FAST/TOOLS MELSEC Equipment (EQPMEL) configuration

TI 50A01A30-01EN

TI 50A01A30-01EN©Copyright Oct. 2016 (YK)1st Edition Oct. 2016 (YK)

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-0212 Fax.: 81-422-52-0571

Page 2: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Blank Page

Page 3: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

i

TI 50A01A30-01EN

Introduction

About this documentThis document explains FAST/TOOLS MELSEC equipment configuration for communication between FAST/TOOLS and MELSEC PLC. The target reader of this document is an engineer who wants to configure FAST/TOOLS and MELSEC PLC communication. It’s required for reader to know some basic engineering methods for both FAST/TOOLS and MELSEC PLC.

Trademark• FAST/TOOLS is registered trademark of Yokogawa Electric Corporation.

• All other company and product names mentioned in this manual are trademarks or registered trademarks of their respective companies.

• We do not use TM or ® mark to indicate those trademarks or registered trademarks in this manual.

All Rights Reserved Copyright © 2016, Yokogawa Electric Corporation Oct. 21, 2016-00

Page 4: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Blank Page

Page 5: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Toc-1

TI 50A01A30-01EN

FAST/TOOLS MELSEC Equipment (EQPMEL) configuration

Oct. 21, 2016-00

CONTENTS

TI 50A01A30-01EN 1st Edition

1 General ...................................................................................................... 1-12 Connection types with MELSEC ............................................................. 2-1

2.1 Ethernet port on Ethernet unit .........................................................................2-12.2 Ethernet port on CPU unit ................................................................................2-12.3 Multi-network environment with Ethernet unit .............................................. 2-22.4 Redundant CPU environment with Ethernet unit .......................................... 2-3

3. Configuration in FAST/TOOLS MELSEC equipment ............................ 3-13.1 FAST/TOOLS installation with EQPMEL patch (R10.02) .............................. 3-13.2 Apply FAST/TOOLS license .............................................................................3-13.3 Setup MELSEC PLC configuration .................................................................3-13.4 Configuration of MELSEC equipment ............................................................3-2

3.4.1 Lines ...................................................................................................3-2

3.4.2 Stations ..............................................................................................3-3

Appendix A. Samples of STATION definition ..........................................App.1-1Appendix B. General procedure of MELSEC setup ...............................App.2-1

Page 6: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Blank Page

Page 7: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<1. General> 1-1

TI 50A01A30-01EN Oct. 21, 2016-00

1 GeneralMELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC PLC can treat many kinds of CPU types and connection types. Refer to Mitsubishi Electric Corp. website for more detailed information.

FAST/TOOLS have provided to communicate with MELSEC PLC from R9.03 as one of EQUIPMENT/FAST options (Model: EQP-S11-MEL).

You must require to setup MELSEC PLC network configuration. For example, IP address and related configurations are required for MELSEC CPU unit or Ethernet unit. Such MELSEC PLC configuration must be required to refer to User’s manual of MELSEC PLC and/or MELSEC Engineering Tools, GX Developer, GX Works etc., even some information is written in this document.

Target environment• FAST/TOOLS: R10.02 or later (Windows OS only)

• MELSEC CPU unit

Series CPU unit nameA series A0J2H, A1S, A1SH, A1SJ, A1SJH, A1N, A2C, A2CJ, A2N(S1), A2S, A2SH, A3N,

A2A(S1), A3A, A1FX, A2U(S1), A3U, A4U, A2US(S1), A2USH-S1QnA series Q2A, Q2AS1, Q3A, Q4A, Q4AR, Q2AS(H), Q2AS(H)-S1Q series Q00J, Q00, Q01, Q02(H), Q06H, Q06PH, Q12H, Q25H, Q02(H)-A, Q06H-A,

Q12PH, Q25PH, Q12PRH, Q25PRH, Q00U, Q00UJ, Q01U, Q02U, Q03UD, Q03UDE, Q03UDV, Q04UDH, Q04UDEH, Q04UDV, Q04UDPV, Q06UDH, Q06UDEH, Q06UDV, Q06UDPV, Q10UDH, Q10UDEH, Q13UDH, Q13UDEH, Q13UDV, Q13UDPV, Q20UDH, Q20UDEH, Q26YDH, Q26UDEH, Q26UDV, Q26UDPV, Q50UDEH, Q100UDEH

FX series FX0(S), FX0N, FX1, FX1S, FX1N(C), FX2(C), FX2N(C), FX3U(C)L series L02, L02S, L02S-P, L02-P, L06, L06-P, L26, L26-BT, L26-P, L26-PBT

Page 8: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<2. Connection types with MELSEC> 2-1

TI 50A01A30-01EN Oct. 21, 2016-00

2 Connection types with MELSECThis section shows some examples of MELSEC connection types with Ethernet. Refer to MELSEC PLC User’s manual for more detailed information.

2.1 Ethernet port on Ethernet unitThis type is to connect MELSEC CPU via MELSEC Ethernet unit and one of simple system configurations.

F020101E.ai

FAST/TOOLS

(PC)

Pow

er

CP

U

Ethernet

(Qj71E

71-100)

2.2 Ethernet port on CPU unitThis type is to connect MELSEC CPU via Ethernet port on CPU unit, and one of simple system configurations.

F020201E.ai

FAST/TOOLS

(PC)

Pow

er

CP

U

Page 9: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<2. Connection types with MELSEC> 2-2

TI 50A01A30-01EN Oct. 21, 2016-00

2.3 Multi-network environment with Ethernet unit

This type is to connect MELSEC CPU via some networks. For example, Ethernet and MELSECNET/H as the image below in case that FAST/TOOLS accesses to CPU2.

F020301E.ai

FAST/TOOLS

(PC)

Pow

er

CP

U1

Ethernet

(Q

J71E71

-100)

Pow

er

CP

U2

ME

LSE

CN

ET/H

(QJ71LP

21-25)

ME

LSE

CN

ET/H

(Q

J71LP21 -25)

Page 10: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<2. Connection types with MELSEC> 2-3

TI 50A01A30-01EN

2.4 Redundant CPU environment with Ethernet unit

This type is to connect MELSEC redundant CPU configuration. MELSEC redundant concept is to have 2 sets of units including CPU and switch control right if any one of units in control set is not working properly.

F020401E.ai

FAST/TOOLS

(PC)

Pow

er

Redundant

CP

U

(QnP

RH

)

Ethernet

(Q

J71E71

-100)

Pow

er

Redundant

CP

U

(QnP

RH

)

Ethernet

(Q

j71E71

-100)

Oct. 21, 2016-00

Page 11: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-1

TI 50A01A30-01EN

3. Configuration in FAST/TOOLS MELSEC equipment

This section shows the procedure to communicate with MELSEC, especially the configurations in FAST/TOOLS.

The basic procedure is following.

1. FAST/TOOLS installation with EQPMEL patch (R10.02)

2. Apply FAST/TOOLS license

3. Setup MELSEC PLC configuration

4. Configuration of MELSEC equipment

3.1 FAST/TOOLS installation with EQPMEL patch (R10.02)

After standard FAST/TOOLS R10.02 installation, you must apply an EQPMEL patch for correct EZSocket installation on later Windows OS environment. This patch is provided for R10.02 and R10.02 SP1 environment. Please contact GSC at [email protected] for requesting the patch.In case you need to connect with MELSEC on R10.01 or earlier versions, also please contact GSC at [email protected].

3.2 Apply FAST/TOOLS licenseMELSEC communication with FAST/TOOLS is provided as one of FAST/TOOLS option licenses (EQP-S11-MEL). So you need a specific license for FAST/TOOLS MELSEC equipment configuration and runtime work. Once you apply a correct license to FAST/TOOLS, you can see “MELSEC” folder in the tree of Engineering Module. (Engineering Module -> I/O Process -> Equipment -> MELSEC)

3.3 Setup MELSEC PLC configurationBefore connecting FAST/TOOLS with MELSEC PLC, some parameters of MELSEC network needs to be configured by MELSEC configuration tool, GX Works, GX Developer etc. Refer to each User manual for required setup parameters

Oct. 21, 2016-00

Page 12: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-2

TI 50A01A30-01EN

3.4 Configuration of MELSEC equipmentIn principle, configuration method of MELSEC equipment in FAST/TOOLS is similar to the other equipment, such as to configure Scan types, Lines, Stations and Points. This section describes Lines and Stations especially, because these include some parameters of MELSEC specific configurations.

3.4.1 LinesFor “Line” definition, it’s almost same as the other equipment. Only the point you need to care is the case of “Redundant lines”.Tab [General]

F030401E.ai

(1)

(2)

(3)

No. Parameter name Description A B C D Values Remark

(1) Line name Name of line X X X X Ex. “MEL01” Put a unique name for all line names.

(2) Equipment process name

Process name of line X X X X Ex. “EQPMEL01” Put a unique name for

all process names.

(3) Redundant lines

Use if redundant lines or not

X X X X

OFF: Single destinationON: Redundant destinations

Must set ON in case you use Redundant.

[In title line]A: Connection type: Ethernet port on Ethernet unitB: Connection type: Ethernet port on CPU unitC: Connection type: Multi-network environment with Ethernet unitD: Connection type: Redundant CPU environment with Ethernet unit

[In other lines]X: Choose or put a correct value depending on your environment.-: Choose or put a common default or fixed value. (i.e. no effects for your trouble shooting)

Oct. 21, 2016-00

Page 13: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-3

TI 50A01A30-01EN

3.4.2 StationsFor “Station” definition, each parameter needs to be selected or input with correct value. These are decided by almost same as the other equipment.Tab [General]

F030402E.ai

(1)

(2)(3)

(5)

(4)

No. Parameter name Description A B C D Values Remark

(1) Station name Name of station X X X X Ex. “MEL01”

(2) Line Name of used line X X X X [Line name] Select one of [Line

name]

(3) Redundant linesUse if redundant lines or not

X X X X

OFF: Single destinationON : Redundant destinations

Must set ON in case you use Redundant.

(4) On scan Start or stop scan X X X X OFF: Scan OFF

ON : Scan ON

(5)General communication status item

Set communication status item

X X X X Item name

Oct. 21, 2016-00

Page 14: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-4

TI 50A01A30-01EN

Tab [Options]

F030403E.ai

(1)(2)(3)(4)

(5)

(6)(7)

No. Parameter name Description A B C D Values Remark

(1) Recover interval

Communication check interval X X X X 10 (seconds)

(2) Try count Number of trials X X X X 2

(3)Time synchronization interval

X X X X 0 – Days 0 means no time sync.

(4) PLC is time master

Time master selection X X X X OFF: PC is master.

ON: PLC is master. (*1)

(5) Time type Time type in MELSEC PLC X X X X

LST: Local Standard TimeLCT: Local Civil TimeGMT: Greenwich Mean Time

(6) Signal gap

Allowed gap size between reading relays or registers in one message

X X X X 50 (bytes)

(7) Number of signals

Allowed maximum size of reading relays or register in one message

X X X X 2000 (bytes)

*1: In case PC is master, it applies to PLC immediately. In case PLC is master, it applies to PC gradually as once for 1-2 seconds.

Oct. 21, 2016-00

Page 15: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-5

TI 50A01A30-01EN

Tab [Line 1/Line 2]

F030404E.ai

(1)

(2)(3)(4)

(5)(6)

(7)(8)(9)

(10)(11)(12)

(13)(14)

(15)(16)

(17)(18)

(19)(20)(21)(22)(23)

Oct. 21, 2016-00

Page 16: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-6

TI 50A01A30-01EN

No. Parameter name Description A B C D Values Remark(1) CPU timeout (ms) Timeout X X X X 1,000

(2) Checksum Whether it uses CheckSum or not - - - - OFF For serial comm.

(3) Through network type

Whether this CPU connection requires through MELSECNET/10 network or not

- - X - OFF

(4) Intelligent performance bit

Whether this CPU connection requires through multi-drop network

- - X - OFF

(5) Network number Network number on target CPU X - X X Ex. 1

(6) Station number Station number of target CPU X - X X Ex. 1

(7) Unit I/O number Unit type of target CPU X X X X (*1)

(8) CPU type CPU type X X X X (*2)(9) Unit type Connected unit type X X X X (*3)

(10) Packet type Communication packet type X X X X (*4)

(11) Protocol type Communication protocol type X X X X (*5)

(12) TCP/IP address Connected IP address of Ethernet port X X X X

(13) Port number Port number of source PC - - - - 0 Any unused ports

(14) Baud rate Communication speed for serial line - - - - 115200 For serial comm.

(15) Number of bits Length of bits for serial line - - - - 8 For serial comm.

(16) Parity Parity type for serial line - - - - EVEN For serial comm.

(17) Number of stop bits

Length of stop bits for serial line - - - - 0 For serial comm.

(18) Control Control signal - - - - 0 For serial comm.

(19) Source network Network no. of source PC X X X X Ex. 1

(20) Source station Station no. of source PC X X X X Ex. 2

(21) Destination port Target port no. of connected unit X X X X (*6)

(22) Destination I/O number - - - - 1023

(23) Multi-drop channel - - - - 1

Oct. 21, 2016-00

Page 17: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-7

TI 50A01A30-01EN

*1: Unit I/O number

Unit type of target CPU Value

(Single) CPU 1023 (0x3FF)

Control system CPU 976 (0x3D0)

Standby system CPU 977 (0x3D1)

System A CPU 978 (0x3D2)

System B CPU 979 (0x3D3)

Unit 1 under Multi-CPU configuration 992 (0x3E0)

Unit 2 under Multi-CPU configuration 993 (0x3E1)

Unit 3 under Multi-CPU configuration 994 (0x3E2)

Unit 4 under Multi-CPU configuration 995 (0x3E3)

*2: CPU type Choose a target CPU type. In case you cannot find the same CPU type, choose similar CPU type. For example, in case your target CPU type is Q25HCPU, then you should choose the type “Q25CPU”.

The below table shows some samples for CPU type parameter. (This is not a complete list.)

Target CPU type Value Target CPU type Value

A0J2H, FR-C500 A0J2HCPU Q04UDHCPU Q04UDHCPU

A1(N) A1NCPU Q03UDECPU Q03UDECPU

A2C, A2CJ A2CCPU Q06UDEHCPU Q06UDEHCPU

A3A A3ACPU Q13UDVCPU Q13UDVCPU

Q2A-S1 Q2AS1CPU Q02PHCPU Q02PHCPU

FX0, FX0S FX0CPU Q25PRHCPU Q25PRHCPU

FX3U(C) FX3UCCPU Q02(H) A mode Q02CPU_A

A171SH A171SHCPU P25, R25 P25

L02CPU, L02CPU-P L02CPU LP25, BR15 LP25

L26CPU, L26CPU-P L26CPU/L26CPU_NONBT QLP25, QBR15 QLP25

L26CPU-BT,

L26CPU-PBT L26CPUBT QJ72LP25/BR15 QJ72LP25

LJ72GF15 LJ72GF15-T2 GOT900, GOT1000 A900GOT

Q00CPU C00CPU Host board BOARD

Q01UCPU Q01UCPU General OTHER

Q03UDCPU Q03UDCPU

Oct. 21, 2016-00

Page 18: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

<3. Configuration in FAST/TOOLS MELSEC equipment> 3-8

TI 50A01A30-01EN

*3: Unit type Choose a connected unit type. For example, in case your connected unit is Ethernet unit for QnCPU (QJ71E71), you should choose the type “QJ71E71”.

The below table shows some samples for unit type parameter. (not a complete list)

Connected unit type Value

ACPU-RS422 port direct ACPU

QnACPU-RS422 port direct QCPU

QnCPU (Q mode) RS232C port direct QNCPU

QnCPU (A mode) RS232C port direct QNCPU_A

QnCPU (Q mode) USB port direct QNUSB

QnCPU (Q mode) Ethernet port QNETHER

QnCPU (Q mode) Ethernet port direct QNETHER_DIRECT

LnCPU-RS232C port direct LNCPU

LnCPU Ethernet port LNETHER

QnCPU Ethernet port via GOT1000 series GOT_QNETHER

QnCPU-RS422 port via Ethernet of GOT1000 series GOTETHER_QNCPU

NZ2GF-ETB (Ethernet adaptor) port NZ2GF_ETB

FXCPU-RS422 port direct FXCPU

Ethernet port on Ethernet unit for QnCPU QJ71E71

MNET/H board MNETHBOARD

CC-Link board CCLINKBOARD

GOT900 series A900GOT

Other connections OTHER

*4: Packet type Choose a packet type. In case of other than AJ71****, you should use “PLC1”.

Packet type Value

Special protocol type 1 (AJ71E71/AJ71QE71) BINARY1

Special protocol type 1 (AJ71(U)C24, AJ71(Q)E71) ASCII1

CPU protocol type (AJ71(Q)E71, QJ71E71) PLC1

*5: Protocol type Choose a protocol type. This is decided by unit type other than Ethernet connection.

The below table shows some samples for protocol type parameter. (not a complete list)

Packet type Value

MNETH board MNETH

Serial port SERIAL

USB port USB

TCP/IP with Ethernet port TCPIP

UDP/IP with Ethernet port UDPIP

*6: Destination port Put a target port number for Ethernet connection. This number is decided by combination of unit type and protocol type.

CPU type Unit type Protocol type Value Remark

QnACPU AJ71QE71 UDP/IP 5001

QnCPU QJ71E71 UDP/IP 5001

QnCPU QJ71E71 TCP/IP 5002

QnCPU, LnCPU Ethernet direct UDP/IP 5006 Specific configuration is required in MELSEC CPU.

QnCPU, LnCPU Ethernet direct TCP/IP 5007

FXCPU FX3U-ENET TCP/IP 5551

Oct. 21, 2016-00

Page 19: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-1

TI 50A01A30-01EN

Appendix A. Samples of STATION definition

Sample 1

- CPU: Q13UDV - Unit: QJ71E71 (Ethernet unit) - Protocol: UDP/IP

FA0A0001E.ai

Oct. 21, 2016-00

Page 20: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-2

TI 50A01A30-01EN

Sample 2

- CPU: Q13UDEH - Unit: Ethernet port on CPU direct - Protocol: TCP/IP

FA0A0002E.ai

Oct. 21, 2016-00

Page 21: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-3

TI 50A01A30-01EN Oct. 21, 2016-00

Sample 3

- CPU: Q13UDH (as CPU2 of the diagram in Section 2.3) - Unit: QJ71E71 (Ethernet unit) - Protocol: UDP/IP

FA0A0003E.ai

Page 22: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-4

TI 50A01A30-01EN Oct. 21, 2016-00

Sample 4

- CPU: Q25PRH (Redundant) - Unit: QJ71E71 (Ethernet unit) - Protocol: UDP/IP

FA0A0004E.ai

Page 23: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-5

TI 50A01A30-01EN Oct. 21, 2016-00

Sample 5

- CPU: FX3UC (FX series) - Unit: FX3U-ENET-L (Ethernet unit) - Protocol: TCP/IP

FA0A0005E.ai

Page 24: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

AppendixASamplesofSTATIONdefinition App.1-6

TI 50A01A30-01EN Oct. 21, 2016-00

Sample 6

- CPU: L26CPU-P (L series) - Unit: Ethernet port on CPU direct - Protocol: TCP/IP

FA0A0006E.ai

Page 25: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-1

TI 50A01A30-01EN

Appendix B. General procedure of MELSEC setup

Here shows one of general procedures for MELSEC PLC configuration by MELSEC tool.1. Install MELSEC Engineering Tool.

2. Setup MELSEC hardware and set power ON.

3. Connect between PC and MELSEC PLC by USB cable.

4. Read current setup parameters in PLC.

5. Write the parameters to PLC.

6. Set PLC power OFF and Power ON.

Setting up of MELSEC PLC is finished.

Step 1: Install MELSEC Engineering Tool.To setup MELSEC CPU and related parameters, you need to install MELSEC Engineering Tool(s). You can get some MELSEC related tools for this purpose, like GX Developer8, GX Works2 or GX Workd3 etc. Which tool you should use is related to what environment you need to configure. Refer MELSEC User’s manual for each tool for detail.Here uses GX Works2 in this Appendix.

Step 2: Setup MELSEC hardware and set power ON.In case you want to set up a MELSEC Qn-series CPU, you need the following unit is required: base, power, CPU. If your target CPU doesn’t have Ethernet port, Ethernet unit is needed additionally. Attach power, CPU and other I/O units on a base unit and set power ON. More detailed information should be referred to a MELSEC User’s manual.

Step 3: Connect between PC and MELSEC PLC by USB cable.When you install Engineering Tool, USB interface drivers are also installed in most of cases, because most of MELSEC CPU has USB interface to configure MELSEC PLC and I/O units.

Oct. 21, 2016-00

Page 26: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-2

TI 50A01A30-01EN

Step 4: Read current setup parameters in PLC.Start installed MELSEC Engineering Tool and read current setup parameters.

FA0B0001E.ai

To read parameters, the following popup is opened. Here you need to choose your current connection environment. In case of direct USB connection, it’s configured as default. In other cases, set your environment. How to set this popup should be referred to a MELSEC Engineering Tool User’s manual.

FA0B0002E.ai

Once you finish the network configuration, you should click the button “Connection Test”. If the configuration is OK and PLC connection is also OK, you can see CPU type information on successful notice as below.

Oct. 21, 2016-00

Page 27: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-3

TI 50A01A30-01EN Oct. 21, 2016-00

FA0B0003E.ai

Then you click the button “OK” for both on successful notice and transfer setup connection, the new popup is appeared as below.

FA0B0004E.ai

You need to click the button “Parameter + Program” to choose parameters to read and click the button “Execute” for parameter reading.

Page 28: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-4

TI 50A01A30-01EN Oct. 21, 2016-00

Step 5: Write the parameters to PLC.In case you succeed to read PLC parameters, you can see the project tree including parameters as below and edit parameters. Here shows Network parameter configuration. How to configure should be referred to a MELSEC Engineering Tool User’s manual.

FA0B0005E.ai

Here shows IP address setting as Operation setting.

FA0B0006E.ai

Page 29: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-5

TI 50A01A30-01EN Oct. 21, 2016-00

Here shows Protocol setting as Open setting.

FA0B0007E.ai

After configuration is finished, you need to download these updated parameters by “Write parameters” as below.

FA0B0008E.ai

Page 30: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

Appendix B General procedure of MELSEC setup App.2-6

TI 50A01A30-01EN Oct. 21, 2016-00

Then the following popup is opened.

FA0B0009E.ai

You can write the edited parameters by a similar operation to reading.

Step 6: Set PLC Power OFF and Power ON.After writing configuration parameters to MELSEC PLC, it must restart PLC in most of cases as Power OFF and Power ON. You need to pay attention to the time between Power OFF and Power ON. Refer to a MELSEC User’s manual in detail.In case of no configuration errors or mistakes for both MELSEC and FAST/TOOLS, you can connect and read MELSEC PLC data.

Page 31: Tecnic Inomtion MELSEC Equipment (EQPMEL) … · 1 General MELSEC PLC has been developed and maintained by Mitsubishi Electric Corp. MELSEC

i

TI 50A01A30-01EN

Revision InformationTitle: FAST/TOOLS MELSEC Equipment (EQPMEL) configurationManual number : TI 50A01A30-01EN

Oct. 2016/1st EditionNewly published

Oct. 21, 2016-00