safety talk 4 / 1 safety talk 4 safe operation of storage tanks: major tank fires

17
Safety Talk 4 / 1 Safety Talk 4 Safe Operation of Storage Tanks: Major Tank Fires

Upload: savion-hastings

Post on 15-Jan-2016

246 views

Category:

Documents


0 download

TRANSCRIPT

Safety Talk 4 / 1

Safety Talk 4

Safe Operation of Storage Tanks: Major Tank FiresSafe Operation of Storage Tanks: Major Tank Fires

Safety Talk 4 / 2

Major tank fire

Safety Talk 4 / 3

Open top floating roof tank

Safety Talk 4 / 4

Sunken floating roof

Safety Talk 4 / 5

Dike / bund drain valves should be keptshut except when draining rainwater

Safety Talk 4 / 6

Open top floating roofs must bechecked after heavy rain

Safety Talk 4 / 7

Roof drain sump

Centre deck Sump cover

Check or non-return valve

SumpTo drain

Safety Talk 4 / 8

Partially blocked screen coveron roof drain

Safety Talk 4 / 9

Corrosion product / debriscollects in roof drain

Safety Talk 4 / 10

Grounding cable between weather shield anddeck. Are they maintained in good condition ?

Safety Talk 4 / 11

Damaged wheel on rolling ladder

Safety Talk 4 / 12

Anti-rotational pole –check condition and rollers

Safety Talk 4 / 13

Check vents and associated screens. Are they clear, free of debris and unrestricted ?

Safety Talk 4 / 14

Check conditionof fire fighting systems

Safety Talk 4 / 15

Test fire fightingsystems whentank taken outfor inspection

Safety Talk 4 / 16

Checklist (to be completed by technician)Cleanliness 1) Is there any debris, rags, bottles, rust scales etc on roof deck & seals ? YES / NO

2) Ponding of rain water on roof deck ? YES / NO

Leakage Sign of oil or holes on roof deck ? YES / NO

Roof Drains Clogging of roof drain screen mesh ? YES / NO

PV Vent Mesh Clogging of PV vent mesh ? YES / NO

Emergency Roof Drain Any clogging of emergency roof drain mesh ? YES / NO

Goose Neck Is there any visible defect ? YES / NO

Weather Shields / Seals 1) Is there any damage or corrosion ? YES / NO2) Excessive gaps between seal and shell YES / NO

Pontoon 1) Presence of water / oil inside pontoon compartments ? YES / NOCompartments 2) Are pontoon covers tightened down on their fastening lugs ? YES / NO

Earthing Cable Any damage on earthing cable connecting roof & Operator’s platform ? YES / NO

Guide Poles Any damage on guide poles rollers ? YES / NO

Rolling Walkway Any damage on wheels of rolling walkway ? YES / NO

Roof Drain Valves Have the roof drain valves been greased & exercised to ensure ease of movements ? YES / NO

Bottom of Shell Water ponding, corrosion, vegetation around bottom curb angle YES / NO

ANY OTHER OBSERVATIONS / REMARKS:

ACTION TAKEN (To be completed by Supervisor)

Safety Talk 4 / 17

Failed / buckled shell of tankdue to excessive internal corrosion