stu chiller 2012
DESCRIPTION
ChillerSistem Tata UdaraTRANSCRIPT
-
FTUI KI-KE
DTM
124.04.2012
CHILLER PLANT
-
FTUI KI-KE
DTM
2
-
FTUI KI-KE
DTM
3
CENTRIFUGAL CHILLER
RECIPROCATING CHILLER
SCREW CHILLER
-
FTUI KI-KE
DTM
4A typical three-stage, water-cooled centrifugal chiller
-
FTUI KI-KE
DTM
5
-
FTUI KI-KE
DTM
6
Penentuan Kinerja Electric Chiller
1. Metoda dan prosedur untuk menentukan kinerja electyric chiller mengacu pada
rekomendasi ASHRAE Guideline 22-2008 Instrumentation for Monitoring Central
Chilled-Water Plant Efficiency.
2. Effisiensi chilled water-plant tergantung pada unjuk kerja tiap komponen peralatan
yaitu chiller, chilled water pump, condenser water pump dan cooling tower.
3. Pekerjaan yang dilakukan hanya terbatas pada penentuan kinerja electric
chiller dan tidak mecakup penentuan kinerja chiller plant keseluruhan.
4. Pengukuran lapangan mencakup variabel :
a. Flow measurements : Chilled water flowrate, kg/s
b. Temperature measurements : Cooler Inlet and outlet chilled water temperature, oC
and ambient temperature TDB and TWB
c. Electrical power : power input to Compressor, kW
-
FTUI KI-KE
DTM
7
5. Perhitungan Kinerja :
a. kW/ton rating = Measured compressor power, kW
Net refrigeration Capacity (TR)
b. COP =
6. Peralatan ukur :
a. Portable Ultrasonic Flowmeter, 10,000 mg/ltr, 0.3 32 m/s, up to 100 oC
b. Handheld digital temperature, Thermocouple K type
c. Sling thermometer (TDB and TWB)
d. Power quality analyzer, 220 1000 Volt, 3 phase
e. Clamp on tester, 1 phase
7. Pengambilan data
a. Pengukuran temperatur dan laju alir volumetrik dimulai setelah kondisi steady
state tercapai, kurang lebih satu jam setelah chiller dioperasikan.
b. Pengambilan data dilakukan setiap satu jam mulai dari kondisi steady state sampai
chiller off pada sore hari, selama lima hari kerja.
8. Perhitungan Kinerja
Mengacu pada ASHRAE Guideline 22-2008 Instrumentation for Monitoring Central
Chilled-Water Plant Efficiency, Chapter 7. Calculations.
-
FTUI KI-KE
DTM
8
Optimizing the Design and Control of
Chilled Water Plants
Steve Taylor
The PG&E Pacific Energy Center
March 7, 2012
Taylor Engineering LLC
Alameda, CA
-
FTUI KI-KE
DTM
9
Optimizing Energy Usage
Chillers Type, efficiency, size, VSD
Cooling Towers Fan type, efficiency, approach, range, speed control, flow
turndown
Chilled Water Pumps Arrangement, flow rate (delta-T), pressure drop, VSD
Condenser Water Pumps Flow rate (delta-T), pressure drop
Air Handling Units Coil sizing, air-side pressure drop, water-side pressure drop
-
FTUI KI-KE
DTM
10
-
FTUI KI-KE
DTM
11
-
FTUI KI-KE
DTM
12
-
FTUI KI-KE
DTM
13
Optimizing CHW Plant Design
Ideal: Design a plant with lowest life cycle costs (first cost
plus lifelong operating costs) accounting for all the
complexities and interaction among plant components
Practical: Design plant subsystems to be near-life cycle cost
optimum using techniques that are simple and practical
enough to be used without a significant increase in design
time
-
FTUI KI-KE
DTM
14
Chilled Water Distribution Systems
Water Distribution System Classes
-
FTUI KI-KE
DTM
15
Constant Flow
Single Chiller, Single Coil, No Control Valve
-
FTUI KI-KE
DTM
16
Constant FlowTwo Chillers, Single Coil, No Control Valve
-
FTUI KI-KE
DTM
17
Constant FlowSingle Chiller, Multiple Coils
-
FTUI KI-KE
DTM
18
Variable FlowSingle Chiller, Multiple Coils
-
FTUI KI-KE
DTM
19
Constant FlowMultiple Parallel Chillers, Multiple Coils
-
FTUI KI-KE
DTM
20
Variable Flow
Vary Flow Through Coil Circuit
Two-way valves
Variable speed coil pump
Configurations
Primary-secondary
Primary-secondary variations
Primary-on
-
FTUI KI-KE
DTM
21
Variable Flow Chilled Water Systems
Old Paradigm
Controls respond to changes in CHW temperature
Variable flow causes low temperature trips, locks out
chiller, requires manual reset (may even freeze)
Hence: Maintain constant flow through chillers
-
FTUI KI-KE
DTM
22
-
FTUI KI-KE
DTM
23
Primary/Secondary
-
FTUI KI-KE
DTM
24
Variable FlowPrimary/Secondary, Multiple Chillers and Coils
-
FTUI KI-KE
DTM
25
Variable FlowPrimary/Secondary, Series Flow, Multiple Chillers
-
FTUI KI-KE
DTM
26
Variable FlowPrimary/Distributed Secondary
-
FTUI KI-KE
DTM
27
Variable Flow Chilled Water Systems
New Paradigm
Modern controls are robust and very responsive to both
flow and temperature variations
Variable flow OK within range and rate-of-change
specd by chiller manufacturer
-
FTUI KI-KE
DTM
28
Variable FlowPrimary-only, Multiple Chillers
-
FTUI KI-KE
DTM
29
Variable FlowPrimary, Bypass Valve
-
FTUI KI-KE
DTM
30
Primary CHW Pump Options