1-151.13November, 2008

Steam/Hot Water Unit Heaters

Horizontal DeliverySide Connections

Horizontal DeliveryTop and Bottom

Connections

Vertical Delivery Power-ThrowTM

Horizontal HighVelocity Delivery

Standard Models Low-Outlet Temperature Models

Steam Hot Water Steam (2# Steam) (200°F In, 180°F Out) (2# Steam)

Heat Heat Final Final Max. Throw @ Final Max. Throw @ ➂ Air Water Air Mtg. Max. Mtg. Air Mtg. Max. Mtg. Motor Temp. Flow Temp. Height Height Temp. Height Height Model Number HP Btu/Hr (°F) Btu/Hr (GPM) (°F) CFM (Ft) (Ft) Model Number Btu/Hr CFM (°F) (Ft) (Ft)

HSB/HC 18 1/60 18,000 107 12,560 1.3 94 340 9 18 HSB/HC 18L 15,900 364 100 9 20 HSB/HC 24 1/25 24,000 119 16,250 1.7 100 370 10 19 HSB/HC 24L 19,300 435 100 11 21 HSB/HC 33 1/25 33,000 108 21,680 2.3 91 630 11 22 HSB/HC 33L 29,500 695 99 12 24 HSB/HC 47 1/12 47,000 119 30,940 3.2 98 730 13 30 HSB/HC 47L 32,000 855 94 14 32 HSB/HC 63 1/12 63,000 111 45,580 4.7 97 1120 15 31 HSB/HC 63L 52,500 1170 101 16 33 HSB/HC 86 1/8 86,000 118 60,210 6.3 101 1340 16 33 HSB/HC 86L 61,500 1510 97 17 36 HSB/HC 108 1/8 108,000 109 83,740 8.7 98 2010 18 33 HSB/HC 108L 86,500 2150 97 19 36 HSB/HC 121 1/5 121,000 122 93,000 9.7 108 1775 17 27 HSB/HC 121L 88,000 2070 98 18 29 HSB/HC 165 1/3 165,000 106 130,950 13.6 97 3240 20 43 HSB/HC 165L 143,000 3480 97 21 45 HSB/HC 193 1/3 193,000 121 143,000 14.9 105 2900 19 40 — — — — — HSB/HC 258 1/2 258,000 111 201,950 21 100 4560 20 47 HSB/HC 258L 190,000 4655 98 22 51 HSB/HC 290 1/2 290,000 117 228,620 23.8 105 4590 21 49 HSB/HC 290L 207,000 5040 94 23 53 HSB/HC 340 1/2 340,000 120 271,110 28.2 108 5130 21 49 HSB/HC 340L 255,000 5575 102 23 53

2

HORIZONTAL AIR DELIVERY MODELS

HSB and HC models feature the following:

•Squaredoffcornersforaclean,smoothappearance.

•HSBmodelshavetopandbottomsupplyandreturnsteelconnections.

•HCmodelshaveacoppertubeandcoppercoilconnectionslocatedonthesideforlowclearanceapplications.

•Atwopiececasingforquickaccesstocoil.

•Anelectricjunctionboxforeasyelectricalconnections.

•Bakedongray-green,electrostaticallyappliedpolyesterpowdercoat,environmentallyfriendlypaint.

•Motorsaretotallyenclosedwiththermaloverloadprotection.

•Lowoutlettemperaturemodelsforhighersteampressuresordirtyatmospheres.

•ListedbytheCanadianStandardsAssociationandCRNregisteredheatexchanger.Model HC

Dimensions - Models HSB/HC

Model HSB

Mounting Holes:Sizes18-86,3/8"-16TapSizes108-340,1/2"-13Tap

➀ Top/BottomConnections(HSBonly)➁ SideConnections(HConly)

HSB HC

C D ➂Approx.

Weight (lbs)Model Size A B A B

18 & 24 12.38 13.00 11.50 13.00 6.00 5.00 16&20

33 & 47 16.38 17.50 15.00 17.50 8.75 6.00 34&36

63 & 86 20.44 21.50 18.50 21.50 8.75 7.75 48&52

108 & 121 24.44 25.50 22.50 25.50 9.50 6.75 74&76

165 30.50 30.50 26.50 29.50 9.25 8.50 92

193 30.50 30.50 30.50 32.50 9.25 8.50 98

258 & 290 38.50 38.50 38.50 38.50 12.50 10.00 162&168

340 38.50 44.50 38.50 44.50 12.50 10.00 176 ➂ Dimensions shown apply to standard 115V/1ph motor (Power Code 01).

Performance Data (60°F Entering Air Temperature)

➂ Dimensions shown apply to standard 115V/1ph motor (Power Code 01).

Standard Models Low-Outlet Temperature Models

Steam Hot Water Steam (2# Steam) (200°F In, 180°F Out) (2# Steam)

*Heat *Heat Final Final *Max. Spread @ Final *Max. Spread @ ➂ Air Water Air Mtg. Max. Mtg. Air Mtg. Max. Mtg. Motor Temp. Flow Temp. Height Height Temp. Height Height Model Number HP Btu/Hr (°F) Btu/Hr (GPM) (°F) CFM (Ft) (Ft) Model Number Btu/Hr CFM (°F) (Ft) (Ft)

V/VN 42 1/30 42,000 103 30,100 3.1 90 950 16 12 V/VN 42L 33,000 960 94 17 13 V/VN 59 1/30 59,000 111 42,640 4.4 96 1155 20 15 V/VN 59L 44,000 1190 96 22 16 V/VN 78 1/15 78,000 109 56,960 5.9 95 1590 21 16 V/VN 78L 62,000 1740 95 26 19 V/VN 95 1/15 95,000 118 69,300 7.2 101 1665 21 16 V/VN 95L 71,000 1760 99 26 19 V/VN 139 1/5 139,000 112 106,600 11.1 99 2660 26 19 V/VN139L 103,000 2860 95 31 23 V/VN 161 1/3 161,000 115 123,220 12.8 101 2945 29 21 V/VN 161L 127,000 3400 96 35 26 V/VN 193 1/3 193,000 116 147,200 15.3 101 3500 32 23 V/VN 193L 149,000 3710 99 36 27 V/VN 212 1/3 212,000 120 161,680 16.8 104 3610 32 23 V/VN 212L 163,000 3830 102 36 27 V/VN 247 1/2 247,000 111 188,700 19.7 98 4820 36 28 V/VN 247L 190,000 5110 96 42 32 V/VN 279 1/2 279,000 111 212,650 22.2 98 5460 39 32 V/VN 279L 215,000 5790 96 45 36 V/VN 333 3/4 333,000 116 260,080 27.1 103 5980 39 32 V/VN 333L 256,000 6340 100 45 36 V/VN 385 1 385,000 110 302,080 31.5 98 7680 38 32 V/VN 385L 296,000 8140 95 43 36 V/VN 500 1-1/2 500,000 108 391,690 40.8 97 10,390 47 39 V/VN 500L 385,00011,000 94 54 45 V/VN 610 1-1/2 610,000 112 450,420 46.9 97 11,750 46 38 V/VN 610L 470,00012,400 97 52 44 V 952 2 952,000 139 721,640 75.2 120 12,170 39 60 V 952L 733,30012,940 115 61 68

3

VERTICAL AIR DELIVERY MODELS

V and VN models feature the following:

•Vmodelshavecoppertubes,VNmodelshavecopper/nickeltubesforhightemperatureand/orpressureapplications.

•Lowoutlettemperaturemodelsforhighersteampressuresordirtyatmospheres.

•Allunitsprovidedwithoutletfanguard.

•Motorcoolingconeshieldsmotorfromheatforlongerlife.

•Optionalairdeflectors,ConeJet,TrunconeandLouversforavarietyofheatthrowpatterns.

•Allunitsincludeanelectricjunctionboxforeasyelectricalconnections.

•Bakedongrey-green,electrostaticallyappliedpolyesterpowdercoat,environmentallyfriendlypaint.

•AllunitsarelistedbytheCanadianStandardsAssociationandCRNregisteredheatexchanger.

Model V and VN

➂ Dimensions shown apply to standard 115V/1ph motor (Power Code 01). *Vertical types equipped with cone jet deflector, except V952 which is without deflector.

C

C

DMaleReturn

MaleSupply

V/VN-42 Through V/VN-279

MaleSupply

MaleReturnV/VN-333,V/VN-385,V/VN-500

C

D

V/VN-333 Through V-952

MaleReturnV/VN-610/952

8-MountingHoles5/8"Dia.inAngle

IronBracket4-MountingHoles

1/2"-13Tap

G

A

F

Diameter12"Min.

2-3/4"

OutletFanGuard

DiameterE

B

V/VN-42throughV/VN610,V952

Models V/VN Dimensions - Inches

Male Approx. Model Fan Conn. NPT Shipping Number A B C D E F G Dia. Top Bottom Wt. (lbs.)

V/VN-42 24-3/4 3-5/8 11-3/8 2-1/8 4-3/8 14-1/2 - 14 1-1/4 1-1/4 36 V/VN-59 24-3/4 5-1/8 11-3/8 2-1/8 4-3/8 14-1/2 - 14 1-1/4 1-1/4 42 V/VN-78 24-3/4 6-5/8 11-3/8 2-1/8 2-5/8 16-1/2 - 16 1-1/4 1-1/4 46 V/VN-95 24-3/4 8-1/8 11-3/8 2-1/8 2-5/8 16-1/2 - 16 1-1/4 1-1/4 48 V/VN-139 34-3/4 6-7/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 70 V/VN-161 34-3/4 8-3/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 80 V/VN-193 34-3/4 9-7/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 86 V/VN-212 34-3/4 12-7/8 18-3/8 2-1/2 3 19-1/2 - 19 2 1-1/4 94 V/VN-247 34-3/4 12-7/8 18-3/8 2-1/2 3 21-1/2 - 21 2 1-1/4 108 V/VN-279 34-3/4 14-3/4 18-3/8 2-1/2 3 21-1/2 - 21 2 1-1/4 112 V/VN-333 43-1/4 14-1/2 24 2-7/8 3-1/8 22-1/2 18-1/5 22 2-1/2 1-1/2 166 V/VN-385 43-1/4 14-1/2 24 2-7/8 3-1/2 27-1/2 18-1/5 27 2-1/2 1-1/2 168 V/VN-500 43-1/4 19 24 2-7/8 3-1/2 27-1/2 18-1/5 27 2-1/2 1-1/2 360 V/VN-610 51-1/2 19-1/8 24 — 3-3/4 30-1/2 31-3/8 30 2-1/2 1-1/2 450 V-952 53-3/4 21-1/4 30 — 3-1/2 31 30 30 3 3 487

Performance Data (60°F Entering Air Temperature)

Standard Models Low-Outlet Temperature Models

Steam Hot Water Steam (2# Steam) (200°F In, 180°F Out) (2# Steam)

Heat Heat Final Final Max. Throw @ Final Max. Throw @ ➂ Air Water Air Mtg. Max. Mtg. Air Mtg. Max. Mtg. Motor Temp. Flow Temp. Height Height Temp. Height Height Model Number HP Btu/Hr (°F) Btu/Hr (GPM) (°F) CFM (Ft) (Ft) Model Number Btu/Hr CFM (°F) (Ft) (Ft)

PT/PTN 279 1/2 279,000 111 192,350 20.0 94 5460 17 106 — — — — — — PT/PTN 333 3/4 333,000 116 238,480 24.8 99 5980 18 117 — — — — — — PT/PTN 385 1 385,000 110 276,080 28.8 95 7680 18 122 — — — — — — PT/PTN 500 1-1/2 500,000 108 357,960 37.3 93 10,390 19 138 — — — — — — PT/PTN 610 1-1/2 610,000 112 450,420 46.9 97 11,750 21 149 PT/PTN 610L 470,000 12400 97 22 154 PT 952 2 952,000 139 721,610 75.2 120 12,170 22 154 — — — — — —

POWER-THROWTM HIGH VELOCITY HORIZONTAL AIR DELIVERY MODELS

PT and PTN models feature the following:

•PTmodelshavecoppertubes,PTNmodelshavecopper/nickeltubesforhightemperatureand/orpressureapplications.

•Highcapacitymodelswithpowerful,highvelocityairdelivery.

•Allunitsprovidedwithhorizontalairdeflectorblades.

•Idealforblanketinglargefrequentlyopeneddoorswithheatedair.

•Distributesheatoverawidearea—canoftenreplaceseveralsmallerunits.

•Allunitsincludeanelectricjunctionboxforeasyelectricalconnections.

•Bakedongrey-green,electrostaticallyappliedpolyesterpowdercoat,environmentallyfriendlypaint.

•AllunitsarelistedbytheCanadianStandardsAssociationandCRNregisteredheatexchanger.

Model PT and PTN

➂ Dimensions shown apply to standard 115V/1ph motor (Power Code 01).

©ModineManufacturingCompany2008 LithoinUSA

Commercial Products GroupModineManufacturingCompany1500DeKovenAvenueRacine,Wisconsin53403-2552Phone:1.800.828.4328(HEAT)Fax:1.800.204.6011

Male Approx. Model Fan Conn. NPT Shipping Number A B C D E Diameter Top Bottom Wt. (lbs.) PT/PTN 279 34-3/4 22-5/8 25-1/4 16-3/4 16-3/4 21 2 1-1/4 122 PT/PTN 333 43-1/4 23-7/8 30 15-3/4 14-3/8 22 2-1/2 1-1/2 176 PT/PTN 385 43-1/4 25-3/4 30 15-3/4 14-3/8 27 2-1/2 1-1/2 184 PT/PTN 500 43-1/4 29 30 20-1/4 14-3/8 27 2-1/2 1-1/2 376 PT/PTN 610 51-1/2 29-5/8 30 20-3/8 21 30 2-1/2 1-1/2 472 PT 952 53-3/4 29-5/8 30 23-1/8 26-7/8 30 3 3 487

Dimensions - Inches

Performance Data (60°F Entering Air Temperature)

TopView