Current Solutions for Future Networks Chris Waller CRYOGENIC CLUSTER DAY PROGRAMME SEP 28 2011 Superconducting Fault Current Limiters

Upload: yellaturi-siva-kishore-reddy

Post on 20-Apr-2017

224 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Rutherford Appleton Cluster Day

Current Solutions for Future Networks

Chris Waller

CRYOGENIC CLUSTER DAY PROGRAMME SEP 28 2011

Superconducting Fault Current Limiters

Page 2: Rutherford Appleton Cluster Day

The John Vandore Challenge

• Squeeze my normal 110 slides which takes an hour into 15 minutes!

• So here goes.

Current Solutions for Future Networks

Page 3: Rutherford Appleton Cluster Day

The fault current challenge - 1

Current Solutions for Future Networks

G Generator

Circuit breaker

LoadCopper line

G

Short circuit:Fault Current unrestricted by load

GCircuit breaker interrupts fault current

Page 4: Rutherford Appleton Cluster Day

The fault current challenge - 2

Current Solutions for Future Networks

Image © Palm Harbor Fire Department

Page 5: Rutherford Appleton Cluster Day

The fault current challenge – 3

Current Solutions for Future Networks

G

G G

G

G G

Climbing fault current

Page 6: Rutherford Appleton Cluster Day

The fault current challenge - 4

Current Solutions for Future Networks

GG

Split the network

Upgrade Circuit Breakers

Install Reactors

Install high resistance Transformers

Page 7: Rutherford Appleton Cluster Day

The fault current challenge - 5

Current Solutions for Future Networks

G GCircuit breaker can operate safely

G GInstant rise in resistance limits fault current

GGZero resistance

Page 8: Rutherford Appleton Cluster Day

The fault current challenge - 6

Current Solutions for Future Networks

132kV

fault prone network

SensitiveLoad

Too Much Load

Plenty of capacity

132kV

33kV

11kV 11kV 11kV

33kV40MW

Wind farm

11kV 11kV

Loadsharing

Securityof supplyGenerator

Generator

Generator

Page 9: Rutherford Appleton Cluster Day

Key characteristics of Fault Current Limiters based on superconducting materials

Under normal operation a fault current limiter inserts negligible impedance into the network

When a fault occurs the limiter‘s impedance rises rapidly, reducing the current flowing through it

The fault current challenge – eureka

Page 10: Rutherford Appleton Cluster Day

Some types of Superconducting Fault Current Limiters

Resistive

Shielded core

Pre-saturatedCore

Induced current in the Superconducting tube shields the iron core until excessive current causes quench.

Superconductor quenches under excessive fault current reverting to a normal conductor, inserting resistance.

Iron core driven into saturation by superconducting DC winding. Fault current opposes the saturation and increased impedance switched into the circuit. DC

Fault Current Limitation

Page 11: Rutherford Appleton Cluster Day

Early Projects

Current Solutions for Future Networks

Project 1 & 2Resistive Type utilising Bulk

BSCCO Nexans Superconductors

Project 3 & 4Pre Saturated Core Type

utilising BSCCO Tape Zenergy Power

Page 12: Rutherford Appleton Cluster Day

Early Projects

Current Solutions for Future Networks

11kV / 100A

2010 2011 20122009

11kV/400A

11kV/1250A

33kV / 800A

11kV/ 1250A MgB2 demonstrator

operation

2013

1st in commercial network

Page 13: Rutherford Appleton Cluster Day

B (magnetic field)

J (current density)

T (Temperature)

Superconductingproperties

Normalconductingproperties

Normalconductingproperties

Normalconductingproperties

Superconductors remain in the superconducting state as long as the current, temperature and flux density remain below the critical values.

Critical CharacteristicsResistive Limiters

Page 14: Rutherford Appleton Cluster Day

Res

ista

nce

Superconducting range

Normal range

Crit

ical

Va

lue

Low

High

Equivalent circuit

Superconducting Characteristics – Resistive Fault Current Limiters

Resistive Limiters

Page 15: Rutherford Appleton Cluster Day

fault current

limited fault current

Up to 90% clampingClamps within 1.5 msRemoves DC component

Resistive FCL – Limiting Behaviour

Page 16: Rutherford Appleton Cluster Day

ETI Commissioned Project secured in June 2011 to develop a MgB2 type SFCL with a view to targeting the future mass market.

The prototype will be installed in substation on Western Power Distribution’s network in Summer 2013.

Key parameters

•Nominal operational voltage and frequency: 11kV, 50Hz•Maximum normal load current: 1250A

•Prospective fault current – 50kApk (20kArms) reduced to less than 7kApk

Resistive MgB2 SFCL Development

Page 17: Rutherford Appleton Cluster Day

HV Bushings

Helium Compressors

Heat Exchanger

Current Limiting Modules

Resistive FCL – Key Components

Page 18: Rutherford Appleton Cluster Day

• Using the quench: Even quenching, no hot spots, material homogeneity

• Wire heating: Removal of the heat (0.96MJ in 120ms)reset within 3 minute

• Low thermal losses Current leadsAC losses in superconductor/sheathInduced losses in cooling systemsEnclosed volume & thermal radiation

Resistive MgB2 SFCL - Challenges

Page 19: Rutherford Appleton Cluster Day

• Customer driven issues Fail safeNo maintenance.Low carbon footprintCompetitive with alternative optionsLow noise.

• Suppliers: Limited MgB2 wire suppliers. All interested in MRI as mass market.

Cryogenic components suppliers needed.

This is why we are here!

Resistive MgB2 SFCL - Challenges

Page 20: Rutherford Appleton Cluster Day

Current Solutions for Future Networks

Thank you !Superconducting Fault Current Limiters are a bottleneck component in the rise of Clean Technologies and Smart Grids and critical to meet Low Carbon targets