REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
D6.1
Version: AUGUST 2016
NETWORK LAYOUT
TYPICAL URBAN WATER SUPPLY
Lot 1
Lot 2
Lot 6
Lot 7
Lot 8
Lot 910Lot
Lot 11
Lot 12
Lot 14
Lot 16 Lot 15
Lot 18
Lot 13
Valve Indicator (See Drawing D6.4)
(See Drawing D6.11)
or Flush Out Valve
(See Drawing D6.3)
with Hydrant
(See Drawing D6.5)
Valve Indicator (See Drawing D6.4)
Access Strip
H
H
Valve Indicator (See Drawing D6.4)
to 5 lots or more)
(Where a ROW is
DN 63 Ridermain
DN
63 R
iderm
ain
Wate
rmain
Ridermain
(See Drawing D6.4)
Valve Indicator
Watermain
This Valve between the two branches
Standard C.I. valve box
surrounds
Pre-cast concrete
Sand backfill Original excavation
75
100 100230
100
100
160
Direction of Main
of Main
Direction
230160
300255
145
150
D6.2
Version: AUGUST 2016REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
SLUICE VALVE DETAILS
piece 150mm pipe
Riser fabricated from one
(- min 1, max. 3)
Cast iron valve packers
Backfill as per D3.2.3
sawcut existing seal
When resetting,
compacted (See Note 1)
'Hotmix' asphalt well
+5mm, -5mm Grass Berm
+0mm, -5mm Pavement
Tolerance: +10mm, -0mm Footpath
RECTANGULAR VALVE BOX AND COVER
(with concrete surroundings for grass berms)
NOTES:
b) the finished surface shall match the surrounding
a) the TNZ backfill can be replaced with pitsand
In Berm Areas1.
NOT TO SCALE
hydrant box
Standard C.I.
Hydrant tee
75
max. 3)
packers (- min 1,
Cast iron valve
50 - 2
00
base (100mm)
Heavy duty concrete
110 110430
110
110
280
Direction of Main
of Main
Direction
430280
pipe
PVC surround
Concrete or
is a 375mm dia.
An alternative
Sand backfill
145
150
per D3.3.1
Backfill as
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
FIRE HYDRANT DETAILS D6.3
Version: AUGUST 2016
NOT TO SCALE
NOTES:
b) the finished surface shall match the surrounding
a) the TNZ backfill can be replaced with pitsand
In Berm Areas1.
(with concrete surroundings for grass berms)
HYDRANT BOX AND COVER
thick)
surrounds (100mm
Pre-cast concrete
+5mm, -5mm Grass Berm
+0mm, -5mm Pavement
Tolerance: +10mm, -0mm Footpath
compacted (See Note 1)
'Hotmix' asphalt well
existing seal
When resetting, sawcut
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION Version: AUGUST 2016
D6.4VALVE INDICATOR AND POST DETAILS
NOT TO SCALE
NOTES:
plates and inserted as required.
All text and numbers are printed on seperate
plates to half round post.
Use stainless steel fasteners to attach marker
and site on the property boundary.
cut in half. Order a № 1 - 130 wide x 2700 long)When no fence is available, use half round post
3.
2.
1.
from Council system.
Running number obtain
Nominal diameter of pipe
- Gate (GV)
- Sluice (SV) or
Type of Valve.
0.2m left
Position of Valve.
2.1m back
130
800
550
round post.
Ground treated half
nailed to foot of post.
50 x 50 survey stake
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
D6.5
Version: AUGUST 2016
RIDERMAIN IN A CUL-DE-SAC
NOTES:
by suitably sized tapping band
Tapped gibault may be replaced
NOT TO SCALE
Ridermain
450 Min.
1000 Max.
Concrete thrust block
connections see D5.7
Metered / Unmetered
150mm pipe
from one piece
Riser fabricated
300 M
ax.
500
mm Min. coversee Drawing D6.3
For details of hydrant installation
surround
Concrete
PLAN
NOTE:
1.
the tapping saddle prior to the installation of other fittings.
gunmetal self-tapping ferrule shall be installed directly on
When a connection is made to an existing watermain, a
Adaptor
DN25 MDPE DN25 MDPE
fitting or tapping saddle
Ridermain 'tee' joint
to Toby Box
Angle vertically
DN20 Ferrule
Point of supply
Isolating valve
Lid
Flow
Manifold Box
300mm 300mm Tail
200mm Wide
250mm LG x
50
mm M
IN
300300
Hig
h
350
mm
than 600mm
Radius not less
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION Version: AUGUST 2016
D6.6AND RESTRICTED FLOW SUPPLIES
SERVICE CONNECTIONS - ON DEMAND
20mm METERED AND UNMETERED
and ferrule
Principal main tapping band
flexible coupling.
top) and lid secured to surround via stainless steel
with blue moulded lid (with 'WATER' moulded into
Moulded manifold box with base and mounting lugs
25mm x ¾" BSP thread
Male threaded adaptor
contaminants
prevent ingress of
Male Adaptor, sealed to
DN25 MDPE Pipe for customer
Boundary
Road
Boundary
Road
BSP ¾" thread both ends.
with dual check valve, female
20mm manifold assembly
25mm x ¾" BSP thread
Male threaded adaptor
Gate Valve
restricted flow supply
Fit flow restrictor for
DN25 MDPE Pipe
Council Supply
(Where required)
Class 'C' Meter
to specification under pipe
Backfill to be compacted
OR
to maintain cover)
Saddle (may be horizontal
25mm on 63mm Tapping
NOT TO SCALE
NOTES:
3.
2.
1.
and residential where requird by Council.
Meters installed on all connections serving commercial, industrial zoned lots
Manifolds with pressure caps to be installed on all DN20 domestic connections.
band or tapped gibault. Tee to be placed horizontally to maintain standard cover.
Connections from ridermains to be made using 63 x 63 MDPE tee in place of a tapping
In-line or one-sided arrangements permitted to suit site conditions.
230
DN63 MDPE fittings
DN63 MDPE
MDPE for DN25 connections
connections and DN32
DN25 MDPE for DN20
suit number of connections
PE Manifold size varied to
300
300
Approved tapping band
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
D6.7
Version: AUGUST 2016
SERVICE CONNECTIONS ON DEMAND
DN20 METERED & UNMETERED
Road Boundary (point of supply)
DN50 Resilient Seat Gate Valve
band onto Watermain
Tapped gibault or Tapping
Unit 1 / Lot 1 connection on LHS
ingress of contaminants
Male Adaptor, sealed to prevent
DN20 connections
dual check valve, for all
Manifold assembly with
Isolating valves
Shut off valve
box and surround
Standard C.I. valve
MANIFOLD ASSEMBLY FOR MULTIPLE WATER CONNECTIONS
NOT TO SCALE
NOTES:
5.
4.
3.
2.
1.
within the Lot, to be owned and maintained by the property owner.
Any backflow requirements necessary to comply with the NZ Building Code G12 shall be installed
In new installations tapping band may be replaced by cut-in tee, tapped gibault or other as directed.
Meter box sized to contain all fittings.
Isolation washers and gaskets to be used between components of dissimilar metals.
minimum 5 times pipe diameter.
Upstream and downstream spacing in accordance with manufacturer's specification or otherwise
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
NOT TO SCALE
D6.8
Version: AUGUST 2016
DN50 METER CONNECTION
Meter box - See Note 3
Valve
Watermain
of connection
See Detail A for plan
ValveTo customer
Point of supply
Lid
See Note 1
300mm
230
Boundary
Road
See Note 1
DETAIL A
DN 80 or larger)
(or cut-in tee on
Tapping Band
NOTES:
property owner.
to be owned and maintained by the
G12 shall be installed within the Lot,
to comply with the NZ Building Code
Any backflow requirements necessary
Meter box sized to contain all fittings.
stainless brackets.
Display to be remote mounted with
chamber wall (2.5mm polythene)
around pipe where it passes through
Protective membrane to be wrapped
dissimilar metals.
used between components of
Isolation washers and gaskets to be
5 times pipe diameter.
specification or otherwise minimum
in accordance with manufacturer's
Upstream and downstream spacing
6.
5.
4.
3.
2.
1.
D6.9
Version: AUGUST 2016
NOT TO SCALE
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
DN100 & DN150 METER CONNECTIONS
Gibault joint
Flanged gibault joint
PVC pipe
Point of supply
PVC pipe
Lid
300mm 300mm
Road B
oundary
joint
Flanged socket
display
Remote
Meter box - See Note 5
PVC pipe
PLAN VIEW
(DN100 Connection shown)
(DN100 Connection shown)
SECTIONAL ELEVATION
or similar
Aquamaster meter(Refer Drawing D6.2)
Sluice valve
D6.10WATER CONNECTIONS LAYOUT
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION Version: AUGUST 2016
SINGLE PROPERTY SINGLE PROPERTY
2 to 4 CUSTOMERS 2 to 4 CUSTOMERS
Accessway - Ridermain
5+ CUSTOMERSSingle Lot - Ridermain
5+ CUSTOMERS
Point of supply at boundary
Service Pipe
Water Main
at boundary
Point of supply
Service Pipe
Water Mainmeter box
share a single
Manifolds, may
at boundary
Point of supply
Service Pipe
Water Main
Manifold
Supply Pipe
etc. not shown
Supply Pipe
at boundary
Point of supply
Fire Supply
Property boundaries
boundaries'
at 'Customer
Point of supply
Water Main
DN50 Ridermain
at end of line
Flushing Valve
Service Line
Service Line
at boundary
Point of supply
DN50 Ridermain
Water Mainby council)
required
(maybe
Flow Meter
Council OwnershipKEY: Private Ownership Manifold Flow Meter
Version: AUGUST 2016REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION
NOT TO SCALE
D6.11FLUSH OUT VALVE ASSEMBLY
and threaded end plug
63mm female threaded adaptor
box
Standard meter
hydrant surrounds
Precast concrete
50
75min
100
75
75
max.
150
concrete base
Heavy duty
DN 63 MDPE ridermain
DN50 gate valve
with fittings
DN63 MDPE pipework
FOOTPATH FORCED AT BOUNDARY
FOOTPATH CENTRAL (PREFERRED OPTION)
FOOTPATH AT KERB
NOTES:
2.
1.
= 600mm below finished level.
Minimum depth for all Services
Trench Details.
Also see Vol.5 WDC14 Shared
Boundary
Po
wer
Gas
Water
Gas
Po
wer
Water
Carriageway
Gas
Po
wer
Water
4500 (min)
4500 (min)
4500 (min)
1000
Carriageway
Footpath
Footpath
min
500
Min.
500
Footpath
Min.
500
Street light column
Batter drainBoundary
300 min
300 min
600
1000-1200
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION Version: AUGUST 2016
D6.12
NOT TO SCALE
TRANSPORT CORRIDOR
LOCATION OF SERVICES IN
Co
mm
unications
(Alternate sides of street)
H.T. Duct if required
Communications or
Co
mm
unications
Co
mm
unications
1200 min*1000 min
light column is located
*1500 where tree or
Waste
water
Storm
water or
Street light column
Street light column or tree
Boundary
Boundary
Waste
water
Storm
water or
Batter drain
Batter drain
�Deepest at ro
ad
�Deepest at ro
ad
OPTION 'A'
OPTION 'B'
REGIONAL INFRASTRUCTURE TECHNICAL SPECIFICATION Version: AUGUST 2016
NOT TO SCALE
D6.13FOR RIGHT OF WAY / SHARED ACCESSWAY
SHARED TRENCH STANDARD DETAIL
Other services
Other services
Other services
tracer tape
Blue metallic
Water pipe
Water pipe
tracer tape
Blue metallic
650 Min.
200
200
650 Min.
400 Min.
400 Min.