subsynchronous oscillations

Upload: sulemankhalid

Post on 13-Oct-2015

60 views

Category:

Documents


1 download

DESCRIPTION

Subsynchronous Oscillations

TRANSCRIPT

  • 5/21/2018 Subsynchronous Oscillations

    1/40

    1539pk

    Copyright P. Kundur

    This material should not be used without the author's consent

  • 5/21/2018 Subsynchronous Oscillations

    2/40

    1539pkSO - 1

    In power system stability studies, turbine-generatorrotor is assumed to be made up of a single mass

    ! Accounts for oscillation of entire rotor! Frequency in the range of 0.2 to 2.0 Hz

    In reality, a steam turbine-generator rotor has a verycomplex structure consisting of several predominant

    masses (rotors of turbine sections, generator, and

    exciter) connected by shafts of finite stiffness

    ! When perturbed, torsional oscillations resultbetween different sections of turbine-generator rotor

    Torsional oscillations in the subsynchronous rangecould, under certain conditions, interact with the

    electrical system in an adverse manner:

    ! Subsynchronous resonance with series capacitorcompensated lines

    ! Torsional interaction with power system controls

  • 5/21/2018 Subsynchronous Oscillations

    3/40

    1539pkSO - 2

    Figure 15.3 shows the torsional characteristics of a555 MVA, 3600 RPM fossil-fuel-fired generating unit

    with a static exciter

    Since rotor has five masses, there are five modes ofoscillation:

    ! 1.67 Hz mode represents oscillation of the entirerotor against the power system. All five masses

    participate equally in this mode. This is the mode

    normally considered in rotor angle stability studies.

    ! 16.3 Hz mode is the first torsional mode. Has onepolarity reversal in the mode shape, with the rotors

    of generator and LPAoscillating against rotors ofLPB, IP and HP sections.

    ! 24.1 Hz is the second torsional mode. Its modeshape has two polarity reversals.

    ! 30.3 Hz and 44.0 Hz torsional modes have three andfour polarity reversals, respectively

  • 5/21/2018 Subsynchronous Oscillations

    4/40

    1539pkSO - 3

    Figure 15.3Rotor natural frequencies and mode shapes of a 555 MVA,

    3,600 r/min steam turbine generator

  • 5/21/2018 Subsynchronous Oscillations

    5/40

    1539pkSO - 4

    Torsional oscillations are inherently lightly damped

    Normally, not affected by generating unit or networkcontrols

    However, there have been several instances ofinstability of torsional modes due to interactions with

    ! Generator excitation controls! Prime-mover controls! Controls of nearby HVDC converters

  • 5/21/2018 Subsynchronous Oscillations

    6/40

    1539pkSO - 5

    Torsional mode destabilization by excitation control was firstobserved in 1969 while applying PSS at Lambton GS in Ontario,Canada

    ! PSS using speed signal at generator end of shaft excitedlowest torsional mode

    ! PSS transfer function designed to provide nearly zero phaseshift at system mode frequency of 1.6 Hz and produce puredamping torque

    ! At torsional frequency of 16 Hz, PSS results in 135 phase lagand hence, negative damping

    Problem solved by using torsional filter and sensing speedbetween the two LP turbine sections! Close to the "node" of 16 Hz torsional mode! Other torsional modes also have very low amplitude

  • 5/21/2018 Subsynchronous Oscillations

    7/40

    1539pkSO - 6

    Examine effect of PSS on torsional stability of a 889MVA, 1,800 RPM generating unit with a tandem

    compound turbine and static exciter

    Each double flow LP turbine section is represented bytwo masses:

    Objective is to examine the system performance withdifferent forms of PSS

    Figure E15.1 Shaft system representation

  • 5/21/2018 Subsynchronous Oscillations

    8/40

    1539pkSO - 7

    Delta-omega stabilizer with shaft speed (-a) as inputsignal with speed measured at

    ! the generator end! at coupling B! coupling C! both couplings B and C

    Excitation system model

    Results shown in Table E15.1Figure E15.3 Thyristor exciter with delta-omega stabilizer

  • 5/21/2018 Subsynchronous Oscillations

    9/40

    1539pkSO - 8

    Speed signal at generator end causes instability ordecreased damping of torsional modes while damping

    system mode

    Sensing at B adversely affects 23 Hz torsional mode Sensing at C adversely affects 9 Hz torsional mode No single speed sensing location suitable for all

    torsional modes

    Combination of B and C best for torsional modes System mode is insensitive to sensing location;

    depends only on gain

    Exciter mode is heavily damped in all cases

  • 5/21/2018 Subsynchronous Oscillations

    10/40

    1539pkSO - 9

    KSTAB

    Speed

    Sensing

    Location

    Torsional Modes System

    ModeExciter Mode

    9 Hz 17 Hz 23 Hz 24 Hz

    0.0 - -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 +0.23j5.7 -

    9.5 Generator +0.31j57.6 +0.20j106.0 +0.24j146.4 -0.06j151.3 -0.73j5.0 -13.7j13.1

    9.5 Coupl-B -0.25j55.3 -0.17j105.6 -0.01j146.2 -0.19j151.2 -0.75j5.0 -16.713.9

    19.0 Coupl-B -0.47j54.3 -0.28j105.5 +0.07j146.3 -0.20j151.2 -1.20j4.2 -14.5j19.7

    9.5 Coupl-C +0.06j56.6 -0.26j105.5 -0.21j146.1 -0.18j151.2 -0.74j5.0 -15.5j13.7

    19.0 Coupl-C +0.20j57.0 -0.46j105.3 -0.31j146.1 -0.19 j151.2 -1.20j4.2 -12.8j18.5

    9.5 Both B and C -0.10j56.0 -0.22j105.5 -0.11j146.1 -0.19j151.2 -0.74j5.0 -16.1j13.8

    19.0 Both B and C -0.16j55.7 -0.37j105.4 -0.12j146.1 -0.20j151.2 -1.20j4.2 -13.6j19.1

    28.5 Both B and C -0.22j55.5 -0.52j105.2 -0.13j146.1 -0.21j151.2 -1.36j3.6 -11.9j22.9

  • 5/21/2018 Subsynchronous Oscillations

    11/40

    1539pkSO - 10

    Stabilizer as in Case A, but with a torsional filterhaving a notch at 9 Hz and substantial attenuation at

    the higher torsional natural frequencies.

    Results shown in Table 15.2 Filter makes torsional modes insensitive to speed

    signal stabilization

    Damping of system mode with filter is about the sameas without

    Filter has adverse effect on "exciter mode"! Filter characteristics increase gain in the frequency

    range associated with exciter mode

    ! Stabilizer gain has to be limited to low values! limits the effectiveness of PSS in damping system

    mode

  • 5/21/2018 Subsynchronous Oscillations

    12/40

    1539pkSO - 11

    KSTAB

    Speed

    Sensing

    Location

    Torsional Modes System

    Mode

    Exciter

    Mode9 Hz 17 Hz 23 Hz 24 Hz

    0.0 - -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 +0.23j5.7 -

    9.5 Generator -0.06j56.2 -0.07j105.7 -0.11j146.1 -0.17j151.2 -0.91j5.1 -10.4j15.8

    9.5 Coupl-B -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -0.94j5.0 -8.114.1

    19.0 Coupl-B -0.05j56.2 -0.06j105.7 -0.10j146.1 -0.17j151.2 -1.42j4.1 -1.9j20.5

    9.5 Coupl-C -0.06j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -0.92j5.0 -10.5j20.0

    19.0 Coupl-C -0.06j56.2 -0.06j105.7 -0.10j146.1 -0.17 j151.2 -1.41j4.2 -3.2j20.0

    9.5 Both B and C -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -0.93j5.0 -9.4j21.3

    19.0 Both B and C -0.05j56.2 -0.06j105.7 -0.10j146.1 -0.17j151.2 -1.42j4.2 -2.5j20.4

    28.5 Both B and C -0.05j56.2 -0.06j105.7 -0.10j146.1 -0.17j151.2 -1.54j3.5 +0.5j20.6

  • 5/21/2018 Subsynchronous Oscillations

    13/40

    1539pkSO - 12

    Stabilizer with electrical power deviation (delta-P) asstabilizing signal

    Similar to previous one, except that an equivalentspeed (-aeq) derived from electrical power is used

    instead of actual shaft speed

    Results shown in Table E15.3 PSS does not cause instability of torsional modes Exciter well damped High stabilizer gain can be used, resulting in a well

    damped system.

    Figure E15.4 Thyristor exciter with delta-P stabilizer

  • 5/21/2018 Subsynchronous Oscillations

    14/40

    1539pkSO - 13

    KSTABTorsional Modes System

    ModeExciterMode9 Hz 17 Hz 23 Hz 24 Hz

    0.0 -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 +0.23j5.7 -

    9.5 -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -0.75j5.0 -15.6j13.7

    19.0 -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -1.20j4.2 -13.118.6

    28.5 -0.05j56.2 -0.07j105.7 -0.10j146.1 -0.17j151.2 -1.40j3.6 -11.3j22.0

  • 5/21/2018 Subsynchronous Oscillations

    15/40

    1539pkSO - 14

    Problem first came to light on Square Butte HVDCsystem in North Dakota

    ! Consists of 250 kV, 500 MW dc link! Rectifier station located adjacent to Milton Young

    GS with two units: 234 MW and 410 MW

    Converters employ equidistant firing system! Normal regulator control modes are constant

    current control at the rectifier and constant voltage

    at the inverter

    ! In addition, a supplementary "frequency sensitivepower controller" (FSPC) is provided for damping

    system oscillations

    Field tests showed that! The supplementary damping controller destabilized

    the first torsional mode (11.5 Hz) of 410 MW

    generating unit

    ! Normal constant current control, without dampingcontroller, could cause instability of 11.5 Hztorsional mode

    Problem solved by modifying converter controls

  • 5/21/2018 Subsynchronous Oscillations

    16/40

    1539pkSO - 15

    Basic Phenomenon

    Torsional mode oscillations cause phase andamplitude modulation of generated voltage waveform

    ! modulated voltage has frequency components equalto fo-ft

    Modulated voltage impressed on the dc systemcommutating bus

    With equidistant firing angle control! a shift in voltage phase due to a torsional mode

    causes a similar shift in firing angle

    ! results in corresponding changes in direct current,voltage and power

  • 5/21/2018 Subsynchronous Oscillations

    17/40

    1539pkSO - 16

    Closed-loop current control responds to correct thesechanges

    ! reflected as a change in the generator power If the net phase lag between the variation in shaft

    speed at the torsional frequency and the resulting

    change in electrical torque of the generator exceeds

    90,

    ! torsional oscillations become unstable

  • 5/21/2018 Subsynchronous Oscillations

    18/40

    1539pkSO - 17

  • 5/21/2018 Subsynchronous Oscillations

    19/40

    1539pkSO - 18

    Occurs mainly in series capacitor compensatedtransmission systems

    First experienced in 1970 resulting in shaft failure ofunits at Mohave Plant in Southern California

    Not until the second failure in 1971 was the real causeof failure recognized as SSR

    Consider a simple radial system:

    Figure 15.9 Radial series compensated system

  • 5/21/2018 Subsynchronous Oscillations

    20/40

    1539pkSO - 19

    Natural frequency fnof the circuit inductance andcapacitance:

    or

    In an uncompensated transmission system, faults andother disturbances result in dc offset components in

    generator stator windings:

    ! result in a component of air-gap torque at slipfrequency equal to fo

    ! necessary to avoid torsional frequencies very nearthe fundamental frequency fo

    In a series capacitor compensated system, instead ofthe dc component, the offset transient current is an

    alternating current of frequency equal to the natural

    frequency fn

    ! induce rotor currents and torques of slip frequency(fo-fn) Hz

  • 5/21/2018 Subsynchronous Oscillations

    21/40

    1539pkSO - 20

    Table 15.1 shows the natural and slip frequencies as afunction of the degree of compensation (with f0 = 60 Hz)

    Percent Compensation

    (XC/XL) x 100 (%)

    Natural Frequency

    fn(Hz)

    Slip Frequency

    60-fn(Hz)

    10 18 42

    25 30 30

    30 32.6 27.4

    40 38 22

    50 42.4 17.6

    Table 15.1

  • 5/21/2018 Subsynchronous Oscillations

    22/40

    1539pkSO - 21

    Here we have considered a simple radial system. For acomplex network, the frequency-dependent

    characteristic of the effective impedance seen by a

    generator may be determined by a frequency scanning

    program

    A series compensated network can cause sustained ornegatively damped subsynchronous oscillations by

    two distinctive mechanisms:

    a) Self-excitation due to induction generator effect

    b) Interactions with torsional oscillations (SSR) A shunt compensated transmission system normally

    has natural frequencies in the supersynchronousrange

    ! Subsynchronous oscillations normally do not posea problem

    ! Exceptions are situations involving very long linesand a high degree of shunt compensation

  • 5/21/2018 Subsynchronous Oscillations

    23/40

    1539pkSO - 22

    Since fn< f0, slip is negative.Depending on fn, Reff can be negative

    At high degrees of compensation, the apparentnegative resistance of the generator may exceed thetransmission network resistance,

    ! Effectively results in an RLC circuit with negativeresistance

    Will result in self-excitation causing electricaloscillations of intolerable levels

    Purely electrical phenomenon; not dependent on shafttorsionals

  • 5/21/2018 Subsynchronous Oscillations

    24/40

    1539pkSO - 23

    If the complement of fn(i.e., f0 - fn) is close to one of thetorsional frequencies, torsional oscillations are excited

    ! Results in a strong "coupling" between electrical andmechanical systems

    ! Condition referred to as "subsynchronous resonance"! A small voltage induced by rotor oscillations can result

    in large subsynchronous currents

    ! Will produce torque whose phase is such that itenhances rotor oscillations

    Consequences of SSR can be dangerous! If oscillations build up, shaft will break!

    Even if oscillations not unstable, system disturbancescan cause shaft torques of high magnitude and loss of

    shaft fatigue life

    Countermeasures to SSR:! Static filter! Dynamic filter! Dynamic stabilizer! Excitation system damper! Protective relays! NGH scheme

  • 5/21/2018 Subsynchronous Oscillations

    25/40

    1539pkSO - 24

    Illustrates the two forms of instability ofsubsynchronous oscillations associated with series

    capacitor compensated systems

    ! SSR and self-excitation Test system considered is shown below

    ! consists of a 555 MVA, 24 kV, 3,600 RPM turbine-generator feeding power through a series capacitor

    compensated transmission system to an infinite bus

    Shaft system parameters and the torsionalcharacteristics of the generating unit are as shown in

    Figure 15.3

  • 5/21/2018 Subsynchronous Oscillations

    26/40

    1539pkSO - 25

    Power flow condition is as follows:

    Pt= 519.5 MW Et= 1.08 EB= 1.0

    Degrees of compensation (i.e., XC/X

    L) is varied and the

    reactive power output of the generator varies

    accordingly

    Focus is on the interaction between the lowesttorsional (16 Hz) mode and the subsynchronous

    natural frequency oscillation of the network for the

    following values of load at the HV bus:

    a) PL= 166.5 MW, QL= 0

    b) PL= 0 QL= 0

  • 5/21/2018 Subsynchronous Oscillations

    27/40

    1539pkSO - 26

    Case (a): With PL= 166.5 MW, QL= 0

    Eigenvalue analysis used to analyze the modal interaction! system model includes the dynamics of the

    transmission network and the generator stator circuits.

    The complete system equations are expressed in the dq

    reference frame

    Table E15.4 gives eigenvalues, frequencies, and dampingratios of lowest torsional mode and network mode

    Participation factors associated with generator speeddeviation and voltage across the series capacitor are also

    given

    ! help identify extent of interaction between the twomodes

    Network is in dqreference frame (rotates at generatorspeed)

    ! frequency of network mode is the complement of thenetwork natural frequency

    With no compensation, torsional mode has frequency of16.29 Hz and small positive damping

    With 25% compensation, frequency and dampingincrease slightly

    ! little interaction between modes

  • 5/21/2018 Subsynchronous Oscillations

    28/40

    1539pkSO - 27

    % Comp.

    Torsional Mode Network Mode

    Freq.(Hz)

    !

    ParticipationFactors Freq.

    (Hz)!

    Participation Factors

    "#1 "vc "#1 "vc

    0.0 16.29 0.0004 0.90 - - - - -

    25.0 16.32 0.0006 0.90 0.002 35.20 0.0130 0.03 1.00

    50.0 16.41 0.0010 0.90 0.01 24.75 0.0288 0.02 0.99

    60.0 16.50 0.0012 0.90 0.04 21.80 0.0231 0.01 1.00

    65.0 16.61 0.0010 0.91 0.09 20.09 0.0230 0.05 1.00

    70.0 16.90 -0.0027 0.91 0.31 18.27 0.0273 0.26 1.00

    75.0 16.85 -0.0468 0.93 0.77 16.88 0.0721 0.65 0.95

    80.0 16.28 -0.0590 0.93 0.75 16.05 0.0858 0.63 0.95

  • 5/21/2018 Subsynchronous Oscillations

    29/40

    1539pkSO - 28

    As compensation is increased! frequency of the torsional mode varies slightly! damping increases slightly at first, then decreases

    At 70% compensation, torsional mode is just unstableand noticeable interaction between torsional and

    network modes

    Further increase in compensation strengthens"coupling"

    ! pulls modes together in frequency but apart indamping

    At 75% to 80% compensation, coupling is strongestand frequencies are nearly equal

    Effect of "interaction" of torsional and network modeon characteristics of network mode can be seen in

    Table E15.5

    ! provides frequency and damping of network modewith and without multimass representation

  • 5/21/2018 Subsynchronous Oscillations

    30/40

    1539pkSO - 29

    % Comp. ofline 2-3

    Network mode withmultimass representation of

    the turbine-generator rotor

    Network mode with singlelumped mass representation

    of the turbine-generator rotor

    Freq. (Hz) Damp. Freq. (Hz) Damp.

    0.0% 0.95 0.0280 0.95 0.0244

    25.0% 35.20 0.0130 35.32 0.0133

    50.0% 24.75 0.0288 25.13 0.0185

    60.0% 21.80 0.0231 21.82 0.0205

    65.0% 20.09 0.0230 20.27 0.0215

    66.0% 19.74 0.0230 19.96 0.0217

    68.0% 19.04 0.0241 19.37 0.0221

    70.0% 18.27 0.0273 18.78 0.0224

    71.3% 17.70 0.0376 18.39 0.0227

    72.0% 17.49 0.0460 18.20 0.0228

    74.0% 17.06 0.0658 17.63 0.0231

    75.0% 16.88 0.0721 17.35 0.0233

    77.0% 16.51 0.0814 16.74 0.0237

    78.0% 16.23 0.0850 16.27 0.0239

    80.0% 16.05 0.0858 15.96 0.0241

  • 5/21/2018 Subsynchronous Oscillations

    31/40

    1539pkSO - 30

    Case (b): With PL= QL= 0

    Results are summarized in Table E15.6 With the load removed, the effective resistance of the

    network is reduced significantly. Consequently, the

    network mode becomes unstable due tothe induction

    motor effect

    As the frequency of the network mode approaches thetorsional mode frequency, the coupling between the

    two modes increases

    ! The effect of the interaction is to increase thedamping of the torsional mode and to decrease the

    damping of the network mode

  • 5/21/2018 Subsynchronous Oscillations

    32/40

    1539pkSO - 31

    % Comp.of line 2-3

    Torsional Mode Network Mode

    Freq.(Hz)

    !

    ParticipationFactors Freq.

    (Hz)!

    Participation Factors

    "#1 "vc "#1 "vc

    0.0 16.28 0.0003 0.896 - - - - -

    25.0 16.32 0.0004 0.898 0.002 35.20 0.0088 0.03 1.00

    70.0 16.94 0.0050 0.909 0.34 18.25 -0.0058 0.33 1.00

    75.0 16.79 0.0570 0.940 0.88 16.94 -0.0611 0.78 1.00

    80.0 16.14 0.0681 0.930 0.88 16.20 -0.0758 0.78 1.00

    85.0 15.53 0.0500 0.871 0.83 15.46 -0.0639 0.71 1.00

    93.7 15.80 0.0013 0.870 0.13 12.9 -0.0241 0.07 1.00

  • 5/21/2018 Subsynchronous Oscillations

    33/40

    1539pkSO - 32

    A generating unit encounters multitude of switchingduties during its lifetime

    ! can produce high levels of oscillatory shaft torques! the resulting cyclic stress variations on the shaft

    may cause loss of "fatigue life"

    ! a cumulative process with each incident using aportion of the total fatigue life

    In the early 1970s, it was recognized that network-switching operations could contribute to shaft fatigue

    damage

    Problem examined by an IEEE Working Group, andgeneral recommendations made to industry

    concerning:

    a) steady-state switching

    b) successive network switching

  • 5/21/2018 Subsynchronous Oscillations

    34/40

    1539pkSO - 33

    Fatigue is a cumulative process in which additional events addto previous life expenditure

    Observable defects such as cracks will not be formed until allthe fatigue life is consumed

    Typical fatigue characteristics:

    High-cycle fatigue limit (HCFL) is the limiting value of cyclicstress to which shaft can be subjected such that nocumulative fatigue damage occurs

    Figure 15.11 A typical fatigue characteristic showing cycle life curve for fullyreversed stress

  • 5/21/2018 Subsynchronous Oscillations

    35/40

    1539pkSO - 34

    Most severe switching operation, with the networkinitially under steady state, is the reclosing of lines

    across a large breaker angle

    ! Depending on network impedances, the resultingsudden increase in generator torque of a nearbygenerator could be very large

    ! If resulting torques are high, this may result in lossof shaft fatigue life

    For planned switching operations, such as a simpleline restoration, IEEE Guidelines recommend that

    switching be conducted so that it does not contribute

    significantly to cumulative shaft fatigue! Magnitude of cycle shaft stress, should be kept

    mostly below HCFL

    ! This way, nearly all of fatigue capability will bepreserved to withstand impact of unplanned and

    unavoidable disturbances, such as faults

  • 5/21/2018 Subsynchronous Oscillations

    36/40

    1539pkSO - 35

    A detailed investigation, involving assessment of shafttorques and loss of fatigue life, for all possible line-

    switching duties would be impractical

    Reference 32 prepared by an IEEE Working Groupprovides general guidelines to permit utilities toscreen switching operations

    ! assume a simple line restoration from steady state! hence, applicable only for delayed (10 seconds or

    more) reclosing

    ! based on detailed studies of a number of cases Breaker angle is not by itself useful in judging severityof a switching operation

    ! circuit impedances play a major role Therefore, severity is measured in terms of the sudden

    change in the generator power ("P), as computed by a

    conventional transient stability program

  • 5/21/2018 Subsynchronous Oscillations

    37/40

    1539pkSO - 36

    A rule-of-thumb limit for "P is:! 0.5 pu of generator MVA rating

    A line-switching case resulting in "P of less than 0.5pu considered safe

    ! no contribution to loss of fatigue life Switching operations resulting in "P greater than the

    0.5 pu limit have to be studied in detail to assess theshaft duty

    Reference 32: IEEE WG Report, "IEEE Screening Guide for Planned Steady-State Switching Operations to Minimize Harmful Effects on Steam TurbineGenerators", IEEE Trans., Vol. PAS-99, No. 4, pp. 1519-1521, July/August1980.

  • 5/21/2018 Subsynchronous Oscillations

    38/40

    1539pkSO - 37

    Successive network disturbances, such as automatichigh-speed line reclosing following a fault,

    ! can result in dangerously high torques Concern is for the compounding effects of the different

    switching operations

    ! torsional oscillations due to successive impactsmay reinforce the initial oscillations

    ! risk of amplifying torsional oscillations to damaginglevels is a function of the type of disturbance and

    the timing of subsequent switching operations

    Reference 33 prepared by the IEEE Working Groupgives a summary of the predicted range of fatigue life

    expenditure for various types of disturbances:

    ! different type faults, fault clearing, successfulreclosing, unsuccessful reclosing

    cont'd

  • 5/21/2018 Subsynchronous Oscillations

    39/40

    1539pkSO - 38

    Automatic high speed reclosing of multiple faultedlines near thermal generating plants pose significant

    risks of shaft fatigue life expenditure

    ! where contemplated, a study of shaft fatigue dutyrecommended

    The following are possible alternative reclosingstrategies with reduced risk of shaft damage:

    ! Delayed reclosing, with a delay of 10 seconds ormore

    ! Sequential reclosing: automatic reclosing from theremote end, followed by synchro-check reclosing of

    the plant end

    ! Selective reclosing: limiting high-speed reclosing toL-G faults and L-L faults

    Reference 33: IEEE Working Interim Report, "Effects of Switching

    Network Disturbances on Turbine-Generator Shaft System", IEEE

    Trans., Vol. PAS-101, No. 9, pp. 3151-3157, September 1982

  • 5/21/2018 Subsynchronous Oscillations

    40/40

    1539pkSO - 39

    Rotor of a hydraulic generating unit consists of aturbine runner and a generator rotor

    ! If unit has a shaft-driven exciter, there is anadditional rotor mass

    ! There are at most two torsional modes of oscillation Inertia of generator rotor about 10 to 40 times that of

    turbine runner (waterwheel)

    No reported cases of adverse dynamic interaction withelectrical network

    Principal reasons for absence of adverse interaction:

    a) High generator rotor inertia relative to turbine runner

    " effectively shields the rotor mechanical systemfrom the electrical network

    b) Viscous waterwheel damping" torsional oscillations inherently highly damped