods for each sensor’s actual environment. Multiple sensor algorithms permit the control equipment to consider readings from up to six sensors in an area to provide faster detection of incipient fires. The AWACS™ algorithm also includes the ability to add reference sensors, such that smoke particles in the incoming air supply to an area can be compensated for, further reducing the possibility of unwanted alarm. Using a point type analogue addressable sensor, the VIEW™ system inherently does not have transit times from sensing points to a detector, (a factor inherent in aspiration systems) delaying the sensing of a fire condition and since it does not rely on a single sensor for the room, no dilution can occur. A point sensor also enables the control panel to provide the operator with a pinpoint description of where the fire is located rather than a room alarm. Features Alternative to Aspiration Systems Advanced laser light source and patented optical design Sleek low profile design Analogue addressable communications Stable communication technique with high noise immunity Pre‑Alarm sensitivity to 0.07%/m & alarm sensitivity to 0.1%/m Low standby current Rotary decade 01 to 99 address switches Dual LED design provides 360° viewing angle. Visible two‑colour LEDs blink green when the sensor is addressed (optional), steady red for alarm Built‑in functional test switch activated by external magnet Optional relay, isolator, or sounder bases VIEW™ Very Intelligent Early Warning HSSD Detector Data Sheet This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom Phone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888 ISO9001 Design, Manufacture and Supply to Quality Manage‑ ment Systems Certified to ISO9001:1994 Page 1 of 3 ‑ 990‑006_0311 www.notifierfiresystems.co.uk

Upload: others

Post on 04-Sep-2019

14 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: VIEW™ Very Intelligent Early Warning HSSD Detector Data Sheet · The VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER

The VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER intelligent fire alarm control panels.

The unique design of this sensor uses an extremely bright, tightly focused laser diode, with special lens and mirror optics, combined with enhanced AWACS™ algorithms in the NOTIFIER fire control panel, to achieve a signal‑to‑noise ratio allowing smoke detection sensitivity up to 50 times greater than traditional photoelectric technology.

In addition, the light beam and algorithms, allow the system to differentiate between dust and smoke particles. Using these algorithms, the VIEW™ system provides drift compensation, three levels of maintenance alert, selection of nine alarm levels and nine pre‑alarm levels. The system includes a self‑learn sensitivity adjustment to set the pre‑alarm level just above the peak levels sensed over extended periods for each sensor’s actual environment. Multiple sensor algorithms permit the control equipment to consider readings from up to six sensors in an area to provide faster detection of incipient fires. The AWACS™ algorithm also includes the ability to add reference sensors, such that smoke particles in the incoming air supply to an area can be compensated for, further reducing the possibility of unwanted alarm.

Using a point type analogue addressable sensor, the VIEW™ system inherently does not have transit times from sensing points to a detector, (a factor inherent in aspiration systems)

delaying the sensing of a fire condition and since it does not rely on a single sensor for the room, no dilution can occur. A point sensor also enables the control panel to provide the operator with a pinpoint description of where the fire is located rather than a room alarm.

Features• Alternative to Aspiration Systems

• Advanced laser light source and patented optical design

• Sleek low profile design

• Analogue addressable communications

• Stable communication technique with high noise immunity

• Pre‑Alarm sensitivity to 0.07%/m & alarm sensitivity to 0.1%/m

• Low standby current

• Rotary decade 01 to 99 address switches

• Dual LED design provides 360° viewing angle.

• Visible two‑colour LEDs blink green when the sensor is addressed (optional), steady red for alarm

• Built‑in functional test switch activated by external magnet

• Optional relay, isolator, or sounder bases

VIEW™ Very Intelligent Early Warning HSSD Detector Data Sheet

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888

ISO9001Design, Manufacture and

Supply to Quality Manage‑ment Systems Certified to

ISO9001:1994

Page 1 of 3 ‑ 990‑006_0311 www.notifierfiresystems.co.uk

Page 2: VIEW™ Very Intelligent Early Warning HSSD Detector Data Sheet · The VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER

SpecificationsVIEW FSL-751E Mechanical Specification

• Height: 43mm installed in B501AP base • Diameter: 104mm installed in B501AP base • Weight: 102g (inc base) • Max Wire Gauge for Terminals: 2.5mm2 • Colour: Ivory

Electrical Specification

• Operating Voltage Range: 15 to 32Vdc

• Max. Standby Current: 230μA @ 24Vdc (no communications) / 255μA @ 24Vdc (LED blink enabled, once every 5 seconds)

• Max. Alarm Current: 6.5 mA @ 24VDC (with LED enabled)

• Loop resistance using the B501AP: 40ohm max.

Environmental Specifications • Temperature Range: ‑10°C to +60°C†

• Humidity: 10 to 93% relative humidity (non‑condensing)

VIEWTM High Sensitivity Smoke Detector - FSL-751EThe VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER intelligent fire alarm control panels.

The unique design of this sensor uses an extremely bright, tightly focused laser diode, with special lens and mirror optics, combined with enhanced AWACS™ algorithms in the NOTIFIER fire control panel, to achieve a signal‑to‑noise ratio allowing smoke detection sensitivity up to 50 times greater than traditional photoelectric technology.

† Do not install detectors in locations where normal ambient temperature exceeds 50°C

Laser Diode & IntegralLens Assembly

Smoke Direction Baffles

Sensing Chamber

Laser Beam

Test LED

Light Trap

Photo ReceiverProtective Housing

RF Shield

Chamber Cover

Insect Screen

Circuit Board

Photo Diode

Housing Interlocks (4)

Smoke Sensing ChamberCover/Screen

Spring Contact ToInsect Screen

Smoke Sensing Chamber Base

Contacts To Mounting Brackets

Sensor Base

Mirror (See Detail)

Page 2 of 3 ‑ 990‑006_0311 www.notifierfiresystems.co.uk

Page 3: VIEW™ Very Intelligent Early Warning HSSD Detector Data Sheet · The VIEW™ is an analogue, addressable, low profile high sensitivity smoke sensor designed for use with NOTIFIER

Product Range at a Glance

Isolator Colour Part NumberVIEW™ high sensitivity analogue addressable laser smoke sen‑sor with twin LED’s, insect resistant screen, removable cover for field cleaning, direct decade 01‑99 address entry, LED output and device blink option.

Ivory FSL‑751E US

Analogue sensor base with SEMS screw connections for isolated and non‑isolated detectors and address identification label n/a Ivory B501AP‑IV

Deep analogue sensor base with built in FET isolator Ivory B524IEFT‑1

Deep analogue sensor base with built in relay Ivory B524RTE

Wet Base shroud for use with standard bases to allowcondensation run off and rear seal. Conduit entry only. n/a Ivory WB‑1AP‑IV

Recess mounting kit suitable for flush mounting bases into a false ceiling. n/a Ivory RMK400

Surface mount kit for detectors. n/a Ivory SMK400EAP‑IV

Charles AvenueBurgess HillW. SussexRH15 9UF

T: +44 (0) 116 246 2255F: +44 (0) 116 246 2210E: [email protected]

Page 3 of 3 ‑ 990‑006_0311