2009 Catalogue

Page 2: Shaw Flex Catalogue

NOTE: The information in this catalog is a guide to assist with product selection. ShawFlex makes no warranties as to the suitability of a product chosen for a particular use. Specifications are subject to change. Please contact ShawFlex for accurate specifications.

Our liability is stated in our standard terms and conditions of sale. The users of these products must make their own evaluation to determine the suitability of the product for its intended application.

Page 3: Shaw Flex Catalogue

Phone: 1 800-668-4842 email: [email protected]

About ShawFlex

More than four decades of experience in designing and manufacturing complex cable configurations has equipped ShawFlex to tackle virtually any application.

ShawFlex is a world-class manufacturer of instrumentation, thermocouple, control, power, marine and robotics cables, with products sold throughout North America, Europe, Asia and the Middle East.

ShawFlex products are used in the petrochemical, power generation, pulp and paper, primary metals, automation, robotics and automotive industries.

ShawFlex excels as a niche specification-based supplier, by developing and manufacturing innovative new wire and cable products. In-house research and development resources and ShawFlex’s track record as a best-in-class supplier of wire and cable products support these initiatives.

Why ShawFlex?

ShawFlex’s reputation for excellence has come from meeting the demanding performance needs of industrial control and instrument applications.

At ShawFlex choosing a cable means more than just selecting products from a catalogue.

ShawFlex works with you by responding to technical problems with innovative solutions

ShawFlex meets your need for dependable products manufactured to your specifications with precision

ShawFlex meets tight deadlines showing the kind of leadership & responsiveness that results in dependable service

For more information on ShawFlex please visit www.shawflex.com

Page 4: Shaw Flex Catalogue

Table of Contents

About ShawFlex .................................................................................................................................................................. .. 1Composite Cables ............................................................................................................................................................... .. 4

Electrical Characteristics CSA Instrumentation & Thermocouple ................................................................................................................................. 6UL Instrumentation & Thermocouple ................................................................................................................................... 7Power & Control ................................................................................................................................................................. .. 8Thermocouple .................................................................................................................................................................... .. 8

CSADesign Standards .................................................................................................................................................................. . 9PVC Insulated Instrumentation: OS (CIC) ........................................................................................................................... 20PVC Insulated Instrumentation: ISOS (CIC) ......................................................................................................................... 21XLPE Insulated Instrumentation: OS (CIC) .......................................................................................................................... 22XLPE Insulated Instrumentation: ISOS (CIC) ....................................................................................................................... 23PVC Insulated Thermocouple: OS (CIC) .............................................................................................................................. 24PVC Insulated Thermocouple: ISOS (CIC) ........................................................................................................................... 25XLPE Insulated Thermocouple: OS (CIC) ............................................................................................................................. 26XLPE Insulated Thermocouple: ISOS (CIC) .......................................................................................................................... 27PVC Insulated Armoured Instrumentation: OS (ACIC) ........................................................................................................ 28PVC Insulated Armoured Instrumentation: ISOS (ACIC) ..................................................................................................... 29XLPE Insulated Armoured Instrumentation: OS (ACIC)....................................................................................................... 30XLPE Insulated Armoured Instrumentation: ISOS (ACIC) .................................................................................................... 31PVC Insulated Armoured Thermocouple: OS (ACIC) ........................................................................................................... 32PVC Insulated Armoured Thermocouple: ISOS (ACIC) ........................................................................................................ 33XLPE Insulated Armoured Thermocouple: OS (ACIC) ......................................................................................................... 34 XLPE Insulated Armoured Thermocouple: ISOS (ACIC) ...................................................................................................... 35PVC Insulated Instrumentation Tray: OS (TC) ................................................................................................................... 36PVC Insulated Instrumentation Tray: ISOS (TC) .................................................................................................................. 37 FR XLPE Insulated Instrumentation Tray: OS (TC) ............................................................................................................. 38 FR XLPE Insulated Instrumentation Tray: ISOS (TC) ........................................................................................................... 39FR PVC Insulated Control Tray (TC) .................................................................................................................................... 40FR XLPE Insulated Power Tray (TC) ..................................................................................................................................... 41FR XLPE Insulated Control Tray (TC) .................................................................................................................................... 42XLPE Insulated Power TECK90 (TECK90) ............................................................................................................................ 43XLPE Insulated Control TECK90 (TECK90) ......................................................................................................................... 44 XLPE Insulated Armoured Control: ARMCON® (ACIC) ....................................................................................................... 45

ULDesign Standards ............................................................................................................................................................... .. 46PVC Insulated Instrumentation: OS (PLTC/ITC) .................................................................................................................. 54PVC Insulated Instrumentation: ISOS (PLTC/ITC) ............................................................................................................... 55XLPE Insulated Instrumentation: OS (PLTC/ITC) ................................................................................................................. 56XLPE Insulated Instrumentation: ISOS (PLTC/ITC) .............................................................................................................. 57PVC Insulated Thermocouple: OS (PLTC/ITC) .................................................................................................................... 58 PVC Insulated Thermocouple: ISOS (PLTC/ITC) .................................................................................................................. 59XLPE Insulated Thermocouple: OS (PLTC/ITC) .................................................................................................................. 60XLPE Insulated Thermocouple: ISOS (PLTC/ITC) ................................................................................................................ 61PVC/Nylon Insulated Instrumentation Tray: OS (TC) ........................................................................................................ 62PVC/Nylon Insulated Instrumentation Tray: ISOS (TC)....................................................................................................... 63XLPE Insulated PVC Jacketed Instrumentation Tray: OS (TC) ............................................................................................. 64 XLPE Insulated PVC Jacketed Instrumentation Tray: ISOS (TC) .......................................................................................... 65XLPE Insulated CPE Jacketed Instrumentation Tray: OS (TC) ............................................................................................. 66 XLPE Insulated CPE Jacketed Instrumentation Tray: ISOS (TC) .......................................................................................... 67XLPE Insulated CSPE Hypalon® Jacketed Instrumentation Tray: OS (TC) ........................................................................... 68

Page 5: Shaw Flex Catalogue

Phone: 1 800-668-4842 email: [email protected]

ULXLPE Insulated CSPE Hypalon® Jacketed Instrumentation Tray: ISOS (TC) ........................................................................ 69PVC/Nylon Insulated Control Tray (TC) .............................................................................................................................. 70PVC/Nylon Insulated Power Tray (TC) ................................................................................................................................ 71XLPE Insulated PVC Jacketed Control Tray (TC) .................................................................................................................. 72 XLPE Insulated PVC Jacketed Power Tray (TC) ................................................................................................................... 73 XLPE Insulated CSPE Hypalon® Jacketed Control Tray (TC) ................................................................................................ 74 XLPE Insulated CSPE Hypalon® Jacketed Power Tray (TC).................................................................................................. 75 XLPE Insulated CPE Jacketed Control & Power Tray: 5 mil CU/LC (TC)............................................................................... 76 XLPE Insulated PVC Jacketed Control & Power Tray: 5 mil CU/LC (TC) .............................................................................. 77XLPE Insulated Thermocouple Tray: OS (TC)....................................................................................................................... 78 XLPE Insulated Thermocouple Tray: ISOS (TC) .................................................................................................................... 79 PVC/Nylon Insulated Armoured Instrumentation: OS (MC) .............................................................................................. 80PVC/Nylon Insulated Armoured Instrumentation: ISOS (MC) ........................................................................................... 81 XLPE Insulated Armoured Instrumentation: OS (MC) ........................................................................................................ 82 XLPE Insulated Armoured Instrumentation: OS (MC) ........................................................................................................ 83 PVC/Nylon Insulated Armoured Power & Control (MC) .................................................................................................... 84XLPE Insulated Armoured Power & Control (MC).............................................................................................................. 85

VFDDesign Standards: UL ........................................................................................................................................................ .. 86Design Standards: CSA ...................................................................................................................................................... .. 88Variable Frequency Drive XLPE Insulated Tray (UL TC) ........................................................................................................ 90Variable Frequency Drive XLPE Insulated Tray (CSA TC) ...................................................................................................... 90 Variable Frequency Drive XLPE Insulated Armoured (CSA TECK90) ................................................................................... 91

FlexarDesign Standards ............................................................................................................................................................... .. 92

Marine & ShipboardDesign Standards ............................................................................................................................................................... .. 94T-Flex Unarmoured (IEC) .................................................................................................................................................. .. 96T-Flex Armoured with Sheath (IEC) .................................................................................................................................. .. 97T-Flex Unarmoured (IEEE) ................................................................................................................................................ .. 98T-Flex Armoured with Sheath (IEEE) ................................................................................................................................. .. 99T-Flex Unarmoured (IEC) ................................................................................................................................................. .. 100 T-Flex Armoured with Sheath (IEC) ................................................................................................................................... 101T/N-Flex Unarmoured (IEEE) ............................................................................................................................................. 102 T/N-Flex Armoured with Sheath (IEC) ............................................................................................................................... 103X-Flex Unarmoured (IEEE) ............................................................................................................................................... .. 104X-Flex Armoured with Sheath (IEEE) ................................................................................................................................. 105X-Flex Unarmoured (IEEE) ................................................................................................................................................ . 106X-Flex Armoured with Sheath (IEEE) ................................................................................................................................. 107X-Flex Unarmoured (IEC) .................................................................................................................................................. . 108X-Flex Armoured with Sheath (IEC) ................................................................................................................................... 109X-Flex Unarmoured (IEC) .................................................................................................................................................. . 110X-Flex Armoured with Sheath (IEC) ................................................................................................................................... 111P-Flex Unarmoured (IEEE) ................................................................................................................................................. 112P-Flex Armoured with Sheath (IEEE) ................................................................................................................................. 113

IndexGlossary of Terms ............................................................................................................................................................ .. 114 Part Number Derivation .................................................................................................................................................. .. 122Cable Handling Instructions .............................................................................................................................................. 136

Page 6: Shaw Flex Catalogue

Composite cables are the best way to integrate several cables that run between common destinations.

Combine different cable elements under a common jacket or armour & save on total installed cost through the faster, easier installation of one cost efficient cable. Provide us with the application environment of the overall cable or simply select from any of the options listed here.

Our Customer Service Representatives & Product Engineering group will work with you to combine instrumentation, control, power & electronic cables under a common armour or jacket. Composite cables can be constructed with components supplied by ShawFlex or provided by the customer.

Wire Selection • Bare Copper • Tinned Copper • Solid • Stranded • Flexible Stranded • Extra Flexible Stranded • Thermocouple Extension Alloys • Specialty Wire

Power, Control &Instrumentation Cable

Power & Control Cable

Insulation Options • UL, CSA or ICEA Standard approved materials • Thermoplastic PVC • PVC/Nylon • Thermoplastic PE • TPE (Thermoplastic Elastomer) • XLPE • FR XLPE • Colour Coding • Specified as per temperature rating requirements • New materials constantly being introduced

Composite Cables

Page 7: Shaw Flex Catalogue

Shielding Options• Aluminum/polyester tape with tinned copper drain wire, OS

&/or over each cable subcomponent• Helically applied copper tape• Corrugated longitudinally applied copper tape• Braided Shield - tinned or bare copper, aluminum, bronze• Specialty tapes such as bronze & copper/polyester

Cabling Options• Common lay• Alternating layers reverse lay cabling• Integration of different types of cables such as coaxial, loose

tube fibre optic, or other data or non data cables, whether jacketed or not jacketed

Armouring Options• UL/CSA Aluminum Interlocked Armour• UL/CSA Steel Interlocked Armour• UL/CSA Steel Wire Armour• UL Zetabon® Moisture/Chemical Barrier• Braid Armoured - tinned or bare copper, aluminum , bronze• Combinations of the above

Jacketing Options• UL, CSA or ICEA Standard approved materials• FR PVC• Polyethylene• CPE (Chlorinated Polyethylene)• CSPE (Hypalon®)• TPE (Thermoplastic Elastomer)• LSZH (Low Smoke Zero Hal)• Polyurethane FR• Metre Marking• Colour options available• Specialty engineered PVCs for sunlight resistance, oil

resistance, lower temperature performance, low acid gas & radiation resistance

High Integrity Cable

Umbilical Cable

Mine Shaft Cable

Composite Cables

Page 8: Shaw Flex Catalogue

Elec

tric

alCh

arac

teri

stics

Nominal Capacitance Characteristic Impedance Inductance Conductor Resistance

Unshielded Pairs Shielded Pairs UnshieldedPairs

ShieldedPairs

(mH/1000 m

(mH/1,000 ft

(ohms/1000 m

(ohms/1,000 ftSize C-C C-S C-C C-S

AWG pf/m pf/ft pf/m pf/ft pf/m pf/ft pf/m pf/ft (ohms) (ohms) loop) Loop) loop) loop)

PVC Insulated 150 V

20 102 31 172 53 164 50 307 94 72 46 0.645 0.197 69 21.0

18 100 31 169 52 160 49 300 92 74 47 0.659 0.201 45 13.6

16 110 34 186 57 182 55 340 103 67 41 0.618 0.188 28 8.5

14 121 37 204 62 205 62 383 116 61 37 0.582 0.178 18 5.4

PVC Insulated 300 V

20 90 27 152 46 141 43 264 80 82 53 0.702 0.214 69 21.0

18 91 28 154 47 142 43 266 80 81 53 0.703 0.214 45 13.6

16 100 31 170 52 161 49 301 92 73 46 0.657 0.200 28 8.5

14 111 34 187 57 182 56 340 105 67 41 0.616 0.188 18 5.4

PVC Insulated 600 V

18 84 26 142 43 129 39 241 73 88 58 0.742 0.226 45 13.6

16 93 28 157 48 146 45 273 84 79 51 0.692 0.211 28 8.5

14 103 31 173 53 165 50 309 94 72 45 0.648 0.197 18 5.4

XLPE Insulated 150 V

20 47 14 79 24 76 23 142 43 107 67 0.645 0.197 69 21.0

18 46 14 78 24 74 22 138 41 109 69 0.659 0.201 45 13.6

16 51 15 86 26 84 25 157 47 99 61 0.618 0.188 28 8.5

14 56 17 94 29 94 29 176 54 90 54 0.582 0.178 18 5.4

XLPE Insulated 300 V

20 41 13 70 21 65 20 122 37 121 78 0.702 0.214 69 21.0

18 42 13 71 22 66 20 123 37 120 78 0.703 0.214 45 13.6

16 46 14 78 24 74 23 139 43 108 69 0.657 0.200 28 8.5

14 51 16 86 26 84 26 157 49 98 61 0.616 0.188 18 5.4

XLPE Insulated 600 V

18 39 12 65 20 60 18 112 34 129 85 0.742 0.226 45 13.6

16 43 13 72 22 67 21 125 39 117 76 0.692 0.211 28 8.5

14 47 14 80 24 76 23 142 43 106 67 0.648 0.197 18 5.4

FR XLPE Insulated 150 V

20 55 17 93 28 89 27 166 50 99 62 0.645 0.197 69 21.0

18 54 16 91 28 87 26 163 49 100 64 0.659 0.201 45 13.6

16 60 18 101 31 98 30 183 56 91 56 0.618 0.188 28 8.5

14 65 20 110 34 111 34 208 64 83 50 0.582 0.178 18 5.4

FR XLPE Insulated 300 V

20 49 15 82 25 76 23 142 43 111 72 0.702 0.214 69 21.0

18 49 15 83 25 77 23 144 43 110 72 0.703 0.214 45 13.6

16 54 17 92 28 87 27 163 50 100 63 0.657 0.200 28 8.5

14 60 18 101 31 98 30 183 56 91 56 0.616 0.188 18 5.4

FR XLPE Insulated 600 V

18 45 14 77 23 70 21 131 39 120 79 0.742 0.226 45 13.6

16 50 15 85 26 79 24 148 45 108 70 0.692 0.211 28 8.5

14 55 17 94 29 89 27 166 50 98 62 0.648 0.197 18 5.4

C-C: Conductor to Conductor; C-S: Conductor to Shield

CSA Instrumentation & Thermocouple: Electrical Characteristics

Page 9: Shaw Flex Catalogue

Phone: 1 800-668-4842 7 email: [email protected]

Nominal Capacitance Characteristic Impedance Inductance Conductor Resistance

Unshielded Pairs Shielded Pairs UnshieldedPairs

ShieldedPairs

(mH/1000 m

(mH/1,000 ft

(ohms/1000 m

(ohms/1,000 ftSize C-C C-S C-C C-S

AWG pf/m pf/ft pf/m pf/ft pf/m pf/ft pf/m pf/ft (ohms) (ohms) loop) Loop) loop) loop)

PVC Insulated 300 V

20 112 34 189 58 185 56 346 105 66 41 0.608 0.185 69 21

18 113 34 191 58 187 57 350 107 65 40 0.610 0.186 45 13.6

16 124 38 210 64 211 64 395 120 60 36 0.576 0.176 28 8.5

14 121 37 204 62 205 62 383 117 61 37 0.582 0.177 18 5.4

FR XLPE (VW-1) Insulated 300 V

20 52 16 88 27 83 25 156 48 102 64 0.646 0.197 69 21

18 57 17 97 30 95 29 178 54 92 56 0.610 0.186 45 13.6

16 63 19 106 32 107 33 200 61 84 50 0.576 0.176 28 8.5

14 62 19 104 32 104 32 195 59 86 51 0.582 0.177 18 5.4

FR XLPE (Non VW-1) Insulated 300 V

20 47 14 80 24 76 23 142 43 107 67 0.646 0.197 69 21

18 52 16 88 27 86 26 162 49 96 59 0.610 0.186 45 13.6

16 63 19 106 32 107 33 200 61 84 50 0.576 0.176 28 8.5

14 56 17 94 29 95 29 177 54 90 54 0.582 0.177 18 5.4

PVC/Nylon Insulated 600 V

18 100 31 169 52 161 49 300 91 74 47 0.658 0.201 45 13.6

16 110 34 186 57 182 55 340 104 67 41 0.618 0.188 28 8.5

14 121 37 204 62 205 62 383 117 61 37 0.582 0.177 18 5.4

FR XLPE (VW-1) Insulated 600 V

18 43 13 72 22 66 20 123 37 123 81 0.742 0.226 45 13.6

16 47 14 80 24 74 23 139 42 112 72 0.692 0.211 28 8.5

14 52 16 88 27 84 26 157 48 101 64 0.648 0.198 18 5.4

FR XLPE (Non VW-1) Insulated 600 V

18 39 12 66 20 60 18 112 34 129 85 0.742 0.226 45 13.6

16 43 13 73 22 68 21 126 39 117 75 0.692 0.211 28 8.5

14 47 14 80 24 76 23 143 44 106 67 0.648 0.198 18 5.4

UL Instrumentation & Thermocouple: Electrical Characteristics

ElectricalCharacteristi

cs

Page 10: Shaw Flex Catalogue

Elec

tric

alCh

arac

teri

stics

Power & Control: Conductor ResistanceConductor Size

Maximum DC Conductor Resistance at 20°Cohm/Mft Conductor Size

Maximum DC Conductor Resistance at 20°Cohm/Mft

AWG Bare Tinned AWG Bare Tinned

18 6.66 6.92 4 0.259 0.269

16 4.19 4.35 2 0.163 0.169

14 2.620 2.73 1 0.129 0.134

12 1.650 1.72 1/0 0.102 0.106

10 1.040 1.08 2/0 0.0811 0.0843

8 0.654 0.679 3/0 0.0643 0.0669

6 0.411 0.427 4/0 0.0510 0.0525

Since thermocouple based temperature measuring systems depend upon the unique EMF characteristics of the thermocouple pair alloy combination, it is vital that the correct alloys be used. A quick measurement of the loop resistance & comparison with the following table will confirm that the correct type has been installed.

AWG Size

Nominal DC Loop Resistance (ohms/1,000 ft loop)

EX JX KX NX SX/RX TX

20 710 375 601 780 38 311

18 447 236 378 491 24 196

16 281 148 238 308 15 123

Identification

ANSI Type

Alloy Identification ANSI Colour Codes

Temperature Range* StandardLimits of Error**Positive Wire Negative Wire Positive Wire Negative Wire Outer Jacket

EX Ni Cr Cu Ni Purple Red Purple 0 to 200°C 32 to 392°F ±1.7°C ±3.1°F

JX Fe Cu Ni White Red Black 0 to 200°C 32 to 392°F ±2.2°C ±4.0°F

KX Ni Cr Ni Al Yellow Red Yellow 0 to 200°C 32 to 392°F ±2.2°C ±4.0°F

NX Ni Cr Si Ni Si Orange Red Orange 0 to 200°C 32 to 392°F ±2.2°C ±4.0°F

RX Cu Copper Alloy Black Red Green 0 to 200°C 32 to 392°F ±5.0°C ±9.0°F

SX Cu Copper Alloy Black Red Green 0 to 200°C 32 to 392°F ±5.0°C ±9.0°F

TX Cu Cu Ni Blue Red Blue 0 to 200°C 32 to 392°F ±1.0°C ±1.8°F

KCB Cu Cu Ni Black Red Yelllow 0 to 180°C ±2.2°C

*Temperature range based on 20 AWG (0.5190 mm2) wire **Reference junction at 0°C (32°F)

Thermocouple: Electrical Characteristics

Page 11: Shaw Flex Catalogue

Phone: 1 800-668-4842 9 email: [email protected]

CSA Cables

ShawFlex CSA Cables

Armoured a. Instrumentation b. Control c. Power d. Thermocouple

Unarmoured a. Instrumentation b. Control c. Power d. Thermocouple

Tray a. Instrumentation b. Control c. Power d. Thermocouple

ShawFlex CSA cables have been designed to meet the rigorous requirements established by the Canadian Standards Association. Although CSA cables are primarily used in Canada they can also be found in projects though out the world.

ArmouredShawFlex CSA Armoured cables can be used for any Hazardous Location (HL) application.

ShawFlex CSA Armoured cables are suitable for use in raceways, including ventilated, non-ventilated, and ladder-type cable trays, direct earth burial, indoor/outdoor, for exposed and concealed wiring wet/dry locations.

Available in three distinct options: Aluminum Interlocked Armour (AIA) Galvanized Steel Interlocked Armour (SIA) Galvanized Steel Served Wire Armoured (SWA)

Type cec (table 19) Characteristics

AIA ACIC, TECK90 Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, excellent mechanical protection, cut & crush resistant, corrosion resistant

SIA ACIC, TECK90 Flame Retardant, Sunlight resistant, -40 Rated, Superior mechanical protection, cut & crush resistant

SWA SW-ACIC Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, reduced diameter, flexible, good cut though resistance, vertical applications

UnarmouredShawFlex CSA Unarmoured cables are suitable for use in conduit or concealed wiring in wet/dry locations. Type cec (table 19) Characteristics

CIC CIC Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, reduced diameter, flexible, tight bend radius

TrayShawFlex CSA tray cables can be used for Hazardous Location application as permitted. ShawFlex CSA Tray cables are suitable for use in raceways, including ventilated, non-ventilated and ladder-type cable trays in wet/dry and indoor/outdoor locations.

Type cec (table 19) Characteristics

TC TC Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, reduced diameter, flexible, tight bend radius

Page 12: Shaw Flex Catalogue

CSA

Cab

les

Armoured Cable Available Constructions:

Instrumentation Control Power Thermocouple

Characteristics:

FT4 Flame Retardant a a a aSunlight Resistant a a a aWet Rated a a a a-40 Cold Impact a a a aDirect Burial a a a a

Voltage Ratings:

300V a a - a600V a a a a1000V - a a -

Armouring Options:

Aluminum Interlock armour a a a aSteel Interlock Armour a a a aSteel wire Served Armour a a a a

Jacketing Options:

PVC Jacket - - - -PVC LAG Jacket a a a aLSZH Jacket a a a a

Insulation Options:

PVC Insulation a a - aXLPE Insulation a a a aFR-XLPE Insulation - - - -

Shielding Options:

OS Aluminum Mylar a a a aISOS Aluminum Mylar a - - aHelical Copper a a a aLongitudinal Copper a a a a

Rated

tray - - - -Hl a a a a

Page 13: Shaw Flex Catalogue

Phone: 1 800-668-4842 11 email: [email protected]

CSA Cables

Unarmoured Cable Available Constructions:

Instrumentation Control Power Thermocouple

Characteristics:

FT4 Flame Retardant a a a aSunlight Resistant a a a aWet Rated a a a a-40 Cold Impact a a a aDirect Burial - - - -

Voltage Ratings:

300V a a - a600V a a a a1000V - a a -

Armouring Options:

Aluminum Interlock armour - - - -Steel Interlock Armour - - - -Steel wire Served Armour - - - -

Jacketing Options:

PVC Jacket a a a aPVC LAG Jacket - - - -LSZH Jacket a a a a

Insulation Options:

PVC Insulation a a - aXLPE Insulation - - - -FR-XLPE Insulation a a a a

Shielding Options:

OS Aluminum Mylar a a a aISOS Aluminum Mylar a - - aHelical Copper a a a aLongitudinal Copper a a a a

Rated

tray - - - -Hl - - - -

Page 14: Shaw Flex Catalogue

CSA

Cab

les

Tray Cable Available Constructions:

Instrumentation Control Power Thermocouple

Characteristics:

FT4 Flame Retardant a a a aSunlight Resistant a a a aWet Rated a a a a-40 Cold Impact a a a aDirect Burial a a a a

Voltage Ratings:

300V a a - a600V a a a a1000V - a a -

Armouring Options:

Aluminum Interlock armour - - - -Steel Interlock Armour - - - -Steel wire Served Armour - - - -

Jacketing Options:

PVC Jacket a a a aPVC LAG Jacket - - - -LSZH Jacket a a a a

Insulation Options:

PVC Insulation a a - aXLPE Insulation - - - -FR-XLPE Insulation a a a a

Shielding Options:

OS Aluminum Mylar a a a aISOS Aluminum Mylar a - - aHelical Copper a a a aLongitudinal Copper a a a a

Rated

tray a a a aHl - - - -

Page 15: Shaw Flex Catalogue

Phone: 1 800-668-4842 13 email: [email protected]

CSA Cables

Available in: PVC XLPE

Unarmoured Instrumentation: OSApplications:

Overall shielded instrumentation cable used to convey analogue or digital signals. Cable can be installed in conduit and other raceways, except cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRY

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Available in: PVC XLPE

Unarmoured Instrumentation: ISOSApplications:

Individual and overall shielded instrumentation cable used to convey analogue or digital signals. Used when there is a possibility of crosstalk between pairs/triads. Cable can be installed in conduit and other raceways, except cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRY

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Page 16: Shaw Flex Catalogue

CSA

Cab

les

Applications: Individual and overall shielded thermocouple extension cable used for measurement of temperature when connected to thermocouples. Used when there is a possibility of crosstalk between pairs. Cable can be installed in conduit and other raceways, except cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRY

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Unarmoured Thermocouple: ISOS

Available in: PVC XLPE

Available in: PVC XLPE

Applications: Overall shielded thermocouple extension cable used for measurement of temperature when connected to thermocouples. Cable can be installed in conduit and other raceways, except cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRY

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Unarmoured Thermocouple: OS

Page 17: Shaw Flex Catalogue

Phone: 1 800-668-4842 15 email: [email protected]

CSA Cables

Available in: PVC XLPE

Armoured Instrumentation: OS

Applications: Overall shielded armoured instrumentation cable used to convey analogue or digital signals. Interlocked armour replaces the use of conduit for mechanical protection.Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE ACIC)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYHL RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Armoured Instrumentation: ISOS

Available in: PVC XLPE

Applications: Individual and overall shielded armoured instrumentation cable used to convey analogue or digital signals. Used when there is a possibility of crosstalk between pairs/triads. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE ACIC)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYHL “BCD” RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Page 18: Shaw Flex Catalogue

CSA

Cab

les

Applications: Individual and overall shielded armoured thermocouple extension cable used for measurement of temperature when connected to thermocouples. Used when there is a possibility of crosstalk between pairs. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE ACIC)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYHL RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Armoured Thermocouple: ISOS

Applications: Overall shielded armoured thermocouple extension cable used for measurement of temperature when connected to thermocouples. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE ACIC)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 105OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYHL RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Armoured Thermocouple: OS

Available in: pvc xlpe

Available in: pvc xlpe

Page 19: Shaw Flex Catalogue

Phone: 1 800-668-4842 17 email: [email protected]

CSA Cables

Available in: PVC FR XLPE

Unarmoured Instrumentation Tray: OSApplications:

Overall shielded instrumentation tray cable used to convey analogue or digital signals. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 230 TRAY CABLE (TYPE TC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 75OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2 CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. Also available in thermocouple extension tray cable. Green insulated bonding conductor can be included upon request.

Available in: pvc fr xlpe

Applications:

Individual and overall shielded instrumentation tray cable used to convey analogue or digital signals. Used when there is a possibility of crosstalk between pairs/triads. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 230 TRAY CABLE (TYPE TC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 75OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYTC “BCD” RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2 CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. Also available in thermocouple extension tray cable. Green insulated bonding conductor can be included upon request.

Unarmoured Instrumentation Tray: ISOS

Page 20: Shaw Flex Catalogue

CSA

Cab

les

Available in: fr xlpe

Unarmoured Power Tray

Applications: Unshielded power tray cable is used to supply power for lighting, drives, motors and pumps. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 230 TRAY CABLE (TYPE TC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)XLPE (RW90) RATED - 90OC WET / 105OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2 CLASS II DIVISION 2

Notes:Uninsulated bonding conductor included in every cable.

Available in a dual rated CSA and UL tray cable upon request.

Available in: FR PVC FR XLPE

Applications: Unshielded control tray cable is used for operation of control automation equipment. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE CIC)CSA C22.2 NO. 230 TRAY CABLE (TYPE TC)CSA C22.2 NO. 75 THERMOPLASTIC INSULATED WIRES (PVC)CSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC (TW75) RATED – 75OC WET / 75OC DRYXLPE (RW90) RATED - 90OC WET / 105OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2 CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. Uninsulated bonding conductor is included in every cable.

Available in a dual rated CSA and UL tray cable upon request.

Unarmoured Control Tray

Page 21: Shaw Flex Catalogue

Phone: 1 800-668-4842 19 email: [email protected]

CSA Cables

Armoured PowerApplications:

Unshielded armoured control cable is used for operation of control automation equipment. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 239 CONTROL & INSTRUMENTATION CABLES (TYPE ACIC - ARMCON®)CSA C22.2 NO. 131 TECK 90 CABLE (TYPE TECK 90)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)XLPE (RW90) RATED - 90OC WET / 105OC DRYHL RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:Uninsulated bonding conductor is included in every cable.

Applications: Unshielded armoured power cable is used to supply power for lighting, drives, motors and pumps. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:CSA C22.2 NO. 131 TECK 90 CABLE (TYPE TECK 90)CSA C22.2 NO. 174 CABLES & CABLE GLANDS FOR USE IN HAZARDOUS LOCATIONSCSA C22.2 NO. 38 THERMOSET INSULATED WIRES & CABLES (XLPE)XLPE (RW90) RATED - 90OC WET / 105OC DRYHL RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0, 1 & 2 CLASS II DIVISION 1 & 2

Notes:Uninsulated bonding conductor is included in every cable.

Armoured Control

Available in: Armcon® Teck90

Available in: Teck90

Page 22: Shaw Flex Catalogue

CSA

Cab

les

PVC Insulated Instrumentation: OS (CIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 63021M200110000 1.14 0.045 6.7 0.263 33 49 3.2 80 16 7

2 Pair 20 AWG 300V 63021M200210000 1.14 0.045 9.7 0.382 63 93 4.6 117 32 15

4 Pair 20 AWG 300V 63021M200410000 1.14 0.045 11.1 0.437 85 126 5.2 133 64 29

6 Pair 20 AWG 300V 63021M200610000 1.14 0.045 13.2 0.518 119 177 6.2 158 96 44

8 Pair 20 AWG 300V 63021M200810000 1.52 0.060 15.0 0.589 158 236 7.1 179 128 58

12 Pair 20 AWG 300V 63021M201210000 1.52 0.060 17.9 0.704 218 325 8.5 215 192 87

16 Pair 20 AWG 300V 63021M201610000 1.52 0.060 19.8 0.779 271 403 9.3 237 256 116

24 Pair 20 AWG 300V 63021M202410000 2.03 0.080 25.3 0.995 417 621 11.9 303 384 174

1 Triad 20 AWG 300V 63031M200110000 1.14 0.045 7.0 0.275 39 59 3.3 84 24 11

2 Triad 20 AWG 300V 63031M200210000 1.14 0.045 10.7 0.420 79 118 5.0 128 48 22

4 Triad 20 AWG 300V 63031M200410000 1.14 0.045 12.2 0.482 112 167 5.8 147 96 44

6 Triad 20 AWG 300V 63031M200610000 1.52 0.060 15.4 0.605 174 258 7.3 184 144 65

8 Triad 20 AWG 300V 63031M200810000 1.52 0.060 16.5 0.651 211 315 7.8 198 192 87

12 Triad 20 AWG 300V 63031M201210000 1.52 0.060 19.9 0.782 298 443 9.4 238 288 131

16 Triad 20 AWG 300V 63031M201610000 2.03 0.080 23.1 0.907 402 598 10.9 277 384 174

24 Triad 20 AWG 300V 63031M202410000 2.03 0.080 28.2 1.108 572 851 13.3 338 576 261

1 Pair 18 AWG 300V 63021M180110000 1.14 0.045 7.7 0.303 44 65 3.6 92 26 12

2 Pair 18 AWG 300V 63021M180210000 1.14 0.045 11.5 0.452 86 128 5.4 138 52 24

4 Pair 18 AWG 300V 63021M180410000 1.14 0.045 13.2 0.520 120 178 6.2 159 104 47

6 Pair 18 AWG 300V 63021M180610000 1.52 0.060 16.6 0.653 186 276 7.8 199 156 71

8 Pair 18 AWG 300V 63021M180810000 1.52 0.060 17.9 0.704 227 338 8.4 214 208 94

12 Pair 18 AWG 300V 63021M181210000 2.03 0.080 22.6 0.889 346 515 10.7 271 312 142

16 Pair 18 AWG 300V 63021M181610000 2.03 0.080 25.0 0.982 427 636 11.8 299 416 189

24 Pair 18 AWG 300V 63021M182410000 2.03 0.080 30.6 1.204 610 908 14.4 367 624 283

1 Triad 18 AWG 300V 63031M180110000 1.14 0.045 8.1 0.318 54 80 3.8 97 39 18

2 Triad 18 AWG 300V 63031M180210000 1.14 0.045 12.7 0.499 110 164 6.0 152 78 35

4 Triad 18 AWG 300V 63031M180410000 1.52 0.060 15.4 0.607 176 261 7.3 185 156 71

6 Triad 18 AWG 300V 63031M180610000 1.52 0.060 18.4 0.723 250 371 8.7 220 234 106

8 Triad 18 AWG 300V 63031M180810000 1.52 0.060 19.9 0.782 308 458 9.4 238 312 142

12 Triad 18 AWG 300V 63031M181210000 2.03 0.080 25.1 0.987 468 697 11.8 301 468 212

16 Triad 18 AWG 300V 63031M181610000 2.03 0.080 27.8 1.093 588 875 13.1 333 624 283

24 Triad 18 AWG 300V 63031M182410000 2.03 0.080 34.2 1.346 847 1,261 16.1 410 936 425

1 Pair 16 AWG 300V 63021M160110000 1.14 0.045 8.3 0.327 55 82 3.9 100 41 19

2 Pair 16 AWG 300V 63021M160210000 1.14 0.045 12.5 0.494 107 159 5.9 151 82 37

4 Pair 16 AWG 300V 63021M160410000 1.52 0.060 15.3 0.600 170 252 7.2 183 165 75

6 Pair 16 AWG 300V 63021M160610000 1.52 0.060 18.2 0.715 241 358 8.6 218 247 112

8 Pair 16 AWG 300V 63021M160810000 1.52 0.060 19.6 0.773 296 441 9.3 235 330 150

12 Pair 16 AWG 300V 63021M161210000 2.03 0.080 24.8 0.975 451 670 11.7 297 494 224

16 Pair 16 AWG 300V 63021M161610000 2.03 0.080 27.5 1.081 564 840 13.0 329 659 299

24 Pair 16 AWG 300V 63021M162410000 2.03 0.080 33.8 1.329 813 1,209 16.0 405 989 449

1 Triad 16 AWG 300V 63031M160110000 1.14 0.045 8.7 0.344 69 103 4.1 105 62 28

2 Triad 16 AWG 300V 63031M160210000 1.52 0.060 14.7 0.577 155 231 6.9 176 124 56

4 Triad 16 AWG 300V 63031M160410000 1.52 0.060 16.9 0.664 228 340 8.0 202 247 112

6 Triad 16 AWG 300V 63031M160610000 1.52 0.060 20.2 0.795 328 487 9.5 242 371 168

8 Triad 16 AWG 300V 63031M160810000 2.03 0.080 22.9 0.901 440 655 10.8 274 494 224

12 Triad 16 AWG 300V 63031M161210000 2.03 0.080 27.6 1.086 623 927 13.0 331 742 336

16 Triad 16 AWG 300V 63031M161610000 2.03 0.080 30.6 1.206 786 1,170 14.5 368 989 449

24 Triad 16 AWG 300V 63031M162410000 2.03 0.080 37.8 1.489 1,142 1,699 17.9 454 1,483 673

Page 23: Shaw Flex Catalogue

Phone: 1 800-668-4842 21 email: [email protected]

CSA Cables

PVC Insulated Instrumentation: ISOS (CIC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 63022M200210000 1.14 0.045 10.2 0.401 70 104 4.8 122 32 15

4 Pair 20 AWG 300V 63022M200410000 1.14 0.045 11.7 0.459 99 148 5.5 140 64 29

6 Pair 20 AWG 300V 63022M200610000 1.52 0.060 14.6 0.576 154 229 6.9 175 96 44

8 Pair 20 AWG 300V 63022M200810000 1.52 0.060 15.7 0.619 186 277 7.4 189 128 58

12 Pair 20 AWG 300V 63022M201210000 1.52 0.060 18.9 0.742 257 383 8.9 226 192 87

16 Pair 20 AWG 300V 63022M201610000 1.52 0.060 20.9 0.822 322 479 9.9 251 256 116

24 Pair 20 AWG 300V 63022M202410000 2.03 0.080 26.7 1.050 496 738 12.6 320 384 174

2 Triad 20 AWG 300V 63032M200210000 1.14 0.045 11.3 0.443 89 133 5.3 135 48 22

4 Triad 20 AWG 300V 63032M200410000 1.14 0.045 12.9 0.510 127 189 6.1 155 96 44

6 Triad 20 AWG 300V 63032M200610000 1.52 0.060 16.2 0.639 195 290 7.7 195 144 65

8 Triad 20 AWG 300V 63032M200810000 1.52 0.060 17.5 0.689 240 357 8.3 210 192 87

12 Triad 20 AWG 300V 63032M201210000 1.52 0.060 21.1 0.830 338 503 10.0 253 288 131

16 Triad 20 AWG 300V 63032M201610000 2.03 0.080 24.4 0.962 456 678 11.5 293 384 174

24 Triad 20 AWG 300V 63032M202410000 2.03 0.080 29.9 1.177 654 973 14.1 359 576 261

2 Pair 18 AWG 300V 63022M180210000 1.14 0.045 12.0 0.473 97 144 5.7 144 52 24

4 Pair 18 AWG 300V 63022M180410000 1.52 0.060 14.6 0.575 154 229 6.9 175 104 47

6 Pair 18 AWG 300V 63022M180610000 1.52 0.060 17.4 0.684 216 322 8.2 208 156 71

8 Pair 18 AWG 300V 63022M180810000 1.52 0.060 18.8 0.738 266 395 8.9 225 208 94

12 Pair 18 AWG 300V 63022M181210000 2.03 0.080 23.7 0.932 406 604 11.2 284 312 142

16 Pair 18 AWG 300V 63022M181610000 2.03 0.080 26.2 1.031 505 751 12.4 314 416 189

24 Pair 18 AWG 300V 63022M182410000 2.03 0.080 32.2 1.266 724 1,077 15.2 386 624 283

2 Triad 18 AWG 300V 63032M180210000 1.14 0.045 13.4 0.526 124 185 6.3 160 78 35

4 Triad 18 AWG 300V 63032M180410000 1.52 0.060 16.2 0.639 198 294 7.7 195 156 71

6 Triad 18 AWG 300V 63032M180610000 1.52 0.060 19.4 0.763 281 419 9.2 233 234 106

8 Triad 18 AWG 300V 63032M180810000 1.52 0.060 21.0 0.825 349 519 9.9 252 312 142

12 Triad 18 AWG 300V 63032M181210000 2.03 0.080 26.5 1.041 533 794 12.5 317 468 212

16 Triad 18 AWG 300V 63032M181610000 2.03 0.080 29.4 1.156 668 994 13.9 352 624 283

24 Triad 18 AWG 300V 63032M182410000 2.03 0.080 36.2 1.425 966 1,437 17.1 434 936 425

2 Pair 16 AWG 300V 63022M160210000 1.14 0.045 13.1 0.516 122 182 6.2 157 82 37

4 Pair 16 AWG 300V 63022M160410000 1.52 0.060 15.9 0.627 198 294 7.5 191 165 75

6 Pair 16 AWG 300V 63022M160610000 1.52 0.060 19.0 0.749 283 422 9.0 228 247 112

8 Pair 16 AWG 300V 63022M160810000 1.52 0.060 20.6 0.809 352 524 9.7 247 330 150

12 Pair 16 AWG 300V 63022M161210000 2.03 0.080 25.9 1.021 533 793 12.3 311 494 224

16 Pair 16 AWG 300V 63022M161610000 2.03 0.080 28.8 1.133 674 1,004 13.6 345 659 299

24 Pair 16 AWG 300V 63022M162410000 2.03 0.080 35.5 1.396 974 1,450 16.8 426 989 449

2 Triad 16 AWG 300V 63032M160210000 1.52 0.060 15.4 0.606 174 259 7.3 185 124 56

4 Triad 16 AWG 300V 63032M160410000 1.52 0.060 17.7 0.699 261 388 8.4 213 247 112

6 Triad 16 AWG 300V 63032M160610000 1.52 0.060 21.3 0.838 374 557 10.1 255 371 168

8 Triad 16 AWG 300V 63032M160810000 2.03 0.080 24.1 0.948 503 748 11.4 289 494 224

12 Triad 16 AWG 300V 63032M161210000 2.03 0.080 29.1 1.145 716 1,066 13.7 349 742 336

16 Triad 16 AWG 300V 63032M161610000 2.03 0.080 32.3 1.273 905 1,346 15.3 388 989 449

24 Triad 16 AWG 300V 63032M162410000 2.03 0.080 40.0 1.575 1,320 1,964 18.9 480 1,483 673

Page 24: Shaw Flex Catalogue

CSA

Cab

les

XLPE Insulated Instrumentation: OS (CIC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 6B021M200110000 1.14 0.045 6.7 0.263 32 48 3.2 80 16 7

2 Pair 20 AWG 300V 6B021M200210000 1.14 0.045 9.7 0.382 61 91 4.6 117 32 15

4 Pair 20 AWG 300V 6B021M200410000 1.14 0.045 11.1 0.437 82 121 5.2 133 64 29

6 Pair 20 AWG 300V 6B021M200610000 1.14 0.045 13.2 0.518 114 170 6.2 158 96 44

8 Pair 20 AWG 300V 6B021M200810000 1.52 0.060 15.0 0.589 152 226 7.1 179 128 58

12 Pair 20 AWG 300V 6B021M201210000 1.52 0.060 17.9 0.704 209 311 8.5 215 192 87

16 Pair 20 AWG 300V 6B021M201610000 1.52 0.060 19.8 0.779 258 384 9.3 237 256 116

24 Pair 20 AWG 300V 6B021M202410000 2.03 0.080 25.3 0.995 398 592 11.9 303 384 174

1 Triad 20 AWG 300V 6B031M200110000 1.14 0.045 7.0 0.275 38 57 3.3 84 24 11

2 Triad 20 AWG 300V 6B031M200210000 1.14 0.045 10.7 0.420 77 115 5.0 128 48 22

4 Triad 20 AWG 300V 6B031M200410000 1.14 0.045 12.2 0.482 107 160 5.8 147 96 44

6 Triad 20 AWG 300V 6B031M200610000 1.52 0.060 15.4 0.605 167 248 7.3 184 144 65

8 Triad 20 AWG 300V 6B031M200810000 1.52 0.060 16.5 0.651 202 301 7.8 198 192 87

12 Triad 20 AWG 300V 6B031M201210000 1.52 0.060 19.9 0.782 283 422 9.4 238 288 131

16 Triad 20 AWG 300V 6B031M201610000 2.03 0.080 23.1 0.907 383 569 10.9 277 384 174

24 Triad 20 AWG 300V 6B031M202410000 2.03 0.080 28.2 1.108 544 809 13.3 338 576 261

1 Pair 18 AWG 300V 6B021M180110000 1.14 0.045 7.7 0.303 43 64 3.6 92 26 12

2 Pair 18 AWG 300V 6B021M180210000 1.14 0.045 11.5 0.452 84 124 5.4 138 52 24

4 Pair 18 AWG 300V 6B021M180410000 1.14 0.045 13.2 0.520 115 171 6.2 159 104 47

6 Pair 18 AWG 300V 6B021M180610000 1.52 0.060 16.6 0.653 178 265 7.8 199 156 71

8 Pair 18 AWG 300V 6B021M180810000 1.52 0.060 17.9 0.704 217 323 8.4 214 208 94

12 Pair 18 AWG 300V 6B021M181210000 2.03 0.080 22.6 0.889 331 493 10.7 271 312 142

16 Pair 18 AWG 300V 6B021M181610000 2.03 0.080 25.0 0.982 407 606 11.8 299 416 189

24 Pair 18 AWG 300V 6B021M182410000 2.03 0.080 30.6 1.204 580 863 14.4 367 624 283

1 Triad 18 AWG 300V 6B031M180110000 1.14 0.045 8.1 0.318 52 78 3.8 97 39 18

2 Triad 18 AWG 300V 6B031M180210000 1.14 0.045 12.7 0.499 106 158 6.0 152 78 35

4 Triad 18 AWG 300V 6B031M180410000 1.52 0.060 15.4 0.607 168 250 7.3 185 156 71

6 Triad 18 AWG 300V 6B031M180610000 1.52 0.060 18.4 0.723 238 355 8.7 220 234 106

8 Triad 18 AWG 300V 6B031M180810000 1.52 0.060 19.9 0.782 293 436 9.4 238 312 142

12 Triad 18 AWG 300V 6B031M181210000 2.03 0.080 25.1 0.987 446 664 11.8 301 468 212

16 Triad 18 AWG 300V 6B031M181610000 2.03 0.080 27.8 1.093 558 831 13.1 333 624 283

24 Triad 18 AWG 300V 6B031M182410000 2.03 0.080 34.2 1.346 803 1,194 16.1 410 936 425

1 Pair 16 AWG 300V 6B021M160110000 1.14 0.045 8.3 0.327 54 80 3.9 100 41 19

2 Pair 16 AWG 300V 6B021M160210000 1.14 0.045 12.5 0.494 104 155 5.9 151 82 37

4 Pair 16 AWG 300V 6B021M160410000 1.52 0.060 15.3 0.600 164 244 7.2 183 165 75

6 Pair 16 AWG 300V 6B021M160610000 1.52 0.060 18.2 0.715 232 345 8.6 218 247 112

8 Pair 16 AWG 300V 6B021M160810000 1.52 0.060 19.6 0.773 284 423 9.3 235 330 150

12 Pair 16 AWG 300V 6B021M161210000 2.03 0.080 24.8 0.975 433 644 11.7 297 494 224

16 Pair 16 AWG 300V 6B021M161610000 2.03 0.080 27.5 1.081 541 805 13.0 329 659 299

24 Pair 16 AWG 300V 6B021M162410000 2.03 0.080 33.8 1.329 777 1,157 16.0 405 989 449

1 Triad 16 AWG 300V 6B031M160110000 1.14 0.045 8.7 0.344 67 100 4.1 105 62 28

2 Triad 16 AWG 300V 6B031M160210000 1.52 0.060 14.7 0.577 151 225 6.9 176 124 56

4 Triad 16 AWG 300V 6B031M160410000 1.52 0.060 16.9 0.664 220 327 8.0 202 247 112

6 Triad 16 AWG 300V 6B031M160610000 1.52 0.060 20.2 0.795 314 468 9.5 242 371 168

8 Triad 16 AWG 300V 6B031M160810000 2.03 0.080 22.9 0.901 423 629 10.8 274 494 224

12 Triad 16 AWG 300V 6B031M161210000 2.03 0.080 27.6 1.086 597 888 13.0 331 742 336

16 Triad 16 AWG 300V 6B031M161610000 2.03 0.080 30.6 1.206 751 1,117 14.5 368 989 449

24 Triad 16 AWG 300V 6B031M162410000 2.03 0.080 37.8 1.489 1,089 1,621 17.9 454 1,483 673

Page 25: Shaw Flex Catalogue

Phone: 1 800-668-4842 23 email: [email protected]

CSA Cables

XLPE Insulated Instrumentation: ISOS (CIC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 6B022M200210000 1.14 0.045 10.2 0.401 68 102 4.8 122 32 15

4 Pair 20 AWG 300V 6B022M200410000 1.14 0.045 11.7 0.459 96 143 5.5 140 64 29

6 Pair 20 AWG 300V 6B022M200610000 1.52 0.060 14.6 0.576 149 222 6.9 175 96 44

8 Pair 20 AWG 300V 6B022M200810000 1.52 0.060 15.7 0.619 180 267 7.4 189 128 58

12 Pair 20 AWG 300V 6B022M201210000 1.52 0.060 18.9 0.742 248 369 8.9 226 192 87

16 Pair 20 AWG 300V 6B022M201610000 1.52 0.060 20.9 0.822 309 460 9.9 251 256 116

24 Pair 20 AWG 300V 6B022M202410000 2.03 0.080 26.7 1.050 477 710 12.6 320 384 174

2 Triad 20 AWG 300V 6B032M200210000 1.14 0.045 11.3 0.443 87 129 5.3 135 48 22

4 Triad 20 AWG 300V 6B032M200410000 1.14 0.045 12.9 0.510 122 182 6.1 155 96 44

6 Triad 20 AWG 300V 6B032M200610000 1.52 0.060 16.2 0.639 188 280 7.7 195 144 65

8 Triad 20 AWG 300V 6B032M200810000 1.52 0.060 17.5 0.689 230 343 8.3 210 192 87

12 Triad 20 AWG 300V 6B032M201210000 1.52 0.060 21.1 0.830 324 482 10.0 253 288 131

16 Triad 20 AWG 300V 6B032M201610000 2.03 0.080 24.4 0.962 437 650 11.5 293 384 174

24 Triad 20 AWG 300V 6B032M202410000 2.03 0.080 29.9 1.177 625 931 14.1 359 576 261

2 Pair 18 AWG 300V 6B022M180210000 1.14 0.045 12.0 0.473 94 140 5.7 144 52 24

4 Pair 18 AWG 300V 6B022M180410000 1.52 0.060 14.6 0.575 149 222 6.9 175 104 47

6 Pair 18 AWG 300V 6B022M180610000 1.52 0.060 17.4 0.684 209 311 8.2 208 156 71

8 Pair 18 AWG 300V 6B022M180810000 1.52 0.060 18.8 0.738 256 381 8.9 225 208 94

12 Pair 18 AWG 300V 6B022M181210000 2.03 0.080 23.7 0.932 391 582 11.2 284 312 142

16 Pair 18 AWG 300V 6B022M181610000 2.03 0.080 26.2 1.031 485 722 12.4 314 416 189

24 Pair 18 AWG 300V 6B022M182410000 2.03 0.080 32.2 1.266 694 1,033 15.2 386 624 283

2 Triad 18 AWG 300V 6B032M180210000 1.14 0.045 13.4 0.526 120 179 6.3 160 78 35

4 Triad 18 AWG 300V 6B032M180410000 1.52 0.060 16.2 0.639 190 283 7.7 195 156 71

6 Triad 18 AWG 300V 6B032M180610000 1.52 0.060 19.4 0.763 270 402 9.2 233 234 106

8 Triad 18 AWG 300V 6B032M180810000 1.52 0.060 21.0 0.825 334 497 9.9 252 312 142

12 Triad 18 AWG 300V 6B032M181210000 2.03 0.080 26.5 1.041 511 761 12.5 317 468 212

16 Triad 18 AWG 300V 6B032M181610000 2.03 0.080 29.4 1.156 638 950 13.9 352 624 283

24 Triad 18 AWG 300V 6B032M182410000 2.03 0.080 36.2 1.425 921 1,371 17.1 434 936 425

2 Pair 16 AWG 300V 6B022M160210000 1.14 0.045 13.1 0.516 119 178 6.2 157 82 37

4 Pair 16 AWG 300V 6B022M160410000 1.52 0.060 15.9 0.627 192 286 7.5 191 165 75

6 Pair 16 AWG 300V 6B022M160610000 1.52 0.060 19.0 0.749 275 409 9.0 228 247 112

8 Pair 16 AWG 300V 6B022M160810000 1.52 0.060 20.6 0.809 340 506 9.7 247 330 150

12 Pair 16 AWG 300V 6B022M161210000 2.03 0.080 25.9 1.021 515 767 12.3 311 494 224

16 Pair 16 AWG 300V 6B022M161610000 2.03 0.080 28.8 1.133 651 969 13.6 345 659 299

24 Pair 16 AWG 300V 6B022M162410000 2.03 0.080 35.5 1.396 939 1,397 16.8 426 989 449

2 Triad 16 AWG 300V 6B032M160210000 1.52 0.060 15.4 0.606 170 253 7.3 185 124 56

4 Triad 16 AWG 300V 6B032M160410000 1.52 0.060 17.7 0.699 252 375 8.4 213 247 112

6 Triad 16 AWG 300V 6B032M160610000 1.52 0.060 21.3 0.838 361 537 10.1 255 371 168

8 Triad 16 AWG 300V 6B032M160810000 2.03 0.080 24.1 0.948 485 722 11.4 289 494 224

12 Triad 16 AWG 300V 6B032M161210000 2.03 0.080 29.1 1.145 690 1,027 13.7 349 742 336

16 Triad 16 AWG 300V 6B032M161610000 2.03 0.080 32.3 1.273 869 1,294 15.3 388 989 449

24 Triad 16 AWG 300V 6B032M162410000 2.03 0.080 40.0 1.575 1,267 1,885 18.9 480 1,483 673

Page 26: Shaw Flex Catalogue

CSA

Cab

les

PVC Insulated Thermocouple: OS (CIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 73021M200147000 1.14 0.045 6.6 0.259 33 49 3.1 79 16 7

2 Pair 20 AWG 300V 73021M200247000 1.14 0.045 9.4 0.368 61 90 4.4 112 32 15

4 Pair 20 AWG 300V 73021M200447000 1.14 0.045 10.7 0.420 81 120 5.0 128 64 29

8 Pair 20 AWG 300V 73021M200847000 1.14 0.045 13.6 0.536 136 202 6.4 163 128 58

12 Pair 20 AWG 300V 73021M201247000 1.52 0.060 17.2 0.675 205 305 8.1 206 192 87

16 Pair 20 AWG 300V 73021M201647000 1.52 0.060 19.0 0.746 254 378 9.0 227 256 116

24 Pair 20 AWG 300V 73021M202447000 2.03 0.080 24.2 0.954 393 584 11.4 291 384 174

36 Pair 20 AWG 300V 73021M203647000 2.03 0.080 27.5 1.082 537 799 13.0 330 576 261

50 Pair 20 AWG 300V 73021M205047000 2.03 0.080 31.6 1.242 707 1,052 14.9 379 800 363

1 Pair 18 AWG 300V 73021M180147000 1.14 0.045 7.5 0.295 43 64 3.5 90 26 12

2 Pair 18 AWG 300V 73021M180247000 1.14 0.045 11.0 0.431 80 119 5.2 131 52 24

4 Pair 18 AWG 300V 73021M180447000 1.14 0.045 12.6 0.495 111 166 5.9 151 104 47

8 Pair 18 AWG 300V 73021M180847000 1.52 0.060 17.0 0.669 210 313 8.0 204 208 94

12 Pair 18 AWG 300V 73021M181247000 1.52 0.060 20.5 0.805 293 436 9.7 245 312 142

16 Pair 18 AWG 300V 73021M181647000 2.03 0.080 23.7 0.933 396 589 11.2 285 416 189

24 Pair 18 AWG 300V 73021M182447000 2.03 0.080 29.0 1.142 562 837 13.7 348 624 283

36 Pair 16 AWG 300V 73021M183647000 2.03 0.080 33.1 1.302 776 1,155 15.6 397 936 425

50 Pair 16 AWG 300V 73021M185047000 2.03 0.080 38.1 1.500 1,036 1,541 18.0 457 1,300 590

1 Pair 16 AWG 300V 73021M160147000 1.14 0.045 8.1 0.317 54 80 3.8 97 41 19

2 Pair 16 AWG 300V 73021M160247000 1.14 0.045 11.9 0.469 100 149 5.6 143 82 37

4 Pair 16 AWG 300V 73021M160447000 1.52 0.060 14.5 0.571 160 238 6.9 174 165 75

8 Pair 16 AWG 300V 73021M160847000 1.52 0.060 18.6 0.732 277 412 8.8 223 330 150

12 Pair 16 AWG 300V 73021M161247000 2.03 0.080 23.5 0.925 422 628 11.1 282 494 224

16 Pair 16 AWG 300V 73021M161647000 2.03 0.080 26.0 1.023 526 782 12.3 312 659 299

24 Pair 16 AWG 300V 73021M162447000 2.03 0.080 31.9 1.256 755 1,123 15.1 383 989 449

36 Pair 16 AWG 300V 73021M163647000 2.03 0.080 36.5 1.435 1,059 1,576 17.2 438 1,483 673

50 Pair 16 AWG 300V 73021M165047000 2.03 0.080 42.1 1.658 1,425 2,121 19.9 505 2,060 934

Page 27: Shaw Flex Catalogue

Phone: 1 800-668-4842 25 email: [email protected]

CSA Cables

PVC Insulated Thermocouple: ISOS (CIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 73022M200247000 1.14 0.045 10.0 0.394 69 103 4.7 120 32 15

4 Pair 20 AWG 300V 73022M200447000 1.14 0.045 11.4 0.450 97 144 5.4 137 64 29

8 Pair 20 AWG 300V 73022M200847000 1.52 0.060 15.4 0.607 182 271 7.3 185 128 58

12 Pair 20 AWG 300V 73022M201247000 1.52 0.060 18.5 0.727 252 375 8.7 222 192 87

16 Pair 20 AWG 300V 73022M201647000 1.52 0.060 20.5 0.805 314 467 9.7 245 256 116

24 Pair 20 AWG 300V 73022M202447000 2.03 0.080 26.1 1.029 483 718 12.3 314 384 174

36 Pair 20 AWG 300V 73022M203647000 2.03 0.080 29.7 1.170 668 994 14.0 357 576 261

50 Pair 20 AWG 300V 73022M205047000 2.03 0.080 34.2 1.345 889 1,322 16.1 410 800 363

2 Pair 18 AWG 300V 73022M180247000 1.14 0.045 11.6 0.458 94 140 5.5 140 52 24

4 Pair 18 AWG 300V 73022M180447000 1.14 0.045 13.4 0.528 135 201 6.3 161 104 47

8 Pair 18 AWG 300V 73022M180847000 1.52 0.060 18.1 0.714 256 381 8.6 218 208 94

12 Pair 18 AWG 300V 73022M181247000 2.03 0.080 22.9 0.902 389 579 10.8 275 312 142

16 Pair 18 AWG 300V 73022M181647000 2.03 0.080 25.3 0.997 483 719 12.0 304 416 189

24 Pair 18 AWG 300V 73022M182447000 2.03 0.080 31.1 1.223 693 1,032 14.7 373 624 283

36 Pair 16 AWG 300V 73022M183647000 2.03 0.080 35.5 1.397 969 1,442 16.8 426 936 425

50 Pair 16 AWG 300V 73022M185047000 2.03 0.080 41.0 1.612 1,299 1,933 19.3 491 1,300 590

2 Pair 16 AWG 300V 73022M160247000 1.14 0.045 12.7 0.498 118 176 6.0 152 82 37

4 Pair 16 AWG 300V 73022M160447000 1.52 0.060 15.4 0.605 191 284 7.3 185 165 75

8 Pair 16 AWG 300V 73022M160847000 1.52 0.060 19.8 0.780 337 502 9.4 238 330 150

12 Pair 16 AWG 300V 73022M161247000 2.03 0.080 25.0 0.984 512 762 11.8 300 494 224

16 Pair 16 AWG 300V 73022M161647000 2.03 0.080 27.7 1.091 646 962 13.1 332 659 299

24 Pair 16 AWG 300V 73022M162447000 2.03 0.080 34.1 1.342 934 1,390 16.1 409 989 449

36 Pair 16 AWG 300V 73022M163647000 2.03 0.080 39.0 1.535 1,319 1,964 18.4 468 1,483 673

50 Pair 16 AWG 300V 73022M165047000 2.79 0.110 46.6 1.835 1,877 2,794 22.0 559 2,060 934

Page 28: Shaw Flex Catalogue

CSA

Cab

les

XLPE Insulated Thermocouple: OS (CIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 7B021M200147000 1.14 0.045 6.6 0.259 32 48 3.1 79 16 7

2 Pair 20 AWG 300V 7B021M200247000 1.14 0.045 9.4 0.368 59 88 4.4 112 32 15

4 Pair 20 AWG 300V 7B021M200447000 1.14 0.045 10.7 0.420 78 116 5.0 128 64 29

8 Pair 20 AWG 300V 7B021M200847000 1.14 0.045 13.6 0.536 131 194 6.4 163 128 58

12 Pair 20 AWG 300V 7B021M201247000 1.52 0.060 17.2 0.675 197 293 8.1 206 192 87

16 Pair 20 AWG 300V 7B021M201647000 1.52 0.060 19.0 0.746 243 361 9.0 227 256 116

24 Pair 20 AWG 300V 7B021M202447000 2.03 0.080 24.2 0.954 376 560 11.4 291 384 174

36 Pair 20 AWG 300V 7B021M203647000 2.03 0.080 27.5 1.082 512 762 13.0 330 576 261

50 Pair 20 AWG 300V 7B021M205047000 2.03 0.080 31.6 1.242 672 1,000 14.9 379 800 363

1 Pair 18 AWG 300V 7B021M180147000 1.14 0.045 7.5 0.295 42 62 3.5 90 26 12

2 Pair 18 AWG 300V 7B021M180247000 1.14 0.045 11.0 0.431 78 116 5.2 131 52 24

4 Pair 18 AWG 300V 7B021M180447000 1.14 0.045 12.6 0.495 107 159 5.9 151 104 47

8 Pair 18 AWG 300V 7B021M180847000 1.52 0.060 17.0 0.669 202 300 8.0 204 208 94

12 Pair 18 AWG 300V 7B021M181247000 1.52 0.060 20.5 0.805 280 417 9.7 245 312 142

16 Pair 18 AWG 300V 7B021M181647000 2.03 0.080 23.7 0.933 379 564 11.2 285 416 189

24 Pair 18 AWG 300V 7B021M182447000 2.03 0.080 29.0 1.142 537 799 13.7 348 624 283

36 Pair 16 AWG 300V 7B021M183647000 2.03 0.080 33.1 1.302 738 1,098 15.6 397 936 425

50 Pair 16 AWG 300V 7B021M185047000 2.03 0.080 38.1 1.500 982 1,462 18.0 457 1,300 590

1 Pair 16 AWG 300V 7B021M160147000 1.14 0.045 8.1 0.317 52 78 3.8 97 41 19

2 Pair 16 AWG 300V 7B021M160247000 1.14 0.045 11.9 0.469 97 145 5.6 143 82 37

4 Pair 16 AWG 300V 7B021M160447000 1.52 0.060 14.5 0.571 155 230 6.9 174 165 75

8 Pair 16 AWG 300V 7B021M160847000 1.52 0.060 18.6 0.732 267 397 8.8 223 330 150

12 Pair 16 AWG 300V 7B021M161247000 2.03 0.080 23.5 0.925 407 606 11.1 282 494 224

16 Pair 16 AWG 300V 7B021M161647000 2.03 0.080 26.0 1.023 506 753 12.3 312 659 299

24 Pair 16 AWG 300V 7B021M162447000 2.03 0.080 31.9 1.256 725 1,079 15.1 383 989 449

36 Pair 16 AWG 300V 7B021M163647000 2.03 0.080 36.5 1.435 1,015 1,510 17.2 438 1,483 673

50 Pair 16 AWG 300V 7B021M165047000 2.03 0.080 42.1 1.658 1,363 2,029 19.9 505 2,060 934

Page 29: Shaw Flex Catalogue

Phone: 1 800-668-4842 27 email: [email protected]

CSA Cables

XLPE Insulated Thermocouple: ISOS (CIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 7B022M200247000 1.14 0.045 10.0 0.394 68 101 4.7 120 32 15

4 Pair 20 AWG 300V 7B022M200447000 1.14 0.045 11.4 0.450 94 140 5.4 137 64 29

8 Pair 20 AWG 300V 7B022M200847000 1.52 0.060 15.4 0.607 177 263 7.3 185 128 58

12 Pair 20 AWG 300V 7B022M201247000 1.52 0.060 18.5 0.727 244 362 8.7 222 192 87

16 Pair 20 AWG 300V 7B022M201647000 1.52 0.060 20.5 0.805 303 451 9.7 245 256 116

24 Pair 20 AWG 300V 7B022M202447000 2.03 0.080 26.1 1.029 466 694 12.3 314 384 174

36 Pair 20 AWG 300V 7B022M203647000 2.03 0.080 29.7 1.170 643 957 14.0 357 576 261

50 Pair 20 AWG 300V 7B022M205047000 2.03 0.080 34.2 1.345 854 1,271 16.1 410 800 363

2 Pair 18 AWG 300V 7B022M180247000 1.14 0.045 11.6 0.458 92 137 5.5 140 52 24

4 Pair 18 AWG 300V 7B022M180447000 1.14 0.045 13.4 0.528 131 194 6.3 161 104 47

8 Pair 18 AWG 300V 7B022M180847000 1.52 0.060 18.1 0.714 247 368 8.6 218 208 94

12 Pair 18 AWG 300V 7B022M181247000 2.03 0.080 22.9 0.902 376 560 10.8 275 312 142

16 Pair 18 AWG 300V 7B022M181647000 2.03 0.080 25.3 0.997 466 694 12.0 304 416 189

24 Pair 18 AWG 300V 7B022M182447000 2.03 0.080 31.1 1.223 668 994 14.7 373 624 283

36 Pair 16 AWG 300V 7B022M183647000 2.03 0.080 35.5 1.397 931 1,385 16.8 426 936 425

50 Pair 16 AWG 300V 7B022M185047000 2.03 0.080 41.0 1.612 1,246 1,854 19.3 491 1,300 590

2 Pair 16 AWG 300V 7B022M160247000 1.14 0.045 12.7 0.498 115 172 6.0 152 82 37

4 Pair 16 AWG 300V 7B022M160447000 1.52 0.060 15.4 0.605 186 276 7.3 185 165 75

8 Pair 16 AWG 300V 7B022M160847000 1.52 0.060 19.8 0.780 327 487 9.4 238 330 150

12 Pair 16 AWG 300V 7B022M161247000 2.03 0.080 25.0 0.984 497 740 11.8 300 494 224

16 Pair 16 AWG 300V 7B022M161647000 2.03 0.080 27.7 1.091 626 932 13.1 332 659 299

24 Pair 16 AWG 300V 7B022M162447000 2.03 0.080 34.1 1.342 904 1,346 16.1 409 989 449

36 Pair 16 AWG 300V 7B022M163647000 2.03 0.080 39.0 1.535 1,275 1,897 18.4 468 1,483 673

50 Pair 16 AWG 300V 7B022M165047000 2.79 0.110 46.6 1.835 1,815 2,701 22.0 559 2,060 934

Page 30: Shaw Flex Catalogue

CSA

Cab

les

PVC Insulated Armoured Instrumentation: OS (ACIC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 63221M200118700 1.27 0.050 14.9 0.587 141 209 7.0 179 16 7

2 Pair 20 AWG 300V 63221M200218700 1.27 0.050 17.9 0.706 199 297 8.5 215 32 15

4 Pair 20 AWG 300V 63221M200418700 1.27 0.050 19.3 0.761 235 350 9.1 232 64 29

6 Pair 20 AWG 300V 63221M200618700 1.27 0.050 21.4 0.842 289 430 10.1 257 96 44

8 Pair 20 AWG 300V 63221M200818700 1.27 0.050 23.2 0.913 347 517 11.0 278 128 58

12 Pair 20 AWG 300V 63221M201218700 1.27 0.050 26.1 1.028 436 649 12.3 313 192 87

16 Pair 20 AWG 300V 63221M201618700 1.27 0.050 28.0 1.103 552 821 13.2 336 256 116

24 Pair 20 AWG 300V 63221M202418700 1.27 0.050 34.1 1.343 775 1,153 16.1 409 384 174

1 Triad 20 AWG 300V 63231M200118700 1.27 0.050 15.2 0.599 150 223 7.2 182 24 11

2 Triad 20 AWG 300V 63231M200218700 1.27 0.050 18.9 0.744 225 335 8.9 227 48 22

4 Triad 20 AWG 300V 63231M200418700 1.27 0.050 20.5 0.806 274 407 9.7 246 96 44

6 Triad 20 AWG 300V 63231M200618700 1.27 0.050 23.6 0.929 367 546 11.1 283 144 65

8 Triad 20 AWG 300V 63231M200818700 1.27 0.050 24.8 0.975 416 619 11.7 297 192 87

12 Triad 20 AWG 300V 63231M201218700 1.27 0.050 28.6 1.126 584 870 13.5 343 288 131

16 Triad 20 AWG 300V 63231M201618700 1.27 0.050 31.8 1.251 728 1,084 15.0 381 384 174

24 Triad 20 AWG 300V 63231M202418700 1.27 0.050 37.0 1.457 966 1,438 17.5 444 576 261

1 Pair 18 AWG 300V 63221M180118700 1.27 0.050 15.9 0.627 162 240 7.5 191 26 12

2 Pair 18 AWG 300V 63221M180218700 1.27 0.050 19.7 0.776 240 357 9.3 237 52 24

4 Pair 18 AWG 300V 63221M180418700 1.27 0.050 21.4 0.844 291 433 10.1 257 104 47

6 Pair 18 AWG 300V 63221M180618700 1.27 0.050 24.8 0.977 390 581 11.7 298 156 71

8 Pair 18 AWG 300V 63221M180818700 1.27 0.050 26.1 1.028 445 662 12.3 313 208 94

12 Pair 18 AWG 300V 63221M181218700 1.27 0.050 31.3 1.233 666 992 14.8 376 312 142

16 Pair 18 AWG 300V 63221M181618700 1.27 0.050 33.8 1.330 781 1,163 16.0 405 416 189

24 Pair 18 AWG 300V 63221M182418700 1.27 0.050 39.4 1.552 1,033 1,537 18.6 473 624 283

1 Triad 18 AWG 300V 63231M180118700 1.27 0.050 16.3 0.641 175 261 7.7 196 39 18

2 Triad 18 AWG 300V 63231M180218700 1.27 0.050 20.9 0.823 276 410 9.9 251 78 35

4 Triad 18 AWG 300V 63231M180418700 1.27 0.050 23.6 0.931 369 549 11.2 284 156 71

6 Triad 18 AWG 300V 63231M180618700 1.27 0.050 26.6 1.047 472 703 12.6 319 234 106

8 Triad 18 AWG 300V 63231M180818700 1.27 0.050 28.6 1.126 594 885 13.5 343 312 142

12 Triad 18 AWG 300V 63231M181218700 1.27 0.050 33.9 1.334 824 1,227 16.0 407 468 212

16 Triad 18 AWG 300V 63231M181618700 1.27 0.050 36.6 1.441 978 1,455 17.3 439 624 283

24 Triad 18 AWG 300V 63231M182418700 1.52 0.060 43.5 1.714 1,348 2,006 20.6 522 936 425

1 Pair 16 AWG 300V 63221M160118700 1.27 0.050 16.5 0.651 179 266 7.8 198 41 19

2 Pair 16 AWG 300V 63221M160218700 1.27 0.050 20.8 0.818 271 403 9.8 249 82 37

4 Pair 16 AWG 300V 63221M160418700 1.27 0.050 23.5 0.924 361 537 11.1 282 165 75

6 Pair 16 AWG 300V 63221M160618700 1.27 0.050 26.4 1.039 461 686 12.5 317 247 112

8 Pair 16 AWG 300V 63221M160818700 1.27 0.050 27.9 1.097 575 856 13.2 334 330 150

12 Pair 16 AWG 300V 63221M161218700 1.27 0.050 33.6 1.323 802 1,194 15.9 403 494 224

16 Pair 16 AWG 300V 63221M161618700 1.27 0.050 36.3 1.428 949 1,412 17.1 435 659 299

24 Pair 16 AWG 300V 63221M162418700 1.52 0.060 43.1 1.698 1,306 1,944 20.4 517 989 449

1 Triad 16 AWG 300V 63231M160118700 1.27 0.050 17.0 0.667 197 293 8.0 203 62 28

2 Triad 16 AWG 300V 63231M160218700 1.27 0.050 22.9 0.901 341 507 10.8 275 124 56

4 Triad 16 AWG 300V 63231M160418700 1.27 0.050 25.1 0.988 436 649 11.9 301 247 112

6 Triad 16 AWG 300V 63231M160618700 1.27 0.050 28.9 1.139 618 919 13.7 347 371 168

8 Triad 16 AWG 300V 63231M160818700 1.27 0.050 31.6 1.245 765 1,138 14.9 379 494 224

12 Triad 16 AWG 300V 63231M161218700 1.27 0.050 36.4 1.434 1,010 1,503 17.2 437 742 336

16 Triad 16 AWG 300V 63231M161618700 1.27 0.050 39.5 1.554 1,211 1,802 18.6 474 989 449

24 Triad 16 AWG 300V 63231M162418700 1.52 0.060 47.2 1.857 1,691 2,516 22.3 566 1,483 673

Page 31: Shaw Flex Catalogue

Phone: 1 800-668-4842 29 email: [email protected]

CSA Cables

PVC Insulated Armoured Instrumentation: ISOS (ACIC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 63222M200218700 1.27 0.050 18.4 0.725 211 314 8.7 221 32 15

4 Pair 20 AWG 300V 63222M200418700 1.27 0.050 19.9 0.783 255 379 9.4 239 64 29

6 Pair 20 AWG 300V 63222M200618700 1.27 0.050 22.9 0.900 339 505 10.8 274 96 44

8 Pair 20 AWG 300V 63222M200818700 1.27 0.050 24.0 0.943 382 569 11.3 287 128 58

12 Pair 20 AWG 300V 63222M201218700 1.27 0.050 27.1 1.066 484 721 12.8 325 192 87

16 Pair 20 AWG 300V 63222M201618700 1.27 0.050 29.6 1.166 620 922 14.0 355 256 116

24 Pair 20 AWG 300V 63222M202418700 1.27 0.050 35.5 1.399 871 1,296 16.8 426 384 174

2 Triad 20 AWG 300V 63232M200218700 1.27 0.050 19.5 0.767 241 358 9.2 234 48 22

4 Triad 20 AWG 300V 63232M200418700 1.27 0.050 21.2 0.833 295 439 10.0 254 96 44

6 Triad 20 AWG 300V 63232M200618700 1.27 0.050 24.5 0.963 396 590 11.6 294 144 65

8 Triad 20 AWG 300V 63232M200818700 1.27 0.050 25.7 1.013 454 676 12.2 309 192 87

12 Triad 20 AWG 300V 63232M201218700 1.27 0.050 29.8 1.174 638 950 14.1 358 288 131

16 Triad 20 AWG 300V 63232M201618700 1.27 0.050 33.3 1.309 804 1,196 15.7 399 384 174

24 Triad 20 AWG 300V 63232M202418700 1.27 0.050 38.8 1.526 1,069 1,590 18.3 465 576 261

2 Pair 18 AWG 300V 63222M180218700 1.27 0.050 20.2 0.797 255 380 9.6 243 52 24

4 Pair 18 AWG 300V 63222M180418700 1.27 0.050 22.8 0.899 339 505 10.8 274 104 47

6 Pair 18 AWG 300V 63222M180618700 1.27 0.050 25.6 1.008 429 638 12.1 307 156 71

8 Pair 18 AWG 300V 63222M180818700 1.27 0.050 27.0 1.062 492 732 12.7 324 208 94

12 Pair 18 AWG 300V 63222M181218700 1.27 0.050 32.4 1.276 739 1,100 15.3 389 312 142

16 Pair 18 AWG 300V 63222M181618700 1.27 0.050 35.0 1.379 874 1,300 16.5 420 416 189

24 Pair 18 AWG 300V 63222M182418700 1.27 0.050 41.0 1.615 1,165 1,734 19.4 492 624 283

2 Triad 18 AWG 300V 63232M180218700 1.27 0.050 21.6 0.850 296 440 10.2 259 78 35

4 Triad 18 AWG 300V 63232M180418700 1.27 0.050 24.4 0.963 399 594 11.6 293 156 71

6 Triad 18 AWG 300V 63232M180618700 1.27 0.050 27.6 1.087 514 765 13.0 331 234 106

8 Triad 18 AWG 300V 63232M180818700 1.27 0.050 29.7 1.169 648 965 14.0 356 312 142

12 Triad 18 AWG 300V 63232M181218700 1.27 0.050 35.3 1.390 906 1,348 16.7 424 468 212

16 Triad 18 AWG 300V 63232M181618700 1.27 0.050 38.2 1.503 1,076 1,602 18.0 458 624 283

24 Triad 18 AWG 300V 63232M182418700 1.52 0.060 45.5 1.793 1,492 2,220 21.5 547 936 425

2 Pair 16 AWG 300V 63222M160218700 1.27 0.050 21.3 0.840 292 434 10.1 256 82 37

4 Pair 16 AWG 300V 63222M160418700 1.27 0.050 24.2 0.951 396 589 11.4 290 165 75

6 Pair 16 AWG 300V 63222M160618700 1.27 0.050 27.2 1.073 512 762 12.9 327 247 112

8 Pair 16 AWG 300V 63222M160818700 1.27 0.050 29.3 1.153 646 961 13.8 351 330 150

12 Pair 16 AWG 300V 63222M161218700 1.27 0.050 34.8 1.369 899 1,337 16.4 417 494 224

16 Pair 16 AWG 300V 63222M161618700 1.27 0.050 37.6 1.481 1,075 1,599 17.8 451 659 299

24 Pair 16 AWG 300V 63222M162418700 1.52 0.060 44.8 1.764 1,489 2,216 21.2 538 989 449

2 Triad 16 AWG 300V 63232M160218700 1.27 0.050 23.6 0.930 367 546 11.2 283 124 56

4 Triad 16 AWG 300V 63232M160418700 1.27 0.050 26.0 1.022 477 710 12.3 312 247 112

6 Triad 16 AWG 300V 63232M160618700 1.27 0.050 30.0 1.182 677 1,007 14.2 360 371 168

8 Triad 16 AWG 300V 63232M160818700 1.27 0.050 32.9 1.295 846 1,259 15.5 395 494 224

12 Triad 16 AWG 300V 63232M161218700 1.27 0.050 37.9 1.493 1,121 1,668 17.9 455 742 336

16 Triad 16 AWG 300V 63232M161618700 1.27 0.050 41.2 1.621 1,350 2,008 19.5 494 989 449

24 Triad 16 AWG 300V 63232M162418700 1.52 0.060 51.0 2.008 1,984 2,952 24.1 612 1,483 673

Page 32: Shaw Flex Catalogue

CSA

Cab

les

XLPE Insulated Armoured Instrumentation: OS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 64221M200118700 1.27 0.050 14.9 0.587 139 207 7.0 179 16 7

2 Pair 20 AWG 300V 64221M200218700 1.27 0.050 17.9 0.706 196 292 8.5 215 32 15

4 Pair 20 AWG 300V 64221M200418700 1.27 0.050 19.3 0.761 229 341 9.1 232 64 29

6 Pair 20 AWG 300V 64221M200618700 1.27 0.050 21.4 0.842 280 417 10.1 257 96 44

8 Pair 20 AWG 300V 64221M200818700 1.27 0.050 23.2 0.913 335 499 11.0 278 128 58

12 Pair 20 AWG 300V 64221M201218700 1.27 0.050 26.1 1.028 418 623 12.3 313 192 87

16 Pair 20 AWG 300V 64221M201618700 1.27 0.050 28.0 1.103 528 786 13.2 336 256 116

24 Pair 20 AWG 300V 64221M202418700 1.27 0.050 34.1 1.343 739 1,100 16.1 409 384 174

1 Triad 20 AWG 300V 64231M200118700 1.27 0.050 15.2 0.599 148 220 7.2 182 24 11

2 Triad 20 AWG 300V 64231M200218700 1.27 0.050 18.9 0.744 221 329 8.9 227 48 22

4 Triad 20 AWG 300V 64231M200418700 1.27 0.050 20.5 0.806 265 394 9.7 246 96 44

6 Triad 20 AWG 300V 64231M200618700 1.27 0.050 23.6 0.929 353 526 11.1 283 144 65

8 Triad 20 AWG 300V 64231M200818700 1.27 0.050 24.8 0.975 398 593 11.7 297 192 87

12 Triad 20 AWG 300V 64231M201218700 1.27 0.050 28.6 1.126 558 830 13.5 343 288 131

16 Triad 20 AWG 300V 64231M201618700 1.27 0.050 31.8 1.251 693 1,031 15.0 381 384 174

24 Triad 20 AWG 300V 64231M202418700 1.27 0.050 37.0 1.457 913 1,358 17.5 444 576 261

1 Pair 18 AWG 300V 64221M180118700 1.27 0.050 15.9 0.627 159 237 7.5 191 26 12

2 Pair 18 AWG 300V 64221M180218700 1.27 0.050 19.7 0.776 235 350 9.3 237 52 24

4 Pair 18 AWG 300V 64221M180418700 1.27 0.050 21.4 0.844 281 419 10.1 257 104 47

6 Pair 18 AWG 300V 64221M180618700 1.27 0.050 24.8 0.977 376 560 11.7 298 156 71

8 Pair 18 AWG 300V 64221M180818700 1.27 0.050 26.1 1.028 426 634 12.3 313 208 94

12 Pair 18 AWG 300V 64221M181218700 1.27 0.050 31.3 1.233 639 950 14.8 376 312 142

16 Pair 18 AWG 300V 64221M181618700 1.27 0.050 33.8 1.330 744 1,107 16.0 405 416 189

24 Pair 18 AWG 300V 64221M182418700 1.27 0.050 39.4 1.552 977 1,454 18.6 473 624 283

1 Triad 18 AWG 300V 64231M180118700 1.27 0.050 16.3 0.641 172 256 7.7 196 39 18

2 Triad 18 AWG 300V 64231M180218700 1.27 0.050 20.9 0.823 269 400 9.9 251 78 35

4 Triad 18 AWG 300V 64231M180418700 1.27 0.050 23.6 0.931 355 529 11.2 284 156 71

6 Triad 18 AWG 300V 64231M180618700 1.27 0.050 26.6 1.047 451 672 12.6 319 234 106

8 Triad 18 AWG 300V 64231M180818700 1.27 0.050 28.6 1.126 566 843 13.5 343 312 142

12 Triad 18 AWG 300V 64231M181218700 1.27 0.050 33.9 1.334 782 1,164 16.0 407 468 212

16 Triad 18 AWG 300V 64231M181618700 1.27 0.050 36.6 1.441 922 1,372 17.3 439 624 283

24 Triad 18 AWG 300V 64231M182418700 1.52 0.060 43.5 1.714 1,264 1,881 20.6 522 936 425

1 Pair 16 AWG 300V 64221M160118700 1.27 0.050 16.5 0.651 176 262 7.8 198 41 19

2 Pair 16 AWG 300V 64221M160218700 1.27 0.050 20.8 0.818 265 395 9.8 249 82 37

4 Pair 16 AWG 300V 64221M160418700 1.27 0.050 23.5 0.924 350 521 11.1 282 165 75

6 Pair 16 AWG 300V 64221M160618700 1.27 0.050 26.4 1.039 444 661 12.5 317 247 112

8 Pair 16 AWG 300V 64221M160818700 1.27 0.050 27.9 1.097 553 824 13.2 334 330 150

12 Pair 16 AWG 300V 64221M161218700 1.27 0.050 33.6 1.323 769 1,144 15.9 403 494 224

16 Pair 16 AWG 300V 64221M161618700 1.27 0.050 36.3 1.428 905 1,347 17.1 435 659 299

24 Pair 16 AWG 300V 64221M162418700 1.52 0.060 43.1 1.698 1,240 1,846 20.4 517 989 449

1 Triad 16 AWG 300V 64231M160118700 1.27 0.050 17.0 0.667 193 287 8.0 203 62 28

2 Triad 16 AWG 300V 64231M160218700 1.27 0.050 22.9 0.901 333 495 10.8 275 124 56

4 Triad 16 AWG 300V 64231M160418700 1.27 0.050 25.1 0.988 420 624 11.9 301 247 112

6 Triad 16 AWG 300V 64231M160618700 1.27 0.050 28.9 1.139 593 882 13.7 347 371 168

8 Triad 16 AWG 300V 64231M160818700 1.27 0.050 31.6 1.245 732 1,089 14.9 379 494 224

12 Triad 16 AWG 300V 64231M161218700 1.27 0.050 36.4 1.434 960 1,429 17.2 437 742 336

16 Triad 16 AWG 300V 64231M161618700 1.27 0.050 39.5 1.554 1,144 1,703 18.6 474 989 449

24 Triad 16 AWG 300V 64231M162418700 1.52 0.060 47.2 1.857 1,591 2,368 22.3 566 1,483 673

Page 33: Shaw Flex Catalogue

Phone: 1 800-668-4842 31 email: [email protected]

CSA Cables

XLPE Insulated Armoured Instrumentation: ISOS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 64222M200218700 1.27 0.050 18.4 0.725 208 310 8.7 221 32 15

4 Pair 20 AWG 300V 64222M200418700 1.27 0.050 19.9 0.783 249 370 9.4 239 64 29

6 Pair 20 AWG 300V 64222M200618700 1.27 0.050 22.9 0.900 330 492 10.8 274 96 44

8 Pair 20 AWG 300V 64222M200818700 1.27 0.050 24.0 0.943 370 551 11.3 287 128 58

12 Pair 20 AWG 300V 64222M201218700 1.27 0.050 27.1 1.066 467 694 12.8 325 192 87

16 Pair 20 AWG 300V 64222M201618700 1.27 0.050 29.6 1.166 596 887 14.0 355 256 116

24 Pair 20 AWG 300V 64222M202418700 1.27 0.050 35.5 1.399 835 1,243 16.8 426 384 174

2 Triad 20 AWG 300V 64232M200218700 1.27 0.050 19.5 0.767 236 352 9.2 234 48 22

4 Triad 20 AWG 300V 64232M200418700 1.27 0.050 21.2 0.833 286 426 10.0 254 96 44

6 Triad 20 AWG 300V 64232M200618700 1.27 0.050 24.5 0.963 383 570 11.6 294 144 65

8 Triad 20 AWG 300V 64232M200818700 1.27 0.050 25.7 1.013 436 649 12.2 309 192 87

12 Triad 20 AWG 300V 64232M201218700 1.27 0.050 29.8 1.174 612 910 14.1 358 288 131

16 Triad 20 AWG 300V 64232M201618700 1.27 0.050 33.3 1.309 768 1,143 15.7 399 384 174

24 Triad 20 AWG 300V 64232M202418700 1.27 0.050 38.8 1.526 1,015 1,511 18.3 465 576 261

2 Pair 18 AWG 300V 64222M180218700 1.27 0.050 20.2 0.797 251 373 9.6 243 52 24

4 Pair 18 AWG 300V 64222M180418700 1.27 0.050 22.8 0.899 330 491 10.8 274 104 47

6 Pair 18 AWG 300V 64222M180618700 1.27 0.050 25.6 1.008 415 617 12.1 307 156 71

8 Pair 18 AWG 300V 64222M180818700 1.27 0.050 27.0 1.062 473 704 12.7 324 208 94

12 Pair 18 AWG 300V 64222M181218700 1.27 0.050 32.4 1.276 711 1,059 15.3 389 312 142

16 Pair 18 AWG 300V 64222M181618700 1.27 0.050 35.0 1.379 837 1,245 16.5 420 416 189

24 Pair 18 AWG 300V 64222M182418700 1.27 0.050 41.0 1.615 1,110 1,652 19.4 492 624 283

1 Triad 18 AWG 300V 64231M180118700 1.27 0.050 16.3 0.641 172 256 7.7 196 39 18

2 Triad 18 AWG 300V 64232M180218700 1.27 0.050 21.6 0.850 289 430 10.2 259 78 35

4 Triad 18 AWG 300V 64232M180418700 1.27 0.050 24.4 0.963 385 573 11.6 293 156 71

6 Triad 18 AWG 300V 64232M180618700 1.27 0.050 27.6 1.087 493 733 13.0 331 234 106

8 Triad 18 AWG 300V 64232M180818700 1.27 0.050 29.7 1.169 621 923 14.0 356 312 142

12 Triad 18 AWG 300V 64232M181218700 1.27 0.050 35.3 1.390 864 1,286 16.7 424 468 212

16 Triad 18 AWG 300V 64232M181618700 1.27 0.050 38.2 1.503 1,020 1,519 18.0 458 624 283

24 Triad 18 AWG 300V 64232M182418700 1.52 0.060 45.5 1.793 1,408 2,096 21.5 547 936 425

2 Pair 16 AWG 300V 64222M160218700 1.27 0.050 21.3 0.840 286 426 10.1 256 82 37

4 Pair 16 AWG 300V 64222M160418700 1.27 0.050 24.2 0.951 385 573 11.4 290 165 75

6 Pair 16 AWG 300V 64222M160618700 1.27 0.050 27.2 1.073 495 737 12.9 327 247 112

8 Pair 16 AWG 300V 64222M160818700 1.27 0.050 29.3 1.153 624 928 13.8 351 330 150

12 Pair 16 AWG 300V 64222M161218700 1.27 0.050 34.8 1.369 866 1,288 16.4 417 494 224

16 Pair 16 AWG 300V 64222M161618700 1.27 0.050 37.6 1.481 1,031 1,534 17.8 451 659 299

24 Pair 16 AWG 300V 64222M162418700 1.52 0.060 44.8 1.764 1,423 2,118 21.2 538 989 449

2 Triad 16 AWG 300V 64232M160218700 1.27 0.050 23.6 0.930 358 533 11.2 283 124 56

4 Triad 16 AWG 300V 64232M160418700 1.27 0.050 26.0 1.022 460 685 12.3 312 247 112

6 Triad 16 AWG 300V 64232M160618700 1.27 0.050 30.0 1.182 652 970 14.2 360 371 168

8 Triad 16 AWG 300V 64232M160818700 1.27 0.050 32.9 1.295 813 1,209 15.5 395 494 224

12 Triad 16 AWG 300V 64232M161218700 1.27 0.050 37.9 1.493 1,071 1,594 17.9 455 742 336

16 Triad 16 AWG 300V 64232M161618700 1.27 0.050 41.2 1.621 1,283 1,910 19.5 494 989 449

24 Triad 16 AWG 300V 64232M162418700 1.52 0.060 51.0 2.008 1,884 2,804 24.1 612 1,483 673

Page 34: Shaw Flex Catalogue

CSA

Cab

les

PVC Insulated Armoured Thermocouple: OS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 73221M200147700 1.27 0.050 14.8 0.583 140 208 7.0 178 16 7

2 Pair 20 AWG 300V 73221M200247700 1.27 0.050 17.6 0.692 194 289 8.3 211 32 15

4 Pair 20 AWG 300V 73221M200447700 1.27 0.050 18.9 0.744 227 338 8.9 227 64 29

8 Pair 20 AWG 300V 73221M200847700 1.27 0.050 21.8 0.860 311 462 10.3 262 128 58

12 Pair 20 AWG 300V 73221M201247700 1.27 0.050 25.4 0.999 415 618 12.0 305 192 87

16 Pair 20 AWG 300V 73221M201647700 1.27 0.050 27.2 1.070 482 718 12.8 326 256 116

24 Pair 20 AWG 300V 73221M202447700 1.27 0.050 33.1 1.302 737 1,097 15.6 397 384 174

36 Pair 20 AWG 300V 73221M203647700 1.27 0.050 36.3 1.430 922 1,372 17.2 436 576 261

50 Pair 20 AWG 300V 73221M205047700 1.27 0.050 40.4 1.590 1,142 1,700 19.1 485 800 363

1 Pair 18 AWG 300V 73221M180147700 1.27 0.050 15.7 0.619 158 236 7.4 189 26 12

2 Pair 18 AWG 300V 73221M180247700 1.27 0.050 19.2 0.755 228 340 9.1 230 52 24

4 Pair 18 AWG 300V 73221M180447700 1.27 0.050 20.8 0.819 276 411 9.8 250 104 47

8 Pair 18 AWG 300V 73221M180847700 1.27 0.050 25.2 0.993 419 624 11.9 303 208 94

12 Pair 18 AWG 300V 73221M181247700 1.27 0.050 29.2 1.149 586 872 13.8 350 312 142

16 Pair 18 AWG 300V 73221M181647700 1.27 0.050 32.4 1.277 730 1,086 15.3 389 416 189

24 Pair 18 AWG 300V 73221M182447700 1.27 0.050 37.8 1.490 966 1,437 17.9 454 624 283

36 Pair 16 AWG 300V 73221M183647700 1.52 0.060 42.4 1.670 1,262 1,878 20.0 509 936 425

50 Pair 16 AWG 300V 73221M185047700 1.52 0.060 47.4 1.868 1,588 2,363 22.4 569 1,300 590

1 Pair 16 AWG 300V 73221M160147700 1.27 0.050 16.3 0.641 175 260 7.7 195 41 19

2 Pair 16 AWG 300V 73221M160247700 1.27 0.050 20.2 0.793 258 384 9.5 242 82 37

4 Pair 16 AWG 300V 73221M160447700 1.27 0.050 22.7 0.895 344 512 10.7 273 165 75

8 Pair 16 AWG 300V 73221M160847700 1.27 0.050 26.8 1.056 501 746 12.7 322 330 150

12 Pair 16 AWG 300V 73221M161247700 1.27 0.050 32.2 1.269 753 1,121 15.2 387 494 224

16 Pair 16 AWG 300V 73221M161647700 1.27 0.050 34.8 1.371 892 1,328 16.5 418 659 299

24 Pair 16 AWG 300V 73221M162447700 1.27 0.050 40.7 1.604 1,194 1,776 19.3 489 989 449

36 Pair 16 AWG 300V 73221M163647700 1.52 0.060 45.8 1.803 1,589 2,365 21.6 550 1,483 673

50 Pair 16 AWG 300V 73221M165047700 1.52 0.060 53.1 2.091 2,122 3,157 25.1 637 2,060 934

Page 35: Shaw Flex Catalogue

Phone: 1 800-668-4842 33 email: [email protected]

CSA Cables

PVC Insulated Armoured Thermocouple: ISOS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 73222M200247700 1.27 0.050 18.2 0.718 209 311 8.6 219 32 15

4 Pair 20 AWG 300V 73222M200447700 1.27 0.050 19.7 0.774 250 372 9.3 236 64 29

8 Pair 20 AWG 300V 73222M200847700 1.27 0.050 23.7 0.931 376 559 11.2 284 128 58

12 Pair 20 AWG 300V 73222M201247700 1.27 0.050 26.7 1.051 475 707 12.6 320 192 87

16 Pair 20 AWG 300V 73222M201647700 1.27 0.050 29.2 1.149 607 903 13.8 350 256 116

24 Pair 20 AWG 300V 73222M202447700 1.27 0.050 35.0 1.377 850 1,265 16.5 420 384 174

36 Pair 20 AWG 300V 73222M203647700 1.27 0.050 38.6 1.518 1,080 1,607 18.2 463 576 261

50 Pair 20 AWG 300V 73222M205047700 1.52 0.060 43.5 1.713 1,387 2,064 20.6 522 800 363

2 Pair 18 AWG 300V 73222M180247700 1.27 0.050 19.9 0.782 249 371 9.4 238 52 24

4 Pair 18 AWG 300V 73222M180447700 1.27 0.050 21.6 0.852 307 457 10.2 260 104 47

8 Pair 18 AWG 300V 73222M180847700 1.27 0.050 26.4 1.038 476 708 12.5 316 208 94

12 Pair 18 AWG 300V 73222M181247700 1.27 0.050 31.6 1.246 713 1,061 15.0 380 312 142

16 Pair 18 AWG 300V 73222M181647700 1.27 0.050 34.2 1.345 841 1,252 16.1 410 416 189

24 Pair 18 AWG 300V 73222M182447700 1.27 0.050 39.9 1.571 1,121 1,668 18.9 479 624 283

36 Pair 16 AWG 300V 73222M183647700 1.52 0.060 44.8 1.765 1,485 2,210 21.2 538 936 425

50 Pair 16 AWG 300V 73222M185047700 1.52 0.060 52.0 2.045 1,976 2,941 24.5 623 1,300 590

2 Pair 16 AWG 300V 73222M160247700 1.27 0.050 20.9 0.822 283 421 9.9 251 82 37

4 Pair 16 AWG 300V 73222M160447700 1.27 0.050 23.6 0.929 383 571 11.2 283 165 75

8 Pair 16 AWG 300V 73222M160847700 1.27 0.050 28.5 1.124 622 926 13.5 342 330 150

12 Pair 16 AWG 300V 73222M161247700 1.27 0.050 33.8 1.332 866 1,288 16.0 406 494 224

16 Pair 16 AWG 300V 73222M161647700 1.27 0.050 36.5 1.439 1,033 1,537 17.3 438 659 299

24 Pair 16 AWG 300V 73222M162447700 1.52 0.060 43.4 1.710 1,431 2,129 20.5 521 989 449

36 Pair 16 AWG 300V 73222M163647700 1.52 0.060 48.3 1.903 1,881 2,800 22.8 580 1,483 673

50 Pair 16 AWG 300V 73222M165047700 1.52 0.060 57.6 2.268 2,646 3,937 27.2 691 2,060 934

Page 36: Shaw Flex Catalogue

CSA

Cab

les

XLPE Insulated Armoured Thermocouple: OS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 74221M200147700 1.27 0.050 14.8 0.583 138 206 7.0 178 16 7

2 Pair 20 AWG 300V 74221M200247700 1.27 0.050 18.2 0.718 206 307 8.6 219 32 15

4 Pair 20 AWG 300V 74221M200447700 1.27 0.050 19.7 0.774 245 364 9.3 236 64 29

8 Pair 20 AWG 300V 74221M200847700 1.27 0.050 23.7 0.931 365 543 11.2 284 128 58

12 Pair 20 AWG 300V 74221M201247700 1.27 0.050 26.7 1.051 459 683 12.6 320 192 87

16 Pair 20 AWG 300V 74221M201647700 1.27 0.050 29.2 1.149 586 871 13.8 350 256 116

24 Pair 20 AWG 300V 74221M202447700 1.27 0.050 35.0 1.377 818 1,218 16.5 420 384 174

36 Pair 20 AWG 300V 74221M203647700 1.27 0.050 38.6 1.518 1,032 1,536 18.2 463 576 261

50 Pair 20 AWG 300V 74221M205047700 1.52 0.060 43.5 1.713 1,321 1,966 20.6 522 800 363

1 Pair 18 AWG 300V 74221M200147700 1.27 0.050 15.7 0.619 156 233 7.4 189 26 12

2 Pair 18 AWG 300V 74221M200247700 1.27 0.050 19.9 0.782 245 365 9.4 238 52 24

4 Pair 18 AWG 300V 74221M200447700 1.27 0.050 21.6 0.852 299 445 10.2 260 104 47

8 Pair 18 AWG 300V 74221M200847700 1.27 0.050 26.4 1.038 459 684 12.5 316 208 94

12 Pair 18 AWG 300V 74221M201247700 1.27 0.050 31.6 1.246 688 1,024 15.0 380 312 142

16 Pair 18 AWG 300V 74221M201647700 1.27 0.050 34.2 1.345 809 1,203 16.1 410 416 189

24 Pair 18 AWG 300V 74221M202447700 1.27 0.050 39.9 1.571 1,072 1,596 18.9 479 624 283

36 Pair 16 AWG 300V 74221M203647700 1.52 0.060 44.8 1.765 1,411 2,101 21.2 538 936 425

50 Pair 16 AWG 300V 74221M205047700 1.52 0.060 52.0 2.045 1,874 2,789 24.5 623 1,300 590

1 Pair 16 AWG 300V 74221M160147700 1.27 0.050 16.3 0.641 172 256 7.7 195 41 19

2 Pair 16 AWG 300V 74221M160247700 1.27 0.050 20.9 0.822 278 414 9.9 251 82 37

4 Pair 16 AWG 300V 74221M160447700 1.27 0.050 23.6 0.929 374 556 11.2 283 165 75

8 Pair 16 AWG 300V 74221M160847700 1.27 0.050 28.5 1.124 603 897 13.5 342 330 150

12 Pair 16 AWG 300V 74221M161247700 1.27 0.050 33.8 1.332 837 1,246 16.0 406 494 224

16 Pair 16 AWG 300V 74221M161647700 1.27 0.050 36.5 1.439 995 1,480 17.3 438 659 299

24 Pair 16 AWG 300V 74221M162447700 1.52 0.060 43.4 1.710 1,374 2,044 20.5 521 989 449

36 Pair 16 AWG 300V 74221M163647700 1.52 0.060 48.3 1.903 1,796 2,672 22.8 580 1,483 673

50 Pair 16 AWG 300V 74221M165047700 1.52 0.060 57.6 2.268 2,527 3,760 27.2 691 2,060 934

Page 37: Shaw Flex Catalogue

Phone: 1 800-668-4842 35 email: [email protected]

CSA Cables

XLPE Insulated Armoured Thermocouple: ISOS (ACIC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 74222M200247700 1.27 0.050 18.2 0.718 206 307 8.6 219 32 15

4 Pair 20 AWG 300V 74222M200447700 1.27 0.050 19.7 0.774 245 364 9.3 236 64 29

8 Pair 20 AWG 300V 74222M200847700 1.27 0.050 23.7 0.931 365 543 11.2 284 128 58

12 Pair 20 AWG 300V 74222M201247700 1.27 0.050 26.7 1.051 459 683 12.6 320 192 87

16 Pair 20 AWG 300V 74222M201647700 1.27 0.050 29.2 1.149 586 871 13.8 350 256 116

24 Pair 20 AWG 300V 74222M202447700 1.27 0.050 35.0 1.377 818 1,218 16.5 420 384 174

36 Pair 20 AWG 300V 74222M203647700 1.27 0.050 38.6 1.518 1,032 1,536 18.2 463 576 261

50 Pair 20 AWG 300V 74222M205047700 1.52 0.060 43.5 1.713 1,321 1,966 20.6 522 800 363

2 Pair 18 AWG 300V 74222M180247700 1.27 0.050 19.9 0.782 245 365 9.4 238 52 24

4 Pair 18 AWG 300V 74222M180447700 1.27 0.050 21.6 0.852 299 445 10.2 260 104 47

8 Pair 18 AWG 300V 74222M180847700 1.27 0.050 26.4 1.038 459 684 12.5 316 208 94

12 Pair 18 AWG 300V 74222M181247700 1.27 0.050 31.6 1.246 688 1,024 15.0 380 312 142

16 Pair 18 AWG 300V 74222M181647700 1.27 0.050 34.2 1.345 809 1,203 16.1 410 416 189

24 Pair 18 AWG 300V 74222M182447700 1.27 0.050 39.9 1.571 1,072 1,596 18.9 479 624 283

36 Pair 16 AWG 300V 74222M183647700 1.52 0.060 52.0 2.045 1,874 2,789 24.5 623 1,300 590

50 Pair 16 AWG 300V 74222M185047700 1.27 0.050 16.3 0.641 172 256 7.7 195 41 19

2 Pair 16 AWG 300V 74222M160247700 1.27 0.050 23.6 0.929 374 556 11.2 283 165 75

4 Pair 16 AWG 300V 74222M160447700 1.27 0.050 28.5 1.124 603 897 13.5 342 330 150

8 Pair 16 AWG 300V 74222M160847700 1.27 0.050 33.8 1.332 837 1,246 16.0 406 494 224

12 Pair 16 AWG 300V 74222M161247700 1.27 0.050 36.5 1.439 995 1,480 17.3 438 659 299

16 Pair 16 AWG 300V 74222M161647700 1.52 0.060 43.4 1.710 1,374 2,044 20.5 521 989 449

24 Pair 16 AWG 300V 74222M162447700 1.52 0.060 48.3 1.903 1,796 2,672 22.8 580 1,483 673

36 Pair 16 AWG 300V 74222M163647700 1.52 0.060 57.6 2.268 2,527 3,760 27.2 691 2,060 934

50 Pair 16 AWG 300V 74222M165047700 1.52 0.060 53.1 2.091 2,002 2,980 25.1 637 2,060 934

Page 38: Shaw Flex Catalogue

CSA

Cab

les

PVC Insulated Instrumentation Tray: OS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 43021M200110008 1.14 0.045 7.7 0.303 40 59 3.6 92 16 7

2 Pair 20 AWG 300V 43021M200210008 1.14 0.045 11.5 0.452 80 119 5.4 138 32 15

4 Pair 20 AWG 300V 43021M200410008 1.14 0.045 13.2 0.520 108 160 6.2 159 64 29

6 Pair 20 AWG 300V 43021M200810008 1.52 0.060 17.9 0.704 202 301 8.4 214 128 58

8 Pair 20 AWG 300V 43021M201210008 2.03 0.080 22.6 0.889 309 459 10.7 271 192 87

12 Pair 20 AWG 300V 43021M201610008 2.03 0.080 25.0 0.982 377 562 11.8 299 256 116

16 Pair 20 AWG 300V 43021M202410008 2.03 0.080 30.6 1.204 535 797 14.4 367 384 174

24 Pair 20 AWG 300V 43021M203610008 2.03 0.080 34.9 1.375 734 1,092 16.5 419 576 261

1 Triad 20 AWG 300V 43021M205010008 2.03 0.080 40.3 1.586 973 1,447 19.0 483 800 363

2 Triad 20 AWG 300V 43031M200110008 1.14 0.045 8.1 0.318 48 72 3.8 97 24 11

4 Triad 20 AWG 300V 43031M200210008 1.14 0.045 12.7 0.499 101 150 6.0 152 48 22

6 Triad 20 AWG 300V 43031M200410008 1.52 0.060 15.4 0.607 157 234 7.3 185 96 44

8 Triad 20 AWG 300V 43031M200810008 1.52 0.060 19.9 0.782 271 403 9.4 238 192 87

12 Triad 20 AWG 300V 43031M201210008 2.03 0.080 25.1 0.987 412 614 11.8 301 288 131

16 Triad 20 AWG 300V 43031M201610008 2.03 0.080 27.8 1.093 513 764 13.1 333 384 174

24 Triad 20 AWG 300V 43031M202410008 2.03 0.080 34.2 1.346 735 1,094 16.1 410 576 261

1 Pair 18 AWG 300V 43021M180110008 1.14 0.045 8.2 0.323 48 72 3.9 98 26 12

2 Pair 18 AWG 300V 43021M180210008 1.14 0.045 12.4 0.487 93 139 5.8 148 52 24

4 Pair 18 AWG 300V 43021M180410008 1.52 0.060 15.0 0.592 147 219 7.1 180 104 47

6 Pair 18 AWG 300V 43021M180810008 1.52 0.060 19.3 0.761 251 374 9.1 232 208 94

8 Pair 18 AWG 300V 43021M181210008 2.03 0.080 24.4 0.961 383 570 11.5 293 312 142

12 Pair 18 AWG 300V 43021M181610008 2.03 0.080 27.0 1.064 475 707 12.8 324 416 189

16 Pair 18 AWG 300V 43021M182410008 2.03 0.080 33.2 1.309 676 1,005 15.7 399 624 283

24 Pair 18 AWG 300V 43021M183610008 2.03 0.080 38.0 1.496 940 1,398 18.0 456 936 425

1 Triad 18 AWG 300V 43021M185010008 2.79 0.110 45.5 1.790 1,346 2,004 21.5 545 1,300 590

2 Triad 18 AWG 300V 43031M180110008 1.14 0.045 8.6 0.339 59 88 4.1 103 39 18

4 Triad 18 AWG 300V 43031M180210008 1.52 0.060 14.4 0.568 137 204 6.8 173 78 35

6 Triad 18 AWG 300V 43031M180410008 1.52 0.060 16.6 0.653 195 290 7.8 199 156 71

8 Triad 18 AWG 300V 43031M180810008 2.03 0.080 22.5 0.885 372 553 10.6 270 312 142

12 Triad 18 AWG 300V 43031M181210008 2.03 0.080 27.1 1.067 523 778 12.8 325 468 212

16 Triad 18 AWG 300V 43031M181610008 2.03 0.080 30.1 1.184 653 971 14.2 361 624 283

24 Triad 18 AWG 300V 43031M182410008 2.03 0.080 37.1 1.462 942 1,401 17.5 445 936 425

1 Pair 16 AWG 300V 43021M160110008 1.14 0.045 8.8 0.347 60 89 4.2 106 41 19

2 Pair 16 AWG 300V 43021M160210008 1.14 0.045 13.4 0.529 118 175 6.3 161 82 37

4 Pair 16 AWG 300V 43021M160410008 1.52 0.060 16.3 0.642 185 275 7.7 196 165 75

8 Pair 16 AWG 300V 43021M160810008 1.52 0.060 21.1 0.830 323 480 10.0 253 330 150

12 Pair 16 AWG 300V 43021M161210008 2.03 0.080 26.6 1.048 494 735 12.6 319 494 224

16 Pair 16 AWG 300V 43021M161610008 2.03 0.080 29.5 1.162 615 916 13.9 354 659 299

24 Pair 16 AWG 300V 43021M162410008 2.03 0.080 36.4 1.434 886 1,319 17.2 437 989 449

36 Pair 16 AWG 300V 43021M163610008 2.03 0.080 41.7 1.643 1,244 1,851 19.7 501 1,483 673

1 Triad 16 AWG 300V 43031M160110008 1.14 0.045 9.3 0.365 76 113 4.4 111 62 28

2 Triad 16 AWG 300V 43031M160210008 1.52 0.060 15.6 0.616 169 251 7.4 188 124 56

4 Triad 16 AWG 300V 43031M160410008 1.52 0.060 18.1 0.711 249 371 8.5 217 247 112

8 Triad 16 AWG 300V 43031M160810008 2.03 0.080 24.5 0.964 479 713 11.6 294 494 224

12 Triad 16 AWG 300V 43031M161210008 2.03 0.080 29.6 1.166 680 1,012 14.0 355 742 336

16 Triad 16 AWG 300V 43031M161610008 2.03 0.080 32.9 1.297 857 1,275 15.6 395 989 449

24 Triad 16 AWG 300V 43031M162410008 2.03 0.080 40.8 1.605 1,246 1,854 19.3 489 1,483 673

Page 39: Shaw Flex Catalogue

Phone: 1 800-668-4842 37 email: [email protected]

CSA Cables

PVC Insulated Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 43022M200210008 1.14 0.045 12.0 0.473 88 131 5.7 144 32 15

4 Pair 20 AWG 300V 43022M200410008 1.52 0.060 14.6 0.575 137 203 6.9 175 64 29

8 Pair 20 AWG 300V 43022M200810008 1.52 0.060 18.8 0.738 231 344 8.9 225 128 58

12 Pair 20 AWG 300V 43022M201210008 2.03 0.080 23.7 0.932 354 527 11.2 284 192 87

16 Pair 20 AWG 300V 43022M201610008 2.03 0.080 26.2 1.031 436 648 12.4 314 256 116

24 Pair 20 AWG 300V 43022M202410008 2.03 0.080 32.2 1.266 620 922 15.2 386 384 174

36 Pair 20 AWG 300V 43022M203610008 2.03 0.080 36.8 1.447 858 1,277 17.4 441 576 261

50 Pair 20 AWG 300V 43022M205010008 2.03 0.080 42.5 1.672 1,144 1,702 20.1 510 800 363

2 Triad 20 AWG 300V 43032M200210008 1.14 0.045 13.4 0.526 112 167 6.3 160 48 22

4 Triad 20 AWG 300V 43032M200410008 1.52 0.060 16.2 0.639 174 259 7.7 195 96 44

8 Triad 20 AWG 300V 43032M200810008 1.52 0.060 21.0 0.825 302 450 9.9 252 192 87

12 Triad 20 AWG 300V 43032M201210008 2.03 0.080 26.5 1.041 463 689 12.5 317 288 131

16 Triad 20 AWG 300V 43032M201610008 2.03 0.080 29.4 1.156 574 854 13.9 352 384 174

24 Triad 20 AWG 300V 43032M202410008 2.03 0.080 36.2 1.425 825 1,227 17.1 434 576 261

2 Pair 18 AWG 300V 4B022M180210008 1.14 0.045 12.9 0.509 104 155 6.1 155 52 24

4 Pair 18 AWG 300V 4B022M180410008 1.52 0.060 15.7 0.618 160 238 7.4 188 104 47

8 Pair 18 AWG 300V 4B022M180810008 1.52 0.060 20.3 0.797 277 413 9.6 243 208 94

12 Pair 18 AWG 300V 4B022M181210008 2.03 0.080 25.6 1.006 422 628 12.1 307 312 142

16 Pair 18 AWG 300V 4B022M181610008 2.03 0.080 28.3 1.116 524 780 13.4 340 416 189

24 Pair 18 AWG 300V 4B022M182410008 2.03 0.080 34.9 1.374 752 1,119 16.5 419 624 283

36 Pair 18 AWG 300V 4B022M183610008 2.03 0.080 40.0 1.573 1,045 1,555 18.9 480 936 425

50 Pair 18 AWG 300V 4B022M185010008 2.79 0.110 47.8 1.880 1,497 2,227 22.6 573 1,300 590

2 Triad 18 AWG 300V 4B032M180210008 1.52 0.060 15.1 0.596 147 218 7.2 182 78 35

4 Triad 18 AWG 300V 4B032M180410008 1.52 0.060 17.5 0.687 207 308 8.2 209 156 71

8 Triad 18 AWG 300V 4B032M180810008 2.03 0.080 23.7 0.932 398 592 11.2 284 312 142

12 Triad 18 AWG 300V 4B032M181210008 2.03 0.080 28.6 1.125 561 834 13.5 343 468 212

16 Triad 18 AWG 300V 4B032M181610008 2.03 0.080 31.8 1.250 698 1,038 15.0 381 624 283

24 Triad 18 AWG 300V 4B032M182410008 2.03 0.080 39.3 1.546 1,009 1,501 18.6 471 936 425

2 Pair 16 AWG 300V 4B022M160210008 1.52 0.060 14.8 0.582 146 217 7.0 177 82 37

4 Pair 16 AWG 300V 4B022M160410008 1.52 0.060 17.0 0.670 207 307 8.0 204 165 75

8 Pair 16 AWG 300V 4B022M160810008 2.03 0.080 23.1 0.909 397 591 10.9 277 330 150

12 Pair 16 AWG 300V 4B022M161210008 2.03 0.080 27.8 1.096 558 831 13.2 334 494 224

16 Pair 16 AWG 300V 4B022M161610008 2.03 0.080 30.9 1.217 699 1,040 14.6 371 659 299

24 Pair 16 AWG 300V 4B022M162410008 2.03 0.080 38.2 1.504 1,012 1,506 18.0 458 989 449

36 Pair 16 AWG 300V 4B022M163610008 2.79 0.110 45.3 1.785 1,519 2,260 21.4 544 1,483 673

2 Triad 16 AWG 300V 4B032M160210008 1.52 0.060 16.4 0.646 183 273 7.8 197 124 56

4 Triad 16 AWG 300V 4B032M160410008 1.52 0.060 19.0 0.747 269 400 9.0 228 247 112

8 Triad 16 AWG 300V 4B032M160810008 2.03 0.080 25.8 1.014 518 770 12.2 309 494 224

12 Triad 16 AWG 300V 4B032M161210008 2.03 0.080 31.2 1.229 735 1,094 14.7 375 742 336

16 Triad 16 AWG 300V 4B032M161610008 2.03 0.080 34.7 1.368 929 1,383 16.4 417 989 449

24 Triad 16 AWG 300V 4B032M162410008 2.79 0.110 44.6 1.756 1,443 2,147 21.1 535 1,483 673

Page 40: Shaw Flex Catalogue

CSA

Cab

les

FR XLPE Insulated Instrumentation Tray: OS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 4B021M200110008 1.14 0.045 7.7 0.303 38 57 3.6 92 16 7

2 Pair 20 AWG 300V 4B021M200210008 1.14 0.045 11.5 0.452 77 114 5.4 138 32 15

4 Pair 20 AWG 300V 4B021M200410008 1.14 0.045 13.2 0.520 101 151 6.2 159 64 29

8 Pair 20 AWG 300V 4B021M200810008 1.52 0.060 17.9 0.704 190 283 8.4 214 128 58

12 Pair 20 AWG 300V 4B021M201210008 2.03 0.080 22.6 0.889 290 431 10.7 271 192 87

16 Pair 20 AWG 300V 4B021M201610008 2.03 0.080 25.0 0.982 353 526 11.8 299 256 116

24 Pair 20 AWG 300V 4B021M202410008 2.03 0.080 30.6 1.204 499 742 14.4 367 384 174

36 Pair 20 AWG 300V 4B021M203610008 2.03 0.080 34.9 1.375 679 1,010 16.5 419 576 261

50 Pair 20 AWG 300V 4B021M205010008 2.03 0.080 40.3 1.586 896 1,334 19.0 483 800 363

1 Triad 20 AWG 300V 4B031M200110008 1.14 0.045 8.1 0.318 46 68 3.8 97 24 11

2 Triad 20 AWG 300V 4B031M200210008 1.14 0.045 12.7 0.499 97 144 6.0 152 48 22

4 Triad 20 AWG 300V 4B031M200410008 1.52 0.060 15.4 0.607 148 220 7.3 185 96 44

8 Triad 20 AWG 300V 4B031M200810008 1.52 0.060 19.9 0.782 253 376 9.4 238 192 87

12 Triad 20 AWG 300V 4B031M201210008 2.03 0.080 25.1 0.987 386 574 11.8 301 288 131

16 Triad 20 AWG 300V 4B031M201610008 2.03 0.080 27.8 1.093 477 710 13.1 333 384 174

24 Triad 20 AWG 300V 4B031M202410008 2.03 0.080 34.2 1.346 681 1,014 16.1 410 576 261

1 Pair 18 AWG 300V 4B021M180110008 1.14 0.045 8.2 0.323 46 69 3.9 98 26 12

2 Pair 18 AWG 300V 4B021M180210008 1.14 0.045 12.4 0.487 91 135 5.8 148 52 24

4 Pair 18 AWG 300V 4B021M180410008 1.52 0.060 15.0 0.592 140 208 7.1 180 104 47

8 Pair 18 AWG 300V 4B021M180810008 1.52 0.060 19.3 0.761 237 353 9.1 232 208 94

12 Pair 18 AWG 300V 4B021M181210008 2.03 0.080 24.4 0.961 363 540 11.5 293 312 142

16 Pair 18 AWG 300V 4B021M181610008 2.03 0.080 27.0 1.064 447 665 12.8 324 416 189

24 Pair 18 AWG 300V 4B021M182410008 2.03 0.080 33.2 1.309 634 943 15.7 399 624 283

36 Pair 18 AWG 300V 4B021M183610008 2.03 0.080 38.0 1.496 876 1,303 18.0 456 936 425

50 Pair 18 AWG 300V 4B021M185010008 2.79 0.110 45.5 1.790 1,258 1,873 21.5 545 1,300 590

1 Triad 18 AWG 300V 4B031M180110008 1.14 0.045 8.6 0.339 57 84 4.1 103 39 18

2 Triad 18 AWG 300V 4B031M180210008 1.52 0.060 14.4 0.568 132 197 6.8 173 78 35

4 Triad 18 AWG 300V 4B031M180410008 1.52 0.060 16.6 0.653 184 274 7.8 199 156 71

8 Triad 18 AWG 300V 4B031M180810008 2.03 0.080 22.5 0.885 351 522 10.6 270 312 142

12 Triad 18 AWG 300V 4B031M181210008 2.03 0.080 27.1 1.067 491 731 12.8 325 468 212

16 Triad 18 AWG 300V 4B031M181610008 2.03 0.080 30.1 1.184 611 909 14.2 361 624 283

24 Triad 18 AWG 300V 4B031M182410008 2.03 0.080 37.1 1.462 878 1,307 17.5 445 936 425

1 Pair 16 AWG 300V 4B021M160110008 1.14 0.045 8.8 0.347 58 86 4.2 106 41 19

2 Pair 16 AWG 300V 4B021M160210008 1.14 0.045 13.4 0.529 114 170 6.3 161 82 37

4 Pair 16 AWG 300V 4B021M160410008 1.52 0.060 16.3 0.642 176 262 7.7 196 165 75

8 Pair 16 AWG 300V 4B021M160810008 1.52 0.060 21.1 0.830 307 457 10.0 253 330 150

12 Pair 16 AWG 300V 4B021M161210008 2.03 0.080 26.6 1.048 470 699 12.6 319 494 224

16 Pair 16 AWG 300V 4B021M161610008 2.03 0.080 29.5 1.162 582 866 13.9 354 659 299

24 Pair 16 AWG 300V 4B021M162410008 2.03 0.080 36.4 1.434 837 1,245 17.2 437 989 449

36 Pair 16 AWG 300V 4B021M163610008 2.03 0.080 41.7 1.643 1,170 1,740 19.7 501 1,483 673

1 Triad 16 AWG 300V 4B031M160110008 1.14 0.045 9.3 0.365 73 108 4.4 111 62 28

2 Triad 16 AWG 300V 4B031M160210008 1.52 0.060 15.6 0.616 164 244 7.4 188 124 56

4 Triad 16 AWG 300V 4B031M160410008 1.52 0.060 18.1 0.711 236 352 8.5 217 247 112

8 Triad 16 AWG 300V 4B031M160810008 2.03 0.080 24.5 0.964 455 677 11.6 294 494 224

12 Triad 16 AWG 300V 4B031M161210008 2.03 0.080 29.6 1.166 643 957 14.0 355 742 336

16 Triad 16 AWG 300V 4B031M161610008 2.03 0.080 32.9 1.297 807 1,201 15.6 395 989 449

24 Triad 16 AWG 300V 4B031M162410008 2.03 0.080 40.8 1.605 1,172 1,744 19.3 489 1,483 673

Page 41: Shaw Flex Catalogue

Phone: 1 800-668-4842 39 email: [email protected]

CSA Cables

FR XLPE Insulated Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 4B022M200210008 1.14 0.045 12.0 0.473 86 128 5.7 144 32 15

4 Pair 20 AWG 300V 4B022M200410008 1.52 0.060 14.6 0.575 131 194 6.9 175 64 29

8 Pair 20 AWG 300V 4B022M200810008 1.52 0.060 18.8 0.738 219 326 8.9 225 128 58

12 Pair 20 AWG 300V 4B022M201210008 2.03 0.080 23.7 0.932 336 501 11.2 284 192 87

16 Pair 20 AWG 300V 4B022M201610008 2.03 0.080 26.2 1.031 411 612 12.4 314 256 116

24 Pair 20 AWG 300V 4B022M202410008 2.03 0.080 32.2 1.266 584 869 15.2 386 384 174

36 Pair 20 AWG 300V 4B022M203610008 2.03 0.080 36.8 1.447 803 1,196 17.4 441 576 261

50 Pair 20 AWG 300V 4B022M205010008 2.03 0.080 42.5 1.672 1,068 1,589 20.1 510 800 363

2 Triad 20 AWG 300V 4B032M200210008 1.14 0.045 13.4 0.526 108 161 6.3 160 48 22

4 Triad 20 AWG 300V 4B032M200410008 1.52 0.060 16.2 0.639 165 245 7.7 195 96 44

8 Triad 20 AWG 300V 4B032M200810008 1.52 0.060 21.0 0.825 284 423 9.9 252 192 87

12 Triad 20 AWG 300V 4B032M201210008 2.03 0.080 26.5 1.041 436 649 12.5 317 288 131

16 Triad 20 AWG 300V 4B032M201610008 2.03 0.080 29.4 1.156 537 800 13.9 352 384 174

24 Triad 20 AWG 300V 4B032M202410008 2.03 0.080 36.2 1.425 770 1,146 17.1 434 576 261

2 Pair 18 AWG 300V 4B022M180210008 1.14 0.045 12.9 0.509 104 155 6.1 155 52 24

4 Pair 18 AWG 300V 4B022M180410008 1.52 0.060 15.7 0.618 160 238 7.4 188 104 47

8 Pair 18 AWG 300V 4B022M180810008 1.52 0.060 20.3 0.797 277 413 9.6 243 208 94

12 Pair 18 AWG 300V 4B022M181210008 2.03 0.080 25.6 1.006 422 628 12.1 307 312 142

16 Pair 18 AWG 300V 4B022M181610008 2.03 0.080 28.3 1.116 524 780 13.4 340 416 189

24 Pair 18 AWG 300V 4B022M182410008 2.03 0.080 34.9 1.374 752 1,119 16.5 419 624 283

36 Pair 18 AWG 300V 4B022M183610008 2.03 0.080 40.0 1.573 1,045 1,555 18.9 480 936 425

50 Pair 18 AWG 300V 4B022M185010008 2.79 0.110 47.8 1.880 1,497 2,227 22.6 573 1,300 590

2 Triad 18 AWG 300V 4B032M180210008 1.52 0.060 15.1 0.596 147 218 7.2 182 78 35

4 Triad 18 AWG 300V 4B032M180410008 1.52 0.060 17.5 0.687 207 308 8.2 209 156 71

8 Triad 18 AWG 300V 4B032M180810008 2.03 0.080 23.7 0.932 398 592 11.2 284 312 142

12 Triad 18 AWG 300V 4B032M181210008 2.03 0.080 28.6 1.125 561 834 13.5 343 468 212

16 Triad 18 AWG 300V 4B032M181610008 2.03 0.080 31.8 1.250 698 1,038 15.0 381 624 283

24 Triad 18 AWG 300V 4B032M182410008 2.03 0.080 39.3 1.546 1,009 1,501 18.6 471 936 425

2 Pair 16 AWG 300V 4B022M160210008 1.52 0.060 14.8 0.582 146 217 7.0 177 82 37

4 Pair 16 AWG 300V 4B022M160410008 1.52 0.060 17.0 0.670 207 307 8.0 204 165 75

8 Pair 16 AWG 300V 4B022M160810008 2.03 0.080 23.1 0.909 397 591 10.9 277 330 150

12 Pair 16 AWG 300V 4B022M161210008 2.03 0.080 27.8 1.096 558 831 13.2 334 494 224

16 Pair 16 AWG 300V 4B022M161610008 2.03 0.080 30.9 1.217 699 1,040 14.6 371 659 299

24 Pair 16 AWG 300V 4B022M162410008 2.03 0.080 38.2 1.504 1,012 1,506 18.0 458 989 449

36 Pair 16 AWG 300V 4B022M163610008 2.79 0.110 45.3 1.785 1,519 2,260 21.4 544 1,483 673

2 Triad 16 AWG 300V 4B032M160210008 1.52 0.060 16.4 0.646 183 273 7.8 197 124 56

4 Triad 16 AWG 300V 4B032M160410008 1.52 0.060 19.0 0.747 269 400 9.0 228 247 112

8 Triad 16 AWG 300V 4B032M160810008 2.03 0.080 25.8 1.014 518 770 12.2 309 494 224

12 Triad 16 AWG 300V 4B032M161210008 2.03 0.080 31.2 1.229 735 1,094 14.7 375 742 336

16 Triad 16 AWG 300V 4B032M161610008 2.03 0.080 34.7 1.368 929 1,383 16.4 417 989 449

24 Triad 16 AWG 300V 4B032M162410008 2.79 0.110 44.6 1.756 1,443 2,147 21.1 535 1,483 673

Page 42: Shaw Flex Catalogue

CSA

Cab

les

FR PVC Insulated Control Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 46010M140200000 1.14 0.045 9.6 0.376 86 128 2.3 57 99 45 15.0

3 14 AWG 600V 46010M140300000 1.14 0.045 10.3 0.407 106 158 2.4 62 132 60 15.0

4 14 AWG 600V 46010M140400000 1.14 0.045 11.2 0.441 130 194 2.6 67 165 75 12.0

5 14 AWG 600V 46010M140500000 1.14 0.045 12.0 0.470 154 230 2.8 72 197 90 12.0

6 14 AWG 600V 46010M140600000 1.14 0.045 13.0 0.511 174 259 3.1 78 230 104 12.0

7 14 AWG 600V 46010M140700000 1.52 0.060 14.8 0.581 214 318 3.5 89 263 119 10.5

8 14 AWG 600V 46010M140800000 1.52 0.060 15.8 0.623 242 359 3.7 95 296 134 10.5

10 14 AWG 600V 46010M141000000 1.52 0.060 17.2 0.676 283 421 4.1 103 362 164 10.5

12 14 AWG 600V 46010M141200000 1.52 0.060 17.7 0.696 321 478 4.2 106 428 194 10.5

15 14 AWG 600V 46010M141500000 1.52 0.060 19.1 0.750 388 577 4.5 114 526 239 10.5

20 14 AWG 600V 46010M142000000 2.03 0.080 22.6 0.892 527 784 5.3 136 691 313 10.5

25 14 AWG 600V 46010M142500000 2.03 0.080 25.0 0.986 642 955 5.9 150 855 388 9.0

30 14 AWG 600V 46010M143000000 2.03 0.080 26.5 1.041 744 1,107 6.2 159 1,020 463 9.0

40 14 AWG 600V 46010M144000000 2.03 0.080 29.5 1.161 959 1,428 7.0 177 1,349 612 9.0

50 14 AWG 600V 46010M145000000 2.03 0.080 32.7 1.288 1,169 1,739 7.7 196 1,678 761 7.5

2 12 AWG 600V 46010M120200000 1.14 0.045 10.5 0.414 116 173 2.5 63 157 71 20.0

3 12 AWG 600V 46010M120300000 1.14 0.045 11.4 0.449 146 217 2.7 68 209 95 20.0

4 12 AWG 600V 46010M120400000 1.14 0.045 12.4 0.488 178 265 2.9 74 261 118 16.0

6 12 AWG 600V 46010M120600000 1.52 0.060 15.2 0.598 263 391 3.6 91 365 166 16.0

10 12 AWG 600V 46010M121000000 1.52 0.060 19.1 0.752 390 580 4.5 115 574 260 14.0

12 12 AWG 600V 46010M121200000 1.52 0.060 19.7 0.775 447 666 4.7 118 679 308 14.0

15 12 AWG 600V 46010M121500000 1.52 0.060 21.3 0.837 539 803 5.0 128 835 379 14.0

20 12 AWG 600V 46010M122000000 2.03 0.080 25.2 0.992 730 1,086 6.0 151 1,096 497 14.0

25 12 AWG 600V 46010M122500000 2.03 0.080 27.9 1.100 893 1,329 6.6 168 1,357 616 12.0

30 12 AWG 600V 46010M123000000 2.03 0.080 29.5 1.163 1,037 1,544 7.0 177 1,618 734 12.0

2 10 AWG 600V 46010M100200000 1.14 0.045 11.8 0.464 161 240 2.8 71 249 113 30.0

3 10 AWG 600V 46010M100300000 1.14 0.045 12.8 0.505 205 306 3.0 77 332 151 30.0

4 10 AWG 600V 46010M100400000 1.52 0.060 14.7 0.580 269 401 3.5 88 415 188 24.0

6 10 AWG 600V 46010M100600000 1.52 0.060 17.1 0.673 367 546 4.0 103 581 264 24.0

10 10 AWG 600V 46010M101000000 2.03 0.080 22.7 0.892 583 867 5.4 136 913 414 21.0

15 10 AWG 600V 46010M101500000 2.03 0.080 25.2 0.990 809 1,204 5.9 151 1,328 602 21.0

20 10 AWG 600V 46010M102000000 2.03 0.080 28.6 1.125 1,040 1,548 6.7 171 1,743 791 21.0

Page 43: Shaw Flex Catalogue

Phone: 1 800-668-4842 41 email: [email protected]

CSA Cables

FR XLPE Insulated Power Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 8 AWG 600V 4C010M080200000 1.52 0.060 15.7 0.616 247 368 3.7 94 348 158 45.0

3 8 AWG 600V 4C010M080300000 1.52 0.060 17.1 0.671 316 471 4.0 102 480 218 45.0

4 8 AWG 600V 4C010M080400000 1.52 0.060 18.6 0.731 393 585 4.4 111 612 278 36.0

2 6 AWG 600V 4C010M060200000 1.52 0.060 17.4 0.684 344 512 4.1 104 552 250 65.0

3 6 AWG 600V 4C010M060300000 1.52 0.060 19.0 0.747 444 661 4.5 114 761 345 65.0

4 6 AWG 600V 4C010M060400000 1.52 0.060 20.7 0.815 553 824 4.9 124 971 440 52.0

2 4 AWG 600V 4C010M040200000 1.52 0.060 19.8 0.778 472 703 4.7 119 800 363 85.0

3 4 AWG 600V 4C010M040300000 1.52 0.060 21.0 0.826 625 930 5.0 126 1,134 514 85.0

4 4 AWG 600V 4C010M040400000 2.03 0.080 24.7 0.971 824 1,226 5.8 148 1,468 666 68.0

2 2 AWG 600V 4C010M020200000 2.03 0.080 23.7 0.934 728 1,084 5.6 142 1,272 577 120.0

3 2 AWG 600V 4C010M020300000 2.03 0.080 25.2 0.991 960 1,428 5.9 151 1,803 818 120.0

4 2 AWG 600V 4C010M020400000 2.03 0.080 28.3 1.115 1,222 1,818 6.7 170 2,334 1,059 96.0

2 1 AWG 600V 4C010M010240000 2.03 0.080 26.7 1.052 885 1,317 6.3 160 1,549 702 140.0

3 1 AWG 600V 4C010M010340000 2.03 0.080 28.4 1.117 1,180 1,756 6.7 170 2,218 1,006 140.0

4 1 AWG 600V 4C010M010440000 2.03 0.080 31.2 1.226 1,503 2,237 7.4 187 2,888 1,310 112.0

2 1/0 AWG 600V 4C010M1/0240000 2.03 0.080 29.1 1.146 997 1,483 6.9 175 1,899 862 155.0

3 1/0 AWG 600V 4C010M1/0340000 2.03 0.080 31.0 1.218 1,388 2,065 7.3 186 2,744 1,245 155.0

4 1/0 AWG 600V 4C010M1/0440000 2.03 0.080 34.0 1.339 1,800 2,679 8.0 204 3,589 1,628 124.0

2 2/0 AWG 600V 4C010M2/0240000 2.03 0.080 31.5 1.238 1,200 1,785 7.4 189 2,339 1,061 185.0

3 2/0 AWG 600V 4C010M2/0340000 2.03 0.080 33.5 1.317 1,678 2,497 7.9 201 3,404 1,544 185.0

4 2/0 AWG 600V 4C010M2/0440000 2.03 0.080 36.8 1.450 2,185 3,252 8.7 221 4,469 2,027 148.0

2 3/0 AWG 600V 4C010M3/0240000 2.03 0.080 33.9 1.336 1,494 2,223 8.0 204 3,005 1,363 210.0

3 3/0 AWG 600V 4C010M3/0340000 2.03 0.080 36.1 1.423 2,078 3,092 8.5 217 4,341 1,969 210.0

4 3/0 AWG 600V 4C010M3/0440000 2.03 0.080 39.8 1.567 2,686 3,997 9.4 239 5,677 2,575 168.0

2 4/0 AWG 600V 4C010M4/0240000 2.03 0.080 36.8 1.450 1,802 2,682 8.7 221 3,720 1,687 235.0

3 4/0 AWG 600V 4C010M4/0340000 2.03 0.080 39.3 1.545 2,555 3,802 9.3 236 5,412 2,455 235.0

4 4/0 AWG 600V 4C010M4/0440000 2.79 0.110 44.8 1.764 3,402 5,063 10.6 269 7,105 3,223 188.0

Page 44: Shaw Flex Catalogue

CSA

Cab

les

FR XLPE Insulated Control Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 4C010M140200000 1.14 0.045 9.6 0.376 84 125 2.3 57 99 45 15.0

3 14 AWG 600V 4C010M140300000 1.14 0.045 10.3 0.407 102 152 2.4 62 132 60 15.0

4 14 AWG 600V 4C010M140400000 1.14 0.045 11.2 0.441 125 186 2.6 67 165 75 12.0

5 14 AWG 600V 4C010M140500000 1.14 0.045 12.0 0.470 148 220 2.8 72 197 90 12.0

6 14 AWG 600V 4C010M140600000 1.14 0.045 13.0 0.511 167 248 3.1 78 230 104 12.0

7 14 AWG 600V 4C010M140700000 1.52 0.060 14.8 0.581 206 306 3.5 89 263 119 10.5

8 14 AWG 600V 4C010M140800000 1.52 0.060 15.8 0.623 232 346 3.7 95 296 134 10.5

10 14 AWG 600V 4C010M141000000 1.52 0.060 17.2 0.676 271 403 4.1 103 362 164 10.5

12 14 AWG 600V 4C010M141200000 1.52 0.060 17.7 0.696 307 457 4.2 106 428 194 10.5

15 14 AWG 600V 4C010M141500000 1.52 0.060 19.1 0.750 370 550 4.5 114 526 239 10.5

20 14 AWG 600V 4C010M142000000 2.03 0.080 22.6 0.892 503 749 5.3 136 691 313 10.5

25 14 AWG 600V 4C010M142500000 2.03 0.080 25.0 0.986 612 911 5.9 150 855 388 9.0

30 14 AWG 600V 4C010M143000000 2.03 0.080 26.5 1.041 707 1,052 6.2 159 1,020 463 9.0

40 14 AWG 600V 4C010M144000000 2.03 0.080 29.5 1.161 912 1,357 7.0 177 1,349 612 9.0

50 14 AWG 600V 4C010M145000000 2.03 0.080 32.7 1.288 1,109 1,650 7.7 196 1,678 761 7.5

2 12 AWG 600V 4C010M120200000 1.14 0.045 10.5 0.414 113 168 2.5 63 157 71 20.0

3 12 AWG 600V 4C010M120300000 1.14 0.045 11.4 0.449 141 210 2.7 68 209 95 20.0

4 12 AWG 600V 4C010M120400000 1.14 0.045 12.4 0.488 172 255 2.9 74 261 118 16.0

5 12 AWG 600V 4C010M120500000 1.14 0.045 13.3 0.522 204 303 3.1 80 313 142 16.0

6 12 AWG 600V 4C010M120600000 1.52 0.060 15.2 0.598 254 377 3.6 91 365 166 16.0

7 12 AWG 600V 4C010M120700000 1.52 0.060 16.4 0.644 289 430 3.9 98 418 189 14.0

8 12 AWG 600V 4C010M120800000 1.52 0.060 17.6 0.692 319 474 4.2 105 470 213 14.0

10 12 AWG 600V 4C010M121000000 1.52 0.060 19.1 0.752 375 558 4.5 115 574 260 14.0

12 12 AWG 600V 4C010M121200000 1.52 0.060 19.7 0.775 430 639 4.7 118 679 308 14.0

15 12 AWG 600V 4C010M121500000 1.52 0.060 21.3 0.837 517 770 5.0 128 835 379 14.0

20 12 AWG 600V 4C010M122000000 2.03 0.080 25.2 0.992 701 1,043 6.0 151 1,096 497 14.0

25 12 AWG 600V 4C010M122500000 2.03 0.080 27.9 1.100 857 1,275 6.6 168 1,357 616 12.0

30 12 AWG 600V 4C010M123000000 2.03 0.080 29.5 1.163 993 1,478 7.0 177 1,618 734 12.0

2 10 AWG 600V 4C010M100200000 1.14 0.045 11.8 0.464 158 236 2.8 71 249 113 30.0

3 10 AWG 600V 4C010M100300000 1.14 0.045 12.8 0.505 200 298 3.0 77 332 151 30.0

4 10 AWG 600V 4C010M100400000 1.52 0.060 14.7 0.580 261 389 3.5 88 415 188 24.0

5 10 AWG 600V 4C010M100500000 1.52 0.060 15.7 0.619 304 453 3.7 94 498 226 24.0

6 10 AWG 600V 4C010M100600000 1.52 0.060 17.1 0.673 355 529 4.0 103 581 264 24.0

7 10 AWG 600V 4C010M100700000 1.52 0.060 18.5 0.727 407 606 4.4 111 664 301 21.0

8 10 AWG 600V 4C010M100800000 1.52 0.060 19.9 0.782 453 674 4.7 119 747 339 21.0

10 10 AWG 600V 4C010M101000000 2.03 0.080 22.7 0.892 565 841 5.4 136 913 414 21.0

12 10 AWG 600V 4C010M101200000 2.03 0.080 23.3 0.919 647 963 5.5 140 1,079 489 21.0

15 10 AWG 600V 4C010M101500000 2.03 0.080 25.2 0.990 781 1,162 5.9 151 1,328 602 21.0

20 10 AWG 600V 4C010M102000000 2.03 0.080 28.6 1.125 1,004 1,494 6.7 171 1,743 791 21.0

25 10 AWG 600V 4C010M102500000 2.03 0.080 31.8 1.250 1,231 1,831 7.5 190 2,158 979 18.0

30 10 AWG 600V 4C010M103000000 2.03 0.080 33.6 1.323 1,436 2,137 7.9 202 2,573 1,167 18.0

40 10 AWG 600V 4C010M104000000 2.03 0.080 37.7 1.483 1,870 2,782 8.9 226 3,403 1,544 18.0

Page 45: Shaw Flex Catalogue

Phone: 1 800-668-4842 43 email: [email protected]

CSA Cables

XLPE Insulated Power TECK90 (TECK90)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 8 AWG 600V 86210M080200700 1.02 0.040 23.4 0.920 412 614 11.0 280 348 158 45.0

3 8 AWG 600V 86210M080300700 1.02 0.040 24.8 0.975 496 738 11.7 297 480 218 45.0

4 8 AWG 600V 86210M080400700 1.02 0.040 26.3 1.035 587 873 12.4 315 612 278 36.0

2 6 AWG 600V 86210M060200700 1.02 0.040 25.1 0.988 523 778 11.9 301 552 250 65.0

3 6 AWG 600V 86210M060300700 1.02 0.040 26.7 1.051 642 956 12.6 320 761 345 65.0

4 6 AWG 600V 86210M060400700 1.02 0.040 28.9 1.139 814 1,212 13.7 347 971 440 52.0

2 4 AWG 600V 86210M040200700 1.02 0.040 28.0 1.102 714 1,062 13.2 336 800 363 85.0

3 4 AWG 600V 86210M040300700 1.02 0.040 29.2 1.150 884 1,315 13.8 350 1,134 514 85.0

4 4 AWG 600V 86210M040400700 1.02 0.040 33.0 1.299 1,132 1,684 15.6 396 1,468 666 68.0

2 2 AWG 600V 86210M020200700 1.02 0.040 32.1 1.262 1,012 1,507 15.1 385 1,272 577 120.0

3 2 AWG 600V 86210M020300700 1.02 0.040 33.5 1.319 1,268 1,887 15.8 402 1,803 818 120.0

4 2 AWG 600V 86210M020400700 1.02 0.040 36.7 1.443 1,566 2,331 17.3 440 2,334 1,059 96.0

2 1 AWG 600V 86210M010240700 1.02 0.040 35.1 1.380 1,192 1,774 16.6 421 1,549 702 140.0

3 1 AWG 600V 86210M010340700 1.02 0.040 36.7 1.445 1,515 2,254 17.3 441 2,218 1,006 140.0

4 1 AWG 600V 86210M010440700 1.02 0.040 39.5 1.554 1,873 2,788 18.7 474 2,888 1,310 112.0

2 1/0 AWG 600V 86210M1/0240700 1.02 0.040 37.4 1.474 1,357 2,019 17.7 449 1,899 862 155.0

3 1/0 AWG 600V 86210M1/0340700 1.02 0.040 39.3 1.547 1,757 2,615 18.6 471 2,744 1,245 155.0

4 1/0 AWG 600V 86210M1/0440700 1.22 0.048 42.8 1.683 2,227 3,314 20.2 513 3,589 1,628 124.0

2 2/0 AWG 600V 86210M2/0240700 1.02 0.040 39.8 1.566 1,584 2,357 18.8 477 2,339 1,061 185.0

3 2/0 AWG 600V 86210M2/0340700 1.22 0.048 42.2 1.662 2,097 3,121 19.9 506 3,404 1,544 185.0

4 2/0 AWG 600V 86210M2/0440700 1.22 0.048 45.6 1.794 2,641 3,931 21.5 547 4,469 2,027 148.0

2 3/0 AWG 600V 86210M3/0240700 1.22 0.048 42.7 1.680 1,925 2,864 20.2 512 3,005 1,363 210.0

3 3/0 AWG 600V 86210M3/0340700 1.22 0.048 44.9 1.767 2,531 3,767 21.2 538 4,341 1,969 210.0

4 3/0 AWG 600V 86210M3/0440700 1.22 0.048 50.2 1.976 3,262 4,854 23.7 602 5,677 2,575 168.0

2 4/0 AWG 600V 86210M4/0240700 1.22 0.048 45.6 1.794 2,270 3,378 21.5 547 3,720 1,687 235.0

3 4/0 AWG 600V 86210M4/0340700 1.22 0.048 49.6 1.954 3,121 4,645 23.5 596 5,412 2,455 235.0

4 4/0 AWG 600V 86210M4/0440700 1.22 0.048 55.2 2.173 4,048 6,024 26.1 662 7,105 3,223 188.0

Page 46: Shaw Flex Catalogue

CSA

Cab

les

XLPE Insulated Control TECK90 (TECK90)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 86210M140200700 1.02 0.040 17.3 0.680 202 301 8.2 207 99 45 15.0

3 14 AWG 600V 86210M140300700 1.02 0.040 18.1 0.711 227 338 8.5 217 132 60 15.0

4 14 AWG 600V 86210M140400700 1.02 0.040 18.9 0.745 255 379 8.9 227 165 75 12.0

5 14 AWG 600V 86210M140500700 1.02 0.040 19.7 0.774 282 420 9.3 236 197 90 12.0

6 14 AWG 600V 86210M140600700 1.02 0.040 20.7 0.815 314 468 9.8 248 230 104 12.0

7 14 AWG 600V 86210M140700700 1.02 0.040 22.5 0.886 369 549 10.6 270 263 119 10.5

8 14 AWG 600V 86210M140800700 1.02 0.040 23.6 0.927 404 602 11.1 283 296 134 10.5

10 14 AWG 600V 86210M141000700 1.02 0.040 24.9 0.980 454 675 11.8 299 362 164 10.5

12 14 AWG 600V 86210M141200700 1.02 0.040 25.4 1.000 493 734 12.0 305 428 194 10.5

15 14 AWG 600V 86210M141500700 1.02 0.040 26.8 1.054 566 842 12.7 321 526 239 10.5

20 14 AWG 600V 86210M142000700 1.02 0.040 30.9 1.216 783 1,166 14.6 370 691 313 10.5

30 14 AWG 600V 86210M143000700 1.02 0.040 34.8 1.369 1,027 1,529 16.4 417 1,020 463 9.0

40 14 AWG 600V 86210M144000700 1.02 0.040 37.8 1.490 1,258 1,872 17.9 454 1,349 612 9.0

50 14 AWG 600V 86210M145000700 1.02 0.040 41.1 1.616 1,483 2,207 19.4 493 1,678 761 7.5

2 12 AWG 600V 86210M120200700 1.02 0.040 18.2 0.718 232 345 8.6 219 137 62 20.0

3 12 AWG 600V 86210M120300700 1.02 0.040 19.1 0.753 266 395 9.0 230 190 86 20.0

4 12 AWG 600V 86210M120400700 1.02 0.040 20.1 0.792 303 452 9.5 241 242 110 16.0

5 12 AWG 600V 86210M120500700 1.02 0.040 21.0 0.826 341 508 9.9 252 294 133 16.0

6 12 AWG 600V 86210M120600700 1.02 0.040 22.9 0.902 407 606 10.8 275 346 157 16.0

7 12 AWG 600V 86210M120700700 1.02 0.040 24.1 0.948 452 673 11.4 289 398 181 14.0

8 12 AWG 600V 86210M120800700 1.02 0.040 25.3 0.996 498 741 12.0 304 451 204 14.0

10 12 AWG 600V 86210M121000700 1.02 0.040 26.8 1.056 566 843 12.7 322 555 252 14.0

12 12 AWG 600V 86210M121200700 1.02 0.040 27.9 1.099 673 1,002 13.2 335 659 299 14.0

15 12 AWG 600V 86210M121500700 1.02 0.040 29.5 1.161 774 1,152 13.9 354 816 370 14.0

20 12 AWG 600V 86210M122000700 1.02 0.040 33.5 1.320 1,004 1,494 15.8 402 1,077 488 14.0

30 12 AWG 600V 86210M123000700 1.02 0.040 37.9 1.491 1,336 1,988 17.9 454 1,599 725 12.0

2 10 AWG 600V 86210M100200700 1.02 0.040 19.5 0.768 283 421 9.2 234 218 99 30.0

3 10 AWG 600V 86210M100300700 1.02 0.040 20.6 0.809 335 499 9.7 247 301 137 30.0

4 10 AWG 600V 86210M100400700 1.02 0.040 22.5 0.884 406 604 10.6 269 384 174 24.0

6 10 AWG 600V 86210M100600700 1.02 0.040 24.8 0.977 521 775 11.7 298 550 250 24.0

10 10 AWG 600V 86210M101000700 1.02 0.040 30.9 1.216 838 1,246 14.6 371 882 400 21.0

15 10 AWG 600V 86210M101500700 1.02 0.040 33.5 1.318 1,080 1,608 15.8 402 1,297 588 21.0

Page 47: Shaw Flex Catalogue

Phone: 1 800-668-4842 45 email: [email protected]

CSA Cables

XLPE Insulated Armoured Control: ARMCON® (ACIC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V 69210M160209714 1.27 0.050 17.0 0.670 186 277 8.0 204 62 28 10.0

3 16 AWG 600V 69210M160309714 1.27 0.050 17.5 0.688 204 304 8.3 210 82 37 10.0

4 16 AWG 600V 69210M160409714 1.27 0.050 18.2 0.718 226 337 8.6 219 103 47 8.0

5 16 AWG 600V 69210M160509714 1.27 0.050 19.2 0.754 251 374 9.1 230 124 56 8.0

6 16 AWG 600V 69210M160609714 1.27 0.050 20.1 0.790 276 411 9.5 241 144 65 8.0

7 16 AWG 600V 69210M160709714 1.27 0.050 21.0 0.826 301 448 9.9 252 165 75 7.0

8 16 AWG 600V 69210M160809714 1.27 0.050 22.7 0.893 352 523 10.7 272 185 84 7.0

10 16 AWG 600V 69210M161009714 1.27 0.050 23.9 0.940 389 578 11.3 287 227 103 7.0

12 16 AWG 600V 69210M161209714 1.27 0.050 24.3 0.958 418 622 11.5 292 268 121 7.0

15 16 AWG 600V 69210M161509714 1.27 0.050 25.6 1.006 468 697 12.1 307 330 150 7.0

20 16 AWG 600V 69210M162009714 1.27 0.050 27.8 1.096 608 905 13.1 334 433 196 7.0

25 16 AWG 600V 69210M162509714 1.27 0.050 31.5 1.240 754 1,122 14.9 378 536 243 6.0

30 16 AWG 600V 69210M163009714 1.27 0.050 32.8 1.293 833 1,240 15.5 394 639 290 6.0

40 16 AWG 600V 69210M164009714 1.27 0.050 35.6 1.400 1,008 1,499 16.8 427 845 383 6.0

50 16 AWG 600V 69210M165009714 1.27 0.050 38.4 1.513 1,173 1,746 18.2 461 1,051 477 5.0

60 16 AWG 600V 69210M166009714 1.27 0.050 40.7 1.604 1,332 1,983 19.2 489 1,257 570 5.0

2 18 AWG 600V 69210M180209714 1.27 0.050 16.4 0.646 168 250 7.8 197 39 18 5.0

3 18 AWG 600V 69210M180309714 1.27 0.050 16.8 0.662 182 271 7.9 202 52 24 5.0

4 18 AWG 600V 69210M180409714 1.27 0.050 17.5 0.689 199 297 8.3 210 65 29 4.0

5 18 AWG 600V 69210M180509714 1.27 0.050 18.3 0.721 220 327 8.7 220 78 35 4.0

6 18 AWG 600V 69210M180609714 1.27 0.050 19.2 0.754 240 357 9.0 230 91 41 4.0

7 18 AWG 600V 69210M180709714 1.27 0.050 20.0 0.786 260 387 9.4 240 104 47 3.5

8 18 AWG 600V 69210M180809714 1.27 0.050 20.8 0.820 281 418 9.8 250 117 53 3.5

10 18 AWG 600V 69210M181009714 1.27 0.050 22.7 0.892 333 495 10.7 272 143 65 3.5

12 18 AWG 600V 69210M181209714 1.27 0.050 23.1 0.908 354 527 10.9 277 169 77 3.5

15 18 AWG 600V 69210M181509714 1.27 0.050 24.2 0.951 392 584 11.4 290 208 94 3.5

20 18 AWG 600V 69210M182009714 1.27 0.050 26.2 1.033 467 695 12.4 315 273 124 3.5

25 18 AWG 600V 69210M182509714 1.27 0.050 28.7 1.128 587 873 13.5 344 338 153 3.0

30 18 AWG 600V 69210M183009714 1.27 0.050 29.8 1.172 640 953 14.1 357 403 183 3.0

40 18 AWG 600V 69210M184009714 1.27 0.050 33.3 1.313 820 1,220 15.8 400 533 242 3.0

50 18 AWG 600V 69210M185009714 1.27 0.050 35.9 1.414 947 1,410 17.0 431 663 301 2.5

60 18 AWG 600V 69210M186009714 1.27 0.050 38.0 1.496 1,067 1,587 18.0 456 793 360 2.5

Page 48: Shaw Flex Catalogue

UL

Cabl

es

ShawFlex UL Cables

Armoured a. Instrumentation b. Control c. Power d. Thermocouple

Tray a. Instrumentation b. Control c. Power d. Thermocouple

ShawFlex UL cables have been designed to meet the rigorous requirements established by the Underwriters Laboratories. UL Cables can be found in projects though out the world.

ArmouredShawFlex UL Armoured cables can be used for Hazardous Location application as permitted.

ShawFlex UL Armoured cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays, direct earth burial, for exposed and concealed wiring wet/dry locations. Available in three distinct options:

Aluminum Interlocked Armour (AIA) Galvanized Steel Interlocked Armour (SIA) Galvanized Steel Served Wire Armoured (SWA)

Construction Nec Characteristics

AIA Type MC (article 330)

Type ITC (article 727)

Type PLTC (article 725)

Flame Retardant, Sunlight resistant, Lightweight, excellent mechanical protection, cut & crush resistant, corrosion resistant

SIA Type MC (article 330)

Type ITC (article 727)

Type PLTC (article 725)

Flame Retardant, Sunlight resistant, Superior mechanical protection, cut & crush resistant

SWA Type ITC (article 727)

Type PLTC (article 725)

Flame Retardant, Sunlight resistant, Lightweight, reduced diameter, flexible, good cut though resistance, vertical applications

TrayShawFlex UL tray cables can be used for Hazardous Location application as permitted.

ShawFlex UL Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays in wet/dry locations. Construction Nec Characteristics

TC Type TC (article 336) Type ITC (article 727)

Type PLTC (article 725)

Flame Retardant, Sunlight resistant, Lightweight, reduced diameter, flexible, tight bend radius

Page 49: Shaw Flex Catalogue

Phone: 1 800-668-4842 47 email: [email protected]

UL Cables

Armoured Cable Available Constructions:

Instrumentation Control Power Thermocouple

Characteristics:

Flame Retardant a a a aSunlight Resistant a a a aWet Rated a a a a-40 Cold Impact a a a aDirect Burial a a a aExposed Runs (ER) a a a a

Voltage Ratings:

300V a a - a600V a a a -2000V - - a -

Armouring Options:

Aluminum Interlock armour a a a aSteel Interlock Armour a a a aSteel wire Served Armour a a - a

Jacketing Options:

PVC Jacket a a a aPVC LAG Jacket a a a aLSZH Jacket a a - aCPE Jacket a a - aCSPE (Hypalon®) Jacket a a - a

Insulation Options:

PVC Insulation a a - aFR-XLPE Insulation a a a aFR-XLPE VW1 Insulation a a a a

Shielding Options:

OS Aluminum Mylar a a a aISOS Aluminum Mylar a - - aHelical Copper a a a aLongitudinal Copper a a a a

Page 50: Shaw Flex Catalogue

UL

Cabl

esTray Cable Available Constructions:

Instrumentation Control Power Thermocouple

Characteristics:

Flame Retardant a a a aSunlight Resistant a a a aWet Rated a a a a-40 Cold Impact a a a aDirect Burial a a a aExposed Runs (ER) - a a -

Voltage Ratings:

300V a a - a600V a a a a2000V - - a -

Armouring Options:

Aluminum Interlock armour - - - -Steel Interlock Armour - - - -Steel wire Served Armour - - - -

Jacketing Options:

PVC Jacket a a a aPVC LAG Jacket a a a aLSZH Jacket a a a aCPE Jacket a a a aCSPE (Hypalon) Jacket a a a a

Insulation Options:

PVC Insulation a a - aFR-XLPE Insulation a a a aFR-XLPE VW1 Insulation a a a a

Shielding Options:

OS Aluminum Mylar a a a aISOS Aluminum Mylar a - - aHelical Copper a a a aLongitudinal Copper a a a a

Page 51: Shaw Flex Catalogue

Phone: 1 800-668-4842 49 email: [email protected]

UL Cables

Applications: Overall shielded thermocouple extension cable used for measurement of temperature when connected to thermocouples. Cable can be installed in conduit and other raceways, except cable tray in wet or dry environments.

600 V Ratings:UL 1277 TRAY CABLE (TYPE TC)•UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)•UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)•PVC/NYLON (THWN, THHN-2) RATED – 75• OC WET / 90OC DRYXLPE (XHHW-2) RATED - 90• OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS:•

CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and UL tray cable upon request.

Unarmoured Thermocouple Tray: OS

Available in: PVC/Nylon PVC XLPE Hypalon® CPE LSZH

Applications: Individual and overall shielded thermocouple extension instrumentation tray cable used for measurement of temperature when connected to thermocouples. Used when there is a possibility of crosstalk between pairs. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

600 V Ratings:UL 1277 TRAY CABLE (TYPE TC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and ul tray cable upon request.

Unarmoured Thermocouple Tray: ISOS

Available in: PVC/Nylon PVC XLPE Hypalon® CPE LSZH

Page 52: Shaw Flex Catalogue

UL

Cabl

esUnarmoured Instrumentation Tray: OSApplications:

Overall shielded instrumentation tray cable used to convey analogue or digital signals. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

300 V Ratings:UL 2250 INSTRUMENTATION TRAY CABLE (TYPE ITC)UL 13 POWER LIMITED TRAY CABLE (TYPE PLTC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC – 60OC WET / 105OC DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRY

600 V Ratings:UL 1277 TRAY CABLE (TYPE TC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS:

CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and UL tray cable upon request.

Available in: PVC/Nylon PVC XLPE Hypalon® CPE LSZH

Unarmoured Instrumentation Tray: ISOSApplications:

Individual and overall shielded instrumentation tray cable used to convey analogue or digital signals. Used when there is a possibility of crosstalk between pairs/triads.Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

300 V Ratings:UL 2250 INSTRUMENTATION TRAY CABLE (TYPE ITC)UL 13 POWER LIMITED TRAY CABLE (TYPE PLTC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC – 60OC WET / 105OC DRYXLPE (XHHW-2, RHW-2) RATED - 90OC WET / 90OC DRYMC RATED FOR USE IN HAZARDOUS LOCATIONS:

CLASS I ZONE 2 CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Available in: PVC XLPE Hypalon® CPE

Page 53: Shaw Flex Catalogue

Phone: 1 800-668-4842 51 email: [email protected]

UL Cables

Unarmoured Instrumentation Tray: ISOSApplications:

Individual and overall shielded instrumentation tray cable used to convey analogue or digital signals. Used when there is a possibility of crosstalk between pairs/triads. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

600 V Ratings:UL 1277 TRAY CABLE (TYPE TC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYXLPE (XHHW-2, RHW-2) RATED - 90OC WET / 90OC DRYMC RATED FOR USE IN HAZARDOUS LOCATIONS:

CLASS I ZONE 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and UL tray cable upon request.

Available in: PVC/Nylon PVC XLPE Hypalon® CPE LSZH

Applications: Individual and overall shielded thermocouple extension instrumentation tray cable used for measurement of temperature when connected to thermocouples. Used when there is a possibility of crosstalk between pairs. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

300 V Ratings:UL 2250 INSTRUMENTATION TRAY CABLE (TYPE ITC)UL 13 POWER LIMITED TRAY CABLE (TYPE PLTC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)PVC – 60OC WET / 105OC DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:PVC is most commonly specified for use. XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important.

Unarmoured Instrumentation Thermocouple: ISOS

Available in: XLPE PVC/Nylon

Page 54: Shaw Flex Catalogue

UL

Cabl

es

Applications: Unshielded power tray cable is used to supply power for lighting, drives, mo-tors and pumps. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:UL 1277 TRAY CABLE (TYPE TC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and UL tray cable upon request.

Unarmoured Control Tray Applications:

Unshielded control tray cable is used for operation of control automation equipment. Cable can be installed in conduit and other raceways, including cable tray in wet or dry environments.

Ratings:UL 1277 TRAY CABLE (TYPE TC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90-C DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS:

CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. XLPE insulated cables also available with Hypalon, CPE or LSZH jackets.

XLPE insulated cable is available in a dual rated CSA and UL tray cable upon request.

Unarmoured Power Tray

Available in: XHHW-2 RHW-2 PVC/Nylon PVC CPE Hypalon LSZH

Available in: XHHW-2 RHW-2 PVC/Nylon PVC CPE Hypalon LSZH

Page 55: Shaw Flex Catalogue

Phone: 1 800-668-4842 53 email: [email protected]

UL Cables

Available in: XHHW-2 RHW-2 PVC/Nylon PVC

Applications: Unshielded armoured power cable is used to supply power for lighting, drives, motors and pumps. Interlocked armour replaces the use of conduit for me-chanical protection. Cable can be directly buried, installed in raceways, includ-ing cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:UL 1569 METALCLAD CABLE (TYPE MC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYXLPE (XHHW-2) RATED - 90OC WET / 90OC DRYTC RATED FOR USE IN HAZARDOUS LOCATIONS: CLASS I ZONE 0 & 2, CLASS II DIVISION 2

Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. Uninsulated bonding conductor is included in every cable.

Armoured ControlApplications:

Unshielded armoured control cable is used for operation of control automation equipment. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use outdoors in exposed industrial applications.

Ratings:UL 1569 METALCLAD CABLE (TYPE MC)UL 44 THERMOSET INSULATED WIRES & CABLES (XLPE)UL 83 THERMOPLASTIC INSULATED WIRES (PVC/NYLON)PVC/NYLON (THWN, THHN-2) RATED – 75OC WET / 90OC DRYXLPE (XHHW-2, RHW-2) RATED - 90OC WET / 90OC DRYMC RATED FOR USE IN HAZARDOUS LOCATIONS:

CLASS I ZONE 2 CLASS II DIVISION 2Notes:XLPE is used for applications where improved electrical properties, mechanical properties and wet resistance are important. Uninsulated bonding conductor is included in every cable.

Armoured Power

Available in: XHHW-2 RHW-2 PVC/Nylon PVC

Page 56: Shaw Flex Catalogue

UL

Cabl

es

PVC Insulated Instrumentation: OS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 23021U200100700 0.89 0.035 5.4 0.211 26 38 2.5 64 29 13

2 Pair 20 AWG 300V 23021U200200700 1.02 0.040 8.1 0.317 53 79 3.8 97 45 20

4 Pair 20 AWG 300V 23021U200400700 1.02 0.040 9.1 0.360 71 105 4.3 110 77 35

8 Pair 20 AWG 300V 23021U200800700 1.27 0.050 12.1 0.477 128 190 5.7 145 141 64

12 Pair 20 AWG 300V 23021U201200700 1.27 0.050 14.4 0.569 176 262 6.8 173 205 93

16 Pair 20 AWG 300V 23021U201600700 1.27 0.050 16.0 0.628 217 324 7.5 191 269 122

24 Pair 20 AWG 300V 23021U202400700 1.52 0.060 20.0 0.788 326 485 9.5 240 397 180

1 Triad 20 AWG 300V 23031U200100700 0.89 0.035 5.6 0.220 31 46 2.6 67 37 17

2 Triad 20 AWG 300V 23031U200200700 1.02 0.040 8.8 0.346 65 96 4.1 105 61 28

4 Triad 20 AWG 300V 23031U200400700 1.02 0.040 10.0 0.395 92 138 4.7 120 109 49

8 Triad 20 AWG 300V 23031U200800700 1.27 0.050 13.3 0.525 171 254 6.3 160 205 93

12 Triad 20 AWG 300V 23031U201200700 1.27 0.050 16.0 0.629 238 354 7.5 192 301 137

16 Triad 20 AWG 300V 23031U201600700 1.52 0.060 18.2 0.716 314 467 8.6 218 397 180

1 Pair 18 AWG 300V 23021U180100700 0.89 0.035 6.2 0.243 36 53 2.9 74 39 18

2 Pair 18 AWG 300V 23021U180200700 1.02 0.040 9.5 0.372 69 103 4.5 114 65 29

4 Pair 18 AWG 300V 23021U180400700 1.27 0.050 11.4 0.447 107 159 5.4 136 117 53

8 Pair 18 AWG 300V 23021U180800700 1.27 0.050 14.5 0.569 182 270 6.8 173 221 100

12 Pair 18 AWG 300V 23021U181200700 1.52 0.060 17.9 0.704 268 399 8.5 215 325 147

16 Pair 18 AWG 300V 23021U181600700 1.52 0.060 19.8 0.779 335 498 9.3 237 429 195

24 Pair 18 AWG 300V 23021U182400700 1.78 0.070 24.8 0.975 496 738 11.7 297 637 289

1 Triad 18 AWG 300V 23031U180100700 0.89 0.035 6.5 0.255 43 64 3.1 78 52 24

2 Triad 18 AWG 300V 23031U180200700 1.27 0.050 10.9 0.430 98 145 5.2 131 91 41

4 Triad 18 AWG 300V 23031U180400700 1.27 0.050 12.5 0.492 142 211 5.9 150 169 77

8 Triad 18 AWG 300V 23031U180800700 1.52 0.060 16.5 0.651 260 387 7.8 198 325 147

12 Triad 18 AWG 300V 23031U181200700 1.52 0.060 19.9 0.782 369 549 9.4 238 481 218

16 Triad 18 AWG 300V 23031U181600700 1.52 0.060 22.0 0.867 464 690 10.4 264 637 289

1 Pair 16 AWG 300V 23021U160100700 0.89 0.035 6.8 0.267 47 69 3.2 81 54 25

2 Pair 16 AWG 300V 23021U160200700 1.27 0.050 11.0 0.434 98 145 5.2 132 95 43

4 Pair 16 AWG 300V 23021U160400700 1.27 0.050 12.6 0.497 142 211 6.0 151 178 81

8 Pair 16 AWG 300V 23021U160800700 1.52 0.060 16.7 0.658 261 388 7.9 200 343 155

12 Pair 16 AWG 300V 23021U161200700 1.52 0.060 20.1 0.791 367 547 9.5 241 507 230

16 Pair 16 AWG 300V 23021U161600700 1.52 0.060 22.3 0.877 462 687 10.5 267 672 305

24 Pair 16 AWG 300V 23021U162400700 1.78 0.070 28.0 1.101 689 1,025 13.2 335 1,002 454

1 Triad 16 AWG 300V 23031U160100700 0.89 0.035 7.1 0.281 57 85 3.4 85 75 34

2 Triad 16 AWG 300V 23031U160200700 1.27 0.050 12.1 0.478 126 188 5.7 146 137 62

4 Triad 16 AWG 300V 23031U160400700 1.27 0.050 14.0 0.549 192 285 6.6 167 260 118

8 Triad 16 AWG 300V 23031U160800700 1.52 0.060 18.5 0.730 358 533 8.8 223 507 230

12 Triad 16 AWG 300V 23031U161200700 1.52 0.060 22.4 0.882 511 760 10.6 269 755 342

16 Triad 16 AWG 300V 23031U161600700 1.78 0.070 25.4 1.000 669 995 12.0 305 1,002 454

Page 57: Shaw Flex Catalogue

Phone: 1 800-668-4842 55 email: [email protected]

UL Cables

PVC Instrumentation Insulated: ISOS (PLTC/ITC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 23022U200200700 1.02 0.040 8.5 0.333 60 89 4.0 102 45 20

4 Pair 20 AWG 300V 23022U200400700 1.02 0.040 9.6 0.380 84 125 4.6 116 77 35

8 Pair 20 AWG 300V 23022U200800700 1.27 0.050 12.8 0.504 153 228 6.0 154 141 64

12 Pair 20 AWG 300V 23022U201200700 1.27 0.050 15.3 0.603 214 319 7.2 184 205 93

16 Pair 20 AWG 300V 23022U201600700 1.52 0.060 17.4 0.687 282 419 8.2 209 269 122

24 Pair 20 AWG 300V 23022U202400700 1.52 0.060 21.3 0.838 401 597 10.1 255 397 180

2 Triad 20 AWG 300V 23032U200200700 1.02 0.040 9.3 0.366 73 109 4.4 112 61 28

4 Triad 20 AWG 300V 23032U200400700 1.27 0.050 11.2 0.439 114 170 5.3 134 109 49

8 Triad 20 AWG 300V 23032U200800700 1.27 0.050 14.2 0.558 198 294 6.7 170 205 93

12 Triad 20 AWG 300V 23032U201200700 1.52 0.060 17.6 0.691 292 434 8.3 211 301 137

16 Triad 20 AWG 300V 23032U201600700 1.52 0.060 19.4 0.764 367 546 9.2 233 397 180

2 Pair 18 AWG 300V 23022U180200700 1.02 0.040 9.9 0.391 79 118 4.7 119 65 29

4 Pair 18 AWG 300V 23022U180400700 1.27 0.050 11.9 0.469 127 188 5.6 143 117 53

8 Pair 18 AWG 300V 23022U180800700 1.27 0.050 15.2 0.599 219 326 7.2 183 221 100

12 Pair 18 AWG 300V 23022U181200700 1.52 0.060 18.9 0.742 322 479 8.9 226 325 147

16 Pair 18 AWG 300V 23022U181600700 1.52 0.060 20.9 0.822 406 604 9.9 251 429 195

24 Pair 18 AWG 300V 23022U182400700 1.78 0.070 26.2 1.030 604 899 12.4 314 637 289

2 Triad 18 AWG 300V 23032U180200700 1.27 0.050 11.5 0.453 110 164 5.4 138 91 41

4 Triad 18 AWG 300V 23032U180400700 1.27 0.050 13.2 0.520 162 241 6.2 158 169 77

8 Triad 18 AWG 300V 23032U180800700 1.52 0.060 17.5 0.689 299 445 8.3 210 325 147

12 Triad 18 AWG 300V 23032U181200700 1.52 0.060 21.1 0.830 424 631 10.0 253 481 218

16 Triad 18 AWG 300V 23032U181600700 1.78 0.070 23.9 0.942 554 825 11.3 287 637 289

2 Pair 16 AWG 300V 23022U160200700 1.27 0.050 11.5 0.454 114 170 5.4 138 95 43

4 Pair 16 AWG 300V 23022U160400700 1.27 0.050 13.2 0.521 170 253 6.2 159 178 81

8 Pair 16 AWG 300V 23022U160800700 1.52 0.060 17.5 0.690 315 469 8.3 210 343 155

12 Pair 16 AWG 300V 23022U161200700 1.52 0.060 21.1 0.832 448 667 10.0 254 507 230

16 Pair 16 AWG 300V 23022U161600700 1.78 0.070 24.0 0.944 586 873 11.3 288 672 305

24 Pair 16 AWG 300V 23022U162400700 1.78 0.070 29.5 1.160 851 1,266 13.9 354 1,002 454

2 Triad 16 AWG 300V 23032U160200700 1.27 0.050 12.8 0.503 144 214 6.0 153 137 62

4 Triad 16 AWG 300V 23032U160400700 1.27 0.050 14.7 0.580 220 327 7.0 177 260 118

8 Triad 16 AWG 300V 23032U160800700 1.52 0.060 19.6 0.771 415 617 9.3 235 507 230

12 Triad 16 AWG 300V 23032U161200700 1.78 0.070 24.2 0.954 611 910 11.4 291 755 342

16 Triad 16 AWG 300V 23032U161600700 1.78 0.070 26.9 1.059 780 1,161 12.7 323 1,002 454

Page 58: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated Instrumentation: OS (PLTC/ITC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 2W021U200100700 0.89 0.035 5.7 0.223 27 40 2.7 68 29 13

2 Pair 20 AWG 300V 2W021U200200700 1.02 0.040 8.6 0.338 56 83 4.1 103 45 20

4 Pair 20 AWG 300V 2W021U200400700 1.02 0.040 9.8 0.385 75 112 4.6 117 77 35

8 Pair 20 AWG 300V 2W021U200800700 1.27 0.050 13.0 0.512 136 203 6.1 156 141 64

12 Pair 20 AWG 300V 2W021U201200700 1.27 0.050 15.5 0.612 188 280 7.3 187 205 93

16 Pair 20 AWG 300V 2W021U201600700 1.52 0.060 17.7 0.697 247 367 8.4 212 269 122

24 Pair 20 AWG 300V 2W021U202400700 1.52 0.060 21.6 0.851 348 518 10.2 259 397 180

1 Triad 20 AWG 300V 2W031U200100700 0.89 0.035 5.9 0.233 33 49 2.8 71 37 17

2 Triad 20 AWG 300V 2W031U200200700 1.02 0.040 9.4 0.370 69 103 4.4 113 61 28

4 Triad 20 AWG 300V 2W031U200400700 1.27 0.050 11.3 0.443 107 159 5.3 135 109 49

8 Triad 20 AWG 300V 2W031U200800700 1.27 0.050 14.3 0.564 182 271 6.8 172 205 93

12 Triad 20 AWG 300V 2W031U201200700 1.52 0.060 17.7 0.698 269 400 8.4 213 301 137

16 Triad 20 AWG 300V 2W031U201600700 1.52 0.060 19.6 0.772 336 500 9.3 235 397 180

1 Pair 18 AWG 300V 2W021U180100700 0.89 0.035 6.2 0.243 36 53 2.9 74 39 18

2 Pair 18 AWG 300V 2W021U180200700 1.02 0.040 9.5 0.372 69 103 4.5 114 65 29

4 Pair 18 AWG 300V 2W021U180400700 1.27 0.050 11.4 0.447 106 158 5.4 136 117 53

8 Pair 18 AWG 300V 2W021U180800700 1.27 0.050 14.5 0.569 180 268 6.8 173 221 100

12 Pair 18 AWG 300V 2W021U181200700 1.52 0.060 17.9 0.704 266 395 8.5 215 325 147

16 Pair 18 AWG 300V 2W021U181600700 1.52 0.060 19.8 0.779 332 494 9.3 237 429 195

24 Pair 18 AWG 300V 2W021U182400700 1.78 0.070 24.8 0.975 491 731 11.7 297 637 289

1 Triad 18 AWG 300V 2W031U180100700 0.89 0.035 6.5 0.255 43 63 3.1 78 52 24

2 Triad 18 AWG 300V 2W031U180200700 1.27 0.050 10.9 0.430 97 144 5.2 131 91 41

4 Triad 18 AWG 300V 2W031U180400700 1.27 0.050 12.5 0.492 141 209 5.9 150 169 77

8 Triad 18 AWG 300V 2W031U180800700 1.52 0.060 16.5 0.651 258 384 7.8 198 325 147

12 Triad 18 AWG 300V 2W031U181200700 1.52 0.060 19.9 0.782 365 544 9.4 238 481 218

16 Triad 18 AWG 300V 2W031U181600700 1.52 0.060 22.0 0.867 459 684 10.4 264 637 289

1 Pair 16 AWG 300V 2W021U160100700 0.89 0.035 6.8 0.267 46 69 3.2 81 54 25

2 Pair 16 AWG 300V 2W021U160200700 1.27 0.050 11.0 0.434 97 144 5.2 132 95 43

4 Pair 16 AWG 300V 2W021U160400700 1.27 0.050 12.6 0.497 141 209 6.0 151 178 81

8 Pair 16 AWG 300V 2W021U160800700 1.52 0.060 16.7 0.658 259 385 7.9 200 343 155

12 Pair 16 AWG 300V 2W021U161200700 1.52 0.060 20.1 0.791 365 543 9.5 241 507 230

16 Pair 16 AWG 300V 2W021U161600700 1.52 0.060 22.3 0.877 458 681 10.5 267 672 305

24 Pair 16 AWG 300V 2W021U162400700 1.78 0.070 28.0 1.101 683 1,016 13.2 335 1,002 454

1 Triad 16 AWG 300V 2W031U160100700 0.89 0.035 7.1 0.281 57 85 3.4 85 75 34

2 Triad 16 AWG 300V 2W031U160200700 1.27 0.050 12.1 0.478 126 187 5.7 146 137 62

4 Triad 16 AWG 300V 2W031U160400700 1.27 0.050 14.0 0.549 190 283 6.6 167 260 118

8 Triad 16 AWG 300V 2W031U160800700 1.52 0.060 18.5 0.730 355 529 8.8 223 507 230

12 Triad 16 AWG 300V 2W031U161200700 1.52 0.060 22.4 0.882 507 754 10.6 269 755 342

16 Triad 16 AWG 300V 2W031U161600700 1.78 0.070 25.4 1.000 663 987 12.0 305 1,002 454

Page 59: Shaw Flex Catalogue

Phone: 1 800-668-4842 57 email: [email protected]

UL Cables

XLPE Insulated Instrumentation: ISOS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 2W022U200200700 1.02 0.040 9.0 0.355 64 95 4.3 108 45 20

4 Pair 20 AWG 300V 2W022U200400700 1.27 0.050 10.8 0.426 97 144 5.1 130 77 35

8 Pair 20 AWG 300V 2W022U200800700 1.27 0.050 13.7 0.540 163 243 6.5 165 141 64

12 Pair 20 AWG 300V 2W022U201200700 1.52 0.060 17.0 0.668 239 355 8.0 203 205 93

16 Pair 20 AWG 300V 2W022U201600700 1.52 0.060 18.7 0.737 298 443 8.8 225 269 122

24 Pair 20 AWG 300V 2W022U202400700 1.52 0.060 22.9 0.902 425 632 10.8 275 397 180

2 Triad 20 AWG 300V 2W032U200200700 1.02 0.040 9.9 0.391 77 115 4.7 119 61 28

4 Triad 20 AWG 300V 2W032U200400700 1.27 0.050 11.9 0.469 122 182 5.6 143 109 49

8 Triad 20 AWG 300V 2W032U200800700 1.27 0.050 15.2 0.599 210 313 7.2 183 205 93

12 Triad 20 AWG 300V 2W032U201200700 1.52 0.060 18.9 0.743 309 460 8.9 226 301 137

16 Triad 20 AWG 300V 2W032U201600700 1.52 0.060 20.9 0.822 388 578 9.9 251 397 180

2 Pair 18 AWG 300V 2W022U180200700 1.02 0.040 9.9 0.391 79 117 4.7 119 65 29

4 Pair 18 AWG 300V 2W022U180400700 1.27 0.050 11.9 0.469 126 187 5.6 143 117 53

8 Pair 18 AWG 300V 2W022U180800700 1.27 0.050 15.2 0.599 217 323 7.2 183 221 100

12 Pair 18 AWG 300V 2W022U181200700 1.52 0.060 18.9 0.742 320 476 8.9 226 325 147

16 Pair 18 AWG 300V 2W022U181600700 1.52 0.060 20.9 0.822 403 600 9.9 251 429 195

24 Pair 18 AWG 300V 2W022U182400700 1.78 0.070 26.2 1.030 600 892 12.4 314 637 289

2 Triad 18 AWG 300V 2W032U180200700 1.27 0.050 11.5 0.453 110 163 5.4 138 91 41

4 Triad 18 AWG 300V 2W032U180400700 1.27 0.050 13.2 0.520 161 240 6.2 158 169 77

8 Triad 18 AWG 300V 2W032U180800700 1.52 0.060 17.5 0.689 297 442 8.3 210 325 147

12 Triad 18 AWG 300V 2W032U181200700 1.52 0.060 21.1 0.830 421 626 10.0 253 481 218

16 Triad 18 AWG 300V 2W032U181600700 1.78 0.070 23.9 0.942 550 818 11.3 287 637 289

2 Pair 16 AWG 300V 2W022U160200700 1.27 0.050 11.5 0.454 114 170 5.4 138 95 43

4 Pair 16 AWG 300V 2W022U160400700 1.27 0.050 13.2 0.521 169 252 6.2 159 178 81

8 Pair 16 AWG 300V 2W022U160800700 1.52 0.060 17.5 0.690 313 466 8.3 210 343 155

12 Pair 16 AWG 300V 2W022U161200700 1.52 0.060 21.1 0.832 445 663 10.0 254 507 230

16 Pair 16 AWG 300V 2W022U161600700 1.78 0.070 24.0 0.944 583 867 11.3 288 672 305

24 Pair 16 AWG 300V 2W022U162400700 1.78 0.070 29.5 1.160 845 1,258 13.9 354 1,002 454

2 Triad 16 AWG 300V 2W032U160200700 1.27 0.050 12.8 0.503 143 213 6.0 153 137 62

4 Triad 16 AWG 300V 2W032U160400700 1.27 0.050 14.7 0.580 219 325 7.0 177 260 118

8 Triad 16 AWG 300V 2W032U160800700 1.52 0.060 19.6 0.771 412 613 9.3 235 507 230

12 Triad 16 AWG 300V 2W032U161200700 1.78 0.070 24.2 0.954 607 904 11.4 291 755 342

16 Triad 16 AWG 300V 2W032U161600700 1.78 0.070 26.9 1.059 774 1,153 12.7 323 1,002 454

Page 60: Shaw Flex Catalogue

UL

Cabl

es

PVC Insulated Thermocouple: OS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 7P021U200147700 0.89 0.035 5.3 0.207 26 38 2.5 63 29 13

2 Pair 20 AWG 300V 7P021U200247700 1.02 0.040 7.7 0.303 49 73 3.6 92 45 20

4 Pair 20 AWG 300V 7P021U200447700 1.02 0.040 8.7 0.343 67 100 4.1 105 77 35

8 Pair 20 AWG 300V 7P021U200647700 1.27 0.050 10.8 0.424 100 148 5.1 129 109 49

6 Pair 20 AWG 300V 7P021U200847700 1.27 0.050 11.5 0.454 120 179 5.4 138 141 64

12 Pair 20 AWG 300V 7P021U201247700 1.27 0.050 13.7 0.540 162 241 6.5 165 205 93

16 Pair 20 AWG 300V 7P021U201647700 1.27 0.050 15.1 0.595 203 302 7.1 181 269 122

24 Pair 20 AWG 300V 7P021U202447700 1.52 0.060 19.0 0.746 302 450 9.0 228 397 180

36 Pair 20 AWG 300V 7P021U203647700 1.52 0.060 21.5 0.847 418 621 10.2 258 589 267

50 Pair 20 AWG 300V 7P021U205047700 1.78 0.070 25.2 0.993 571 850 11.9 303 813 369

1 Pair 18 AWG 300V 7P021U180147700 0.89 0.035 6.0 0.235 34 50 2.8 72 39 18

2 Pair 18 AWG 300V 7P021U180247700 1.02 0.040 8.9 0.352 66 98 4.2 107 65 29

4 Pair 18 AWG 300V 7P021U180447700 1.27 0.050 10.7 0.422 99 148 5.1 129 117 53

6 Pair 18 AWG 300V 7P021U180647700 1.27 0.050 12.6 0.497 136 203 6.0 151 169 77

8 Pair 18 AWG 300V 7P021U180847700 1.27 0.050 13.6 0.534 168 250 6.4 163 221 100

12 Pair 18 AWG 300V 7P021U181247700 1.52 0.060 16.8 0.661 245 365 7.9 201 325 147

16 Pair 18 AWG 300V 7P021U181647700 1.52 0.060 18.5 0.730 306 456 8.8 222 429 195

24 Pair 18 AWG 300V 7P021U182447700 1.52 0.060 22.7 0.893 437 650 10.7 272 637 289

30 Pair 18 AWG 300V 7P021U183647700 1.78 0.070 26.4 1.038 631 939 12.5 316 949 430

50 Pair 18 AWG 300V 7P021U185047700 1.78 0.070 30.3 1.193 841 1,251 14.3 364 1,313 596

1 Pair 16 AWG 300V 7P021U160147700 0.89 0.035 6.5 0.257 44 66 3.1 78 54 25

2 Pair 16 AWG 300V 7P021U160247700 1.02 0.040 9.9 0.390 83 123 4.7 119 95 43

4 Pair 16 AWG 300V 7P021U160447700 1.27 0.050 11.9 0.468 133 197 5.6 143 178 81

6 Pair 18 AWG 300V 7P021U160647700 1.27 0.050 14.1 0.554 187 278 6.7 169 260 118

8 Pair 16 AWG 300V 7P021U160847700 1.27 0.050 15.2 0.598 230 343 7.2 182 343 155

12 Pair 16 AWG 300V 7P021U161247700 1.52 0.060 18.8 0.740 339 504 8.9 226 507 230

16 Pair 16 AWG 300V 7P021U161647700 1.52 0.060 20.8 0.820 428 637 9.8 250 672 305

24 Pair 16 AWG 300V 7P021U162447700 1.78 0.070 26.1 1.028 638 949 12.3 313 1,002 454

30 Pair 16 AWG 300V 7P021U163647700 1.78 0.070 29.8 1.172 899 1,337 14.1 357 1,496 679

50 Pair 16 AWG 300V 7P021U165047700 2.03 0.080 34.8 1.371 1,234 1,837 16.5 418 2,073 940

Page 61: Shaw Flex Catalogue

Phone: 1 800-668-4842 59 email: [email protected]

UL Cables

PVC Insulated Thermocouple: ISOS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 7P022U200247700 1.02 0.040 8.3 0.326 60 89 3.9 99 45 20

4 Pair 20 AWG 300V 7P022U200447700 1.02 0.040 9.4 0.371 83 123 4.5 113 77 35

8 Pair 20 AWG 300V 7P022U200647700 1.27 0.050 11.7 0.459 124 184 5.5 140 109 49

6 Pair 20 AWG 300V 7P022U200847700 1.27 0.050 12.5 0.492 150 224 5.9 150 141 64

12 Pair 20 AWG 300V 7P022U201247700 1.27 0.050 14.9 0.588 210 312 7.1 179 205 93

16 Pair 20 AWG 300V 7P022U201647700 1.52 0.060 17.0 0.670 274 408 8.0 204 269 122

24 Pair 20 AWG 300V 7P022U202447700 1.52 0.060 20.7 0.816 392 583 9.8 249 397 180

36 Pair 20 AWG 300V 7P022U203647700 1.78 0.070 24.1 0.949 564 840 11.4 289 589 267

50 Pair 20 AWG 300V 7P022U205047700 1.78 0.070 27.6 1.088 754 1,121 13.1 332 813 369

2 Pair 18 AWG 300V 7P022U180247700 1.02 0.040 9.6 0.376 77 114 4.5 115 65 29

4 Pair 18 AWG 300V 7P022U180447700 1.27 0.050 11.5 0.452 120 179 5.4 138 117 53

6 Pair 18 AWG 300V 7P022U180647700 1.27 0.050 13.6 0.534 169 252 6.4 163 169 77

8 Pair 18 AWG 300V 7P022U180847700 1.27 0.050 14.6 0.575 208 310 6.9 175 221 100

12 Pair 18 AWG 300V 7P022U181247700 1.52 0.060 18.1 0.713 307 457 8.6 217 325 147

16 Pair 18 AWG 300V 7P022U181647700 1.52 0.060 20.0 0.788 386 575 9.5 240 429 195

24 Pair 18 AWG 300V 7P022U182447700 1.78 0.070 25.1 0.987 573 852 11.8 301 637 289

30 Pair 18 AWG 300V 7P022U183647700 1.78 0.070 28.6 1.125 806 1,199 13.5 343 949 430

50 Pair 18 AWG 300V 7P022U185047700 2.03 0.080 33.4 1.316 1,105 1,644 15.8 401 1,313 596

2 Pair 16 AWG 300V 7P022U160247700 1.27 0.050 11.1 0.436 108 161 5.2 133 95 43

4 Pair 16 AWG 300V 7P022U160447700 1.27 0.050 12.7 0.499 162 242 6.0 152 178 81

6 Pair 18 AWG 300V 7P022U160647700 1.27 0.050 15.1 0.593 231 343 7.1 181 260 118

8 Pair 16 AWG 300V 7P022U160847700 1.52 0.060 16.8 0.661 301 448 7.9 201 343 155

12 Pair 16 AWG 300V 7P022U161247700 1.52 0.060 20.2 0.795 428 637 9.5 242 507 230

16 Pair 16 AWG 300V 7P022U161647700 1.52 0.060 22.4 0.881 543 807 10.6 269 672 305

24 Pair 16 AWG 300V 7P022U162447700 1.78 0.070 28.1 1.106 810 1,205 13.3 337 1,002 454

30 Pair 16 AWG 300V 7P022U163647700 1.78 0.070 32.1 1.264 1,150 1,711 15.2 385 1,496 679

50 Pair 16 AWG 300V 7P022U165047700 2.03 0.080 37.6 1.479 1,585 2,358 17.7 451 2,073 940

Page 62: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated Thermocouple: OS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 20 AWG 300V 7W021U200147700 0.89 0.035 5.6 0.219 27 41 2.6 67 29 13

2 Pair 20 AWG 300V 7W021U200247700 1.02 0.040 8.2 0.324 54 80 3.9 99 45 20

4 Pair 20 AWG 300V 7W021U200447700 1.02 0.040 9.4 0.368 72 107 4.4 112 77 35

8 Pair 20 AWG 300V 7W021U200647700 1.27 0.050 11.6 0.455 107 159 5.5 139 109 49

6 Pair 20 AWG 300V 7W021U200847700 1.27 0.050 12.4 0.489 128 191 5.9 149 141 64

12 Pair 20 AWG 300V 7W021U201247700 1.27 0.050 14.8 0.583 177 263 7.0 178 205 93

16 Pair 20 AWG 300V 7W021U201647700 1.52 0.060 16.9 0.664 230 343 8.0 203 269 122

24 Pair 20 AWG 300V 7W021U202447700 1.52 0.060 20.6 0.809 326 485 9.7 247 397 180

36 Pair 20 AWG 300V 7W021U203647700 1.78 0.070 23.9 0.941 466 693 11.3 287 589 267

50 Pair 20 AWG 300V 7W021U205047700 1.78 0.070 27.4 1.079 617 918 12.9 329 813 369

1 Pair 18 AWG 300V 7W021U180147700 0.89 0.035 6.0 0.235 34 50 2.8 72 39 18

2 Pair 18 AWG 300V 7W021U180247700 1.02 0.040 8.9 0.352 65 97 4.2 107 65 29

4 Pair 18 AWG 300V 7W021U180447700 1.27 0.050 10.7 0.422 99 147 5.1 129 117 53

6 Pair 18 AWG 300V 7W021U180647700 1.27 0.050 12.6 0.497 135 201 6.0 151 169 77

8 Pair 18 AWG 300V 7W021U180847700 1.27 0.050 13.6 0.534 167 248 6.4 163 221 100

12 Pair 18 AWG 300V 7W021U181247700 1.52 0.060 16.8 0.661 243 362 7.9 201 325 147

16 Pair 18 AWG 300V 7W021U181647700 1.52 0.060 18.5 0.730 304 452 8.8 222 429 195

24 Pair 18 AWG 300V 7W021U182447700 1.52 0.060 22.7 0.893 434 645 10.7 272 637 289

30 Pair 18 AWG 300V 7W021U183647700 1.78 0.070 26.4 1.038 626 931 12.5 316 949 430

50 Pair 18 AWG 300V 7W021U185047700 1.78 0.070 30.3 1.193 834 1,240 14.3 364 1,313 596

1 Pair 16 AWG 300V 7W021U160147700 0.89 0.035 6.5 0.257 44 65 3.1 78 54 25

2 Pair 16 AWG 300V 7W021U160247700 1.02 0.040 9.9 0.390 82 122 4.7 119 95 43

4 Pair 16 AWG 300V 7W021U160447700 1.27 0.050 11.9 0.468 132 196 5.6 143 178 81

6 Pair 18 AWG 300V 7W021U160647700 1.27 0.050 14.1 0.554 186 276 6.7 169 260 118

8 Pair 16 AWG 300V 7W021U160847700 1.27 0.050 15.2 0.598 229 341 7.2 182 343 155

12 Pair 16 AWG 300V 7W021U161247700 1.52 0.060 18.8 0.740 337 501 8.9 226 507 230

16 Pair 16 AWG 300V 7W021U161647700 1.52 0.060 20.8 0.820 425 633 9.8 250 672 305

24 Pair 16 AWG 300V 7W021U162447700 1.78 0.070 26.1 1.028 633 942 12.3 313 1,002 454

30 Pair 16 AWG 300V 7W021U163647700 1.78 0.070 29.8 1.172 892 1,328 14.1 357 1,496 679

50 Pair 16 AWG 300V 7W021U165047700 2.03 0.080 34.8 1.371 1,225 1,823 16.5 418 2,073 940

Page 63: Shaw Flex Catalogue

Phone: 1 800-668-4842 61 email: [email protected]

UL Cables

XLPE Insulated Thermocouple: ISOS (PLTC/ITC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 20 AWG 300V 7W022U200247700 1.02 0.040 8.8 0.348 63 93 4.2 106 45 20

4 Pair 20 AWG 300V 7W022U200447700 1.02 0.040 10.1 0.397 87 130 4.8 121 77 35

8 Pair 20 AWG 300V 7W022U200647700 1.27 0.050 12.5 0.491 130 194 5.9 150 109 49

6 Pair 20 AWG 300V 7W022U200847700 1.27 0.050 13.4 0.528 160 238 6.3 161 141 64

12 Pair 20 AWG 300V 7W022U201247700 1.52 0.060 16.6 0.653 234 348 7.8 199 205 93

16 Pair 20 AWG 300V 7W022U201647700 1.52 0.060 18.3 0.721 291 434 8.6 220 269 122

24 Pair 20 AWG 300V 7W022U202447700 1.52 0.060 22.4 0.881 414 617 10.6 268 397 180

36 Pair 20 AWG 300V 7W022U203647700 1.78 0.070 26.0 1.024 598 890 12.3 312 589 267

50 Pair 20 AWG 300V 7W022U205047700 1.78 0.070 29.9 1.177 795 1,183 14.1 359 813 369

2 Pair 18 AWG 300V 7W022U180247700 1.02 0.040 9.6 0.376 76 114 4.5 115 65 29

4 Pair 18 AWG 300V 7W022U180447700 1.27 0.050 11.5 0.452 120 178 5.4 138 117 53

6 Pair 18 AWG 300V 7W022U180647700 1.27 0.050 13.6 0.534 168 251 6.4 163 169 77

8 Pair 18 AWG 300V 7W022U180847700 1.27 0.050 14.6 0.575 207 308 6.9 175 221 100

12 Pair 18 AWG 300V 7W022U181247700 1.52 0.060 18.1 0.713 305 454 8.6 217 325 147

16 Pair 18 AWG 300V 7W022U181647700 1.52 0.060 20.0 0.788 384 571 9.5 240 429 195

24 Pair 18 AWG 300V 7W022U182447700 1.78 0.070 25.1 0.987 569 847 11.8 301 637 289

30 Pair 18 AWG 300V 7W022U183647700 1.78 0.070 28.6 1.125 800 1,191 13.5 343 949 430

50 Pair 18 AWG 300V 7W022U185047700 2.03 0.080 33.4 1.316 1,097 1,633 15.8 401 1,313 596

2 Pair 16 AWG 300V 7W022U160247700 1.27 0.050 11.1 0.436 108 161 5.2 133 95 43

4 Pair 16 AWG 300V 7W022U160447700 1.27 0.050 12.7 0.499 162 241 6.0 152 178 81

6 Pair 18 AWG 300V 7W022U160647700 1.27 0.050 15.1 0.593 230 342 7.1 181 260 118

8 Pair 16 AWG 300V 7W022U160847700 1.52 0.060 16.8 0.661 300 446 7.9 201 343 155

12 Pair 16 AWG 300V 7W022U161247700 1.52 0.060 20.2 0.795 426 634 9.5 242 507 230

16 Pair 16 AWG 300V 7W022U161647700 1.52 0.060 22.4 0.881 540 803 10.6 269 672 305

24 Pair 16 AWG 300V 7W022U162447700 1.78 0.070 28.1 1.106 805 1,199 13.3 337 1,002 454

30 Pair 16 AWG 300V 7W022U163647700 1.78 0.070 32.1 1.264 1,144 1,702 15.2 385 1,496 679

50 Pair 16 AWG 300V 7W022U165047700 2.03 0.080 37.6 1.479 1,576 2,345 17.7 451 2,073 940

Page 64: Shaw Flex Catalogue

UL

Cabl

es

PVC/Nylon Insulated Instrumentation Tray: OS (TC) current

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 29021U180100700 1.27 0.050 16.6 0.655 184 273 7.9 200 47 21

2 Pair 18 AWG 600V 29021U180200700 1.27 0.050 20.0 0.789 259 385 9.5 241 65 29

4 Pair 18 AWG 600V 29021U180400700 1.27 0.050 21.9 0.863 315 469 10.4 263 117 53

8 Pair 18 AWG 600V 29021U180800700 1.27 0.050 26.3 1.036 455 677 12.4 316 221 100

12 Pair 18 AWG 600V 29021U181200700 1.27 0.050 28.4 1.118 544 809 13.4 341 325 147

16 Pair 18 AWG 600V 29021U181600700 1.27 0.050 30.1 1.187 632 941 14.2 362 429 195

24 Pair 18 AWG 600V 29021U182400700 1.27 0.050 35.2 1.386 840 1,250 16.6 422 637 289

36 Pair 18 AWG 600V 29021U183600700 1.27 0.050 17.2 0.679 203 302 8.1 207 54 25

50 Pair 18 AWG 600V 29021U185000700 1.27 0.050 21.1 0.831 293 436 10.0 253 103 47

1 Triad 18 AWG 600V 29031U180100700 1.27 0.050 23.2 0.915 368 547 11.0 279 185 84

2 Triad 18 AWG 600V 29031U180200700 1.27 0.050 28.2 1.111 548 816 13.3 339 350 159

4 Triad 18 AWG 600V 29031U180400700 1.27 0.050 30.2 1.189 666 991 14.3 362 515 234

8 Triad 18 AWG 600V 29031U180800700 1.27 0.050 32.6 1.285 789 1,174 15.4 392 680 308

12 Triad 18 AWG 600V 29031U181200700 1.27 0.050 38.4 1.511 1,067 1,587 18.1 461 1,009 458

16 Triad 18 AWG 600V 29031U181600700 1.14 0.045 7.2 0.283 44 65 3.4 86 360 163

24 Triad 18 AWG 600V 29031U182400700 1.14 0.045 7.8 0.307 55 82 3.7 94 375 170

1 Pair 16 AWG 600V 29021U160100700 1.14 0.045 7.2 0.283 44 65 3.4 86 360 163

2 Pair 16 AWG 600V 29021U160200700 1.14 0.045 7.8 0.307 55 82 3.7 94 375 170

4 Pair 16 AWG 600V 29021U160400700 1.27 0.050 16.6 0.655 184 273 7.9 200 360 163

8 Pair 16 AWG 600V 29021U160800700 1.27 0.050 20.0 0.789 259 385 9.5 241 65 29

12 Pair 16 AWG 600V 29021U161200700 1.27 0.050 21.9 0.863 315 469 10.4 263 117 53

16 Pair 16 AWG 600V 29021U161600700 1.27 0.050 26.3 1.036 455 677 12.4 316 221 100

24 Pair 16 AWG 600V 29021U162400700 1.27 0.050 28.4 1.118 544 809 13.4 341 325 147

36 Pair 16 AWG 600V 29021U163600700 1.27 0.050 30.1 1.187 632 941 14.2 362 429 195

50 Pair 16 AWG 600V 29021U165000700 1.27 0.050 35.2 1.386 840 1,250 16.6 422 637 289

1 Triad 16 AWG 600V 29031U160100700 1.27 0.050 17.2 0.679 203 302 8.1 207 54 25

2 Triad 16 AWG 600V 29031U160200700 1.27 0.050 21.1 0.831 293 436 10.0 253 103 47

4 Triad 16 AWG 600V 29031U160400700 1.27 0.050 23.2 0.915 368 547 11.0 279 185 84

8 Triad 16 AWG 600V 29031U160800700 1.27 0.050 28.2 1.111 548 816 13.3 339 350 159

12 Triad 16 AWG 600V 29031U161200700 1.27 0.050 30.2 1.189 666 991 14.3 362 515 234

16 Triad 16 AWG 600V 29031U161600700 1.27 0.050 32.6 1.285 789 1,174 15.4 392 680 308

24 Triad 16 AWG 600V 29031U162400700 1.27 0.050 38.4 1.511 1,067 1,587 18.1 461 1,009 458

Page 65: Shaw Flex Catalogue

Phone: 1 800-668-4842 63 email: [email protected]

UL Cables

PVC/Nylon Insulated Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 29022U180200700 1.14 0.045 11.1 0.437 91 136 5.2 133 65 29

4 Pair 18 AWG 600V 29022U180400700 1.14 0.045 12.8 0.502 131 196 6.0 153 117 53

8 Pair 18 AWG 600V 29022U180800700 1.52 0.060 17.2 0.679 249 371 8.1 207 221 100

12 Pair 18 AWG 600V 29022U181200700 1.52 0.060 20.8 0.817 350 521 9.8 249 325 147

16 Pair 18 AWG 600V 29022U181600700 2.03 0.080 24.0 0.947 473 704 11.4 289 429 195

24 Pair 18 AWG 600V 29022U182400700 2.03 0.080 29.4 1.158 675 1,004 13.9 353 637 289

36 Pair 18 AWG 600V 29022U183600700 2.03 0.080 33.6 1.321 940 1,399 15.9 403 949 430

50 Pair 18 AWG 600V 29022U185000700 2.03 0.080 38.7 1.523 1,257 1,870 18.3 464 1,313 596

2 Triad 18 AWG 600V 29032U180200700 1.14 0.045 12.3 0.484 114 169 5.8 147 91 41

4 Triad 18 AWG 600V 29032U180400700 1.52 0.060 14.9 0.588 186 276 7.1 179 169 77

8 Triad 18 AWG 600V 29032U180800700 1.52 0.060 19.2 0.756 324 483 9.1 230 325 147

12 Triad 18 AWG 600V 29032U181200700 2.03 0.080 24.2 0.954 494 735 11.4 291 481 218

16 Triad 18 AWG 600V 29032U181600700 2.03 0.080 26.8 1.056 620 922 12.7 322 637 289

24 Triad 18 AWG 600V 29032U182400700 2.03 0.080 33.0 1.298 888 1,322 15.6 396 949 430

2 Pair 16 AWG 600V 29022U160200700 1.14 0.045 12.2 0.480 116 173 5.8 146 95 43

4 Pair 16 AWG 600V 29022U160400700 1.52 0.060 14.8 0.584 191 284 7.0 178 178 81

8 Pair 16 AWG 600V 29022U160800700 1.52 0.060 19.1 0.750 335 498 9.0 229 343 155

12 Pair 16 AWG 600V 29022U161200700 2.03 0.080 24.1 0.947 509 758 11.4 289 507 230

16 Pair 16 AWG 600V 29022U161600700 2.03 0.080 26.6 1.048 640 953 12.6 319 672 305

24 Pair 16 AWG 600V 29022U162400700 2.03 0.080 32.7 1.288 920 1,369 15.5 393 1,002 454

36 Pair 16 AWG 600V 29022U163600700 2.03 0.080 37.4 1.473 1,300 1,935 17.7 449 1,496 679

50 Pair 16 AWG 600V 29022U165000700 2.03 0.080 43.2 1.701 1,751 2,606 20.4 519 2,073 940

2 Triad 16 AWG 600V 29032U160200700 1.14 0.045 13.6 0.533 149 222 6.4 163 137 62

4 Triad 16 AWG 600V 29032U160400700 1.52 0.060 16.5 0.648 246 366 7.8 197 260 118

8 Triad 16 AWG 600V 29032U160800700 1.52 0.060 21.3 0.838 439 653 10.1 255 507 230

12 Triad 16 AWG 600V 29032U161200700 2.03 0.080 26.9 1.058 670 997 12.7 322 755 342

16 Triad 16 AWG 600V 29032U161600700 2.03 0.080 29.8 1.174 846 1,259 14.1 358 1,002 454

24 Triad 16 AWG 600V 29032U162400700 2.03 0.080 36.8 1.448 1,227 1,827 17.4 441 1,496 679

Page 66: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated PVC Jacketed Instrumentation Tray: OS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 2C021U180100700 1.14 0.045 8.2 0.323 51 75 3.9 98 39 18

2 Pair 18 AWG 600V 2C021U180200700 1.14 0.045 12.4 0.487 94 139 5.8 148 65 29

4 Pair 18 AWG 600V 2C021U180400700 1.52 0.060 15.0 0.592 145 216 7.1 180 117 53

8 Pair 18 AWG 600V 2C021U180800700 1.52 0.060 19.3 0.761 243 361 9.1 232 221 100

12 Pair 18 AWG 600V 2C021U181200700 2.03 0.080 24.4 0.961 372 553 11.5 293 325 147

16 Pair 18 AWG 600V 2C021U181600700 2.03 0.080 27.0 1.064 457 680 12.8 324 429 195

24 Pair 18 AWG 600V 2C021U182400700 2.03 0.080 33.2 1.309 644 958 15.7 399 637 289

1 Triad 18 AWG 600V 2C031U180100700 1.14 0.045 8.6 0.339 59 87 4.1 103 52 24

2 Triad 18 AWG 600V 2C031U180200700 1.52 0.060 14.4 0.568 137 204 6.8 173 91 41

4 Triad 18 AWG 600V 2C031U180400700 1.52 0.060 16.6 0.653 189 282 7.8 199 169 77

8 Triad 18 AWG 600V 2C031U180800700 2.03 0.080 22.5 0.885 359 534 10.6 270 325 147

12 Triad 18 AWG 600V 2C031U181200700 2.03 0.080 27.1 1.067 500 744 12.8 325 481 218

16 Triad 18 AWG 600V 2C031U181600700 2.03 0.080 30.1 1.184 619 921 14.2 361 637 289

24 Triad 18 AWG 600V 2C031U182400700 2.03 0.080 37.1 1.462 886 1,319 17.5 445 949 430

1 Pair 16 AWG 600V 2C021U160100700 1.14 0.045 8.8 0.347 62 92 4.2 106 54 25

2 Pair 16 AWG 600V 2C021U160200700 1.14 0.045 13.4 0.529 117 175 6.3 161 95 43

4 Pair 16 AWG 600V 2C021U160400700 1.52 0.060 16.3 0.642 182 271 7.7 196 178 81

8 Pair 16 AWG 600V 2C021U160800700 1.52 0.060 21.1 0.830 312 465 10.0 253 343 155

12 Pair 16 AWG 600V 2C021U1612000700 2.03 0.080 26.6 1.048 463 690 12.6 319 507 230

16 Pair 16 AWG 600V 2C021U161600700 2.03 0.080 29.5 1.162 592 881 13.9 354 672 305

24 Pair 16 AWG 600V 2C021U162400700 2.03 0.080 36.4 1.434 847 1,261 17.2 437 1,002 454

1 Triad 16 AWG 600V 2C031U160100700 1.14 0.045 9.3 0.365 75 111 4.4 111 75 34

2 Triad 16 AWG 600V 2C031U160200700 1.52 0.060 15.6 0.616 168 251 7.4 188 137 62

4 Triad 16 AWG 600V 2C031U160400700 1.52 0.060 18.1 0.711 242 360 8.5 217 260 118

8 Triad 16 AWG 600V 2C031U160800700 2.03 0.080 24.5 0.964 463 689 11.6 294 507 230

12 Triad 16 AWG 600V 2C031U161200700 2.03 0.080 29.6 1.166 652 971 14.0 355 755 342

16 Triad 16 AWG 600V 2C031U161600700 2.03 0.080 32.9 1.297 816 1,214 15.6 395 1,002 454

24 Triad 16 AWG 600V 2C031U162400700 2.03 0.080 40.8 1.605 1,179 1,755 19.3 489 1,496 679

Page 67: Shaw Flex Catalogue

Phone: 1 800-668-4842 65 email: [email protected]

UL Cables

XLPE Insulated PVC Jacketed Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 2C022U180200700 1.14 0.045 12.9 0.509 107 160 6.1 155 65 29

4 Pair 18 AWG 600V 2C022U180400700 1.52 0.060 15.7 0.618 166 247 7.4 188 117 53

8 Pair 18 AWG 600V 2C022U180800700 1.52 0.060 20.3 0.797 283 422 9.6 243 221 100

12 Pair 18 AWG 600V 2C022U181200700 2.03 0.080 25.6 1.006 432 642 12.1 307 325 147

16 Pair 18 AWG 600V 2C022U181600700 2.03 0.080 28.3 1.116 535 796 13.4 340 429 195

24 Pair 18 AWG 600V 2C022U182400700 2.03 0.080 34.9 1.374 763 1,135 16.5 419 637 289

2 Triad 18 AWG 600V 2C022U185000700 2.79 0.110 47.8 1.880 1,515 2,255 22.6 573 1,313 596

4 Triad 18 AWG 600V 2C032U180200700 1.52 0.060 15.1 0.596 151 225 7.2 182 91 41

8 Triad 18 AWG 600V 2C032U180400700 1.52 0.060 17.5 0.687 213 316 8.2 209 169 77

12 Triad 18 AWG 600V 2C032U180800700 2.03 0.080 23.7 0.932 406 605 11.2 284 325 147

16 Triad 18 AWG 600V 2C032U181200700 2.03 0.080 28.6 1.125 571 849 13.5 343 481 218

24 Triad 18 AWG 600V 2C032U181600700 2.03 0.080 31.8 1.250 707 1,052 15.0 381 637 289

2 Pair 16 AWG 600V 2C022U160200700 1.52 0.060 14.8 0.582 150 224 7.0 177 95 43

4 Pair 16 AWG 600V 2C022U160400700 1.52 0.060 17.0 0.670 213 317 8.0 204 178 81

8 Pair 16 AWG 600V 2C022U160800700 2.03 0.080 23.1 0.909 407 605 10.9 277 343 155

12 Pair 16 AWG 600V 2C022U161200700 2.03 0.080 27.8 1.096 569 847 13.2 334 507 230

16 Pair 16 AWG 600V 2C022U161600700 2.03 0.080 30.9 1.217 710 1,057 14.6 371 672 305

24 Pair 16 AWG 600V 2C022U162400700 2.03 0.080 38.2 1.504 1,023 1,522 18.0 458 1,002 454

2 Triad 16 AWG 600V 2C032U160200700 1.52 0.060 16.4 0.646 188 280 7.8 197 137 62

4 Triad 16 AWG 600V 2C032U160400700 1.52 0.060 19.0 0.747 274 408 9.0 228 260 118

8 Triad 16 AWG 600V 2C032U160800700 2.03 0.080 25.8 1.014 527 784 12.2 309 507 230

12 Triad 16 AWG 600V 2C032U161200700 2.03 0.080 31.2 1.229 745 1,108 14.7 375 755 342

16 Triad 16 AWG 600V 2C032U161600700 2.03 0.080 34.7 1.368 939 1,397 16.4 417 1,002 454

24 Triad 16 AWG 600V 2C032U162400700 2.79 0.110 44.6 1.756 1,461 2,174 21.1 535 1,496 679

Page 68: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated CPE Jacketed Instrumentation Tray: OS (TC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 2C021U180100400 1.14 0.045 8.2 0.323 49 72 3.9 98 39 18

2 Pair 18 AWG 600V 2C021U180200400 1.14 0.045 12.4 0.487 90 134 5.8 148 65 29

4 Pair 18 AWG 600V 2C021U180400400 1.52 0.060 15.0 0.592 140 209 7.1 180 117 53

8 Pair 18 AWG 600V 2C021U180800400 1.52 0.060 19.3 0.761 237 352 9.1 232 221 100

12 Pair 18 AWG 600V 2C021U181200400 2.03 0.080 24.4 0.961 362 538 11.5 293 325 147

16 Pair 18 AWG 600V 2C021U181600400 2.03 0.080 27.0 1.064 445 663 12.8 324 429 195

24 Pair 18 AWG 600V 2C021U182400400 2.03 0.080 33.2 1.309 629 936 15.7 399 637 289

36 Pair 18 AWG 600V 2C021U183600400 2.03 0.080 38.0 1.496 868 1,292 18.0 456 949 430

50 Pair 18 AWG 600V 2C021U185000400 2.79 0.110 45.5 1.790 1,248 1,858 21.5 545 1,313 596

1 Triad 18 AWG 600V 2C031U180100400 1.14 0.045 8.6 0.339 57 84 4.1 103 52 24

2 Triad 18 AWG 600V 2C031U180200400 1.52 0.060 14.4 0.568 132 197 6.8 173 91 41

4 Triad 18 AWG 600V 2C031U180400400 1.52 0.060 16.6 0.653 184 273 7.8 199 169 77

8 Triad 18 AWG 600V 2C031U180800400 2.03 0.080 22.5 0.885 349 520 10.6 270 325 147

12 Triad 18 AWG 600V 2C031U181200400 2.03 0.080 27.1 1.067 488 727 12.8 325 481 218

16 Triad 18 AWG 600V 2C031U181600400 2.03 0.080 30.1 1.184 606 902 14.2 361 637 289

24 Triad 18 AWG 600V 2C031U182400400 2.03 0.080 37.1 1.462 870 1,295 17.5 445 949 430

1 Pair 16 AWG 600V 2C021U160100400 1.14 0.045 8.8 0.347 60 89 4.2 106 54 25

2 Pair 16 AWG 600V 2C021U160200400 1.14 0.045 13.4 0.529 114 170 6.3 161 95 43

4 Pair 16 AWG 600V 2C021U160400400 1.52 0.060 16.3 0.642 177 263 7.7 196 178 81

8 Pair 16 AWG 600V 2C021U160800400 1.52 0.060 21.1 0.830 305 454 10.0 253 343 155

12 Pair 16 AWG 600V 2C021U161200400 2.03 0.080 26.6 1.048 468 697 12.6 319 507 230

16 Pair 16 AWG 600V 2C021U161600400 2.03 0.080 29.5 1.162 580 863 13.9 354 672 305

24 Pair 16 AWG 600V 2C021U162400400 2.03 0.080 36.4 1.434 832 1,238 17.2 437 1,002 454

36 Pair 16 AWG 600V 2C021U163600400 2.03 0.080 41.7 1.643 1,160 1,726 19.7 501 1,496 679

1 Triad 16 AWG 600V 2C031U160100400 1.14 0.045 9.3 0.365 72 107 4.4 111 75 34

2 Triad 16 AWG 600V 2C031U160200400 1.52 0.060 15.6 0.616 163 243 7.4 188 137 62

4 Triad 16 AWG 600V 2C031U160400400 1.52 0.060 18.1 0.711 236 351 8.5 217 260 118

8 Triad 16 AWG 600V 2C031U160800400 2.03 0.080 24.5 0.964 453 674 11.6 294 507 230

12 Triad 16 AWG 600V 2C031U161200400 2.03 0.080 29.6 1.166 640 952 14.0 355 755 342

16 Triad 16 AWG 600V 2C031U161600400 2.03 0.080 32.9 1.297 802 1,193 15.6 395 1,002 454

24 Triad 16 AWG 600V 2C031U162400400 2.03 0.080 40.8 1.605 1,161 1,728 19.3 489 1,496 679

Page 69: Shaw Flex Catalogue

Phone: 1 800-668-4842 67 email: [email protected]

UL Cables

XLPE Insulated CPE Jacketed Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 2C022U180200400 1.14 0.045 12.9 0.509 104 155 6.1 155 65 29

4 Pair 18 AWG 600V 2C022U180400400 1.52 0.060 15.7 0.618 161 239 7.4 188 117 53

8 Pair 18 AWG 600V 2C022U180800400 1.52 0.060 20.3 0.797 277 412 9.6 243 221 100

12 Pair 18 AWG 600V 2C022U181200400 2.03 0.080 25.6 1.006 421 626 12.1 307 325 147

16 Pair 18 AWG 600V 2C022U181600400 2.03 0.080 28.3 1.116 523 778 13.4 340 429 195

24 Pair 18 AWG 600V 2C022U182400400 2.03 0.080 34.9 1.374 748 1,113 16.5 419 637 289

36 Pair 18 AWG 600V 2C022U183600400 2.03 0.080 40.0 1.573 1,037 1,544 18.9 480 949 430

50 Pair 18 AWG 600V 2C022U185000400 2.79 0.110 47.8 1.880 1,487 2,213 22.6 573 1,313 596

2 Triad 18 AWG 600V 2C032U180200400 1.52 0.060 15.1 0.596 146 218 7.2 182 91 41

4 Triad 18 AWG 600V 2C032U180400400 1.52 0.060 17.5 0.687 207 308 8.2 209 169 77

8 Triad 18 AWG 600V 2C032U180800400 2.03 0.080 23.7 0.932 396 590 11.2 284 325 147

12 Triad 18 AWG 600V 2C032U181200400 2.03 0.080 28.6 1.125 558 831 13.5 343 481 218

16 Triad 18 AWG 600V 2C032U181600400 2.03 0.080 31.8 1.250 693 1,032 15.0 381 637 289

24 Triad 18 AWG 600V 2C032U182400400 2.03 0.080 39.3 1.546 1,000 1,488 18.6 471 949 430

2 Pair 16 AWG 600V 2C022U160200400 1.52 0.060 14.8 0.582 146 217 7.0 177 95 43

4 Pair 16 AWG 600V 2C022U160400400 1.52 0.060 17.0 0.670 207 308 8.0 204 178 81

8 Pair 16 AWG 600V 2C022U160800400 2.03 0.080 23.1 0.909 397 591 10.9 277 343 155

12 Pair 16 AWG 600V 2C022U161200400 2.03 0.080 27.8 1.096 557 829 13.2 334 507 230

16 Pair 16 AWG 600V 2C022U161600400 2.03 0.080 30.9 1.217 697 1,037 14.6 371 672 305

24 Pair 16 AWG 600V 2C022U162400400 2.03 0.080 38.2 1.504 1,006 1,498 18.0 458 1,002 454

36 Pair 16 AWG 600V 2C022U163600400 2.79 0.110 45.3 1.785 1,512 2,250 21.4 544 1,496 679

2 Triad 16 AWG 600V 2C032U160200400 1.52 0.060 16.4 0.646 183 272 7.8 197 137 62

4 Triad 16 AWG 600V 2C032U160400400 1.52 0.060 19.0 0.747 268 399 9.0 228 260 118

8 Triad 16 AWG 600V 2C032U160800400 2.03 0.080 25.8 1.014 516 768 12.2 309 507 230

12 Triad 16 AWG 600V 2C032U161200400 2.03 0.080 31.2 1.229 731 1,088 14.7 375 755 342

16 Triad 16 AWG 600V 2C032U161600400 2.03 0.080 34.7 1.368 924 1,375 16.4 417 1,002 454

24 Triad 16 AWG 600V 2C032U162400400 2.79 0.110 44.6 1.756 1,435 2,135 21.1 535 1,496 679

Page 70: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated CSPE Hypalon® Jacketed Instrumentation Tray: OS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 2C021U180100600 1.14 0.045 8.2 0.323 53 78 3.9 98 39 18

2 Pair 18 AWG 600V 2C021U180200600 1.14 0.045 12.4 0.487 97 144 5.8 148 65 29

4 Pair 18 AWG 600V 2C021U180400600 1.52 0.060 15.0 0.592 151 224 7.1 180 117 53

8 Pair 18 AWG 600V 2C021U180800600 1.52 0.060 19.3 0.761 250 372 9.1 232 221 100

12 Pair 18 AWG 600V 2C021U181100600 2.03 0.080 23.7 0.933 363 540 11.2 284 299 136

16 Pair 18 AWG 600V 2C021U181600600 2.03 0.080 27.0 1.064 470 700 12.8 324 429 195

24 Pair 18 AWG 600V 2C021U182400600 2.03 0.080 33.2 1.309 661 983 15.7 399 637 289

36 Pair 18 AWG 600V 2C021U183600600 2.03 0.080 38.0 1.496 904 1,346 18.0 456 949 430

50 Pair 18 AWG 600V 2C021U185000600 2.79 0.110 45.5 1.790 1,306 1,944 21.5 545 1,313 596

1 Triad 18 AWG 600V 2C031U180100600 1.14 0.045 8.6 0.339 61 91 4.1 103 52 24

2 Triad 18 AWG 600V 2C031U180200600 1.52 0.060 14.4 0.568 142 212 6.8 173 91 41

4 Triad 18 AWG 600V 2C031U180400600 1.52 0.060 16.6 0.653 195 291 7.8 199 169 77

8 Triad 18 AWG 600V 2C031U180800600 2.03 0.080 22.5 0.885 370 551 10.6 270 325 147

12 Triad 18 AWG 600V 2C031U181200600 2.03 0.080 27.1 1.067 513 764 12.8 325 481 218

16 Triad 18 AWG 600V 2C031U181600600 2.03 0.080 30.1 1.184 634 944 14.2 361 637 289

24 Triad 18 AWG 600V 2C031U182400600 2.03 0.080 37.1 1.462 906 1,348 17.5 445 949 430

1 Pair 16 AWG 600V 2C021U160100600 1.14 0.045 8.8 0.347 64 96 4.2 106 54 25

2 Pair 16 AWG 600V 2C021U160200600 1.14 0.045 13.4 0.529 121 180 6.3 161 95 43

4 Pair 16 AWG 600V 2C021U160400600 1.52 0.060 16.3 0.642 188 280 7.7 196 178 81

8 Pair 16 AWG 600V 2C021U160800600 1.52 0.060 21.1 0.830 320 477 10.0 253 343 155

12 Pair 16 AWG 600V 2C021U161200600 2.03 0.080 26.6 1.048 493 734 12.6 319 507 230

16 Pair 16 AWG 600V 2C021U161600600 2.03 0.080 29.5 1.162 607 904 13.9 354 672 305

24 Pair 16 AWG 600V 2C021U162400600 2.03 0.080 36.4 1.434 866 1,289 17.2 437 1,002 454

36 Pair 16 AWG 600V 2C021U163600600 2.03 0.080 41.7 1.643 1,200 1,785 19.7 501 1,496 679

1 Triad 16 AWG 600V 2C031U160100600 1.14 0.045 9.3 0.365 77 115 4.4 111 75 34

2 Triad 16 AWG 600V 2C031U160200600 1.52 0.060 15.6 0.616 174 259 7.4 188 137 62

4 Triad 16 AWG 600V 2C031U160400600 1.52 0.060 18.1 0.711 249 370 8.5 217 260 118

8 Triad 16 AWG 600V 2C031U160800600 2.03 0.080 24.5 0.964 475 707 11.6 294 507 230

12 Triad 16 AWG 600V 2C031U161200600 2.03 0.080 29.6 1.166 668 993 14.0 355 755 342

16 Triad 16 AWG 600V 2C031U161600600 2.03 0.080 32.9 1.297 833 1,239 15.6 395 1,002 454

24 Triad 16 AWG 600V 2C031U162400600 2.03 0.080 40.8 1.605 1,200 1,786 19.3 489 1,496 679

Page 71: Shaw Flex Catalogue

Phone: 1 800-668-4842 69 email: [email protected]

UL Cables

XLPE Insulated CSPE Hypalon® Jacketed Instrumentation Tray: ISOS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 2C022U180200600 1.14 0.045 12.9 0.509 111 165 6.1 155 65 29

4 Pair 18 AWG 600V 2C022U180400600 1.52 0.060 15.7 0.618 172 255 7.4 188 117 53

8 Pair 18 AWG 600V 2C022U180800600 1.52 0.060 20.3 0.797 291 433 9.6 243 221 100

12 Pair 18 AWG 600V 2C022U181200600 2.03 0.080 25.6 1.006 444 661 12.1 307 325 147

16 Pair 18 AWG 600V 2C022U181600600 2.03 0.080 28.3 1.116 549 817 13.4 340 429 195

24 Pair 18 AWG 600V 2C022U182400600 2.03 0.080 34.9 1.374 781 1,162 16.5 419 637 289

36 Pair 18 AWG 600V 2C022U183600600 2.03 0.080 40.0 1.573 1,076 1,601 18.9 480 949 430

50 Pair 18 AWG 600V 2C022U185000600 2.79 0.110 47.8 1.880 1,549 2,304 22.6 573 1,313 596

2 Triad 18 AWG 600V 2C032U180200600 1.52 0.060 15.1 0.596 157 233 7.2 182 91 41

4 Triad 18 AWG 600V 2C032U180400600 1.52 0.060 17.5 0.687 219 326 8.2 209 169 77

8 Triad 18 AWG 600V 2C032U180800600 2.03 0.080 23.7 0.932 418 622 11.2 284 325 147

12 Triad 18 AWG 600V 2C032U181200600 2.03 0.080 28.6 1.125 585 871 13.5 343 481 218

16 Triad 18 AWG 600V 2C032U181600600 2.03 0.080 31.8 1.250 723 1,076 15.0 381 637 289

24 Triad 18 AWG 600V 2C032U182400600 2.03 0.080 39.3 1.546 1,037 1,544 18.6 471 949 430

2 Pair 16 AWG 600V 2C022U160200600 1.52 0.060 14.8 0.582 156 232 7.0 177 95 43

4 Pair 16 AWG 600V 2C022U160400600 1.52 0.060 17.0 0.670 219 326 8.0 204 178 81

8 Pair 16 AWG 600V 2C022U160800600 2.03 0.080 23.1 0.909 418 622 10.9 277 343 155

12 Pair 16 AWG 600V 2C022U161200600 2.03 0.080 27.8 1.096 583 868 13.2 334 507 230

16 Pair 16 AWG 600V 2C022U161600600 2.03 0.080 30.9 1.217 726 1,080 14.6 371 672 305

24 Pair 16 AWG 600V 2C022U162400600 2.03 0.080 38.2 1.504 1,043 1,552 18.0 458 1,002 454

36 Pair 16 AWG 600V 2C022U163600600 2.79 0.110 45.3 1.785 1,570 2,336 21.4 544 1,496 679

2 Triad 16 AWG 600V 2C032U160200600 1.52 0.060 16.4 0.646 194 289 7.8 197 137 62

4 Triad 16 AWG 600V 2C032U160400600 1.52 0.060 19.0 0.747 281 419 9.0 228 260 118

8 Triad 16 AWG 600V 2C032U160800600 2.03 0.080 25.8 1.014 540 803 12.2 309 507 230

12 Triad 16 AWG 600V 2C032U161200600 2.03 0.080 31.2 1.229 761 1,132 14.7 375 755 342

16 Triad 16 AWG 600V 2C032U161600600 2.03 0.080 34.7 1.368 957 1,424 16.4 417 1,002 454

24 Triad 16 AWG 600V 2C032U162400600 2.79 0.110 44.6 1.756 1,492 2,220 21.1 535 1,496 679

Page 72: Shaw Flex Catalogue

UL

Cabl

es

PVC/Nylon Insulated Control Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 29010U140200700 1.14 0.045 8.5 0.336 67 100 2.0 51 400 181 25.0

3 14 AWG 600V 29010U140300700 1.14 0.045 9.0 0.353 85 126 2.1 54 433 196 25.0

4 14 AWG 600V 29010U140400700 1.14 0.045 9.7 0.382 101 150 2.3 58 466 211 20.0

5 14 AWG 600V 29010U140500700 1.14 0.045 10.6 0.417 122 182 2.5 63 498 226 20.0

6 14 AWG 600V 29010U140600700 1.14 0.045 11.5 0.451 144 214 2.7 69 531 241 20.0

7 14 AWG 600V 29010U140700700 1.14 0.045 11.5 0.451 158 235 2.7 69 564 256 17.5

8 14 AWG 600V 29010U140800700 1.14 0.045 12.3 0.486 180 269 2.9 74 597 271 17.5

10 14 AWG 600V 29010U141000700 1.52 0.060 15.1 0.596 241 359 3.6 91 663 301 12.5

12 14 AWG 600V 29010U141200700 1.52 0.060 15.6 0.613 276 411 3.7 93 729 331 12.5

15 14 AWG 600V 29010U141500700 1.52 0.060 16.8 0.659 329 489 4.0 100 827 375 12.5

20 14 AWG 600V 29010U142000700 1.52 0.060 18.9 0.745 430 640 4.5 114 992 450 12.5

25 14 AWG 600V 29010U142500700 1.52 0.060 21.0 0.826 525 782 5.0 126 1,156 525 11.3

30 14 AWG 600V 29010U143000700 2.03 0.080 23.2 0.913 643 957 5.5 139 1,321 599 11.3

40 14 AWG 600V 29010U144000700 2.03 0.080 25.8 1.016 830 1,235 6.1 155 1,650 748 10.0

50 14 AWG 600V 29010U145000700 2.03 0.080 28.5 1.124 1,019 1,516 6.7 171 1,979 898 8.8

2 12 AWG 600V 29010U120200700 1.14 0.045 9.5 0.374 89 132 2.2 57 438 199 30.0

3 12 AWG 600V 29010U120300700 1.14 0.045 10.0 0.394 114 170 2.4 60 491 222 30.0

4 12 AWG 600V 29010U120400700 1.14 0.045 10.9 0.428 144 214 2.6 65 543 246 24.0

5 12 AWG 600V 29010U120500700 1.14 0.045 11.9 0.468 176 262 2.8 71 595 270 24.0

6 12 AWG 600V 29010U120600700 1.14 0.045 12.9 0.508 202 301 3.0 77 647 294 24.0

7 12 AWG 600V 29010U120700700 1.14 0.045 12.9 0.508 224 333 3.0 77 699 317 21.0

8 12 AWG 600V 29010U120800700 1.52 0.060 14.7 0.578 272 405 3.5 88 752 341 21.0

10 12 AWG 600V 29010U121000700 1.52 0.060 17.1 0.672 337 502 4.0 102 856 388 15.0

12 12 AWG 600V 29010U121200700 1.52 0.060 17.6 0.692 388 578 4.2 105 960 436 15.0

15 12 AWG 600V 29010U121500700 1.52 0.060 18.9 0.746 473 703 4.5 114 1,117 507 15.0

20 12 AWG 600V 29010U122000700 2.03 0.080 22.5 0.886 648 965 5.3 135 1,378 625 15.0

25 12 AWG 600V 29010U122500700 2.03 0.080 24.9 0.980 793 1,180 5.9 149 1,639 743 13.5

30 12 AWG 600V 29010U123000700 2.03 0.080 26.3 1.035 924 1,375 6.2 158 1,900 862 13.5

40 12 AWG 600V 29010U124000700 2.03 0.080 29.3 1.154 1,196 1,780 6.9 176 2,422 1,099 12.0

50 12 AWG 600V 29010U125000700 2.03 0.080 32.5 1.280 1,473 2,192 7.7 195 2,944 1,335 10.5

2 10 AWG 600V 29010U100200700 1.14 0.045 11.3 0.444 129 192 2.7 68 500 227 40.0

3 10 AWG 600V 29010U100300700 1.14 0.045 11.9 0.469 168 250 2.8 72 583 264 40.0

4 10 AWG 600V 29010U100400700 1.14 0.045 13.0 0.512 211 315 3.1 78 666 302 32.0

5 10 AWG 600V 29010U100500700 1.52 0.060 15.0 0.592 275 410 3.6 90 749 340 32.0

6 10 AWG 600V 29010U100600700 1.52 0.060 16.3 0.643 326 485 3.9 98 832 377 32.0

7 10 AWG 600V 29010U100700700 1.52 0.060 16.3 0.643 361 537 3.9 98 915 415 28.0

8 10 AWG 600V 29010U100800700 1.52 0.060 17.6 0.694 405 603 4.2 106 998 453 28.0

10 10 AWG 600V 29010U101000700 1.52 0.060 20.6 0.812 504 750 4.9 124 1,164 528 20.0

12 10 AWG 600V 29010U101200700 1.52 0.060 21.3 0.837 584 869 5.0 128 1,330 603 20.0

15 10 AWG 600V 29010U101500700 2.03 0.080 24.0 0.945 747 1,112 5.7 144 1,579 716 20.0

20 10 AWG 600V 29010U102000700 2.03 0.080 27.2 1.072 974 1,450 6.4 163 1,994 904 20.0

25 10 AWG 600V 29010U102500700 2.03 0.080 30.2 1.190 1,195 1,779 7.1 181 2,409 1,093 18.0

30 10 AWG 600V 29010U103000700 2.03 0.080 32.0 1.259 1,397 2,079 7.6 192 2,824 1,281 18.0

40 10 AWG 600V 29010U104000700 2.03 0.080 35.8 1.410 1,820 2,709 8.5 215 3,654 1,657 16.0

50 10 AWG 600V 29010U105000700 2.03 0.080 39.8 1.569 2,249 3,347 9.4 239 4,484 2,034 14.0

Page 73: Shaw Flex Catalogue

Phone: 1 800-668-4842 71 email: [email protected]

UL Cables

PVC/Nylon Insulated Power Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 29010U140200700 1.14 0.045 8.5 0.336 67 100 2.0 51 79 36 25.0

3 14 AWG 600V 29010U140300700 1.14 0.045 9.0 0.353 85 126 2.1 54 112 51 25.0

4 14 AWG 600V 29010U140400700 1.14 0.045 9.7 0.382 101 150 2.3 58 145 66 20.0

2 12 AWG 600V 29010U120200700 1.14 0.045 9.5 0.374 89 132 2.2 57 117 53 30.0

3 12 AWG 600V 29010U120300700 1.14 0.045 10.0 0.394 114 170 2.4 60 170 77 30.0

4 12 AWG 600V 29010U120400700 1.14 0.045 10.9 0.428 144 214 2.6 65 222 101 24.0

2 10 AWG 600V 29010U100200700 1.14 0.045 11.3 0.444 129 192 2.7 68 179 81 40.0

3 10 AWG 600V 29010U100300700 1.14 0.045 11.9 0.469 168 250 2.8 72 262 119 40.0

4 10 AWG 600V 29010U100400700 1.14 0.045 13.0 0.512 211 315 3.1 78 345 156 32.0

2 8 AWG 600V 29010U080200700 1.52 0.060 14.7 0.580 213 317 3.5 88 278 126 55.0

3 8 AWG 600V 29010U080300700 1.52 0.060 15.6 0.613 279 415 3.7 93 410 186 55.0

4 8 AWG 600V 29010U080400700 1.52 0.060 17.0 0.669 354 526 4.0 102 542 246 44.0

2 6 AWG 600V 29010U060200700 1.52 0.060 16.5 0.648 294 437 3.9 99 432 196 75.0

3 6 AWG 600V 29010U060300700 1.52 0.060 17.4 0.686 393 586 4.1 105 642 291 75.0

4 6 AWG 600V 29010U060400700 1.52 0.060 19.0 0.750 500 743 4.5 114 852 386 60.0

2 4 AWG 600V 29010U040200700 1.52 0.060 20.0 0.786 441 657 4.7 120 681 309 95.0

3 4 AWG 600V 29010U040300700 1.52 0.060 21.2 0.834 600 893 5.0 127 1,015 460 95.0

4 4 AWG 600V 29010U040400700 2.03 0.080 24.3 0.955 806 1,199 5.7 146 1,349 612 76.0

2 2 AWG 600V 29010U020200700 2.03 0.080 23.9 0.942 677 1,007 5.7 144 1,075 488 130.0

3 2 AWG 600V 29010U020300700 2.03 0.080 25.4 0.999 916 1,363 6.0 152 1,606 729 130.0

4 2 AWG 600V 29010U020400700 2.03 0.080 27.8 1.094 1,182 1,759 6.6 167 2,137 970 104.0

2 1 AWG 600V 29010U010240700 2.03 0.080 27.0 1.064 840 1,250 6.4 162 1,352 613 150.0

3 1 AWG 600V 29010U010340700 2.03 0.080 28.7 1.130 1,145 1,704 6.8 172 2,022 917 150.0

4 1 AWG 600V 29010U010440700 2.03 0.080 31.5 1.241 1,475 2,195 7.4 189 2,691 1,221 120.0

2 1/0 AWG 600V 29010U1/0240700 2.03 0.080 29.4 1.158 960 1,428 6.9 176 1,703 772 170.0

3 1/0 AWG 600V 29010U1/0340700 2.03 0.080 31.3 1.231 1,355 2,016 7.4 188 2,547 1,155 170.0

4 1/0 AWG 600V 29010U1/0440700 2.03 0.080 34.4 1.354 1,777 2,644 8.1 206 3,392 1,539 136.0

2 2/0 AWG 600V 29010U2/0240700 2.03 0.080 31.8 1.250 1,171 1,743 7.5 190 2,143 972 195.0

3 2/0 AWG 600V 29010U2/0340700 2.03 0.080 33.8 1.330 1,664 2,477 8.0 203 3,207 1,455 195.0

4 2/0 AWG 600V 29010U2/0440700 2.03 0.080 37.2 1.464 2,169 3,227 8.8 223 4,272 1,938 156.0

2 3/0 AWG 600V 29010U3/0240700 2.03 0.080 34.2 1.348 1,417 2,109 8.1 205 2,684 1,218 225.0

3 3/0 AWG 600V 29010U3/0340700 2.03 0.080 36.5 1.436 2,014 2,996 8.6 219 4,020 1,824 225.0

4 3/0 AWG 600V 29010U3/0440700 2.03 0.080 40.2 1.582 2,635 3,921 9.5 241 5,356 2,429 180.0

2 4/0 AWG 600V 29010U4/0240700 2.03 0.080 37.1 1.462 1,730 2,575 8.8 223 3,399 1,542 260.0

3 4/0 AWG 600V 29010U4/0340700 2.03 0.080 39.6 1.558 2,497 3,716 9.3 237 5,091 2,309 260.0

4 4/0 AWG 600V 29010U4/0440700 2.79 0.110 45.2 1.778 3,375 5,023 10.7 271 6,784 3,077 208.0

Page 74: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated PVC Jacketed Control Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 2C010U140200700 1.14 0.045 9.6 0.376 74 110 2.3 57 400 181 25.0

3 14 AWG 600V 2C010U140300700 1.14 0.045 10.1 0.396 92 137 2.4 60 433 196 25.0

4 14 AWG 600V 2C010U140400700 1.14 0.045 10.9 0.430 114 170 2.6 66 466 211 20.0

5 14 AWG 600V 2C010U140500700 1.14 0.045 12.0 0.470 139 207 2.8 72 498 226 20.0

6 14 AWG 600V 2C010U140600700 1.14 0.045 13.0 0.511 158 235 3.1 78 531 241 20.0

7 14 AWG 600V 2C010U140700700 1.14 0.045 13.0 0.511 172 256 3.1 78 564 256 17.5

8 14 AWG 600V 2C010U140800700 1.52 0.060 14.8 0.581 213 317 3.5 89 597 271 17.5

10 14 AWG 600V 2C010U141000700 1.52 0.060 17.2 0.676 263 392 4.1 103 663 301 12.5

12 14 AWG 600V 2C010U141200700 1.52 0.060 17.7 0.696 300 446 4.2 106 729 331 12.5

15 14 AWG 600V 2C010U141500700 1.52 0.060 19.1 0.750 362 538 4.5 114 827 375 12.5

20 14 AWG 600V 2C010U142000700 2.03 0.080 22.6 0.892 502 746 5.3 136 992 450 12.5

25 14 AWG 600V 2C010U142500700 2.03 0.080 25.0 0.986 608 905 5.9 150 1,156 525 11.3

30 14 AWG 600V 2C010U143000700 2.03 0.080 26.5 1.041 702 1,045 6.2 159 1,321 599 11.3

40 14 AWG 600V 2C010U144000700 2.03 0.080 29.5 1.161 899 1,338 7.0 177 1,650 748 10.0

50 14 AWG 600V 2C010U145000700 2.03 0.080 32.7 1.288 1,102 1,640 7.7 196 1,979 898 8.8

2 12 AWG 600V 2C010U120200700 1.14 0.045 10.5 0.414 97 145 2.5 63 438 199 30.0

3 12 AWG 600V 2C010U120300700 1.14 0.045 11.1 0.437 125 186 2.6 67 491 222 30.0

4 12 AWG 600V 2C010U120400700 1.14 0.045 12.1 0.476 154 230 2.9 72 543 246 24.0

5 12 AWG 600V 2C010U120500700 1.14 0.045 13.3 0.522 188 280 3.1 80 595 270 24.0

6 12 AWG 600V 2C010U120600700 1.52 0.060 15.2 0.598 239 356 3.6 91 647 294 24.0

7 12 AWG 600V 2C010U120700700 1.52 0.060 15.2 0.598 262 390 3.6 91 699 317 21.0

8 12 AWG 600V 2C010U120800700 1.52 0.060 16.4 0.644 291 433 3.9 98 752 341 21.0

10 12 AWG 600V 2C010U121000700 1.52 0.060 19.1 0.752 361 538 4.5 115 856 388 15.0

12 12 AWG 600V 2C010U121200700 1.52 0.060 19.7 0.775 417 620 4.7 118 960 436 15.0

15 12 AWG 600V 2C010U121500700 1.52 0.060 21.3 0.837 503 749 5.0 128 1,117 507 15.0

20 12 AWG 600V 2C010U122000700 2.03 0.080 25.2 0.992 693 1,032 6.0 151 1,378 625 15.0

25 12 AWG 600V 2C010U122500700 2.03 0.080 27.9 1.100 846 1,259 6.6 168 1,639 743 13.5

30 12 AWG 600V 2C010U123000700 2.03 0.080 29.5 1.163 982 1,462 7.0 177 1,900 862 13.5

40 12 AWG 600V 2C010U124000700 2.03 0.080 33.0 1.300 1,268 1,888 7.8 198 2,422 1,099 12.0

50 12 AWG 600V 2C010U125000700 2.03 0.080 36.7 1.445 1,562 2,324 8.7 220 2,944 1,335 10.5

2 10 AWG 600V 2C010U100200700 1.14 0.045 11.8 0.464 131 195 2.8 71 500 227 40.0

3 10 AWG 600V 2C010U100300700 1.14 0.045 12.5 0.491 172 255 2.9 75 583 264 40.0

4 10 AWG 600V 2C010U100400700 1.14 0.045 13.6 0.536 218 325 3.2 82 666 302 32.0

5 10 AWG 600V 2C010U100500700 1.52 0.060 15.7 0.619 280 417 3.7 94 749 340 32.0

6 10 AWG 600V 2C010U100600700 1.52 0.060 17.1 0.673 330 491 4.0 103 832 377 32.0

7 10 AWG 600V 2C010U100700700 1.52 0.060 17.1 0.673 365 543 4.0 103 915 415 28.0

8 10 AWG 600V 2C010U100800700 1.52 0.060 18.5 0.727 409 609 4.4 111 998 453 28.0

10 10 AWG 600V 2C010U101000700 2.03 0.080 22.7 0.892 543 809 5.4 136 1,164 528 20.0

12 10 AWG 600V 2C010U101200700 2.03 0.080 23.3 0.919 626 931 5.5 140 1,330 603 20.0

15 10 AWG 600V 2C010U101500700 2.03 0.080 25.2 0.990 759 1,130 5.9 151 1,579 716 20.0

20 10 AWG 600V 2C010U102000700 2.03 0.080 28.6 1.125 986 1,467 6.7 171 1,994 904 20.0

25 10 AWG 600V 2C010U102500700 2.03 0.080 31.8 1.250 1,208 1,797 7.5 190 2,409 1,093 18.0

30 10 AWG 600V 2C010U103000700 2.03 0.080 33.6 1.323 1,413 2,103 7.9 202 2,824 1,281 18.0

40 10 AWG 600V 2C010U104000700 2.03 0.080 37.7 1.483 1,833 2,728 8.9 226 3,654 1,657 16.0

50 10 AWG 600V 2C010U105000700 2.03 0.080 41.9 1.651 2,265 3,370 9.9 252 4,484 2,034 14.0

Page 75: Shaw Flex Catalogue

Phone: 1 800-668-4842 73 email: [email protected]

UL Cables

XLPE Insulated PVC Jacketed Power Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 2C010U140200700 1.14 0.045 9.6 0.376 74 110 2.3 57 79 36 25.0

3 14 AWG 600V 2C010U140300700 1.14 0.045 10.1 0.396 92 137 2.4 60 112 51 25.0

4 14 AWG 600V 2C010U140400700 1.14 0.045 10.9 0.430 114 170 2.6 66 145 66 20.0

2 12 AWG 600V 2C010U120200700 1.14 0.045 10.5 0.414 97 145 2.5 63 117 53 30.0

3 12 AWG 600V 2C010U120300700 1.14 0.045 11.1 0.437 125 186 2.6 67 170 77 30.0

4 12 AWG 600V 2C010U120400700 1.14 0.045 12.1 0.476 154 230 2.9 72 222 101 24.0

2 10 AWG 600V 2C010U100200700 1.14 0.045 11.8 0.464 131 195 2.8 71 179 81 40.0

3 10 AWG 600V 2C010U100300700 1.14 0.045 12.5 0.491 172 255 2.9 75 262 119 40.0

4 10 AWG 600V 2C010U100400700 1.14 0.045 13.6 0.536 218 325 3.2 82 345 156 32.0

2 8 AWG 600V 2C010U080200700 1.52 0.060 15.7 0.616 223 331 3.7 94 278 126 55.0

3 8 AWG 600V 2C010U080300700 1.52 0.060 16.6 0.652 289 430 3.9 99 410 186 55.0

4 8 AWG 600V 2C010U080400700 1.52 0.060 18.1 0.712 365 544 4.3 109 542 246 44.0

2 6 AWG 600V 2C010U060200700 1.52 0.060 17.4 0.684 299 445 4.1 104 432 196 75.0

3 6 AWG 600V 2C010U060300700 1.52 0.060 18.4 0.725 399 594 4.3 110 642 291 75.0

4 6 AWG 600V 2C010U060400700 1.52 0.060 20.1 0.793 506 753 4.8 121 852 386 60.0

2 4 AWG 600V 2C010U040200700 1.52 0.060 19.8 0.778 428 636 4.7 119 681 309 95.0

3 4 AWG 600V 2C010U040300700 1.52 0.060 21.0 0.826 580 863 5.0 126 1,015 460 95.0

4 4 AWG 600V 2C010U040400700 2.03 0.080 24.0 0.946 779 1,159 5.7 144 1,349 612 76.0

2 2 AWG 600V 2C010U020200700 2.03 0.080 23.7 0.934 659 981 5.6 142 1,075 488 130.0

3 2 AWG 600V 2C010U020300700 2.03 0.080 25.2 0.991 890 1,325 5.9 151 1,606 729 130.0

4 2 AWG 600V 2C010U020400700 2.03 0.080 27.6 1.085 1,148 1,708 6.5 165 2,137 970 104.0

2 1 AWG 600V 2C010U010240700 2.03 0.080 26.7 1.052 816 1,214 6.3 160 1,352 613 150.0

3 1 AWG 600V 2C010U010340700 2.03 0.080 28.4 1.117 1,110 1,652 6.7 170 2,022 917 150.0

4 1 AWG 600V 2C010U010440700 2.03 0.080 31.2 1.226 1,429 2,126 7.4 187 2,691 1,221 120.0

2 1/0 AWG 600V 2C010U1/0240700 2.03 0.080 29.1 1.146 933 1,388 6.9 175 1,703 772 170.0

3 1/0 AWG 600V 2C010U1/0340700 2.03 0.080 31.0 1.218 1,315 1,957 7.3 186 2,547 1,155 170.0

4 1/0 AWG 600V 2C010U1/0440700 2.03 0.080 34.0 1.339 1,724 2,566 8.0 204 3,392 1,539 136.0

2 2/0 AWG 600V 2C010U2/0240700 2.03 0.080 31.5 1.238 1,141 1,698 7.4 189 2,143 972 195.0

3 2/0 AWG 600V 2C010U2/0340700 2.03 0.080 33.5 1.317 1,606 2,389 7.9 201 3,207 1,455 195.0

4 2/0 AWG 600V 2C010U2/0440700 2.03 0.080 36.8 1.450 2,110 3,139 8.7 221 4,272 1,938 156.0

2 3/0 AWG 600V 2C010U3/0240700 2.03 0.080 33.9 1.336 1,383 2,059 8.0 204 2,684 1,218 225.0

3 3/0 AWG 600V 2C010U3/0340700 2.03 0.080 36.1 1.423 1,964 2,922 8.5 217 4,020 1,824 225.0

4 3/0 AWG 600V 2C010U3/0440700 2.03 0.080 39.8 1.567 2,569 3,823 9.4 239 5,356 2,429 180.0

2 4/0 AWG 600V 2C010U4/0240700 2.03 0.080 36.8 1.450 1,699 2,529 8.7 221 3,399 1,542 260.0

3 4/0 AWG 600V 2C010U4/0340700 2.03 0.080 39.3 1.545 2,440 3,632 9.3 236 5,091 2,309 260.0

4 4/0 AWG 600V 2C010U4/0440700 2.79 0.110 44.8 1.764 3,300 4,911 10.6 269 6,784 3,077 208.0

Page 76: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated CSPE Hypalon® Jacketed Control Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 2C010U140200610 1.14 0.045 9.6 0.376 77 114 2.3 57 400 181 25.0

3 14 AWG 600V 2C010U140300610 1.14 0.045 10.1 0.396 95 141 2.4 60 433 196 25.0

4 14 AWG 600V 2C010U140400610 1.14 0.045 10.9 0.430 117 175 2.6 66 466 211 20.0

5 14 AWG 600V 2C010U140500610 1.14 0.045 12.0 0.470 143 212 2.8 72 498 226 20.0

6 14 AWG 600V 2C010U140600610 1.14 0.045 13.0 0.511 161 240 3.1 78 531 241 20.0

7 14 AWG 600V 2C010U140610610 1.14 0.045 13.0 0.511 161 240 3.1 78 531 241 20.0

8 14 AWG 600V 2C010U140800610 1.52 0.060 14.8 0.581 218 324 3.5 89 597 271 17.5

10 14 AWG 600V 2C010U141000610 1.52 0.060 17.2 0.676 269 401 4.1 103 663 301 12.5

12 14 AWG 600V 2C010U141200610 1.52 0.060 17.7 0.696 306 456 4.2 106 729 331 12.5

15 14 AWG 600V 2C010U141500610 1.52 0.060 19.1 0.750 369 549 4.5 114 827 375 12.5

20 14 AWG 600V 2C010U142000610 2.03 0.080 22.6 0.892 512 763 5.3 136 992 450 12.5

25 14 AWG 600V 2C010U142500610 2.03 0.080 25.0 0.986 620 923 5.9 150 1,156 525 11.3

30 14 AWG 600V 2C010U143000610 2.03 0.080 26.5 1.041 715 1,064 6.2 159 1,321 599 11.3

40 14 AWG 600V 2C010U144000610 2.03 0.080 29.5 1.161 914 1,360 7.0 177 1,650 748 10.0

50 14 AWG 600V 2C010U145000610 2.03 0.080 32.7 1.288 1,118 1,664 7.7 196 1,979 898 8.8

2 12 AWG 600V 2C010U120200610 1.14 0.045 10.5 0.414 100 149 2.5 63 438 199 30.0

3 12 AWG 600V 2C010U120300610 1.14 0.045 11.1 0.437 128 191 2.6 67 491 222 30.0

4 12 AWG 600V 2C010U120400610 1.14 0.045 12.1 0.476 158 235 2.9 72 543 246 24.0

5 12 AWG 600V 2C010U120500610 1.14 0.045 13.3 0.522 192 286 3.1 80 595 270 24.0

6 12 AWG 600V 2C010U120600610 1.52 0.060 15.2 0.598 245 364 3.6 91 647 294 24.0

7 12 AWG 600V 2C010U120610610 1.52 0.060 15.2 0.598 245 364 3.6 91 647 294 24.0

8 12 AWG 600V 2C010U120800610 1.52 0.060 16.4 0.644 297 442 3.9 98 752 341 21.0

10 12 AWG 600V 2C010U121000610 1.52 0.060 19.1 0.752 369 548 4.5 115 856 388 15.0

12 12 AWG 600V 2C010U121200610 1.52 0.060 19.7 0.775 424 631 4.7 118 960 436 15.0

15 12 AWG 600V 2C010U121500610 1.52 0.060 21.3 0.837 511 760 5.0 128 1,117 507 15.0

20 12 AWG 600V 2C010U122000610 2.03 0.080 25.2 0.992 705 1,050 6.0 151 1,378 625 15.0

25 12 AWG 600V 2C010U122500610 2.03 0.080 27.9 1.100 859 1,279 6.6 168 1,639 743 13.5

30 12 AWG 600V 2C010U123000610 2.03 0.080 29.5 1.163 997 1,483 7.0 177 1,900 862 13.5

40 12 AWG 600V 2C010U124000610 2.03 0.080 33.0 1.300 1,285 1,912 7.8 198 2,422 1,099 12.0

50 12 AWG 600V 2C010U125000610 2.03 0.080 36.7 1.445 1,580 2,351 8.7 220 2,944 1,335 10.5

2 10 AWG 600V 2C010U100200610 1.14 0.045 11.8 0.464 134 200 2.8 71 500 227 40.0

3 10 AWG 600V 2C010U100300610 1.14 0.045 12.5 0.491 175 260 2.9 75 583 264 40.0

4 10 AWG 600V 2C010U100400610 1.14 0.045 13.6 0.536 222 330 3.2 82 666 302 32.0

5 10 AWG 600V 2C010U100500610 1.52 0.060 15.7 0.619 286 425 3.7 94 749 340 32.0

6 10 AWG 600V 2C010U100600610 1.52 0.060 17.1 0.673 336 500 4.0 103 832 377 32.0

7 10 AWG 600V 2C010U100610610 1.52 0.060 17.1 0.673 336 500 4.0 103 832 377 32.0

8 10 AWG 600V 2C010U100800610 1.52 0.060 18.5 0.727 416 619 4.4 111 998 453 28.0

10 10 AWG 600V 2C010U101000610 2.03 0.080 22.7 0.892 554 825 5.4 136 1,164 528 20.0

12 10 AWG 600V 2C010U101200610 2.03 0.080 23.3 0.919 637 948 5.5 140 1,330 603 20.0

15 10 AWG 600V 2C010U101500610 2.03 0.080 25.2 0.990 771 1,148 5.9 151 1,579 716 20.0

20 10 AWG 600V 2C010U102000610 2.03 0.080 28.6 1.125 1,000 1,488 6.7 171 1,994 904 20.0

25 10 AWG 600V 2C010U102500610 2.03 0.080 31.8 1.250 1,224 1,821 7.5 190 2,409 1,093 18.0

30 10 AWG 600V 2C010U103000610 2.03 0.080 33.6 1.323 1,430 2,128 7.9 202 2,824 1,281 18.0

40 10 AWG 600V 2C010U104000610 2.03 0.080 37.7 1.483 1,852 2,756 8.9 226 3,654 1,657 16.0

50 10 AWG 600V 2C010U105000610 2.03 0.080 41.9 1.651 2,286 3,401 9.9 252 4,484 2,034 14.0

Page 77: Shaw Flex Catalogue

Phone: 1 800-668-4842 75 email: [email protected]

UL Cables

XLPE Insulated CSPE Hypalon® Jacketed Power Tray (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 2C010U140200610 1.14 0.045 9.6 0.376 74 110 2.3 57 79 36 25.0

3 14 AWG 600V 2C010U140300610 1.14 0.045 10.1 0.396 92 137 2.4 60 112 51 25.0

4 14 AWG 600V 2C010U140400610 1.14 0.045 10.9 0.430 114 170 2.6 66 145 66 20.0

2 12 AWG 600V 2C010U120200610 1.14 0.045 10.5 0.414 97 145 2.5 63 117 53 30.0

3 12 AWG 600V 2C010U120300610 1.14 0.045 11.1 0.437 125 186 2.6 67 170 77 30.0

4 12 AWG 600V 2C010U120400610 1.14 0.045 12.1 0.476 154 230 2.9 72 222 101 24.0

2 10 AWG 600V 2C010U100200610 1.14 0.045 11.8 0.464 131 195 2.8 71 179 81 40.0

3 10 AWG 600V 2C010U100300610 1.14 0.045 12.5 0.491 172 255 2.9 75 262 119 40.0

4 10 AWG 600V 2C010U100400610 1.14 0.045 13.6 0.536 218 325 3.2 82 345 156 32.0

2 8 AWG 600V 2C010U080200610 1.52 0.060 15.7 0.616 223 331 3.7 94 278 126 55.0

3 8 AWG 600V 2C010U080300610 1.52 0.060 16.6 0.652 289 430 3.9 99 410 186 55.0

4 8 AWG 600V 2C010U080400610 1.52 0.060 18.1 0.712 365 544 4.3 109 542 246 44.0

2 6 AWG 600V 2C010U060200610 1.52 0.060 17.4 0.684 299 445 4.1 104 432 196 75.0

3 6 AWG 600V 2C010U060300610 1.52 0.060 18.4 0.725 399 594 4.3 110 642 291 75.0

4 6 AWG 600V 2C010U060400610 1.52 0.060 20.1 0.793 506 753 4.8 121 852 386 60.0

2 4 AWG 600V 2C010U040200610 1.52 0.060 19.8 0.778 428 636 4.7 119 681 309 95.0

3 4 AWG 600V 2C010U040300610 1.52 0.060 21.0 0.826 580 863 5.0 126 1,015 460 95.0

4 4 AWG 600V 2C010U040400610 2.03 0.080 24.0 0.946 779 1,159 5.7 144 1,349 612 76.0

2 2 AWG 600V 2C010U020200610 2.03 0.080 23.7 0.934 659 981 5.6 142 1,075 488 130.0

3 2 AWG 600V 2C010U020300610 2.03 0.080 25.2 0.991 890 1,325 5.9 151 1,606 729 130.0

4 2 AWG 600V 2C010U020400610 2.03 0.080 27.6 1.085 1,148 1,708 6.5 165 2,137 970 104.0

2 1 AWG 600V 2C010U010240610 2.03 0.080 26.7 1.052 816 1,214 6.3 160 1,352 613 150.0

3 1 AWG 600V 2C010U010340610 2.03 0.080 28.4 1.117 1,110 1,652 6.7 170 2,022 917 150.0

4 1 AWG 600V 2C010U010440610 2.03 0.080 31.2 1.226 1,429 2,126 7.4 187 2,691 1,221 120.0

2 1/0 AWG 600V 2C010U1/0240610 2.03 0.080 29.1 1.146 933 1,388 6.9 175 1,703 772 170.0

3 1/0 AWG 600V 2C010U1/0340610 2.03 0.080 31.0 1.218 1,315 1,957 7.3 186 2,547 1,155 170.0

4 1/0 AWG 600V 2C010U1/0440610 2.03 0.080 34.0 1.339 1,724 2,566 8.0 204 3,392 1,539 136.0

2 2/0 AWG 600V 2C010U2/0240610 2.03 0.080 31.5 1.238 1,141 1,698 7.4 189 2,143 972 195.0

3 2/0 AWG 600V 2C010U2/0340610 2.03 0.080 33.5 1.317 1,606 2,389 7.9 201 3,207 1,455 195.0

4 2/0 AWG 600V 2C010U2/0440610 2.03 0.080 36.8 1.450 2,110 3,139 8.7 221 4,272 1,938 156.0

2 3/0 AWG 600V 2C010U3/0240610 2.03 0.080 33.9 1.336 1,383 2,059 8.0 204 2,684 1,218 225.0

3 3/0 AWG 600V 2C010U3/0340610 2.03 0.080 36.1 1.423 1,964 2,922 8.5 217 4,020 1,824 225.0

4 3/0 AWG 600V 2C010U3/0440610 2.03 0.080 39.8 1.567 2,569 3,823 9.4 239 5,356 2,429 180.0

2 4/0 AWG 600V 2C010U4/0240610 2.03 0.080 36.8 1.450 1,699 2,529 8.7 221 3,399 1,542 260.0

3 4/0 AWG 600V 2C010U4/0340610 2.03 0.080 39.3 1.545 2,440 3,632 9.3 236 5,091 2,309 260.0

4 4/0 AWG 600V 2C010U4/0440610 2.79 0.110 44.8 1.764 3,300 4,911 10.6 269 6,784 3,077 208.0

Page 78: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated CPE Jacketed Control & Power Tray: 5 mil CU/LC (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

4 14 AWG 600V 2C015U140400410 1.14 0.045 13.1 0.514 153 227 6.2 157 145 66 20.0

5 14 AWG 600V 2C015U140500410 1.52 0.060 14.8 0.584 198 295 7.0 178 178 81 20.0

7 14 AWG 600V 2C015U140700410 1.52 0.060 16.1 0.635 233 346 7.6 194 243 110 17.5

9 14 AWG 600V 2C015U140900410 1.52 0.060 19.0 0.747 293 436 9.0 228 309 140 17.5

12 14 AWG 600V 2C015U141200410 1.52 0.060 19.8 0.780 354 527 9.4 238 408 185 12.5

19 14 AWG 600V 2C015U141900410 2.03 0.080 24.5 0.965 545 811 11.6 294 638 289 12.5

37 14 AWG 600V 2C015U143700410 2.03 0.080 31.1 1.225 927 1,379 14.7 373 1,230 558 10.0

2 12 AWG 600V 2C015U120200410 1.14 0.045 13.2 0.518 137 204 6.2 158 117 53 30.0

3 12 AWG 600V 2C015U120300410 1.14 0.045 13.2 0.521 163 243 6.3 159 170 77 30.0

4 12 AWG 600V 2C015U120400410 1.52 0.060 15.0 0.590 213 317 7.1 180 222 101 24.0

5 12 AWG 600V 2C015U120500410 1.52 0.060 16.1 0.636 248 369 7.6 194 274 124 24.0

7 12 AWG 600V 2C015U120700410 1.52 0.060 17.3 0.682 312 464 8.2 208 378 172 21.0

9 12 AWG 600V 2C015U120900410 1.52 0.060 20.0 0.786 382 569 9.4 240 483 219 21.0

12 12 AWG 600V 2C015U121200410 2.03 0.080 23.3 0.919 510 759 11.0 280 639 290 15.0

19 12 AWG 600V 2C015U121900410 2.03 0.080 26.7 1.050 728 1,084 12.6 320 1,005 456 15.0

37 12 AWG 600V 2C015U123700410 2.03 0.080 34.0 1.338 1,275 1,898 16.1 408 1,944 882 12.0

2 12 AWG 600V 2C015U100200410 1.52 0.060 14.9 0.588 191 284 7.1 179 179 81 40.0

3 12 AWG 600V 2C015U100300410 1.52 0.060 15.4 0.605 231 343 7.3 184 262 119 40.0

4 10 AWG 600V 2C015U100400410 1.52 0.060 16.8 0.660 285 424 7.9 201 345 156 32.0

5 10 AWG 600V 2C015U100500410 1.52 0.060 18.9 0.743 334 497 8.9 227 428 194 32.0

7 10 AWG 600V 2C015U100700710 1.52 0.060 19.2 0.757 424 632 9.1 231 594 269 28.0

9 10 AWG 600V 2C015U100900410 2.03 0.080 23.3 0.916 554 824 11.0 279 760 345 28.0

12 10 AWG 600V 2C015U101200410 2.03 0.080 25.7 1.013 705 1,049 12.2 309 1,009 458 20.0

19 810AWG 600V 2C015U101900410 2.03 0.080 29.8 1.175 1,014 1,509 14.1 358 1,590 721 20.0

37 10 AWG 600V 2C015U103700410 2.03 0.080 38.7 1.523 1,810 2,694 18.3 464 3,084 1,399 16.0

3 8 AWG 600V 2C015U080300410 1.52 0.060 18.9 0.746 344 512 9.0 227 410 186 55.0

3 6 AWG 600V 2C015U060300410 1.52 0.060 20.4 0.805 457 680 9.7 245 642 291 75.0

3 4 AWG 600V 2C015U040300410 2.03 0.080 24.5 0.966 685 1,020 11.6 294 1,015 460 95.0

3 2 AWG 600V 2C015U020300410 2.03 0.080 27.2 1.071 970 1,444 12.8 326 1,606 729 130.0

3 1 AWG 600V 2C015U010340410 2.03 0.080 30.7 1.207 1,196 1,780 14.5 368 2,022 917 150.0

3 1/0 AWG 600V 2C015U1/0340410 2.03 0.080 33.5 1.319 1,413 2,103 15.8 402 2,547 1,155 170.0

3 2/0 AWG 600V 2C015U2/0340410 2.03 0.080 35.5 1.397 1,706 2,538 16.8 426 3,207 1,455 195.0

3 3/0 AWG 600V 2C015U3/0340410 2.03 0.080 38.7 1.523 2,072 3,083 18.3 464 4,020 1,824 225.0

3 4/0 AWG 600V 2C015U4/0340410 2.03 0.080 41.5 1.635 2,557 3,806 19.6 498 5,091 2,309 260.0

Page 79: Shaw Flex Catalogue

Phone: 1 800-668-4842 77 email: [email protected]

UL Cables

XLPE Insulated PVC Jacketed Control & Power Tray: 5 mil CU/LC (TC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

4 14 AWG 600V 2C015U140400700 1.14 0.045 13.1 0.514 155 231 6.2 157 466 211 20.0

5 14 AWG 600V 2C015U140500700 1.52 0.060 14.8 0.584 202 301 7.0 178 498 226 20.0

7 14 AWG 600V 2C015U140700700 1.52 0.060 16.1 0.635 237 353 7.6 194 564 256 17.5

9 14 AWG 600V 2C015U140900700 1.52 0.060 19.0 0.747 299 444 9.0 228 630 286 17.5

12 14 AWG 600V 2C015U141200700 1.52 0.060 19.8 0.780 360 535 9.4 238 729 331 12.5

19 14 AWG 600V 2C015U141900700 2.03 0.080 24.5 0.965 554 824 11.6 294 959 435 12.5

37 14 AWG 600V 2C015U143700700 2.03 0.080 31.1 1.225 939 1,397 14.7 373 1,551 704 10.0

2 12 AWG 600V 2C015U120200700 1.14 0.045 13.2 0.518 140 209 6.2 158 438 199 30.0

3 12 AWG 600V 2C015U120300700 1.14 0.045 13.2 0.521 166 247 6.3 159 491 222 30.0

4 12 AWG 600V 2C015U120400700 1.52 0.060 15.0 0.590 217 323 7.1 180 543 246 24.0

5 12 AWG 600V 2C015U120500700 1.52 0.060 16.1 0.636 253 376 7.6 194 595 270 24.0

7 12 AWG 600V 2C015U120700700 1.52 0.060 17.3 0.682 317 471 8.2 208 699 317 21.0

9 12 AWG 600V 2C015U120900700 1.52 0.060 20.0 0.786 388 577 9.4 240 804 365 21.0

12 12 AWG 600V 2C015U121200700 2.03 0.080 23.3 0.919 518 772 11.0 280 960 436 15.0

19 12 AWG 600V 2C015U121900700 2.03 0.080 26.7 1.050 738 1,099 12.6 320 1,326 601 15.0

37 12 AWG 600V 2C015U123700700 2.03 0.080 34.0 1.338 1,289 1,918 16.1 408 2,265 1,028 12.0

2 12 AWG 600V 2C015U100200700 1.52 0.060 14.9 0.588 195 290 7.1 179 500 227 40.0

3 12 AWG 600V 2C015U100300700 1.52 0.060 15.4 0.605 235 350 7.3 184 583 264 40.0

4 10 AWG 600V 2C015U100400700 1.52 0.060 16.8 0.660 290 431 7.9 201 666 302 32.0

5 10 AWG 600V 2C015U100500700 1.52 0.060 18.9 0.743 339 505 8.9 227 749 340 32.0

7 10 AWG 600V 2C015U100700700 1.52 0.060 19.2 0.757 425 632 9.1 231 915 415 28.0

9 10 AWG 600V 2C015U100900700 2.03 0.080 23.3 0.916 562 837 11.0 279 1,081 490 28.0

12 10 AWG 600V 2C015U101200700 2.03 0.080 25.7 1.013 714 1,063 12.2 309 1,330 603 20.0

19 810AWG 600V 2C015U101900700 2.03 0.080 29.8 1.175 1,025 1,526 14.1 358 1,911 867 20.0

37 10 AWG 600V 2C015U103700700 2.03 0.080 38.7 1.523 1,825 2,716 18.3 464 3,405 1,544 16.0

3 8 AWG 600V 2C015U080300700 1.52 0.060 18.9 0.746 349 520 9.0 227 731 331 55.0

3 6 AWG 600V 2C015U060300700 1.52 0.060 20.4 0.805 463 688 9.7 245 963 437 75.0

3 4 AWG 600V 2C015U040300700 2.03 0.080 24.5 0.966 694 1,033 11.6 294 1,336 606 95.0

3 2 AWG 600V 2C015U020300700 2.03 0.080 27.2 1.071 981 1,459 12.8 326 1,927 874 130.0

3 1 AWG 600V 2C015U010340700 2.03 0.080 30.7 1.207 1,208 1,798 14.5 368 2,342 1,063 150.0

3 1/0 AWG 600V 2C015U1/0340700 2.03 0.080 33.5 1.319 1,426 2,122 15.8 402 2,868 1,301 170.0

3 2/0 AWG 600V 2C015U2/0340700 2.03 0.080 35.5 1.397 1,720 2,559 16.8 426 3,528 1,600 195.0

3 3/0 AWG 600V 2C015U3/0340700 2.03 0.080 38.7 1.523 2,087 3,105 18.3 464 4,341 1,969 225.0

3 4/0 AWG 600V 2C015U4/0340700 2.03 0.080 41.5 1.635 2,574 3,830 19.6 498 5,412 2,455 260.0

Page 80: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated Thermocouple Tray: OS (TC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 7C021U180147700 1.14 0.045 8.0 0.315 48 72 3.8 96 39 18

2 Pair 18 AWG 600V 7C021U180247700 1.14 0.045 11.8 0.466 89 133 5.6 142 65 29

4 Pair 18 AWG 600V 7C021U180447700 1.52 0.060 14.4 0.567 137 204 6.8 173 117 53

6 Pair 18 AWG 600V 7C021U180647700 1.52 0.060 17.1 0.673 188 279 8.1 205 169 77

8 Pair 18 AWG 600V 7C021U180847700 1.52 0.060 18.5 0.727 227 338 8.7 221 221 100

12 Pair 18 AWG 600V 7C021U181247700 2.03 0.080 23.3 0.918 349 519 11.0 280 325 147

16 Pair 18 AWG 600V 7C021U181647700 2.03 0.080 25.8 1.015 424 631 12.2 309 429 195

24 Pair 18 AWG 600V 7C021U182447700 2.03 0.080 31.7 1.246 601 894 15.0 380 637 289

36 Pair 18 AWG 600V 7C021U183647700 2.03 0.080 36.2 1.423 822 1,223 17.1 434 949 430

50 Pair 18 AWG 600V 7C021U185047700 2.03 0.080 41.7 1.643 1,091 1,623 19.7 501 1,313 596

1 Pair 16 AWG 600V 7C021U160147700 1.14 0.045 8.6 0.337 61 90 4.0 103 54 25

2 Pair 16 AWG 600V 7C021U160247700 1.14 0.045 12.8 0.504 110 163 6.1 154 95 43

4 Pair 16 AWG 600V 7C021U160447700 1.52 0.060 15.6 0.613 172 255 7.4 187 178 81

6 Pair 16 AWG 600V 7C021U160647700 1.52 0.060 18.6 0.731 241 359 8.8 223 260 118

8 Pair 16 AWG 600V 7C021U160847700 1.52 0.060 20.1 0.790 295 438 9.5 241 343 155

12 Pair 16 AWG 600V 7C021U161247700 2.03 0.080 25.3 0.997 448 666 12.0 304 507 230

16 Pair 16 AWG 600V 7C021U161647700 2.03 0.080 28.1 1.105 557 829 13.3 337 672 305

24 Pair 16 AWG 600V 7C021U162447700 2.03 0.080 34.6 1.361 795 1,184 16.3 415 1,002 454

36 Pair 16 AWG 600V 7C021U163647700 2.03 0.080 39.6 1.557 1,103 1,641 18.7 475 1,496 679

50 Pair 16 AWG 600V 7C021U165047700 2.79 0.110 47.3 1.861 1,582 2,354 22.3 567 2,073 940

Page 81: Shaw Flex Catalogue

Phone: 1 800-668-4842 79 email: [email protected]

UL Cables

XLPE Insulated Thermocouple Tray: ISOS (TC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 7C022U180247700 1.14 0.045 12.6 0.494 104 155 5.9 151 65 29

4 Pair 18 AWG 600V 7C022U180447700 1.52 0.060 15.3 0.601 161 240 7.2 183 117 53

6 Pair 18 AWG 600V 7C022U18047700 1.52 0.060 18.2 0.716 225 335 8.6 218 169 77

8 Pair 18 AWG 600V 7C022U180847700 1.52 0.060 19.7 0.774 273 406 9.3 236 221 100

12 Pair 18 AWG 600V 7C022U181247700 2.03 0.080 24.8 0.977 417 621 11.7 298 325 147

16 Pair 18 AWG 600V 7C022U181647700 2.03 0.080 27.5 1.082 517 769 13.0 330 429 195

24 Pair 18 AWG 600V 7C022U182447700 2.03 0.080 33.8 1.331 736 1,095 16.0 406 637 289

36 Pair 18 AWG 600V 7C022U183647700 2.03 0.080 38.7 1.523 1,015 1,511 18.3 464 949 430

50 Pair 18 AWG 600V 7C022U185047700 2.79 0.110 46.2 1.821 1,459 2,172 21.8 555 1,313 596

2 Pair 16 AWG 600V 7C022U160247700 1.14 0.045 13.6 0.534 130 194 6.4 163 95 43

4 Pair 16 AWG 600V 7C022U160447700 1.52 0.060 16.5 0.649 206 307 7.8 198 178 81

6 Pair 16 AWG 600V 7C022U160647700 1.52 0.060 19.7 0.775 292 435 9.3 236 260 118

8 Pair 16 AWG 600V 7C022U160847700 1.52 0.060 21.3 0.839 359 534 10.1 256 343 155

12 Pair 16 AWG 600V 7C022U161247700 2.03 0.080 26.9 1.059 550 818 12.7 323 507 230

16 Pair 16 AWG 600V 7C022U161647700 2.03 0.080 29.9 1.175 685 1,019 14.1 358 672 305

24 Pair 16 AWG 600V 7C022U162447700 2.03 0.080 34.6 1.361 795 1,184 16.3 415 1,002 454

36 Pair 16 AWG 600V 7C022U163647700 2.03 0.080 39.6 1.557 1,103 1,641 18.7 475 1,496 679

50 Pair 16 AWG 600V 7C022U165047700 2.79 0.110 47.3 1.861 1,582 2,354 22.3 567 2,073 940

Page 82: Shaw Flex Catalogue

UL

Cabl

es

PVC/Nylon Insulated Armoured Instrumentation: OS (MC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 29621U180100700 1.27 0.050 16.6 0.655 184 273 7.9 200 47 21

2 Pair 18 AWG 600V 29621U180200700 1.27 0.050 20.0 0.789 259 385 9.5 241 65 29

4 Pair 18 AWG 600V 29621U180400700 1.27 0.050 21.9 0.863 315 469 10.4 263 117 53

8 Pair 18 AWG 600V 29621U180800700 1.27 0.050 26.3 1.036 455 677 12.4 316 221 100

12 Pair 18 AWG 600V 29621U181200700 1.27 0.050 28.4 1.118 544 809 13.4 341 325 147

16 Pair 18 AWG 600V 29621U181600700 1.27 0.050 30.1 1.187 632 941 14.2 362 429 195

24 Pair 18 AWG 600V 29621U182400700 1.27 0.050 35.2 1.386 840 1,250 16.6 422 637 289

1 Triad 18 AWG 600V 29631U180100700 1.27 0.050 17.0 0.668 196 292 8.0 204 52 24

2 Triad 18 AWG 600V 29631U180200700 1.27 0.050 21.1 0.831 291 433 10.0 253 91 41

4 Triad 18 AWG 600V 29631U180400700 1.27 0.050 23.2 0.914 367 546 11.0 279 169 77

8 Triad 18 AWG 600V 29631U180800700 1.27 0.050 28.2 1.110 550 818 13.3 338 325 147

12 Triad 18 AWG 600V 29631U181200700 1.27 0.050 30.2 1.188 670 997 14.3 362 481 218

16 Triad 18 AWG 600V 29631U181600700 1.27 0.050 32.6 1.284 795 1,183 15.4 391 637 289

24 Triad 18 AWG 600V 29631U182400700 1.27 0.050 38.4 1.510 1,077 1,603 18.1 460 949 430

1 Pair 16 AWG 600V 29621U160100700 1.27 0.050 17.2 0.679 203 302 8.1 207 54 25

2 Pair 16 AWG 600V 29621U160200700 1.27 0.050 21.1 0.831 293 436 10.0 253 103 47

4 Pair 16 AWG 600V 29621U160400700 1.27 0.050 23.2 0.915 368 547 11.0 279 185 84

8 Pair 16 AWG 600V 29621U160800700 1.27 0.050 28.2 1.111 548 816 13.3 339 350 159

12 Pair 16 AWG 600V 29621U161200700 1.27 0.050 30.2 1.189 666 991 14.3 362 515 234

16 Pair 16 AWG 600V 29621U161600700 1.27 0.050 32.6 1.285 789 1,174 15.4 392 680 308

24 Pair 16 AWG 600V 29621U162400700 1.27 0.050 38.4 1.511 1,067 1,587 18.1 461 1,009 458

1 Triad 16 AWG 600V 29631U160100700 1.27 0.050 17.6 0.694 220 327 8.3 212 82 37

2 Triad 16 AWG 600V 29631U160200700 1.27 0.050 22.3 0.878 336 500 10.5 268 144 65

4 Triad 16 AWG 600V 29631U160400700 1.27 0.050 24.7 0.973 437 650 11.7 297 268 121

8 Triad 16 AWG 600V 29631U160800700 1.27 0.050 30.0 1.181 674 1,004 14.2 360 515 234

12 Triad 16 AWG 600V 29631U161200700 1.27 0.050 32.7 1.288 841 1,252 15.5 393 762 346

16 Triad 16 AWG 600V 29631U161600700 1.27 0.050 35.5 1.396 1,018 1,514 16.8 426 1,009 458

24 Triad 16 AWG 600V 29631U162400700 1.27 0.050 42.0 1.654 1,399 2,081 19.8 504 1,504 682

Page 83: Shaw Flex Catalogue

Phone: 1 800-668-4842 81 email: [email protected]

UL Cables

PVC/Nylon Insulated Armoured Instrumentation: ISOS (MC)

Number of Pairs

or Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 29622U180200700 1.27 0.050 20.5 0.809 273 407 9.7 247 52 24

4 Pair 18 AWG 600V 29622U180400700 1.27 0.050 22.5 0.887 337 502 10.6 270 104 47

8 Pair 18 AWG 600V 29622U180800700 1.27 0.050 27.2 1.071 492 732 12.9 326 208 94

12 Pair 18 AWG 600V 29622U181200700 1.27 0.050 29.0 1.143 604 899 13.7 348 312 142

16 Pair 18 AWG 600V 29622U181600700 1.27 0.050 31.3 1.233 715 1,063 14.8 376 416 189

24 Pair 18 AWG 600V 29622U182400700 1.27 0.050 36.7 1.444 961 1,430 17.3 440 624 283

2 Triad 18 AWG 600V 29632U180200700 1.27 0.050 21.7 0.856 309 460 10.3 261 78 35

4 Triad 18 AWG 600V 29632U180400700 1.27 0.050 24.0 0.945 391 581 11.3 288 156 71

8 Triad 18 AWG 600V 29632U180800700 1.27 0.050 28.9 1.139 585 870 13.7 347 312 142

12 Triad 18 AWG 600V 29632U181200700 1.27 0.050 31.5 1.240 737 1,096 14.9 378 468 212

16 Triad 18 AWG 600V 29632U181600700 1.27 0.050 34.1 1.342 884 1,316 16.1 409 624 283

24 Triad 18 AWG 600V 29632U182400700 1.27 0.050 40.2 1.584 1,205 1,793 19.0 483 936 425

2 Pair 16 AWG 600V 29622U160200700 1.27 0.050 21.6 0.852 310 462 10.2 260 82 37

4 Pair 16 AWG 600V 29622U160400700 1.27 0.050 23.9 0.941 395 587 11.3 287 165 75

8 Pair 16 AWG 600V 29622U160800700 1.27 0.050 28.8 1.133 594 883 13.6 345 330 150

12 Pair 16 AWG 600V 29622U161200700 1.27 0.050 31.3 1.233 750 1,117 14.8 376 494 224

16 Pair 16 AWG 600V 29622U161600700 1.27 0.050 33.9 1.334 903 1,344 16.0 407 659 299

24 Pair 16 AWG 600V 29622U162400700 1.27 0.050 40.0 1.574 1,234 1,836 18.9 480 989 449

2 Triad 16 AWG 600V 29632U160200700 1.27 0.050 23.0 0.906 359 534 10.9 276 124 56

4 Triad 16 AWG 600V 29632U160400700 1.27 0.050 25.6 1.007 467 694 12.1 307 247 112

8 Triad 16 AWG 600V 29632U160800700 1.27 0.050 31.2 1.230 724 1,077 14.8 375 494 224

12 Triad 16 AWG 600V 29632U161200700 1.27 0.050 34.1 1.344 935 1,391 16.1 410 742 336

16 Triad 16 AWG 600V 29632U161600700 1.27 0.050 37.1 1.460 1,135 1,690 17.5 445 989 449

24 Triad 16 AWG 600V 29632U162400700 1.27 0.050 44.0 1.734 1,576 2,345 20.8 529 1,483 673

Page 84: Shaw Flex Catalogue

UL

Cabl

es

XLPE Insulated Armoured Instrumentation: OS (MC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 Pair 18 AWG 600V 2C621U180100700 1.27 0.050 17.7 0.695 201 299 8.3 212 39 18

2 Pair 18 AWG 600V 2C621U180200700 1.27 0.050 21.8 0.859 290 432 10.3 262 65 29

4 Pair 18 AWG 600V 2C621U180400700 1.27 0.050 24.1 0.949 357 532 11.4 289 117 53

8 Pair 18 AWG 600V 2C621U180800700 1.27 0.050 29.1 1.145 521 776 13.7 349 221 100

12 Pair 18 AWG 600V 2C621U181200700 1.27 0.050 31.7 1.247 621 924 15.0 380 325 147

16 Pair 18 AWG 600V 2C621U181600700 1.27 0.050 34.3 1.350 728 1,084 16.2 412 429 195

24 Pair 18 AWG 600V 2C621U182400700 1.27 0.050 40.5 1.595 967 1,440 19.1 486 637 289

1 Triad 18 AWG 600V 2C631U180100700 1.27 0.050 18.1 0.711 215 321 8.5 217 52 24

2 Triad 18 AWG 600V 2C631U180200700 1.27 0.050 23.1 0.910 330 491 10.9 277 91 41

4 Triad 18 AWG 600V 2C631U180400700 1.27 0.050 25.7 1.012 417 621 12.1 309 169 77

8 Triad 18 AWG 600V 2C631U180800700 1.27 0.050 31.4 1.237 632 940 14.8 377 325 147

12 Triad 18 AWG 600V 2C631U181200700 1.27 0.050 34.4 1.353 772 1,149 16.2 412 481 218

16 Triad 18 AWG 600V 2C631U181600700 1.27 0.050 37.3 1.470 916 1,363 17.6 448 637 289

24 Triad 18 AWG 600V 2C631U182400700 1.27 0.050 44.4 1.748 1,243 1,849 21.0 533 949 430

1 Pair 16 AWG 600V 2C621U160100700 1.27 0.050 18.3 0.719 220 327 8.6 219 54 25

2 Pair 16 AWG 600V 2C621U160200700 1.27 0.050 22.9 0.901 327 486 10.8 275 103 47

4 Pair 16 AWG 600V 2C621U160400700 1.27 0.050 25.4 1.001 410 610 12.0 305 185 84

8 Pair 16 AWG 600V 2C621U160800700 1.27 0.050 31.0 1.221 617 918 14.6 372 350 159

12 Pair 16 AWG 600V 2C621U161200700 1.27 0.050 33.9 1.333 749 1,115 16.0 406 515 234

16 Pair 16 AWG 600V 2C621U161600700 1.27 0.050 36.8 1.448 887 1,319 17.4 441 680 308

24 Pair 16 AWG 600V 2C621U162400700 1.27 0.050 43.7 1.720 1,200 1,786 20.6 524 1,009 458

1 Triad 16 AWG 600V 2C631U160100700 1.27 0.050 18.7 0.737 240 357 8.8 225 82 37

2 Triad 16 AWG 600V 2C631U160200700 1.27 0.050 24.3 0.958 375 558 11.5 292 144 65

4 Triad 16 AWG 600V 2C631U160400700 1.27 0.050 27.2 1.072 488 727 12.9 327 268 121

8 Triad 16 AWG 600V 2C631U160800700 1.27 0.050 33.6 1.324 762 1,134 15.9 404 515 234

12 Triad 16 AWG 600V 2C631U161200700 1.27 0.050 36.9 1.452 948 1,410 17.4 443 762 346

16 Triad 16 AWG 600V 2C631U161600700 1.27 0.050 40.2 1.582 1,139 1,695 19.0 482 1,009 458

24 Triad 16 AWG 600V 2C631U162400700 1.27 0.050 48.0 1.891 1,569 2,335 22.7 576 1,504 682

Page 85: Shaw Flex Catalogue

Phone: 1 800-668-4842 83 email: [email protected]

UL Cables

XLPE Insulated Armoured Instrumentation: ISOS (MC)

Number of Pairs or

Triads Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

2 Pair 18 AWG 600V 2C622U180200700 1.27 0.050 22.4 0.881 310 461 10.6 269 52 24

4 Pair 18 AWG 600V 2C622U180400700 1.27 0.050 24.8 0.976 379 564 11.7 298 104 47

8 Pair 18 AWG 600V 2C622U180800700 1.27 0.050 30.1 1.185 556 828 14.2 361 208 94

12 Pair 18 AWG 600V 2C622U181200700 1.27 0.050 32.8 1.292 686 1,020 15.5 394 312 142

16 Pair 18 AWG 600V 2C622U181600700 1.27 0.050 35.6 1.402 812 1,209 16.8 427 416 189

24 Pair 18 AWG 600V 2C622U182400700 1.27 0.050 42.2 1.660 1,096 1,630 19.9 506 624 283

2 Triad 18 AWG 600V 2C632U180200700 1.27 0.050 23.8 0.938 353 525 11.3 286 78 35

4 Triad 18 AWG 600V 2C632U180400700 1.27 0.050 26.6 1.047 445 663 12.6 319 156 71

8 Triad 18 AWG 600V 2C632U180800700 1.27 0.050 32.7 1.288 671 999 15.5 393 312 142

12 Triad 18 AWG 600V 2C632U181200700 1.27 0.050 35.8 1.411 850 1,265 16.9 430 468 212

16 Triad 18 AWG 600V 2C632U181600700 1.27 0.050 39.0 1.536 1,013 1,507 18.4 468 624 283

24 Triad 18 AWG 600V 2C632U182400700 1.27 0.050 46.5 1.832 1,386 2,063 22.0 558 936 425

2 Pair 16 AWG 600V 2C622U160200700 1.27 0.050 23.5 0.924 349 519 11.1 282 82 37

4 Pair 16 AWG 600V 2C622U160400700 1.27 0.050 26.2 1.030 440 654 12.4 314 165 75

8 Pair 16 AWG 600V 2C622U160800700 1.27 0.050 32.1 1.263 666 991 15.2 385 330 150

12 Pair 16 AWG 600V 2C622U161200700 1.27 0.050 35.1 1.382 842 1,253 16.6 421 494 224

16 Pair 16 AWG 600V 2C622U161600700 1.27 0.050 38.2 1.503 1,009 1,502 18.0 458 659 299

24 Pair 16 AWG 600V 2C622U162400700 1.27 0.050 45.5 1.790 1,383 2,059 21.5 546 989 449

2 Triad 16 AWG 600V 2C632U160200700 1.27 0.050 25.1 0.988 402 598 11.9 301 124 56

4 Triad 16 AWG 600V 2C632U160400700 1.27 0.050 28.2 1.109 522 776 13.3 338 247 112

8 Triad 16 AWG 600V 2C632U160800700 1.27 0.050 35.0 1.379 814 1,211 16.5 420 494 224

12 Triad 16 AWG 600V 2C632U161200700 1.27 0.050 38.5 1.515 1,046 1,557 18.2 462 742 336

16 Triad 16 AWG 600V 2C632U161600700 1.27 0.050 42.0 1.654 1,270 1,890 19.8 504 989 449

24 Triad 16 AWG 600V 2C632U162400700 1.52 0.060 50.9 2.002 1,800 2,678 24.0 610 1,483 673

Page 86: Shaw Flex Catalogue

UL

Cabl

es

PVC/Nylon Insulated Armoured Power & Control (MC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 29610U140200700 1.27 0.050 18.0 0.708 230 342 8.5 216 99 45 25.0

3 14 AWG 600V 29610U140300700 1.27 0.050 18.7 0.734 257 382 8.8 224 132 60 25.0

4 14 AWG 600V 29610U140400700 1.27 0.050 19.4 0.763 284 423 9.2 233 165 75 20.0

5 14 AWG 600V 29610U140500700 1.27 0.050 20.0 0.788 311 462 9.5 240 197 90 20.0

7 14 AWG 600V 29610U140700700 1.27 0.050 21.8 0.858 374 556 10.3 261 263 119 17.5

12 14 AWG 600V 29610U141200700 1.27 0.050 24.3 0.955 494 735 11.5 291 428 194 12.5

2 12 AWG 600V 29610U120200700 1.27 0.050 18.9 0.746 271 404 9.0 227 157 71 30.0

3 12 AWG 600V 29610U120300700 1.27 0.050 19.7 0.777 306 455 9.3 237 209 95 30.0

4 12 AWG 600V 29610U120400700 1.27 0.050 20.6 0.810 344 512 9.7 247 261 118 24.0

5 12 AWG 600V 29610U120500700 1.27 0.050 21.3 0.840 380 566 10.1 256 313 142 24.0

7 12 AWG 600V 29610U120700700 1.27 0.050 23.4 0.920 466 694 11.0 281 418 189 21.0

12 12 AWG 600V 29610U121200700 1.27 0.050 26.3 1.034 634 943 12.4 315 679 308 15.0

2 10 AWG 600V 29610U100200700 1.27 0.050 20.7 0.816 341 507 9.8 249 249 113 40.0

3 10 AWG 600V 29610U100300700 1.27 0.050 21.7 0.855 391 581 10.3 261 332 151 40.0

4 10 AWG 600V 29610U100400700 1.27 0.050 22.8 0.897 447 665 10.8 273 415 188 32.0

5 10 AWG 600V 29610U100500700 1.27 0.050 23.7 0.935 502 746 11.2 285 498 226 32.0

7 10 AWG 600V 29610U100700700 1.27 0.050 26.3 1.036 626 931 12.4 316 664 301 28.0

12 10 AWG 600V 29610U101200700 1.27 0.050 29.6 1.164 874 1,300 14.0 355 1,079 489 20.0

2 8 AWG 600V 29610U080200700 1.27 0.050 23.4 0.922 436 648 11.1 281 348 158 55.0

3 8 AWG 600V 29610U080300700 1.27 0.050 24.7 0.973 521 775 11.7 297 480 218 55.0

4 8 AWG 600V 29610U080400700 1.27 0.050 26.1 1.029 610 908 12.3 314 612 278 44.0

2 6 AWG 600V 29610U060400700 1.27 0.050 28.2 1.112 797 1,186 13.3 339 971 440 60.0

3 6 AWG 600V 29610U060300700 1.27 0.050 26.6 1.048 673 1,001 12.6 319 761 345 75.0

4 6 AWG 600V 29610U060400700 1.27 0.050 28.2 1.112 797 1,186 13.3 339 971 440 60.0

Page 87: Shaw Flex Catalogue

Phone: 1 800-668-4842 85 email: [email protected]

UL Cables

XLPE Insulated Armoured Power & Control (MC)

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 14 AWG 600V 2C610U140200709 1.65 0.065 16.2 0.636 184 275 7.6 194 99 45 25.0

3 14 AWG 600V 2C610U140300709 1.65 0.065 16.9 0.667 208 310 8.0 203 132 60 25.0

4 14 AWG 600V 2C610U140400709 1.65 0.065 17.8 0.701 235 350 8.4 214 165 75 20.0

5 14 AWG 600V 2C610U140500709 1.65 0.065 18.6 0.731 262 390 8.8 223 197 90 20.0

7 14 AWG 600V 2C610U140700709 1.65 0.065 20.6 0.812 324 482 9.7 247 263 119 17.5

12 14 AWG 600V 2C610U141200709 1.65 0.065 23.5 0.926 443 659 11.1 282 428 194 12.5

2 12 AWG 600V 2C610U120200709 1.65 0.065 17.1 0.674 221 328 8.1 205 157 71 30.0

3 12 AWG 600V 2C610U120300709 1.65 0.065 18.0 0.709 253 377 8.5 216 209 95 30.0

4 12 AWG 600V 2C610U120400709 1.65 0.065 19.0 0.748 290 432 9.0 228 261 118 24.0

5 12 AWG 600V 2C610U120500709 1.65 0.065 19.9 0.782 327 487 9.4 238 313 142 24.0

7 12 AWG 600V 2C610U120700709 1.65 0.065 22.2 0.874 410 610 10.5 266 418 189 21.0

12 12 AWG 600V 2C610U121200709 1.65 0.065 25.5 1.005 577 859 12.1 306 679 308 15.0

2 10 AWG 600V 2C610U100200709 1.65 0.065 18.4 0.724 274 407 8.7 221 249 113 40.0

3 10 AWG 600V 2C610U100300709 1.65 0.065 19.4 0.765 326 484 9.2 233 332 151 40.0

4 10 AWG 600V 2C610U100400709 1.65 0.065 20.6 0.810 372 554 9.7 247 415 188 32.0

5 10 AWG 600V 2C610U100500709 1.65 0.065 21.6 0.849 424 631 10.2 259 498 226 32.0

7 10 AWG 600V 2C610U100700709 1.65 0.065 24.3 0.957 541 805 11.5 292 664 301 28.0

12 10 AWG 600V 2C610U101200709 1.65 0.065 28.2 1.109 779 1,159 13.3 338 1,079 489 20.0

2 8 AWG 600V 2C610U080200709 1.65 0.065 21.5 0.846 365 543 10.2 258 348 158 55.0

3 8 AWG 600V 2C610U080300709 1.65 0.065 22.9 0.901 446 663 10.8 275 480 218 55.0

4 8 AWG 600V 2C610U080400709 1.65 0.065 24.4 0.961 534 795 11.5 293 612 278 44.0

2 6 AWG 600V 2C610U060200709 1.65 0.065 23.2 0.914 469 699 11.0 279 552 250 75.0

3 6 AWG 600V 2C610U060300709 1.65 0.065 24.8 0.977 586 872 11.7 298 761 345 75.0

4 6 AWG 600V 2C610U060400709 1.65 0.065 26.5 1.045 705 1,049 12.5 318 971 440 60.0

2 4 AWG 600V 2C610U040200709 1.65 0.065 25.6 1.008 607 903 12.1 307 800 363 95.0

3 4 AWG 600V 2C610U040300709 1.65 0.065 26.8 1.056 773 1,151 12.7 322 1,134 514 95.0

4 4 AWG 600V 2C610U040400709 1.65 0.065 29.1 1.145 956 1,423 13.7 349 1,468 666 76.0

2 2 AWG 600V 2C610U020200709 1.65 0.065 28.1 1.108 840 1,250 13.3 338 1,272 577 130.0

3 2 AWG 600V 2C610U020300709 1.65 0.065 29.6 1.165 1,089 1,621 14.0 355 1,803 818 130.0

4 2 AWG 600V 2C610U020400709 1.65 0.065 32.7 1.289 1,370 2,039 15.5 393 2,334 1,059 104.0

2 1 AWG 600V 2C610U010240709 1.65 0.065 31.1 1.226 1,002 1,492 14.7 374 1,549 702 150.0

3 1 AWG 600V 2C610U010340709 1.65 0.065 32.8 1.291 1,318 1,961 15.5 394 2,218 1,006 150.0

4 1 AWG 600V 2C610U010440709 1.65 0.065 35.6 1.400 1,662 2,474 16.8 427 2,888 1,310 120.0

2 1/0 AWG 600V 2C610U1/0240709 1.65 0.065 33.5 1.320 1,153 1,716 15.8 402 1,899 862 170.0

3 1/0 AWG 600V 2C610U1/0340709 1.65 0.065 35.4 1.392 1,545 2,300 16.7 424 2,744 1,245 170.0

4 1/0 AWG 600V 2C610U1/0440709 1.65 0.065 38.4 1.513 1,974 2,938 18.2 461 3,589 1,628 136.0

2 2/0 AWG 600V 2C610U2/0240709 1.65 0.065 35.9 1.412 1,367 2,034 16.9 430 2,339 1,061 195.0

3 2/0 AWG 600V 2C610U2/0340709 1.65 0.065 37.9 1.491 1,847 2,748 17.9 455 3,404 1,544 195.0

4 2/0 AWG 600V 2C610U2/0440709 1.65 0.065 41.2 1.624 2,371 3,529 19.5 495 4,469 2,027 156.0

2 3/0 AWG 600V 2C610U3/0240709 1.65 0.065 38.4 1.510 1,667 2,481 18.1 460 3,005 1,363 225.0

3 3/0 AWG 600V 2C610U3/0340709 1.65 0.065 40.6 1.597 2,264 3,369 19.2 487 4,341 1,969 225.0

4 3/0 AWG 600V 2C610U3/0440709 1.65 0.065 44.2 1.741 2,887 4,297 20.9 531 5,677 2,575 180.0

2 4/0 AWG 600V 2C610U4/0240709 1.65 0.065 41.2 1.624 1,994 2,968 19.5 495 3,720 1,687 260.0

3 4/0 AWG 600V 2C610U4/0340709 1.65 0.065 43.7 1.719 2,749 4,091 20.6 524 5,412 2,455 260.0

4 4/0 AWG 600V 2C610U4/0440709 1.65 0.065 47.7 1.878 3,528 5,251 22.5 572 7,105 3,223 208.0

Page 88: Shaw Flex Catalogue

VFD

ShawFlex VFD UL Cables

Armoured a. Power

Tray a. Power

ShawFlex UL cables have been designed to meet the rigorous requirements established by the Underwriters Laboratories. UL Cables can be found in projects though out the world.

ArmouredShawFlex VFD Armoured cables can be used for Hazardous Location application as permitted.

ShawFlex VFD Armoured cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays, direct earth burial, for exposed and concealed wiring wet/dry locations. Available in two distinct options:

Aluminum Interlocked Armour (AIA) Galvanized Steel Interlocked Armour (SIA)

Construction Nec Characteristics

AIA Type MC (article 330) Flame Retardant, Sunlight resistant, Lightweight, excellent mechanical protection, cut & crush resistant, corrosion resistant

SIA Type MC (article 330) Flame Retardant, Sunlight resistant, Superior mechanical protection, cut & crush resistant

TrayShawFlex UL tray cables can be used for Hazardous Location application as permitted.

ShawFlex UL Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays in wet/dry locations. Construction Nec Characteristics

TC Type TC (article 336) Flame Retardant, Sunlight resistant, Lightweight, reduced diameter, flexible, tight bend radius

Page 89: Shaw Flex Catalogue

Phone: 1 800-668-4842 87 email: [email protected]

VFD

VFD UL Cable Available Constructions:

Armoured Tray

Characteristics:

Flame Retardant a aSunlight Resistant a aWet Rated a a-40 Cold Impact a aDirect Burial a aExposed Runs (ER) a a

Voltage Ratings:

600V a a2000V a a

Armouring Options:

Aluminum Interlock armour a -Steel Interlock Armour a -

Jacketing Options:

PVC Jacket a aPVC LAG Jacket a aLSZH Jacket - aCPE Jacket - aCSPE (Hypalon®) Jacket - a

Insulation Options:

FR-XLPE Insulation a aFR-XLPE VW1 Insulation a a

Shielding Options:

Helical Copper a a

Page 90: Shaw Flex Catalogue

VFD

ShawFlex VFD CSA Cables

Armoured a. Power

Tray a. Power

ShawFlex CSA cables have been designed to meet the rigorous requirements established by the Canadian Standards Association. Although CSA cables are primarily used in Canada they can also be found in projects though out the world.

ArmouredShawFlex VFD Armoured cables can be used for Hazardous Location application as permitted.

ShawFlex VFD Armoured cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays, direct earth burial, for exposed and concealed wiring wet/dry locations. Available in two distinct options:

Aluminum Interlocked Armour (AIA) Galvanized Steel Interlocked Armour (SIA)

Type cec (table 19) Characteristics

AIA ACIC, TECK90 Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, excellent mechan-ical protection, cut & crush resistant, corrosion resistant

SIA ACIC, TECK90 Flame Retardant, Sunlight resistant, -40 Rated, Superior mechanical protec-tion, cut & crush resistant

TrayShawFlex csa tray cables can be used for Hazardous Location application as permitted.

ShawFlex csa Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/outdoor and ladder-type cable trays in wet/dry locations. Type cec (table 19) Characteristics

TC TC Flame Retardant, Sunlight resistant, -40 Rated, Lightweight, reduced diameter, flexible, tight bend radius

Page 91: Shaw Flex Catalogue

Phone: 1 800-668-4842 89 email: [email protected]

VFD

VFD CSA Cable Available Constructions:

Armoured Tray

Characteristics:

FT4 Flame Retardant a aSunlight Resistant a aWet Rated a a-40 Cold Impact a aDirect Burial a a

Voltage Ratings:

600V a a1000V a a

Armouring Options:

Aluminum Interlock armour a -Steel Interlock Armour a -

Jacketing Options:

PVC Jacket - aPVC LAG Jacket a -LSZH Jacket a aCPE Jacket - -CSPE (Hypalon®) Jacket - -

Insulation Options:

XLPE Insulation a -FR-XLPE Insulation - a

Shielding Options:

Helical Copper a a

Page 92: Shaw Flex Catalogue

VFD

Variable Frequancy Drive XLPE Insulated Tray (UL TC)

Number of Conductors Gauge Voltage Part Number

Number of Strands

Ground Wire Size

AWG

Insulation Thickness

IN

Jacket Thickness

INOverall OD

INWeightlb/Mft

Conductor Circular Mils Ampacity

3 14 AWG 600V 2C01HU1403077DR 7 3 x 18 0.030 0.045 0.412 133 4 110 25

3 12 AWG 600V 2C01HU1203077DR 7 3 x 16 0.030 0.045 0.453 178 6 530 30

3 10 AWG 600V 2C01HU1003077DR 7 3 x 14 0.030 0.045 0.511 263 10 380 40

3 8 AWG 600V 2C01HU0803077DR 7 3 x 14 0.045 0.060 0.672 397 16 510 55

7 6 AWG 600V 2C01HU0603077DR 7 3 x 12 0.045 0.060 0.741 538 26 240 75

3 4 AWG 600V 2C01HU0403077DR 7 3 x 12 0.045 0.080 0.822 763 41 740 95

3 2 AWG 600V 2C01HU0203077DR 7 3 x 10 0.045 0.080 1.006 1,090 66 360 130

3 1 AWG 600V 2C01HU0103477DR 19 3 x 10 0.055 0.080 1.133 1,326 83 690 150

3 1/0 AWG 600V 2C01HU1/03477DR 19 3 x 10 0.055 0.080 1.234 1,585 105 600 170

3 2/0 AWG 600V 2C01HU2/03477DR 19 3 x 10 0.055 0.080 1.332 1,903 133 100 195

3 3/0 AWG 600V 2C01HU3/03477DR 19 3 x 8 0.055 0.080 1.438 2,345 167 800 225

3 4/0 AWG 600V 2C01HU4/03477DR 19 3 x 8 0.055 0.080 1.560 2,837 211 600 260

Variable Frequancy Drive XLPE Insulated Tray (CSA TC)

Number of Conductors Gauge Voltage Part Number

Number of Strands

Ground Wire Size

AWG

Insulation Thickness

IN

Jacket Thickness

INOverall OD

INWeightlb/Mft

Conductor Circular Mils Ampacity

3 14 AWG 1000V 4D01HM1403070DR 7 3 x 18 1.143 1.143 11.913 224 4 110 15

3 12 AWG 1000V 4D01HM1203070DR 7 3 x 16 1.143 1.143 12.929 290 6 530 20

3 10 AWG 1000V 4D01HM1003070DR 7 3 x 14 1.143 1.524 15.265 422 10 380 30

3 8 AWG 1000V 4D01HM0803070DR 7 3 x 14 1.143 1.524 16.967 546 16 510 45

7 6 AWG 1000V 4D01HM0603070DR 7 3 x 12 1.524 1.524 20.345 806 26 240 65

3 4 AWG 1000V 4D01HM0403070DR 7 3 x 12 1.524 2.032 23.927 1136 41 740 85

3 2 AWG 1000V 4D01HM0203070DR 7 3 x 10 1.524 2.032 27.102 1623 66 360 120

3 1 AWG 1000V 4D01HM0103470DR 19 3 x 10 2.032 2.032 31.420 2022 83 690 140

3 1/0 AWG 1000V 4D01HM1/03470DR 19 3 x 10 2.032 2.032 33.985 2417 105 600 155

3 2/0 AWG 1000V 4D01HM2/03470DR 19 3 x 10 2.032 2.032 36.474 2892 133 100 185

3 3/0 AWG 1000V 4D01HM3/03470DR 19 3 x 8 2.032 2.032 39.167 3546 167 800 210

3 4/0 AWG 1000V 4D01HM4/03470DR 19 3 x 8 2.032 2.032 42.266 4283 211 600 235

Variable Frequancy Drive XLPE Insulated Tray (CSA TC)

Number of Conductors Gauge Voltage Part Number

Number of Strands

Ground Wire Size

AWG

Insulation Thickness

IN

Jacket Thickness

INOverall OD

INWeightlb/Mft

Conductor Circular Mils Ampacity

3 14 AWG 600V 4C01HM1403070DR 7 3 x 18 0.762 1.143 10.36 192 4 107 25

3 12 AWG 600V 4C01HM1203070DR 7 3 x 16 0.762 1.143 11.40 254 6 530 30

3 10 AWG 600V 4C01HM1003070DR 7 3 x 14 0.762 1.143 12.98 379 10 380 40

3 8 AWG 600V 4C01HM0803070DR 7 3 x 14 1.143 1.524 17.07 573 16 510 55

7 6 AWG 600V 4C01HM0603070DR 7 3 x 12 1.143 1.524 18.82 780 26 250 75

3 4 AWG 600V 4C01HM0403070DR 7 3 x 12 1.143 2.032 22.40 1 120 41 740 95

3 2 AWG 600V 4C01HM0203070DR 7 3 x 10 1.143 2.032 25.58 1 594 66 370 130

3 1 AWG 600V 4C01HM0103470DR 19 3 x 10 1.397 2.032 28.78 1 921 83 690 150

3 1/0 AWG 600V 4C01HM1/03470DR 19 3 x 10 1.397 2.032 31.34 2 325 105 600 170

3 2/0 AWG 600V 4C01HM2/03470DR 19 3 x 10 1.397 2.032 33.83 2 775 133 100 195

3 3/0 AWG 600V 4C01HM3/03470DR 19 3 x 8 1.397 2.032 36.55 3 431 167 800 225

3 4/0 AWG 600V 4C01HM4/03470DR 19 3 x 8 1.397 2.032 39.62 4 140 211 600 260

Page 93: Shaw Flex Catalogue

Phone: 1 800-668-4842 91 email: [email protected]

VFD

Cable Cross Section

Overall Armour: Aluminum or Steel Interlock armour is available

Overall Jacket: yellow FR PVC with a Nylon ripcord

Fillers: Polypropylene fillers under each ground wire

Three Phase Conductors: 14 to 4/0 AWG stranded bare copper, 90°C FR XLPE insulated

Three Ground Wires: Trisection ground wires in immediate contact with copper tape, helically applied over the core assembly to control EMI

Variable Frequancy Drive XLPE Insulated Armoured (CSA TECK90)

Number of Conductors Gauge Voltage Part Number

Number of Strands

Ground Wire Size

AWG

Insulation Thickness

IN

Inner Jacket Thickness

IN

Outer Jacket

ThicknessIN

Overall ODIN

Weightlb/Mft

Conductor Circular

Mils Ampacity

3 14 AWG 1000V 8021HM1403077DR 7 3 x 18 1.143 1.143 1.270 20.345 464 4 100 15

3 12 AWG 1000V 8021HM1203077DR 7 3 x 16 1.143 1.143 1.270 21.361 545 6 530 20

3 10 AWG 1000V 8021HM1003077DR 7 3 x 14 1.143 1.524 1.270 23.698 712 10 380 30

3 8 AWG 1000V 8021HM0803077DR 7 3 x 14 1.143 1.524 1.270 25.400 862 16 510 45

7 6 AWG 1000V 8021HM0603077DR 7 3 x 12 1.524 1.524 1.270 29.286 1250 26 240 65

3 4 AWG 1000V 8021HM0403077DR 7 3 x 12 1.524 2.032 1.270 32.868 1646 41 740 85

3 2 AWG 1000V 8021HM0203077DR 7 3 x 10 1.524 2.032 1.270 36.043 2193 66 360 120

3 1 AWG 1000V 8021HM0103477DR 19 3 x 10 2.032 2.032 1.270 40.361 2675 83 690 140

3 1/0 AWG 1000V 8021HM1/03477DR 19 3 x 10 2.032 2.032 1.524 43.434 3164 105 600 155

3 2/0 AWG 1000V 8021HM2/03477DR 19 3 x 10 2.032 2.032 1.524 45.923 3690 133 100 185

3 3/0 AWG 1000V 8021HM3/03477DR 19 3 x 8 2.032 2.032 1.524 50.267 4534 167 800 210

3 4/0 AWG 1000V 8021HM4/03477DR 19 3 x 8 2.032 2.032 1.524 53.365 5345 211 600 235

Variable Frequancy Drive XLPE Insulated Armoured (CSA TECK90)

Number of Conductors Gauge Voltage Part Number

Number of Strands

Ground Wire Size

AWG

Insulation Thickness

IN

Inner Jacket Thickness

IN

Outer Jacket

ThicknessIN

Overall ODIN

Weightlb/Mft

Conductor Circular

Mils Ampacity

3 14 AWG 600V 6921HM1403077DR 7 3 x 18 0.762 1.143 1.270 18.80 412 4 107 25

3 12 AWG 600V 6921HM1203077DR 7 3 x 16 0.762 1.143 1.270 19.84 489 6 530 30

3 10 AWG 600V 6921HM1003077DR 7 3 x 14 0.762 1.143 1.270 21.41 637 10 380 40

3 8 AWG 600V 6921HM0803077DR 7 3 x 14 1.143 1.524 1.270 25.50 890 16 510 55

7 6 AWG 600V 6921HM0603077DR 7 3 x 12 1.143 1.524 1.270 27.25 1 122 26 250 75

3 4 AWG 600V 6921HM0403077DR 7 3 x 12 1.143 2.032 1.270 31.34 1 596 41 740 95

3 2 AWG 600V 6921HM0203077DR 7 3 x 10 1.143 2.032 1.270 34.52 2 126 66 370 130

3 1 AWG 600V 6921HM0103477DR 19 3 x 10 1.397 2.032 1.270 37.74 5 206 83 690 150

3 1/0 AWG 600V 6921HM1/03477DR 19 3 x 10 1.397 2.032 1.270 40.08 2 954 105 600 170

3 2/0 AWG 600V 6921HM2/03477DR 19 3 x 10 1.397 2.032 1.524 43.31 3 494 133 100 195

3 3/0 AWG 600V 6921HM3/03477DR 19 3 x 8 1.397 2.032 1.524 46.00 4 199 167 800 225

3 4/0 AWG 600V 6921HM4/03477DR 19 3 x 8 1.397 2.032 1.524 50.75 5 093 211 600 260

Page 94: Shaw Flex Catalogue

Flex

ar

ShawFlex Flexar (csa/ul) Cables

Unarmoured a. Control

ShawFlex Flexar cables have been designed to meet the rigorous requirements established by both the Underwriters Laboratories and The Canadian Standards Association. Flexar Cables can be found in projects though out the world.

UnarmouredShawFlex Flexar cables are primarily used in c-track, conveyor systems, robotics, automation & machine tool applications. All Flexar Cables are oil and Abrasion resistant.

TYPE CSA UL Characteristics

SF AWM 1 A/B II A/B AWM STYLE # 2586 Stationary Control: Unshielded

SFB AWM 1 A/B II A/B AWM STYLE # 2586 Stationary Control: Tin Copper Braid Shield

SFC AWM 1 A/B II A/B AWM STYLE # 20669 Stationary Control: -40c Unshielded

SFBC AWM 1 A/B II A/B AWM STYLE # 20669 Stationary Control: -40c Tin Copper Braid Shield

SFP AWM 1 A/B II A/B AWM STYLE # 20669 Stationary Control: Unshielded

SFBP AWM 1 A/B II A/B AWM STYLE # 20669 Stationary Control: Tin Copper Braid Shield

EF AWM 1 A/B II A/B AWM STYLE # 2586 Intermediate Flexing Applications: Unshielded

EFB AWM 1 A/B II A/B AWM STYLE # 2586 Intermediate Flexing Applications: Tin Copper Braid Shield

EFC AWM 1 A/B II A/B AWM STYLE # 20669 Intermediate Flexing Applications: -40c Unshielded

EFBC AWM 1 A/B II A/B AWM STYLE # 20669 Intermediate Flexing Applications: -40c Tin Copper Braid Shield

EFP AWM 1 A/B II A/B AWM STYLE # 20669 Intermediate Flexing Applications: : Unshielded

EFBP AWM 1 A/B II A/B AWM STYLE # 20669 Intermediate Flexing Applications: Tin Copper Braid Shield

UF AWM 1 A/B II A/B AWM STYLE # 2586 Heavy Duty, Continuous Applications: Unshielded

UFB AWM 1 A/B II A/B AWM STYLE # 2586 Heavy Duty, Continuous Applications: Tin Copper Braid Shield

UFC AWM 1 A/B II A/B AWM STYLE # 20669 Heavy Duty, Continuous Applications: -40c Unshielded

UFBC AWM 1 A/B II A/B AWM STYLE # 20669 Heavy Duty, Continuous Applications: -40c Tin Copper Braid Shield

UFP AWM 1 A/B II A/B AWM STYLE # 20669 Heavy Duty, Continuous Applications: Unshielded

UFBP AWM 1 A/B II A/B AWM STYLE # 20669 Heavy Duty, Continuous Applications: Tin Copper Braid Shield

Page 95: Shaw Flex Catalogue

Phone: 1 800-668-4842 93 email: [email protected]

Flexar

Unshielded Flexar Cable Available Constructions:

SF SFC SFP EF EFC EFP UF UFC UFP

Characteristics:

Stationary Bend Radius 5x 5x 5x 5x 5x 5x 5x 5x 5x

Flexing Bend Radius None None None 12x 12x 12x 8x 8x 8x

Flame Retardant - FT4 a - - a - - a - -Flame Retardant - FT1 a a a a a a a a a-40c - a - - a - - a -Superior Abrasion Resistant - a a - a a - a aVoltage Ratings:

600V a a a a a a a a aJacketing Options:

PVC Jacket a - - a - - a - -Polyurethane Jacket - a a - a a - a aInsulation Options:

PVC Insulation a - a a - a a - aTPE Insulation - a - - a - - a -Shielding Options:

tin copper braid - - - - - - - - -

Shielded Flexar Cable Available Constructions:

SFB SPBC SFBP EFB EPBC EFBP UFB UPBC UFBP

Characteristics:

Stationary Bend Radius 8x 8x 8x 8x 8x 8x 8x 8x 8x

Flexing Bend Radius None None None 15x 15x 15x 10x 10x 10x

Flame Retardant - FT4 a - - a - - a - -Flame Retardant - FT1 a a a a a a a a a-40c - a - - a - - a -Superior Abrasion Resistant - a a - a a - a aVoltage Ratings:

600V a a a a a a a a aJacketing Options:

PVC Jacket a - - a - - a - -Polyurethane Jacket - a a - a a - a aInsulation Options:

PVC Insulation a - a a - a a - aTPE Insulation - a - - a - - a -Shielding Options:

tin copper braid a a a - - - - - -tin copper braid with bedding jacket

- - - a a a a a a

Page 96: Shaw Flex Catalogue

Ship

boar

d Ca

bles

ShawFlex Marine/Shipboard Cables

Armoured a. Instrumentation (Signal) b. Control c. Power (Distribution)

Unarmoured a. Instrumentation (Signal) b. Control c. Power (Distribution)

ShawFlex Marine/Shipboard cables have been designed to meet the rigorous requirements established by both the IEEE and the IEC.

Unarmoured TYPE IEEE IEC Temp Rating Approvals

T (PVC) 1580 - 75OC ABS, Transport Canada

T (PVC) - 60092-37660092-353

70OC ABS, Transport Canada, DNV

T/N (PVC/NYLON) 1580 - 90OC ABS, Transport Canada

X (XLPE) 1580 60092-37660092-353

90OC ABS, Transport Canada, DNV

X (XLPE) 1580 - 90OC ABS, Transport Canada

P (XLPO) 1580 - 100OC ABS, Transport Canada, DNV

Armoured TYPE IEEE IEC Temp Rating Approvals

T (PVC) 1580 - 75OC ABS, Transport Canada

T (PVC) - 60092-37660092-353

70OC ABS, Transport Canada, DNV

T/N (PVC/NYLON) 1580 - 90OC ABS, Transport Canada

X (XLPE) 1580 60092-37660092-353

90OC ABS, Transport Canada, DNV

X (XLPE) 1580 - 90OC ABS, Transport Canada

P (XLPO) 1580 - 100OC ABS, Transport Canada, DNV

Page 97: Shaw Flex Catalogue

Phone: 1 800-668-4842 95 email: [email protected]

Shipboard Cables

Unarmoured Marine/Shipboard Cables Available Constructions:T (PVC)

IEEET (PVC)

IECT/N (PVC/NYLON)

IEEEX (XLPE)

IEEEX (XLPE)

IECP (XLPO)

IEEE

Characteristics:

Flame Retardant - IEEE 1202 a - a a - aFlame Retardant - IEC 60332-3 Cat A

- a - - a -

-40c a a - a a aSunlight Resistant a a a a a aVoltage Ratings:

150V/250V a a - - a -300V a - a a - a600V/1000V a a a a a aJacketing Options:

90OC PVC Jacket a a a a a -90OC CP (Hypalon®) Jacket - - - - - aShielding Options:

OS Aluminum Mylar a a a a a aISOS Aluminum Mylar a a a a a atin copper braid a a a a a a

Armoured Marine/Shipboard Cables Available Constructions:T (PVC)

IEEET (PVC)

IECT/N (PVC/NYLON)

IEEEX (XLPE)

IEEEX (XLPE)

IECP (XLPO)

IEEE

Characteristics:

Flame Retardant - IEEE 1202 a - a a - aFlame Retardant - IEC 60332-3 Cat A

- a - - a -

-40c a a - a a aSunlight Resistant a a a a a aVoltage Ratings:

150V/250V a a - - a -300V a - a a - a600V/1000V a a a a a aArmouring Options:

tin copper braid a a a a a aBronze Braid a a a a a aAluminum Braid a a a a a aJacketing Options:

90OC PVC Jacket a a a a a -90OC CP (Hypalon®) Jacket - - - - - aShielding Options:

OS Aluminum Mylar a a a a a aISOS Aluminum Mylar a a a a a atin copper braid a a a a a a

Page 98: Shaw Flex Catalogue

Ship

boar

d Ca

bles

T-Flex UnarmouredIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V SW021U200100000 1.02 0.040 6.4 0.253 31 46 3.0 77 350 159

2 20 AWG 150V/250V SW021U200200000 1.14 0.045 10.2 0.401 70 104 4.8 122 366 166

4 20 AWG 150V/250V SW021U200400000 1.14 0.045 11.7 0.459 103 154 5.5 140 398 180

6 20 AWG 150V/250V SW021U200600000 1.27 0.050 14.1 0.556 144 214 6.7 169 430 195

8 20 AWG 150V/250V SW021U200800000 1.27 0.050 15.2 0.599 175 261 7.2 183 462 210

10 20 AWG 150V/250V SW021U201000000 1.40 0.055 18.1 0.711 221 329 8.5 217 494 224

12 20 AWG 150V/250V SW021U201200000 1.40 0.055 18.6 0.732 250 372 8.8 223 526 239

14 20 AWG 150V/250V SW021U201400000 1.52 0.060 19.8 0.780 291 433 9.4 238 558 253

16 20 AWG 150V/250V SW021U201600000 1.52 0.060 20.9 0.822 321 477 9.9 251 590 268

18 20 AWG 150V/250V SW021U201800000 1.52 0.060 22.0 0.866 357 531 10.4 264 622 282

20 20 AWG 150V/250V SW021U202000000 1.65 0.065 23.3 0.919 403 599 11.0 280 654 297

1 18 AWG 150V/250V SW021U180100000 1.02 0.040 6.9 0.273 38 57 3.3 83 360 163

2 18 AWG 150V/250V SW021U180200000 1.14 0.045 11.1 0.437 88 131 5.2 133 386 175

4 18 AWG 150V/250V SW021U180400000 1.27 0.050 13.0 0.512 137 203 6.1 156 438 199

6 18 AWG 150V/250V SW021U180600000 1.40 0.055 15.7 0.620 192 286 7.4 189 490 222

8 18 AWG 150V/250V SW021U180800000 1.40 0.055 17.0 0.669 238 354 8.0 204 542 246

10 18 AWG 150V/250V SW021U181000000 1.52 0.060 20.1 0.793 301 447 9.5 242 594 269

12 18 AWG 150V/250V SW021U181200000 1.52 0.060 20.8 0.817 343 511 9.8 249 646 293

14 18 AWG 150V/250V SW021U181400000 1.52 0.060 21.8 0.859 388 577 10.3 262 698 317

16 18 AWG 150V/250V SW021U181600000 1.65 0.065 23.3 0.917 439 654 11.0 279 750 340

18 18 AWG 150V/250V SW021U181800000 1.65 0.065 24.5 0.965 488 727 11.6 294 802 364

20 18 AWG 150V/250V SW021U182000000 1.78 0.070 26.0 1.024 551 820 12.3 312 854 387

1 16 AWG 150V/250V SW021U160100000 1.02 0.040 8.1 0.317 53 78 3.8 97 375 170

2 16 AWG 150V/250V SW021U160200000 1.27 0.050 13.4 0.526 126 188 6.3 160 416 189

4 16 AWG 150V/250V SW021U160400000 1.40 0.055 15.7 0.617 202 301 7.4 188 499 226

6 16 AWG 150V/250V SW021U160600000 1.52 0.060 19.0 0.749 282 420 9.0 228 581 264

8 16 AWG 150V/250V SW021U160800000 1.52 0.060 20.6 0.809 351 522 9.7 247 664 301

10 16 AWG 150V/250V SW021U161000000 1.65 0.065 24.4 0.961 444 661 11.5 293 746 338

12 16 AWG 150V/250V SW021U161200000 1.65 0.065 25.2 0.991 507 754 11.9 302 828 376

14 16 AWG 150V/250V SW021U161400000 1.78 0.070 26.8 1.054 589 877 12.6 321 911 413

16 16 AWG 150V/250V SW021U161600000 1.78 0.070 28.3 1.113 653 972 13.4 339 993 450

Page 99: Shaw Flex Catalogue

Phone: 1 800-668-4842 97 email: [email protected]

Shipboard Cables

T-Flex Armoured with SheathIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V SWB21U200100009 0.89 0.035 9.9 0.390 97 144 4.7 119 350 159

2 20 AWG 150V/250V SWB21U200200009 0.89 0.035 13.7 0.538 170 253 6.5 164 366 166

4 20 AWG 150V/250V SWB21U200400009 1.02 0.040 15.4 0.606 222 331 7.3 185 398 180

6 20 AWG 150V/250V SWB21U200600009 1.02 0.040 17.9 0.703 286 426 8.4 214 430 195

8 20 AWG 150V/250V SWB21U200800009 1.02 0.040 19.0 0.747 328 488 9.0 228 462 210

10 20 AWG 150V/250V SWB21U201000090 1.14 0.045 22.0 0.868 409 608 10.4 265 494 224

12 20 AWG 150V/250V SWB21U201200009 1.14 0.045 22.6 0.890 443 659 10.7 271 526 239

14 20 AWG 150V/250V SWB21U201400009 1.14 0.045 23.8 0.937 496 737 11.2 286 558 253

16 20 AWG 150V/250V SWB21U201600009 1.14 0.045 24.9 0.979 536 798 11.8 299 590 268

18 20 AWG 150V/250V SWB21U201800009 1.27 0.050 26.2 1.033 592 880 12.4 315 622 282

20 20 AWG 150V/250V SWB21U202000090 1.27 0.050 27.6 1.086 651 969 13.0 331 654 297

1 18 AWG 150V/250V SWB21U180100009 0.89 0.035 10.4 0.410 109 162 4.9 125 360 163

2 18 AWG 150V/250V SWB21U180200009 0.89 0.035 14.6 0.574 197 292 6.9 175 386 175

4 18 AWG 150V/250V SWB21U180400009 1.02 0.040 16.7 0.659 269 400 7.9 201 438 199

6 18 AWG 150V/250V SWB21U180600009 1.02 0.040 19.5 0.767 350 521 9.2 234 490 222

8 18 AWG 150V/250V SWB21U180800009 1.14 0.045 21.0 0.826 415 617 9.9 252 542 246

10 18 AWG 150V/250V SWB21U181000090 1.14 0.045 24.1 0.950 509 757 11.4 290 594 269

12 18 AWG 150V/250V SWB21U181200009 1.14 0.045 24.8 0.974 557 829 11.7 297 646 293

14 18 AWG 150V/250V SWB21U181400009 1.27 0.050 26.1 1.027 621 924 12.3 313 698 317

16 18 AWG 150V/250V SWB21U181600009 1.27 0.050 27.5 1.084 687 1,023 13.0 330 750 340

18 18 AWG 150V/250V SWB21U181800009 1.27 0.050 28.8 1.133 749 1,115 13.6 345 802 364

20 18 AWG 150V/250V SWB21U182000090 1.27 0.050 30.3 1.192 827 1,230 14.3 363 854 387

1 16 AWG 150V/250V SWB21U160100009 0.89 0.035 11.5 0.454 133 199 5.5 139 375 170

2 16 AWG 150V/250V SWB21U160200009 1.02 0.040 17.1 0.673 261 389 8.1 205 416 189

4 16 AWG 150V/250V SWB21U160400009 1.02 0.040 19.4 0.764 360 535 9.2 233 499 226

6 16 AWG 150V/250V SWB21U160600009 1.14 0.045 23.0 0.906 479 713 10.9 276 581 264

8 16 AWG 150V/250V SWB21U160800009 1.14 0.045 24.6 0.967 563 838 11.6 295 664 301

10 16 AWG 150V/250V SWB21U161000090 1.27 0.050 28.7 1.128 704 1,047 13.5 344 746 338

12 16 AWG 150V/250V SWB21U161200009 1.27 0.050 29.4 1.159 774 1,152 13.9 353 828 376

14 16 AWG 150V/250V SWB21U161400009 1.40 0.055 31.3 1.231 883 1,314 14.8 375 911 413

16 16 AWG 150V/250V SWB21U161600009 1.40 0.055 32.8 1.290 963 1,434 15.5 393 993 450

Page 100: Shaw Flex Catalogue

Ship

boar

d Ca

bles

T-Flex UnarmouredIEEE Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 300V ST021U200100000 1.14 0.045 7.2 0.283 36 54 3.4 86 350 159

2 20 AWG 300V ST022U200200000 1.14 0.045 11.1 0.437 79 117 5.2 133 366 166

4 20 AWG 300V ST022U200400000 1.14 0.045 12.8 0.502 114 170 6.0 153 398 180

6 20 AWG 300V ST022U200600000 1.52 0.060 16.0 0.630 171 254 7.6 192 430 195

8 20 AWG 300V ST022U200800000 1.52 0.060 17.2 0.679 208 310 8.1 207 462 210

10 20 AWG 300V ST022U201000000 1.52 0.060 20.1 0.793 256 381 9.5 242 494 224

12 20 AWG 300V ST022U201200000 1.52 0.060 20.8 0.817 290 431 9.8 249 526 239

14 20 AWG 300V ST022U201400000 2.03 0.080 22.8 0.899 356 530 10.8 274 558 253

16 20 AWG 300V ST022U201600000 2.03 0.080 24.0 0.947 392 584 11.4 289 590 268

18 20 AWG 300V ST022U201800000 2.03 0.080 25.3 0.995 434 645 11.9 303 622 282

20 20 AWG 300V ST022U202000000 2.03 0.080 26.5 1.044 480 714 12.5 318 654 297

24 20 AWG 300V ST022U202400000 2.03 0.080 29.4 1.157 564 839 13.9 353 718 326

1 18 AWG 300V ST021U180100000 1.14 0.045 7.7 0.303 44 66 3.6 92 360 163

2 18 AWG 300V ST022U180200000 1.14 0.045 12.0 0.473 97 144 5.7 144 386 175

4 18 AWG 300V ST022U180400000 1.52 0.060 14.6 0.575 162 241 6.9 175 438 199

6 18 AWG 300V ST022U180600000 1.52 0.060 17.4 0.684 217 322 8.2 208 490 222

8 18 AWG 300V ST022U180800000 1.52 0.060 18.8 0.738 265 394 8.9 225 542 246

10 18 AWG 300V ST022U181000000 2.03 0.080 23.0 0.905 360 535 10.9 276 594 269

12 18 AWG 300V ST022U181200000 2.03 0.080 23.7 0.932 406 604 11.2 284 646 293

14 18 AWG 300V ST022U181400000 2.03 0.080 24.9 0.979 459 684 11.7 298 698 317

16 18 AWG 300V ST022U181600000 2.03 0.080 26.2 1.031 506 753 12.4 314 750 340

18 18 AWG 300V ST022U181800000 2.03 0.080 27.6 1.086 561 836 13.0 331 802 364

20 18 AWG 300V ST022U182000000 2.03 0.080 29.0 1.140 621 925 13.7 347 854 387

1 16 AWG 300V ST021U160100000 1.14 0.045 8.3 0.327 55 82 3.9 100 375 170

2 16 AWG 300V ST022U160200000 1.14 0.045 13.1 0.516 122 181 6.2 157 416 189

4 16 AWG 300V ST022U160400000 1.52 0.060 15.9 0.627 208 310 7.5 191 499 226

6 16 AWG 300V ST022U160600000 1.52 0.060 19.0 0.749 283 421 9.0 228 581 264

8 16 AWG 300V ST022U160800000 1.52 0.060 20.6 0.809 352 523 9.7 247 664 301

10 16 AWG 300V ST022U161000000 2.03 0.080 25.2 0.991 470 700 11.9 302 746 338

12 16 AWG 300V ST022U161200000 2.03 0.080 25.9 1.021 534 795 12.3 311 828 376

14 16 AWG 300V ST022U161400000 2.03 0.080 27.3 1.074 609 906 12.9 327 911 413

16 16 AWG 300V ST022U161600000 2.03 0.080 28.8 1.133 674 1,003 13.6 345 993 450

18 16 AWG 300V ST022U161800000 2.03 0.080 30.3 1.193 750 1,117 14.3 364 1,076 488

20 16 AWG 300V ST022U162000000 2.03 0.080 31.9 1.254 832 1,239 15.1 382 1,158 525

Page 101: Shaw Flex Catalogue

Phone: 1 800-668-4842 99 email: [email protected]

Shipboard Cables

T-Flex Armoured with Sheath IEEE Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 300V STB21U200100009 1.14 0.045 11.2 0.440 116 173 5.3 134 350 159

2 20 AWG 300V STB22U200200009 1.52 0.060 15.9 0.624 213 317 7.5 190 366 166

4 20 AWG 300V STB22U200400009 1.52 0.060 17.5 0.689 267 397 8.3 210 398 180

6 20 AWG 300V STB22U200600009 1.52 0.060 20.8 0.817 358 533 9.8 249 430 195

8 20 AWG 300V STB22U200800009 2.03 0.080 23.0 0.906 440 654 10.9 276 462 210

10 20 AWG 300V STB22U201000090 2.03 0.080 25.9 1.020 523 778 12.2 311 494 224

12 20 AWG 300V STB22U201200009 2.03 0.080 26.5 1.044 564 840 12.5 318 526 239

14 20 AWG 300V STB22U201400009 2.03 0.080 28.6 1.127 656 976 13.5 343 558 253

16 20 AWG 300V STB22U201600009 2.03 0.080 29.8 1.174 707 1,052 14.1 358 590 268

18 20 AWG 300V STB22U201800009 2.03 0.080 31.1 1.223 763 1,136 14.7 373 622 282

20 20 AWG 300V STB22U202000090 2.03 0.080 32.3 1.272 824 1,227 15.3 388 654 297

24 20 AWG 300V STB22U202400009 2.03 0.080 35.2 1.385 944 1,405 16.6 422 718 326

1 18 AWG 300V STB21U180100009 1.14 0.045 11.7 0.460 129 192 5.5 140 360 163

2 18 AWG 300V STB22U180200009 1.52 0.060 16.8 0.660 241 359 7.9 201 386 175

4 18 AWG 300V STB22U180400009 1.52 0.060 19.4 0.763 335 498 9.2 232 438 199

6 18 AWG 300V STB22U180600009 2.03 0.080 23.1 0.911 450 669 10.9 278 490 222

8 18 AWG 300V STB22U180800009 2.03 0.080 24.5 0.965 515 766 11.6 294 542 246

10 18 AWG 300V STB22U181000090 2.03 0.080 28.8 1.132 661 984 13.6 345 594 269

12 18 AWG 300V STB22U181200009 2.03 0.080 29.4 1.159 716 1,066 13.9 353 646 293

14 18 AWG 300V STB22U181400009 2.03 0.080 30.6 1.206 784 1,167 14.5 368 698 317

16 18 AWG 300V STB22U181600009 2.03 0.080 32.0 1.259 846 1,260 15.1 384 750 340

18 18 AWG 300V STB22U181800009 2.03 0.080 33.3 1.313 919 1,368 15.8 400 802 364

20 18 AWG 300V STB22U182000090 2.03 0.080 34.7 1.367 996 1,482 16.4 417 854 387

1 16 AWG 300V STB21U160100009 1.14 0.045 12.3 0.484 147 218 5.8 148 375 170

2 16 AWG 300V STB22U160200009 1.52 0.060 17.9 0.703 278 414 8.4 214 416 189

4 16 AWG 300V STB22U160400009 1.52 0.060 20.7 0.814 395 588 9.8 248 499 226

6 16 AWG 300V STB22U160600009 2.03 0.080 24.8 0.976 536 797 11.7 297 581 264

8 16 AWG 300V STB22U160800009 2.03 0.080 26.3 1.037 624 928 12.4 316 664 301

10 16 AWG 300V STB22U161000090 2.03 0.080 30.9 1.218 798 1,188 14.6 371 746 338

12 16 AWG 300V STB22U161200009 2.03 0.080 31.7 1.249 872 1,297 15.0 381 828 376

14 16 AWG 300V STB22U161400009 2.03 0.080 33.1 1.301 963 1,433 15.6 397 911 413

16 16 AWG 300V STB22U161600009 2.03 0.080 34.6 1.360 1,046 1,557 16.3 415 993 450

18 16 AWG 300V STB22U161800009 2.03 0.080 36.1 1.421 1,141 1,699 17.1 433 1,076 488

Page 102: Shaw Flex Catalogue

Ship

boar

d Ca

bles

T-Flex UnarmouredIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V S3021U200100000 1.02 0.040 6.9 0.273 34 50 3.3 83 350 159

2 20 AWG 150V/250V S3021U200200000 1.14 0.045 10.6 0.417 71 105 5.0 127 366 166

4 20 AWG 150V/250V S3021U200400000 1.27 0.050 12.4 0.489 104 155 5.9 149 398 180

6 20 AWG 150V/250V S3021U200600000 1.27 0.050 14.7 0.580 138 206 7.0 177 430 195

8 20 AWG 150V/250V S3021U200800000 1.40 0.055 16.2 0.636 173 257 7.6 194 462 210

10 20 AWG 150V/250V S3021U201000000 1.52 0.060 19.1 0.754 220 328 9.0 230 494 224

12 20 AWG 150V/250V S3021U201200000 1.52 0.060 19.7 0.776 248 369 9.3 237 526 239

14 20 AWG 150V/250V S3021U201400000 1.52 0.060 20.7 0.816 277 412 9.8 249 558 253

16 20 AWG 150V/250V S3021U201600000 1.52 0.060 21.9 0.861 305 454 10.3 262 590 268

18 20 AWG 150V/250V S3021U201800000 1.65 0.065 23.3 0.917 346 515 11.0 279 622 282

20 20 AWG 150V/250V S3021U202000000 1.65 0.065 24.5 0.963 382 569 11.6 293 654 297

1 18 AWG 150V/250V S3021U180100000 1.02 0.040 7.4 0.293 41 62 3.5 89 360 163

2 18 AWG 150V/250V S3021U180200000 1.14 0.045 11.5 0.452 86 128 5.4 138 386 175

4 18 AWG 150V/250V S3021U180400000 1.27 0.050 13.5 0.530 128 191 6.4 162 438 199

6 18 AWG 150V/250V S3021U180600000 1.40 0.055 16.3 0.643 180 268 7.7 196 490 222

8 18 AWG 150V/250V S3021U180800000 1.40 0.055 17.6 0.694 220 328 8.3 211 542 246

10 18 AWG 150V/250V S3021U181000000 1.52 0.060 20.9 0.823 281 418 9.9 251 594 269

12 18 AWG 150V/250V S3021U181200000 1.52 0.060 21.6 0.849 316 471 10.2 259 646 293

14 18 AWG 150V/250V S3021U181400000 1.65 0.065 22.9 0.903 364 541 10.8 275 698 317

16 18 AWG 150V/250V S3021U181600000 1.65 0.065 24.2 0.952 403 599 11.4 290 750 340

18 18 AWG 150V/250V S3021U181800000 1.65 0.065 25.5 1.004 448 667 12.0 306 802 364

20 18 AWG 150V/250V S3021U182000000 1.78 0.070 27.1 1.065 507 754 12.8 325 854 387

1 16 AWG 150V/250V S3021U160100000 1.02 0.040 8.1 0.317 53 78 3.8 97 375 170

2 16 AWG 150V/250V S3021U160200000 1.27 0.050 12.8 0.504 111 166 6.0 154 416 189

4 16 AWG 150V/250V S3021U160400000 1.27 0.050 14.7 0.580 168 250 7.0 177 499 226

6 16 AWG 150V/250V S3021U160600000 1.40 0.055 17.9 0.705 234 348 8.5 215 581 264

8 16 AWG 150V/250V S3021U160800000 1.52 0.060 19.6 0.773 296 440 9.3 235 664 301

10 16 AWG 150V/250V S3021U161000000 1.65 0.065 23.3 0.917 376 560 11.0 279 746 338

12 16 AWG 150V/250V S3021U161200000 1.65 0.065 24.0 0.945 426 635 11.3 288 828 376

14 16 AWG 150V/250V S3021U161400000 1.65 0.065 25.3 0.995 485 722 11.9 303 911 413

16 16 AWG 150V/250V S3021U161600000 1.78 0.070 26.9 1.061 546 812 12.7 323 993 450

Page 103: Shaw Flex Catalogue

Phone: 1 800-668-4842 101 email: [email protected]

Shipboard Cables

T-Flex Armoured with SheathIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V S3B21U200100009 0.89 0.035 10.4 0.410 104 155 4.9 125 350 159

2 20 AWG 150V/250V S3B21U200200009 0.89 0.035 14.1 0.555 175 260 6.7 169 366 166

4 20 AWG 150V/250V S3B21U200400009 1.02 0.040 16.2 0.636 230 343 7.6 194 398 180

6 20 AWG 150V/250V S3B21U200600009 1.02 0.040 18.5 0.728 287 427 8.7 222 430 195

8 20 AWG 150V/250V S3B21U200800009 1.02 0.040 19.9 0.784 335 498 9.4 239 462 210

10 20 AWG 150V/250V S3B21U201000090 1.14 0.045 23.1 0.911 419 623 10.9 278 494 224

12 20 AWG 150V/250V S3B21U201200009 1.14 0.045 23.7 0.934 452 672 11.2 285 526 239

14 20 AWG 150V/250V S3B21U201400009 1.14 0.045 24.7 0.974 491 730 11.7 297 558 253

16 20 AWG 150V/250V S3B21U201600009 1.27 0.050 26.1 1.028 539 802 12.3 313 590 268

18 20 AWG 150V/250V S3B21U201800009 1.27 0.050 27.5 1.084 594 884 13.0 330 622 282

20 20 AWG 150V/250V S3B21U202000090 1.27 0.050 28.7 1.130 642 956 13.6 344 654 297

1 18 AWG 150V/250V S3B21U180100009 0.89 0.035 10.9 0.430 117 174 5.2 131 360 163

2 18 AWG 150V/250V S3B21U180200009 1.02 0.040 15.2 0.599 204 303 7.2 183 386 175

4 18 AWG 150V/250V S3B21U180400009 1.02 0.040 17.2 0.678 265 394 8.1 207 438 199

6 18 AWG 150V/250V S3B21U180600009 1.14 0.045 20.3 0.800 351 522 9.6 244 490 222

8 18 AWG 150V/250V S3B21U180800009 1.14 0.045 21.6 0.851 403 600 10.2 259 542 246

10 18 AWG 150V/250V S3B21U181000090 1.14 0.045 24.9 0.981 496 739 11.8 299 594 269

12 18 AWG 150V/250V S3B21U181200009 1.27 0.050 25.8 1.016 547 814 12.2 310 646 293

14 18 AWG 150V/250V S3B21U181400009 1.27 0.050 27.2 1.070 608 905 12.8 326 698 317

16 18 AWG 150V/250V S3B21U181600009 1.27 0.050 28.4 1.120 660 982 13.4 341 750 340

18 18 AWG 150V/250V S3B21U181800009 1.27 0.050 29.7 1.171 719 1,070 14.1 357 802 364

20 18 AWG 150V/250V S3B21U182000090 1.40 0.055 31.6 1.242 804 1,196 14.9 379 854 387

1 16 AWG 150V/250V S3B21U160100009 0.89 0.035 11.5 0.454 134 199 5.5 139 375 170

2 16 AWG 150V/250V S3B21U160200009 1.02 0.040 16.5 0.651 241 359 7.8 198 416 189

4 16 AWG 150V/250V S3B21U160400009 1.02 0.040 18.5 0.728 316 471 8.7 222 499 226

6 16 AWG 150V/250V S3B21U160600009 1.14 0.045 21.9 0.863 420 625 10.4 263 581 264

8 16 AWG 150V/250V S3B21U160800009 1.14 0.045 23.6 0.930 499 742 11.2 283 664 301

10 16 AWG 150V/250V S3B21U161000090 1.27 0.050 27.5 1.084 624 929 13.0 330 746 338

12 16 AWG 150V/250V S3B21U161200009 1.27 0.050 28.3 1.113 682 1,015 13.4 339 828 376

14 16 AWG 150V/250V S3B21U161400009 1.27 0.050 29.5 1.163 754 1,121 14.0 354 911 413

16 16 AWG 150V/250V S3B21U161600009 1.40 0.055 31.4 1.238 842 1,253 14.9 377 993 450

Page 104: Shaw Flex Catalogue

Ship

boar

d Ca

bles

T/N-Flex Unarmoured IEEE Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V S9010U160200000 1.14 0.045 7.8 0.306 51 76 1.8 47 375 170 15.0

3 16 AWG 600V/1000V S9010U160300000 1.14 0.045 8.2 0.321 61 91 1.9 49 396 179 18.0

4 16 AWG 600V/1000V S9010U160400000 1.14 0.045 8.8 0.346 75 112 2.1 53 416 189 14.4

6 16 AWG 600V/1000V S9010U160600000 1.14 0.045 10.3 0.406 106 158 2.4 62 458 208 14.4

7 16 AWG 600V/1000V S9010U160700000 1.14 0.045 10.3 0.406 115 172 2.4 62 478 217 12.6

8 16 AWG 600V/1000V S9010U160800000 1.14 0.045 11.1 0.436 131 194 2.6 66 499 226 12.6

10 16 AWG 600V/1000V S9010U161000000 1.14 0.045 12.9 0.506 161 240 3.0 77 540 245 9.0

12 16 AWG 600V/1000V S9010U161200000 1.14 0.045 13.2 0.521 183 272 3.1 79 581 264 9.0

24 16 AWG 600V/1000V S9010U162400000 1.52 0.060 18.8 0.740 366 545 4.4 113 828 376 8.1

36 16 AWG 600V/1000V S9010U163600000 1.52 0.060 21.3 0.840 517 769 5.0 128 1,076 488 7.2

2 14 AWG 600V/1000V S9010U140200000 1.14 0.045 8.5 0.336 68 100 2.0 51 400 181 24.0

3 14 AWG 600V/1000V S9010U140300000 1.14 0.045 9.0 0.353 85 126 2.1 54 433 196 29.0

4 14 AWG 600V/1000V S9010U140400000 1.14 0.045 9.7 0.382 101 151 2.3 58 466 211 23.2

6 14 AWG 600V/1000V S9010U140600000 1.14 0.045 11.5 0.451 145 215 2.7 69 531 241 23.2

7 14 AWG 600V/1000V S9010U140700000 1.14 0.045 11.5 0.451 159 236 2.7 69 564 256 20.3

8 14 AWG 600V/1000V S9010U140800000 1.14 0.045 12.3 0.486 181 270 2.9 74 597 271 20.3

10 14 AWG 600V/1000V S9010U141000000 1.52 0.060 15.1 0.596 242 360 3.6 91 663 301 14.5

12 14 AWG 600V/1000V S9010U141200000 1.52 0.060 15.6 0.613 277 412 3.7 93 729 331 14.5

24 14 AWG 600V/1000V S9010U142400000 1.52 0.060 21.3 0.838 518 771 5.0 128 1,124 510 13.1

2 12 AWG 600V/1000V S9010U120200000 1.14 0.045 9.5 0.374 89 133 2.2 57 438 199 29.0

3 12 AWG 600V/1000V S9010U120300000 1.14 0.045 10.0 0.394 115 171 2.4 60 491 222 36.0

4 12 AWG 600V/1000V S9010U120400000 1.14 0.045 10.9 0.428 144 215 2.6 65 543 246 28.8

6 12 AWG 600V/1000V S9010U120600000 1.14 0.045 12.9 0.508 203 302 3.0 77 647 294 28.8

7 12 AWG 600V/1000V S9010U120700000 1.14 0.045 12.9 0.508 225 334 3.0 77 699 317 25.2

8 12 AWG 600V/1000V S9010U120800000 1.52 0.060 14.7 0.578 273 406 3.5 88 752 341 25.2

10 12 AWG 600V/1000V S9010U121000000 1.52 0.060 17.1 0.672 338 504 4.0 102 856 388 18.0

12 12 AWG 600V/1000V S9010U121200000 1.52 0.060 17.6 0.692 390 580 4.2 105 960 436 18.0

24 12 AWG 600V/1000V S9010U122400000 2.03 0.080 25.2 0.992 782 1,163 6.0 151 1,587 720 16.2

36 12 AWG 600V/1000V S9010U123600000 2.03 0.080 28.6 1.126 1,114 1,657 6.8 172 2,213 1,004 14.4

2 10 AWG 600V/1000V S9010U100200000 1.14 0.045 11.3 0.444 129 193 2.7 68 500 227 38.0

3 10 AWG 600V/1000V S9010U100300000 1.14 0.045 11.9 0.469 169 251 2.8 72 583 264 46.0

4 10 AWG 600V/1000V S9010U100400000 1.14 0.045 13.0 0.512 212 316 3.1 78 666 302 36.8

6 10 AWG 600V/1000V S9010U100600000 1.52 0.060 16.3 0.643 327 487 3.9 98 832 377 36.8

7 10 AWG 600V/1000V S9010U100700000 1.52 0.060 16.3 0.643 362 539 3.9 98 915 415 32.2

8 10 AWG 600V/1000V S9010U100800000 1.52 0.060 17.6 0.694 406 605 4.2 106 998 453 32.2

10 10 AWG 600V/1000V S9010U101000000 1.52 0.060 20.6 0.812 506 753 4.9 124 1,164 528 23.0

12 10 AWG 600V/1000V S9010U101200000 1.52 0.060 21.3 0.837 586 872 5.0 128 1,330 603 23.0

24 10 AWG 600V/1000V S9010U102400000 2.03 0.080 30.5 1.202 1,177 1,751 7.2 183 2,326 1,055 20.7

Page 105: Shaw Flex Catalogue

Phone: 1 800-668-4842 103 email: [email protected]

Shipboard Cables

T/N-Flex Armoured with Sheath IEEE Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V S9B10U160200009 1.14 0.045 11.8 0.463 142 211 5.6 141 375 170 15.0

3 16 AWG 600V/1000V S9B10U160300009 1.14 0.045 12.2 0.478 156 233 5.7 146 396 179 18.0

4 16 AWG 600V/1000V S9B10U160400009 1.14 0.045 12.8 0.503 177 263 6.0 153 416 189 14.4

6 16 AWG 600V/1000V S9B10U160600009 1.52 0.060 15.1 0.593 240 358 7.1 181 458 208 14.4

7 16 AWG 600V/1000V S9B10U160700009 1.52 0.060 15.1 0.593 250 371 7.1 181 478 217 12.6

8 16 AWG 600V/1000V S9B10U160800009 1.52 0.060 15.8 0.623 274 407 7.5 190 499 226 12.6

10 16 AWG 600V/1000V S9B10U161000090 1.52 0.060 17.6 0.693 325 483 8.3 211 540 245 9.0

12 16 AWG 600V/1000V S9B10U161200009 1.52 0.060 18.0 0.708 351 522 8.5 216 581 264 9.0

24 16 AWG 600V/1000V S9B10U162400009 2.03 0.080 24.6 0.967 635 944 11.6 295 828 376 8.1

36 16 AWG 600V/1000V S9B10U163600009 2.03 0.080 27.1 1.067 818 1,218 12.8 325 1,076 488 7.2

2 14 AWG 600V/1000V S9B10U140200009 1.14 0.045 12.5 0.493 166 248 5.9 150 400 181 24.0

3 14 AWG 600V/1000V S9B10U140300009 1.14 0.045 13.0 0.511 188 280 6.1 156 433 196 29.0

4 14 AWG 600V/1000V S9B10U140400009 1.14 0.045 13.7 0.539 212 316 6.5 164 466 211 23.2

6 14 AWG 600V/1000V S9B10U140600009 1.52 0.060 16.2 0.638 292 434 7.7 195 531 241 23.2

7 14 AWG 600V/1000V S9B10U140700009 1.52 0.060 16.2 0.638 306 455 7.7 195 564 256 20.3

8 14 AWG 600V/1000V S9B10U140800009 1.52 0.060 17.1 0.673 339 504 8.1 205 597 271 20.3

10 14 AWG 600V/1000V S9B10U141000090 1.52 0.060 19.9 0.783 432 642 9.4 239 663 301 14.5

12 14 AWG 600V/1000V S9B10U141200009 1.52 0.060 20.3 0.801 472 702 9.6 244 729 331 14.5

24 14 AWG 600V/1000V S9B10U142400009 2.03 0.080 27.1 1.065 819 1,219 12.8 325 1,124 510 13.1

2 12 AWG 600V/1000V S9B10U120200009 1.14 0.045 13.5 0.531 198 295 6.4 162 438 199 29.0

3 12 AWG 600V/1000V S9B10U120300009 1.52 0.060 14.8 0.582 245 365 7.0 177 491 222 36.0

4 12 AWG 600V/1000V S9B10U120400009 1.52 0.060 15.6 0.615 285 424 7.4 187 543 246 28.8

6 12 AWG 600V/1000V S9B10U120600009 1.52 0.060 17.7 0.695 367 546 8.3 212 647 294 28.8

7 12 AWG 600V/1000V S9B10U120700009 1.52 0.060 17.7 0.695 389 578 8.3 212 699 317 25.2

8 12 AWG 600V/1000V S9B10U120800009 1.52 0.060 19.4 0.766 458 681 9.2 233 752 341 25.2

10 12 AWG 600V/1000V S9B10U121000090 2.03 0.080 22.8 0.899 584 870 10.8 274 856 388 18.0

12 12 AWG 600V/1000V S9B10U121200009 2.03 0.080 23.4 0.920 642 956 11.0 280 960 436 18.0

24 12 AWG 600V/1000V S9B10U122400009 2.03 0.080 31.0 1.219 1,133 1,687 14.6 372 1,587 720 16.2

36 12 AWG 600V/1000V S9B10U123600009 2.03 0.080 34.4 1.353 1,510 2,246 16.2 413 2,213 1,004 14.4

2 10 AWG 600V/1000V S9B10U100200009 1.52 0.060 16.0 0.631 275 409 7.6 192 500 227 38.0

3 10 AWG 600V/1000V S9B10U100300009 1.52 0.060 16.7 0.657 322 479 7.9 200 583 264 46.0

4 10 AWG 600V/1000V S9B10U100400009 1.52 0.060 17.8 0.699 377 561 8.4 213 666 302 36.8

6 10 AWG 600V/1000V S9B10U100600009 1.52 0.060 21.1 0.830 531 790 10.0 253 832 377 36.8

7 10 AWG 600V/1000V S9B10U100700009 1.52 0.060 21.1 0.830 566 842 10.0 253 915 415 32.2

8 10 AWG 600V/1000V S9B10U100800009 2.03 0.080 23.4 0.921 659 981 11.1 281 998 453 32.2

10 10 AWG 600V/1000V S9B10U101000090 2.03 0.080 26.4 1.039 798 1,188 12.5 317 1,164 528 23.0

12 10 AWG 600V/1000V S9B10U101200009 2.03 0.080 27.0 1.065 887 1,319 12.8 325 1,330 603 23.0

24 10 AWG 600V/1000V S9B10U102400009 2.03 0.080 36.3 1.429 1,598 2,378 17.2 436 2,326 1,055 20.7

Page 106: Shaw Flex Catalogue

Ship

boar

d Ca

bles

X-Flex - UnarmouredIEEE Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SY010U160200000 1.14 0.045 8.8 0.346 58 86 2.1 53 375 170 15.0

3 16 AWG 600V/1000V SY010U160300000 1.14 0.045 9.3 0.364 72 107 2.2 55 396 179 18.0

4 16 AWG 600V/1000V SY010U160400000 1.14 0.045 10.0 0.394 85 126 2.4 60 416 189 14.4

6 16 AWG 600V/1000V SY010U160600000 1.14 0.045 11.8 0.466 120 179 2.8 71 458 208 14.4

7 16 AWG 600V/1000V SY010U160700000 1.14 0.045 11.8 0.466 131 195 2.8 71 478 217 12.6

8 16 AWG 600V/1000V SY010U160800000 1.14 0.045 12.8 0.502 150 224 3.0 77 499 226 12.6

10 16 AWG 600V/1000V SY010U161000000 1.52 0.060 15.7 0.616 202 300 3.7 94 540 245 9.0

12 16 AWG 600V/1000V SY010U161200000 1.52 0.060 16.1 0.634 229 342 3.8 97 581 264 9.0

24 16 AWG 600V/1000V SY010U162400000 2.03 0.080 22.9 0.900 454 676 5.4 137 828 376 8.1

36 16 AWG 600V/1000V SY010U163600000 2.03 0.080 25.9 1.020 634 943 6.1 155 1,076 488 7.2

2 14 AWG 600V/1000V SY010U140200000 1.14 0.045 9.6 0.376 73 109 2.3 57 400 181 24.0

3 14 AWG 600V/1000V SY010U140300000 1.14 0.045 10.1 0.396 92 137 2.4 60 433 196 29.0

4 14 AWG 600V/1000V SY010U140400000 1.14 0.045 10.9 0.430 116 172 2.6 66 466 211 23.2

6 14 AWG 600V/1000V SY010U140600000 1.14 0.045 13.0 0.511 161 239 3.1 78 531 241 23.2

7 14 AWG 600V/1000V SY010U140700000 1.14 0.045 13.0 0.511 176 262 3.1 78 564 256 20.3

8 14 AWG 600V/1000V SY010U140800000 1.52 0.060 14.8 0.581 216 322 3.5 89 597 271 20.3

10 14 AWG 600V/1000V SY010U141000000 1.52 0.060 17.2 0.676 268 399 4.1 103 663 301 14.5

12 14 AWG 600V/1000V SY010U141200000 1.52 0.060 17.7 0.696 307 457 4.2 106 729 331 14.5

24 14 AWG 600V/1000V SY010U142400000 2.03 0.080 25.4 0.998 614 913 6.0 152 1,124 510 13.1

36 14 AWG 600V/1000V SY010U143600000 2.03 0.080 28.8 1.133 868 1,291 6.8 173 1,518 689 11.6

2 12 AWG 600V/1000V SY010U120200000 1.14 0.045 10.5 0.414 97 144 2.5 63 438 199 29.0

3 12 AWG 600V/1000V SY010U120300000 1.14 0.045 11.1 0.437 126 187 2.6 67 491 222 36.0

4 12 AWG 600V/1000V SY010U120400000 1.14 0.045 12.1 0.476 156 233 2.9 72 543 246 28.8

6 12 AWG 600V/1000V SY010U120600000 1.52 0.060 15.2 0.598 242 360 3.6 91 647 294 28.8

7 12 AWG 600V/1000V SY010U120700000 1.52 0.060 15.2 0.598 266 396 3.6 91 699 317 25.2

8 12 AWG 600V/1000V SY010U120800000 1.52 0.060 16.4 0.644 296 440 3.9 98 752 341 25.2

10 12 AWG 600V/1000V SY010U121000000 1.52 0.060 19.1 0.752 368 548 4.5 115 856 388 18.0

12 12 AWG 600V/1000V SY010U121200000 1.52 0.060 19.7 0.775 426 634 4.7 118 960 436 18.0

24 12 AWG 600V/1000V SY010U122400000 2.03 0.080 28.2 1.112 851 1,267 6.7 169 1,587 720 16.2

2 10 AWG 600V/1000V SY010U100200000 1.14 0.045 11.8 0.464 131 194 2.8 71 500 227 38.0

3 10 AWG 600V/1000V SY010U100300000 1.14 0.045 12.5 0.491 173 258 2.9 75 583 264 46.0

4 10 AWG 600V/1000V SY010U100400000 1.14 0.045 13.6 0.536 221 329 3.2 82 666 302 36.8

6 10 AWG 600V/1000V SY010U100600000 1.52 0.060 17.1 0.673 334 497 4.0 103 832 377 36.8

7 10 AWG 600V/1000V SY010U100700000 1.52 0.060 17.1 0.673 371 552 4.0 103 915 415 32.2

8 10 AWG 600V/1000V SY010U100800000 1.52 0.060 18.5 0.727 416 620 4.4 111 998 453 32.2

10 10 AWG 600V/1000V SY010U101000000 2.03 0.080 22.7 0.892 549 818 5.4 136 1,164 528 23.0

12 10 AWG 600V/1000V SY010U101200000 2.03 0.080 23.3 0.919 635 945 5.5 140 1,330 603 23.0

24 10 AWG 600V/1000V SY010U102400000 2.03 0.080 32.1 1.262 1,213 1,804 7.6 192 2,326 1,055 20.7

Page 107: Shaw Flex Catalogue

Phone: 1 800-668-4842 105 email: [email protected]

Shipboard Cables

X-Flex - Armoured with SheathIEEE Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SYB10U160200009 1.14 0.045 12.8 0.503 154 229 6.0 153 375 170 15.0

3 16 AWG 600V/1000V SYB10U160300009 1.14 0.045 13.2 0.521 172 256 6.3 159 396 179 18.0

4 16 AWG 600V/1000V SYB10U160400009 1.52 0.060 14.8 0.581 207 308 7.0 177 416 189 14.4

6 16 AWG 600V/1000V SYB10U160600009 1.52 0.060 16.6 0.653 263 391 7.8 199 458 208 14.4

7 16 AWG 600V/1000V SYB10U160700009 1.52 0.060 16.6 0.653 274 407 7.8 199 478 217 12.6

8 16 AWG 600V/1000V SYB10U160800009 1.52 0.060 17.5 0.689 303 450 8.3 210 499 226 12.6

10 16 AWG 600V/1000V SYB10U161000090 1.52 0.060 20.4 0.803 386 574 9.6 245 540 245 9.0

12 16 AWG 600V/1000V SYB10U161200009 1.52 0.060 20.9 0.821 418 622 9.9 250 581 264 9.0

24 16 AWG 600V/1000V SYB10U162400009 2.03 0.080 28.6 1.127 754 1,122 13.5 344 828 376 8.1

36 16 AWG 600V/1000V SYB10U163600009 2.03 0.080 31.7 1.247 971 1,445 15.0 380 1,076 488 7.2

2 14 AWG 600V/1000V SYB10U140200009 1.14 0.045 13.5 0.533 177 263 6.4 163 400 181 24.0

3 14 AWG 600V/1000V SYB10U140300009 1.52 0.060 14.8 0.584 216 321 7.0 178 433 196 29.0

4 14 AWG 600V/1000V SYB10U140400009 1.52 0.060 15.7 0.617 248 369 7.4 188 466 211 23.2

6 14 AWG 600V/1000V SYB10U140600009 1.52 0.060 17.7 0.698 316 470 8.4 213 531 241 23.2

7 14 AWG 600V/1000V SYB10U140700009 1.52 0.060 17.7 0.698 331 493 8.4 213 564 256 20.3

8 14 AWG 600V/1000V SYB10U140800009 1.52 0.060 19.5 0.769 391 581 9.2 234 597 271 20.3

10 14 AWG 600V/1000V SYB10U141000090 2.03 0.080 22.9 0.903 499 742 10.8 275 663 301 14.5

12 14 AWG 600V/1000V SYB10U141200009 2.03 0.080 23.5 0.924 544 809 11.1 282 729 331 14.5

24 14 AWG 600V/1000V SYB10U142400009 2.03 0.080 31.1 1.225 944 1,405 14.7 374 1,124 510 13.1

36 14 AWG 600V/1000V SYB10U143600009 2.03 0.080 34.6 1.360 1,240 1,845 16.3 415 1,518 689 11.6

2 12 AWG 600V/1000V SYB10U120200009 1.52 0.060 15.3 0.601 225 334 7.2 183 438 199 29.0

3 12 AWG 600V/1000V SYB10U120300009 1.52 0.060 15.9 0.625 260 388 7.5 190 491 222 36.0

4 12 AWG 600V/1000V SYB10U120400009 1.52 0.060 16.8 0.663 301 449 8.0 202 543 246 28.8

6 12 AWG 600V/1000V SYB10U120600009 1.52 0.060 20.0 0.785 421 626 9.4 239 647 294 28.8

7 12 AWG 600V/1000V SYB10U120700009 1.52 0.060 20.0 0.785 445 662 9.4 239 699 317 25.2

8 12 AWG 600V/1000V SYB10U120800009 1.52 0.060 21.1 0.832 487 725 10.0 253 752 341 25.2

10 12 AWG 600V/1000V SYB10U121000090 2.03 0.080 24.9 0.979 622 926 11.8 299 856 388 18.0

12 12 AWG 600V/1000V SYB10U121200009 2.03 0.080 25.5 1.003 687 1,023 12.0 306 960 436 18.0

24 12 AWG 600V/1000V SYB10U122400009 2.03 0.080 34.0 1.339 1,217 1,811 16.1 408 1,587 720 16.2

2 10 AWG 600V/1000V SYB10U100200009 1.52 0.060 16.5 0.651 273 406 7.8 199 500 227 38.0

3 10 AWG 600V/1000V SYB10U100300009 1.52 0.060 17.2 0.678 322 480 8.1 207 583 264 46.0

4 10 AWG 600V/1000V SYB10U100400009 1.52 0.060 18.4 0.723 383 570 8.7 220 666 302 36.8

6 10 AWG 600V/1000V SYB10U100600009 1.52 0.060 21.9 0.860 534 794 10.3 262 832 377 36.8

7 10 AWG 600V/1000V SYB10U100700009 1.52 0.060 21.9 0.860 571 849 10.3 262 915 415 32.2

8 10 AWG 600V/1000V SYB10U100800009 2.03 0.080 24.2 0.954 663 986 11.4 291 998 453 32.2

10 10 AWG 600V/1000V SYB10U101000090 2.03 0.080 28.4 1.119 847 1,260 13.4 341 1,164 528 23.0

12 10 AWG 600V/1000V SYB10U101200009 2.03 0.080 29.1 1.146 941 1,401 13.8 349 1,330 603 23.0

Page 108: Shaw Flex Catalogue

Ship

boar

d Ca

bles

X-Flex Unarmoured IEEE Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 300V SX021U200100000 1.14 0.045 7.2 0.283 36 54 3.4 86 350 159

2 20 AWG 300V SX022U200200000 1.14 0.045 11.1 0.437 79 117 5.2 133 366 166

4 20 AWG 300V SX022U200400000 1.14 0.045 12.8 0.502 114 170 6.0 153 398 180

6 20 AWG 300V SX022U200600000 1.52 0.060 16.0 0.630 170 253 7.6 192 430 195

8 20 AWG 300V SX022U200800000 1.52 0.060 17.2 0.679 208 309 8.1 207 462 210

10 20 AWG 300V SX022U201000000 1.52 0.060 20.1 0.793 256 380 9.5 242 494 224

12 20 AWG 300V SX022U201200000 1.52 0.060 20.8 0.817 289 430 9.8 249 526 239

14 20 AWG 300V SX022U201400000 2.03 0.080 22.8 0.899 355 528 10.8 274 558 253

16 20 AWG 300V SX022U201600000 2.03 0.080 24.0 0.947 391 582 11.4 289 590 268

18 20 AWG 300V SX022U201800000 2.03 0.080 25.3 0.995 432 644 11.9 303 622 282

20 20 AWG 300V SX022U202000000 2.03 0.080 26.5 1.044 478 712 12.5 318 654 297

24 20 AWG 300V SX022U202400000 2.03 0.080 29.4 1.157 562 837 13.9 353 718 326

1 18 AWG 300V SX021U180100000 1.14 0.045 7.7 0.303 44 65 3.6 92 360 163

2 18 AWG 300V S0X22U180200000 1.14 0.045 12.0 0.473 96 144 5.7 144 386 175

4 18 AWG 300V S0X22U180400000 1.52 0.060 14.6 0.575 162 241 6.9 175 438 199

6 18 AWG 300V S0X22U180600000 1.52 0.060 17.4 0.684 216 322 8.2 208 490 222

8 18 AWG 300V S0X22U180800000 1.52 0.060 18.8 0.738 264 394 8.9 225 542 246

10 18 AWG 300V S0X22U181000000 2.03 0.080 23.0 0.905 359 534 10.9 276 594 269

12 18 AWG 300V S0X22U181200000 2.03 0.080 23.7 0.932 405 603 11.2 284 646 293

14 18 AWG 300V S0X22U181400000 2.03 0.080 24.9 0.979 458 682 11.7 298 698 317

16 18 AWG 300V S0X22U181600000 2.03 0.080 26.2 1.031 505 751 12.4 314 750 340

18 18 AWG 300V S0X22U181800000 2.03 0.080 27.6 1.086 560 834 13.0 331 802 364

20 18 AWG 300V S0X22U182000000 2.03 0.080 29.0 1.140 620 922 13.7 347 854 387

24 18 AWG 300V SX021U160100000 1.14 0.045 8.3 0.327 55 82 3.9 100 375 170

1 16 AWG 300V SX022U160200000 1.14 0.045 13.1 0.516 122 181 6.2 157 416 189

2 16 AWG 300V SX022U160400000 1.52 0.060 15.9 0.627 208 309 7.5 191 499 226

4 16 AWG 300V SX022U160600000 1.52 0.060 19.0 0.749 282 420 9.0 228 581 264

6 16 AWG 300V SX022U160800000 1.52 0.060 20.6 0.809 351 522 9.7 247 664 301

8 16 AWG 300V SX022U161000000 2.03 0.080 25.2 0.991 469 698 11.9 302 746 338

10 16 AWG 300V SX022U161200000 2.03 0.080 25.9 1.021 533 793 12.3 311 828 376

12 16 AWG 300V SX022U161400000 2.03 0.080 27.3 1.074 608 904 12.9 327 911 413

14 16 AWG 300V SX022U161600000 2.03 0.080 28.8 1.133 673 1,001 13.6 345 993 450

16 16 AWG 300V SX022U161800000 2.03 0.080 30.3 1.193 749 1,114 14.3 364 1,076 488

18 16 AWG 300V SX022U162000000 2.03 0.080 31.9 1.254 831 1,236 15.1 382 1,158 525

Page 109: Shaw Flex Catalogue

Phone: 1 800-668-4842 107 email: [email protected]

Shipboard Cables

X-Flex Armoured with Sheath IEEE Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 300V SXB21U200100009 1.14 0.045 11.2 0.440 116 173 5.3 134 350 159

2 20 AWG 300V SXB22U200200009 1.52 0.060 15.9 0.624 213 317 7.5 190 366 166

4 20 AWG 300V SXB22U200400009 1.52 0.060 17.5 0.689 267 397 8.3 210 398 180

6 20 AWG 300V SXB22U200600009 1.52 0.060 20.8 0.817 358 533 9.8 249 430 195

8 20 AWG 300V SXB22U200800009 2.03 0.080 23.0 0.906 439 653 10.9 276 462 210

10 20 AWG 300V SXB22U201000090 2.03 0.080 25.9 1.020 522 777 12.2 311 494 224

12 20 AWG 300V SXB22U201200009 2.03 0.080 26.5 1.044 563 838 12.5 318 526 239

14 20 AWG 300V SXB22U201400009 2.03 0.080 28.6 1.127 655 975 13.5 343 558 253

16 20 AWG 300V SXB22U201600009 2.03 0.080 29.8 1.174 706 1,050 14.1 358 590 268

18 20 AWG 300V SXB22U201800009 2.03 0.080 31.1 1.223 762 1,134 14.7 373 622 282

20 20 AWG 300V SXB22U202000090 2.03 0.080 32.3 1.272 823 1,225 15.3 388 654 297

24 20 AWG 300V SXB22U202400009 2.03 0.080 35.2 1.385 942 1,402 16.6 422 718 326

1 18 AWG 300V SXB21U180100009 1.14 0.045 11.7 0.460 129 192 5.5 140 360 163

2 18 AWG 300V SBX22U180200009 1.52 0.060 16.8 0.660 241 358 7.9 201 386 175

4 18 AWG 300V SBX22U180400009 1.52 0.060 19.4 0.763 335 498 9.2 232 438 199

6 18 AWG 300V SBX22U180600009 2.03 0.080 23.1 0.911 449 668 10.9 278 490 222

8 18 AWG 300V SBX22U180800009 2.03 0.080 24.5 0.965 514 765 11.6 294 542 246

10 18 AWG 300V SBX22U181000090 2.03 0.080 28.8 1.132 661 983 13.6 345 594 269

12 18 AWG 300V SBX22U181200009 2.03 0.080 29.4 1.159 715 1,064 13.9 353 646 293

14 18 AWG 300V SBX22U181400009 2.03 0.080 30.6 1.206 783 1,165 14.5 368 698 317

16 18 AWG 300V SBX22U181600009 2.03 0.080 32.0 1.259 845 1,258 15.1 384 750 340

18 18 AWG 300V SBX22U181800009 2.03 0.080 33.3 1.313 918 1,366 15.8 400 802 364

20 18 AWG 300V SBX22U182000090 2.03 0.080 34.7 1.367 994 1,480 16.4 417 854 387

1 16 AWG 300V SXB22U160200009 1.14 0.045 12.3 0.484 147 218 5.8 148 375 170

2 16 AWG 300V SXB22U160400009 1.52 0.060 17.9 0.703 278 413 8.4 214 416 189

4 16 AWG 300V SXB22U160600009 1.52 0.060 20.7 0.814 395 587 9.8 248 499 226

6 16 AWG 300V SXB22U160800009 2.03 0.080 24.8 0.976 535 797 11.7 297 581 264

8 16 AWG 300V SXB22U161000090 2.03 0.080 26.3 1.037 623 927 12.4 316 664 301

10 16 AWG 300V SXB22U161200009 2.03 0.080 30.9 1.218 798 1,187 14.6 371 746 338

12 16 AWG 300V SXB22U161400009 2.03 0.080 31.7 1.249 871 1,296 15.0 381 828 376

14 16 AWG 300V SXB22U161600009 2.03 0.080 33.1 1.301 961 1,431 15.6 397 911 413

16 16 AWG 300V SXB22U161800009 2.03 0.080 34.6 1.360 1,045 1,555 16.3 415 993 450

18 16 AWG 300V SXB22U162000009 2.03 0.080 36.1 1.421 1,140 1,696 17.1 433 1,076 488

Page 110: Shaw Flex Catalogue

Ship

boar

d Ca

bles

X-Flex - UnarmouredIEC Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SV010U160200000 1.14 0.045 8.8 0.346 58 86 2.1 53 375 170 15.0

3 16 AWG 600V/1000V SV010U160300000 1.14 0.045 9.3 0.364 72 107 2.2 55 396 179 18.0

4 16 AWG 600V/1000V SV010U160400000 1.14 0.045 10.0 0.394 85 126 2.4 60 416 189 14.4

6 16 AWG 600V/1000V SV010U160600000 1.27 0.050 12.1 0.476 124 185 2.9 73 458 208 14.4

7 16 AWG 600V/1000V SV010U160700000 1.27 0.050 12.1 0.476 135 201 2.9 73 478 217 12.6

8 16 AWG 600V/1000V SV010U160800000 1.27 0.050 13.0 0.512 155 230 3.1 78 499 226 12.6

10 16 AWG 600V/1000V SV010U161000000 1.40 0.055 15.4 0.606 196 292 3.6 92 540 245 9.0

12 16 AWG 600V/1000V SV010U161200000 1.40 0.055 15.9 0.624 224 333 3.7 95 581 264 9.0

24 16 AWG 600V/1000V SV010U162400000 1.52 0.060 21.8 0.860 424 630 5.2 131 828 376 8.1

36 16 AWG 600V/1000V SV010U163600000 1.65 0.065 25.2 0.990 608 904 5.9 151 1,076 488 7.2

2 14 AWG 600V/1000V SV010U10200000 1.14 0.045 9.6 0.376 73 109 2.3 57 400 181 24.0

3 14 AWG 600V/1000V SV010U140300000 1.14 0.045 10.1 0.396 92 137 2.4 60 433 196 29.0

4 14 AWG 600V/1000V SV010U140400000 1.14 0.045 10.9 0.430 116 172 2.6 66 466 211 23.2

6 14 AWG 600V/1000V SV010U140600000 1.27 0.050 13.2 0.521 165 246 3.1 79 531 241 23.2

7 14 AWG 600V/1000V SV010U140700000 1.27 0.050 13.2 0.521 181 269 3.1 79 564 256 20.3

8 14 AWG 600V/1000V SV010U140800000 1.27 0.050 14.3 0.561 206 307 3.4 86 597 271 20.3

10 14 AWG 600V/1000V SV010U141000000 1.40 0.055 16.9 0.666 262 390 4.0 101 663 301 14.5

12 14 AWG 600V/1000V SV010U141200000 1.40 0.055 17.4 0.686 301 448 4.1 105 729 331 14.5

24 14 AWG 600V/1000V SV010U142400000 1.65 0.065 24.6 0.968 588 875 5.8 148 1,124 510 13.1

36 14 AWG 600V/1000V SV010U143600000 1.78 0.070 28.3 1.113 848 1,263 6.7 170 1,518 689 11.6

2 12 AWG 600V/1000V SV010U120200000 1.14 0.045 10.5 0.414 97 144 2.5 63 438 199 29.0

3 12 AWG 600V/1000V SV010U120300000 1.14 0.045 11.1 0.437 126 187 2.6 67 491 222 36.0

4 12 AWG 600V/1000V SV010U120400000 1.27 0.050 12.3 0.486 160 239 2.9 74 543 246 28.8

6 12 AWG 600V/1000V SV010U120600000 1.27 0.050 14.7 0.578 232 345 3.5 88 647 294 28.8

7 12 AWG 600V/1000V SV010U120700000 1.27 0.050 14.7 0.578 256 381 3.5 88 699 317 25.2

8 12 AWG 600V/1000V SV010U120800000 1.40 0.055 16.1 0.634 290 432 3.8 97 752 341 25.2

10 12 AWG 600V/1000V SV010U121000000 1.52 0.060 19.1 0.752 368 548 4.5 115 856 388 18.0

12 12 AWG 600V/1000V SV010U121200000 1.52 0.060 19.7 0.775 426 634 4.7 118 960 436 18.0

24 12 AWG 600V/1000V SV010U122400000 1.78 0.070 27.7 1.092 832 1,238 6.6 166 1,587 720 16.2

2 10 AWG 600V/1000V SV010U100200000 1.27 0.050 12.0 0.474 135 200 2.8 72 500 227 38.0

3 10 AWG 600V/1000V SV010U100300000 1.27 0.050 12.7 0.501 177 264 3.0 76 583 264 46.0

4 10 AWG 600V/1000V SV010U100400000 1.27 0.050 13.9 0.546 226 336 3.3 83 666 302 36.8

6 10 AWG 600V/1000V SV010U100600000 1.40 0.055 16.8 0.663 328 488 4.0 101 832 377 36.8

7 10 AWG 600V/1000V SV010U100700000 1.40 0.055 16.8 0.663 365 543 4.0 101 915 415 32.2

8 10 AWG 600V/1000V SV010U100800000 1.40 0.055 18.2 0.717 410 610 4.3 109 998 453 32.2

10 10 AWG 600V/1000V SV010U101000000 1.52 0.060 21.6 0.852 519 773 5.1 130 1,164 528 23.0

12 10 AWG 600V/1000V SV010U101200000 1.65 0.065 22.6 0.889 612 911 5.3 135 1,330 603 23.0

Page 111: Shaw Flex Catalogue

Phone: 1 800-668-4842 109 email: [email protected]

Shipboard Cables

X-Flex - Armoured with Sheath IEC Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SVB10U160200009 0.89 0.035 12.3 0.483 145 216 5.8 147 375 170 15.0

3 16 AWG 600V/1000V SVB10U160300009 0.89 0.035 12.7 0.501 164 244 6.0 153 396 179 18.0

4 16 AWG 600V/1000V SVB10U160400009 0.89 0.035 13.5 0.531 183 273 6.4 162 416 189 14.4

6 16 AWG 600V/1000V SVB10U160600009 1.02 0.040 15.8 0.623 248 369 7.5 190 458 208 14.4

7 16 AWG 600V/1000V SVB10U160700009 1.02 0.040 15.8 0.623 258 385 7.5 190 478 217 12.6

8 16 AWG 600V/1000V SVB10U160800009 1.02 0.040 16.7 0.659 287 426 7.9 201 499 226 12.6

10 16 AWG 600V/1000V SVB10U161000090 1.02 0.040 19.1 0.753 351 523 9.0 230 540 245 9.0

12 16 AWG 600V/1000V SVB10U161200009 1.02 0.040 19.6 0.771 383 570 9.3 235 581 264 9.0

24 16 AWG 600V/1000V SVB10U162400009 1.27 0.050 26.1 1.027 657 978 12.3 313 828 376 8.1

36 16 AWG 600V/1000V SVB10U163600009 1.27 0.050 29.4 1.157 875 1,302 13.9 353 1,076 488 7.2

2 14 AWG 600V/1000V SVB10U10200009 0.89 0.035 13.0 0.513 168 250 6.2 156 400 181 24.0

3 14 AWG 600V/1000V SVB10U140300009 0.89 0.035 13.6 0.534 192 285 6.4 163 433 196 29.0

4 14 AWG 600V/1000V SVB10U140400009 0.89 0.035 14.4 0.567 223 332 6.8 173 466 211 23.2

6 14 AWG 600V/1000V SVB10U140600009 1.02 0.040 17.0 0.668 299 446 8.0 204 531 241 23.2

7 14 AWG 600V/1000V SVB10U140700009 1.02 0.040 17.0 0.668 315 469 8.0 204 564 256 20.3

8 14 AWG 600V/1000V SVB10U140800009 1.02 0.040 18.0 0.709 350 521 8.5 216 597 271 20.3

10 14 AWG 600V/1000V SVB10U141000090 1.14 0.045 20.9 0.823 438 652 9.9 251 663 301 14.5

12 14 AWG 600V/1000V SVB10U141200009 1.14 0.045 21.4 0.844 482 718 10.1 257 729 331 14.5

24 14 AWG 600V/1000V SVB10U142400009 1.27 0.050 28.8 1.135 850 1,264 13.6 346 1,124 510 13.1

36 14 AWG 600V/1000V SVB10U143600009 1.40 0.055 32.8 1.290 1,158 1,724 15.5 393 1,518 689 11.6

2 12 AWG 600V/1000V SVB10U120200009 0.89 0.035 14.0 0.551 200 298 6.6 168 438 199 29.0

3 12 AWG 600V/1000V SVB10U120300009 1.02 0.040 14.8 0.585 240 357 7.0 178 491 222 36.0

4 12 AWG 600V/1000V SVB10U120400009 1.02 0.040 16.1 0.633 286 426 7.6 193 543 246 28.8

6 12 AWG 600V/1000V SVB10U120600009 1.02 0.040 18.4 0.725 380 565 8.7 221 647 294 28.8

7 12 AWG 600V/1000V SVB10U120700009 1.02 0.040 18.4 0.725 404 601 8.7 221 699 317 25.2

8 12 AWG 600V/1000V SVB10U120800009 1.02 0.040 19.9 0.782 452 672 9.4 238 752 341 25.2

10 12 AWG 600V/1000V SVB10U121000090 1.14 0.045 23.1 0.909 566 842 10.9 277 856 388 18.0

12 12 AWG 600V/1000V SVB10U121200009 1.14 0.045 23.7 0.933 630 937 11.2 284 960 436 18.0

24 12 AWG 600V/1000V SVB10U122400009 1.40 0.055 32.2 1.269 1,136 1,691 15.2 387 1,587 720 16.2

2 10 AWG 600V/1000V SVB10U100200009 1.02 0.040 15.8 0.621 257 383 7.5 189 500 227 38.0

3 10 AWG 600V/1000V SVB10U100300009 1.02 0.040 16.5 0.648 307 456 7.8 198 583 264 46.0

4 10 AWG 600V/1000V SVB10U100400009 1.02 0.040 17.6 0.693 366 544 8.3 211 666 302 36.8

6 10 AWG 600V/1000V SVB10U100600009 1.14 0.045 20.8 0.820 504 749 9.8 250 832 377 36.8

7 10 AWG 600V/1000V SVB10U100700009 1.14 0.045 20.8 0.820 541 804 9.8 250 915 415 32.2

8 10 AWG 600V/1000V SVB10U100800009 1.14 0.045 22.2 0.874 599 892 10.5 266 998 453 32.2

10 10 AWG 600V/1000V SVB10U101000090 1.27 0.050 25.9 1.019 751 1,117 12.2 311 1,164 528 23.0

12 10 AWG 600V/1000V SVB10U101200009 1.27 0.050 26.8 1.056 853 1,269 12.7 322 1,330 603 23.0

Page 112: Shaw Flex Catalogue

Ship

boar

d Ca

bles

X-Flex UnamouredIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V SW021U200100000 1.02 0.040 6.4 0.253 31 46 3.0 77 350 159

2 20 AWG 150V/250V SW022U200200000 1.14 0.045 10.2 0.401 70 104 4.8 122 366 166

4 20 AWG 150V/250V SW022U200400000 1.14 0.045 11.7 0.459 103 154 5.5 140 398 180

6 20 AWG 150V/250V SW022U200600000 1.27 0.050 14.1 0.556 144 214 6.7 169 430 195

8 20 AWG 150V/250V SW022U200800000 1.27 0.050 15.2 0.599 175 261 7.2 183 462 210

10 20 AWG 150V/250V SW022U201000000 1.40 0.055 18.1 0.711 221 329 8.5 217 494 224

12 20 AWG 150V/250V SW022U201200000 1.40 0.055 18.6 0.732 250 372 8.8 223 526 239

14 20 AWG 150V/250V SW022U201400000 1.52 0.060 19.8 0.780 291 433 9.4 238 558 253

16 20 AWG 150V/250V SW022U201600000 1.52 0.060 20.9 0.822 321 477 9.9 251 590 268

18 20 AWG 150V/250V SW022U201800000 1.52 0.060 22.0 0.866 357 531 10.4 264 622 282

20 20 AWG 150V/250V SW022U202000000 1.65 0.065 23.3 0.919 403 599 11.0 280 654 297

1 18 AWG 150V/250V SW021U180100000 1.02 0.040 6.9 0.273 38 57 3.3 83 360 163

2 18 AWG 150V/250V SW022U180200000 1.14 0.045 11.1 0.437 88 131 5.2 133 386 175

4 18 AWG 150V/250V SW022U180400000 1.27 0.050 13.0 0.512 137 203 6.1 156 438 199

6 18 AWG 150V/250V SW022U180600000 1.40 0.055 15.7 0.620 192 286 7.4 189 490 222

8 18 AWG 150V/250V SW022U180800000 1.40 0.055 17.0 0.669 238 354 8.0 204 542 246

10 18 AWG 150V/250V SW022U181000000 1.52 0.060 20.1 0.793 301 447 9.5 242 594 269

12 18 AWG 150V/250V SW022U181200000 1.52 0.060 20.8 0.817 343 511 9.8 249 646 293

14 18 AWG 150V/250V SW022U181400000 1.52 0.060 21.8 0.859 388 577 10.3 262 698 317

16 18 AWG 150V/250V SW022U181600000 1.65 0.065 23.3 0.917 439 654 11.0 279 750 340

18 18 AWG 150V/250V SW022U181800000 1.65 0.065 24.5 0.965 488 727 11.6 294 802 364

20 18 AWG 150V/250V SW022U182000000 1.78 0.070 26.0 1.024 551 820 12.3 312 854 387

1 16 AWG 150V/250V SW021U160100000 1.02 0.040 8.1 0.317 53 78 3.8 97 375 170

2 16 AWG 150V/250V SW022U160200000 1.27 0.050 13.4 0.526 126 188 6.3 160 416 189

4 16 AWG 150V/250V SW022U160400000 1.40 0.055 15.7 0.617 202 301 7.4 188 499 226

6 16 AWG 150V/250V SW022U160600000 1.52 0.060 19.0 0.749 282 420 9.0 228 581 264

8 16 AWG 150V/250V SW022U160800000 1.52 0.060 20.6 0.809 351 522 9.7 247 664 301

10 16 AWG 150V/250V SW022U161000000 1.65 0.065 24.4 0.961 444 661 11.5 293 746 338

12 16 AWG 150V/250V SW022U161200000 1.65 0.065 25.2 0.991 507 754 11.9 302 828 376

14 16 AWG 150V/250V SW022U161400000 1.78 0.070 26.8 1.054 589 877 12.6 321 911 413

16 16 AWG 150V/250V SW022U161600000 1.78 0.070 28.3 1.113 653 972 13.4 339 993 450

Page 113: Shaw Flex Catalogue

Phone: 1 800-668-4842 111 email: [email protected]

Shipboard Cables

X-Flex Armoured with SheathIEC Shielded Signal Cable

Number of Pairs Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

mm in mm in lb/mft kg/km in mm lb kg

1 20 AWG 150V/250V SWB21U200100009 0.89 0.035 9.9 0.390 97 144 4.7 119 350 159

2 20 AWG 150V/250V SWB22U200200009 0.89 0.035 13.7 0.538 170 253 6.5 164 366 166

4 20 AWG 150V/250V SWB22U200400009 1.02 0.040 15.4 0.606 222 331 7.3 185 398 180

6 20 AWG 150V/250V SWB22U200600009 1.02 0.040 17.9 0.703 286 426 8.4 214 430 195

8 20 AWG 150V/250V SWB22U200800009 1.02 0.040 19.0 0.747 328 488 9.0 228 462 210

10 20 AWG 150V/250V SWB22U201000090 1.14 0.045 22.0 0.868 409 608 10.4 265 494 224

12 20 AWG 150V/250V SWB22U201200009 1.14 0.045 22.6 0.890 443 659 10.7 271 526 239

14 20 AWG 150V/250V SWB22U201400009 1.14 0.045 23.8 0.937 496 737 11.2 286 558 253

16 20 AWG 150V/250V SWB22U201600009 1.14 0.045 24.9 0.979 536 798 11.8 299 590 268

18 20 AWG 150V/250V SWB22U201800009 1.27 0.050 26.2 1.033 592 880 12.4 315 622 282

20 20 AWG 150V/250V SWB22U202000090 1.27 0.050 27.6 1.086 651 969 13.0 331 654 297

1 18 AWG 150V/250V SWB21U180100009 0.89 0.035 10.4 0.410 109 162 4.9 125 360 163

2 18 AWG 150V/250V SWB22U180200009 0.89 0.035 14.6 0.574 197 292 6.9 175 386 175

4 18 AWG 150V/250V SWB22U180400009 1.02 0.040 16.7 0.659 269 400 7.9 201 438 199

6 18 AWG 150V/250V SWB22U180600009 1.02 0.040 19.5 0.767 350 521 9.2 234 490 222

8 18 AWG 150V/250V SWB22U180800009 1.14 0.045 21.0 0.826 415 617 9.9 252 542 246

10 18 AWG 150V/250V SWB22U181000090 1.14 0.045 24.1 0.950 509 757 11.4 290 594 269

12 18 AWG 150V/250V SWB22U181200009 1.14 0.045 24.8 0.974 557 829 11.7 297 646 293

14 18 AWG 150V/250V SWB22U181400009 1.27 0.050 26.1 1.027 621 924 12.3 313 698 317

16 18 AWG 150V/250V SWB22U181600009 1.27 0.050 27.5 1.084 687 1,023 13.0 330 750 340

18 18 AWG 150V/250V SWB22U181800009 1.27 0.050 28.8 1.133 749 1,115 13.6 345 802 364

20 18 AWG 150V/250V SWB22U182000090 1.27 0.050 30.3 1.192 827 1,230 14.3 363 854 387

1 16 AWG 150V/250V SWB21U160100009 0.89 0.035 11.5 0.454 133 199 5.5 139 375 170

2 16 AWG 150V/250V SWB22U160200009 1.02 0.040 17.1 0.673 261 389 8.1 205 416 189

4 16 AWG 150V/250V SWB22U160400009 1.02 0.040 19.4 0.764 360 535 9.2 233 499 226

6 16 AWG 150V/250V SWB22U160600009 1.14 0.045 23.0 0.906 479 713 10.9 276 581 264

8 16 AWG 150V/250V SWB22U160800009 1.14 0.045 24.6 0.967 563 838 11.6 295 664 301

10 16 AWG 150V/250V SWB22U161000090 1.27 0.050 28.7 1.128 704 1,047 13.5 344 746 338

12 16 AWG 150V/250V SWB22U161200009 1.27 0.050 29.4 1.159 774 1,152 13.9 353 828 376

14 16 AWG 150V/250V SWB22U161400009 1.40 0.055 31.3 1.231 883 1,314 14.8 375 911 413

16 16 AWG 150V/250V SWB22U161600009 1.40 0.055 32.8 1.290 963 1,434 15.5 393 993 450

Page 114: Shaw Flex Catalogue

Ship

boar

d Ca

bles

P-Flex - UnarmouredIEEE Control Cable

Number of Con-ductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SY010U160200600 1.14 0.045 8.8 0.346 63 94 2.1 53 375 170 15.0

3 16 AWG 600V/1000V SY010U160300600 1.14 0.045 9.3 0.364 77 115 2.2 55 396 179 18.0

4 16 AWG 600V/1000V SY010U160400600 1.14 0.045 10.0 0.394 91 135 2.4 60 416 189 14.4

6 16 AWG 600V/1000V SY010U160600600 1.14 0.045 11.8 0.466 128 190 2.8 71 458 208 14.4

7 16 AWG 600V/1000V SY010U160700600 1.14 0.045 11.8 0.466 139 206 2.8 71 478 217 12.6

8 16 AWG 600V/1000V SY010U160800600 1.14 0.045 12.8 0.502 158 236 3.0 77 499 226 12.6

12 16 AWG 600V/1000V SY010U161200600 1.52 0.060 16.1 0.634 243 361 3.8 97 581 264 9.0

24 16 AWG 600V/1000V SY010U162400600 2.03 0.080 22.9 0.900 479 712 5.4 137 828 376 8.1

36 16 AWG 600V/1000V SY010U163600600 2.03 0.080 25.9 1.020 662 985 6.1 155 1,076 488 7.2

2 14 AWG 600V/1000V SY010U140200600 1.14 0.045 9.6 0.376 79 118 2.3 57 400 181 24.0

3 14 AWG 600V/1000V SY010U140300600 1.14 0.045 10.1 0.396 99 147 2.4 60 433 196 29.0

4 14 AWG 600V/1000V SY010U140400600 1.14 0.045 10.9 0.430 122 182 2.6 66 466 211 23.2

6 14 AWG 600V/1000V SY010U140600600 1.14 0.045 13.0 0.511 169 252 3.1 78 531 241 23.2

7 14 AWG 600V/1000V SY010U140700600 1.14 0.045 13.0 0.511 185 275 3.1 78 564 256 20.3

8 14 AWG 600V/1000V SY010U140800600 1.52 0.060 14.8 0.581 228 340 3.5 89 597 271 20.3

12 14 AWG 600V/1000V SY010U141200600 1.52 0.060 17.7 0.696 322 479 4.2 106 729 331 14.5

24 14 AWG 600V/1000V SY010U142400600 2.03 0.080 25.4 0.998 642 955 6.0 152 1,124 510 13.1

36 14 AWG 600V/1000V SY010U143600600 2.03 0.080 28.8 1.133 900 1,339 6.8 173 1,518 689 11.6

2 12 AWG 600V/1000V SY010U120200600 1.14 0.045 10.5 0.414 103 153 2.5 63 438 199 29.0

3 12 AWG 600V/1000V SY010U120300600 1.14 0.045 11.1 0.437 133 198 2.6 67 491 222 36.0

4 12 AWG 600V/1000V SY010U120400600 1.14 0.045 12.1 0.476 164 244 2.9 72 543 246 28.8

6 12 AWG 600V/1000V SY010U120600600 1.52 0.060 15.2 0.598 254 378 3.6 91 647 294 28.8

7 12 AWG 600V/1000V SY010U120700600 1.52 0.060 15.2 0.598 279 415 3.6 91 699 317 25.2

8 12 AWG 600V/1000V SY010U120800600 1.52 0.060 16.4 0.644 309 460 3.9 98 752 341 25.2

12 12 AWG 600V/1000V SY010U121200600 1.52 0.060 19.7 0.775 443 659 4.7 118 960 436 18.0

24 12 AWG 600V/1000V SY010U122400600 2.03 0.080 28.2 1.112 882 1,313 6.7 169 1,587 720 16.2

2 10 AWG 600V/1000V SY010U100200600 1.14 0.045 11.8 0.464 138 206 2.8 71 500 227 38.0

3 10 AWG 600V/1000V SY010U100300600 1.14 0.045 12.5 0.491 181 269 2.9 75 583 264 46.0

4 10 AWG 600V/1000V SY010U100400600 1.14 0.045 13.6 0.536 230 342 3.2 82 666 302 36.8

6 10 AWG 600V/1000V SY010U100600600 1.52 0.060 17.1 0.673 348 518 4.0 103 832 377 36.8

7 10 AWG 600V/1000V SY010U100700600 1.52 0.060 17.1 0.673 385 573 4.0 103 915 415 32.2

8 10 AWG 600V/1000V SY010U100800600 1.52 0.060 18.5 0.727 432 643 4.4 111 998 453 32.2

12 10 AWG 600V/1000V SY010U101200600 2.03 0.080 23.3 0.919 661 983 5.5 140 1,330 603 23.0

24 10 AWG 600V/1000V SY010U102400600 2.03 0.080 32.1 1.262 1,248 1,858 7.6 192 2,326 1,055 20.7

Page 115: Shaw Flex Catalogue

Phone: 1 800-668-4842 113 email: [email protected]

Shipboard Cables

P-Flex - Armoured with SheathIEEE Control Cable

Number of Conductors Gauge Voltage Part Number

Jacket Thickness OD Weight Min. Bend Radius Max. Pulling Tension

Ampacitymm in mm in lb/mft kg/km in mm lb kg

2 16 AWG 600V/1000V SYB10U160200609 1.14 0.045 12.8 0.503 168 250 6.0 153 375 170 15.0

3 16 AWG 600V/1000V SYB10U160300609 1.14 0.045 13.2 0.521 187 278 6.3 159 396 179 18.0

4 16 AWG 600V/1000V SYB10U160400609 1.52 0.060 14.8 0.581 226 337 7.0 177 416 189 14.4

6 16 AWG 600V/1000V SYB10U160600609 1.52 0.060 16.6 0.653 285 424 7.8 199 458 208 14.4

7 16 AWG 600V/1000V SYB10U160700609 1.52 0.060 16.6 0.653 296 440 7.8 199 478 217 12.6

8 16 AWG 600V/1000V SYB10U160800609 1.52 0.060 17.5 0.689 326 486 8.3 210 499 226 12.6

10 16 AWG 600V/1000V SYB10U161000609 1.52 0.060 20.4 0.803 417 621 9.6 245 540 245 9.0

12 16 AWG 600V/1000V SYB10U161200609 1.52 0.060 20.9 0.821 450 670 9.9 250 581 264 9.0

24 16 AWG 600V/1000V SYB10U162400609 2.03 0.080 28.6 1.127 813 1,210 13.5 344 828 376 8.1

36 16 AWG 600V/1000V SYB10U163600609 2.03 0.080 31.7 1.247 1,037 1,544 15.0 380 1,076 488 7.2

2 14 AWG 600V/1000V SYB10U140200609 1.14 0.045 13.5 0.533 192 286 6.4 163 400 181 24.0

3 14 AWG 600V/1000V SYB10U140300609 1.52 0.060 14.8 0.584 235 350 7.0 178 433 196 29.0

4 14 AWG 600V/1000V SYB10U140400609 1.52 0.060 15.7 0.617 269 400 7.4 188 466 211 23.2

6 14 AWG 600V/1000V SYB10U140600609 1.52 0.060 17.7 0.698 340 506 8.4 213 531 241 23.2

7 14 AWG 600V/1000V SYB10U140700609 1.52 0.060 17.7 0.698 355 529 8.4 213 564 256 20.3

8 14 AWG 600V/1000V SYB10U140800609 1.52 0.060 19.5 0.769 420 625 9.2 234 597 271 20.3

10 14 AWG 600V/1000V SYB10U141000609 2.03 0.080 22.9 0.903 540 803 10.8 275 663 301 14.5

12 14 AWG 600V/1000V SYB10U141200609 2.03 0.080 23.5 0.924 586 872 11.1 282 729 331 14.5

24 14 AWG 600V/1000V SYB10U142400609 2.03 0.080 31.1 1.225 1,009 1,502 14.7 374 1,124 510 13.1

36 14 AWG 600V/1000V SYB10U143600609 2.03 0.080 34.6 1.360 1,314 1,955 16.3 415 1,518 689 11.6

2 12 AWG 600V/1000V SYB10U120200609 1.52 0.060 15.3 0.601 245 364 7.2 183 438 199 29.0

3 12 AWG 600V/1000V SYB10U120300609 1.52 0.060 15.9 0.625 281 419 7.5 190 491 222 36.0

4 12 AWG 600V/1000V SYB10U120400609 1.52 0.060 16.8 0.663 324 482 8.0 202 543 246 28.8

6 12 AWG 600V/1000V SYB10U120600609 1.52 0.060 20.0 0.785 451 671 9.4 239 647 294 28.8

7 12 AWG 600V/1000V SYB10U120700609 1.52 0.060 20.0 0.785 475 708 9.4 239 699 317 25.2

8 12 AWG 600V/1000V SYB10U120800609 1.52 0.060 21.1 0.832 520 774 10.0 253 752 341 25.2

10 12 AWG 600V/1000V SYB10U121000609 2.03 0.080 24.9 0.979 667 993 11.8 299 856 388 18.0

12 12 AWG 600V/1000V SYB10U121200609 2.03 0.080 25.5 1.003 734 1,092 12.0 306 960 436 18.0

24 12 AWG 600V/1000V SYB10U122400609 2.03 0.080 34.0 1.339 1,289 1,918 16.1 408 1,587 720 16.2

2 10 AWG 600V/1000V SYB10U100200609 1.52 0.060 16.5 0.651 295 439 7.8 199 500 227 38.0

3 10 AWG 600V/1000V SYB10U100300609 1.52 0.060 17.2 0.678 346 514 8.1 207 583 264 46.0

4 10 AWG 600V/1000V SYB10U100400609 1.52 0.060 18.4 0.723 408 607 8.7 220 666 302 36.8

6 10 AWG 600V/1000V SYB10U100600609 1.52 0.060 21.9 0.860 568 845 10.3 262 832 377 36.8

7 10 AWG 600V/1000V SYB10U100700609 1.52 0.060 21.9 0.860 605 900 10.3 262 915 415 32.2

8 10 AWG 600V/1000V SYB10U100800609 2.03 0.080 24.2 0.954 707 1,052 11.4 291 998 453 32.2

10 10 AWG 600V/1000V SYB10U101000609 2.03 0.080 28.4 1.119 905 1,347 13.4 341 1,164 528 23.0

12 10 AWG 600V/1000V SYB10U101200609 2.03 0.080 29.1 1.146 1,001 1,490 13.8 349 1,330 603 23.0

Page 116: Shaw Flex Catalogue

Glo

ssar

yAbrasion Resistance

Ability of material or cable to resist surface wear

Alternating Current

An electric current that continually reverses its direction giving a definite plus & minus wave form at fixed intervals

Ambient Temperature

Any all encompassing temperature within a given area

Ampacity The maximum current an insulated conductor or cable can continuously carry without exceeding its temperature rating It is also called ampacity

Anneal To subject to heat with subsequent cooling When annealing copper; the act of softening the metal by means of heat to render it less brittle

Anti-Oxidant A substance which prevents or slows down oxygen decomposition of a material

Armour Mechanical protection usually accomplished by a metallic layer of tape, braid or served wires

Armoured CableA cable provided with a wrapping of metal, usually steel wires, flat tapes, or interlocked tapes, primarily for the purpose of mechanical protection

ASTM Abbreviation for American Society for Testing & Materials

Attenuation Loss of signal

AWG Abbreviation for American Wire Gage, a standard system used for designating wire diameter Also referred to as the Brown & Sharpe (B&S) wire gage

Binder A helically applied tape or thread used for holding assembled cable components in place until additional manufacturing operations are performed

Bonding Conductor

provides good electrical contact between the non-current carrying metal parts of an electrical systems to the system grounded conductor and/or grounding electrode conductor

Braid A fibrous or metallic group of filaments interwoven in cylindrical form to form a covering over one or more wires

Breakdown (Puncture)

A disruptive discharge through insulation due to failure under electrostatic stress

Breakdown Voltage

The voltage at which the insulation between two conductors, or a conductor & ground will break down

Building Wire Wire used for light & power in permanent installations utilizing 600 volts or less Usually in an enclosure & which will not be exposed to outdoor environments

Bunch StrandingA method of stranding where a single conductor is formed from any number of wires twisted together in the same direction, such that all strands have the same lay length, but no specific geometric arrangement

Butt JointA splice or connection formed by placing the ends of two conductors together & joining them by welding, brazing or soldering

Butt Wrap Tape wrapped in an edge- to -edge manner with no over-lapping between adjacent turns

Cable Core A cable core is the portion of an insulated cable lying under the protective covering or coverings

Cable Filler The material used in multiple conductor cables to occupy the spaces formed by the assembly of components, thus forming a core of the desired shape

Capacitance (Capacity)

That property of a system of conductors & dielectrics which permits the storage of electricity when potential difference exists between the conductors

Page 117: Shaw Flex Catalogue

Phone: 1 800-668-4842 115 email: [email protected]

Glossary

Capacitive Coupling

Electrical interaction between two conductors caused by the capacitance between them

Carbon Black A black pigment It imparts useful ultraviolet protective properties, & so is frequently suspended into plastic & elastomeric compounds intended for outside weather exposure

Charging CurrentThe current produced when a d-c voltage is first applied to conductors of an unterminated cable It is caused by the capacitive reactance of the cable, & decreases exponentially with time

Chlorinated Polyethylene (CPE)

A synthetic rubber jacketing compound

Chlorosulfonated Polyethylene (CSPE)

A synthetic rubber jacketing compound manufactured by Du Pont under trade name of Hypalon

Circuit Integrity Allows fire alarms, emergency exit lighting and critical electrical systems to operate longer during a fire situation to provide more time for people to evacuate a building safely

Circular Mil A unit of area equal to the area of a circle whose diameter is 1 mil (0001 inch) Used chiefly in specifying cross-sectional areas of round conductors

Coating A material applied to the surface of a conductor to prevent environmental deterioration, facilitate soldering or improve electrical performance

Cold Flow Any permanent deformation due to pressure or mechanical force, without the aid of eat softening

Cold Joint A soldered joint made with insufficient heat

Cold Test Any test to determine the performance of cables during or after subjection to a specified low temperature for a specified time

Cold Work The hardening & embrittlement of metal by repeated flexing action

Colour Code A Colour system for circuit identification by use of solid Colours tracers, braids surface Printing, etc

Compact Stranded Conductor

A unidirectional or conventional concentric conductor manufactured to a specified diameter, approximately 8 to 10% below the nominal diameter of a noncompact conductor of the same cross-sectional area

Concentric Stranding

A method of stranding, wherein a single conductor is formed from a central wire surrounded by one or more layers of helically layed wires Each layer is applied with an opposite direction of lay The first layer has six wires, & each additional layer has six more wires than does the previous one Thus the second layer has twelve wires, the third layer has eighteen wires, etc

Concentricity In a wire or cable, the measurement of the location of the center of the conductor with respect to the geometric center of the circular insulation

ConductivityA term used in describing the capability of a material to carry an electrical charge Usually expressed as a percentage of copper conductivity -- copper being one hundred (100%) percent Conductivity is expressed for a standard configuration of conductor

Conductor A wire or combination of wires not insulated from one another, suitable for carrying an electric current

Conductor Core The center strand or member about which one of more layers of wires or members are laid helically to form a concentric-lay or rope-lay conductor

Continuous Vulcanization

Simultaneous extrusion & vulcanization of wire coating materials It is abbreviated CV

Contrahelical A term meaning the application of two or more layers of spirally twisted, served, or wrapped materials where each successive layer is wrapped in the opposite direction to the preceding layer

Cord Small, flexible insulated cable usually size l0AWG or smaller

Page 118: Shaw Flex Catalogue

Glo

ssar

y

CoreAny portion of a cable over which some other cable component, such as a shield, jacket, sheath or armour, is applied

CoronaA luminous discharge due to ionization of the gas surrounding a conductor around which exists a voltage gradient exceeding a certain critical value

Corona ResistanceThe time that insulation will withstand a specified level field-intensified ionization that does not result in the immediate complete breakdown of the insulation Also called voltage endurance

CrazingMinute lines appearing in or near the surface of materials, such as ceramics & plastics usually resulting as a response to environment Crazing cannot be felt by running a fingernail across it If the fingernail catches, it is a crack, not crazing

CreepThe dimensional change with time of a material under load At room temperature, it is sometimes called cold flow

Cross LinkingThe establishment of chemical bonds between polymer molecule chains It may be accomplished by heat, vulcanization, irradiation or the addition of a suitable chemical agent

Cross Sectional Area

The area of the cut surface of an object cut at right angles to the length of the object

Cross Sectional Area of a Conductor

The sum of cross sectional areas of all the individual wires composing the conductor It is generally expressed in circular mils

Crush Resistance Test

A test to determine the ability of a cable to resist damage from radial compression, such as might be encountered in service

Cut-through Resistance

The ability of a given material to withstand penetration by a solid object of specified dimensions & weight, which is permitted to free fall onto this material from a specified height

Cycle One complete sequence of variations in an alternating current The number of cycles occurring in one second is called the frequency

Decibel Unit to express differences of power level It is used to express power loss in cables

Density The weight per unit volume of a substance

Derating Factor A factor used to reduce a current carrying capacity of a wire when used in other environments from that for which the value was established

Dielectric breakdown

The voltage at which a dielectric material is punctured; which is divisible by thickness to give dielectric strength

Dielectric Constant

That property (K) of an insulating material which is the ratio of the parallel capacitance (C) of a given configuration of electrodes with the material as the dielectric, to the capacitance of the same electrode configuration with a vacuum as the dielectric

Dielectric Strength

The voltage which an insulating material can withstand before breakdown occurs, usually expressed as a voltage gradient (such as volts per mil)

Dielectric Tests

1 Tests which consist of the application of a voltage higher than the rated voltage for a specified time for the purpose of determining the adequacy against breakdown of insulating materials & spacings under normal conditions 2 The testing of insulating materials by application of constantly increasing voltage until failure occurs

Direction of LayThe lateral direction, designated as left-hand or right-hand, in which the wires of a member or units of a conductor run over the top of the member or conductor as they recede from an observer looking along the axis of the member or conductor

Dissipation Unusable or lost energy, as the production of unused heat in a circuit

Drain WireAn uninsulated wire, usually placed directly beneath & in electrical contact with a grounded shield, which is used for making ground connections

Page 119: Shaw Flex Catalogue

Phone: 1 800-668-4842 117 email: [email protected]

Glossary

DurometerA measurement used to denote the hardness of a substance (usually of thermosetting & thermoplastic materials)

EccentricityA measure of the lack of coincidence of longitudinal axes of a circular cross-sectional wire & its surrounding circular cross-sectional insulation It is expressed as the percentage ratio of the distance between wire & insulation centers to the difference between wire & insulation radii

Elastic Deformation

A change in a substance whereby it reverts to its original dimensions on release of an applied stress

ElastomerA material that at room temperature returns rapidly to approximately its initial dimensions & shape after substantial deformation by a weak stress & release of the stress

Elongation The fractional increase in length of a material stressed in tension

Embossing A means of marker identification by means of thermal indentation leaving raised lettering on the sheath material of cable

Environmental Stress Cracking Resistance

The ability of a material to resist crack formation & crack propagation when subjected to stress within a contaminating environment

Equilay conductor Conductor constructed with a central core surrounded by more than one layer of helically laid wires, all layers having a common length of lay, direction of lay being reversed successive layers

Extrusion The process of continuously forcing either a plastic or elastomer & a conductor or core through a die, thereby applying an insulation or jacket to the conductor or core

Fatigue Resistance The ability of a repeatedly deformed material to resist crystallization & accompanying failure

Fault CurrentThe maximum electrical current that will flow in a short-circuited system prior to the actuation of any current-limiting device It is far in excess of normal current flow & is limited only by a system’s generating capacity & a cable’s impedance

Fibrous Filler A material used to fill interstices in cables made from fibers, such as jute, polypropylene, cotton, glass, etc

FillerAny material used in multiconductor cables to occupy interstices between insulated conductors or form a core into a desired shape (usually circular) Also, any substance, often inert, added to a plastic or elastomer to improve its properties or decrease its cost

Flame Resistance 1 The ability of material to extinguish its own flame, once its flame-initiating heat source is removed2 The ability of a wire or cable to pass a CSA, UL or industry standard flame or fire test

Flame RetardanceAbility of a material to prevent the spread of combustion by a low rate of travel so the flame will not be conveyed

Flex Life The number of bends or twists, of specified type, that a cable will withstand before failure

Flexing Test Any test to determine the ability of a cable to withstand repeated bending & twisting

GroundA conducting connection, intentional or accidental, between an electric circuit or equipment & the earth or some conducting body serving in place of the earth

Ground Potential Zero potential with respect to the ground or earth

Grounded Neutral A circuit operates with grounded neutral when the neutral is metallically connected to ground & there is a provision for immediate removal of a faulted element

Grounding Conductor

A conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode or electrodes; usually Coloured green

Hard-drawn Wire As applied to aluminum & copper, wire that has been cold drawn to final size so as to approach the maximum strength obtainable

Page 120: Shaw Flex Catalogue

Glo

ssar

yHalogen Free Plastic compounds that do not contain halogens such as chlorine, fluorine, and iodine

Heat Endurance The time of heat aging that a material can withstand before failing a specific physical or electrical test

Heat ResistanceAbility of a substance to maintain physical & chemical identity & chemical identity & electrical integrity under specified temperature conditions

Heat Shock A test to determine stability of a material by sudden exposure to a high temperature for a short period of time

Helix A spiral winding

Hertz (Abbrev H) A term rapidly replacing cycles-per-second as an indication of frequency

High Voltage Time Test

A high-voltage time test is an accelerated life test on a cable sample in which voltage is the factor increased

Hygroscopic Attracting or absorbing moisture from the ambient atmosphere

Hypalon Du Pont trademark for chlorosulfonated polyethylene (CSPE) synthetic rubber

ICEA Insulated Cable Engineers Association (Formerly lPCEA) An Association of Engineers of most cable manufacturers

Irradiation The exposure of a material to high energy emissions In insulations for the purpose of favorably altering the molecular structure Excessive exposure can be detrimental to the physical & electrical properties

Jacket A material covering over a wire insulation or an assembly of components, usually an extruded plastic or elastomer

Jumper A short length of conductor used to make a connection between terminals, around a break in a circuit, or around an instrument

Lap Splice A permanent joint formed in a short overlapping region of two parallel conductors or tapes Also called parallel splice

Lay

The distance along a cable occupied by one complete helix of a strand or conductor The direction of lay (left or right hand) is the direction of the helix looking away from an observer Also to arrange the wires or members of a conductor either by twisting them or by forming them into one or more layers helically applied

Length of Lay The axial length of one turn of the helix of a wire or member

Low Acid Gas (LAG) refers to plastic compounds that exhibit a significant reduction in the amount of corrosive and toxic acidic gases (typically chlorine) that are emitted under fire conditions

Low Smoke Zero Hal (LSZH)

compounds that are highly flame retardant, less corrosive, low toxicity and generate less smoke in a fire situation

Marker Tape A narrow strip of fabric, paper or plastic laid longitudinally within a cable; it bears printed information such as the specification to which the cable was made & the name of the cable’s manufacturer

Marker ThreadsColoured strings laid parallel & adjacent to the strands of an insulated conductor to reveal information such as the conductor’s manufacturer, the specification to which it was made, or its thermal capability

Messenger Wire A metallic supporting member either solid or stranded which may also perform the function of a conductor

Migration The loss of plasticizer from a plastic, usually due to heat or aging It is undesirable since it will make the plastic hard & brittle It is also called leaching

Mil Unit of measure equal to 1/1000 of an inch

Page 121: Shaw Flex Catalogue

Phone: 1 800-668-4842 119 email: [email protected]

Glossary

Mining CableA flame retardant cable especially constructed to withstand rough handling & exposure to moisture for underground use in the environment of a mine or tunnel, or surface use where exposed to sunlight & extremes of temperature

Moisture Absorption

The amount of water that an insulation or jacket, which is initially dry, will absorb under specified conditions It is expressed as the percentage ration of the absorbed water’s weight to the weight of the jacket or insulation alone

NEMA Standards Property values adopted as standard by the National Electrical Manufacturers Association

NominalName or identifying value of a measurable property by which a conductor or component or property of a conductor is identified, & to which tolerances are applied

Plastic Any solid material employing organic matter of a high molecular weight as a principal constituent, which can be shaped by heat & pressure during manufacturing or processing into a finished article

Plasticizer A substance incorporated into a material to increase its workability or flexibility

Plating Any thin metallic coating applied over a metallic substratum

Polyester A resin generally used as a thin film in tape form, commonly known as Mylar

Polyethylene A thermoplastic material composed of polymers of ethylene

Polymer A material formed by the chemical combination of monomers having either the same or different chemical composition

Polypropylene A thermoplastic polymer of propylene

PolyolefinA polyolefin is a polymer produced from a simple olefin (also called an alkene with the general formula CnH2n) as a monomer For example, polyethylene is the polyolefin produced by polymerizing the olefin ethylene

Polyvinyl Chloride (PVC)

A thermoplastic material composed of polymers of vinyl chloride, which may be rigid or elastomeric, depending on specific formulation

Potting Applying a hydrostatic seal & mechanical reinforcement by means of a thermosetting liquid, which cures either at room temperature or at a slightly elevated temperature

Quad A structural unit employed in cables, consisting of four separately insulated conductors twisted together

Resistance Property of a conductor that opposed the current flow produced by a given difference of potential The ohm is the practical unit of resistance

Rope-lay conductor

Conductor constructed of a bunch-stranded or a concentric-stranded member or members, as a central core, around which are laid one or more helical layers of such members

RubberA material that is capable of recovering from large deformations quickly & forcibly, & can be, or already is, modified to a state in which it is essentially insoluble (but can swell) in boiling solvent

Rupture In the breaking strength or tensile strength tests the point at which a material physically comes apart as opposed to yield strength, elongation, etc

Screen (See Shield)

Secondary Insulation

Any extremely high resistance material which is placed over primary insulation to protect it from abrasion

Semi-conductor A solid material characterized by comparatively high resistivities

Serve Any helical wrapping applied over a wire or cable core It may consist of wires, fibers, yarns or tapes

Served Wire Shield A barrier to the passage of interference formed by a helical wrapping of wires over a cable core It is also called spiral shield

Page 122: Shaw Flex Catalogue

Glo

ssar

y

Sheath The material, usually an extruded plastic or elastomer, applied outermost to a wire or cable Very often referred to as a jacket, or an impervious metal covering usually lead

Shield Any barrier to the passage of interference

Shield CoverageThe amount of cable core surface area which is covered by a shield It is expressed as a percentage of the cable core’s total surface area It is also called braid coverage when applied to a braided shield

Shielding

The practice of confining the electrical field around a conductor to the primary insulation of the cable by putting a conducting layer over and/or under the insulation (External shielding is a conducting layer on the outside of the insulation Strand or internal shielding is a conducting layer over the conductor itself)

Soft Wire Wire that has been drawn or rolled to final size & then annealed to remove the effects of cold working

Spark TestA test designed to locate pin-holes in an insulated wire by application of an electrical potential across the material for a very short period of time while the wire is drawn through an electrode field

Specific Dielectric Strength

The dielectric strength per millimeter of thickness of an insulating material

Specific Gravity The density (mass per unit volume) of any material divided by that of water at a standard temperature

Specific Inductance Capacitance

That property of a dielectric material which determines how much electrostatic energy can be stored per unit volume when unit voltage is applied

Specific Resistance The resistance of a unit conductor having a length of one foot & across-sectional area of one circular mil

Spiral Wrap A term given to describe the helical wrap of a tape or thread over a core

Splice A joint used for connecting two lengths of conductor or cable with good mechanical strength as well as good conductivity

Stabilizer Any ingredient added to plastics to preserve their physical & chemical properties

Static Electrical discharges in the atmosphere such as lightning, corona, etc

Strand One of the wires of any stranded conductor

Strand Lay The distance of advance of one strand of a spirally stranded conductor, in one turn, measured axially

Stranded Conductor

A conductor composed of a group of wires, usually twisted, or of any combination of such groups of wires

Tank Test A voltage dielectric test where the specimen to be tested is submerged in a liquid (usually water) & a voltage potential applied between the conductor & the liquid as ground

Tape WrapA term denoting a spirally or longitudinally applied tape material wrapped around the wire, either insulated or uninsulated, used as an insulation or mechanical barrier

Tear Strength The force required to initiate or continue a rip in a jacket or other insulation under specified conditions

Temperature Rating

The maximum temperature at which a given insulation or jacket may be safely maintained during continuous use, without incurring any thermally-induced deterioration

Tensile Strength The longitudinal stress required to break a specimen of prescribed dimension divided by the original cross-sectional area at the point of rupture (usually expressed in pounds per square inch)

Thermal Conductivity

Ability of material to conduct heat

Page 123: Shaw Flex Catalogue

Phone: 1 800-668-4842 121 email: [email protected]

Glossary

Thermal Endurance

The time in hours at a selected temperature for an insulating material or system of material or system of materials to deteriorate to some predetermined level of electrical, mechanical, or chemical performance under prescribed conditions of test

Thermal Rating The maximum and/or minimum temperature at which a material will perform its function without undue degradation

Thermoplastic A classification of resin that can be readily softened & reformed by heating & be rehardened by cooling

Thermoplastic Elastomer (TPE)

A thermoplastic material that looks and feels like a thermoset This material is typically used as an insulation &/or jacket for outdoor applications due to its excellent low temperature properties

Thermoset 1) To cure through chemical reaction by heat to a point of not being resoftened by subsequent heating 2) A resin which cures by chemical reaction

Tinned Wire Copper wire that has been coated during manufacture with a layer of tin or solder to prevent corrosion or facilitate soldering

Tolerance A specified allowance for error from a standard or given dimension, weight or property

TPE A trade name of Uniroyal Inc for their thermoplastic rubber

Triad Any grouping of three conductors or three assemblages of conductors, generally twisted together & found within a cable

Triplex Three single conductors twisted together, usually three single conductor cables twisted without over-all covering Do not use for three conductors laid parallel on a reel

Ultra Violet Degradation

The degradation caused by long time exposure of a material to sunlight or other ultraviolet rays containing radiation

Unidirectional conductor

Conductor constructed with a central core surrounded by more than one layer of helically laid wire, all layers having a common direction of lay, with increase in length of lay for each successive layer

Unilay conductor Conductor constructed with a central core surrounded by more than one layer of helically laid wires, all layers having a common length & direction of lay

Volt Unit of electromotive force It is the difference of potential required to make a current of one ampere flow through resistance of one ohm

Voltage Drop The voltage developed between the terminals of a circuit component by the flow of current through the resistance or impedance of that part

Voltage Rating The maximum voltage at which a given cable or insulated conductor may be safely maintained during continuous use in a normal manner It is also called working voltage

VulcanizationAn irreversible process during which a rubber compound through a change in its chemical structure (for example, cross-linking), becomes less plastic & more resistant to swelling by organic liquids & elastic properties are conferred, improved, or extended over a greater range of temperature

Water Absorption The ratio of the weight of water absorbed by a given material under specified conditions, to the weight of that material when dry It is generally expressed as a percentage

Wicking The longitudinal flow of a liquid in a wire or cable construction due to capillary action

Wire Drawing In the manufacture of wire, pulling the metal through a die or series of dies for reduction of diameter to specified size

Wire Gage Any of several standard systems for designating wire sizes As an example, see AWG

Work Hardening The increased stiffness & brittleness accompanying plastic deformation of metal

XLPE Cross-linked polyethylene

Yield StrengthThe lowest stress at which a material undergoes plastic deformation Below this stress, the material is elastic; above it, viscous

Page 124: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

CSA Tray Cable (TC) 4X0XXMXXXXXXXXX4X SERIES/ VOLTAGE RATING

43 300V PVC 4B 300V FR XLPE (M. CURE)

45 300V FR XLPE (E BEAM) 4C 600V FR XLPE (M. CURE)

46 600V PVC 4D 1000V FR XLPE (M. CURE)

48 600V FR XLPE (E BEAM) 4H 600V FR XLPE LSZH

40 1000V FR XLPE (E BEAM)

0 ARMOUR

0 UNARMOURED

X TYPE

1 MULTI-COND 4 QUADS

2 PAIRS 9 OTHER

3 TRIADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 4 19 STRAND BARE COPPER 8 CLASS K BARE COPPER

1 7 STRAND TINNED COPPER 5 19 STRAND TINNED COPPER 9 OTHER

2 SOLID BARE COPPER 6 37 STRAND BARE COPPER

3 SOLID TINNED COPPER 7 37 STRAND TINNED COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

0 90-40C FR PVC 8 FR PE LSZH

XX SPECIAL

00 STANDARD CONSTRUCTION 4 BONDING CONDUCTOR VARIATION 8 INSULATION VARIATIONS

1 COLOUR CODE CHANGE 55 STOCK 9 JACKET VARIATIONS

2 PHONE WIRE 6 COMPOSITE CONSTRUCTION Z TINNED COPPER TAPE

3 TAPE VARIATIONS 7 SPECIAL LONG LENGTH

Page 125: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 123 email: [email protected]

6XXXXMXXXXXXXXX CSA Control & Instrument Cable (CIC OR ACIC)6X SERIES/ VOLTAGE RATING

61 150V PVC 66 600V PVC 6C 600V FR XLPE (M. CURE)

62 150V XLPE 68 600V FR XLPE (E BEAM) 6D 1000V FR XLPE (M. CURE)

63 300V PVC 69 600V XLPE 6H 600V FR XLPE LSZH

64 300V XLPE 6A 150V FR XLPE (M. CURE)

65 300V FR XLPE (E BEAM) 6B 300V FR XLPE (M. CURE)

X ARMOUR

0 UNARMOURED 2 AIA

1 SIA 3 SERVED WIRE ARMOUR

X TYPE

1 MULTI-COND 3 TRIADS 9 OTHER

2 PAIRS 4 QUADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 3 SOLID TINNED COPPER 6 37 STRAND BARE COPPER 9 OTHER

1 7 STRAND TINNED COPPER 4 19 STRAND BARE COPPER 7 37 STRAND TINNED COPPER

2 SOLID BARE COPPER 5 19 STRAND TINNED COPPER 8 CLASS K BARE COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

0 90-40C FR PVC 8 FR PE LSZH

7 90-40C FR PVC LAG 9 OTHER

XX SPECIAL

00 STANDARD CONSTRUCTION 4 BONDING CONDUCTOR VARIATION 8 INSULATION VARIATIONS

1 COLOUR CODE CHANGE 55 STOCK 9 JACKET VARIATIONS

2 PHONE WIRE 6 COMPOSITE CONSTRUCTION Z TINNED COPPER TAPE

3 TAPE VARIATIONS 7 SPECIAL LONG LENGTH

Page 126: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

CSA Teck 90 Cable 8X1XXMXXXXXXXXX8X SERIES/ VOLTAGE RATING

86 600V XLPE (RW90) 80 1000V XLPE (RW90)

X ARMOUR

1 SIA 2 AIA

1 TYPE

1 MULTI-COND

0 SHIELD

0 UNSHIELDED

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 6 37 STRAND BARE COPPER

1 7 STRAND TINNED COPPER 7 37 STRAND TINNED COPPER

4 19 STRAND BARE COPPER 9 OTHER

5 19 STRAND TINNED COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

7 90-40C FR PVC LAG

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

2 PHONE WIRE 8 INSULATION VARIATIONS

4 BONDING CONDUCTOR VARIATION 9 JACKET VARIATIONS

55 STOCK

Page 127: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 125 email: [email protected]

4X1XXMXXXXXXXDR CSA VFD Tray Cable (TC)4X SERIES/ VOLTAGE RATING

48 600V FR XLPE (E BEAM) 4C 600V FR XLPE (M. CURE)

40 1000V FR XLPE (E BEAM) 4D 1000V FR XLPE (M. CURE)

0 ARMOUR

0 UNARMOURED

1 TYPE

1 MULTI-COND

X SHIELD

H SINGLE HELICAL COPPER TAPE 9 OTHER / TIN COPPER BRAID

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 4 19 STRAND BARE COPPER 6 37 STRAND BARE COPPER 8 CLASS K BARE COPPER

1 7 STRAND TINNED COPPER 5 19 STRAND TINNED COPPER 7 37 STRAND TINNED COPPER 9 OTHER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW (STANDARD) 9 OTHER

X JACKET TYPE

0 90-40C FR PVC

DR SPECIAL

DR AC DRIVE CABLE

Page 128: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

CSA Thermocouple Ext. Cable 7XX2XMXXXXXXXXX7X SERIES/ VOLTAGE RATING

71 150V PVC 75 300V FR XLPE (E BEAM) 7A 150V FR XLPE (M. CURE)

72 150V XLPE 76 600V PVC 7B 300V FR XLPE (M. CURE)

73 300V PVC 78 600V FR XLPE (E BEAM) 7C 600V FR XLPE (M. CURE)

74 300V XLPE 79 600V XLPE 7H 600V FR XLPE LSZH

X ARMOUR

0 UNARMOURED 2 AIA

1 SIA 3 SERVED WIRE ARMOUR

2 TYPE

2 PAIRS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 EX SOLID 4 KX SOLID 8 TX SOLID

1 EX 7 STRAND 5 KX 7 STRAND 9 TX 7 STRAND

2 JX SOLID 6 SX SOLID N NX SOLID

3 JX 7 STRAND 7 SX 7 STRAND

X JACKET COLOUR

0 BLACK (JX) 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE (TX) 5 ORANGE (NX) 7 YELLOW (KX) 9 OTHER (EX, SX)

X JACKET TYPE

0 90-40C FR PVC 8 FR PE LSZH

7 90-40C FR PVC LAG 9 OTHER

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

2 PHONE WIRE 8 INSULATION VARIATIONS

3 TAPE VARIATIONS 9 JACKET VARIATIONS

4 BONDING CONDUCTOR VARIATION Z TINNED COPPER TAPE

55 STOCK

Page 129: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 127 email: [email protected]

7X02XMXXXXXXXXX CSA Thermocouple Ext. Tray Cable7X SERIES/ VOLTAGE RATING

73 300V PVC 7B 300V FR XLPE (M. CURE)

75 300V FR XLPE (E BEAM) 7C 600V FR XLPE (M. CURE)

76 600V PVC 7H 600V FR XLPE LSZH

78 600V FR XLPE (E BEAM)

0 ARMOUR

0 UNARMOURED

2 TYPE

2 PAIRS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

M SEQUENTIAL METRE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 EX SOLID 4 KX SOLID 8 TX SOLID

1 EX 7 STRAND 5 KX 7 STRAND 9 TX 7 STRAND

2 JX SOLID 6 SX SOLID N NX SOLID

3 JX 7 STRAND 7 SX 7 STRAND

X JACKET COLOUR

0 BLACK (JX) 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE (TX) 5 ORANGE (NX) 7 YELLOW (KX) 9 OTHER (EX, SX)

X JACKET TYPE

0 90-40C FR PVC 9 OTHER

8 FR PE LSZH

XX SPECIAL

00 STANDARD CONSTRUCTION 7 SPECIAL LONG LENGTH

1 COLOUR CODE CHANGE 8 INSULATION VARIATIONS

2 PHONE WIRE 9 JACKET VARIATIONS

3 TAPE VARIATIONS T FOR TRAY CABLE 600V

4 BONDING CONDUCTOR VARIATION T8 FOR TRAY CABLE 300V

55 STOCK Z TINNED COPPER TAPE

6 COMPOSITE CONSTRUCTION

Page 130: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

UL VFD Tray Cable (TC) 2X01XUXXXXXXXDR2X SERIES/ VOLTAGE RATING

2C 600V FR XLPE (XHHW-2) 2R 600V FR XLPE (RHW-2)

2V 600V FR XLPE (XHHW-2) (VW-1) 2K 2000V FR XLPE (RHW-2)

0 ARMOUR

0 UNARMOURED

1 TYPE

1 MULTI-COND

X SHIELD

H SINGLE HELICAL COPPER TAPE 9 OTHER / TIN COPPER BRAID

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 6 37 STRAND BARE COPPER

1 7 STRAND TINNED COPPER 7 37 STRAND TINNED COPPER

4 19 STRAND BARE COPPER 8 CLASS K BARE COPPER

5 19 STRAND TINNED COPPER 9 OTHER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW (STANDARD) 9 OTHER

X JACKET TYPE

0 90 –40C FR PVC 6 90C HYPALON

4 90C THERMOPLASTIC CPE 7 90C FR PVC LAG

DR SPECIAL

DR AC DRIVE CABLE

Page 131: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 129 email: [email protected]

2XXXXUXXXXXXXXX UL 300V Power Limited Tray Cable (PLTC) Instrument Tray Cable (ITC)

2X SERIES/ VOLTAGE RATING

23 300V FR PVC 2W 300V FR XLPE (VW-1)

2X 300V FR XLPE 2T 300V TPE

X ARMOUR

0 UNARMOURED 4 ZETBON 6 AIA

3 SERVED WIRE ARMOUR 5 SIA

X TYPE

1 MULTI-COND 3 TRIADS 9 OTHER

2 PAIRS 4 QUADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 4 19 STRAND BARE COPPER 8 CLASS K BARE COPPER

1 7 STRAND TINNED COPPER 5 19 STRAND TINNED COPPER 9 OTHER

2 SOLID BARE COPPER 6 37 STRAND BARE COPPER

3 SOLID TINNED COPPER 7 37 STRAND TINNED COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

0 90 –40C FR PVC 4 90C CPE 7 90C FR PVC LAG

2 90C FR PVC (SPECIAL 210,00 BTU) 6 90C HYPALON T TPE (TPE Insulation only)

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

2 PHONE WIRE 8 INSULATION VARIATIONS

3 TAPE VARIATIONS 9 JACKET VARIATIONS

4 DRAIN WIRE/BOND COND.VAR. Z TINNED COPPER TAPE

55 STOCK

Page 132: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

UL Tray Cable (TC) XX0XXUXXXXXXXXXXX SERIES/ VOLTAGE RATING

29 PVC/NYLON TFN/TFFN (18 TO 16AWG) THHN/THWN (14 TO 10AWG) NC 600V FR XLPE THINNER INSULATION (NON VW-1)

2C 600V FR XLPE (NON VW-1) (XHHW-2) NV 600V FR XLPE THINNER INSULATION (VW-1)

2V 600V FR XLPE (XHHW-2) (VW-1) JC 600V FR XLPE (NON VW-1) THINNER JACKET

2R 600V FR XLPE (RWH-2) JV 600V FR XLPE (VW-1) THINNER JACKET

2K 2000V FR XLPE (RWH-2) BC 600V FR XLPE (NON VW-1) THINNER INSULATION AND JACKET

0 ARMOUR

0 UNARMOURED

1 TYPE

1 MULTI-COND 4 QUADS

2 PAIRS 9 OTHER

3 TRIADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 3 SOLID TINNED COPPER 6 37 STRAND BARE COPPER 9 OTHER

1 7 STRAND TINNED COPPER 4 19 STRAND BARE COPPER 7 37 STRAND TINNED COPPER

2 SOLID BARE COPPER 5 19 STRAND TINNED COPPER 8 CLASS K BARE COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE (I.S.) 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW (STANDARD) 9 OTHER

X JACKET TYPE

0 90-40C FR PVC 4 90C CPE 7 90C FR PVC LAG

1 90 –25C FR PVC 6 90C HYPALON

XX SPECIAL

00 STANDARD CONSTRUCTION 4 BONDING CONDUCTOR VARIATION 8 INSULATION VARIATIONS

1 COLOUR CODE CHANGE 55 STOCK 9 JACKET VARIATIONS

2 PHONE WIRE 6 COMPOSITE CONSTRUCTION Z TINNED COPPER TAPE

3 TAPE VARIATIONS 7 SPECIAL LONG LENGTH

Page 133: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 131 email: [email protected]

7XXXXUXXXXXXXXX UL 300V PLTC/ITC 600V TRAY THERMOCOUPLE EXT. CABLE

7X SERIES/ VOLTAGE RATING

7P 300V FR PVC(20 TO 16AWG) 7X 300V FR XLPE (M.CURE) (20 TO 16AWG)

7N 600V PVC/NYLON (TFN/TFFN 18 TO 16AWG) 7W 300V FR XLPE (VW-1) (20 TO 16AWG)

7V 600V FR XLPE (VW-1) (18 TO 16AWG) 7T 300V TPE

7C 600V FR XLPE (M.CURE) (18 TO 16AWG)

X ARMOUR

0 UNARMOURED 4 ZETABON 6 AIA

3 SERVED WIRE ARMOUR 5 SIA

X TYPE

2 PAIRS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 EX SOLID 4 KX SOLID 8 TX SOLID

1 EX 7 STRAND 5 KX 7 STRAND 9 TX 7 STRAND

2 JX SOLID 6 SX SOLID N NX SOLID

3 JX 7 STRAND 7 SX 7 STRAND

X JACKET COLOUR

0 BLACK (JX) 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE (TX) 5 ORANGE (NX) 7 YELLOW (KX) 9 OTHER (EX, SX)

X JACKET TYPE

0 90-40C FR PVC 4 90C CPE T TPE (TPE INSULATION ONLY)

1 90-25C FR PVC 6 90C HYPALON

2 90C FR PVC (SPECIAL 210,00 BTU) 7 90-40C FR PVC LAG

XX SPECIAL

00 STANDARD CONSTRUCTION 55 STOCK Z TINNED COPPER TAPE

1 COLOUR CODE CHANGE 6 COMPOSITE CONSTRUCTION N C OR V -600V THINNER INSUL

2 PHONE WIRE 7 SPECIAL LONG LENGTH J C or V-600V Non VW-1 or VW-1 THINNER JACKET

3 TAPE VARIATIONS 8 INSULATION VARIATIONS B C OR V -600V THINNER INSUL & JACKET

4 BONDING CONDUCTOR VARIATION 9 JACKET VARIATIONS

Page 134: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

UL Metal Clad Cable (MC) 2XXXXUXXXXXX7XX

2X SERIES/ VOLTAGE RATING

29 600V PVC/NYLON TFN/TFFN (18 TO 16AWG) THHN/THWN (14 TO 4/0AWG) 2V 600V FR XLPE (XHHW-2) (VW-1) 2K 2000V FR XLPE (RHW-2)

2C 600V FR XLPE (XHHW-2) 2R 600V FR XLPE (RHW-2)

X ARMOUR

5 SIA 7 LOOSE AIA

6 AIA 9 LOOSE SIA

X TYPE

1 MULTI-COND 3 TRIADS 9 OTHER

2 PAIRS 4 QUADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 5 19 STRAND TINNED COPPER 8 CLASS K BARE COPPER

1 7 STRAND TINNED COPPER 6 37 STRAND BARE COPPER 9 OTHER

4 19 STRAND BARE COPPER 7 37 STRAND TINNED COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

7 JACKET TYPE

7 90C FR PVC LAG

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

2 PHONE WIRE 8 INSULATION VARIATIONS

3 TAPE VARIATIONS 9 NO INNER JKT / JACKET VARIATIONS

4 BONDING CONDUCTOR VARIATION Z TINNED COPPER TAPE

55 STOCK

Page 135: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 133 email: [email protected]

AX0XXUXXXXXXXXX Flexar Cable

AX SERIES/ VOLTAGE RATING

A6 600V FR PVC AT 600V TPE

0 ARMOUR

0 UNARMOURED

X TYPE

1 MULTI-COND 4 QUADS (SPECIAL)

2 PAIRS (SPECIAL) 9 OTHER (SPECIAL)

3 TRIADS (SPECIAL)

X SHIELD

0 UNSHIELDED 2 INDIVIDUAL + OVERALL ALUM/MYLAR (SPECIAL)

1 OVERALL ALUM/MYLAR (SPECIAL) 9 OTHER / TIN COPPER BRAID

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

A FLEXAR UF (ROPE LAY) C FLEXAR SF (K-STRANDING)

B FLEXAR EF (K-STRANDING) F FLEXAR SF (M-STRANDING)

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

1 90C FR PVC (FT-1) (WITH PVC INSULATION) P 90C PUR (FT-1) (WITH TPE OR PVC INSULATION)

2 90C FR PVC (FT-4) (WITH PVC INSULATION)

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

4 BONDING CONDUCTOR VARIATION 8 INSULATION VARIATIONS

55 STOCK 9 JACKET VARIATIONS

Page 136: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Shipboard Cable (IEEE 1580 & IEC 60092-350) SXXXXUXXXXXXXXX

SX SERIES/ VOLTAGE RATING

SN 300V PVC/NYLON SX 300V FR XLPE SW 150V/250V XLPE (IEC 60092-350)

S9 600V/1000V PVC/NYLON SY 600V/1000V FR XLPE S6 600V/1000V PVC (IEC 60092-350)

ST 300V FR PVC SZ 2000V FR XLPE S3 150V/250V PVC (IEC 60092-350)

SU 600V/1000V FR PVC SV 600V/1000V XLPE (IEC 60092-350)

X ARMOUR

0 UNARMOURED B BRONZE BRAID ARMOUR

A ALUM. BRAID ARMOUR C TIN COPPER BRAID ARMOUR

X TYPE

1 MULTI-COND 3 TRIADS 9 OTHER

2 PAIRS 4 QUADS

X SHIELD

0 UNSHIELDED 2 INDIVIDUAL + OVERALL ALUM/MYLAR

1 OVERALL ALUM/MYLAR 9 OTHER / TIN COPPER BRAID

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 3 SOLID TINNED COPPER 6 37 STRAND BARE COPPER 9 OTHER

1 7 STRAND TINNED COPPER 4 19 STRAND BARE COPPER 7 37 STRAND TINNED COPPER

2 SOLID BARE COPPER 5 19 STRAND TINNED COPPER 8 CLASS K BARE COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

0 90C FR PVC 6 90C FR HYPALON (BLACK ONLY)

XX SPECIAL

00 STANDARD CONSTRUCTION 55 STOCK

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

4 BONDING CONDUCTOR VARIATION 8 INSULATION VARIATIONS

6 COMPOSITE CONSTRUCTION 9 JACKET VARIATIONS

Page 137: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 PB email: [email protected]

Part # D

erivationPa

rt #

D

eriv

ation

Phone: 1 800-668-4842 135 email: [email protected]

5XXXXUXXXXXXXXX Utility Type Cable

5X SERIES/ VOLTAGE RATING

51 150V LAG PVC 58 600V FR XLPE (NUC RW90) 5D 1000V Non VW-1 ICEA

57 150V FR XLPE (NUC RW90) 5X 300V Non VW-1 XLPE ICEA 5M 1000V VW-1 ICEA

53 300V LAG PVC 5W 300V VW-1 XLPE ICEA 5K 2000V VW-1 ICEA

55 300V FR XLPE (NUC RW90) 5C 600V Non VW-1 XLPE ICEA 5K 2000V Non VW-1 ICEA

56 600V LAG PVC 5V 600V VW-1 XLPE ICEA

X ARMOUR

0 UNARMOURED 1 SIA 2 AIA

X TYPE

1 MULTI-COND 3 TRIADS 9 OTHER

2 PAIRS 4 QUADS

X SHIELD

0 UNSHIELDED 6 INDIVIDUAL AL/MYLAR + OVERALL LONGITUDINAL CORRUGATED 5MIL COPPER TAPE

1 OVERALL ALUM/MYLAR 7 OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

2 INDIVIDUAL + OVERALL ALUM/MYLAR 8 INDIVIDUAL AL/MYLAR + OVERALL DUAL HELICAL “GAP STYLE” 5MIL COPPER TAPE 42% O/L

3 OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L 9 OTHER / TIN COPPER BRAID

4 INDIVIDUAL AL/MYLAR + OVERALL DUAL INTERCALATED 5MIL COPPER TAPE 25% O/L

H SINGLE HELICAL COPPER TAPE 5MIL 25% O/L

5 OVERALL LONGITUDIAL CORRUGATED 5MIL COPPER TAPE S SINGLE HELICAL COPPER TAPE 5MIL 25% O/L WITH INDIVIDUAL AL/MYLAR

U SEQUENTIAL FOOTAGE MARK

XX AWG SIZE

XX NUMBER OF COMPONENTS

X CONDUCTOR STRAND & TYPE

0 7 STRAND BARE COPPER 3 SOLID TINNED COPPER 6 37 STRAND BARE COPPER 9 OTHER

1 7 STRAND TINNED COPPER 4 19 STRAND BARE COPPER 7 37 STRAND TINNED COPPER

2 SOLID BARE COPPER 5 19 STRAND TINNED COPPER 8 CLASS K BARE COPPER

X JACKET COLOUR

0 BLACK 2 RED 4 LIGHT BLUE 6 BROWN 8 GREY

1 WHITE 3 BLUE 5 ORANGE 7 YELLOW 9 OTHER

X JACKET TYPE

0 90-40C FR PVC (FT4 / IEEE 1202) 3 90 – 30C FR PVC LAG 7 90C FR PVC LAG

1 90 –25C FR PVC (FT4 / IEEE 1202) 6 90C HYPALON 9 OTHER

XX SPECIAL

00 STANDARD CONSTRUCTION 6 COMPOSITE CONSTRUCTION

1 COLOUR CODE CHANGE 7 SPECIAL LONG LENGTH

2 PHONE WIRE 8 INSULATION VARIATIONS

3 TAPE VARIATIONS 9 JACKET VARIATIONS

4 BONDING CONDUCTOR VARIATION Z TINNED COPPER TAPE

55 STOCK

Page 138: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Number of Pairs or Triads

Maximum Pulling Tension

20 AWG (0.519 mm2) 18 AWG (0.823 mm2) 16 AWG (1.31 mm2) 14 AWG (2.08 mm2)

kg lb kg lb kg lb kg lb

Unshielded Pairs

1 7 15 12 26 19 42 30 66

2 15 33 24 53 38 84 60 132

4 29 64 47 104 75 165 119 262

8 59 130 94 207 150 331 239 527

12 89 196 141 311 225 496 358 789

16 118 260 186 410 299 659 477 1,052

24 178 392 282 622 450 992 716 1,579

36 267 589 423 933 674 1,486 1074 2,368

50 370 816 588 1,296 936 2,064 1491 3,287

Unshielded Triads

1 11 24 18 40 28 62 45 99

2 22 49 35 77 56 123 89 196

4 44 97 71 157 112 247 179 395

8 89 196 141 311 225 496 358 789

12 133 296 212 467 337 743 537 1,184

16 178 392 282 622 450 992 716 1,579

24 267 589 423 933 674 1,486 1074 2,368

Shielded Pairs

1 11 24 15 33 24 53 39 86

2 22 49 31 68 49 108 78 172

4 44 97 62 137 98 216 157 346

8 89 196 124 273 197 434 313 690

12 133 293 186 410 295 650 470 1,036

16 178 392 247 545 394 869 627 1,382

24 267 589 371 818 591 1,303 941 2,075

36 400 882 557 1,228 886 1,953 1411 3,111

50 555 1,224 773 1,704 1230 2,712 1960 4,321

Shielded Triads

1 15 33 21 46 34 75 54 119

2 29 64 43 95 68 150 108 238

4 59 130 85 187 136 300 216 476

8 118 260 171 377 272 600 433 955

12 178 392 256 564 408 899 649 1,431

16 237 522 342 754 543 1,197 865 1,907

24 355 783 512 1,129 815 1,797 1299 2,864

Instrumentation & Thermocouple: Maximum Pulling Tensions

Instrumentation & thermocouple cables may be pulled using the conductors. In order to support & to prevent pulling the core out of the jacket or armour it is recommended that a Kellems (basket) grip be secured over the jacket. For armoured constructions, the outer covering & armour should be stripped back to allow the grip to be secured to the inner jacket, armour & outer covering.

The maximum pulling tensions are based on a maximum pulling force of 3.63 kg/0.51mm2 (8.00 lb/1,000 circular mils) of conductor area.

Page 139: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 137 email: [email protected]

Number of Conductors

16 AWG (1.31 mm2) 14 AWG (2.08 mm2) 12 AWG (3.31 mm2) 10 AWG (5.27 mm2)

kg lb kg lb kg lb kg lb

2 28 62 45 99 62 137 99 218

3 37 82 60 132 86 190 137 301

4 47 103 75 165 110 242 174 384

5 56 124 90 197 133 294 212 467

6 65 144 104 230 157 346 250 550

7 75 165 119 263 181 398 287 633

8 84 185 134 296 204 451 325 716

10 103 227 164 362 252 555 400 882

12 121 268 194 428 299 659 475 1,048

15 150 330 239 526 370 816 588 1,297

20 196 433 313 691 488 1,077 777 1,712

25 243 536 388 855 607 1,338 965 2,127

30 290 639 463 1,020 725 1,599 1153 2,542

40 383 845 612 1,349 962 2,121 1530 3,372

50 477 1,051 761 1,678 1199 2,643 1906 4,202

60 570 1,257 910 2,007 1436 3,165 2283 5,032

8 AWG (8.35 mm2) 6 AWG (13.3 mm2) 4 AWG (21.2 mm2) 2 AWG (33.6 mm2)

2 158 348 250 552 363 800 577 1,272

3 218 480 345 761 514 1,113 818 1,803

4 278 612 440 971 665 1,467 1059 2,335

1 AWG (42.4 mm2) 1/0 AWG 2/0 AWG (67.5 mm2) 3/0 AWG (85.0 mm2)

2 703 1549 860 1897 1061 2339 1369 3019

3 1006 2218 1243 2741 1544 3404 1978 4361

4 1310 2888 1626 3584 2027 4469 2587 5703

4/0 AWG (107.2 mm2)

2 1687 3719

3 2455 5412

4 3223 7105

Power & Control: Maximum Pulling Tensions

Page 140: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

gCable Handling, Storage & Installation

The following information is supplied as a guide for ShawFlex cable handling, storage and installation. Important considerations in any cable installation are ambient temperature, equipment used, conduit or tray fill, friction forces, mechanical layout of a raceway and physical limitations of the cable. This document is not intended to be an all inclusive reference. It simply highlights some pertinent aspects of cable installation and should be viewed as a complement to good working practices.

Cable Handling

The following procedures are recommended to prevent cable damage during handling.

When using a forklift to move reels, lift from the reel flanges. Never lift reels with the forks between the flanges. Do not allow the forks to contact the cable.

When using a crane or other overhead lifting device to move reels, insert steel lifting bar in reel arbor hole and use lifting yoke or spreader bar to prevent damage to the reel flanges and possible unbalanced lifting condition.

Before moving reels, ensure that the cable end is secure on the reel. Roll reels only in the same direction as the cable was wound onto the reel.

Cable Removal and Rewinding

Cable rewinding should be done from the bottom or the top of the reel. Allow adequate space, 20 feet is recommended, between the reels to allow the cable to unwind naturally and straighten. Support reels on reel

jacks or stands using a suitable diameter bar through the reel arbor holes.

Do not pull the cable over the end of the reel flange. This can produce kinks and twists in the cable.

Cable Storage

Reels should be stored indoors on a smooth, hard, dry surface whenever possible. Each reel should be chocked from both sides. Reels should be stored in an orderly manner, aligned flange to flange. If outside storage is necessary, ideally the cable should be stored in the same manner. Additionally the cables should be protected from the weather and UV radiation. When it is not possible to store the reels on a smooth, hard, dry surface, the reels should be supported on the flanges, off the ground, so that the flanges do not become embedded in the ground which could cause damage the cable.

Page 141: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 139 email: [email protected]

Cable Pulling

If a cable is bent in a radius which is too severe and/or pulled with a tension that exceeds maximum allowable limits, the cable structure may be damaged. Experience in the field combined with data obtained in laboratory tests, have been used to determine the minimum bending radii and maximum allowable pulling tensions and sidewall bearing pressures for various cable designs.

Before commencing cable installation, it is recommended that checks be done to ensure that bends, pulling tensions and sidewall bearing pressures will not exceed specified limits. It is important to note that different cable constructions may demonstrate varying degrees of resistance to physical damage. Good raceway design and careful installation practices are essential to ensure long, reliable cable performance.

The design limits indicated herein may be modified if experience and/or knowledge of a particular installation warrant an alternate approach. It should also be noted that the sidewall bearing pressures and allowable bending radii indicated are not necessarily applicable to cable pulled around rollers or sheaves. These apparatus tend to apply more severe point force to a cable, as opposed to the more evenly distributed forces experienced

by a cable installed, for example, in conduit.

Bending Radius

The following table outlines the minimum bending radii that are generally acceptable for low voltage power, control and instrumentation cables if maximum allowable sidewall bearing pressures and pulling tensions are not exceeded.

There are two bending radii involved when installing cable:1. Pulling (during installation, while pulling with tension applied along the cable axis)2. Training (following installation, with no tension along the cable axis)

Cable Type

Minimum Bend Radius (multiples of cable OD)

Pulling Training

No Armour, No Shield 9 6

With Shield, no Armour 18 12

Interlocked Armour 18 12

Note: In all cases, the minimum bending radius specified refers to the inner surface of the cable and not to the

axis of the cable.

Pulling Tension

The maximum allowable pulling tension that can be applied to a particular cable is determined by the physical limitations of the cable, both tensile and crushing (sidewall bearing) strength, whether pulling eyes or cable grips are used, and the design of the raceway, duct system, etc. When using steel wire basket grips, the maximum recommended pulling tensions are typically limited by the tensile strength and frictional forces of the outer layers of a cable as they interact with the cable core. This method of cable pulling is typically not as reliable or robust as when pulling eyes are employed. Pulling eyes act directly on the cable core via the conductors, therefore maximum allowable pulling tension is usually determined by the total cross-sectional area of all current-carrying conductors within a given cable. It is recommended that shield drain wires in instrumentation

cables not be used for cable pulling.

Page 142: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

gCable Grip

The maximum allowable pulling tension when incorporating a cable grip may be calculated as follows:

T = k1 x t x (D – t)

Where:

T = Maximum Allowable Pulling Tension (lbs)k1 = Constant; 3,140t = Jacket Thickness (inches)

D = Cable Outside Diameter (inches)

Pulling Eye

Pulling eyes are recommended for heavy pulls and should be used in conjunction with a swivel joint. The maximum allowable pulling tension when incorporating a pulling can be calculated as follows:

T = k2 x n x A

Where:

T = Maximum Allowable Pulling Tension (lbs)k2 = Constant; 0.008 (copper conductors only)n = Number of Conductors Attached to Pulling Eye

A = Area of One Conductor (circular mils, cmil)

Friction

The coefficient of friction is a critical component of cable pulling calculations and must be selected with care. It is dependent on the cable exterior covering, raceway or duct material, and type of pulling lubricant used. Typically, values between .25 and .50 are experienced for polymeric covered cables installed in a clean, smooth, well lubricated raceway. If this value is unknown, a conservative value of f = .50 is usually sufficient for estimation purposes. Typical coefficients of friction are tabulated below for various raceway materials interacting with PVC cable jackets using water based pulling lubricants.

Raceway Material Coefficient of Friction, f (kinetic)

PVC 0.35

Polyethylene 0.25

Steel 0.50

Installed over rollers 0.15

Note: Static coefficients of friction are generally higher than kinetic coefficients of friction. It is therefore preferable to not stop a cable pull that is in progress, especially one that is approaching maximum allowable design limits for pulling tension and sidewall bearing pressure.

Use only approved lubricants that are compatible with the cable outer covering. During pulling, qualified personnel should be located at sufficiently close intervals to monitor the movement of the cable during installation. Accelerate slowly and smoothly from rest to a constant pulling speed in the range of 15 ft/min to 50 ft/min.

Page 143: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 141 email: [email protected]

Installation With Rollers

The maximum required spacing of rollers along the cable route varies with cable weight, pulling tension, cable construction, and the amount of clearance between the rollers and the tray bottom. Near the end of the pull, where the tension is approaching the maximum value, the spacing can be greater on straight sections than at the beginning of the pull, where the tension is at the minimum, as less cable sag is experienced. For relatively flexible cable constructions, the following expression can be used as an approximation in determining roller spacing.S = √(8 x H x T / W)

Where:

S = distance between rollers (ft) H = height of top of roller above tray surface (ft) T = tension (lbs)

W = weight per foot of cables (lbs/ft)

Installation Without Rollers

Cables with interlocked armour must not be installed on ladder trays without rollers. For smooth unarmoured cables (e.g. Type TC) a coefficient of friction of 0.25 is suggested. If more than one layer of cable is installed in the tray, and cable is dragged over other installed cables, a coefficient of 0.5 will yield reasonably accurate results.

Pulling Tension Calculations

The final pulling tension for a particular installation may be determined by summing the contribution of each section of a cable route. Where the run contains a bend (or several bends) a reduction in pulling tension can be achieved if the cable is fed into the raceway at the end closest to the bend(s). The calculations to be used for each of these sections are described below.

Straight Pull

T2 = T1 + W · f · L

Where:

T2 = Tension at the end of the section (lbs)T1 = Tension at the beginning of the section (lbs)f = Coefficient of friction W = Weight of the cable (lbs/ft)L = Length of the straight section (ft)

Page 144: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

gHorizontal Bend

T2 = T1 · e (f · Θ)

Where:

T2 = Tension at the end of the section (lbs)T1 = Tension at the beginning of the section (lbs)f = Coefficient of friction Θ = Angle of Bend (radians)

Note: to convert degrees to radians multiply by 0.01745

Upward Pull

T2 = T1 + W · L (sinΘ + f · cosΘ)

Where:

T2 = Tension at the end of the section (lbs)T1 = Tension at the beginning of the section (lbs)f = Coefficient of friction W = Weight of the cable (lbs/ft)L = Length of the straight section (ft)Θ = Angle of Slope (radians)

Downward Pull

T2 = T1 - W · L (sinΘ - f · cosΘ)

Where:

T2 = Tension at the end of the section (lbs)T1 = Tension at the beginning of the section (lbs)f = Coefficient of friction W = Weight of the cable (lbs/ft)L = Length of the straight section (ft)Θ = Angle of Slope (radians)

Page 145: Shaw Flex Catalogue

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 PB email: [email protected]

Cable H

andlingCabl

e

Han

dlin

g

Phone: 1 800-668-4842 143 email: [email protected]

Sidewall Bearing Pressure

Sidewall bearing pressure is the compressive force that is applied to a cable as it is pulled around a bend. A simplified version of the formula for calculating this value is shown below. It excludes the influence of the weight of the cable, itself. This assumption doesn’t usually add any appreciable error to the calculation.

SWBP = T2/R

Where:

SWBP = Sidewall Bearing Pressure (lbs/ft)T2 = Tension at the end of the section (lbs)R = Radius of the bend (ft)

A conservative upper limit for SWBP covering most multi-conductor low voltage cable constructions is 200 lbs/ft.

Cold Temperature Installations

The low temperature marking on cables should not be taken as the minimum cable installation temperature. The actual rigors of cable installation may surpass the test performance parameters associated with laboratory test conditions. CSA addresses this in the following disclaimer:

CSA C22.2 #239 APPENDIX “D”

Low Temperature Handling D1.

The term “Do Not Handle Below -40OC” found in many CSA standards is being removed because of its ambiguity and the implication that cables can be handled at -40OC without precaution. The -40OC marking indicates that the cables have passed a cold bend and/or cold impact test under carefully controlled laboratory conditions. These conditions may or may not reflect actual field conditions. It is therefore recommended that all cables be warmed to at least -10OC before installation.

Minimum pulling temperature without pre-heating of cable

ShawFlex rates some cables constructions suitable for installation at -25OC without pre-heating of the cable (please confirm! Standard cable types may be installed only down to -10OC). If it is absolutely necessary to install below this temperature, it is required that the cables be stored in a building heated to room temperature for 48 hours immediately prior to the cable pull. The cables will then be easier to install and less prone to damage.

During cold weather installation, cable should be pulled more slowly and trained in place the same day it is removed from storage. Do not impact, drop, kink or bend the cable sharply in cold temperatures. Most cable failures are due to mechanical damage during installation.

Page 146: Shaw Flex Catalogue

25 Bethridge Road Toronto, ON M9W 1M7 Canada

Website: www.shawflex.comEmail: [email protected]: (416) 743-7111Fax: (416) 743-2565