  • TPS Process Manager I/O

    Specification and Technical Data

    IO03-500Release 500

    11/97

  • IO03-500Page 2 11/97

    TPS Process Manager I/O Honeywell Inc.Specification and Technical Data

    Table of Contents

    Introduction .................................................................................................................. 3Functional Description ................................................................................................ 4Functional Overview.....................................................................................................................................................4Serial Interface (SI) (APM and HPM only) ..................................................................................................................10Pulse Input (PI)...........................................................................................................................................................11Analog Output ............................................................................................................................................................12Digital Input Sequence of Events (APM and HPM only) .............................................................................................13I/O Simulation Option .................................................................................................................................................14Card File Assemblies..................................................................................................................................................15Field Termination Assemblies ....................................................................................................................................16

    Options ....................................................................................................................... 16I/O Redundancy .........................................................................................................................................................16Harsh Environment Option .........................................................................................................................................19

    European Community (EC) Compliance .................................................................. 20Specifications............................................................................................................. 21I/O Link Extender (Remote I/O) ..................................................................................................................................21European Community Compliance (CE-Mark) ...........................................................................................................21High Level Analog Input Processor - 16 Inputs MC-PAIH03 ......................................................................................22High Level Analog Input Processor Redundancy Option MU-TAIH12, TAIH52, TAIH13, TAIH53, TAIH22, ..............23TAIH23, TAIH62 .........................................................................................................................................................23Low Level Analog Input Processor - 8 Inputs MU-PAIL02..........................................................................................23Low Level Analog Input Multiplexer Processor - 32 Inputs MU-PLAM02 ..................................................................25Remote Hardened Multiplexer Processor - 32 Inputs MU-PRHM01...........................................................................28Smart Transmitter Interface Processor MU-PSTX03..................................................................................................30Smart Transmitter Interface Processor Redundancy Option MU-TAIH12, TAIH52, TSTX13, TSTX53 ......................30Serial Device Interface (General Specifications) MU-PSDX02...................................................................................31Serial Device Interface - Toledo Weigh Cell MU -TSDT02 ........................................................................................31Serial Device Interface - Manual/Auto Station MU-TSDM02 .....................................................................................32Serial Device Interface - UDC 6000 Process Controller MU-TSDU02.......................................................................33Serial Interface I/O Processor/FTA - Modbus MU-TSIM12 ........................................................................................34Serial Interface I/O Processor/FTA - Allen-Bradley MU-TSIA12 ................................................................................35Allen-Bradley File Types ............................................................................................................................................35Pulse Input Processor/FTA MU-PPIX02.....................................................................................................................36Analog Output 8-Point Processor/FTA MC-PAOX03..................................................................................................37Analog Output 8-Point Processor Redundancy Option MU-TAOX12, TAOX52 .........................................................37Analog Output 16-Point Processor/FTA MU-PAOY22................................................................................................38Analog Output 16-Point Processor Redundancy Option MU-TAOY22, TAOY23, TAOY52, TAOY53 ........................38Digital Input Processor and Digital Input Sequence of Events Processor MU-PDIX02/MU-PDIS12 ..........................39Digital Input Processor Redundancy Option...............................................................................................................40Digital Input 24 Vdc Processor MU-PDIY22 ...............................................................................................................41Digital Output 16-Point Processor MU-PDOX02 .......................................................................................................42Digital Output 32-Point Processor MU-PDOY22 ........................................................................................................46Analog Input IOP Comparison....................................................................................................................................48Analog Output IOP Comparison .................................................................................................................................49Digital Input IOP Comparison .....................................................................................................................................50Digital Output IOP Comparison ..................................................................................................................................51IOP/FTA CompatibilityMatrox .....................................................................................................................................52Model Numbers ..........................................................................................................................................................57

  • IO03-50011/97 Page 3

    Honeywell Inc. TPS Process Manager I/OSpecification and Technical Data

    IntroductionThe Process Manager (PM), Advanced ProcessManager (APM) and High Performance ProcessManager (HPM) are Honeywells leading TotalPlantSolution (TPS) system control and data acquisitiondevices for industrial process applications. Theyrepresent a powerful combination of cost-effectiveHoneywell controllers which can be applied to solve abroad range of industrial process control problems.

    The PM, APM, and HPM offer highly flexible I/O(input/output) functions for both data monitoring andcontrol. One of the unique features of this family ofcontrollers is its common set of Input/OutputProcessors (IOPs) and Field Termination Assemblies(FTAs). All IOPs and FTAs are usable by all threecontrollers (with only minor exceptions).

    This specification and technical data sheet providesinformation on PM, APM, and HPM IOPs and FTAs.Please refer to the following specification andtechnical data sheets for information about eachcontroller:

    PM03-400 - Process Manager Specification andTechnical Data

    AP03-500 - Advanced Process ManagerSpecification and Technical Data

    HP03-500 - High Performance Process ManagerSpecification and Technical Data

    14174

    Power

    Status

    Analog Output

    C

    Figure 1 PM/APM/HPMInput OutputProcessor

  • IO03-500Page 4 11/97

    TPS Process Manager I/O Honeywell Inc.Specification and Technical Data

    Functional Description

    Functional Overview

    I/O Processors, along with Field Termination Assemblies (FTAs), perform input andoutput scanning and processing on all field PM/APM/HPM I/O (Figure 2).

    INTERNAL FUNCTIONS

    I/O PROCESSINGPV Testing Conversion to EU PV Alarm CharacterizationOutput Verification

    FIELD TERMINATIONConditioningIsolation Surge Protection FusingCurrent Limiting

    FIELD TERMINATION

    ASSEMBLY

    I/O PROCESSOR

    RedundantI/O Link to

    PM/APM/HPM

    Field Wiring

    PROCESSOR TYPES

    Analog Inputs Smart Transmitter

    Interfaces Serial Interfaces Analog Outputs Pulse Inputs Digital Inputs Digital Outputs

    14175

    Figure 2 PM/APM/HPM I/O Functions

    A redundant I/O Link is standard for maximum security. Optionally, High LevelAnalog Input, Smart Transmitter Interface, Analog Output, Digital Input and DigitalOutput processors can be redundant. I/O processing is performed separately fromcontrol processing functions so that I/O scan rates are completely independent of I/Oquantity, cont