pnp npn converter

3
NpN and PnP Sensor Outputs Finally Explained. Most engineers will have suffered at the hands of NpN/PnP at one point in their career. If the incorrect type is wired into your machine, the downstream device (relay, PLC etc) will not function correctly. Once the differences between PnP and NpN are fully understood you can identify the type of sensor currently installed and find a suitable replacement. It is also surprisingly easy to convert an output to the desired type. This could half the amount of spare sensors you have to keep and save valuable production time spent waiting for the correct output type. It is important to realise that NpN and PnP are completely different to normally open and normally closed. You can have an NpN n/o or an NpN n/c, and a PnP n/o or PnP n/c sensor. NPN (sinking) This is a switched Negative output. A permanent +vdc supply will be connected to the device that is to be activated (relay coil, PLC common terminal etc) When the sensor turns on, it switches the 0vdc used to power the sensor, through the transistor in the sensor body (fig 1). This 0vdc is now present on the sensor output wire (normally the black wire) and will be wired to the device that is to be turned on (eg –ve input on relay coil). If +vdc is connected to the other side of the relay coil, then a circuit is completed and the relay or PLC input will turn on. It is effectively just a switch that connects the 0vdc side of a supply to another device. Fig 1. More Control Ltd Tel: 0345 00 00 400 Email: [email protected] Web: www.more-control.com

Upload: tani-ricafrente

Post on 15-Nov-2015

75 views

Category:

Documents


1 download

DESCRIPTION

PLC Sensors

TRANSCRIPT

  • NpN and PnP Sensor Outputs Finally Explained.

    Most engineers will have suffered at the hands of NpN/PnP at one point in their career. If the incorrect type is wired into your machine, the downstream device (relay, PLC etc) will not function correctly.Once the differences between PnP and NpN are fully understood you can identify the type of sensor currently installed and find a suitable replacement.It is also surprisingly easy to convert an output to the desired type. This could half the amount of spare sensors you have to keep and save valuable production time spent waiting for the correct output type.

    It is important to realise that NpN and PnP are completely different to normally open and normally closed. You can have an NpN n/o or an NpN n/c, and a PnP n/o or PnP n/c sensor.

    NPN (sinking)

    This is a switched Negative output. A permanent +vdc supply will be connected to the device that is to be activated (relay coil, PLC common terminal etc)

    When the sensor turns on, it switches the 0vdc used to power the sensor, through the transistor in the sensor body (fig 1). This 0vdc is now present on the sensor output wire (normally the black wire) and will be wired to the device that is to be turned on (eg ve input on relay coil).If +vdc is connected to the other side of the relay coil, then a circuit is completed and the relay or PLC input will turn on. It is effectively just a switch that connects the 0vdc side of a supply to another device.Fig 1.

    More Control Ltd

    Tel: 0345 00 00 400

    Email: [email protected]

    Web: www.more-control.com

  • PNP (sourcing)

    This is a switched Positive output. A permanent -vdc supply will be connected to the device that is to be activated (relay coil, PLC common terminal etc)

    When the sensor turns on, it switches the +vdc used to power the sensor, through the transistor in the sensor body (fig 2). This +vdc is now present on the sensor output wire (normally the black wire) and will be wired to the device that is to be turned on (eg +ve input on relay coil).If -vdc is connected to the other side of the relay coil, then a circuit is completed and the relay or PLC input will turn on. It is effectively just a switch that connects the +vdc side of a supply to another device.Fig 2.

    If you do have the incorrect sensor type More Control has the solution in the form of two types 5mm din rail mount converters in a standard terminal style body. They are compact and cost effective devices that will easily convert from NpN to Pnp or PnP to Npn. (please see attached specification sheet).

    With one of each device kept in your stores you will never again be left waiting for a particular sensor type but can use any sensor you have available at the time.

    To order the converters please fill in the attached order form or contact our office on 0345 00 00 400 or email to: [email protected]

  • SnapLine Inverter2-wire version of NPN/PNP or PNP/NPN conversion

    More Control Ltd

    Tel: 0345 00 00 400

    Email: [email protected]

    Web: www.more-control.com

    MC2002-0020MC2002-0021

    5-60 V DC

    1 V5 KHz

    100 mA

    12K Ohms>2.5 V

    10 A

    -40 C up to + 70 C2.5mm (AWG 24-14)

    0.4 NM5.08 x 86.5 x 44 mm

    More Control Part Number:

    MC2002-0020: NPN/PNPMC2002-0021: PNP/NPN