Page 1 Toshiba Air Condioning—RAV SM / SP Data Sheet RAV-###SDT-E RAV Slim Ducted Systems All UK dues are based on Cooling Indoor air temperature 22 o C DB/16 o C WB Outdoor air temperature 28 o C DB 50% RH, high fan speed, 5m pipe run. Heang Indoor air temperature 21 o C DB Outdoor air temperature –4 o C DB 100% RH, high fan speed, 5m pipe run. Values are based on the maximum compressor output. Data obtained from Toshiba Air Condioning Web Data July 2013. www.cdlweb.info The compact design of the slim duct provides an excellent soluon for applicaons where shallow ceiling voids are present and maximum control of airflow is required. The slim ducted system offers improved airflow with ultra low noise levels and is ideal for areas with irregular shapes or large areas require maximum air distribuon.

Upload: buihanh

Post on 27-Aug-2018

284 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Toshiba Air Conditioning—RAV SM / SP Data Sheet … Toshiba Specification sheet RAV - SDT.pdf · Page 1 Toshiba Air Conditioning—RAV SM / SP Data Sheet RAV-###SDT-E RAV Slim Ducted

Page 1

Toshiba Air Conditioning—RAV SM / SP Data Sheet

RAV-###SDT-E RAV Slim Ducted Systems

All UK duties are based on Cooling Indoor air temperature 22oC DB/16oC WB Outdoor air temperature 28oC DB 50% RH, high fan speed, 5m pipe run. Heating Indoor air temperature 21oC DB Outdoor air temperature –4oC DB 100% RH, high fan speed, 5m pipe run. Values are based on the maximum compressor output.

Data obtained from Toshiba Air Conditioning Web Data July 2013.

www.cdlweb.info

The compact design of the slim duct provides an excellent solution

for applications where shallow ceiling voids are present and maximum control of airflow is required. The slim ducted system

offers improved airflow with ultra low noise levels and is ideal for areas with irregular shapes or large areas require maximum air

distribution.

Page 2: Toshiba Air Conditioning—RAV SM / SP Data Sheet … Toshiba Specification sheet RAV - SDT.pdf · Page 1 Toshiba Air Conditioning—RAV SM / SP Data Sheet RAV-###SDT-E RAV Slim Ducted

Page 2

Toshiba Air Conditioning—RAV SM / SP Data Sheet

RAV-###SDT-E RAV Slim Ducted Systems

All UK duties are based on Cooling Indoor air temperature 22oC DB/16oC WB Outdoor air temperature 28oC DB 50% RH, high fan speed, 5m pipe run. Heating Indoor air temperature 21oC DB Outdoor air temperature –4oC DB 100% RH, high fan speed, 5m pipe run. Values are based on the maximum compressor output.

Data obtained from Toshiba Air Conditioning Web Data July 2013.

www.cdlweb.info

Model Reference RAV SM404SDT-E SM566SDT

Nominal Cooling (kW) 3.6 5.0

Nominal Heating (kW) 4.0 5.6

UK Cooling (SM / SP*) (kW) — / 3.4 4.7 / 4.7

UK Sensible Cooling (SM / SP*) (kW) — / 2.54 3.5 / 3.5

UK Heating (SM /SP*) (kW) — / 3.7 4.53 / 5.18

Annual Power Consumption (SM / SP*) (kWh) —- / 515 830 / 780

Sound Pressure (H / L) Rear (dB(A)) 39 / 33 45 / 36

Sound Pressure (H / L) Base (dB(A)) 30 / 26 33 / 28

Sound Power (H / L) Rear (dB(A)) 54 / 48 60 / 51

Sound Power (H / L) Base (dB(A)) 45 / 41 48 / 43

Air Flow (H—L) (m3/h) 690 / 522 780 / 582

Air Flow (H / L) (l/s) 192 / 145 217 / 162

External static pressure range (Pa) 10 - 50 ( 4 steps)

Default static pressure (Pa) 10

Total Dimension (HxWxD) (mm) 210 x 845 x 645

Weight (kg) 22

System Start Current (SM / SP*) (A) 1 / 1

Suggested Fuse Size (SM / SP*) (A) — / 16 16 / 16

Running Current (SM /SP*) (A) —- / 5.20 7.94 / 7.24

Power Supply—Outdoor (V-ph-Hz) 220/240-1-50/60#

Interconnecting Cable 3 Core & Earth

Pipe Sizes Liquid - Suction (inch) 1/4 - 1/2 1/4—1/2

EER / COP (SM / SP*) — / — 3.50 / 4.00 3.01 / 3.52 3.21/3.82

SEER / SCOP (SM / SP*) — / — 5.11 / 3.90 5.06 / 3.82 5.10 / 3.83

Energy Label Cool / Heat (SM / SP*) —/— A/A B/A A/A

Compatible Outdoor Units

Single (RAV-SM### / RAV-SP### AT-E) ——- /SP404 SM564/SP564

Twin (RAV-SM#### / RAV-SP#### AT-E) SM804/SP804 SM1104/SP1104

Triple (RAV-SM#### / RAV-SP#### AT(8)-E) SM1404/SP1404 SM1603/SP1604

Quad (RAV-SM#### / RAV-SP#### AT(8)-E) SM1603/SP1604 SM2244

* Refers to outdoor combination SM= Digital Inverter / SP= Super Digital Inverter # 4 series SM Only