provision for plumbing services

23
PROVISION FOR PLUMBING SERVICES WATER SUPPY, DRAINAGE, SANITATION, SOLID WASTE MANAGEMENT.

Upload: govind-suthar

Post on 14-Aug-2015

187 views

Category:

Education


2 download

TRANSCRIPT

Page 1: Provision for plumbing services

PROVISION FOR PLUMBING SERVICESWATER SUPPY, DRAINAGE, SANITATION, SOLID WASTE MANAGEMENT.

Page 2: Provision for plumbing services

PURPOSE OF BYLAW This Bylaw, despite any other provision herein, shall be interpreted in accordance with this section. This Bylaw has been enacted for the purpose of regulating plumbing work within the City in the general public interest. The activities undertaken by or on behalf of the City pursuant to this Bylaw are for the sole purpose of providing a limited and interim spot checking function for reason of health, safety and the protection of persons and property. It is not contemplated nor intended, nor does the purpose of this Bylaw extend.

1. To the protection of owners, owner/builders or constructors from economic loss;

2. To providing any person a warranty of design or workmanship with respect to any plumbing work for which a permit is issued under this Bylaw;

3. To providing a warranty or assurance that construction undertaken pursuant to plumbing permits issued by the City is free form latent or any defects;

4. to providing any person a warranty that construction is in compliance with the Plumbing Code, this Bylaw or any other enactment with respect to a plumbing work for which a plumbing permit is issued

under this Bylaw.

Page 3: Provision for plumbing services

PROHIBITIONS No person shall commence or continue any plumbing work unless a Plumbing Inspector has issued a valid and subsisting plumbing permit for that work.

No person shall knowingly submit false or misleading information to a Plumbing Inspector in relation to any permit application or plumbing work undertaken pursuant to this Bylaw.

No person shall, unless authorized in writing by a Plumbing Inspector, reverse, alter, deface, cover, remove or in any way tamper with any notice, plumbing permit or certificate posted upon or affixed to a building or structure pursuant to this Bylaw.

No person shall do any work that is substantially at variance with the accepted plans and specification for which a plumbing permit has been issued.

Page 4: Provision for plumbing services

PROHIBITIONS No person shall obstruct the entry on property of a Plumbing Inspector or other authorized official of the City in the administration of this Bylaw.

No person shall erase, alter or modify plans, specifications or other supporting documents that have been:

(a) reviewed by the Plumbing Inspector; or

(b) filed for reference with the Plumbing Inspector after a plumbing permit has been issued on the basis of the plans or supporting documents.

No person shall cover or conceal any plumbing work without the approval of the Plumbing Inspector.

Page 5: Provision for plumbing services

PERMIT CONDITIONS A plumbing permit is required before any work regulated under this Bylaw is to be undertaken.

Neither the issuance of a plumbing permit under this Bylaw nor the acceptance or review of plans, drawings or specifications or supporting documents, nor any inspections made by or on behalf of the City shall in any way relieve the owner or his or her representatives from full and sole responsibility to perform the work in strict accordance with the Plumbing Code, the requirements of this Bylaw or other applicable enactments respecting safety.

An owner of property for which a plumbing permit is issued shall conform to all requirements of this bylaw and all other enactments and City bylaws applicable to the plumbing work for which the permit was issued.

Page 6: Provision for plumbing services

PLUMBING SERVICES The planning, design, construction and installation of water supply, drainage

and sanitation and gas supply system shall be in accordance with Part-IX Plumbing Services, section-l water supply; section-2 drainage and sanitation and section-3 gas supply of National Building Code of India.

Requirement of water supply for various occupancies in buildings shall be as given in upcoming slides

Page 7: Provision for plumbing services

WATER SUPPLYSI.NO Type of Occupancy Consumption per head per day (in lt.)

1 Residentiala) In living unitsb) Hotels with lodging accommodation (per bed)

135180

2 Educational a) Day schools b) Boarding Schools

 45135

3 Institutional (Medical Hospitals) a) No. of beds not exceeding 100b) No. of beds exceeding 100c) Medical quarters and hostels

340450135

4 Assembly- Cinema theatres, auditoria, etc. (per seat accommodation)

15

Page 8: Provision for plumbing services

WATER SUPPLYSI.NO Type of Occupancy Consumption per head per day (in lt.)

5 Government or semi public business 45

6 Mercantile (Commercial) a) Restaurants (per seat) b) Other business building

 7045

7 Industrial a) Factories where bath-rooms are to be

provided b) Factories where bath-rooms are not

to be provided

 4530

8 Storage ( including Warehouses ) 30

9 Hazardous 30

Page 9: Provision for plumbing services

WATER SUPPLYSI.NO Type of Occupancy Consumption per head per day (in lt.)

10 Intermediate Stations (excluding mail and express stops).

45

11 Junction Station 70

12 Terminal Stations 45

13 International and Domestic Airports 70

Note: The number of persons for Sl. No. 10 to 13 shall be determined by the average number of passenger handled by the station daily with due consideration given to the staff and workers likely to use the facilities.

Page 10: Provision for plumbing services

FIXTURE UNIT FOR DIFFERENT TYPES OF FIXTURES BASED ONPIPE OR TRAP DIAMETERS.NO TRAP OUTLET DIAMETER (MM) FIXTURE UNIT

1 32 1

2 40 2

3 50 3

4 65 4

5 75 5

6 100 6

Page 11: Provision for plumbing services

MINIMUM INTERNAL DIAMETER FOR SANITARY APPLIANCES

S.NO APPLIANCE DIAMETER OF WATER OUTLET(MM)

1 WATER CLOSET 100

2 LIPPED URINALS 40

3 STALL URINALS 50

4 URINALS WITH INTERNAL TRAPS 75

5 SINK CLEANERS 50

SOIL APPLIANCES

Page 12: Provision for plumbing services

MINIMUM INTERNAL DIAMETERFOR SANITARY APPLIANCESWASTE APPLIANCES

S.NO APPLIANCE DIAMETER OF WATER OUTLET(MM)

1 WATER CLOSETS 100

2 URINALS 32

3 WASH BASINS 32

4 DRINKING WATER FOUNTAIN 25

5 BATHTUB 50

6 FLOOR TRAPS 65

7 SINK 40

Page 13: Provision for plumbing services

REQUIRED APPLIANCES FORDIFFERENT TYPES OF BUILDING

OFFICE BUILDINGS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 25 1 PER 15

2 URINALS 1 FOR ( 1 TO 20 ) 1 FOR ( 1 TO 20 )

3 WASH BASIN 1 PER 25 1 PER 25

4 DRINKING WATER FOUNTAIN

1 PER 100 1 PER 100

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH CLOSET

Page 14: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGFACTORIESS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 25 1 PER 15

2 URINALS 1 FOR ( 1 TO 20 ) 1 FOR ( 1 TO 20 )

3 WASH BASIN 1 PER 25 1 PER 25

4 DRINKING WATER FOUNTAIN

1 PER 100 1 PER 100

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH CLOSET

Page 15: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGCONCERT HALL, CINEMA AND THEATERSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 100 3 PER 100

2 URINALS 1 FOR ( 1 TO 25 ) 1 FOR ( 1 TO 25 )

3 WASH BASIN 1 PER 25 1 PER 25

4 DRINKING WATER FOUNTAIN

1 PER 100 1 PER 100

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH CLOSET

Page 16: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGART GALLERIES, MUESUMS AND LIBRARIESS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 200 1 PER 100

2 URINALS 1 FOR ( 1 TO 50 ) 1 FOR ( 1 TO 50 )

3 WASH BASIN 1 PER 200 1 PER 200

4 DRINKING WATER FOUNTAIN

1 PER 100 1 PER 100

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH CLOSET

Page 17: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGHOSPITALS WITH INDOOR PATIENT WARDS S.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 8 1 PER 8

2 URINALS 1 PER 30 1 PER 30

3 WASH BASIN 2 PER 30 2 PER 30

4 DRINKING WATER FOUNTAIN

1 PER WARD 1 PER WARD

5 CLEANER’S SINK 1 PER WARD

6 ABLUTION TRAP 1 WITH EACH WC

Page 18: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGHOSPITALS WITH OUTDOOR PATIENT WARDS S.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 100 2 PER 100

2 URINALS 1 PER 50 1 PER 50

3 WASH BASIN 2 PER 100 2 PER 100

4 DRINKING WATER FOUNTAIN

1 PER 500 1 PER 500

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH CLOSET

Page 19: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGHOTELSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 100 2 PER 100

2 URINALS 1 PER 50 1 PER 50

3 WASH BASIN 1 PER WC/URINAL 1 PER WC

4 DRINKING WATER FOUNTAIN

XX XX

5 CLEANER’S SINK 1 PER 10

6 ABLUTION TRAP 1 WITH EACH WC

Page 20: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGRESTAURANTSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 50 2 PER 50

2 URINALS 1 PER 50 1 PER 50

3 WASH BASIN 1 PER WC 1 PER WC

4 DRINKING WATER FOUNTAIN

XX XX

5 CLEANER’S SINK 1 PER EACH RESTAURANT

6 ABLUTION TRAP 1 WITH EACH WC

Page 21: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGEDUCATION INSTITUTIONSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 40 1 PER 25

2 URINALS 1 PER 20 1 PER 20

3 WASH BASIN 1 PER 60 1 PER 60

4 DRINKING WATER FOUNTAIN

1 PER 50 1 PER 50

5 CLEANER’S SINK 1 PER FLOOR

6 ABLUTION TRAP 1 WITH EACH WC

Page 22: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGFRUIT AND VEGETABLE MARKETSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 1 PER 15 1 PER 12

2 URINALS 1 PER ( 7 TO 20 ) 1 PER ( 7 TO 20 )

3 WASH BASIN 1 PER 15 1 PER 12

4 DRINKING WATER FOUNTAIN

1 PER 100 1 PER 100

5 BATH ( SHOP OWNER ) 1 PER 8 1 PER 6

6 ABLUTION TRAP 1 WITH EACH WC

Page 23: Provision for plumbing services

REQUIRED APPLIANCES FOR DIFFERENT TYPES OF BUILDINGRAILWAY STATIONS AND AIRPORTSS.NO APPLIANCE MALE ( FIXTURE UNIT ) FEMALE ( FIXTURE UNIT )

1 WATER CLOSETS 3 FOR 1000 4 FOR 1000

2 URINALS 4 FOR 1000 4 FOR 1000

3 WASH BASIN 1 PER WC/URINAL 1 PER WC

4 DRINKING WATER FOUNTAIN

2 FOR 1000 1 PER 50

5 CLEANER’S SINK 1 PER TOILET

6 BATH 2 FOR 1000 2 FOR 1000