SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: [email protected] Sysco FreshPoint Denver 5151 Bannock Street Denver, CO, 80216 Company Contact: Dave Schlernitzauer Project: 08220616

Upload: others

Post on 23-Aug-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

SYSCO FRESHPOINTDENVER

DENVER,COLORADO

June, 2016

Infrared Inspection Report©

2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: [email protected]

Sysco FreshPoint Denver5151 Bannock StreetDenver, CO, 80216Company Contact:Dave SchlernitzauerProject: 08220616

Page 2: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

DISCLAIMERThis report and the recommendations contained in it are based upon conditions and practices observed and information madeavailable to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not in-tended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteriashown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility’s condition,maintenance practices or correction of conditions indicated herein.By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, con-cerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in anymanner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) forpersonal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

ORDER OF REPORT CONTENTS

1: Data To Facilitate Understanding &Utilizing Scan Report

2: Scan Results Overview & Action TakenForm

3: Identified Faulting Conditions,Information & Photographs

4: List Of Facility Equipment IdentifiedBy The Customer Representative &Notations Of Faulting Conditions Found

Page 3: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

Utilizing Report Contents

Included in this report are Photographs and Thermographs of problem areas found during our recent

Infrared Inspection of your facility.

Each problem area picture is accompanied by:

Date

Location Information

Temperature Calculations

Color-coded Temperature Intensity and/or Condition Significance Data

A Brief Comment Relating The Item In The Photograph To Its Corresponding

Thermograph

Suggested Corrective Recommendations.

In most cases, problems (faults) found will be listed according to the date and order that they were located,

rather then by significance or priority, as we feel that you and/or your personnel can best judge this,

keeping in mind circuit importance and thermograph intensity.

Thermal intensity is indicated by use of a color-coded data inserts that locate a fault‘s position on the

standard electrical failure curve. The color of the insert represents the temperature range of the hottest

item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the

colored inserts represent are grouped as follows:

INSERT Temperature Range

Red 70ºC/126ºF and higher above Ambient Operating Temp.

Orange 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp.

Yellow 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp.

Green *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp.( * See page 4)

Page 4: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

FAULTY EQUIPMONTHS MONTHS TO WEEKS WEEKS TO NOW

Determining Cost Effective Responses

Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing thefailure curve into temp. ranges and locating a problems position on the curve allows us to indicate theprobable time to its failure. Knowing a problems probable time to failure allows you to make a cost effectiveresponse to the problem areas that we locate.

Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and thecolors that we assign to faults detailed in our reports.

Built In Trend Monitoring

When yearly scans are accomplished, report results allow you to trend monitor your electrical equipmentwithout having to cross reference previous report findings.

If a previous years problem is not repaired it will show up again in the current scan report and its currentintensity range indicates a current effective response.

YEARS

10ºC *18ºF

25ºC45ºF

40°C72ºF

70°C126ºF

AMBIENT TEMP

STANDARD ELECTRICAL FAULT FAILURE CURVE(Does Not Include Area In Blue)

DEVICETEMP

ISAMBIENT,

BUTDEVICE

ISEITHERFAULTY

ORUNSAFE.INTERMEDIATEMINOR SERIOUS CRITICAL

Page 5: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

Defining Total Temperature and Ambient Operating Temperature AndExplanation For Their Use

Total Temperature:

Total Temperature = Ambient Operating Temperature + Fault temperature

Allows you, the customer, to evaluate possible damage to equipment.

Leads fail between 90ºC/194ºF and 110ºC/230ºPhenolic fails around 200ºC/392ºFTransformers and Motor Insulation failure temperature depends oninsulation class rating.Contacts start to fail around 130ºC/266ºF

Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes:

Temperature within a device container (Box or Cabinet) that is not directly affected byfaulting component = Normal Equipment Operating Temperature Contained By Boxor Cabinet.

If there is no container (Example: Device mounted to a wall) it is the temperatureadjacent to the device not affected by the fault.

Allows you, the customer, to determine if device will operate at intended amperage.

Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to50ºC/122ºF (Marine)

If AOT is enough above normal rated temperature, either of the followingconditions can cause an unanticipated trip.

1. An intermittent high load.2. A minor (Green) or intermediate (Yellow) fault.

Report pages with photographs:

PH stands for Visible Light PhotographTH stands for Infrared Light Thermograph

*AOT stands for Ambient Operating Temperature

Both black & white and color infrared thermographs are presented to better depict thefault condition.

Page 6: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

In addition to the corrective response time frame suggested below and the failure curve lo-cated on the previous page, you may want to consider using the militarystandard responses presented below.

Military Standard For Evaluating Faults Located In Electrical Equipment UtilizingTemperature Data Obtained With Infrared Imaging Equipment:

Temperatures rise above Ambient Operating Temperature:

*10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at nextscheduled routine maintenance period or as scheduling permits. (Green Label)

25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label)

40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected.(Orange Label)

70ºC/126ºF and above component failure imminent. Immediately inform the person responsible forcontinued operation of equipment. (Red Label)

Note: United Spectrographics uses a Blue Label to indicate faults that require attention due toeither ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafeconditions.

* Note: Temperature conditions below 10ºC/18ºF rise above AOT are not consideredsignificant enough to record and are usually not included in the reports unless the faulttemperature is being affected by a cooling medium such as oil or wind.

Fault Correction Recommendation When Our Source AssessmentIs Inaccurate:

When a fault is indicated in a connection or component and examination by your electriciandoes not turn up a loose connection or faulty component where we have indicated, a fault doesexist.

The electrician should continue to investigate the next connection or component to be foundin the direction that the heat is coming from until a source is located.

Example:

If a molded case breaker line side lead connection lug is indicated as a fault source and isfound to be secure, but not frozen in place, look for a loose connection or sign of over temp.in the lead holder lug.

Page 7: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

SCAN RESULTS OVERVIEW

PROMPT ATTENTION ITEMS:

Because of:

1. The intensity or heat level indicated at the time of the scan.

2. Deterioration caused by excessive temperature not present at the time of the scan.

3. Physical condition irregularities observed at the time of the scan.

We recommend that the following faults be given prompt attention:

Faults: #1, #3

Items With Asterisks Have High Total or Ambient Operating Temperatures.

United SpectrographicsJune, 2016

Page 8: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

SUMMARY OF FINDINGS

FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO.

MINOR 1 2/58

INTERMEDIATE 1 4/73

SERIOUS 1 1/34

CRITICAL 1 3/73

SERIOUS 0 0

Number of items located at facility: 88

Number of faults: 4

Page 9: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

ACTION TAKENSysco FreshPoint Denver

Denver, ColoradoJune, 2016

Fault # Item # Category Repaired Monitor Date Name

1 34 Serious

2 58 Minor

3 73 Critical

4 73 Intermediate

Page 10: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South B IsleControl Cabinet Labeled:

#13Combination Starter

PH # 1 >

ITEM: Aø of Motor Control Overload Relay

SOURCE: Heater internal contact area.

TEMP: Temp. of heater is:62ºC / 144ºF Total Temp

- 15ºC / 59ºF AOT= 47ºC / 85ºF above AOT.

TH # 1 >

COMMENTS

Abnormal heat is being generated in motor con-trol component. See orange arrows in PH#1 andTH#1.

Loose and/or corroded contact area. Clean, in-spect and re-secure serviceable components.

TEMPERATURE ABOVEAOT

47°C / 85°F

TH # 1 >

Page 11: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: RoofControl Cabinet Labeled:

Cond. 25Center of CabinetLeft 3ø Fuse Circuit

< PH # 2

ITEM: Aø & Bø Fuse Block

SOURCE: Load side fuse clip.

TEMP: Temp. of fuse clips range to:46ºC / 115ºF Total Temp.

- 32ºC / 90ºF AOT= 14ºC / 25ºF above AOT.

< TH # 2

COMMENTS

Abnormal heat is being generated in fuse blockcomponents. See green arrows in PH#2 andTH#2.

Loose and/or corroded contact areas. Clean, in-spect and re-secure.

TEMPERATURE ABOVEAOT

14°C / 25°F

< TH # 2

Page 12: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: Maintenance ShopBox Labeled:

E. Shop HeaterFuse Disconnect

PH # 3 >

ITEM: Cø of Disconnect

SOURCE: Line and load side disconnect bladecontact area.

TEMP: Temp. of contact areas range to:142ºC / 288ºF Total Temp.- 36ºC / 97ºF AOT

= 106ºC / 191ºF above AOT.

TH # 3 >

COMMENTS

Abnormal heat is being generated in disconnectcomponents. See red arrows in PH#3 and TH#3.

Loose and/or corroded contact areas. Clean, in-spect and re-secure serviceable components.

TEMPERATURE ABOVEAOT

106°C / 191°F

TH # 3 >

Page 13: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: Maintenance ShopBox Labeled:

E. Shop HeaterFuse Disconnect(Same As Previous Fault)

< PH # 4

ITEM: Cø Fuse Block

SOURCE: Load side fuse clipAndLoad side lead connection lug.

TEMP: Temp. of areas indicating a faultingcondition range to:

83ºC / 181ºF Total Temp.- 36ºC / 97ºF AOT

= 36ºC / 65ºF above AOT.

< TH # 4

COMMENTS

Abnormal heat is being generated in fuse blockcomponents. See yellow arrows in PH#4 andTH#4.

Loose and/or corroded contact area. Clean, in-spect and re-secure.

TEMPERATURE ABOVEAOT

36°C / 65°F

< TH # 4

Page 14: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South DockRefrigerated AreaLoading Bay Door 1Condition Exist Plant Wide

PH # 5 >

TH # 5 >

TH # 5 >

Page 15: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South DockRefrigerated AreaLoading Bay Door 5Condition Exist Plant Wide

< PH # 6

< TH # 6

< TH # 6

Page 16: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South DockRefrigerated AreaExterior Man Door 2Condition Exist Plant Wide

PH # 7 >

TH # 7 >

TH # 7 >

Page 17: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South DockRefrigerated AreaExterior WallCondition Exist Plant Wide

< PH # 8

< TH # 8

< TH # 8

Page 18: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South DockMain OfficeRefrigerated AreaInterior WallCondition Exist Plant Wide

PH # 9 >

TH # 9 >

TH # 9 >

Page 19: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PROJECT: 08220616

CUST REP: David Sharp

SCAN REP: Patrick Shamblin

DATE: 06/22/2016

LOCATION: South B IsleExterior WallRefrigerated AreaCondition Exist Plant Wide

< PH # 10

< TH # 10

< TH # 10

Page 20: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

No. Equipment Operating VisuallyInspected

Fault #

DRY STORAGE

1 #10Combination Starter X

2 #9 Combination Starter X

3 #4 Combination Starter (No Access)

4 #3 Combination Starter X

5 #5 Combination Starter (No Access)

6 #2 Combination Starter X

7 #6 Combination Starter X

8 #1 Combination Starter X

9 #7 Combination Starter X

10 #8 Combination Starter X

11 LPR 1 240 Volt Distribution Panel X

TOMATO STORAGE

12 X 240 Volt Distribution Panel X

SOUTH DOCK

13 Unlabeled 240 Volt Distribution Panel X

14 Unlabeled 480 Volt Distribution Panel X

15 Left Unlabeled 240 Volt Distribution Panel X

16 Right Unlabeled 240 Volt Distribution Panel X

17 Overhead Buss X

NORTH DOCK

18 PP3 480 Volt Distribution Panel X

19 Unlabeled 240 Volt Distribution Panel X

20 Over Head Transformer X

21 RU3 240 Volt Distribution Panel X

AREA/EQUIPMENT LIST

Following is a list of the electrical equipment located at the Sysco FreshPoint Denver, Colorado, facilityand data relating to its operating condition at the time the scan was performed.

NOTE: Items noted as visually inspected were not operational or show no visibleload at the time of the inspection.

Page 21: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

No. Equipment Operating VisuallyInspected

Fault #

A COOLER

22 HD 480 Volt Distribution Panel X

23 LH 208 Volt Distribution Panel X

24 LG 208 Volt Distribution Panel X

25 Left Overhead Transformer X

26 Middle Overhead Transformer X

27 Right Overhead Transformer X

28 LE 240 Volt Distribution Panel X

29 A 480 Volt Distribution Panel X

30 B 480 Volt Distribution Panel X

31 C 208 Volt Distribution Panel X

32 Overhead Transformer X

UPSTAIRS OFFICE

33 LE 240 Volt Distribution Panel X

SOUTH B ISLE

34 #13 Contactor Cabinet X 1

35 Weyco Disconnect Panel X

COMPRESSOR ROOM

36 Pravnon Disconnect (Interlocked)

37 HC 480 Volt Distribution Panel X

38 Sorgel Transformer (Cust. Did not open)

39 LF Overflow 208 Volt Distribution Panel X

40 LF 208 Volt Distribution Panel X

41 Cooler A Contactor Cabinet X

42 Freezer Lighting 240 Volt Distribution Panel X

43 Exhaust Fan South Combination Starter NIS

44 Exhaust Fan Middle Combination Starter NIS

45 Exhaust Fan North Combination Starter NIS

46 Unlabeled 480 Volt Distribution Panel NIS

Page 22: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

No. Equipment Operating VisuallyInspected

Fault #

47 Unlabeled 208 Volt Distribution Panel NIS

48 Sylvania Transformer NIS

49 Compressor 13 Control Cabinet X

50 Left Exhaust Fan Motor Control X

51 Right Exhaust Fan Motor Control X

52 Compressor 3 X

53 Compressor 5 X

54 Compressor 6 X

55 Compressor 4 X

56 Compressor 14 X

ROOF

57 Front Dock Disconnect X

58 Cond. 25 Control Cabinet X 2

59 Cond 26 Control Cabinet NIS

60 Cond 6 Disconnect (Interlocked)

61 Cond 8 Disconnect X

62 Cond 7 X

63 Cond 1 X

64 Cond 13 (Interlocked)

65 Cond 15 X

B ISLE

66 14 Control Cabinet X

67 Weyco Disconnect Panel X

68 5 Control Cabinet X

69 Back Up Air Compressor Disconnect X

70 Air Compressor Fuse Disconnect X

MAINTENACE SHOP

71 Unlabeled 240 Volt Distribution Panel X

72 Air Compressor Disconnect X

73 E. Shop Heater Fuse Disconnect X 3, 4

Page 23: Sysco FreshPoint Denver, CO Reports/2016 Reports/Sysco...SYSCO FRESHPOINT DENVER DENVER, COLORADO June, 2016 Infrared Inspection Report© 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

No. Equipment Operating VisuallyInspected

Fault #

74 N. Shop Heater Disconnect X

75 Overhead Transformer X

IN FRONT OF PROCESS ROOM

76 FD 120 Alarm Panel X

77 FH 1 480 Volt Distribution Panel X

78 FO 240 Volt Distribution Panel X

79 FO Disconnect X

80 FH 2 480 Volt Distribution Panel X

81 FC 240 Volt Distribution Panel X

82 Weyco Disconnect Panel X

83 #12 Control Cabinet X

84 Left Overhead Transformer X

85 Right Overhead Transformer X

BATTERY CHARGING STATION

86 J 480 Volt Distribution Panel X

87 Unlabeled 240 Volt Sub panel X

88 FH1 Disconnect (Interlocked)