tender document · providing reinforcement for rcc work including straightening ... bressummers...
TRANSCRIPT
INDIAN INSTITUTE OF TECHNOLOGY GUWAHATI
Guwahati - 781 039, Assam
Phone : (0361) 2582061, 2692771 : : Fax : (0361) 2692771 , 2690762
TENDER DOCUMENT
NIT NO: IITG/ENGG/17/NIT/01 Dated: 19.01.2017
Part – B : Price Bid
NAME OF WORK
Extension of Academic Complex Phase-VI (CIF & CET Building) at
IITG Campus.
Sl. No. Particulars Amount (Rs.)
1
PART - A : Building Works
PART - B : Sanitary and Water Supply Installation
PART - C : Site Development Work
PART - D : Electrical Works
PART - E : HVAC Works
PART - F : Passenger Lift
2
PART - A : Building Works
PART - B : Sanitary and Water Supply Installation
PART - C : Electrical Works
Total =
Technology (CET) Building and Construction of Central Instruments Facility (CIF) Building at
IITG campus, Guwahati
Construction of Centre for Educational Technology (CET) Building :
Construction of Central Instruments Facility (CIF) Building :
ABSTRACT OF COST
Name of Work : Extension of Academic Complex (Phase-VI) – Construction of Centre for Educational
PART - C : Electrical Works
PART - D : HVAC Works
Interest bearing mobilisation advance (if required) =
Non-Interest bearing mobilisation advance (if required) =
Grand Total (Sl. No. 1 + 2) =
Rebate if any =
Total after rebate =
Total =
(Rebate shall be given at this space in the form of percentage of the rates quoted and rebate given in any other place other than this space, shall not be acceptable)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1 BORED CAST IN SITU PILE
a Boring, providing and installing bored cast-in-situ reinforced cement concretepiles of specified capacity, diameter and length by DMC mechanical meansas per specifications, drawings below the pile cap in cement concrete ofgrade-M30 to carry a safe working load not less than the specified excludingcost of steel reinforcement but including the cost of boring, casing of alllengths, bentonite, concreting and all other arrangements as requiredetc.and the length of the pile to be embedded in the pile cap as specified inthe specifications (effective length of pile for payment will be measured frombottom of the pile up to the cut off level of piles. Rate shall includearrangement of all equipments and drilling mud etc. 500 mm dia. Piles
Metre 8160.00
b Vertical load testing of pile in accordance with IS:2911 (Part-IV) includinginstallation of loading plateform and preparation of pile head or constructionof test cap and dismantling of test cap after test etc. complete as perspecification and direction of engineer-in-Charge.(capacity up to 100 tonnes)
(i) Initial test (Test Load 2.5 times the Design load) Per test 2
PART - A : Building Works
Name of Work : Construction of Centre for Educational Technology (CET) Building
(ii) Routine test (Test Load 1.5 times the Design load) Per test 4
c Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15cm deep and disposal of rubbish, lead up to 50mand lift up to 1.5m: All kinds of soil
sqm 1,000.00
2 EARTH WORK IN EXCAVATION
(a) Earth work in excavation in foundation trenches and drains including bailingout water, dressing of sides, shoring & strutting, ramming of bottoms,including all lifts from the existing ground level and getting out the excavatedsoil, disposal of excavated soil at suitable places within the IIT campus asdirected including refilling the foundation trenches with approved qualityselected excavated / imported soil (excluding rock) etc. including bailing outwater before filling in layers
Cum 1,107.00
not exceeding 20 cm in depth; consolidating/compacting each depositedlayer to the acceptable density by ramming and watering all complete asdirected with all leads and lifts. (Measurements for excavation in foundationfor footings shall be taken on vertical lines with 300 mm tolerance all aroundthe finished concrete of the foundation and that for plinth beams/walls or anyother structure, shall be made on vertical lines with tolerance 150mm aroundthe finished surfaces of concrete. No extra payment shall be made onaccount of removal of slipped earth and backfilling thereof, dewatering,shoring & strutting, etc.) a) In all types of soil
3 EARTH WORK IN FILLING
Earth work in filling in Plinth with approved quality granular soil under floors,plinth beam, etc. as per drawing and as directed including watering,ramming, consolidating upto acceptable limit of 90% proctor density anddressing complete.( The rate shall be inclusive of providing soil including allleads and lifts, payment for land compensation for obtaining earth, paymentof royalty , taxes etc.)
Cum 722.00
4 ANTI-TERMITE TREATMENT
Providing and injecting chemical emulsion for pre-constructional anti-termitetreatment and creating a chemical barrier under & all-round the column pits,wall trenches, basement excavation, top surface of plinth filling, junction ofwall and floor, along the external perimeter of building, expansion joints,surroundings of pipes and conduits etc. complete. Stages shall be treated asper CPWD specification. (Plinth area of the building at ground floor level onlyshall be measured for payments).- With Chlorpyriphos Emulsifiable
Sq.M. 985.00
shall be measured for payments).- With Chlorpyriphos Emulsifiableconcentrate 20% with 1% concentration.
5 CEMENT CONCRETE WORK
Providing,vibrating, laying in position cement concrete of specified gradeincluding curing but excluding the cost of centring and shuttering in all worksupto floor-V level.
(a) 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominalsize) Cum 224.00
(b) 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mmnominal size) Cum 42.00
( c ) Providing and laying damp proof course 40 mm thick with cement concrete1:2:4 (1 cement: 2 course sand: 4 graded stone aggregate 12.5 mm nominalsize) with approved quality water proofing compound in cement concrete and cement mortar work at the rate as recommended by the manufacturers.
Sq.M. 98.50
(d) Applying a coat of residual petroleum bitumen of penetration 80/100 0fapproved quality using 1.7kg per square metre on damp proof course aftercleaning the surface with brushes and finally with a piece of cloth lightlysoaked in kerosene oil.
Sq.M. 98.50
(e) Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mmbed by dry brick ballast 40mm nominal size well rammed and consolidatedand grouted with fine sand including finshing the top smooth.
Sq.M. 150.00
6 STEEL REINFORCEMENT
Providing reinforcement for RCC work including straightening, cutting,bending, binding with specified wire & placing in position complete as perspecifications and drawings - Fe 500 D grade super ductile steel ofapproved manufacturers only of all diameters as per relevent IS codes.
kg 701,608.00
7 CENTERING AND SHUTTERING
Providing, fitting and fixing of centring and shuttering including strutting,propping etc., & removal of forms at all heights and levels for concrete workto give desired surface finish on the concrete.
(a) Foundations, footings, pile caps, bases of columns, mass concrete , etc. Sq.M. 605.00
(b) Walls of any thickness including attached pilasters, buttress, plinth and string course etc.
Sq.M. 911.00
( c) Suspended floors, roofs, inclined roofs and balconies / projections andchajjas, shelves.
Sq.M. 5,781.00
(d) Lintels, beams, girders, bressummers & cantilevers including sloping beams. Sq.M. 6,486.00
(e) Column, pillars, posts & struts. Sq.M. 2,966.00
(f) Staircase plain/folded plate including landings. Sq.M. 460.00
(g) Vertical and horizontal fins individually or forming box louvers, band andfacias and eaves boards.
Sq.M. 479.00
(h) Extra for shuttering in circular work (20% of respective centering andshuttering items)
Sq.M. 220.00
(i) Small lintels not exceeding 1.5 m clear span, moulding as in cornices,window sills, string courses, bands, copings, bed plates, anchor blocks andthe like
Sq.M. 69.00
8 REINFORCED CEMENT CONCRETE
Providing and laying in position machine batched and machine mixed designmix M-25 grade cement concrete for reinforced cement concrete work, usingcement content as per approved design mix, including pumping ofconcrete to site of laying but excluding the cost of centering, shuttering,finishing and reinforcement, including admixtures in recommendedproportions as per IS: 9103 to accelerate, retard setting of concrete, improveworkability without impairing strength and durability as per direction ofEngineer-in-charge. All works at all heights and level.Engineer-in-charge. All works at all heights and level.
(a) In rafts, footings, pile caps, bases of columns and footing beams etc.Cum 839.00
All works above plinth level upto floor V level
(b) In lintels, beams, bressummers, suspended floors, roofs including inclinedroof, landings, balconies, chajjas, staircases etc. upto floor five level. Cum 1537.00
( c) In walls (of any thickness) including attached pillarsters, buttresses, plinthand string courses, fillets, column, pillars, piers, abutments posts and strutsetc. up to floor five level.
Cum 343.00
(d) Reinforced cement concrete work in vertical and horizontal fins individuallyor forming box louvers, facias and eaves boards up to floor five level,excluding the cost of centering, shuttering, finishing and reinforcement, with1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mmnominal size).
Cum 22.00
(e) Providing, hoisting and fixing upto floor five level pre-cast reinforced cementconcrete in shelves including setting in cement mortar 1:3 ( 1 cement : 3coarse sand) cost of required centring, shuttering and finishing with neatcement punning on exposed surfaces but excluding the cost ofreinforcement with 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stoneaggregate 12.5mm nominal size)
Cum 8.50
All works above floor V level
(f) In lintels, beams, bressummers, suspended floors, roofs including inclinedroof, landings, balconies, chajjas, staircases etc. upto floor five level. Cum 392.00
(g) In walls (of any thickness) including attached pillarsters, buttresses, plinthand string courses, fillets, column, pillars, piers, abutments posts and strutsetc. up to floor five level.
Cum 78.00
(h) Reinforced cement concrete work in vertical and horizontal fins individuallyor forming box louvers, facias and eaves boards up to floor five level,excluding the cost of centering, shuttering, finishing and reinforcement, with1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mmnominal size).
Cum 5.00
9 MASONRY WORKS
(a) Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:
Cum 104.00designation 7.5 in foundation and plinth in:
Cum 104.00
Cement mortar 1:4 (1 cement : 4 coarse sand)
(b) Providing and laying autoclaved aerated concrete (AAC) blocks masonrywith 100/150/200 mm thick AAC blocks in super structure above plinth levelup to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rateincludes providing placing in position 2 nos of 6mm dia MS bar at every thirdcoarse of masonry works.
Cum 1119.00
( c) Making circular opening for exhaust fan up to 600 mm dia in brick/AAC workby providing precast RCC ring of required diameter complete as directed byEngineer-in-Charge.
Each 24
(d) Extra for brick work / AAC block masonry / Tile brick masonry insuperstructure above floor V level, for each four floors or part thereof bymechanical means.
Cum 208.00
10 FLOORING
(a) Providing flat brick soling under foundation, floor, plinth beam includingpacking with coarse sand and watering etc complete as directed with bricksclass designation-75 in cement mortar in proportion 1:4 including curingcomplete as specified and as directed.
Sq.M. 1017.00
(b) 100 mm thick cement concrete in floors in proportion 1:2:4 (1 cement : 2coarse sand : 4 graded stone aggregate 20 mm nominal size) over flat bricksoling with brick of designation 75 (to be measured and paid separately)including curing etc. complete as directed.
Sq.M. 15.50
( c) 40mm thick cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with floating coat ofneat cement slurry.
Sq.M. 323.00
( d) Extra over item no.10(c) for finishing with NITOFLOR HARDTOP/equivalentof approved shade as per manufacturers specifications in place of floatingcoat of neat cement cement slurry complete as per drawing and as directedby the Engineer-in -charge
Sq.M. 323.00
(e) Stone tile (polished) work for wall lining over 12 mm thick bed of cementmortar 1:3 (1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/sqmincluding pointing in white cement complete.
8mm thick
Granite of any colour and shade Sq.M. 280.00
(f) Providing and laying flamed finish Granite stone flooring in required design(f) Providing and laying flamed finish Granite stone flooring in required designand patterns, in linear as well as curvilinear portions of the building allcomplete as per the architectural drawings with 18 mm thick stone slab over20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarsesand) laid and jointed with cement slurry and pointing with white cementslurry admixed with pigment of matching shade including rubbing, curing andpolishing etc. all complete as specified and as directed by the Engineerin-Charge :
Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eyeor equivalent.
Sq.M. 496.00
( g) Providing and fixing markana Chak doongri marble stone of averagethickness 18mm to 20mm over 20 mm thick base mortar of proportion 1:4 (1cement : 4 coarse sand) laid and jointed with tiles jointing compound ofmatching shade including half round moulding of the nose, rubbing andpolishing complete in all respects including cutting the stone to makenoutch/offset on all corners vertical and horizontal and moulding as per
noutch detail in drawing and directed in window sills
Sq.M. 17.00
(h) Extra over item no. 10(g) for mirror polishing of marble stone surfaces. Sq.M. 17.00
(i) Providing edge moulding to 18 mm thick marble stone counters, Vanitiesetc., including machine polishing to edge to give high gloss finishetc.complete as per design approved by Engineer-in-Charge.
Metre 584.00
Granite work
(j) Providing and fixing stone slab with table rubbed, edges rounded andpolished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions bycutting a chase of appropriate width with chase cutter and embedding thestone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as perdirection of Engineer-in-charge and finished smooth.
Sq.M. 6.00
Granite Stone of approved shade
(k) Kota stone slab flooring over 20 mm (average) thick base laid over andjointed with grey cement slurry mixed with pigment to match the shade of theslab, including rubbing and polishing complete with base of cement mortar 1jointed with grey cement slurry mixed with pigment to match the shade of theslab, including rubbing and polishing complete with base of cement mortar 1: 4 (1 cement : 4 coarse sand) : 25 mm thick
Sq.M. 359.00
(l) Providing and laying in floor Group -V matt finished ceramic tile of minimumthickness 7.8mm without warpage of approved design and manufacturerlaid on 20mm thick cement mortar 1:3(1cement:3 sand) including filling thejoints with pigmented tile joint filler Nitotile-GR or equivalent of matchingshade and approved manufacturer as per manufacturers specification etc.and cleaning the surface with detergent and water complete.Size 400 mm x 400mm..
Sq.M. 120.00
(m) Providing and laying polished vitrified tiles in floors and skirting in differentsizes with water absorption's less than 0.08% and conforming to IS: 15622of approved make in all colours and shades,laid on 20mm thick cementmortar 1:3 (1 cement : 3 coarse sand) including grouting the joints withapproved tile jointing compound of matching colour etc.complete. Size ofTile 1000x1000 mm
Sq.M. 4560.00
(n) Providing and laying matt finished vitrified tile of size 300x300x9.8mm havingwith water absorption less than 0.5% and conforming to IS: 15622 ofapproved make in all colours and shades in for outdoor floors such asfootpath, court yard, multi modals location etc., laid on 20mm thick base ofcement mortar 1:4 (1cement : 4 coarse sand) in all shapes & patternsincluding grouting the joints with white cement mixed with matching pigmentsetc. complete as per direction of Engineer-in-Charge.
Sq.M. 150.00
(o) Extra for providing opening of required size & shape for wash basins, kitchensink in kitchen platform, vanity counters and similar locations in mable/granite/ stone work including necessary holes for pillar tapes etc. includingrubbing and polishing of cut edges etc. complete.
Each 28
11 DADO, SKIRTING, STEPS & RISERS
(a) Providing and laying Vitrified tiles in different sizes (thickness to be specifiedby manufacturer), with water absorption less than 0.08 % and conforming toI.S. 15622, of approved make, in all colours & shade, in skirting, riser ofsteps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarsesand), including grouting the joint with white cement & matching pigments
Sq.M. 373.00sand), including grouting the joint with white cement & matching pigmentsetc. complete.Size of Tile 1000x1000 mm
(b) Providing and fixing ceramic tiles of approved design & shade and ofminimum thickness 5.6mm thick in dado/skirting in any pattern and size over12mm thick cement mortar 1:3(1cement : 3 coarse sand ) and filling thejoints with Nitotile-GR or equivalent of matching shade as per manufacturersspecification etc and cleaning the surface with detergent and watercomplete. Size-300mm x 600 mm
Sq.M. 490.00
(c) Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laidon 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) andjointed with grey cement slurry mixed with pigment to match the shade of theslabs, including rubbing and polishing complete.
Sq.M. 85.00
(d) Extra for nosing of the stone edges as per detail and polishing the same togive mirror finish as directed by Engineer in Charge. Rm 658.00
12 DOORS AND WINDOWS
(a) Providing and fixing pressed steel door frames confirming to IS:4351manufactured from commercial mild sreel sheet of 1.6mm thicknessincluding hinges ,jamb,lock jamb,bead and if required angle threshold of mildsteel angle of section 50x25mm or base ties of 1.6mm pressed mild steelwelded or rigidly fixed together by mechanical means,adjustable lugs withsplit end tail to each jamb including steel but hinges 2.5mm thick with mortarguards,lock strike plate and shock absorber as specified and applying a coatof approved steel primer after ptre treatment of the surface as directed byEngineer-in Charge a) Profile-B
Rm 410.00
(b) Providing and fixing ISI marked flush door shutters conforming to IS: 2202(Part) decorative, core of block construction with frame of 1st class hardwood and well matched teak 3 ply veneering with vertical grains or crossbands and face vanees on both faces of shutters.
Sq.M. 153.00
35 mm thick including ISI marked Stainless Steel built hinges with necessaryscrews.
(c ) Providing and fixing ISI marked flush door shutters conforming to IS : 2202(Part I) non-decorative type, core of block board construction with frame of1st class hard wood and well matched commercial 3 ply veneering withvertical grains or cross bands and face veneers on both faces of shutters:
30 mm thick including ISI marked Stainless Steel butt hinges with necessaryscrews
Sq.M. 11.00
(d) Providing and fixing glazing in doors, windows and ventilators shutterscompete as per architectural drawings and the directions of Engineer-in–charge.
With clear glass panes of 5.0 mm thickness (weight not less than 13.75kg/sqm)
Sq.M. 370.00
(e) With float glass panes of 8 mm thickness
Sq.M. 65.00
(f) With frosted glass panes of 5.0 mm thickness (weight not less than13.75kg/sqm) Sq.M. 48.00
13 ALUMINIUM WINDOWS
(a) Providing and fixing powder coated aluminium work for doors,windows(catchment/sliding), ventilators, partitions or any other places withextruded built up standard tubular and other sections of approved makeconfirming to IS:733 and IS: 1285, anodised transparent according to IS:1868 (Minimum anodic coating of grade AC 15), fixed with rawl plugs andscrews or with fixing clips, or with expansion hold fasteners includingnecessary filling up of gaps at junction, at top, bottom and sides withrequired PVC/ neoprene felt, silicon sealants etc. to make perfactlywatertight. Aluminium sections shall be smooth , rust free, straight, andjointed mechanically wherever required including cleat angle, aluminiumsnap beading for glazing/ panelling, C.P./ stainless steel screws, hinges allcomplete as per architectural drawings and the directions of Engineer-in-Charge. (Glazing and panelling shall be paid separately)
Aluminium sections shall be smooth, rust free, straight, mitred and jointedmechanically wherever required including cleat angle, Aluminium snapbeading for glazing / paneling, C.P. brass / stainless steel screws, allcomplete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
kg 5527.00
For fixed portions like outer frames etc
(b) For shutters of doors, windows & ventilators including providing and fixinghinges/ pivots and making provision for fixing of fittings wherever requiredincluding the cost of EPDM rubber / neoprene gasket required (Fittings shallbe paid for separately)be paid for separately)
Polyester powder coated aluminium (minimum thickness of polyester powdercoating 50 micron)
kg 3423.00
( c) Providing and fixing of double action heavy duty Hydraulic door spring ofapproved make (hardwyn or equivalent) Each 78
(d) Providing and fixing 12mm prelaminated three layer medium density(exteriorgrade) particle board Grade-I, type-II conforming to IS:12823 bonded withphenol formaldehyde synthetic resin of approved brand and manufacturer inpanelling fixed in aluminium door shutter with C.P./ Brass/ stainless steelscrews etc. complete as per Architectural drawings and the direction ofEngineer-in-charge
Sq.M. 115.00
(e) Providing and fixing 12mm thick frameless toughened glass door shutter ofapproved brand and manufacture, including providing and fixing top &bottom pivot & spring type fixing arrangement and making necessary holesetc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc. to be paid separately)
Sq.M. 15
(f) Providing and fixing aluminium casement window stainless steel frictionstays of required length for aluminium windows with necessary screws etc.complete.
pair 21
14 PARTITIONS AND FALSE CEILING WORKS
(a) Providing and fixing false ceiling at all height including providing and fixing offrame work made of special sections, power pressed from M.S. sheets andgalvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS :277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick withflanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixedto the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm diabolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm ofrequired length with nuts & bolts of required size and other end of anglehanger fixed with intermediate G.I. channels 45x15x0.9 mm running at thespacing of 1200 mm centre to centre, to which the ceiling section 0.5 mmthick bottom wedge of 80 mm with tapered flanges of 26 mm each havinglips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a directionperpendicular to G.I. intermediate channel with connecting clips made
Sq.M. 4079.00
out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixingperimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and30 mm long, the perimeter of ceiling fixed to wall/partition with the help ofrawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mminterval, including fixing of gypsum board to ceiling section and perimeterchannel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c,including jointing and finishing to a flush finish of tapered and square edgesof the board with recomme-nded jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides ofjoint and two coats of primer suitable for board, all as per manufacturer’sspecification and also including the cost of making openings for light fittings,grills, diffusers, cutouts made with frame of perimeter channels suitablyfixed, all complete as per drawings, specification and direction of theEngineer in Charge but excluding the cost of painting with
12.5 mm thick tapered edge gypsum moisture resistant board
(b) 98mm thick metal stud partition which includes one layer of tapered edge13mm thick DURALINE gypboard of India gypsum or equivalent (confirmingto IS:2095-1982) screw fixed with drywall screws of 25mm at 300mm centresto either sides of 70mm studs (0.55mm thick having one flange of 34mm &another flange of 36mm made GI steel) placed at 610mm centre to centre in72mm floor and ceiling channel (0.55mm thick having equal flanges of 32mm made GI steel) with joints staggered to avoid leakage through joints. Finallythe square and tapered edges of the boards are to be joined and finished soas to have a flush look which includes filling and finishing with jointing Sq.M. 420.00as to have a flush look which includes filling and finishing with jointingcompound. Joint paper tape and two coats of drywall top coat suitable forgypboard including angle bead to be at external angles to get straight linefinish & protection from normal impacts and edge bead to be used to protectthe exposed gypsum core of gypboard specially at cut edges of the openingfor doors/ windows/ glazig or any other unprotected core complete as per thedrawing & direction of engineer-in-charge (as per recommended practices ofIndia gypsum)
Sq.M. 420.00
15 STEEL WORK
(a) Providing and fixing M.S. grills of required pattern in frames of windows etc.with M.S. flats, square or round bars etc. including priming coat withapproved steel primer all complete.
Fixed to openings /wooden frames with rawl plugs screws etc. Kg 3348.00
(b) Steel work in built up tubular ( round, square or rectangular hollow tubesetc.) trusses etc.,including cutting, hoisting, fixing in position and applying apriming coat of approved steel primer, including welding and bolted withspecial shaped washers etc. complete.
Kg 23058.00
Hot finished welded type tubes
( c) Providing and fixing stainless steel ( Grade 304) railing made of Hollowtubes, channels, plates etc., including welding, grinding, buffing, polishingand making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete, i/c fixing the railing withnecessary accessories & stainless steel dash fasteners , stainless steelbolts etc., of required size, on the top of the floor or the side of waist slabwith suitable arrangement as per approval of Engineer-in-charge, (forpayment purpose only weight of stainless steel members shall be consideredexcluding fixing accessories such as nuts, bolts, fasteners etc.).
Kg 6665.00
(d) Providing, fabrication and fixing of structural glazing made out of colouredanodised aluminium mother frame (INDAL 9303) and subframe (INDAL9406)and 5mm reflective glass of approved shade. The glass to be pasted usingstructural silicon (DC995) and weatherseal silicon to be used (DC789), thestructure complete with all accessories as and where necessary.
Sq.M. 444.00
16 WOOD & P.V.C. WORK
(a) Providing wood work in frames of doors, windows, clerestory windows andother frames, wrought framed and fixed in position with hold fast lugs or withdash fasteners of required dia & length ( hold fast lugs or dash fastener shall
Cum 4.00dash fasteners of required dia & length ( hold fast lugs or dash fastener shallbe paid for separately).
Second class teak wood
( b) Providing and fixing Pre-laminated flat pressed 3 layer (medium density)particle board or graded wood particle board IS : 3087 marked, with one sidedecorative and other side balancing lamination Grade I, Type II exteriorgrade IS : 12823 marked, in shelves with screws and fittings whereverrequired, edges to be painted with polyurethane primer (fittings to be paidseparately).
Sq.M. 145.00
18 mm thick
(c) Extra for providing lipping with 2nd class teak wood battens 25 mm minimumdepth on all edges of flush door shutters (over all area of door shutter to bemeasured).
Sq.M. 153.00
(d) Providing and fixing cup board shutters 25 mm thick, with Pre-laminated flatpressed three layer particle board or graded wood particle board IS: 12823marked, exterior grade (Grade l Type ll), having one side decorativelamination and other side balancing lamination, including IInd class teakwood lipping of 25 mm wide x12 mm thick with necessary screws and brightfinished stainless steel piano hinges, complete as per direction of theEngineer-in-Charge
Sq.M. 45.00
17 TERRACING
( a) Providing and fixing on wall face unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A,including jointing with seal ring conformingto IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.
Metre 450.00
110 mm diameter
( b) Providing and fixing on wall face un-plasticised - Regid PVC moulded fittingsconforming to IS : 13592 type-A including jointing with seal ring conformingto IS : 5382 leaving 10 mm gape for thermal expansion
Coupler
110 mm Each 225
Bend 87.5°
110 mm bend Each 18
Shoe (Plain)
110 mm Shoe Each 18
( c) Providing and fixing unplasticised -PVC pipe clips of approved design tounplasticised - PVC rain water pipes by means of 50x50x50 mm hard woodplugs, screwed with M.S. screws of required length, including cutting brickwork and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and makinggood the wall etc. complete.
Each 225
110 mm
(d) Providing gola 75x75mm in cement concrete 1:2:4 (1cement:2coarsesand:4 graded stone aggregate 10mm and down size) including finishingwith cement mortar 1:3( 1cement:3 fine sand) as per standard design. In75x75mm deep chase.
Metre 148.00
( e) Making khurras 45x45 cm with average minimum thickness of 5cm cementconcrete 1:2:4 (1cement:2 coarse sand:4 graded stone aggregate 20mmnominal size) over 1mX1mx 400 micron PVC sheet finished with 12mm thickcement plaster 1:3 (1cement:3 coarse sand) and a coat of neat cementrounding the edges and making and finishing the outlet complete.
Each 18
( f) Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15cm diameter and weighing not less than 440 grams. Each 18
( h) Providing and fixing precoated galvanised iron profile sheets (size, shapeand pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05 %) total coated thickness with zinc coating 120 grams per sqm as perIS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side ofthe sheet and polyester top coat 15-18 microns. Sheet should haveprotective guard film of 25 microns minimum to avoid scratches duringtransportation and should be supplied in single length upto 12 metre or asdesired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto anypitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins,rafters and trusses and including cutting to size and shape whereverrequired.
Sqm 444
( i) Providing and fixing precoated galvanised steel sheet roofing accessories0.50 mm (+ 0.05 %) total coated thickness, Zinc coating 120 grams per sqmas per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on bothside of the sheet and polyester top coat 15-18 microns using self drilling/ self
Rm 163.00as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on bothside of the sheet and polyester top coat 15-18 microns using self drilling/ selftapping screws complete :
Rm 163.00
Flashings/ Aprons.( Upto 600 mm)
( j) Providing & Fixing of 12mm thick UV protected polycarbonate panels withopaque & Transluscent combination for aesthetic appeal with verticalstanding seam on both sides, snap on locking system. The system will befitted on MS rafters/Purlin (will be paid separately) with spacing as specifiedby manufacturer.
Sq.M. 466.00
18 WATER PROOFING
(a) Providing water proofing treatment with best quality acrylic polymer modifiedcementitious composite slurry quoating and fibre glass cloth of approvedbrand over sunken floors roof and terraces as per manufacturer'sspecification and as approved by Engineer-in-Charge.
Sq.M. 265.00
(b) Providing and laying water proofing treatment on roofs of slabs by applyingcement slurry mixed with water proofing cement compound consisting ofapplying: a) after surface preparation, first layer of slurry of cement @ 0.488kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. b)laying second layer of Fibre glass cloth when the first layer is still green.Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layerof 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixedwith water proofing cement compound @ 0.670 kg/sqm and coarse sand @1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by watercuring for 48 hours. The entire treatment will be taken upto 30 cm on parapetwall and tucked into groove in parapet all around. d) fourth and final layer ofbrick tiling with cement mortar (which will be paid for separately. For thepurpose of measurement the entire treated surface will be measured.
Sq.M. 946.00
( c) Grading roof for water proofing treatment with
Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size)
Cum 66.00
(d) Cement mortar 1:4 (1cement : 4 coarse sand) Cum 66.00
19 FINISHING
(a) 12 mm thick cement plaster on even surface of wall with cement mortar 1:4(1 cement : 4 sand)
Sq.M. 18734.00
(b) 15 mm thick cement plaster on the rough side of single or half brick wall with(b) 15 mm thick cement plaster on the rough side of single or half brick wall withcement mortar of 1:4 (1 cement : 4 sand) Sq.M. 8847.00
( c) 6 mm plaster to ceiling in cement mortar 1:3 (1 cement : 3 sand) Sq.M. 5500.00
( d) 20mm thick cement plaster 1:3(1 cement : 3 coarse sand) finished with afloating coat of neat cement slurry damp proof on wall between plinth leveldifference.
Sq.M. 180.00
( e) 18 mm thick cement mortar plastering consisting of 12mm undercoat ofcement mortar 1:4(1 cement : 4 coarse sand) with 6mm thick finishing coatof cement mortar 1:3(1cement:3 fine sand) to give desired pattern oversloping roof
Sq.M. 444.00
(f) Neat cement punning. Sq.M. 454.00
(g) Providing and applying wall care putty of Birla White/JK white or equivalentat all heights and levels on the entire surface including removal ofundulations and sand papering the wall after the surface is dry to get asmooth and even surface
Sqm 27581.00
(h) Providing and applying cement primer of approved manufacturers overprepared surface Sq.M. 27581.00
(i) Finishing walls with textured exterior paint of required shade
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and includingpriming coat of exterior primer applied @ 2.20kg/ 10 sqm
Sq.M. 250.00
(j) Finishing walls with water proofing cement paint or equivalent of approvedcolour, Shade and anufacturer and as per direction of Engineer-in -charge -New Work
Sq.M. 300.00
(k) Finishing walls with fungus and algae resistant superior grade water proofacrylic paint of approved shade and brand to give an even shade to allexternal wall surfaces(two or more coats) including surface preparation togive an even surface as per manufacturer's specification
Sq.M. 8847.00
(l) Applying priming coat :
With ready mixed pink or Grey primer of approved brand and manufactureon wood work (hard and soft wood)
Sq.M. 420.00
(m) Painting with synthetic enamel paint of approved brand and manufacture to(m) Painting with synthetic enamel paint of approved brand and manufacture togive an even shade :Two or more coats on wood work/ steel work in allshades
Sq.M. 1624.00
(n) Varnishing with varnish of approved brand and manufacture
Two or more coats of glue sizing with copal varnish over an under coat offlatting varnish
Sq.M. 306.00
(o) Providing and applying on walls two or more coats of Acrylic emulsion ofapproved shades and manufacturer. Sq.M. 18734.00
(p) Providing and applying on walls and ceiling two or more coats of Acrylicwashable distemper of approved shades and manufacturer. Sq.M. 5500.00
20 BUILDING HARDWARE
(a) Providing 40x5 mm flat iron hold fast 40 cm long including fixing to framewith 10 mm diameter bolts, nuts and wooden plugs and embedding incement concrete block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand: 6graded stone aggregate 20mm nominal size).
Each 1000.00
(b) Providing and fixing special quality bright finished brass cupboard or wardrobe locks with four levers of approved quality including necessary screwsetc. complete.50 mm
Each 68
( c ) Providing and fixing aluminium sliding door bolts, ISI marked anodisedanodic coating not less than grade AC 10 as per IS : 1868), transparent ordyed to required colour or shade, with nuts and screws etc. complete :
Each 114
300x16 mm
(d) Providing and fixing aluminium tower bolts, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868 ) transparent or dyed torequired colour or shade, with necessary screws etc. complete :
Each 246
300x10 mm
(e) Providing and fixing aluminium handles, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868) transparent or dyed torequired colour or shade, with necessary screws etc. complete :
125 mm
Each 142
100 mm
Each 68
(f) Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour and shade, with necessary screwsetc. complete.
Single rubber stopper
Each 38
Twin rubber stopper
Each 78
(g) Providing and fixing aluminium round shape handle of outer dia 100 mm withSS screws etc. complete as per direction of Engineerin-charge
Polyester powder coated minimum thickness 50 micronaluminium
Each 156
21 MISCELLANEOUS ITEMS
(a) Under Deck (Roof) Insulation:SINGLE LAYER SYSTEM UNDER DECKTHERMAL INSULATION SYSTEM WITH INSU.BOARD
Sq.M. 790.00
Cleaning of the surface by brush
(b) Day Time use Building: Providing & Laying of Insuboard, thickness 50mm ofdensity 32 kgs/ cum over the RCC CEILING ( Plastered Surface) frominside. The insuboard will be fixed over the wall surface by the PVC Fastner(side lap) (Make: M/S Supreme or equivalent)
Sq.M. 790.00
PARTITIONS AND ASSOCIATED WORKS
Toilet Cubical
( d) Providing & fixing Greenlam Sturdo Classique Versatile Toilet Cubicle (of
following standard dimension which includes 600mm door size width) made
of heat, bacteria, water, chemical, scratch, impact and anti bacterial
resistant 12mm thick solid compact laminate panels tested by Shriram
Test House. Finish of the compact laminate should be Suede, which
includs doors, pilasters & intermediate panels finished with approvedtexture/shade as per the detail drawings & as per IS 2046 (Indian Standard)
and as per fire retardant BS-476/97 standard. The product should have
Green Guard Certificate.
This also includes providing and fixing in position necessary hardware made
No. 11.00
This also includes providing and fixing in position necessary hardware madeout of Stainless steel (Grade 304) &
Aluminium powder coated top rail as per manufacturer’s specifications &Architects instructions like (1) SS Door Knob, (2) SS Gravity hinges, (3) SSThumb turn lockset indicators, (4) Aluminum Powder Coated Top Rail, (5)SS Coat Hooks, (6) SS U-Channels, (7) SS Adjustable Foot, (8) NoiseDeafening Tape etc. (9) Screws & wall Plugs.The top fitting should consist of Aluminium Powder Coated top rail which willget fixed with Mid & End pilasters. All other hardware & screws will of stainless steel in 304 Grade with satinfinish. Top rail is extruded Aluminium will be powder coated or anodized(Grade 6063 Micron Aluminium). All pilasters are supported by stainlesssteel adjustable footing with non corrosive steel inserts.
Toilet Cubicle with standard dimension of 1955mm Height x 1000mm
Width x 1550mm Depth, which includes 600mm door size width).
Toilet Cubicle I-Shape (Front Partition) with standard dimension of
1955mm Height x 1000mm Width which includes 600mm door size width).
All aspects specified by the manufactures, Greenlam Sturdo Classique
Versatile Model or equivalent.
TOTAL (PART - A : Building Works)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1 Providing and fixing water closet squatting pan (Indian type W.C. pan ) with100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushingcistern, including flush pipe, with manually controlled device (handle lever)conforming to IS : 7231, with all fittings and fixtures complete, includingcutting and making good the walls and floors wherever required:
White Vitreous china Orissa pattern W.C. pan of size 580x440 mm withintegral type foot rests
Each 4
2 Providing fitting and fixing Vitreous china wall hang water closet (Europeantype W.C pan 400mm high) with seat and lead ,CP brass hinges and rubberbuffers , CI/MS brackets , 40 mm dia flush band with fittings includingpainting of fittings and brackets, required. (Flushing Cistern to be paidseparately)
a) Parryware make
Indus walvit Pan set (inclusive of seat cover and fittings) (white) Each 21
3 Providing and fixing white vitreous china flat back or wall corner type lippedfront SENSOR operated urinal basin of approved size. (Sample to beapproved by the engineer in charge)
Each 14
4 Providing and fixing toilet paper holder :
C.P. brass Each 21
PART - B : Sanitary and Water Supply Installation
Name of Work : Construction of Centre for Educational Technology (CET) Building
C.P. brass Each 21
5 Providing and fixing one piece construction white vitreous china squattingplate with an integral longitudinal flushing pipe, white P.V.C. automaticflushing cistern, with fittings, standard size G.I. / PVC flush pipe for back andfront flush with standard spreader pipes with fittings, G.I clamps and C.P.brass coupling complete, including painting of fittings and cutting and makinggood the walls and floors etc. wherever required :
Single squatting plate with 5 litre P.V.C. automatic flushingcistern
Each 3
6 Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200mm wide with minimum distances of 37 mm from wall face with concealedfittings arrangement of approved quality and colour, weighing not less than88 gms.
Each 28
7 Providing and fixing PTMT towel rail complete with brackets fixed to woodencleats with CP brass screws with concealed fitting arrangement of approvedquality and colour. 600mm long towel rail with total length of 645mm, width78mm and effective height of 88mm, weighing not less than 190gms.
Each 20
8 Providing and fixing square-mouth S.W. gully trap grade 'A' complete withC.I. grating brick masonry chamber with water tight C.I. cover with frame of300x300mm size (inside) the weight of cover to be not less than 4.50 kg andframe to be not less than 2.70 kg as per standard design: 100x100mm sizeP type. With F.P.S. Bricks class designation 75.
Each 21
9 Providing vitreous china counter-top wash basin of size 490mm dia ofHindware make with 32mm CP brass waste coupling of standard pattern,C.P brass chain with plug, PVC waste pipe including painting of fittings andbrackets, cutting and making good the wall and slabs wherever required.
Each 27
a) Coloured vitreous china counter-top wash basin of size 490mm dia
10 Providing, fitting and fixing recessed soap tray of Hindware make completeas specified and directed, Coloured. Size 216mm x 108mm. Each 27
11 Providing and fixing 600x450mm bevelled edge mirror of superior glass (ofapproved quality) complete with 6mm thick hard board ground fixed towooden cleats with C.P. brass screws and washers complete.
Each. 27
12 Supplying and fitting fixing C.P. pillar cock of 15mm dia of 5011 of Jaquarbrand as specified and directed. Each 56brand as specified and directed. Each 56
13 Providing and fixing 600x120x5 mm glass shelf with edges rounded offsupported on anodised aluminium angle frame with C.P. brass brackets andguard rail complete fixed with 40mm long screws, rawl plugs etc. complete.
Each 27
14 Providing fitting and fixing C.P. Grating to the floors complete as directedand specified.
Circular type
100 mm nominal dia Each 35
15 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including paintingof fittings and brackets, cutting and making good the walls wherever required:
Each 1
Kitchen sink with drain board
510x1040 mm bowl depth 250 mm
16 Providing and fixing white vitreous china laboratory sink with C.I. brackets,C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P.brass trap with necessary C.P. brass unions complete, including painting offittings and brackets, cutting and making good the wall wherever required :
Each 28
Size 600x450x200 mm
17 Providing and fixing P.V.C. waste pipe for sink or wash basin includingP.V.C. waste fittings complete.
Semi rigid pipeEach 56
32 mm dia
18 Providing and fixing PTMT Waste Coupling for wash basin and sink, ofapproved quality and colour.
Waste coupling 38 mm dia of 83 mm length and 77mm breadth,weighing not less than 60 gms
Each 27
19 Providing and fixing PTMT Bottle Trap for Wash basin and sink.
Bottle trap 31mm single piece moulded with height of 270 mm, effectivelength of tail pipe 260 mm from the centre of the waste coupling, 77 mmbreadth with 25 mm minimum water seal, weighing not less than 260 gms
Each 27
PP- R PIPES
20 Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipesSDR 7.4, U V stabilized & anti - microbial fusion welded, having thermalstability for hot & cold water supply, including all PP - R plain & brassthreaded polypropylene random fittings, i/c fixing the pipe with clamps at1.00 m spacing. This includes testing of joints complete as per direction of1.00 m spacing. This includes testing of joints complete as per direction ofEngineer in Charge.
Internal work - Exposed on wall
18.4.3 PN - 16 Pipe, 25 mm OD Metre 40.00
18.4.4 PN - 16 Pipe, 32 mm OD Metre 70.00
18.4.5 PN - 16 Pipe, 40 mm OD Metre 100.00
21 Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipesSDR 7.4, U V stabilized & anti - microbial fusion welded, having thermalstability for hot & cold water supply, including all PP - R plain & brassthreaded polypropylene random fittings, i/c fixing the pipe with clamps at1.00 m spacing. This includes the cost of cutting chases and making goodthe same including testing of joints complete as per direction of Engineer inCharge.
Concealed work, including cutting chases and making good the
walls etc.,
PN - 16 Pipe, 16 mm OD
Metre 90.00
PN - 16 Pipe, 20 mm OD
Metre 110.00
PN - 16 Pipe, 25 mm OD
Metre 90.00
BRASS FITTINGS
22 Providing and fixing brass bib cock of approved quality :
15 mm nominal bore Each 28
23 Providing and fixing brass stop cock of approved quality :
15 mm nominal bore Each 62 15 mm nominal bore Each 62
24 Providing and fixing ball valve (brass) of approved quality, High or lowpressure, with plastic floats complete :
15 mm nominal bore Each 15
25 Providing and fixing uplasticised PVC connection pipe with brass unions :
45 cm length
15 mm nominal bore Each 24
26 Constructing masonry Chamber 60x60x75 cm inside, in brick work in cementmortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside)with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4graded stone aggregate 20mm nominal size ) , i/c necessary excavation,foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stoneaggregate 40 mm nominal size) and inside plastering with cement mortar 1:3(1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neatcement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of classdesignation 7.5
Each 10
27 Providing and fixing PTMT soap Dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fitting arrangements,weighing not less than 106 gms.
Each 27
PVC PIPES,BENDS,JUNCTIONS,TEES ETC.
28 Supplying, fitting and fixing PVC pipes of 6 Kg/cm2 (Supreme/Prince) orother ISI approved including joining ,fitting and fixing with clamps etc.asnecessary complete at all levels including below G.L as directed andspecified.
a) In exposed surfaces or in trenches.
110 mm dia Metre 120.00
75 mm diameter : Metre 95.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Metre 190.00
75 mm diameter : Metre 185.00
29Supplying, fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) orother ISI approved including joining ,fitting and fixing etc.as necessarycomplete at all levels including below G.L as directed and specified.
a) In exposed surfaces or in trenches.
110 mm dia Each 25.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Each 20.00
75 mm diameter : Each 10.00
30 Supplying fiting and fixing 87.5 degree PVC bend with door of(Supreme/Prince) or other ISI approved including joining , fitting and fixingetc. as necessary complete at all levels including below G.L. as directed andspecified.
a) In exposed surfaces or in trenches.
110 mm dia Each 25.00110 mm dia Each 25.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Each 20.00
75 mm diameter : Each 10.00
31Supplying fiting and fixing 45degree PVC bend of (Supreme/Prince) orother ISI approved including joining , fitting and fixing etc. as necessarycomplete at all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
110 mm dia Each 25.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Each 20.00
75 mm diameter : Each 10.00
32Supplying fiting and fixing PVC Plain single tee of (Supreme/ Prince) or otherISI approved including joining, fitting and fixing etc. as necessary completeat all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
110 mm dia Each 25.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.good to the damages.
110 mm dia Each 15.00
75 mm diameter : Each 15.00
33 Supplying fiting and fixing PVC single tee with door of (Supreme/Prince) orother ISI approved including joining , fitting and fixing etc. as necessarycomplete at all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
110 mm dia Each 15.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Each 15.00
75 mm diameter : Each 15.00
34 Supplying fiting and fixing PVC single ‘Y’ of (Supreme/Prince) or other ISIapproved including joining , fitting and fixing etc. as necessary complete atall levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
110 mm dia Each 15.00
75 mm diameter : Each 15.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
110 mm dia Each 10.00
75 mm diameter : Each 10.00
TOTAL (PART - B : Sanitary and Water Supply Installation)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1 Earth work in excavation over areas (exceeding 30 cm in depth, 1.5 m inwidth as well as 10 sqm on plan including disposal of excavated earth,including all lead and lift, disposal earth to be leveled and neatly dressed : All types of soil
Cum 64.8
2 Earthwork in filling for site preparation with approved quality earth includingfilling the portion within plinth area upto the formation level, peripheral apron& drains etc. complete upto the formation level in layers not exceeding 20cm in depth including watering, ramming, consolidating to the acceptable densityand dressing complete as directed including obtaining earth and removal oftop vegetation ,dressing the surface upto proper grade and slope. (The rateshall be inclusive of providing earth including all lead and lifts, payment forland compensation for obtaining earth, payment of royalty, taxes etc. thepayment of earthwork shall be made in profile measurement.)
Cum 786.6
3 Earth work in excavation for foundation trenches and drains including bailingout water, dressing of sides, shoring & strutting, ramming of bottoms,including all lifts from the existing ground level and getting out the excavatedsoil, disposal of excavated soil at suitable places within the IIT campus asdirected including refilling the foundation trenches with approved qualityselected, excavated/ imported soil (excluding rock) etc. in trenches, plinth, Cum 64.8
PART - C : Site Development Work
Name of Work : Construction of Centre for Educational Technology (CET) Building
selected, excavated/ imported soil (excluding rock) etc. in trenches, plinth,sides of foundations etc., including bailing out water before filling in layersnot exceeding 20cm in depth; consolidating/compacting each depositedlayer to the acceptable density by ramming and watering all complete asdirected with all leads and lifts.
Cum 64.8
(retaining wall manholes, sewer line etc.) (Measurements for excavation forfoundation of columns shall be taken on vertical lines with 300mm toleranceall around the finished concrete of foundation and that for plinth beams/wallsor any other structures, shall be made on vertical lines with tolerance of150mm around the finished surfaces. No extra payment will be made onaccount of removal of slipped earth and backfilling thereof, dewatering,shoring & strutting, etc.)
4 Brick work with bricks of class designation 75 in foundation & plinth incement mortar 1:4 (1 cement : 4 coarse sand) Cum 36.45
5 20mm thick cement plaster 1:3(1 cement : 3 coarse sand) finished with afloating coat of neat cement slurry damp proof on wall between plinth leveldifference.
Sqm 306.00
6 Cement concerete 1:2:4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size) in pavements, laid to required slope andcamber in panels as required including consolidation finishing and tempingcomplete.
Cum 16.2
7 Providing and laying interlocking precast cement concrete paver of approveddesign and compressive strength of 300kg/sqcm laid on a bed of 40mm thickcoarse sand including filling the joints with local sand complete 75mm
sqm 170
8 Labour for consolidaiton of stone metal (construction of Water BoundMacadam) including local carriage of materials within one Km. Spreadingthe stone metal evenly and uniformly over the prepared sub-grade and sub-base, between prepared shoulders in layers of thickness not exceeding100mm (loose)/200mm (loose) incase of 53.22.4mm size aggregates, testingthe depth with depth blocks and surface with templates, correcting the highand low spots by adding or removing, stones, dry rolling with a power rollerof 8-10 tonnes, commencing rolling from the edges, running the rollersforward and backward until the edges are fimrly compacted, progressingrolling from edges to centre, parallel to the centrline of the road and lappinguniformly the preceeding rear wheel by one half width, rolling on until theuniformly the preceeding rear wheel by one half width, rolling on until theentire area of the surface has been rolled by the rear wheel and until theroad metal is throughly keyed and creeping of stone ahead of the roller is nolonger visible,slight sprinkling of water, if required, adding or removingmaterials after lossening, if necessary, to keep the longitudinal and the crossprofile within the permissible tolerance limits, checking the profile withtemplate and straight edges, applying screenings in 3 or more applications ata uniform and slow rate, dry rolling till the surface is free from any deformity,copiously sprinkling water (to be supplied by the contractor), sweepingrolling, applying additional screenings and water forms ahead of the roller,applying binding materials (to be supplied by the contractor) and sufficientwateing and rolling until a paste of blindge and water beings to flow ahead ofthe roller, (WBM will be measured as finsiehd work in position for thecompacted thickness)
cum 40
9 Turfing with selection No.1 grass including watering and maintenance of the lawn for 30 days
or more till the grass forms a thick lawn, free from weeds and fit for mowing including
supplying good earth, if needed (the good earth shall be paid for separately).Sqm 120
10 Constructing brick masonry circular type manhole 0.91 m internal dia atbottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand),in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with a floating coat of neat cement, foundationconcrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size), and making necessary channel in cement concrete 1:2:4(1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)finished with a floating coat of neat cement, all complete as per standarddesign : 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20grade designation) 560 mm internal diameter conforming to I.S. 12592, totalweight of cover and frame to be not less than 182 kg., fixed in cementconcrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mmnominal size) including centering,shuttering all complete. (Excavation, foot rests and12mm thick cement plaster at the external surface shall be paid forseparately) : With common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5
Each 25
11 Clearing jungle including uprooting of rank vegetation, grass, brush wood,trees and saplings of girth upto 30 cm measured at a height of 1 m aboveground level and removal of rubbish upto a distance of 50 m outside theperiphery of the area cleared.
Sq.M. 1311.00
TOTAL (PART - C : Site Development Work)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1.0 POINT WIRING AND SUBMAIN WIRING
1.1
Wiring for light point / fan point / exhaust fan point / call bell point with 1.5sq.mm. PVC insulated, FR, multistrand copper conductor cable in surface/recessed medium class PVC conduit complete with modular switch, modularplate, suitable G.I. box and earthing the point with 1.5 sq.mm, FR PVC insulatedcoper conductor single core cable etc., as required..
Point 935
1.2
Wiring for twin control light point with 1.5 sq.mm FR PVC insulated copperconductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with1.5 sq.mm FR PVC insulated copper conductor single core cable etc. asrequired.
Point 68
1.3Wiring for submain with the following sizes of PVC insulated, FR copperconductor, single core cable in surface/recessed PVC conduit, as required.
a) 3 X 1.5 sq.mm Mtr. 1120
b) 3 X 2.5 sq.mm Mtr. 2600
PART - D : Electrical Works
Name of Work : Construction of Centre for Educational Technology (CET) Building
b) 3 X 2.5 sq.mm Mtr. 2600
c) 3 X 4 sq.mm Mtr. 36000
d) 3 X 6 sq.mm Mtr. 1500
e) 6 X 4 sq.mm Mtr. 2050
f) 6 X 2.5 sq.mm Mtr. 1360
g) 6 X 6 sq.mm Mtr. 1200
h) 2 X 10 sq.mm + 1 X 6 sq.mm earth wire Mtr. 800
i) 4 X 10 sq.mm + 2 X 6 sq.mm earth wire Mtr. 2700
j) 4 X 16 sq.mm + 2 X 6 sq.mm earth wire Mtr. 2550
1.4Supplying & fixing suitable size G.I. box with modular plate & cover in front onsurface or in recess, including providing & fixing, 3/5 pin 5/6 Amp. modularsocket outlet and 5/6 Amp. modular switch. connections etc., as required.
No. 340
1.5Supplying & fixing suitable size G.I. box with modular plate & cover in front onsurface or in recess, including providing & fixing 6 pin 15/16 Amp. Modularsocket outlet and 15/16 Amp. modular switch, connections, etc., as required.
No. 510
1.6Supplying & fixing following size / modules, G.I. box along with modular base &cover plate for modular switches / sockets in recess etc., as required.
a) 1 or two module (75 mm x 75 mm) No. 200
b) 3 module (100 mm x 75 mm) No. 50
c) 4 module (125 mm x 75 mm) No. 80
d) 6 module (200 mm x 75 mm) No. 200
e) 8 module (125 mm x 125 mm) No. 350
f) 12 module (200 mm x 150 mm) No. 180
1.7Supplying & fixing following modular switch / socket on the existing modularplate and switch box including connections, but excluding modular plate etc. asrequired.
a) 5/6A switch No. 400
b) 15/16A switch No. 600
c) 3/5 pin 5/6A socket No. 900
d) 6 pin 15/16A socket No. 800d) 6 pin 15/16A socket No. 800
1.8Supplying and fixing two module stepped type electronic fan regulator alongwith two module box cover plate etc. complete.
No. 25
1.9Supply & installation including connection to existing wiring etc. of followingpresence detectors / movement detector -
a) High sensitivity detector - area of detection, 1-7 m for Class rooms, Cat.-Hager / EE883 or equivalent.
No. 16
b) Single lens, 360°, 6 m dia detector, 10A, AC, 1 Channel surface / flushmounted for corridor / toilet - Cat.- Hager - EE804 / 805 or equivalent.
No. 48
1.10Supply & installation of modular 20 A, DP, Energy Key switch with boxes & allaccessories.
No. 16
2.0 CABLING
2.1 Supplying of following PVC/XLPE insulated cable 1.1 KV grade
a) 3.5 C 300 sq.mm Mtr. 800
b) 3.5 C 185 sq.mm Mtr. 200
2.2Laying of one number PVC/XLPE insulated and sheated 1.1KVgrade Aluminiumarmoured power cable of following size in ground including excavation & sandcushioning, brick protection and refilling etc. all complete.
a) above 185 sq.mm and upto 400 sq mm M 380
Laying of one additional number PVC/XLPE insulated and s sheathed cable 1.1KV grade aluninium armoured cable of following size direct in ground in same
2.3KV grade aluninium armoured cable of following size direct in ground in sametrench in one tier horizonal formation including excavation, sand cushioning,protective brick covering and refilling etc., as required size exceeding 120sq.mm but not exceeding 400 sq.mm
a) above 185 sq.mm and upto 400 sq mm M 380
2.4Laying of one number PVC/XPLE insulated and sheated 1.1KV gradeAluminium armouredpower cable of following size in duct pipe/trench etc.
a) above 95 sq.mm and upto 185 sq mm Mtr. 200
b) above 185 sq.mm and upto 400 sq mm Mtr. 40
2.5Supplying and making end termination with brass compression gland andaluminioum lig the following size of PVC/XLPE insulated conductor cable of1.1KV grade, as required.
a) 3½ C 300 sq.mm Set 4
b) 3½ C 185 sq.mm Set 20
3.0 DISTRUBTION BOARDS / MV PANEL
3.1Supplying and fixing of miniature circuit breaker with 'C' curve, 10 KA offollowing poles in the existing MCB DB complete with connections, testing andcommissioning etc., as required (5-32A).
a) Single pole No. 786
b) Double pole No. 24
c) Triple pole No. 32
d) Triple pole & netural No. 18
3.2Supplying and fixing single pole, blanking plate in the existing MCB DBcomplete etc. as required.
No. 60
3.3
Supplying and fixing 20amps, 240 volts, SPN industrial type, socket outlet, with2 pole and earth, metal enclosed plug top along with 20amps C-series, SP,MCB in sheet steel enclosure, on surface or in recess, with chained metal coverfor the socket outlet, and complete with connections, testing and commissioningetc. as required.
No. 50
3.4
Supplying and fixing 30amps, TPN industrial type socket outlet, with 4 pole andearth, metal enclosed plug top along with 30amps "C' series TP MCB in sheetenclosure, on surface or in recess, with chained metal cover for the socketoutlet and complete with connection, testing, commissioning as required.
No. 30
3.5
Supplying and fixing of following way single pole and netural, steel, dustprotected double door type MCB distribution board 240 volts, onsurfacew/racess complete with loose wire box, terminal blocks, tinned copperbusbar, neutral link, earth bar, din bar, detachable gland plate, inter-connections, including power coated painting,earthing etc., as required.
a) 8 way, Double door No. 12
b) 12 way, Double door No. 12
Supplying, installation, testing and commissioning of surface/recess mounting,horizontal type, double door 415 volts, TPN MCB distrubtionboard of sheet
3.6
horizontal type, double door 415 volts, TPN MCB distrubtionboard of sheetsteel, 1.6 mm thick, dust protected, duly phosphatized and painted, inclusive of200amps tinned copper busbars, earth bar, common neutral link, din bar formounting MCB's detachable gland/kNo.ck out plates, hinged front acrylic coerand with built in loose wire box, and superior make terminal connectiors for allincoming and outgoing circuits, duly prewired with adequate size of PVCinsulated copper wires between the busbars and the MCB's as well as theincomer and upto the terminal connectors/neutral link and ready for installation,of followin ways (but without the supply of outgoing MCB's/Isolator)
a) 6 way (4+18), Double door No. 18
3.7
Supplying, installation, testing and commissioning of surface/recess mounting,vertical type, double door, 415 volts, TPN MCB distrubtion board of sheet steel,1.6 mm thick, dust protected, duly phosphatized and painted, inclusive of200amps tinned copper busbars, earth bar, common neutral link, din bar formounting MCB's detachable gland/kNo.ck out plates, hinged front acrylic coverand with built in loose wire bix, and superior make terminal connectiors for allincoming and outgoing circuits, duly prewired with adequate size of PVCinsulated copper wires between the busbars and the MCB's as well as theincomer and upto the terminal connectors/neutral link and ready for installation,of following ways complete with supply of one 100A, 16 KA, TP MCCB at theincomer (but without the supply of outgoing MCBs)
a) 8 way (4+24), Double door No. 15
3.8
Fabrication, supplying, installation, testing & commissioning of wall/floormounted cubicle board out of 2mm thick CRCA MS sheet steel, havingmountings as detailed below in suitable size compartments, lockingarrangement for each compartment including interconnection with 1100V gradePVC insulated copper conductor of size as that of sunmains, labelling, earthing,brass compression glands for incoming and outgoing cables and suitableadapter box for outgoing submains:
SDBSDB
Incomer: No. 6
200A FP MCCB, 35 KA breaking capacity having 70%-100% adjustable thermalseeting - 2 Nos.
200A FP, 35 KA breaking capacity Bus Coupler breaker - 1 No.
2 Sets digital multifunction meter for measurement of current, voltage, KWh,KVAh & p.f., current Transformer, Selector Switches indicating Lammps at theincoming for both incomings.
Bus Bar:
200A 4 Strip Aluminioum Bus Bar - 2 Sections
Outgoing in each Section :
100A TP MCCB, 25KA breaking capacity - 5 Nos.
63A TP MCCB, 25KA breaking capacity - 4 Nos.
32A DP MCB - 4 Nos.
4.0 LIGHTING FIXTURE & FANS
4.1Installation, testing and commissoning of wall bracket / ceiling fittings of all sizesof LED fittings on ceiling/wall recessed or surface including connections with 1.5sq.mm PVC insulated, copper conductor, single core cable etc., as required.
No. 725
4.2Installation of exhust fan upto 450mm sweep in the existing opening, includingmaking the hole to suit the size of the above fan, making good the damage,connections, testing, commissioning etc., as required.
No. 30
4.3Installation, testing & commissioning of ceiling fan including wiring the downrods of standard length (upto 30 cm) with 3 x 1.5 sq.mm copper wire single corecable as required.
No. 25
4.4Supplying & fixing extra conduit down rod of 20 cm length G.I. pipe, 15 mm dia,heavy gauge including painting etc. as required.
No. 50
4.5Supply of following light fittngs (LED) complete with all accessories such asholders, copper/HF ballast, wherever required, etc. complete factory wired witcopper conductor and lamp as required.
(i) RC 380B G2 LED 35S-6500 PSU OD WH - 2 x 2 square LED recessed fittingof Philips
No. 280
(ii) BN 150W LED 20S-6500 PSE OD GR - LED batten of Philips. No. 220
(iii) DN192B LED 9S-6500 PSU WH SI round LED recessed light of Philips No. 225
Equivalent fittings from Philips / Crompton / Wipro / Syska / Havells may beused subject to approval. All LED fittings shall have 5 years warranty from themanufacturer w.e.f from the date of supply.
4.6 Supply of following energy efficient 5-Star rated ceiling fan -
a) 1200 mm sweep No. 25
4.7 Supply of following heavy duty Exhaust fans with louvers
a) 300 mm sweep No. 30
4.8 Supply & installation of 450 mm sweep wall mounted bracket fan. No. 18
5.0 EARTHING AND LIGHTNING PROTECTION
5.1Earthing with G.I. earth pipe 4.5m long X 40mm dia including accessories, andproviding masonry enclosure with cover plate having locking arrangement andwatering pipe etc. ( with charcoal or coke and salt) complete, as required.
Set 10
5.2
Earthing with G.I. earth plate 600mm X 600mm X 6mm thick includingaccessories, and providing masonry enclosure with cover plate having lockingarrangement and waterting pipe etc. (with charcoal or coke and salt) complete,as required.
Set 6
5.3Supplying and laying 25mm X 5mm G.I. strip at 0.50m below ground level asstrip earth electrode, including soldering etc., as required.
Mtr. 50
5.4Providing and fixing 25mm X 5mm G.I. strip in 40mm dia G.I. pipe from the earthelectrode, as required.
Mtr. 40
5.5Providing and fixing 25mm X 5mm G.I. strip on surface or in recess for
Mtr. 1255.5Providing and fixing 25mm X 5mm G.I. strip on surface or in recess forconnections etc., as required
Mtr. 125
5.6Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loopearthing along with the existing surface/recessed conduit/submain wiring/cableas required
Mtr. 30
5.7Providing and fixing of lightning conductor final made of 25mm dia, 300mm longG.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. plateincluding holes etc., as required.
No. 8
5.8Revetting, sweating and soldering of copper/G.I. tape (with aNo.thercopper/G.I> tape, base of the finial or any other metalic object) as required.
No. 80
5.9Providing and fixing G.I. tape 20mm X 3mm thick on parapet on surface of wallfor lighting conductor as required. (for horizontal run)
Mtr. 250
5.10Providing and fixing G.I. tape 20mm X 3mm thick on parapet or surface of wallfor lighting conductor as required. (for vertical run)
Mtr. 250
5.11Providing and fixing testing joint, made of 20mm X 3mm thick G.I. strip, 125mmlong, with 4 Nos. of G.I. bolts, nuts, check nuts and spring washers etc.complete as required.
No. 15
6.0 WIRING FOR TELEPHONE
6.1Wiring for telephone points/tag blocks/call indicator units with following sizePVC insulated annealed tinned electrolytic copper conductor cable in existingrecessed conduits, ducts, shafts etc. (cost includes supply of wires)
a) 0.5 mm dia 2 pair Mtr. 3200
6.2Providing and fixing in posotion telephone junction box complete with hingeddoor having locking arrangement with following tag blocks.
a) 50 pair tag block No. 2
b) 20 pair tag block No. 6
6.3Supplying and fixing of 2 pin Telephone jack RJ-11 modualr type in compatiablebox along with cover plate etc. complete
No. 150
6.4Supplying and fixing of following size of PVC conduit along with the acessoriesin surface/recess incuding painting in case of surface conduit, or cutting the wallmaking good the same in case of recessed conduit as required.
a) 20 mm Mtr. 1200
b) 25 mm Mtr. 900
7.0 JELLY FILLED TELEPHONE CABLE
7.1Supplying of following polyethylene insulated jelly filled armoured telephonecables as per DOT specification.
a) 50 pair, 0.5mm copper armoured cable Mtr. 500
b) 20 pair 0.5 mm copper unarmoured cable Mtr. 200
7.2Excavation and trenching one meter depth and 0.3m width including refillingwith excavated earth after laying of jelly filled telephone cable dressing, sandcushing and protective bricks covering etc as required.
Mtr. 600
7.3Laying of jelly filled cable in trenches (excavated under item 7.2) as per DOTSpecification including transportation, loadning & unloading of cable fromconcernd store depot to work site of following jelly filled cable
a) 50 Pair. Mtr. 500
b) 20 Pair. Mtr. 200
8.0 COMPUTER WIRING AND LAN CABLING
8.1Supplying and laying of UTP 4 pair Cat-6 computer Networking cable n existingPVC conduit and terminaiton etc., as required (one run).
Mtr. 22500
8.2Providing, fitting & fixing of computer point RJ-45 of approved make computersocket in compatiable MS/PVC box, screw etc., as required.
No. 750
8.3 Supplying & laying of following size PVC conduit recessed in wall/celling
a) 20 mm Mtr. 10000
b) 25 mm Mtr. 8000
8.4 Installation of 6 U wall mounted rack for Patch panel No. 6
9.0 FIRE DETECTION & ALARM SYSTEM
9.1
Supply, installation, testing & commissioning of intelligent plug in photo electricsmoke detectors having features like integral communication, dual LED for 360˚viewing angle, walk test with address display etc. UL / LPCB approved, Make :HONEYWELL, MORLEY IAS, Model : MI - PSE or equiv.
No. 140
9.2
Supply, installation, testing & commissioning of intelligent plug in thermaldetectors having features like integral communication, dual LED for 360˚viewing angle, walk test with address display etc. UL / LPCB approved, Make:HONEYWELL, MORLEY IAS, Model : MI - RHSE or equiv.
No. 15
9.3Supply, installation, testing & commissioning of Addressable hooter completewith control module.UL / LPCB approved, Make - HONEYWELL, MORLEY IAS, No. 129.3 with control module.UL / LPCB approved, Make - HONEYWELL, MORLEY IAS,Model - MI - LASR + NBD / R or equiv.
No. 12
9.4
Supply, installation, testing & commissioning of Dual action pull station withaddressable interface, built in bicolour LED with key reset facility & smooth dualaction design.UL / LPCB listed. Make : HONEYWELL, MORLEY IAS, Model :MI - LASR + NBD / R or equiv.
No. 15
9.5Supply, installation, testing & commissioning of response indicator to give visualindication of detection of smoke - RED colour LED for indication. Make - AgniSuraksha, System Sensor.
No. 30
9.6
Supply, installation, testing & commissioning of 5 Loop Intelligent / AnalogueAddressable Fire Alarm Panel Microprocessor based character display Networkoption built in Alarm, Trouble & supervisory relays LPCB listed. Make :HONEYWELL, MORLEY IAS, Model - ZX 5 e or equiv.
No. 1
9.7Supply, installation, testing & commissioning of Addressable Base Model -Detectors, LPCB approved, Make - HONEYWELL, MORLEY IAS or equiv.
No. 155
9.8Wiring with 1100V grade PVC insulated copper conductor in existing PVC / MSconduit (including supply of wire)
i) 3 x 1.5 mm2 RM 1300
9.9 Supply and laying of following PVC conduit recessed in wall/ ceiling
i) 20 mm RM 800
10.0 BUS TRUNKING SYSTEM
10.1
Supplying, installing on wall, testing and commissioning of following capacity AirInsulated Compact Type Rising Mains for use on 3 phase 4 wire 415 volts,50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap offboxes and all accessories, made of 1.6mm thick steel sheet duly powder coatedin convenient sections complete with 4 Nos aluminium bus bars, having currentdensity of 130 A/ sq.cm at Nominal current rating, necessary joints & expansion
10.1density of 130 A/ sq.cm at Nominal current rating, necessary joints & expansionjoints, fire barrier at each floor, provision of tapping at every metre, continuousearthing with 2 Nos. aluminium strip of suitable size (one on each side)including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.
a) 400 Amp lsc = 30 KA for 1 second Mtr. 50
10.2
Supplying, installing, testing & commissioning of following capacity End FeedUnit for the existing Air Insulated Compact Type bus trunking / rising mains foruse on 3 phase 4 wire 415 Volts, 50Hz A.C. supply made with 1.6 mm thicksteel sheet enclosure (IP54) duly powder coated with provision of MCCB / ACB(but without MCCB / ACB) complete with necessary joints including clampingbrackets, angle iron bracket, steel fasteners, connecting to earthing system etc.as required.
a) 400 Amps lsc = 30 KA for 1 second No. 4
10.3
Supplying, installation, testing & commissioning of following capacity Plug In /tap off box on the existing Air Insulated Compact Type bus trunking / risingmains for use on 3 phase 4 wire 415 Volts, 50Hz A.C. supply made with 1.6 mmthick steel sheet enclosure (IP54) duly powder coated with provision of MCCB(but without MCCB) complete etc. as required.
a) 200 Amps lsc = 25 KA for 1 second No. 12
10.4Providing & fixing following rating and breaking capacity and pole MCCB withthermo-magnetic release and terminal spreaders in the above end-feed units /tap off boxes including drilling holes etc. making connections etc. as required.
a) 400 Amp, 35 KA, TPMCCB No. 4
b) 200 Amp, 25 KA, TPMCCB No. 12
11.0 MISCELLANEOUS ITEMS
11.1Providing, laying and jointing GI pipes of medium class including excavationand back filling all complete as pipe ducts for passing services through roads,pavements, foundations, floors, etc.)
a) 50 mm dia Mtr. 20
b) 100 mm dia Mtr. 20
c) 150 mm dia Mtr. 20
11.2
Supplying & installing of perforated, pre-painted M.S. cable trays withperforation No.t more than 17.5% in convenient sections joined with connectors,suspended from the ceiling with M.S. suspenders including bolts & nuts paintingetc., as required.
a) 100 mm width x 50 mm depth x 1.6 mm thick Mtr. 30
b) 150 mm width x 50 mm depth x 1.6 mm thick Mtr. 150
c) 225 mm width x 50 mm depth x 1.6 mm thick Mtr. 20
d) 300 mm width x 50 mm depth x 1.6 mm thick Mtr. 20
TOTAL (PART - D : Electrical Works)
1 EQUIPMENTUnit Qty
Rate (INR in
Figure) Rate in words Amount(INR)
Double Skin Air Handling Units
1.1
Supply, installation, testing and commissioning of sheet metal sectionalised
construction thermal break type double skin AHU of following capacity with Chilled
water cooling coil, 50 mm thick prefilter having efficiency 90% down to 10 micron,
Microvee Filter Section sutable to accomodate 300 mm Microvee filter, squirrel
cage induction motor,DIDW centrifugal backward curved fan, belt drive package
and vibration isolation (spring mounted), insulated drain pan,thermostate,wiring
etc. as per specification complete as required.
aDouble skin floor mounted AHU 8.0 TR, 3700 CFM, 65 mm SP, 6 RD, 12 FPI with
mixing boxNo 6
bDouble skin floor mounted AHU 4.0 TR, 1600 CFM, 65 mm SP, 6 RD, 12 FPI with
mixing boxNo 5
cDouble skin floor mounted AHU 11 TR, 5400 CFM, 65 mm SP, 6 RD, 12 FPI with
mixing box No 1
dDouble skin floor mounted AHU 12 TR, 5800 CFM, 65 mm SP, 6 RD, 12 FPI with
mixing box No 4
1.2 Double Skin Ceiling Suspended Air Handling Units
aS/I/T/C of Double skin Ceiling suspended AHU 4 TR, 1600 CFM, 35 mm SP, 6 RD,
12 FPI i/c all accessories complete as required.No 3
1.3 Fan Coil Unit
Supply , installation, testing and commissioning of Low height Inverter driven
lownoise fan coil unit complete with hidden/ exposed with 3 RD cooling coils , 3
speed fan, extended drain pan (sandwitched construction only),thermostate,wiring
and pre filters. Suitable for 230 V, 50Hz single phase power connection.Coil face
velocity shall be limited to 350 FPM.
a 2.0TR No 1
b 1.5TR No 17
1.4
Supply, installation, testing and commissioning of Double Skin Plenum Box
with Microvee filter of efficiency 95% down to 3 micron of folloiwng sets along with
necessary trap doors. The Height of the Plenum box should not be more than
1225mm complete as required.
a 4 nos 600 x 600 x 300 (depth Microvee Filter Nos 6
b 6 nos 600 x 600 x 300 (depth) microvee filter Nos 6
1.5
Supply, Installation, Testing & Commissioning of Desicent Rotor Heat recovery
wheel with DIDW Centrifugal Forward Curved Supply & Exhaust fan, Sq. Cage
Motor for Supply & Exhaust fan & HRW Wheel, The unit shall be completely factory
fabricated with purge arrangement and having minimum 65% efficiency complete
as required
a 750 CFM No 1
Name of Work : Construction of Centre for Educational Technology (CET) Building
PART - E : HVAC WORKS
b 300 CFM No 2
1.6 AUTO AIR VENT
a
Supply, installation, testing and commissioning of Auto Air vents at the highest
points in the chilled water piping as per approved makes and specifications 50 mm
Dia Auto Air Vents complete as required.
No 20
1.7
Supply, installation, testing and commissioning of 2kwX3strip heater bank on the
duct with thermostat & dehumidifier,control connection ,DOL starter etc complete
as required,
No 2
2 PIPING
2.1
Supply, Installation, testing & Commissioning of CHILLED WATER PIPING as per
IS 1239 with all necessary supports MS / Civil etc as required as per site condition
and as per specification with MS Heavy class pipe, fittings etc.
2.1.1
Providing and fixing in position the following MS HEAVY class chilled water piping,
cut to required length and installed with welded joints,including at necessary
fittings such as elbow, tees, etc. And confirming to the specifications as detailed
in the relevant chapter in the document.
a 150 mm dia RM 10
b 100 mm dia RM 24
c 80 mm dia RM 68
d 65 mm dia RM 10
e 50 mm dia RM 220
f 40 mm dia RM 440
g 32 mm dia RM 240
h 25 mm dia RM 240
2.2
Providing and fixing of Chilled water pipe insulation with 25 mm thk. Al. Foil Faced
Closed cell Nitrile rubber pipe Section with approved thermal protection layer etc
Complete as required as per specification as required.
a 150 mm dia RM 10
b 100 mm dia RM 24
c 80 mm dia RM 68
d 65 mm dia RM 10
e 50 mm dia RM 220
f 40 mm dia RM 440
g 32 mm dia RM 240
h 25 mm dia RM 240
2.3Providing and fixing of Chilled water pipeline Valve insulation as per chilled water
pipe insulation complete as required.Lot 1
TOTAL CARRIED OVER TO SUMMARY (EQUIPMENT)
2.4 Drain Water Piping (GI PIPE)
2.4.1Providing and fixing of Condensate drain water pipeline with 19 mm thick al.foil
facia closed cell nitrile rubber pipe section complete as required.
a 50 NB RMT 40
b 25 NB RMT 6
2.5 Drain Water Piping Insulation
condensate drain water insulation with 19 mm thick AL. foil faced closed cell
Nitrile rubber pipe section complete as required
a 50 NB RMT 40
b 25 NB RMT 6
2.6Excavation of trench Trench work to take the chilled water piping upto 250 mm dia
and refilling with excavated soil with compaction with fine sand. RM 20
2.7
Supply, Installation, testing & Commissioning of Underground CHILLED
WATER PIPING with insulation with 75 mm thick expanded. polystyrine of 20
kg/cm3 density .covered with chickenwire mesh,10mm cement sand plaster . 2
layes of terfelt and finally painted the bituminus paint in 2 layers. All the pipes will
be as per IS 1239 with all necessary supports MS / Civil etc as required as per site
condition and as per specification with MS Heavy class pipe, fittings etc comp-lete
as required.a 150mm dia RM 20
b 100mm dia RM 30
3Providing and fixing in position the following insulated butterfly valves i/c all
accessories complete as required..
a 100 mm dia No. 12
b 50 mm dia No 12
c 40 mm dia No 12
d 32 mm No 16
3.1Providing and fixing in position the following insulated ball valves with strainner
complete as required..
a 25 mm dia Set 17
3.2Providing and fixing in position Industrial type pressure gauges with ball valves for
isolation and necessary fittings for the USE of maintenance and operation
complete as required.
No 36
3.3Providing and fixing in position stem alcohol filled industrial thermometers
comple as required.No 36
3.4
Supply, installation, testing and commissioning of insulated Electronic, Self-
balancing Pressure independent type dynamic balancing valve with integrated 2
way modulating control valves in a single body. The actuator shall be capable of
accepting 2 - 10 VDC,4 - 20 mA electric signal and shall provide similar
trnasduced feedback output signal to control system. The minimum close-off rating
of actuator must be 1.5 times shut off head of pump as per specifications for the
following sizesa 20 mm dia No 17
b 25 mm dia No 8
c 32 mm dia No 6
d 40 mm dia No 6
3.5 Supply, Installation, testing & Commissioning of Proportional type thermostat
having 0-10V DC / 4-20mA output with Controller suitable to work with the above
valve or VFD input for AHU of approved make.
No 57
3.6Providing and fixing in position the following insulated Y-Strainers i/c all
accessories complete as required.
a 50 mm dia No 6
b 40 mm dia No 6
c 32 mm dia No 6
4 AIR DISTRIBUTION
a 0.63 mm (24 gauge) GSS Sqm 1000
b 0.8 mm (22 gauge) GSS Sqm 200
4.2
Supply, installation and testing of multiblade type louver damper of MS sheet for
Fresh air to be provided with suitable links, levers and quadrants for manual control
of volume of Fresh air flow as per approved shop floor drawings and specifications
complete as required..
Sqm 1
4.3
Supply, installation and testing of multiblade box type GSS construction
damper for ducts to be provided with suitable links and Supply, installation and
testing of multiblade box type GSS quadrants for control of volume of air.
Complete as required .
Sqm 15
4.4
Supply, installation, testing and commissioning of motorized combination fire
and smoke damper (spring return type) of approved make of atleast 90 minute fire
rating and as per the specifications as detailed earlier in the relevant sections. The
fire damper shall be complete with electronic temperature sensor and
electrically operated actuator. The fire dampers shall be located in the supply
/return air ducts at all fire rated crossovers (shaft/walls etc.) The control panel will
be such located that the reset can be easily done.These combination smoke and
fire dampers shall be interlocked withthe building management system for fire
detection / HVAC and shall trip/close in the event of fire / smoke in the respective
zone.(a+b++c)a Providing and fixing,Bare Fire Dampers with sleeve and fixing arrangement. Sqm 6
bProviding and fixing,Control panel actuator including Electrical spring type actuator
with smoke sensor and remote indication of the dire damper positionand control
wiring etc as required..
No 20
cInterconnecting wiring for the fire alarm system with the AHU and the smoke
dampersLot 20
4.5
Supply, installation, testing and commissioning of Fusible link type fire damper of
approved make of atleast 90 minute fire rating with Limit Switch and as per the
specifications as detailed earlier in the relevant sections for return air duct.(a+b+c)
a Bare Fire Dampers with sleeve and fixing arrangement Sqm 5
TOTAL CARRIED TO SUMMARY (PIPING) Rs
4.1
Supply, Fabrication, Installation and testing of sheet metal ducts in accordance
with the approved shop floor drawings and specifications and shall also
confirm to the ISI specifications
b Fusible link for fire damper No 18
c Interconnecting wiring for the Fire damper limit switch with AHU stater Lot 18
4.6
Supply, installation, testing and commissioning of square supply air diffusers as per
approved shop floor drawings and colour. Each diffuser will be equipped with
removable core and a aluminium volume control damper which will be key operated
complete as required.
aPowder coated extruded aluminium supply air diffuser with VCD of approved colour
and shade complete as required.Sqm 15
bPowder coated extruded aluminium supply air grill with VCD of approved colour and
shade complete as required.Sqm 4
4.7
Supply, installation, Testing and commissioning of Linear Grill for return air diffuser
as per approved shop floor drawings and colour. Each diffuser will be equipped with
removable core
aPowder coated extruded aluminium return air Grill of approved colour and
shadecomplete as required.Sqm 30
bPowder coated extruded aluminium return air diffuser/grill of approved colour and
shadecomplete as required.Sqm 6
5 INSULATION
5.1Supply and Application of accoustic lining within the supply air duct as per
specifications and drawings
a25 mm thick, 48 kg/m3 density FGP with 24G aluminium perforated sheet, tissue
paper as per specification etc as required.Sqm 126
5.2
Supply and Application of external thermal insulation of ducting with Self Adehisive
type Closed Cell Nitrial Rubber/FR XLPE with aluminium foil facia and of density
as specified in the specifications
a 19 mm thick for Supply air Sqm 1000
b 13 mm thick for Return air Sqm 150
5.3Supply, fixing and application of under deck insulation of roof exposed to direct
Sun with 25 mm Self Adhesiv type Close Cell Nitrial Rubber /FR XLPE with
necessary accessories complete as required..
Sqm 500
5.4 AHU Room WALL accostic Lining
a
Supply,installation,testing and commissioning of accoustion lining on all sides of
walls of each AHU room with fibreglass ,tissue paper and 24 gauge perforated
aluminium sheet.The fibre glass insulation shall be of 50 mmx32kg/m3 of board
type and shall be fixed on GI frame as per site condition and specification as
required.
Sqm 150
5.5Supply,installation,testing and commissioning of Inline Exhaust Fan complete as
required.
a 300 CFM No 5
6
TOTAL CARRIED TO SUMMARY (AIR DISTRIBUTION) Rs
TOTAL CARRIED TO SUMMARY (INSULATION) Rs
ELECTRICAL WORKS
6.1
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of following LT panels fabricated out of 14 gauge CRCA sheet
steel in cubical formation with reinforcement of suitable size angle iron and channel
T iron flats. All steel material used in the construction of panels shall undergo seven
tank process before painting as per standards with 2 coats of red oxide primer and
final approved shade of enamel paint. A solid busbar shall be provided at the
bottom of the panel with two connecting eyes for termination. The boards shall be
suitable for 415 volts, 50 Hz, 3 phase, 4 wire supply system. All the hardware used
in the fabrication of the panel shall be galvanized with zinc passivation. The panel
shall be compartmentalized to accomodate one feeder in eachcompartment.
A vertical cable alley of suitable width shall be provided to serve on or two
vertical feeder sections. Also the opening between the busbar chamber and the
feeder section shall be shrouded with bakelite/hylam sheet with mm 3 mm
thickness.All panels to have Auto Manual switches to make them compatible
Facility Management System (BMS).The panel drawing shall be approved before
taking up the fabrication.6.1.1
All panels to have Auto-Manual switches to make them compatible with Facility
Management System (BMS)
6.1.11 The panel drawing shall be approved before taking up the fabrication
a2 KW AHU stater panel with 2 KW VFD & DOL Bypass stater having MCCB as
incomer, phase indicating lamp, voltmeter, volt meter selecting switch,
semiconductor fuse for VFD, control fuse, 24V 50VA transformer for Fire damper
No 12
b
1 KW AHU stater panel with 1 KW VFD & DOL Bypass stater having MCCB as
incomer, phase indicating lamp, voltmeter, volt meter selecting switch,
semiconductor fuse for VFD, control fuse, 24V 50VA transformer for Fire damper
actuator & Dynamic balancing valve, toggle switch, start / Stop push button for
stater, power & Control terminals etc as per specification and of approved make.
(VFD will be supplied with Panel)
No 8
6.2 CABLING (POWER)
6.2.1 Power Cabling and Earthing
Electrical contractor but the terminations shall be done by the HVAC contractor
PVC insulation PVC sheathed armoured Aluminium FRLS cable of 1.1 kv grade
with termination glands and GI earthing identification tags, clamps, saddles etc.
a 3C x 6 sqmm RM 60
b 3C x 6 sqmm RM 40
6.2.2
aCopper conductor, PVC insulated PVC sheathed armoured FRLS cable of 1.1 kv
grade 2C x 1.5 sqmmRM 200
6.2.3 Cable Trays
6.2.31
P/F cable trays of ladder type made of GI slats 100 mm high and 2.6 mm thick
complete with clamps and suspension arrangement comprising of MS rods
(10 mm dia) etc. duly painted with Polyurethane plant.
a 100 mm wide RM 50
Control Cabling
TOTAL CARRIED OUT TO SUMMARY (ELECTRICAL)
SUMMARY
EQUIPMENT
ELECTRICAL WORKS
TOTAL PART AC WORKS ,PART :E
PIPING
AIRDISTRIBUTION
INSULATION
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1.0 PASSENGER LIFT :
1.1
Design, manufacture, supply, installation, testing & commissioning offollowing Passenger Lifts of 10 persons (680kg) capacity Gearless andmachine roomless, having minimum speed 1.0 m/sec., stainless steel body,automatic power operated center opening stainless steel power door withvision panel, Granite flooring finish, variable voltage and variable frequencydrive with microprocessor based Simplex full collective control, fitted withdirection & position indicator, emergency light & alarm bell, battery operatedemergency rescue device and infra-red door safety system as perspecification.
No. 1
Make : Shindler / Otis / Kone / Mistubishi / Jhonson (Subject to approval of
the dept. & subject to availability of service center at Guwahati).
a) 6 Stop, 6 Level, 6 Opening - (Ground to 5th floor).
TOTAL (PART - F : Passenger Lift)
PART - F : Passenger Lift
Name of Work : Construction of Centre for Educational Technology (CET) Building
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1 CEMENT CONCRETE WORK
(a) Providing,vibrating, laying in position cement concrete of specified gradeincluding curing but excluding the cost of centring and shuttering in all worksupto floor-V level.
1:4:8 (1 cement : 4 coarse sand: 8 graded stone agg. 40 mm nominal size
Cum 41.00
(b) Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3coarse sand : 6 graded stone aggregate 20mm nominal size) over 75mmbed by dry brick ballast 40mm nominal size well rammed and consolidatedand grouted with fine sand including finshing the top smooth.
Sq.M. 206.25
2 STEEL REINFORCEMENT
Providing reinforcement for RCC work including straightening, cutting,bending, binding with specified wire & placing in position complete as perspecifications and drawings - Fe 500 D grade super ductile steel ofapproved manufacturer of all diameters as per relevent IS codes.
kilogram
233,870.01
3 CENTERING AND SHUTTERING
Providing, fitting and fixing of centring and shuttering including strutting,
PART - A : Building Works
Name of Work : Construction of Central Instruments Facility (CIF) Building
Providing, fitting and fixing of centring and shuttering including strutting,propping etc., & removal of forms at all heights and levels for concrete workto give desired surface finish on the concrete.
a Walls of any thickness including attached pilasters, buttress, plinth and string course etc. Sq.M. 3,065.20
b Suspended floors, roofs, inclined roofs and balconies / projections andchajjas, shelves. Sq.M. 4,100.50
c Lintels, beams, girders, bressummers & cantilevers including sloping beams.
Sq.M. 4,161.00
d Column, pillars, posts & struts.
Sq.M. 2,068.00
e Staircase plain/folded plate including landings.
Sq.M. 132.00
f Small lintels not exceeding 1.5 m clear span, moulding as in cornices,window sills, string courses, bands, copings, bed plates, anchor blocks andthe like
Sq.M. 82.00
4 REINFORCED CEMENT CONCRETE
Providing and laying in position machine batched and machine mixed designmix M-25 grade cement concrete for reinforced cement concrete work, usingcement content as per approved design mix, including pumping ofconcrete to site of laying but excluding the cost of centering, shuttering,finishing and reinforcement, including admixtures in recommendedproportions as per IS: 9103 to accelerate, retard setting of concrete, improveworkability without impairing strength and durability as per direction ofEngineer-in-charge. All works at all heights and level.
a In lintels, beams, bressummers, suspended floors, roofs including inclinedroof, landings, balconies, chajjas, staircases etc. upto floor five level. Cum 1300.00
b In walls (of any thickness) including attached pillarsters, buttresses, plinthb In walls (of any thickness) including attached pillarsters, buttresses, plinthand string courses, fillets, column, pillars, piers, abutments posts and strutsetc. up to floor five level.
Cum 73.00
c Reinforced cement concrete work in vertical and horizontal fins individuallyor forming box louvers, facias and eaves boards up to floor five level,excluding the cost of centering, shuttering, finishing and reinforcement, with1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mmnominal size).
Cum 25.00
d Providing, hoisting and fixing upto floor five level pre-cast reinforced cementconcrete in shelves including setting in cement mortar 1:3 ( 1 cement : 3coarse sand) cost of required centring, shuttering and finishing with neatcement punning on exposed surfaces but excluding the cost ofreinforcement with 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stoneaggregate 12.5mm nominal size)
Cum 9.00
5 MASONRY WORKS
a Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in superstructure : Cum 100.00
Cement mortar 1:4 (1 cement : 4 coarse sand)
b Providing and laying autoclaved aerated concrete (AAC) blocks masonrywith 100/150/200 mm thick AAC blocks in super structure above plinth levelup to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rateincludes providing placing in position 2 nos of 6mm dia MS bar at every thirdcoarse of masonry works.
Cum 1200.00
c Making circular opening for exhaust fan up to 600 mm dia in brick/AAC workby providing precast RCC ring of required diameter complete as directed byEngineer-in-Charge
Each 6
6 FLOORING
(a) 100 mm thick cement concrete in floors in proportion 1:2:4 (1 cement : 2coarse sand : 4 graded stone aggregate 20 mm nominal size) over flat bricksoling with brick of designation 75 (to be measured and paid separately)including curing etc. complete as directed.
CUM 9.00
(b) 40mm thick cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with floating coat ofneat cement slurry in proper line and level.
Sq.M. 300.00
(c) Extra over item no.6(b) for finishing with NITOFLOR HARDTOP/equivalentof approved shade as per manufacturers specifications in place of floatingcoat of neat cement cement slurry complete as per drawing and as directed Sq.M. 300.00coat of neat cement cement slurry complete as per drawing and as directedby the Engineer-in -charge
Sq.M. 300.00
(d) Providing and laying flamed finish Granite stone flooring in required designand patterns, in linear as well as curvilinear portions of the building allcomplete as per the architectural drawings with 18 mm thick stone slab over20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarsesand) laid and jointed with cement slurry and pointing with white cementslurry admixed with pigment of matching shade including rubbing, curing andpolishing etc. all complete as specified and as directed by the Engineerin-Charge :
Sq.M. 143.00
Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eyeor equivalent.
(e) Providing and fixing markana Chak doongri marble stone of averagethickness 18mm to 20mm over 20 mm thick base mortar of proportion 1:4 (1cement : 4 coarse sand) laid and jointed with tiles jointing compound ofmatching shade including half round moulding of the nose, rubbing andpolishing complete in all respects including cutting the stone to makenoutch/offset on all corners vertical and horizontal and moulding as pernoutch detail in drawing and directed in window sills.
Sq.M. 122.00
(f) Extra over item no. 6(e) for mirror polishing of marble stone surfaces.
Sq.M. 122.00
(g) Providing edge moulding to 18 mm thick marble stone counters, Vanitiesetc., including machine polishing to edge to give high gloss finishetc.complete as per design approved by Engineer-in-Charge.
Metre 258.00
Granite work
(h) Extra for providing opening of required size & shape for wash basins, kitchensink in kitchen platform, vanity counters and similar locations in mable/granite/ stone work including necessary holes for pillar tapes etc. includingrubbing and polishing of cut edges etc. complete.
Each 4
(i) Providing and fixing stone slab with table rubbed, edges rounded andpolished, of size 75 x 90 cm deep and 1.8 cm thick, fixed in urinal partitionsby cutting a chase of appropriate width with chase cutter and embedding thestone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per
Sq.M. 55.00: 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as perdirection of Engineer-in-charge and finished smooth.
Granite Stone of approved shade mirror polished on both sides.
(j) 25 mm thick Kota stone slab flooring in steps over 20 mm (average) thickbase laid over and jointed with grey cement slurry mixed with pigment tomatch the shade of the slab, including rubbing and polishing complete withbase of cement mortar 1 : 4 (1 cement : 4 coarse sand) including mouldingof the nose complete as per Engineer-in-Charge :
Sq.M. 197.00
(k) Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laidon 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) andjointed with grey cement slurry mixed with pigment to match the shade of theslabs, including rubbing and polishing complete.
Sq.M. 125.00
(l) Providing and laying in floor Group -V matt finished ceramic tile of minimumthickness 7.8mm without warpage of approved design and manufacturerlaid on 20mm thick cement mortar 1:3(1cement:3 sand) including filling thejoints with pigmented tile joint filler Nitotile-GR or equivalent of matchingshade and approved manufacturer as per manufacturers specification etc.and cleaning the surface with detergent and water complete.Size 400 mm x 400mm.
Sq.M. 117.00
(m) Providing and laying in floor heavy duty vitrified antiskid matt finish tiles incorridors as per IS:4457 of minimum thickness 10mm without warpage ofapproved design and manufacturer laid on 20mm thick cement mortar1:3(1cement:4 sand) including filling the joints with pigmented tile joint fillerNitotile-GR or equivalent of matching shade and approved manufacturer asper manufacturers specification etc. and cleaning the surface with detergentand water complete. Size : 600 mm x 600 mm.
Sq.M. 1017.00
(o) Providing and laying vitrified tiles in floors and skirting in different sizes withwater absorption's less than 0.08% and conforming to IS: 15622 of approvedmake in all colours and shades,laid on 20mm thick cement mortar 1:3 (1cement : 3 coarse sand) including grouting the joints with approved tilejointing compound of matching colour etc.complete. Size 600 mm x 600 mm
Sq.M. 1945.00
(n) Providing and laying V.C shield Tiles of SOMANY / DURATUFF of ASEANTiles of 1st quality conforming to IS: 15622 of approved make in colours,shades, laid on 20mm thick cement mortar 1:3(1 cement : 3 coarse sand)including pointing the joints with tile jointing compounds of approvedmanufacturwer and matching shades etc. all complete (size 600mm X 600mm or more)
Sq.M. 450.00
mm or more)
7 DADO, SKIRTING, STEPS & RISERS
(a) Providing and laying Vitrified tiles in different sizes (thickness to be specifiedby manufacturer), with water absorption less than 0.08 % and conforming toI.S. 15622, of approved make, in all colours & shade, in skirting, riser ofsteps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarsesand), including grouting the joint with white cement & matching pigmentsetc. complete.
Sq.M. 135.00
(b) Providing and laying in steps, landings and risers heavy duty, vitrified,antiskid and matt finish tiles as per IS:4457 of minimum thickness 10mmwithout warpage of approved design and manufacturer laid on 20mm thickcement mortar 1:3(1cement:3 sand) including filling the joints withpigmented tile joint filler Nitotile-GR or equivalent of matching shade andapproved manufacturer as per manufacturers specification etc. andcleaning the surface with detergent and water complete Size: 600 mm x600mm
Sq.M. 131.00
(c) Providing and fixing ceramic tiles of approved design & shade and ofminimum thickness 5.6mm thick in dado/skirting in any pattern and size over12mm thick cement mortar 1:3(1cement : 3 coarse sand ) and filling thejoints with Nitotile-GR or equivalent of matching shade as per manufacturersspecification etc and cleaning the surface with detergent and watercomplete. Size-300mm x 600 mm
Sq.M. 304.00
8 DOORS AND WINDOWS
(a) Providing and fixing pressed steel door frames confirming to IS:4351manufactured from commercial mild sreel sheet of 1.6mm thicknessincluding hinges ,jamb,lock jamb,bead and if required angle threshold of mildsteel angle of section 50x25mm or base ties of 1.6mm pressed mild steelwelded or rigidly fixed together by mechanical means,adjustable lugs withsplit end tail to each jamb including steel but hinges 2.5mm thick with mortarguards,lock strike plate and shock absorber as specified and applying a coatof approved steel primer after ptre treatment of the surface as directed byEngineer-in Charge a) Profile-B
R.M. 380.00
(b) Providing and fixing ISI marked flush door shutters conforming to IS: 2202(Part) decorative, core of block construction with frame of 1st class hardwood and well matched teak 3 ply veneering with vertical grains or crossbands and face vanees on both faces of shutters. 30mm thick including ISImarked Stainless Steel built hinges with necessary screws.
Sq.M. 83.00
(c) Providing and fixing ISI marked flush door shutters conforming to IS : 2202(Part I) non-decorative type, core of block board construction with frame of1st class hard wood and well matched commercial 3 ply veneering withvertical grains or cross bands and face veneers on both faces of shutters:
30 mm thick including ISI marked Stainless Steel butt hinges with necessaryscrews Sq.M. 59.00
(d) Providing and fixing glazing in doors, windows and ventilators shutterscompete as per architectural drawings and the directions of Engineer-in–charge.
With clear glass panes of 5.0 mm thickness (weight not less than 13.75kg/sqm) Sq.M. 350.00
(e) With float glass panes of 8 mm thickness
Sq.M. 392.00
(f) With frosted glass panes of 5.0 mm thickness (weight not less than13.75kg/sqm) Sq.M. 14.00
9 ALUMINIUM WINDOWS
(a) Providing and fixing 50 micron powder coated aluminium work for doors,windows(catchment/sliding), ventilators, partitions or any other places withextruded built up standard tubular and other sections of approved makeconfirming to IS:733 and IS: 1285, fixed with rawl plugs and screws or withfixing clips, or with expansion hold fasteners including necessary filling up ofgaps at junction, at top, bottom and sides with required PVC/ neoprene felt,silicon sealants etc. to make perfactly watertight. Aluminium sections shallbe smooth , rust free, straight, and jointed mechanically wherever requiredbe smooth , rust free, straight, and jointed mechanically wherever requiredincluding cleat angle, aluminium snap beading for glazing/ panelling, C.P./stainless steel screws, hinges all complete as per architectural drawings andthe directions of Engineer-in-Charge. (Glazing and panelling shall be paidseparately)
oAluminium sections shall be smooth, rust free, straight, mitred and jointedmechanically wherever required including cleat angle, Aluminium snapbeading for glazing / paneling, C.P. brass / stainless steel screws, allcomplete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
For fixed portions like outer frames etc
kg 3481.00
(b) For shutters of doors, windows & ventilators including providing and fixinghinges/ pivots and making provision for fixing of fittings wherever requiredincluding the cost of EPDM rubber / neoprene gasket required (Fittings shallbe paid for separately)
kg 3089.00
Polyester powder coated aluminium (minimum thickness of polyester powdercoating 50 micron)
(c) Providing and fixing of double action heavy duty Hydraulic door spring ofapproved make (hardwyn or equivalent) Each 52
(d) Providing and fixing 12mm prelaminated three layer medium density(exteriorgrade) particle board Grade-I, type-II conforming to IS:12823 bonded withphenol formaldehyde synthetic resin of approved brand and manufacturer inpanelling fixed in aluminium door shutter with C.P./ Brass/ stainless steelscrews etc. complete as per Architectural drawings and the direction ofEngineer-in-charge
Sq.M. 890.00
10 PARTITIONS AND FALSE CEILING WORKS
(a) Providing and fixing 6mm thick hollow PVC strips and other accessories ofapproved colour in the frame work made of special sections power pressedfrom M.S. sheet and galvanized in accordance with zinc coating 600 as perIS: 277 and consisting of angle cleats of size 25mm wide x 1.6 mm thick withflanges of 22 mm and 37 mm at 1200 mm centre to centre one flange fixedto the ceiling with dash fastener 12.5 mm dia x 40 mm long with dashfastener 12.5 mm dia x 40 mm long with 6mm dia bolts to the angle hangersof 25 x 25 x 5 mm of required length , and other end of angle hanger being Sq.M. 3050.00of 25 x 25 x 5 mm of required length , and other end of angle hanger beingfixed with nut and bolts to G.I channels 45 x 15 x 0.9 mm running at the rateof 1200 mm centre to centre to which the ceiling section 0.5 mm thick bottomwedge of 80 mm with tapered flanges of 26 mm each having clips of 10.5mm at 450 , maintaining the descried profile ( horizontal / vertical / slanting /arch ) as per drawing all complete as per drawing and specification anddirection of the engineer – in charge
Sq.M. 3050.00
(b) 98mm thick metal stud partition which includes one layer of tapered edge13mm thick DURALINE gypboard of India gypsum or equivalent (confirmingto IS:2095-1982) screw fixed with drywall screws of 25mm at 300mm centresto either sides of 70mm studs (0.55mm thick having one flange of 34mm &another flange of 36mm made GI steel) placed at 610mm centre to centre in72mm floor and ceiling channel (0.55mm thick having equal flanges of 32mm made GI steel) with joints staggered to avoid leakage through joints. Finallythe square and tapered edges of the boards are to be joined and finished soas to have a flush look which includes filling and finishing with jointingcompound. Joint paper tape and two coats of drywall top coat suitable forgypboard including angle bead to be at external angles to get straight linefinish & protection from normal impacts and edge bead to be used to protectthe exposed gypsum core of gypboard specially at cut edges of the openingfor doors/ windows/ glazig or any other unprotected core complete as per thedrawing & direction of engineer-in-charge (as per recommended practices ofIndia gypsum)
Sq.M. 575.00
11 STEEL WORK
Providing and fixing M.S. grills of required pattern in frames of windows etc.with M.S. flats, square or round bars etc. including priming coat withapproved steel primer all complete.
a) Fixed to openings /wooden frames with rawl plugs screws etc.
Kg 4935.00
b) Steel work in built up tubular trusses including cutting , welding hoistingfixing in position and applying a coat of yellow zinc chromate primer welded
Kg 1874.00fixing in position and applying a coat of yellow zinc chromate primer weldedand bolted including special shaped washers complete a) Hot finishedwelded type tubes
Kg 1874.00
c) Providing and fixing bolts including nuts and washers complete.
Kg 302.00
d) Providing and fixing stainless steel ( Grade 304) railing made of Hollowtubes, channels, plates etc., including welding, grinding, buffing, polishingand making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete, i/c fixing the railing withnecessary accessories & stainless steel dash fasteners , stainless steelbolts etc., of required size, on the top of the floor or the side of waist slabwith suitable arrangement as per approval of Engineer-in-charge, ( forpayment purpose only weight of stainless steel members shall be consideredexcluding fixing accessories such as nuts, bolts, fasteners etc.).
Kg 4270.00
e) Providing, fabrication and fixing of structural glazing made out of colouredanodised aluminium mother frame (INDAL 9303) and subframe (INDAL9406)and 5mm reflective glass of approved shade. The glass to be pasted usingstructural silicon (DC995) and weatherseal silicon to be used (DC789), thestructure complete with all accessories as and where necessary.
Sq.M. 75.00
12 TERRACING
(a) Providing and fixing on wall face unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A,including jointing with seal ring conformingto IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketedpipes.
Metre 578.00
110 mm diameter
(b) Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS :13592 Type A, including jointing with seal ring conforming to IS : 5382,leaving 10 mm gap for thermal expansion.
Coupler Coupler
110 mm
Each 289
( c ) Bend 87.5°
110 mm bend Each 34
(d) Shoe (Plain)
110 mm Shoe Each 34
( e) Providing and fixing unplasticised -PVC pipe clips of approved design tounplasticised - PVC rain water pipes by means of 50x50x50 mm hard woodplugs, screwed with M.S. screws of required length, including cutting brickwork and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and makinggood the wall etc. complete.
Each 289
110 mm
( f) Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarsesand : 4 stone aggregate 10 mm and down gauge), including finishing withcement mortar 1:3 (1 cement : 3 fine sand) as per standard design : Metre 291.00
In 75x75 mm deep chase
( g) Making khurras 45x45 cm with average minimum thickness of 5 cm cementconcrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neatcement, rounding the edges and making and finishing the outlet complete.
Each 34
(h) Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15cm diameter and weighing not less than 440 grams. Each 34
(i) Providing & Fixing of 12mm thick UV protected polycarbonate panels withopaque & Transluscent combination for aesthetic appeal with verticalstanding seam on both sides, snap on locking system. The system will befitted on MS rafters/Purlin (will be paid separately) with spacing as specified
Sq.M. 126.00fitted on MS rafters/Purlin (will be paid separately) with spacing as specifiedby manufacturer.
13 WATER PROFFING
(a) Providing water proofing treatment with best quality acrylic polymer modifiedcementitious composite slurry quoating and fibre glass cloth of approvedbrand over sunken floors roof and terraces as per manufacturer'sspecification and as approved by Engineer-in-Charge.
Sq.M. 163.00
(b) Providing and laying water proofing treatment on roofs of slabs by applyingcement slurry mixed with water proofing cement compound consisting ofapplying: a) after surface preparation, first layer of slurry of cement @ 0.488kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. b)laying second layer of Fibre glass cloth when the first layer is still green.Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layerof 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixedwith water proofing cement compound @ 0.670 kg/sqm and coarse sand @1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by watercuring for 48 hours. The entire treatment will be taken upto 30 cm on parapetwall and tucked into groove in parapet all around. d) fourth and final layer ofbrick tiling with cement mortar (which will be paid for separately. For thepurpose of measurement the entire treated surface will be measured.
Sq.M. 2230.00
Grading roof for water proofing treatment with
(c) Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size) Cum 323.10
(d) Providing 12mm thick plaster to protect waterproofing treatment in cementmortar 1:4 ( 1cement : 4 coarse sand) . Sq.M. 105.00
14 FINISHING
( a ) 12 mm thick cement plaster on even surface of wall with cement mortar 1:4(1 cement : 4 sand)
Sq.M. 17317.00
(b) 15 mm thick cement plaster on the rough side of single or half brick wall withcement mortar of 1:4 (1 cement : 4 sand)
Sq.M. 4885.00
( c ) 6 mm plaster to ceiling in cement mortar 1:3 (1 cement : 3 sand) Sq.M. 4212.00
( d ) Neat cement punning. Sq.M. 25.00
( e) Providing and applying wall care putty of Birla White/JK white or equivalentat all heights and levels on the entire surface including removal ofundulations and sand papering the wall after the surface is dry to get asmooth and even surface
Sqm 22202.00
( f) Providing and applying cement primer of approved manufacturers overprepared surface: Sq.M. 22202.00
( g ) Finishing walls with textured exterior paint of required shade
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and includingpriming coat of exterior primer applied @ 2.20kg/ 10 sqm Sq.M. 245.00
(h) Finishing walls with fungus and algae resistant superior grade water proofacrylic paint of approved shade and brand to give an even shade to allexternal wall surfaces(two or more coats) including surface preparation togive an even surface as per manufacturer's specification
Sq.M. 4906.00
Applying priming coat :
( i ) With ready mixed pink or Grey primer of approved brand and manufactureon wood work (hard and soft wood) Sq.M. 295.00
( j) With ready mixed yellow zinc chromate primer of approved brand andmanufacture on steel galvanised iron/ steel works Sq.M. 472.00
( k) Painting with synthetic enamel paint of approved brand and manufacture to( k) Painting with synthetic enamel paint of approved brand and manufacture togive an even shade : Sq.M. 767.00
Two or more coats on new work
( l ) Providing and applying on walls two or more coats of Acrylic emulsion ofapproved shades and manufacturer. Sq.M. 17317.00
(m) Providing and applying on walls and ceiling two or more coats of Acrylicwashable distemper of approved shades and manufacturer. Sq.M. 4212.00
15 BUILDING HARDWARE
(a) Providing and fixing aluminium sliding door bolts, ISI marked anodisedanodic coating not less than grade AC 10 as per IS : 1868), transparent ordyed to required colour or shade, with nuts and screws etc. complete : -300x16mm.
Each 140
(b Providing and fixing aluminium tower bolts, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868 ) transparent or dyed torequired colour or shade, with necessary screws etc. complete 300x10mmsize.
Each 188
(c) Providing and fixing aluminium handles ISI marked coloured anodised(anodic coating not less than grade AC 10 as per IS:1868) of approvedcolour or shade wiith necessary screws etc. complete: 125mm.
Each 188
(d) Providing and fixing aluminium hanging floor door stopper ISI markedanodised (anodic coating not less than grade AC 10 as per IS: 1868transparent or dyed to require colour and shade with necessary screws etc.complete.
i) Single rubber stopper
Each 56
ii) Twin rubber stopper
Each 52
(e) Providing and fixing aluminium round shape handle of outer dia 100 mm withSS screws etc. complete as per direction of Engineerin-chargeSS screws etc. complete as per direction of Engineerin-charge
Polyester powder coated minimum thickness 50 micronaluminium Each 108
16 DISMANTALING WORK
( a ) Demolishing cement concrete manually/ by mechanical means includingdisposal of material within the IITG campus as per direction of Engineer - in -charge.
Cum 15.00
(b) Demolishing R.C.C. work manually/ by mechanical means including stackingof steel bars and disposal of unserviceable material within the IITG Campusas per direction of Engineer - in- charge.
Cum 35.00
( c ) Demolishing brick work manually/ by mechanical means including stackingof serviceable material and disposal of unserviceable material within theIITG Campus as per direction of Engineer-in-charge.
Cum 63.50
( d) Dismantling roofing including ridges, hips, valleys and gutters etc.,andstacking the material within the IITG Campus of G.S. Sheet. : Sq.M. 239.00
17 MISCELLANEOUS ITEMS
PARTITIONS AND ASSOCIATED WORKS
Toilet Cubical
( a ) Providing & fixing Greenlam Sturdo Classique Versatile Toilet Cubicle (offollowing standard dimension which includes 600mm door size width) madeof heat,bacteria, water, chemical, scratch, impact and anti bacterial resistant12mm thick solid compact laminate panels tested by Shriram Test House.Finish of the compact laminate should be Suede, which includs doors,pilasters & intermediate panels finished with approved texture/shade as perthe detail drawings & as per IS 2046 (Indian Standard) and as per fireretardant BS-476/97 standard. The product should have Green GuardCertificate.This also includes providing and fixing in position necessary hardware madeout of Stainless steel (Grade 304) &
No. 8
Aluminium powder coated top rail as per manufacturer’s specifications &Architects instructions like (1) SS Door Knob, (2) SS Gravity hinges, (3) SSThumb turn lockset indicators, (4) Aluminum Powder Coated Top Rail, (5)SS Coat Hooks, (6) SS U-Channels, (7) SS Adjustable Foot, (8) NoiseSS Coat Hooks, (6) SS U-Channels, (7) SS Adjustable Foot, (8) NoiseDeafening Tape etc. (9) Screws & wall Plugs.The top fitting should consist ofAluminium Powder Coated top rail which will get fixed with Mid & Endpilasters. All other hardware & screws will of stainless steel in 304 Grade with satinfinish. Top rail is extruded Aluminium will be powder coated or anodized(Grade 6063 Micron Aluminium). All pilasters are supported by stainlesssteel adjustable footing with non corrosive steel inserts.
Toilet Cubicle with standard dimension of 1955mm Height x 1000mm Widthx 1550mm Depth, which includes 600mm door size width).
Toilet Cubicle I-Shape (Front Partition) with standard dimension of 1955mmHeight x 1000mm Width which includes 600mm door size width).
All aspects specified by the manufactures, Greenlam Sturdo ClassiqueVersatile Model or equivalent.
(b) Under Deck (Roof) Insulation:SINGLE LAYER SYSTEM UNDER DECKTHERMAL INSULATION SYSTEM WITH INSU.BOARD Sq.M. 1700.00
Cleaning of the surface by brush
(c) Day Time use Building: Providing & Laying of Insuboard, thickness 50mm ofdensity 32 kgs/ cum over the RCC CEILING ( Plastered Surface) frominside. The insuboard will be fixed over the wall surface by the PVC Fastner(side lap) (Make: M/S Supreme or equivalent)
Sq.M. 1700.00
. TOTAL (PART - A : Building Works)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1 Providing and fixing white vitreous china pedestal / wall hung type watercloset (European type W.C. pan) with seat and lid, 10 litre low level whiteP.V.C.flushing cistern, including flush pipe, with manually controlled device(handle lever), conforming to IS : 7231, with all fittings and fixtures complete,including cutting and making good the walls and floors wherever required :
W.C. pan with ISI marked white solid plastic seat and lid
Each 10
2 Providing and fixing P.V.C. waste pipe for sink or wash basin includingP.V.C. waste fittings complete.
Semi rigid pipe
32 mm dia Each 10
3 Providing and fixing white vitreous china flat back half stall urinal of size580x380x350 mm with electrically operated concealed electronics flushingsystem and standard size C.P. brass flush pipe, spreaders with unions andclamps (all in C.P. brass) witrh waste fitting as per IS : 2556, C.I. trap withoutlet grating and other couplings in C.P. brass including painting of fittings
Each 10
PART - B : Sanitary and Water Supply Installation
Name of Work : Construction of Central Instruments Facility (CIF) Building
outlet grating and other couplings in C.P. brass including painting of fittingsand cutting and making good the walls and floors wherever required.
4 Providing and fixing 600x450 mm beveled edge mirror of superior glass(ofapproved quality) complete with 6 mm thick hard board ground fixed towooden cleats with C.P. brass screws and washers complete.
Each. 10
5 Providing and fixing 600x120x5 mm glass shelf with edges round off,supported on anodised aluminium angle frame with C.P. brass brackets andguard rail complete fixed with 40 mm long screws, rawl plugs etc., complete.
Each 10
6 Providing and fixing toilet paper holder :
C.P. brass Each 10
7 Providing and fixing PTMT Bottle Trap for Wash basin and sink.
Bottle trap 31mm single piece moulded with height of 270 mm,effective length of tail pipe 260 mm from the centre of the wastecoupling, 77 mm breadth with 25 mm minimum water seal,weighing not less than 260 gms
Each 10
8 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including paintingof fittings and brackets, cutting and making good the walls wherever required:
Each 5
Kitchen sink with drain board
510x1040 mm bowl depth 250 mm
9 Providing and fixing white vitreous china laboratory sink with C.I. brackets,C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P.brass trap with necessary C.P. brass unions complete, including painting offittings and brackets, cutting and making good the wall wherever required :
Each 3
Size 600x450x200 mm
10 Providing and fixing PTMT towel rail complete with brackets fixed to woodencleats with CP brass screws with concealed fittings arrangement ofapproved quality and colour.
600 mm long towel rail with total length of 645 mm, width 78mm andeffective height of 88 mm, weighing not less than 190 gms Each 10effective height of 88 mm, weighing not less than 190 gms Each 10
PP- R PIPES
11 Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipesSDR 7.4, U V stabilized & anti - microbial fusion welded, having thermalstability for hot & cold water supply, including all PP - R plain & brassthreaded polypropylene random fittings, i/c fixing the pipe with clamps at1.00 m spacing. This includes testing of joints complete as per direction ofEngineer in Charge.
Internal work - Exposed on wall
18.4.3 PN - 16 Pipe, 25 mm OD
Metre 100.00
18.4.4 PN - 16 Pipe, 32 mm OD
Metre 130.00
18.4.5 PN - 16 Pipe, 40 mm OD
Metre 75.00
12 Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipesSDR 7.4, U V stabilized & anti - microbial fusion welded, having thermalstability for hot & cold water supply, including all PP - R plain & brassthreaded polypropylene random fittings, i/c fixing the pipe with clamps at1.00 m spacing. This includes the cost of cutting chases and making goodthe same including testing of joints complete as per direction of Engineer inCharge.
Concealed work, including cutting chases and making good the walls
etc.,
18.5.1 PN - 16 Pipe, 16 mm OD
Metre 155
18.5.2 PN - 16 Pipe, 20 mm OD
Metre 145
BRASS FITTINGS
13 Providing and fixing brass bib cock of approved quality :13 Providing and fixing brass bib cock of approved quality :
15 mm nominal bore
Each 20
14 Providing and fixing brass stop cock of approved quality :
15 mm nominal bore
Each 36
15 Providing and fixing ball valve (brass) of approved quality, High or lowpressure, with plastic floats complete :
15 mm nominal bore
Each 2
16 Providing and fixing uplasticised PVC connection pipe with brass unions :
45 cm length
15 mm nominal bore
Each 25
17 Providing and placing on terrace (at all floor levels) polyethylene waterstorage tank, ISI : 12701 marked, with cover and suitable lockingarrangement and making necessary holes for inlet, outlet and overflow pipesbut without fittings and the base support for tank.
per litre
2000
18 Supplying and fitting fixing C.P. pillar cock of 15mm dia of 5011 of Jaquarbrand as specified and directed. Each 15
19 Providing fitting and fixing C.P. Grating to the floors complete as directedand specified. Each 30
a) 100mm dia
20 Providing and fixing PTMT soap Dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fitting arrangements,weighing not less than 106 gms.
Each 10
PVC PIPES,BENDS,JUNCTIONS,TEES ETC.
21 Supplying, fitting and fixing PVC pipes of 6 Kg/cm2 (Supreme/Prince) orother ISI approved including joining ,fitting and fixing with clamps etc.asnecessary complete at all levels including below G.L as directed andnecessary complete at all levels including below G.L as directed andspecified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Metre 89.00
ii) 75 mm diameter : Metre 89.00
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Metre 55.00
ii) 75 mm diameter : Metre 42.00
22 Supplying, fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) orother ISI approved including joining ,fitting and fixing etc.as necessarycomplete at all levels including below G.L as directed and specified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 15
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 8
ii) 75 mm diameter : Each 10
23 Supplying fiting and fixing 87.5 degree PVC bend with door of(Supreme/Prince) or other ISI approved including joining , fitting and fixingetc. as necessary complete at all levels including below G.L. as directed andspecified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 8
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 10
24Supplying fiting and fixing 45degree PVC bend of (Supreme/Prince) orother ISI approved including joining , fitting and fixing etc. as necessarycomplete at all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 8
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makingb) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 8
25Supplying fiting and fixing PVC Plain single tee of (Supreme/ Prince) or otherISI approved including joining, fitting and fixing etc. as necessary completeat all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 10
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 8
ii) 75 mm diameter : Each 8
26Supplying fiting and fixing PVC single tee with door of (Supreme/Prince) orother ISI approved including joining , fitting and fixing etc. as necessarycomplete at all levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 8
ii) 75 mm diameter : Each 8
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 8
ii) 75 mm diameter : Each 8
27Supplying fiting and fixing PVC single ‘Y’ of (Supreme/Prince) or other ISIapproved including joining , fitting and fixing etc. as necessary complete atall levels including below G.L. as directed and specified.
a) In exposed surfaces or in trenches.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 10
b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and makinggood to the damages.
i) 110 mm dia Each 10
ii) 75 mm diameter : Each 10
28 Providing vitreous China wash basin with CI/MS brackets, C.P brass chainwith plug,PVC waste pipe including painting of fittings and brackets, cuttingand making good the walls wherever required. (Pillar cock, stop cocks,waste coupling are to be paid separately)
(a) White(a) White
(i) Optra 570 x 440 (Cat. No.91008)
Each 10
29 Providing and fixing of Health faucet CAT NO. ALDCHR-579
Each 10
TOTAL (PART - B : Sanitary and Water Supply Installation)
Sl.
No.Item Description Unit Qty.
Rate in Figure
(Rs.)Rate in Words
Amount
(Rs.)
1.0 POINT WIRING AND SUBMAIN WIRING
1.1
Wiring for light point / fan point / exhaust fan point / call bell point with 1.5sq.mm. PVC insulated, FR, multistrand copper conductor cable in surface/recessed medium class PVC conduit complete with modular switch, modularplate, suitable G.I. box and earthing the point with 1.5 sq.mm, FR PVC insulatedcoper conductor single core cable etc., as required..
Point 520
1.2
Wiring for twin control light point with 1.5 sq.mm FR PVC insulated copperconductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with1.5 sq.mm FR PVC insulated copper conductor single core cable etc. asrequired.
Point 10
1.3Wiring for submain with the following sizes of PVC insulated, FR copperconductor, single core cable in surface/recessed PVC conduit, as required.
a) 3 X 1.5 sq.mm Mtr. 650
b) 3 X 2.5 sq.mm Mtr. 1500
PART - C : Electrical Works
Name of Work : Construction of Central Instruments Facility (CIF) Building
b) 3 X 2.5 sq.mm Mtr. 1500
c) 3 X 4 sq.mm Mtr. 22000
d) 3 X 6 sq.mm Mtr. 1500
e) 6 X 4 sq.mm Mtr. 1500
f) 6 X 2.5 sq.mm Mtr. 1100
g) 6 X 6 sq.mm Mtr. 650
h) 2 X 10 sq.mm + 1 X 6 sq.mm earth wire Mtr. 450
i) 4 X 10 sq.mm + 2 X 6 sq.mm earth wire Mtr. 1800
j) 4 X 16 sq.mm + 2 X 6 sq.mm earth wire Mtr. 1700
1.4
Supplying and fixing metal box of 150mm X 75mm X 60mm deep (normal size)in recess with suitable size pheno;ic laminated sheet cover in the front includingproviding and fixing of one 5 pin 5/6amps socket outlet and one 5/6amps pianotype switch. connections painting etc., as per required. (for light plugs).
No. 250
1.5
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (normal size)in recess with suitable size phenolic laminated sheet cover in the front includingproviding and fixing one 6 pin 15/16 Amp. socket & 15/16 Amp. piano type
No. 2801.5providing and fixing one 6 pin 15/16 Amp. socket & 15/16 Amp. piano typeswitch, connections, painting etc., as required (for power plugs)
No. 280
1.6
Supplying and fixing metal box of 200 mm x 150 mm x 60 mm deep (nominalsize) on surface or in recessed with suitable size of phenolic laminated sheetcover in the front including providing & fixing 3 nos. 5 pin 6 Amp socket outletand 1 no. 16 Amp piano type switch connection painting ect., as required. (forComputer Power Point)
No. 410
1.7 Supplying & fixing of following switchs in existing box
a) 6A piano type switch No. 270
b) 16A Piano switch No. 620
1.8 Supply & fixing of following sockets in existing box
a) 6A socket No. 920
b) 16A socket No. 600
1.9Supplying and fixing in RCC slab before concreting M.S. sheet hexagonal fanhook box of approximately 150mm dia and covering with suitable of phenoliclamitad sheet cover with brass screws, as required.
No. 2
1.10Supplying, fixing of following M.S. boxes complete with phenolic laminatedsheet cover, including painting etc. complete.
a) 180mm X 100mm X 60mm No. 450
b) 200mm X 150mm X 60mm No. 260
c) 200mm X 250mm X 60mm No. 180
1.11 Supplying & installation of electronic step regulator in existing switch box No. 29
1.12Supply & installation including connection to existing wiring etc. of followingpresence detectors / movement detector -
a) Single lens, 360°, 6 m dia detector, 10A, AC, 1 Channel surface / flushmounted for corridor / toilet - Cat.- Hager - EE804 / 805 or equivalent.
No. 45
2.0 CABLING
2.1 Supplying of following PVC/XLPE insulated cable 1.1 KV grade
a) 3.5 C 240 sq.mm Mtr. 100
b) 3.5 C 185 sq.mm Mtr. 80
c) 4 C 25 sq.mm Mtr. 100
2.2Laying of one number PVC/XPLE insulated and sheated 1.1KV gradeAluminium armouredpower cable of following size in duct pipe/trench etc.
a) above 95 sq.mm and upto 185 sq mm Mtr. 50
b) above 185 sq.mm and upto 400 sq mm Mtr. 100
c) Upto 35 sq.mm Mtr. 100
2.3Supplying and making end termination with brass compression gland andaluminioum lig the following size of PVC/XLPE insulated conductor cable of1.1KV grade, as required.
a) 3½ C 240 sq.mm Set 4
b) 3½ C 185 sq.mm Set 6
c) 4 C 25 sq.mm Set 6
3.0 DISTRUBTION BOARDS / MV PANEL
3.1Supplying and fixing of miniature circuit breaker with 'C' curve, 10 KA offollowing poles in the existing MCB DB complete with connections, testing andcommissioning etc., as required (5-32A).
a) Single pole No. 704
b) Double pole No. 16
c) Triple pole No. 40
d) Triple pole & netural No. 32
3.2Supplying and fixing single pole, blanking plate in the existing MCB DBcomplete etc. as required.
No. 30
Supplying and fixing 20amps, 240 volts, SPN industrial type, socket outlet, with
3.3
Supplying and fixing 20amps, 240 volts, SPN industrial type, socket outlet, with2 pole and earth, metal enclosed plug top along with 20amps C-series, SP,MCB in sheet steel enclosure, on surface or in recess, with chained metal coverfor the socket outlet, and complete with connections, testing and commissioningetc. as required.
No. 50
3.4
Supplying and fixing 30amps, TPN industrial type socket outlet, with 4 pole andearth, metal enclosed plug top along with 30amps "C' series TP MCB in sheetenclosure, on surface or in recess, with chained metal cover for the socketoutlet and complete with connection, testing, commissioning as required.
No. 35
3.5
Supplying and fixing of following way single pole and netural, steel, dustprotected double door type MCB distribution board 240 volts, onsurfacew/racess complete with loose wire box, terminal blocks, tinned copperbusbar, neutral link, earth bar, din bar, detachable gland plate, inter-connections, including power coated painting,earthing etc., as required.
a) 8 way, Double door No. 8
b) 12 way, Double door No. 8
3.6
Supplying, installation, testing and commissioning of surface/recess mounting,horizontal type, double door 415 volts, TPN MCB distrubtionboard of sheetsteel, 1.6 mm thick, dust protected, duly phosphatized and painted, inclusive of200amps tinned copper busbars, earth bar, common neutral link, din bar formounting MCB's detachable gland/knock out plates, hinged front acrylic coerand with built in loose wire box, and superior make terminal connectiors for allincoming and outgoing circuits, duly prewired with adequate size of PVCinsulated copper wires between the busbars and the MCB's as well as theincomer and upto the terminal connectors/neutral link and ready for installation,of followin ways (but without the supply of outgoing MCB's/Isolator)
a) 6 way (4+18), Double door No. 16a) 6 way (4+18), Double door No. 16
3.7
Supplying, installation, testing and commissioning of surface/recess mounting,vertical type, double door, 415 volts, TPN MCB distrubtion board of sheet steel,1.6 mm thick, dust protected, duly phosphatized and painted, inclusive of200amps tinned copper busbars, earth bar, common neutral link, din bar formounting MCB's detachable gland/knock out plates, hinged front acrylic coverand with built in loose wire bix, and superior make terminal connectiors for allincoming and outgoing circuits, duly prewired with adequate size of PVCinsulated copper wires between the busbars and the MCB's as well as theincomer and upto the terminal connectors/neutral link and ready for installation,of following ways complete with supply of one 100A, 16 KA, TP MCCB at theincomer (but without the supply of outgoing MCBs)
a) 8 way (4+24), Double door No. 20
3.8
Fabrication, supplying, installation, testing & commissioning of wall/floormounted cubicle board out of 2mm thick CRCA MS sheet steel, havingmountings as detailed below in suitable size compartments, lockingarrangement for each compartment including interconnection with 1100V gradePVC insulated copper conductor of size as that of sunmains, labelling, earthing,brass compression glands for incoming and outgoing cables and suitableadapter box for outgoing submains:
a) MDB-1
Incomer: No. 1
400A TP MCCB, 50KA breaking capacity having 70%-100% adjustment thermalseeting -1 No.
1 set digital multifunction meter for measurement of current, voltage, KWh,KVAh & p.f. current Transformer, Selector Switches including Lamps at theincoming.
Bus Bar:
400A 4 Strip Aluminioum Bus Bar
Outgoing:
200A TP MCCB, 35KA breaking capacity- 4 No.
100A TP MCCB, 25KA breaking capacity -10 Nos.
63A TP MCCB, 25KA breaking capacity -6 Nos.
32A DP MCB - 10 Nos.32A DP MCB - 10 Nos.
b) SDB-1
Incomer: No. 2
200A TP MCCB, 35KA breaking capacity having 70%-100% adjustable thermalseeting - 1 No.
1 Set digital multifunction meter for measurement of current, voltage, KWh,KVAh & p.f., current Transformer, Selector Switches indicating Lammps at theincoming.
Bus Bar:
200A 4 Strip Aluminioum Bus Bar
Outgoing:
100A TP MCCB, 25KA breaking capacity - 10 Nos.
63A TP MCCB, 25KA breaking capacity - 6 Nos.
32A DP MCB - 6 Nos.
4.0 LIGHTING FIXTURE & FANS
4.1Installation, testing and commissoning of wall bracket / ceiling fittings of all sizesof LED fittings on ceiling/wall recessed or surface including connections with 1.5sq.mm PVC insulated, copper conductor, single core cable etc., as required.
No. 450
4.2Installation of exhust fan upto 450mm sweep in the existing opening, includingmaking the hole to suit the size of the above fan, making good the damage,connections, testing, commissioning etc., as required.
No. 30
4.3Supply of following light fittngs (LED) complete with all accessories such asholders, copper/HF ballast, wherever required, etc. complete factory wired witcopper conductor and lamp as required.
(i) RC 380B G2 LED 35S-6500 PSU OD WH - 2 x 2 square LED recessed fittingof Philips
No. 200
(ii) BN 150W LED 20S-6500 PSE OD GR - LED batten of Philips. No. 50
(iii) DN192B LED 9S-6500 PSU WH SI round LED recessed light of Philips No. 200
Equivalent fittings from Philips / Crompton / Wipro / Syska / Havells may beused subject to approval. All LED fittings shall have 5 years warranty from themanufacturer w.e.f from the date of supply.manufacturer w.e.f from the date of supply.
4.4 Supply of following heavy duty Exhaust fans with louvers
a) 300mm sweep No. 6
5.0 EARTHING AND LIGHTNING PROTECTION
5.1Earthing with G.I. earth pipe 4.5m long X 40mm dia including accessories, andproviding masonry enclosure with cover plate having locking arrangement andwatering pipe etc. ( with charcoal or coke and salt) complete, as required.
Set 4
5.2
Earthing with G.I. earth plate 600mm X 600mm X 6mm thick includingaccessories, and providing masonry enclosure with cover plate having lockingarrangement and waterting pipe etc. (with charcoal or coke and salt) complete,as required.
Set 4
5.3Supplying and laying 25mm X 5mm G.I. strip at 0.50m below ground level asstrip earth electrode, including soldering etc., as required.
Mtr. 80
5.4Providing and fixing 25mm X 5mm G.I. strip in 40mm dia G.I. pipe from the earthelectrode, as required.
Mtr. 15
5.5Providing and fixing 25mm X 5mm G.I. strip on surface or in recess forconnections etc., as required
Mtr. 200
5.6Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loopearthing along with the existing surface/recessed conduit/submain wiring/cableas required
Mtr. 30
5.7Providing and fixing of lightning conductor final made of 25mm dia, 300mm longG.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. plateincluding holes etc., as required.
No. 8
5.8Revetting, sweating and soldering of copper/G.I. tape (with another copper/G.I>tape, base of the finial or any other metalic object) as required.
No. 80
5.9Providing and fixing G.I. tape 20mm X 3mm thick on parapet on surface of wallfor lighting conductor as required. (for horizontal run)
Mtr. 250
5.10Providing and fixing G.I. tape 20mm X 3mm thick on parapet or surface of wallfor lighting conductor as required. (for vertical run)
Mtr. 160
5.11Providing and fixing testing joint, made of 20mm X 3mm thick G.I. strip, 125mmlong, with 4 nos. of G.I. bolts, nuts, check nuts and spring washers etc.complete as required.
No. 8
6.0 WIRING FOR TELEPHONE
6.1Wiring for telephone points/tag blocks/call indicator units with following sizePVC insulated annealed tinned electrolytic copper conductor cable in existingrecessed conduits, ducts, shafts etc. (cost includes supply of wires)
a) 0.5 mm dia 2 pair Mtr. 2100
6.2Providing and fixing in posotion telephone junction box complete with hingeddoor having locking arrangement with following tag blocks.
a) 50 pair tag block No. 1
b) 20 pair tag block No. 2
6.3Supplying and fixing of 2 pin Telephone jack RJ-11 modualr type in compatiablebox along with cover plate etc. complete
No. 60
6.4Supplying and fixing of following size of PVC conduit along with the acessoriesin surface/recess incuding painting in case of surface conduit, or cutting the wallmaking good the same in case of recessed conduit as required.
a) 20 mm Mtr. 800
b) 25 mm Mtr. 600b) 25 mm Mtr. 600
7.0 JELLY FILLED TELEPHONE CABLE
7.1Supplying of following polyethylene insulated jelly filled armoured telephonecables as per DOT specification.
a) 50 pair, 0.5mm copper armoured cable Mtr. 150
b) 20 pair 0.5 mm copper unarmoured cable Mtr. 100
7.2Excavation and trenching one meter depth and 0.3m width including refillingwith excavated earth after laying of jelly filled telephone cable dressing, sandcushing and protective bricks covering etc as required.
Mtr. 250
7.3Laying of jelly filled cable in trenches (excavated under item 7.2) as per DOTSpecification including transportation, loadning & unloading of cable fromconcernd store depot to work site of following jelly filled cable
a) 50 Pair. Mtr. 150
b) 20 Pair. Mtr. 100
8.0 COMPUTER WIRING AND LAN CABLING
8.1Supplying and laying of UTP 4 pair Cat-6 computer Networking cable n existingPVC conduit and terminaiton etc., as required (one run).
Mtr. 15000
8.2Providing, fitting & fixing of computer point RJ-45 of approved make computersocket in compatiable MS/PVC box, screw etc., as required.
No. 550
8.3 Supplying & laying of following size PVC conduit recessed in wall/celling
a) 20 mm Mtr. 8000
b) 25 mm Mtr. 6000
8.4 Installation of 6 U wall mounted rack for Patch panel No. 2
9.0 FIRE DETECTION & ALARM SYSTEM
9.1
Supply, installation, testing & commissioning of intelligent plug in photo electricsmoke detectors having features like integral communication, dual LED for 360˚viewing angle, walk test with address display etc. UL / LPCB approved, Make :HONEYWELL, MORLEY IAS, Model : MI - PSE or equiv.
No. 88
9.2
Supply, installation, testing & commissioning of intelligent plug in thermaldetectors having features like integral communication, dual LED for 360˚viewing angle, walk test with address display etc. UL / LPCB approved, Make:HONEYWELL, MORLEY IAS, Model : MI - RHSE or equiv.
No. 10
9.3Supply, installation, testing & commissioning of Addressable hooter completewith control module.UL / LPCB approved, Make - HONEYWELL, MORLEY IAS,Model - MI - LASR + NBD / R or equiv.
No. 8
9.4
Supply, installation, testing & commissioning of Dual action pull station withaddressable interface, built in bicolour LED with key reset facility & smooth dualaction design.UL / LPCB listed. Make : HONEYWELL, MORLEY IAS, Model :MI - LASR + NBD / R or equiv.
No. 12
9.5Supply, installation, testing & commissioning of response indicator to give visualindication of detection of smoke - RED colour LED for indication. Make - AgniSuraksha, System Sensor.
No. 20
9.6
Supply, installation, testing & commissioning of 4 Loop Intelligent / AnalogueAddressable Fire Alarm Panel Microprocessor based character display Networkoption built in Alarm, Trouble & supervisory relays LPCB listed. Make :HONEYWELL, MORLEY IAS, Model - ZX 5 e or equiv.
No. 1
Supply, installation, testing & commissioning of Addressable Base Model -9.7
Supply, installation, testing & commissioning of Addressable Base Model -Detectors, LPCB approved, Make - HONEYWELL, MORLEY IAS or equiv.
No. 98
9.8Wiring with 1100V grade PVC insulated copper conductor in existing PVC / MSconduit (including supply of wire)
i) 3 x 1.5 mm2 RM 1100
9.9 Supply and laying of following PVC conduit recessed in wall/ ceiling
i) 20 mm RM 500
10.0 MISCELLANEOUS ITEMS
10.1Providing, laying and jointing GI pipes of medium class including excavationand back filling all complete as pipe ducts for passing services through roads,pavements, foundations, floors, etc.)
a) 50 mm dia Mtr. 20
b) 100 mm dia Mtr. 10
c) 150 mm dia Mtr. 10
10.2
Supplying & installing of perforated, pre-painted M.S. cable trays withperforation not more than 17.5% in convenient sections joined with connectors,suspended from the ceiling with M.S. suspenders including bolts & nuts paintingetc., as required.
a) 100 mm width x 50 mm depth x 1.6 mm thick Mtr. 50
b) 150 mm width x 50 mm depth x 1.6 mm thick Mtr. 200
c) 225 mm width x 50 mm depth x 1.6 mm thick Mtr. 20
d) 300 mm width x 50 mm depth x 1.6 mm thick Mtr. 200
TOTAL (PART - C : Electrical Works)
1 EQUIPMENTUnit Qty
Rate (INR in
Figure) Rate in words Amount(INR)
Double Skin Air Handling Units
a Double skin floor mounted AHU 8.0 TR, 3700 CFM, 65 mm SP, 6 RD, 12 FPI
with mixing boxNo 4
b
Double skin floor mounted AHU 4.0 TR, 1600 CFM, 65 mm SP, 6 RD, 12 FPI
with mixing box No 1
c
Double skin floor mounted AHU 11 TR, 5400 CFM, 65 mm SP, 6 RD, 12 FPI
with mixing box No 10
d
Double skin floor mounted AHU 12 TR, 5800 CFM, 65 mm SP, 6 RD, 12 FPI
with mixing box No 1
1.2 Double Skin Ceiling Suspended Air Handling Units
aS/I/T/C of Double skin Ceiling suspended AHU 4 TR, 1600 CFM, 35 mm SP, 6
RD, 12 FPI i/c all accessories complete as required. No 2
1.3 Fan Coil Unit
Supply , installation, testing and commissioning of Low height Inverter driven
lownoise fan coil unit complete with hidden/ exposed with 3 RD cooling coils ,
3 speed fan, extended drain pan (sandwitched construction
only),thermostate,wiring and pre filters. Suitable for 230 V, 50Hz single
phase power connection.Coil face velocity shall be limited to 350 FPM.
a 2.0TR No 7
b 1.5TR No 4
1.4
Supply, installation, testing and commissioning of Double Skin Plenum
Box with Microvee filter of efficiency 95% down to 3 micron of folloiwng sets
along with necessary trap doors. The Height of the Plenum box should not be
more than 1225mm complete as required.
a4 nos 600 x 600 x 300 (depth Microvee Filter
Nos 4
b6 nos 600 x 600 x 300 (depth) microvee filter Nos 10
1.5
Supply, Installation, Testing & Commissioning of Desicent Rotor Heat
recovery wheel with DIDW Centrifugal Forward Curved Supply & Exhaust fan,
Sq. Cage Motor for Supply & Exhaust fan & HRW Wheel, The unit shall be
completely factory fabricated with purge arrangement and having minimum
65% efficiency complete as required
Name of Work : Construction of Central Instruments Facility (CIF) Building
Supply, installation, testing and commissioning of sheet metal
sectionalised construction thermal break type double skin AHU of following
capacity with Chilled water cooling coil, 50 mm thick prefilter having efficiency
90% down to 10 micron, Microvee Filter Section sutable to accomodate
300 mm Microvee filter, squirrel cage induction motor,DIDW centrifugal
backward curved fan, belt drive package and vibration isolation (spring
mounted), insulated drain pan,thermostate,wiring etc. as per specification
complete as required.
PART - D : HVAC WORKS
1.1
a750 CFM
No 1
b 300 CFM No 1
1.6AUTO AIR VENT
a
Supply, installation, testing and commissioning of Auto Air vents at the highest
points in the chilled water piping as per approved makes and specifications 50
mm Dia Auto Air Vents complete as required.
No 14
1.7
Supply, installation, testing and commissioning of 2kwX3strip heater bank on
the duct with thermostat & dehumidifier,control connection ,DOL starter etc
complete as required,
No 8
2 PIPING
2.1.1Providing and fixing in position the following MS HEAVY class chilled water
piping, cut to required length and installed with welded joints,including at
necessary fittings such as elbow, tees, etc. And confirming to the
a 150 mm dia RM 10
b 100 mm dia RM 200
c 80 mm dia RM 160
d 65 mm dia RM 140
e 50 mm dia RM 210
f 40 mm dia RM 114
g 32 mm dia RM 52
h 25 mm dia RM 48
2.2Providing and fixing of Chilled water pipe insulation with 25 mm thk. Al. Foil
Faced Closed cell Nitrile rubber pipe Section with approved thermal protection
layer etc Complete as required as per specification as required.a 150 mm dia RM 10
b 100 mm dia RM 200
c 80 mm dia RM 160
d 65 mm dia RM 140
e 50 mm dia RM 210
f 40 mm dia RM 114
g 32 mm dia RM 52
h 25 mm dia RM 48
Supply, Installation, testing & Commissioning of CHILLED WATER PIPING as
per IS 1239 with all necessary supports MS / Civil etc as required as per site
condition and as per specification with MS Heavy class pipe, fittings etc.2.1
TOTAL CARRIED OVER TO SUMMARY (EQUIPMENT)
2.3Providing and fixing of Chilled water pipeline Valve insulation as per chilled
water pipe insulation complete as required.Lot 1
2.4 Drain Water Piping (GI PIPE)
2.4.1Providing and fixing of Condensate drain water pipeline with 19 mm thick
al.foil facia closed cell nitrile rubber pipe section complete as required.
a 50 NB RM 100
b 25 NB RM 40
2.5 Drain Water Piping Insulation
condensate drain water insulation with 19 mm thick AL. foil faced closed
cell Nitrile rubber pipe section complete as required
a 50 NB RM 100
b 25 NB RM 40
2.6Excavation of trench Trench work to take the chilled water piping upto 250 mm
dia and refilling with excavated soil with compaction with fine sand.RM 20
2.7
Supply, Installation, testing & Commissioning of Underground CHILLED
WATER PIPING with insulation with 75 mm thick expanded. polystyrine of 20
kg/cm3 density .covered with chickenwire mesh,10mm cement sand plaster .
2 layes of terfelt and finally painted the bituminus paint in 2 layers. All the
pipes will be as per IS 1239 with all necessary supports MS / Civil etc as
required as per site condition and as per specification with MS Heavy class
pipe, fittings etc comp-lete as required.
a 150mm dia RM 30
b 100mm dia RM 20
3Providing and fixing in position the following insulated butterfly valves i/c
all accessories complete as required..
a 100 mm dia No. 4
b 50 mm dia No 20
c 40 mm dia No 8
d 32 mm No 4
3.1Providing and fixing in position the following insulated ball valves with
strainner complete as required..
a 25 mm dia Set 12
3.2
Providing and fixing in position Industrial type pressure gauges with ball
valves for isolation and necessary fittings for the USE of maintenance
and operation complete as required.
No 28
3.3Providing and fixing in position stem alcohol filled industrial
thermometers comple as required.No 28
3.4Supply, installation, testing and commissioning of insulated Electronic,
Self-balancing Pressure independent type dynamic balancing valve with
integrated 2 way modulating control valves in a single body. The actuator shall a 20 mm dia No 12
b 25 mm dia No 2
c 32 mm dia No 4
d 40 mm dia No 10
3.5
Supply, Installation, testing & Commissioning of Proportional type thermostat
having 0-10V DC / 4-20mA output with Controller suitable to work with the
above valve or VFD input for AHU of approved make.
No 30
3.6Providing and fixing in position the following insulated Y-Strainers i/c all
accessories complete as required.
a 50 mm dia No 10
b 40 mm dia No 4
c 32 mm dia No 2
4 AIR DISTRIBUTION
a 0.63 mm (24 gauge) GSS Sqm 900
b 0.8 mm (22 gauge) GSS Sqm 200
4.2
Supply, installation and testing of multiblade type louver damper of MS sheet
for Fresh air to be provided with suitable links, levers and quadrants for
manual control of volume of Fresh air flow as per approved shop floor
drawings and specifications complete as required..
Sqm 2
4.3
Supply, installation and testing of multiblade box type GSS construction
damper for ducts to be provided with suitable links and Supply, installation
and testing of multiblade box type GSS quadrants for control of volume of
air. Complete as required .
Sqm 6
4.4
Supply, installation, testing and commissioning of motorized combination
fire and smoke damper (spring return type) of approved make of atleast 90
minute fire rating and as per the specifications as detailed earlier in the
relevant sections. The fire damper shall be complete with electronic
temperature sensor and electrically operated actuator. The fire dampers
shall be located in the supply /return air ducts at all fire rated crossovers
(shaft/walls etc.) The control panel will be such located that the reset can be
easily done.These combination smoke and fire dampers shall be interlocked
withthe building management system for fire detection / HVAC and shall
trip/close in the event of fire / smoke in the respective zone.(a+b++c)
aProviding and fixing,Bare Fire Dampers with sleeve and fixing arrangement.
Sqm 6
b
Providing and fixing,Control panel actuator including Electrical spring type
actuator with smoke sensor and remote indication of the dire damper
positionand control wiring etc as required..
No 16
cInterconnecting wiring for the fire alarm system with the AHU and the smoke
dampersLot 16
4.5
Supply, installation, testing and commissioning of Fusible link type fire damper
of approved make of atleast 90 minute fire rating with Limit Switch and as per
the specifications as detailed earlier in the relevant sections for return air
duct.(a+b+c)
TOTAL CARRIED TO SUMMARY (PIPING) Rs
Supply, Fabrication, Installation and testing of sheet metal ducts in
accordance with the approved shop floor drawings and specifications
and shall also confirm to the ISI specifications
4.1
a Bare Fire Dampers with sleeve and fixing arrangement Sqm 8
b Fusible link for fire damper No 14
c Interconnecting wiring for the Fire damper limit switch with AHU stater Lot 14
4.6
Supply, installation, testing and commissioning of square supply air diffusers
as per approved shop floor drawings and colour. Each diffuser will be
equipped with removable core and a aluminium volume control damper which
will be key operated complete as required.
aPowder coated extruded aluminium supply air diffuser with VCD of approved
colour and shade complete as required.Sqm 15
bPowder coated extruded aluminium supply air grill with VCD of approved
colour and shade complete as required.Sqm 4
4.7
Supply, installation, Testing and commissioning of Linear Grill for return air
diffuser as per approved shop floor drawings and colour. Each diffuser will be
equipped with removable core
aPowder coated extruded aluminium return air Grill of approved colour and
shadecomplete as required.Sqm 30
bPowder coated extruded aluminium return air diffuser/grill of approved colour
and shadecomplete as required. Sqm 6
5.1Supply and Application of accoustic lining within the supply air duct as per
specifications and drawings
a25 mm thick, 48 kg/m3 density FGP with 24G aluminium perforated sheet,
tissue paper as per specification etc as required.Sqm 200
5.2
Supply and Application of external thermal insulation of ducting with Self
Adehisive type Closed Cell Nitrial Rubber/FR XLPE with aluminium foil facia
and of density as specified in the specifications
a 19 mm thick for Supply air Sqm 900
b 13 mm thick for Return air Sqm 100
5.3
Supply, fixing and application of under deck insulation of roof exposed to
direct Sun with 25 mm Self Adhesiv type Close Cell Nitrial Rubber /FR XLPE
with necessary accessories complete as required..Sqm 1200
5.4 AHU Room WALL accostic Lining
a
Supply,installation,testing and commissioning of accoustion lining on all sides
of walls of each AHU room with fibreglass ,tissue paper and 24 gauge
perforated aluminium sheet.The fibre glass insulation shall be of 50
mmx32kg/m3 of board type and shall be fixed on GI frame as per site
condition and specification as required.
Sqm 250
5.5Supply,installation,testing and commissioning of Inline Exhaust Fan complete
as required.
a 300 CFM No 2
6
TOTAL CARRIED TO SUMMARY (AIR DISTRIBUTION) Rs
ELECTRICAL WORKS
INSULATION5
TOTAL CARRIED TO SUMMARY (INSULATION) Rs
6.1
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of following LT panels fabricated out of 14 gauge CRCA
sheet steel in cubical formation with reinforcement of suitable size angle iron
and channel T iron flats. All steel material used in the construction of panels
shall undergo seven tank process before painting as per standards with 2
coats of red oxide primer and final approved shade of enamel paint. A solid
busbar shall be provided at the bottom of the panel with two connecting eyes
for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase, 4
wire supply system. All the hardware used in the fabrication of the panel shall
be galvanized with zinc passivation. The panel shall be compartmentalized
to accomodate one feeder in eachcompartment. A vertical cable alley of
suitable width shall be provided to serve on or two vertical feeder
sections. Also the opening between the busbar chamber and the feeder
section shall be shrouded with bakelite/hylam sheet with mm 3 mm
thickness.All panels to have Auto Manual switches to make them compatible
Facility Management System (BMS).The panel drawing shall be approved
before taking up the fabrication.
6.1.1All panels to have Auto-Manual switches to make them compatible with
Facility Management System (BMS)
6.2 CABLING (POWER)
6.2.1 Power Cabling and Earthing
Electrical contractor but the terminations shall be done by the HVAC
contractor
PVC insulation PVC sheathed armoured Aluminium FRLS cable of 1.1 kv
grade with termination glands and GI earthing identification tags, clamps,
saddles etc.
a 3C x 6 sqmm RM 70
b 3C x 6 sqmm RM 30
6.2.2 Control Cabling
aCopper conductor, PVC insulated PVC sheathed armoured FRLS cable of 1.1
kv grade 2C x 1.5 sqmmRM 134
6.2.3 Cable Trays
The panel drawing shall be approved before taking up the fabrication
2 KW AHU stater panel with 2 KW VFD & DOL Bypass stater having MCCB
as incomer, phase indicating lamp, voltmeter, volt meter selecting switch,
semiconductor fuse for VFD, control fuse, 24V 50VA transformer for Fire
damper actuator & Dynamic balancing valve, toggle switch, start / Stop push
button for stater, power & Control terminals etc as per specification and of
approved make.The Panel Should also have 2 nos feeder for Supply &
Exhaust fan of HRW & One No. Feeder for Wheel
No 14
1 KW AHU stater panel with 1 KW VFD & DOL Bypass stater having MCCB
as incomer, phase indicating lamp, voltmeter, volt meter selecting switch,
semiconductor fuse for VFD, control fuse, 24V 50VA transformer for Fire
damper actuator & Dynamic balancing valve, toggle switch, start / Stop push
button for stater, power & Control terminals etc as per specification and of
approved make. (VFD will be supplied with Panel)
2
a
6.1.11
b No
6.2.31
P/F cable trays of ladder type made of GI slats 100 mm high and 2.6 mm
thick complete with clamps and suspension arrangement comprising of
MS rods (10 mm dia) etc. duly painted with Polyurethane plant.
a 100 mm wide RM 75
TOTAL PART AC WORKS ,PART :E
SUMMARY
TOTAL CARRIED OUT TO SUMMARY (ELECTRICAL)
EQUIPMENT
PIPING
AIRDISTRIBUTION
ELECTRICAL WORKS
INSULATION