SAVAIR ENERGY LTD. Technical Queries: SEL-TQ-FS001-01 PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset. PLANT: ETP Jhalora Effluent transfer pump VENDOR: FLOWSERVE Sr. Parameters ONGC-ES Compliance By Vendor SAVAIR REMARKS C&T reply 1 Manufacturer Name Flowserve 2 Model No. 65-40 CPX315 3 QTY 2 Nos Vendor to Comply yes 4 Capacity (Normal) 60 m3/hr Vendor to Comply yes 5 Capacity (Rated) 60 m3/hr 60 m3/hr 6 Head (meters) 150 m 150 m 7 Discharge pressure 15 kg/cm2g Vendor to Comply yes 8 Suction Connection (Site:4") 65 mm/150#/RF 9 Discharge Connection (Site:3") 40 mm/150#/RF 10 Rated Speed 1450/2900 Rpm. 2960 Vendor to Comply yes 11 Efficiency of Pump 49.90% 12 Rated Power (KW) 49 Kw 13 Driver Power (kW) 75 kW 14 Liquid Handled 15 Pump Should be confirm ISO 2858/DIN 5199/Din 2456 16 Operating Temperature Deg C. up to 80 Deg c. 17 Arrow Of Pump Rotation on Casing By Vendor A Material of construction 1 CASE SS316 (ASTM 743 Gr CF8M) A315 CF8M 2 IMPELLER SS316 (ASTM 743 Gr CF8M) A890 GR.A1 (DUPLEX) 3 SHAFT SS316 (ASTM 276 type 316) SS316 Vendor to Comply yes 4 BASEPLATE M.S FABRICATED Vendor to Comply 5 SHAFT SLEEVE SS (ASTM 743 Gr CF8) SS316 Vendor to Comply SS316 6 WEAR RING SS316 /(ASTM 743 Gr CF8M) NA Vendor to Comply Not applicable 7 Gland For packing SS 316 (ASTM 743 Gr CF8M) 8 Bearing Housing CI (ASTM 48) DI 9 Casing Gasket 10 Gland Packing 11 Stage Single 12 Casing type single stage/Volute Vendor to Comply yes 13 Mounting Vendor to Comply Foot 14 Split Vendor to Comply Radial split 15 Impeller Diameter- RATED 314 16 MAXIMUM 320 17 MINIMUM 256 18 Bearing type & No. DE/NDE Vendor to Comply 6309 / 3309 19 Lubrication system oil 20 Packing type (size & No.) chesterton 21 Coupling type / Mfr Flexible spacer / Rathi 22 Sound Level Vendor to Comply yes 23 Weight & overall dimensions Vendor to Comply later 24 Performance characteristics of pump E591/0129/2 25 Accessories of pump a pressure guage at suction Vendor to Comply not considered Effluent water with dissolved chemicals/minerals & Traces of crude oil Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808) MS fabricated epoxy painted Compressed non-asbestos fiber TIWA teflon impreganated white non asbestos/graphite impregnated less than 90dba at a sdistance 1 mtr from pump 3" dial jelly filled, stem mounted range 5m to 10m

Upload: alvin-smith

Post on 27-Oct-2015

68 views

Category:

Documents


4 download

DESCRIPTION

TQ

TRANSCRIPT

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-01

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT: ETP Jhalora Effluent transfer pump VENDOR: FLOWSERVE

Sr. Parameters ONGC-ES Compliance By Vendor SAVAIR REMARKS C&T reply1 Manufacturer Name Flowserve2 Model No. 65-40 CPX3153 QTY 2 Nos Vendor to Comply yes4 Capacity (Normal) 60 m3/hr Vendor to Comply yes5 Capacity (Rated) 60 m3/hr 60 m3/hr6 Head (meters) 150 m 150 m7 Discharge pressure 15 kg/cm2g Vendor to Comply yes8 Suction Connection (Site:4") 65 mm/150#/RF9 Discharge Connection (Site:3") 40 mm/150#/RF

10 Rated Speed 1450/2900 Rpm. 2960 Vendor to Comply yes11 Efficiency of Pump 49.90%12 Rated Power (KW) 49 Kw13 Driver Power (kW) 75 kW

14 Liquid Handled

15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M) A315 CF8M2 IMPELLER SS316 (ASTM 743 Gr CF8M) A890 GR.A1 (DUPLEX)3 SHAFT SS316 (ASTM 276 type 316) SS316 Vendor to Comply yes

4 BASEPLATE M.S FABRICATED Vendor to Comply

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8) SS316 Vendor to Comply SS3166 WEAR RING SS316 /(ASTM 743 Gr CF8M) NA Vendor to Comply Not applicable7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48) DI

9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage Single12 Casing type single stage/Volute Vendor to Comply yes13 Mounting Vendor to Comply Foot14 Split Vendor to Comply Radial split15 Impeller Diameter- RATED 31416 MAXIMUM 32017 MINIMUM 25618 Bearing type & No. DE/NDE Vendor to Comply 6309 / 330919 Lubrication system oil20 Packing type (size & No.) chesterton21 Coupling type / Mfr Flexible spacer / Rathi

22 Sound Level Vendor to Comply yes

23 Weight & overall dimensions Vendor to Comply later24 Performance characteristics of pump E591/0129/225 Accessories of pump

a pressure guage at suction Vendor to Comply not considered

Effluent water with dissolved chemicals/minerals & Traces of crude oil

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

MS fabricated epoxy painted

TIWA teflon impreganated white non asbestos/graphite impregnated

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

b pressure guage at Discharge Vendor to Comply not considered

c Gauge Dampener Vendor to Comply not considered

d Name Plate as per Purchaser demand Vendor to Comply as per Flowserve std

B Electrical Motor

1 Type Sq. Cage Induction Motor yes

2 Make Vendor to Comply yes

3 Duty Contnuous (S1)

4 Model/Frame Vendor to Comply E280M

5 Area of Classification Hazardous Area( Zone 1) Vendor to Comply yes

6 Type of explosion protection EX (d) Vendor to Comply yes

7 Method Of starting ATS starters Vendor to Comply to be confirmed later

8 Rated Power HP/(KW) Vendor to Comply 49

9 BKW at full load Vendor to Comply 60.2

10 Rated Speed Rpm Vendor to Comply 2960

11 Starting current ampere Vendor to Comply later

12 Full load current ampere Vendor to Comply later

13Voltage/Frequency / Phase

Vendor to Comply yes

14 Frequency Vendor to Comply 50Hz

15 Type of bearing (DE & NDE) Vendor to Comply later

16 Number of pole 2 pole Vendor to Comply yes

17Service Factor

Vendor to Comply 1.15

18Ambient Temp/ Temp Rise in° C

Vendor to Comply yes

19Applicable Coad / Standerds

Vendor to Comply IS 2148

20Type of Lubrication

Grease Vendor to Comply yes

21 Full load Torque Vendor to Comply later

22Starting Torque % of full load Torque

Vendor to Comply later

23 Efficiency at 100% load Vendor to Comply later

24 Efficiency at 75%, 50%, 25% load Vendor to Comply later

25Degree Of Protection

Vendor to Comply IP55

26Insulation Class

Vendor to Comply yes

27Starting Method

Vendor to Comply DOL

28Space Heaters watts/Volts

240 Volts AC Vendor to Comply ok

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

Vendor to Comply motor is energy Efficient

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulationIS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

Class F (with temp. rise to class B)

29Maximum No Of Start / Stop Permitted

Vendor to Comply later

30No. of Terminals

3 Vendor to Comply later

31Rotation viewed from NDE

Vendor to Comply ccw from Cpg end

32Coupling/Pully

Vendor to Comply coupling

33Locked Rotor Current % Amps

Vendor to Comply later

34Locked Rotor withstand time- Hot-Secs

Vendor to Comply later

35Locked Rotor withstand time- Cold-Secs

Vendor to Comply later

36Stator/Rotor Time constant minutes

Vendor to Comply later

37Power factor at 100% load

Vendor to Comply later

38Power factor at 75%, 50%, 25% load

Vendor to Comply later

39Brakdown or pull out Torque %

Vendor to Comply later

40GD2 of Motor

Vendor to Comply later

41 GD2 of Loadr Vendor to Comply later42 Starting time (At 100%, 75% V) Sec. Vendor to Comply later

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1 Vendor to Comply canopy not considered

44 Cable Size / TypeVendor to Comply

later

45 Fault levelVendor to Comply

later

46 Fan For Motor Cooling Driven By Vendor to Comply ok

47 Yes/No Vendor to Comply

48 Yes/No Vendor to Comply

49 Yes/No Vendor to Comply

50 Yes/No Vendor to Comply

51 Yes/No Vendor to Comply

52 Yes/No Vendor to Comply

53 Yes/No Vendor to Comply

ok

54 Yes/No Vendor to Comply

55 Yes/No Vendor to Comply

56 Yes/No Vendor to Comply

ok

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

as per motor vendor's std

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

as per motor vendor's std

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

as per motor vendor's std

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

as per motor vendor's std

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

as per motor vendor's std

On- line Greasing arrangement shall be provided for motors offered.

as per motor vendor's std

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

as per motor vendor's std

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

as per motor vendor's std

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

57 Yes/No

Vendor to Comply

ok

58 Yes/No

Vendor to Comply

ok

C SCOPE OF SUPPLY

1 Filter back wash pump with motor Vendor to Comply ok2 Foundation Bolts (If applicable) Vendor to Comply ok3 First Fill Up Lubricant Vendor to Comply ok4 Discharge Check Valve Vendor to Comply NA5 Companion Flanges Vendor to Comply ok6 Local Control Panel Hazardous Area( Zone 1) Vendor to Comply Not in our scope7 Temperature And Pressure Gauages Vendor to Comply Not in our scope

8Common skid for Motor & Pump with alignment

Vendor to Comply ok

D OTHER DETAILS

1 Special Tools For Maintenance, If Any Vendor to Comply NA2 Commissioning Spares Vendor to Comply ok

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-02

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT: CTF Kalol

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 3Nos4 Capacity (Normal) 45 m3/hr5 Capacity (Rated) 45 m3/hr6 Head (meters) 150 m7 Discharge pressure 15 kg/cm2g8 Suction Connection Suction Connection(Site:2")9 Discharge Connection Discharge Connection(Site:1.5")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)

14Liquid Handled

15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4

BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)

6WEAR RING SS316 /(ASTM 743 Gr CF8M)

7Gland For packing SS 316 (ASTM 743 Gr CF8M)

8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

Effluent water with dissolved chemicals/minerals & Traces of crude oil

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

10Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting14 Split15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

apressure guage at suction

b

pressure guage at Discharge

cGauge Dampener

d Name Plate as per Purchaser demandB Electrical Motor

1Type

2Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting ATS starters8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase

TIWA teflon impreganated white non asbestos/graphite impregnated

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor18 Ambient Temp/ Temp Rise in° C

19 Applicable Coad / Standerds20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection26 Insulation Class Class F (with temp. rise to class B)27 Starting Method28 Space Heaters watts/Volts 240 Volts AC

29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps

34 Locked Rotor withstand time- Hot-Secs

35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.43 Canopy to be provided TEFC, IP-55 (Ex-'d' for Zone 1

44Cable Size / Type

45Fault level

46 Fan For Motor Cooling Driven By

47

Yes/No

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

48

Yes/No

49Yes/No

50Yes/No

51Yes/No

52Yes/No

53Yes/No

54Yes/No

55Yes/No

56

Yes/No

57

Yes/No

58

Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges6 Local Control Panel Hazardous Area( Zone 1)7 Temperature And Pressure Gauages

8D OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

Common skid for Motor & Pump with alignment

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARKS C&T replyFlowserve

65-40 CPX315Vendor to Comply yesVendor to Comply yes

45 m3/hr150 m

Vendor to Comply yes65 mm/150#/RF40 mm/150#/RF

296044.60%41.2 Kw75 kW

Vendor to Comply yes

Vendor to Comply yesVendor to Comply yesVendor to Comply yes

SS316SS316SS316

MS

SS316

SS316 Not applicable

Vendor to Comply SS316 gland plate

Vendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

SingleVendor to Comply yesVendor to Comply FootVendor to Comply Radial split

308320256

Vendor to Comply 6309 / 3309oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply laterE591/0129/2

Vendor to Comply

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply as per Flowserve std

Sq. Cage Induction Motor yes

Vendor to Comply yes

yesVendor to Comply E280MVendor to Comply yesVendor to Comply yesVendor to Comply to be confirmed laterVendor to Comply 41.2Vendor to Comply 56.2Vendor to Comply 2960Vendor to Comply laterVendor to Comply laterVendor to Comply yes

Vendor to Comply motor is energy Efficient

Vendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15Vendor to Comply yes

Vendor to Comply IS 2148

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP55Vendor to Comply yesVendor to Comply DOLVendor to Comply ok

Vendor to Comply later

Vendor to Comply laterVendor to Comply ccw from Cpg endVendor to Comply coulingVendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply canopy not considered

Vendor to Complylater

Vendor to Complylater

Vendor to Comply ok

Vendor to Comply

as per motor vendor's std

Vendor to Comply

as per motor vendor's std

Vendor to Complyas per motor vendor's std

Vendor to Complyas per motor vendor's std

Vendor to Complyas per motor vendor's std

Vendor to Complyas per motor vendor's std

Vendor to Complyok

Vendor to Complyas per motor vendor's std

Vendor to Complyas per motor vendor's std

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply NAVendor to Comply okVendor to Comply Not in our scopeVendor to Comply Not in our scope

Vendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-04

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT:ETP II Kalol channel water transfer pump

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 2 Nos4 Capacity (Normal) 3.96 m3/hr5 Capacity (Rated) 3.96 m3/hr6 Head (meters) 25 m7 Discharge pressure 2.5 kg/cm2g8 Suction Connection Suction Connection(Site:1")9 Discharge Connection Discharge Connection(Site:0.5")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled Channel water transfer pump15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting14 Split15 Impeller Diameter- RATED16 MAXIMUM

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting DOL8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor18 Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection26 Insulation Class Class F (with temp. rise to class B)27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 Yes/No

51 Yes/No

52 Yes/No

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

53 Yes/No

54 Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges6 Local Control Panel Hazardous Area( Zone 1)7 Temperature And Pressure Gauages8 Common skid for Motor & Pump with alignment

D OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

2) Comply the sheet and send it before 14th Aug, 2012

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T replyFlowserve

40-25 CPX125Vendor to Comply yesVendor to Comply yes

4 m3/hr25 m

Vendor to Comply yes40 mm/150#/RF25 mm/150#/RF

284023.60%1.14 Kw2.2 kW

Vendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply yes

A315 CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA Vendor to Comply NA

Vendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply OK

SingleVendor to Comply yesVendor to Comply FootVendor to Comply Radial split

136140

98Vendor to Comply 6207 / 3306

oilchesterton

Flexible spacer / Rathi

Vendor to Comply YES

Vendor to Comply laterE591/0001/1

Vendor to Comply

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply

Vendor to ComplyVendor to Comply

Sq. Cage Induction Motor yes

Vendor to Comply yes

Vendor to Comply E90LVendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply 1.14Vendor to Comply 1.69Vendor to Comply 2840Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15Vendor to Comply yes

Vendor to Comply IS-2148

as per Flowserve std

Vendor to Comply motor is energy Efficient

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP55Vendor to Comply yesVendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply ccw from Cpg endVendor to Comply couplingVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Complylater

Vendor to Complylater

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Complyok

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply NAVendor to Comply okVendor to Comply Not in our scopeVendor to Comply Not in our scopeVendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok

as per motor vendor's std

as per motor vendor's std

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-05

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT:CWIP I Kalol booster pump

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 3 Nos4 Capacity (Normal) 51.01 m3/hr5 Capacity (Rated) 51.01 m3/hr6 Head (meters)7 Discharge pressure 2 kg/cm2g8 Suction Connection Suction Connection(Site:1")9 Discharge Connection Discharge Connection(Site:0.5")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting14 Split

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)

4 Model/Frame

5 Area of Classification Hazardous Area( Zone 1)

6 Type of explosion protection EX (d)

7 Method Of starting DOL starter

8 Rated Power HP/(KW)

9 BKW at full load

10 Rated Speed Rpm

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

11 Starting current ampere

12 Full load current ampere

13Voltage/Frequency / Phase

14 Frequency

15 Type of bearing (DE & NDE)

16 Number of pole 2 pole

17Service Factor

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20Type of Lubrication

Grease

21Full load Torque

22Starting Torque % of full load Torque

23Efficiency at 100% load

24Efficiency at 75%, 50%, 25% load

25Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27Starting Method

28Space Heaters watts/Volts

240 Volts AC

29Maximum No Of Start / Stop Permitted

30No. of Terminals

3

31Rotation viewed from NDE

32Coupling/Pully

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

33Locked Rotor Current % Amps

34Locked Rotor withstand time- Hot-Secs

35Locked Rotor withstand time- Cold-Secs

36Stator/Rotor Time constant minutes

37Power factor at 100% load

38Power factor at 75%, 50%, 25% load

39Brakdown or pull out Torque %

40GD2 of Motor

41GD2 of Loadr

42Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 Yes/No

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

51 Yes/No

52 Yes/No

53 Yes/No

54 Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1Filter back wash pump with motor

2Foundation Bolts (If applicable)

3First Fill Up Lubricant

4Discharge Check Valve

5Companion Flanges

6Local Control Panel

Hazardous Area( Zone 1)

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

7Temperature And Pressure Gauages

8

D OTHER DETAILS

1Special Tools For Maintenance, If Any

2Commissioning Spares

3Mandatory Spares

4Packing & Shipment

5Surface Protection & Painting

6Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1Layout/ G.A Drawing of Pump and Motor,

2Capacity calculation sheet based on site condition

3Performance Curves of Pump and Motor

4Filled in motor Data Sheet

5Utility Requirement details,If any

6Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

Common skid for Motor & Pump with alignment

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

BY Vendor SAVAIR REMARK C&T replyFlowserve

80-50 CPX125Vendor to Comply yesVendor to Comply yes

51 m3/hr20 m

Vendor to Comply yes80 mm/150#/RF50 mm/150#/RF

290064.40%4.31 Kw5.5 kW

Vendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply yes

A216 WCBA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA NA

Vendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

SingleVendor to Comply yesVendor to Comply FootVendor to Comply Radial split

12914098

Vendor to Comply 6207 / 3306oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply laterE591/0004/1

Vendor to Comply

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply

yes

Vendor to Comply yes

Vendor to Comply E132M

Vendor to Comply yes

Vendor to Comply yes

Vendor to Comply yes

Vendor to Comply 4.31

Vendor to Comply 5.12

Vendor to Comply 2900

as per Flowserve std

Sq. Cage Induction Motor

Vendor to Comply motor is energy Efficient

Vendor to Comply later

Vendor to Comply later

Vendor to Comply yes

Vendor to Comply 50Hz

Vendor to Comply later

Vendor to Comply yes

Vendor to Comply 1.15

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yes

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOL

Vendor to Comply ok

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply

Vendor to Complylater

Vendor to Complylater

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply

Vendor to Comply

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply NA

Vendor to Comply ok

Vendor to Comply Not in our scope

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply Not in our scope

Vendor to Comply ok

Vendor to Comply NA

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply later

Vendor to Comply NA

Vendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-06

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT: CWIP II Kalol booster pump

Sr. Parameters ONGC-ES BY Vendor1 Manufacturer Name Flowserve2 Model No. 80-50 CPX1253 QTY 4 Nos4 Capacity (Normal) 51.01 m3/hr5 Capacity (Rated) 51.01 m3/hr 51 m3/hr6 Head (meters) 20 m7 Discharge pressure 2 kg/cm2g8 Suction Connection Suction Connection(Site:3") 80 mm/150#/RF9 Discharge Connection Discharge Connection(Site:2") 50 mm/150#/RF

10 Rated Speed 1450/2900 Rpm. 290011 Efficiency of Pump 64.40%12 Rated Power (KW) 4.31 Kw13 Driver Power (kW) 5.5 kW14 Liquid Handled15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M) A216 WCB2 IMPELLER SS316 (ASTM 743 Gr CF8M) A890 GR.A1 (DUPLEX)3 SHAFT SS316 (ASTM 276 type 316) SS316

4 BASEPLATE M.S FABRICATED

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8) SS3166 WEAR RING SS316 /(ASTM 743 Gr CF8M) NA7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage Single12 Casing type single stage/Volute13 Mounting14 Split

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

15 Impeller Diameter- RATED 12916 MAXIMUM 14017 MINIMUM 9818 Bearing type & No. DE/NDE19 Lubrication system oil20 Packing type (size & No.) chesterton21 Coupling type / Mfr Flexible spacer / Rathi

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump E591/0004/125 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demandB Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)

4 Model/Frame

5 Area of Classification Hazardous Area( Zone 1)

6 Type of explosion protection EX (d)

7 Method Of starting DOL starter

8 Rated Power HP/(KW)

9 BKW at full load

10 Rated Speed Rpm

11 Starting current ampere

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

Sq. Cage Induction Motor

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

12 Full load current ampere

13Voltage/Frequency / Phase

14 Frequency

15 Type of bearing (DE & NDE)

16 Number of pole 2 pole

17Service Factor

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20Type of Lubrication

Grease

21Full load Torque

22Starting Torque % of full load Torque

23Efficiency at 100% load

24Efficiency at 75%, 50%, 25% load

25Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27Starting Method

28Space Heaters watts/Volts

240 Volts AC

29Maximum No Of Start / Stop Permitted

30No. of Terminals

3

31Rotation viewed from NDE

32Coupling/Pully

33Locked Rotor Current % Amps

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

34Locked Rotor withstand time- Hot-Secs

35Locked Rotor withstand time- Cold-Secs

36Stator/Rotor Time constant minutes

37Power factor at 100% load

38Power factor at 75%, 50%, 25% load

39Brakdown or pull out Torque %

40GD2 of Motor

41GD2 of Loadr

42Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 Yes/No

51 Yes/No

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

52 Yes/No

53 Yes/No

54 Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1Filter back wash pump with motor

2Foundation Bolts (If applicable)

3First Fill Up Lubricant

4Discharge Check Valve

5Companion Flanges

6Local Control Panel

Hazardous Area( Zone 1)

7Temperature And Pressure Gauages

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

8

D OTHER DETAILS

1Special Tools For Maintenance, If Any

2Commissioning Spares

3Mandatory Spares

4Packing & Shipment

5Surface Protection & Painting

6Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1Layout/ G.A Drawing of Pump and Motor,

2Capacity calculation sheet based on site condition

3Performance Curves of Pump and Motor

4Filled in motor Data Sheet

5Utility Requirement details,If any

6Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

Common skid for Motor & Pump with alignment

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

SAVAIR REMARK C&T reply

Vendor to Comply yesVendor to Comply yes

Vendor to Comply yes

Vendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply yes

NAVendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

Vendor to Comply yesVendor to Comply FootVendor to Comply Radial split

Vendor to Comply 6207 / 3306

Vendor to Comply yes

Vendor to Comply later

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply as per Flowserve std

Vendor to Comply

yes

Vendor to Comply yes

Vendor to Comply E132M

Vendor to Comply yes

Vendor to Comply yes

Vendor to Comply yes

Vendor to Comply 4.31

Vendor to Comply 5.12

Vendor to Comply 2900

Vendor to Comply later

Vendor to Comply motor is energy Efficient

Vendor to Comply later

Vendor to Comply yes

Vendor to Comply 50Hz

Vendor to Comply later

Vendor to Comply yes

Vendor to Comply 1.15

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yes

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOL

Vendor to Comply ok

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply later

Vendor to Comply

Vendor to Complylater

Vendor to Complylater

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply NA

Vendor to Comply ok

Vendor to Comply Not in our scope

Vendor to Comply Not in our scope

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply ok

Vendor to Comply NA

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply later

Vendor to Comply NA

Vendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-07

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT:ETP II Kalol Filter feed pump

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 2 Nos4 Capacity (Normal) 50 m3/hr5 Capacity (Rated) 50 m3/hr6 Head (meters)7 Discharge pressure 10 kg/cm2g8 Suction Connection Suction Connection(Site:2.5")9 Discharge Connection Discharge Connection(Site:2")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled Filter feed pump with motor15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)

9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

14 Split15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting DOL8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

17 Service Factor

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs

35Locked Rotor withstand time- Cold-Secs

36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47 Yes/No

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

48 Yes/No

49 Yes/No

50 Yes/No

51 Yes/No

52 Yes/No

53 Yes/No

54 Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

4 Discharge Check Valve5 Companion Flanges6 Local Control Panel Hazardous Area( Zone 1)7 Temperature And Pressure Gauages

8

D OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

Common skid for Motor & Pump with alignment

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T replyFlowserve

65-40 CPX315Vendor to Comply yesVendor to Comply yes

50 m3/hr100 m

Vendor to Comply yes65 mm/150#/RF40 mm/150#/RF

296046.00%29.6 Kw37 kW

Vendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply yes

A315CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA NA

Vendor to ComplyVendor to Comply DI

Vendor to Comply PTFE

Vendor to Comply ok

Singleyes

Foot Foot

Radial Radial split265320256

Vendor to Comply 6309 / 3309oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply laterE591/0129/2

Vendor to Comply

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply as per Flowserve std

Sq. Cage Induction Motor

Vendor to Comply yes

yesVendor to Comply E200LVendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply 29.6Vendor to Comply 34.3Vendor to Comply 2960Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yes

Vendor to Comply motor is energy Efficient

Vendor to Comply 1.15

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply later

Vendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Complylater

Vendor to Complylater

Vendor to Comply ok

Vendor to Comply

canopy not considered

as per motor vendor's std

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Complyok

Vendor to Comply

Vendor to Comply

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply

ok

Vendor to Comply okVendor to Comply okVendor to Comply ok

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply NAVendor to Comply okVendor to Comply Not in our scopeVendor to Comply Not in our scope

Vendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-08

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT:: ETP II Kalol Sludge Transfer pump

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 1 No.4 Capacity (Normal) 50 m3/hr5 Capacity (Rated) 50 m3/hr6 Head (meters)7 Discharge pressure 5 kg/cm2g8 Suction Connection Suction Connection(Site:2")9 Discharge Connection Discharge Connection(Site:2")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting14 Split15 Impeller Diameter- RATED16 MAXIMUM

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels

ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plateas per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting DOL8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor18 Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20 Type of Lubrication Grease21 Full load Torque

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump

approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection26 Insulation Class Class F (with temp. rise to class B)27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47

Yes/No

48Yes/No

49Yes/No

50Yes/No

51Yes/No

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

52Yes/No

53Yes/No

54Yes/No

55Yes/No

56Yes/No

57

Yes/No

58

Yes/No C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges6 Local Control Panel Hazardous Area( Zone 1)7 Temperature And Pressure Gauages

8Common skid for Motor & Pump with alignment

D OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T Flowserve

80-50 CPX200Vendor to Comply yesVendor to Comply yes

50 m3/hr50 m

80 mm/150#/RF50 mm/150#/RF

294065.60%10.4 Kw15 kW

A315CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA

DIPTFE

ok

SingleHorizontal yes

Foot FootRadial Radial split

186210

168

oilchesterton

Flexible spacer / Rathi

yes

E591/0015/1

not considered

not considered

not considered

Sq. Cage Induction Motor yes

Vendor to Comply yes

Vendor to Comply E160LVendor to Comply yesVendor to Comply yesVendor to Comply yesVendor to Comply 10.4Vendor to Comply 14.2Vendor to Comply 2940Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yesVendor to Comply later

as per Flowserve std

Vendor to Comply motor is energy

Efficient

Vendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP 55Vendor to Comply yesVendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply CCW from cpgVendor to Comply couplingVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Comply later

Vendor to Comply later

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply NAVendor to Comply okVendor to Comply Not in our scopeVendor to Comply Not in our scope

Vendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply later

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply NAVendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-09

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT :ETP I Kalol CONDITIONED WATER TRANSFER PUMP

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 1 No.4 Capacity (Normal)5 Capacity (Rated) 100 m3/hr6 Head (meters)7 Discharge pressure 10 kg/cm2g8 Suction Connection Suction Connection(Site:6")9 Discharge Connection Discharge Connection(Site:4")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)

14 Liquid Handled

15 Pump Should be confirm ISO 2858/DIN 5199/Din 245616 Operating Temperature Deg C. up to 80 Deg c.17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type single stage/Volute13 Mounting

CONT. TRANSFER OF TREATED EFFLUENT/WATER

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

14 Split15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting DOL8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

50 Yes/No

51 Yes/No

52 Yes/No

53 Yes/No

54 Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges6 Local Control Panel Hazardous Area( Zone 1)7 Temperature And Pressure Gauages8 Common skid for Motor & Pump with alignment

D OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Terminal box shall be rotatable through 360º at 90º interval

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T replyFlowserve

100-65CPX315Vendor to Comply yesVendor to Comply

100 m3/hr yes100 m

10 kg/cm2g100mm/150#/RF65 mm/150#/RF

296058.00%49.9 Kw75 kW

Vendor to Complyyes

Vendor to Comply yes

up to 50 Deg c.Vendor to Comply yes

A315CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA NA

Vendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

SingleHorizontal yes

Foot Foot

Radial Radial split262320256

Vendor to Comply 6311 / 3311oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply laterE591/0015/1

Vendor to Comply

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply

Vendor to Comply

Sq. Cage Induction Motor yes

Vendor to Comply yes

Vendor to Comply yesVendor to Comply E280MVendor to Comply yesVendor to Comply yesVendor to Comply yes

75Kw 46.9Vendor to Comply 56.3Vendor to Comply 2960Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15

as per Flowserve std

Vendor to Comply motor is energy

Efficient

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply CCW from cpgVendor to Comply couplingVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Comply later

Vendor to Comply later

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply NAVendor to Comply okVendor to Comply Not in our scopeVendor to Comply Not in our scopeVendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply ok

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-10

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT: GGS- V -KALOL EEFLUENT DISPATCH PUMP

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 1 No.4 Capacity (Normal)5 Capacity (Rated) 45 m3/hr6 Head (meters)7 Discharge pressure 15 kg/cm2g8 Suction Connection Suction Connection(Site:6")9 Discharge Connection Discharge Connection(Site:4")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled EFFLUENT15 Pump Should be confirm ISO 2858/DIN 5199/Din 2456

16 Operating Temperature Deg C. up to 80 Deg c.

17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type Horizontal13 Mounting

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

14 Split15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demand

B Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting ATS Starter8 Rated Power HP/(KW)9 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

50 Yes/No

51 Yes/No

52 Yes/No

53 Yes/No

54Terminal box shall be rotatable through 360º at 90º interval

Yes/No

55 Yes/No

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges

6Local Control Panel

Hazardous Area( Zone 1)

7Temperature And Pressure Gauages

8 Common skid for Motor & Pump with alignmentD OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor,

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data

2) Comply the sheet and send it before 14th Aug, 2012

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T replyFlowserve

65-40CPX315Vendor to Comply yesVendor to Comply yes

45m3/hr

65 mm/150#/RF40 mm/150#/RF

296044.60%41.2 Kw75 kW

EFFLUENTVendor to Comply yes

Vendor to Comply yes

CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA NA

Vendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

SingleHorizontal yes

Foot Foot

15 KG/CM2

up to 50°C. Mim 10°C, max80°C

Radial Radial split308320256

Vendor to Comply 6309 / 3309oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply laterE591/0015/1

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Sq. Cage Induction Motor yes

Vendor to Comply yes

Vendor to Comply yesVendor to Comply E280MVendor to Comply yesVendor to Comply yesVendor to Comply

75Kw 46.9Vendor to Comply 56.3Vendor to Comply 2960Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15

not considered

not considered

not considered

as per Flowserve std

Vendor to Comply motor is energy

Efficient

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply CCW from cpgVendor to Comply couplingVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Comply later

Vendor to Comply later

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply NAVendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply ok

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Not in our scope

Not in our scope

Vendor to Comply okVendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok

SAVAIR ENERGY LTD.

Technical Queries: SEL-TQ-FS001-14

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.PLANT : ETP-I EFFLUENT TRANSFER PUMP

Sr. Parameters ONGC-ES1 Manufacturer Name2 Model No.3 QTY 1 No.4 Capacity (Normal)5 Capacity (Rated) 100 m3/hr6 Head (meters)7 Discharge pressure 5 kg/cm2g8 Suction Connection Suction Connection(Site:4")9 Discharge Connection Discharge Connection(Site:3")

10 Rated Speed 1450/2900 Rpm.11 Efficiency of Pump12 Rated Power (KW)13 Driver Power (kW)14 Liquid Handled EFFLUENT TRANSFER15 Pump Should be confirm ISO 2858/DIN 5199/Din 2456

16 Operating Temperature Deg C. up to 80°C

17 Arrow Of Pump Rotation on Casing By VendorA Material of construction1 CASE SS316 (ASTM 743 Gr CF8M)2 IMPELLER SS316 (ASTM 743 Gr CF8M)3 SHAFT SS316 (ASTM 276 type 316)

4 BASEPLATE

5 SHAFT SLEEVE SS (ASTM 743 Gr CF8)6 WEAR RING SS316 /(ASTM 743 Gr CF8M)7 Gland For packing SS 316 (ASTM 743 Gr CF8M)8 Bearing Housing CI (ASTM 48)9 Casing Gasket Compressed non-asbestos fiber

10 Gland Packing

11 Stage12 Casing type Horizontal13 Mounting14 Split15 Impeller Diameter- RATED16 MAXIMUM17 MINIMUM

Heavy duty single M.S. Fabricated (Plate IS 2062 Gr. B or ASTM /A-36 & C Channels ISME 200 as per IS 808)

TIWA teflon impreganated white non asbestos/graphite impregnated

18 Bearing type & No. DE/NDE19 Lubrication system20 Packing type (size & No.)21 Coupling type / Mfr

22 Sound Level

23 Weight & overall dimensions24 Performance characteristics of pump25 Accessories of pump

a pressure guage at suction

b pressure guage at Discharge

c Gauge Dampener

d Name Plate as per Purchaser demandB Electrical Motor

1 Type

2 Make

3 Duty Contnuous (S1)4 Model/Frame5 Area of Classification Hazardous Area( Zone 1)6 Type of explosion protection EX (d)7 Method Of starting ATS Starter8 Rated Power HP/(KW) 309 BKW at full load

10 Rated Speed Rpm11 Starting current ampere12 Full load current ampere13 Voltage/Frequency / Phase14 Frequency15 Type of bearing (DE & NDE)16 Number of pole 2 pole17 Service Factor

18Ambient Temp/ Temp Rise in° C

19Applicable Coad / Standerds

20 Type of Lubrication Grease21 Full load Torque22 Starting Torque % of full load Torque23 Efficiency at 100% load

less than 90dba at a sdistance 1 mtr from pump

3" dial jelly filled, stem mounted range 5m to 10m

3" dial jelly filled, stem mounted range(1/2" BSP/NPT) range of pump approx 1.4 times rated pressure.

1/2" threaded SS valve along with suitable for Pressure Guage

Flameproof Sq. Cage Induction Motor ( energy Efficient)

CGL/KEC/Siemens/NGEF/BBL/GEC/ALSTHOM

415±6% / 50± 3% /

50 ° C / limited to CI "B" insulation

IS 325/IS -2148/IS12615/IS-4029m& as per Standerd Specification MV motor

24 Efficiency at 75%, 50%, 25% load25 Degree Of Protection

26Insulation Class

Class F (with temp. rise to class B)

27 Starting Method28 Space Heaters watts/Volts 240 Volts AC29 Maximum No Of Start / Stop Permitted30 No. of Terminals 331 Rotation viewed from NDE32 Coupling/Pully33 Locked Rotor Current % Amps34 Locked Rotor withstand time- Hot-Secs35 Locked Rotor withstand time- Cold-Secs36 Stator/Rotor Time constant minutes37 Power factor at 100% load38 Power factor at 75%, 50%, 25% load39 Brakdown or pull out Torque %40 GD2 of Motor41 GD2 of Loadr42 Starting time (At 100%, 75% V) Sec.

43Canopy to be provided

TEFC, IP-55 (Ex-'d' for Zone 1

44 Cable Size / Type

45 Fault level

46 Fan For Motor Cooling Driven By

47 Yes/No

48 Yes/No

49 Yes/No

50 Yes/No

51 Yes/No

52 Yes/No

53 Yes/No

54Terminal box shall be rotatable through 360º at 90º interval

Yes/No

55 Yes/No

for motor space heater shall be 2CX4 sq. mm (Cu) 1.1 KV PVC/ Armoured Cable

40 KW for 0.25 Sec. for Motor above 30 KW

The terminal box shall be spacious enough and shall be suitable for the cable size as specified by ONGC during drawing approval stage.

The cable gland shall be DGMS flame proof , double compression type brass nickel-plated type in case of flame proof motors(Ex-'d')

The cable gland shall be double compression type brass nickel-plated type for Non FLP Motors

The terminal box shall be suitable for type of enclosures selected for FLP/Non-FLP Motors

The motor shall be painted with corrosion resistant epoxy paint of light grey;grade 631 as per IS:5

On- line Greasing arrangement shall be provided for motors offered.

Space heater of sufficient capacity shall be provided for the motors above 30KW

Energy Efficient Motor Supplied(Efficiency guaranteed as per IS:12615)

56 Yes/No

57 Yes/No

58 Yes/No

C SCOPE OF SUPPLY

1 Filter back wash pump with motor 2 Foundation Bolts (If applicable)3 First Fill Up Lubricant4 Discharge Check Valve5 Companion Flanges

6Local Control Panel

Hazardous Area( Zone 1)

7Temperature And Pressure Gauages

8 Common skid for Motor & Pump with alignmentD OTHER DETAILS

1 Special Tools For Maintenance, If Any2 Commissioning Spares3 Mandatory Spares 4 Packing & Shipment5 Surface Protection & Painting

6 Inspection And Tests

E DOCUMENTS TO BE ENCLOSED WITH THE OFFER

1 Layout/ G.A Drawing of Pump and Motor, 2 Capacity calculation sheet based on site condition3 Performance Curves of Pump and Motor4 Filled in motor Data Sheet 5 Utility Requirement details,If any6 Civil load details

F DEVIATION IF ANY

Note: 1) Please send the updated data sheets & GAD with load data2) Comply the sheet and send it before 14th Aug, 2012

he flameproof motor shall be in accordance with IS:2148 and suitable for Zone1/Zone2 Gas groupIIA/IIB and temp.class T3

The following drawings/certificates shall be furnished for ONGC approval after LOI(prior to manufecturing clearance) a) Motor dimension drg. b) Hot/Cold withstand erstic curves of the motor. c) A Copy of DGMS approval certificate forFLP(Ex-'d') Motor

The following Third party Inspection/QA Deptt.of ONGC(whichever is applicable) release certificates alongwith the supply of the motors: a) Routine test Certificates b) Type test certificate

PROJECT : Replacement of Process Pump, Fire Water Pump & Fire Water Jet Monitor at ONGC, Ahmedabad Asset.

By Vendor SAVAIR REMARK C&T Flowserve

100-65CPX200Vendor to Comply yesVendor to Comply yes

100 m3/hr100 m

100 mm/150#/RF60 mm/150#/RF

294065.50%

20.42 Kw30 kW

EFFLUENTVendor to Comply yes

Vendor to Comply yes

A315 CF8MA890 GR.A1 (DUPLEX)

SS316

M.S FABRICATED

SS316NA

Vendor to ComplyVendor to Comply DIVendor to Comply PTFE

Vendor to Comply ok

SingleHorizontal yes

Foot FootRadial Radial split

180210152

5 KG/CM2

up to 30°C. Mim 10°C, max50°C

Vendor to Comply 6309 / 3309oil

chestertonFlexible spacer / Rathi

Vendor to Comply yes

Vendor to Comply later

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply not considered

Vendor to Comply

Vendor to ComplyVendor to Comply

Sq. Cage Induction Motor yes

Vendor to Comply yes

Vendor to Comply yesVendor to Comply E200LVendor to Comply yesVendor to Comply yesVendor to Comply yes

75Kw 20.4Vendor to Comply 26.8Vendor to Comply 2940Vendor to Comply laterVendor to Comply laterVendor to Comply yesVendor to Comply 50HzVendor to Comply laterVendor to Comply yesVendor to Comply 1.15

Vendor to Comply yes

Vendor to Comply IS-2148

Vendor to Comply yesVendor to Comply laterVendor to Comply laterVendor to Comply later

as per Flowserve std

Vendor to Comply motor is energy

Efficient

Vendor to Comply laterVendor to Comply IP 55

Vendor to Comply yes

Vendor to Comply DOLVendor to Comply okVendor to Comply laterVendor to Comply laterVendor to Comply CCW from cpgVendor to Comply couplingVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply laterVendor to Comply later

Vendor to Comply

Vendor to Comply later

Vendor to Comply later

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply

Vendor to Comply ok

Vendor to Comply

Vendor to Comply

canopy not considered

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

as per motor vendor's std

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply NAVendor to Comply ok

Vendor to Comply Not in our scope

Vendor to Comply Not in our scope

Vendor to Comply ok

Vendor to Comply NAVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply ok

Vendor to Comply okVendor to Comply okVendor to Comply okVendor to Comply laterVendor to Comply NAVendor to Comply ok