1.- REMOVE EXISTING RECESSED MOUNTED STEAM CONVECTOR ANDASSOCIATED PIPING. PATCH FLOORS TO MATCH EXISTING THROUGHOUT.
2.- REMOVE EXISTING AIR HANDLING UNIT AND ASSOCIATED CONTROLS.
3.- REMOVE ALL EXISTING DUCTWORK ASSOCIATED WITH AIR HANDLER TO RISER.
4.- REMOVE EXISTING LOUVER AND DAMPER. OUTSIDE AIR DUCT SIZE 12"X12".
5.- REMOVE EXISTING STEAM AND CONDENSATE PIPING BACK TO MAIN. PIPINGTO BE REPLACED FROM MAIN DISTRIBUTION LINE.
6.- EXISTING LOW AND MEDIUM PRESSURE PRESSURE REDUCING (PRV) STATIONSHALL BE REMOVED AND REPLACED WITH NEW. MEDIUM PRESSURE PRVSTATION IS NOT PRESENT, ALTHOUGH THE ASSOCIATED PIPING FOR THISSYSTEM SHALL BE REMOVED BACK TO THE MAIN LINE AND CAPPED ANDSEALED. THE EXISTING LOW PRESSURE PRV'S SHALL BE DISCONNECTED BACKTO A POINT AT WHICH THE NEW PRV STATION CAN BE INSTALLED ANDREPIPED TO THE EXISTING LOW PRESSURE SYSTEMS.
7.- REMOVE VISIBLE SURFACE CONTAMINANTS AND DEPOSITS FROM WITHIN THEHVAC SYSTEM. SYSTEM AND COMPONENTS TO BE CLEANED: AIR DEVICES -SUPPLY AND RETURN, SUPPLY AIR DUCTWORK, RETURN AIR DUCTWORK.DUCTWORK FROM MECHANICAL ROOM LEVEL UP TO THE CONNECTINGCORRIDOR BETWEEN BUILDING 409 AND 305. ASSUME APPROXIMATELY 150FEET OF SUPPLY AIR DUCTWORK AND 45 FEET OF RETURN AIR DUCTWORK.DUCTWORK IS TO BE CLEANED IN ACCORDANCE WITH THE NATIONAL AIR
DUCT CLEANERS ASSOCIATION DOCUMENT (NADCA) ACR 2006. UTILIZEMECHANICAL CLEANING METHODOLOGY WHICH INCLUDES CONTINUOUSNEGATIVE PRESSURE HEPA FILTRATION COLLECTION EQUIPMENT ON THEDUCTWORK TO COLLECT DEBRIS, AND MECHANICAL AGITATION DEVICES TODISLODGE DEBRIS THAT IS ADHERED TO THE INTERIOR SURFACES OF THE HVACSYSTEM COMPONENTS. ENSURE CLEANING METHODS SHALL NOT DAMAGETHE INTEGRITY OF HVAC SYSTEM COMPONENTS. ALL SYSTEM COMPONENTSSHALL BE VISIBLY CLEAN.
PLAN NOTES
1
2
3
4
5
22"X10"
18"X10"
6
7
HVAC DEMOLITION PLAN BASEMENTSCALE: 1/8"=1'-0"
NORTH M100
BASEMENTHVAC
DEMOLITION PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
T
S
1 1 1 1
1
2
3
4
4
4
4
3
3 4
5 5
6
6 7
8
8
8
8
8
88
1
1
1
1
(CONV)E
1
EXISTING SPACE TO REMAIN
131
.
C-1-2
CORRIDOR
127
.
126
.
101
TECHNICIANOFFICE
148
TECHNICIANOFFICE
118
H.A.C.
150
149
103
.
103A
.
104
.
104A
.
105
.
106
.
107
.
109
.
110
SOLARIUM
110A
.
111
.
112
.113
.
115A
SHOWER &BATH
115
WASH ROOM116
TOILET
117
.
118
.
C-1-3
CORRIDOR
C-1-4
CORRIDOR
130
H.A.C.
138
.
139
.
140
.
141
.
142
.
142A
.
117A
.
114
H.A.C.
109A
.
C-1-3
CORRIDOR
C-1-3
CORRIDOR
122
DINING ROOM
122B
H.A.C.
122C
STOR.
123
.
122A
.
120
.
121
.
119
.
SW3
STAIR
9
9
133
.
132
.
131
.
C-1
CORR
137
.
134
SOLARIUM
135A
.
137
.
1381.- REMOVE EXISTING WALL MOUNTED STEAM CONVECTOR AND ASSOCIATED
PIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROM EACHCONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TO MATCHEXISTING THROUGHOUT.
2.- REMOVE EXISTING ELECTRIC BASEBOARD HEATER AND ASSOCIATEDCONTROLS. ELECTRIC SERVING HEATER TO BE REMOVED, SEE ELECTRICALDRAWINGS FOR FURTHER INFORMATION.
3.- REMOVE EXISTING DUCTWORK.
4.- REMOVE EXISTING GRILLES AND DIFFUSERS.
5.- REMOVE ENTIRE BRANCH DUCT FROM FIRST TO THIRD FLOOR.
6.- REMOVE EXISTING EXHAUST FAN AND ASSOCIATED CONTROLS.
7.- PATCH WALL TO MATCH EXISTING.
8.- REMOVE EXISTING RECESSED MOUNTED STEAM CONVECTOR ANDASSOCIATED PIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROMEACH CONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TOMATCH EXISTING THROUGHOUT.
9.- REMOVE ENTIRE BRANCH DUCT AND ASSOCIATED GRILLES ON THIS LEVEL.BRANCH DUCT TO BE REMOVED FROM FIRST FLOOR TO THIRD FLOOR.
PLAN NOTES
HVAC DEMOLITION PLAN LEVEL 1SCALE: 1/8"=1'-0"
NORTH M101
LEVEL 1HVAC
DEMOLITION PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.-REMOVE ENTIRE BRANCH DUCT FROM FIRST TO THIRD FLOOR.
2.- EXISTING SUPPLY AND RETURN STEAM RISERS SERVING FLOOR ABOVE. RISERS
AND ASSOCIATED PIPING THAT SERVES THE THIRD FLOOR SHALL BE REMOVED
ENTIRELY. RISERS SHALL BE REMOVED BACK DOWN TO THE FLOOR BELOW IF
NO ADDITIONAL STEAM CONNECTIONS SERVING THIS FLOOR EXISTS ABOVE
THE SECOND FLOOR LEVEL.
PLAN NOTES
C-2-1
CORRIDOR
C-2-4
CORRIDOR
C-2-3
CORRIDOR
229
.
220
.
221
.
222
DAYROOM
223
KITCHENNOURISHMENT
225
.
219
TOILET
218
SHOWER &BATH
231
.
247A
.
246
.
245
.
244
.
232
.
248
.
247
.
237
.
233A
.
233
.
235a
SHOWER ANDBATH
235
WASH ROOM
234
TOILET
236
H.A.C.
202B
.
201
.
201A
.
202
.
202A
.
203
.
204
.
205
.
206
.
SW2
STAIR
209
SOLARIUM
211
.
212
.
214A
SHOWER &BATH
214
WASH ROOM215
TOILET
216
.
216A
.
217
.
208A
.
213
.
226
.
228
.
218A
.
SW3
STAIR
SW4
STAIR
1 1
1
1
2 2
22 2 2 2
2
2
2
2
222221
2
2
244
.
243
.
SW1
STAIR
241
.
240
SOLARIUM
248AA
.
248AA
.
23238
.
239
.
HVAC DEMOLITION PLAN LEVEL 2SCALE: 1/8"=1'-0"
NORTH M102
LEVEL 2HVAC
DEMOLITION PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.- REMOVE EXISTING WALL MOUNTED STEAM CONVECTOR AND ASSOCIATEDPIPING. PIPING TO BE REMOVED BACK TO THE MAINS FROM EACHCONVECTOR UNIT. CAP AND SEAL LINES AT MAIN. PATCH FLOORS TO MATCHEXISTING THROUGHOUT.
2.- REMOVE EXISTING EXHAUST SYSTEM (INCLUDING DUCTWORK, FANS, GRILLES,
CONTROLS) ASSOCIATED WITH THIS ROOM.
3.- REMOVE EXISTING EXHAUST FAN AND PATCH WALL TO MATCH EXISTING.
4.- REMOVE EXISTING EXHAUST FAN AND REPAIR WINDOW TO MATCH EXISTING.
PLAN NOTES
(EF)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E (CONV)E (CONV)E (CONV)E (CONV)E (CONV)E (CONV)E
(CONV)E (CONV)E
(CONV)E
(CONV)E
(CONV)E(CONV)E(CONV)E
(CONV)E(CONV)E(CONV)E(CONV)E(CONV)E(CONV)E(CONV)E(CONV)E
(EF)E (EF)E(EF)E
(EF)E
(EF)E
(EF)E
(CONV)E
(CONV)E
(CONV)E
(CONV)E
1
2
1
1 1 1 1 1 1 1 1
1 1
1
1
1
1
11 11 1 1 1 1
1 1 1
1
2
2
1
1
1
1
1
2
2
3
3
332
.
331
STOR.
C-3-1
CORRIDOR
332A
.
333
.
334
TOILET
335
WASH ROOM
335A
SHOWER &BATH
336
H.A.C.
337
.
344
.
345
.
346
.
347
.
347A
.
347AA
.
302
.
302A
.
303
.
304
.
305
.
306
.
308
.
309
.
309A
.
309B
.
310
.
311
.
311A
.
SW2
STAIR302B
.
308A
.
312
.
317
.
316
B.P.S.
314A
SHOWER &BATH
313
H.A.C.
314
WASH ROOM315
TOILET
317A
.
320
.
321
.
325
.
326
.
327
.
328
.
322
DAYROOM
324
.
323
.
SW4
STAIR
317
.
C-3-2
CORRIDOR
C-3-3
CORRIDOR
C-3-4
CORRIDOR
301E
.
301D
.
301
.
301A
STORAGE
301E
.
301B
.
318
BATH
319
TOILET
4 4
337
.
338
.
338A
.
340
.
340A
.
340B
.
SW1
STAIR
343
.
341A
.
HVAC DEMOLITION PLAN LEVEL 3SCALE: 1/8"=1'-0"
NORTH M103
LEVEL 3HVAC
DEMOLITION PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.- REMOVE EXISTING DUCTWORK.
2.- PATCH WALL OPENING TO MATCH EXISTING.
3.- REMOVE EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK.
4.- REMOVE EXISTING EXHAUST DUCT RISER FROM ATTIC TO FIRST FLOOR. PATCH
ALL OPENINGS DUE TO EXISTING DUCTWORK REMOVAL TO MATCH EXISTING.
5.- REMOVE EXISTING LOUVER AND PREPARE EXISTING OPENING FOR
INSTALLATION OF NEW LOUVER.
6.-REMOVE EXISTING WINDOW-MOUNTED EXHAUST FAN AND ASSOCIATED
CONTROLS.
7.- PATCH FLOOR OPENING TO MATCH EXISTING.
PLAN NOTES
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
8.3
4
12"x20"
6"x8"
12"x28"
12"x28"
6"x8"
12"x20"
410"x8"
5
1
2
3
4
4
6"x8"
6"x6"
6
1
11
44
5
5
5
5
5
4
2
2
T S R Q
U
6
9
5
5
5
HVAC DEMOLITION PLAN LEVEL 4SCALE: 1/8"=1'-0"
NORTH
M104
LEVEL 4HVAC
DEMOLITION PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.- 18" X 14" EXHAUST DUCT UP TO FLOOR ABOVE.
2.- 18" X 14" SUPPLY DUCT UP TO FLOOR ABOVE.
3.- DUCT FOR FUTURE EXHAUST FOR GENERAL OFFICE SHELL SPACE, CAP ANDSEAL AIRTIGHT.
4.- DUCTWORK SHALL BE ROUTED BENEATH BEAM. KEEP DUCTS TIGHT TOSTRUCTURE ABOVE ALONG BEAM SECTION AND THROUGHOUT CORRIDOR
SECTION.
5.- UNIT TO BE MOUNTED IN MECHANICAL SPACE. SUSPEND UNIT FROMSTRUCTURE ABOVE. UNIT SHALL BE ASSEMBLED IN MECHANICAL SPACE.CONTRACTOR SHALL INCLUDE IN HIS PRICE ALL LABOR AND EQUIPMENT TO
DISASSEMBLE, TRANSPORT, AND RE-ASSEMBLE UNIT IN MECHANICAL SPACE.
6.- FURNISH AND INSTALL MOTORIZED DAMPER AND WIRE TO OPEN WHEN AH-1FAN OPERATES.
7.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 900 CFM FRESH AIR FUTURE
CAPACITY.
8.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 855 CFM EXHAUST AIR FUTURECAPACITY.
9.- LOUVER SIZE SHOWN FOR BIDDING PURPOSES ONLY . VERIFY EXISTINGWINDOW OPENING SIZE AND SIZE NEW LOUVER TO FIT IN OPENING.
10.- BALANCE MANUAL DAMPER TO 1,400 CFM.
11.- DUCTWORK TO BE COORDINATED WITH EXISTING PIPING AND CONDUITS
WITHIN SPACE. RUN DUCTWORK AS HIGH AS POSSIBLE IN THIS AREA. WHEREDUCTWORK DROPS DOWN AGAINST NORTH WALL, KEEP TIGHT TO NORTHWALL.
12.- DUCTWORK TO BE ROUTED ACROSS PIPING CHASE BELOW BASEMENT LEVELIN CRAWLSPACE. COORDINATE DUCT WORK WITH EXISTING PIPING
THROUGH THIS CHASE. KEEP DUCTWORK AS TIGHT TO BASEMENT FLOORLEVEL AS POSSIBLE TO MAXIMIZE HEAD ROOM IN CRAWL SPACE.
13.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 1250 CFM FRESH AIR FUTURECAPACITY.
14.- CAP AND SEAL DUCT AIRTIGHT, DESIGNED FOR 1180 CFM EXHAUST AIR
FUTURE CAPACITY.
15.- PROVIDE AND INSTALL FIRE DAMPERS AT FLOOR LEVEL OF EXISTING SHAFT.
PLAN NOTES
A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT ASNECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.
GENERAL NOTES
UP
DN
DN
UP
DN
UP
DN
DN
UP
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1
CUH-1
FC-1
B
B
B1
2
3
3
AH-1
5
6
L-10
24"x42"9
22"x10"
18"x10"
M
10
3
3
11
12
18
"x1
4"
M200A
D R
4
D R
10
"x8
"
8"x
8"
DR
RD
SW3
SW2
041
040A 040B
C-B-8
C-B-2
C-B-7C-B-6
C-B-1
C-B-4
028
001
7 8
12
13
14
B15
UP
UP
T S R Q
U
C-B-4
SW1
SW1B
C-B-5
10
'-1
"
10
"
18"X14"
10"x14"
6'-
11
1 2"
8"x10"
8'-
31 2
"
7'-
11 2
"
8'-
31 2
"
001 UNOCCUPIED
028 STORAGE 001CW STORAGE
040A ELECT RM 000WW ELECTRICAL
040B COMM RM 001WW COMMUNICATIONS
041 ENTRY 000CW VESTIBULE
- -
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
HVAC DUCT PLAN BASEMENTSCALE: 1/8"=1'-0"
NORTH M200
BASEMENTHVAC DUCT PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
t h i n k c h a m p l i n . c o m
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
SOUTH WING A-SECTION DETAILSCALE: 1/8"=1'-0"
CEILING HEIGHT
22"X15"
36"X14"
18"X14"
FC-5
8"24"X10"
MOUNT FAN COIL AS
HIGH AS POSSIBLE
1.- 36" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 18" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.
2.- 36" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 18" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.
3.- 28" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 22" X 10" EXHAUST DUCT
DOWN TO 1ST FLOOR.
4.- 28" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 22" X 10" SUPPLY DUCT DOWN
TO 1ST FLOOR.
5.- DUCT FOR FUTURE EXHAUST FOR FIRST FLOOR EAST SHELL SPACE. SIZED FOR
APPROXIMATELY 1150 CFM.
6.- DUCT FOR FUTURE SUPPLY FOR FIRST FLOOR EAST SHELL SPACE. SIZED FOR
APPROXIMATELY 1210 CFM.
PLAN NOTES
A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT AS
NECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.
GENERAL NOTES
DN
UP
UP
UP
DNDN
DN
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
NOT IN SCOPE
6.8
Prntr
Copy
Files
Camera
SCOPE OF WORK
A
1
9
8.3
6
TV
Bro
ch
ure
s
WHITEBOARD
WHITEBOARD
WHITEBOARD
WH
ITE
BO
AR
D
PROJSCREEN
OVERHEADPROJECTOR
OVERHEADPROJECTOR
PROJSCREEN
MOVEABLE PARTITION
6.1
TYP.
TYPICAL
TYPICAL
CUH-2
E2345
E2380
E245
FC-4
FC-824"X10"
FC-6
24"X8"
24"X8"
FC-6
FC-6
FC-5
24"X8"
FC-4
24"X8"
FC-7
FC-7
FC-5
190 CFM
114 CFM
111 CFM
120 CFM
185 CFM
60 CFM
203 CFM
202 CFM
FC-2
FC-1
630 CFM
14"X10"
20
"X1
2"
20
"X1
2"
16
"X1
2"
14"X10"
10
"X1
4"
14
"X1
0"
14
"X1
0"
14
"X1
0"
14
"X1
0"
10
"X8
"
20
"X1
5"
12"
6"
8"
20
"X1
0"
8"
8"
15
"X1
0"
8"
8"
6"
10"X8"
8"
8"
B
B
BB
1
2
3
4
5
6
14"X10"
M201A
FC-4
24"X8"14"X10"
8"
123
123A
122D
122A
120
102
101
122B
125
125A
144
143
C-1-1
C-1-2
C-1-4
122
C-1-6
121
118
120A
C-1-5
SW4
SW2
SW3
122G
C-1-3
102B
305 Connector
410 Connector
102A
135 CFM
80 CFM
R Q
UP
DN
DN
7.5
8.2
T S
7
8
6.8
U
9
6
101 VESTIBULE 100CW VESTIBULE
102 WAITING 102CW WAITING
102A RECEPTION 102CW
102B REGISTER 133EW
118 CONFERENCE #4 132EW CONFERENCE
120 MEN 104CW MEN
120A JAN 103CW HAC CLOSET
121 WOMEN 105CW WOMEN
122 CYBER CAFE 106CW CAFE
122A VENDING 107CW VENDING
122B EMPLOYEE DINING 108CW DINING
122D CONFERENCE 3 109CW CONFERENCE
122G CANTEEN - -
123 CONFERENCE 1 111CW CONFERENCE
123A CONFERENCE 2 110CW CONFERENCE
125 COMM RM 112CW COMMUNICATIONS
125A ELECT RM 100WW ELECTRICAL
143 ENROLLMENT 113CW
144 PBS/STAFF 114CW
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
HVAC DUCT PLAN LEVEL 1SCALE: 1/8"=1'-0"
NORTH M201
LEVEL 1HVAC DUCT PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
SOUTH WING A-SECTION DETAILSCALE: 1/8"=1'-0"
1.- 46" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 36" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.
2.- 48" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 36" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.
3.- 28" X 20" EXHAUST DUCT UP TO FLOOR ABOVE. 28" X 14" EXHAUST DUCT
DOWN TO 1ST FLOOR.
4.- 28" X 18 SUPPLY DUCT UP TO FLOOR ABOVE. 28" X 14" SUPPLY DUCT DOWN
TO 1ST FLOOR.
5.- DUCT FOR FUTURE EXHAUST FOR SECOND FLOOR EAST SHELL SPACE. SIZED
FOR APPROXIMATELY 1150 CFM.
6.- DUCT FOR FUTURE SUPPLY FOR SECOND FLOOR EAST SHELL SPACE. SIZED
FOR APPROXIMATELY 1210 CFM.
7.- DUCT FOR FUTURE EXHAUST FOR SECOND FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 1250 CFM.
8.- DUCT FOR FUTURE SUPPLY FOR SECOND FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 1350 CFM.
PLAN NOTES
Q
7.5
8.2
P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
6.1
UPDN
UPDN
UPDN
F.E.
B
B
BB 1
2
3
4
5
6
78
SW3
SW2
SW4
231
231A
C-2-2
C-1-4 C-2-4
UP
DN
T S R Q
STAIR-2
U
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
231 COMM RM
231A ELECTR
200CW COMMUNICATIONS
200WW ELECTRICAL HVAC DUCT PLAN LEVEL 2SCALE: 1/8"=1'-0"
NORTH M202
LEVEL 2HVAC DUCT PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
t h i n k c h a m pl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
CEILING HEIGHT
14"X20" 14"X12"FC-5
MOUNT FAN COIL AS
HIGH AS POSSIBLE
1.- 60" X 14" EXHAUST DUCT UP TO FLOOR ABOVE. 46" X 14" EXHAUST DUCT
DOWN TO 2ND FLOOR.
2.- 62" X 14" SUPPLY DUCT UP TO FLOOR ABOVE. 48" X 14" SUPPLY DUCT DOWN
TO 2ND FLOOR.
3.- PROVIDE BALANCE DAMPER IN DUCT EXTENSION FOR FINAL BALANCE.
4.- DUCT FOR FUTURE EXHAUST FOR THIRD FLOOR SOUTH SHELL SPACE. SIZED
FOR APPROXIMATELY 700 CFM.
5.- DUCT FOR FUTURE SUPPLY FOR THIRD FLOOR SOUTH SHELL SPACE. SIZED FOR
APPROXIMATELY 730 CFM.
6.- 28" X 20" EXHAUST DUCT UP TO FLOOR ABOVE. 28" X 20" EXHAUST DUCT
DOWN TO 2ND FLOOR.
7.- 28" X 20 SUPPLY DUCT UP TO FLOOR ABOVE. 28" X 18" SUPPLY DUCT DOWN
TO 2ND FLOOR.
PLAN NOTES
A.- CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING AND CONDUIT AS
NECESSARY TO ALLOW FOR INSTALLATION OF NEW DUCTWORK.
GENERAL NOTES
DN
DN
DN
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1E2
345
E2380
E245
FC-7
130 CFM
FC-4
50 CFM
FC-6
24"X8"
55 CFM
FC-5
630 CFM
FC-4
50 CFM
FC-1
FC-6
30"X10"
24"X8"
14"X12"
30"X10"
30"X10"
30"X10"
14"X12"
80 CFM 8"X8"
14"X6"
FC-1 FC-1 FC-1 FC-1
FC-1
FC-1
FC-1
FC-1
FC-3
FC-2
48"X10"
18"X8"
48"X10"
18"X8"
12"X8"
140 CFM
FC-1FC-1
FC-8
24"X10"
90 CFMFC-8
48"X10"
18"X8"
FC-8
48"X10"
18"X8"
FC-8
48"X10"
18"X8"
10
"X8
"
12"
6"
6"
8"
6"
B
22
"X6
"
14"x10"
6"
14"x10" 12"x10"
6" 6"
10"x8"
8"
8"x6"
8"x6"
20
"X1
4"
20"x10" 15"x10"
12"x8"
12
"x8
"12
3
4
5 30"X10"
14"X12"
3
3 3
3
3
3
3
3
33 3
3
3
6
7
B
3 3 3
12"X14"
B
D14"X20"
M203A
SW3
SW2
311
310
308
309
307
302A 302B 303 303A
305A304A
314315
305
302
301A
331
331A
318A
328
306
318
319
312
304
313A
313
316317
C-3-4
301
348
C-3-1
327
C-3-5
C-3-4
6"
90 CFM 90 CFM
R Q
DN
7.5
8.2
T S
7
8
6.8
U
9
6
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
301 WAITING 300EW PATIENT BUSINESSSERVICES
301A BREAK ROOM 301EW BREAK ROOM
302 PRIVACY OFFICER 302EW OFFICE
302A TUMOR REGISTRY 303EW OFFICE
302B CODING SUPERVISOR 304EW OFFICE
303 TRAINER 305EW OFFICE
303A COMPUTERCOORDINATOR
306EW OFFICE
304 RELEASE TECHS 308EW OPEN OFFICE
304A RELEASE SUPERVISOR 307EW OFFICE
305 STORAGE 309EW STORAGE
305A 310EW OFFICE
306 ELECTR 311EW ELECTRICAL
307 SCANNING STAGING 313EW
308 PBS CHIEF 314EW OFFICE
309 ADMINISTRATIVEASSISTANT
315EW OFFICE
310 ASSISTANT CHIEF 316EW OFFICE
311 CHIEF OF HIMS 317EW OFFICE
312 SCANING TECHS 318EW OPEN OFFICE
313 WORK ROOM 312 EW OFFICE
313A CORRIDOR
314 319EW OFFICE
315 320EW OFFICE
316 FEE BASIS TECHS - -
317 CODING TECHS 321EW OFFICE
317A RECEPTION 322EW RECEPTION
318 MEN 301CW MEN
318A JANITOR 300CW HAC CLOSET
319 WOMEN 302CW WOMEN
327 STORAGE 303CW STORAGE
328 STORAGE 304CW STORAGE
331 COMM RM 300WW COMMUNICATIONS
331A ELECTRICAL 301WW ELECTRICAL
348 CONFERENCE 305CW CONFERENCE
HVAC DUCT PLAN LEVEL 3SCALE: 1/8"=1'-0"
NORTH M203
LEVEL 3HVAC DUCT PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
SOUTH WING A-SECTION DETAILSCALE: 1/8"=1'-0"
DOAS-2
28"x20"
28"x20"
DOAS-2
28"x20"
28"x20"
EXIST. SPR. LINE (TYP.)
DOAS-1
30"x25"
30"x25"30"x25"
EXIST. SPR. LINE (TYP.)
DOAS-130"x25"
30"x25"
1.-LOUVER SIZE SHOWN IS FOR BIDDING PURPOSES ONLY. CONTRACTOR TOFIELD-VERIFY EXISTING OPENING SIZE AND SIZE NEW LOUVER TO MATCHEXISTING OPENING SIZE.
2.-PROVIDE FIRE DAMPERS AT ALL DUCT ATTIC FLOOR PENETRATIONS.
3.-COORDINATE ALL DUCTWORK INSTALLATION IN ATTIC AND PENTHOUSE WITHEXISTING SPRINKLER PIPING.
4.-AIR HANDLER MUST BE DISASSEMBLED AS NECESSARY TO TRANSPORT UNIT TOATTIC SPACE, THEN RE-ASSEMBLED IN ATTIC SPACE. CONTRACTOR SHALLINCLUDE IN HIS PRICE ALL LABOR AND MATERIALS AS NECESSARY TODISASSEMBLE, TRANSPORT, AND RE-ASSEMBLE UNIT IN ATTIC. AIR HANDLERMANUFACTURER'S REPRESENTATIVE SHALL SUPERVISE, APPROVE, ORPERFORM (AT THE DESCRETION OF UNIT MANUFACTURER) ALLDISASSEMBLING AND RE-ASSEMBLING OF UNIT.
5.-RUN 1-1/2" AC CONDENSATE DRAIN PIPING FROM AIR HANDLER TO NEARESTFLOOR DRAIN.
6.-INSTALL ALL DUCTWORK IN ATTIC AND PENTOUSE WITH TOP OF DUCT AT MIN.24" BELOW ALL SPRINKLER HEADS.
7.-INSTALL DRAIN IN BOTTOM OF LOUVER PLENUM AND RUN 1" INSULATEDDRAIN PIPE TO NEAREST FLOOR DRAIN.
8.- COORDINATE CLOSELY WITH REFRIGERANT PIPING, SO THAT BOTHDUCTWORK AND REFRIGERANT PIPING HAVE ACCESS TO THE CHASE BELOWON THE THIRD FLOOR.
9.- FOOTPRINT FOR FUTURE UNIT TO SERVE ALL ADDITIONAL FLOORS. SHOWNFOR REFERENCE ONLY (NOT INCLUDED IN CONTRACT).
10.- PROVIDE AND INSTALL NEW LOUVERS IN THESE LOCATIONS TO MATCHEXISTING LOUVERS INSTALLED ON EAST WING. LOUVERS ARE SHOWN WITHFLOW PARAMETERS FOR GUIDELINES, NOTHING WILL BE CONNECTED TOLOUVERS IN ATTIC SPACE. PROVIDE INSULATED BLANK-OFF PLATES ON ATTICSIDE OF LOUVERS FOR FUTURE CONNECTION TO DOAS-X.
PLAN NOTES
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
8.3
DOAS-XDOAS-2
EXH IN
SA
OA
EXH OUT
DOAS-1
28"x20" 28"x20"
28"x20"
18
"x1
8"
18
"x1
8"
L-442" Ø
L-5
42" Ø
L-6
48" Ø
1
1
1
3
6
6
6
6
7
7
7
28"x20"
4 5
82
82
30
"x2
5"
L-3
48" Ø
L-130"x60"
L-2
48" Ø
30
"x2
5"
1
1
1
20
"x2
2"
4 5
3
3
3
6
6
6
6
7
7
7
30
"x2
5"
6
62"x14"60"x14"
OA
EX
H IN
EX
H O
UT
SA
D
M204A
M204B
D
OAEXH IN
EXH OUTSA
M2
04
C
6 28"x20"
DD
M2
04
D
D
9
2
T S R Q
U
6
9
L-442" Ø
L-5
42" Ø
L-6
48" Ø
10
10
10
HVAC DUCT PLAN LEVEL 4SCALE: 1/8"=1'-0"
NORTH M204
LEVEL 4HVAC DUCT PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
EAST WING C-SECTION DETAILSCALE: 1/8"=1'-0"
EAST WING D-SECTION DETAILSCALE: 1/8"=1'-0"
SOUTH WING A-SECTION DETAILSCALE: 1/8"=1'-0"
SOUTH WING B-SECTION DETAILSCALE: 1/8"=1'-0"
1.-REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.
2.-1" COOLING COIL CONDENSATE DRAIN LINE UP THRU SLAB TO FAN COIL UNITON FLOOR ABOVE.
3.-DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHERPIPING IN CHASE.
4.-BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.
5.-EXISTING 3" FLOOR DRAIN IN MECHANICAL ROOM. ROUTE CONDENSATEDRAIN LINES DOWN WALL AND NEAR DRAIN.
6.-REFRIGERANT LINES TO CONDENSING UNIT 1. SEE M301 FOR FURTHERINFORMATION.
7.-REFRIGERANT LINES TO CONDENSING UNIT 2. SEE M301 FOR FURTHERINFORMATION.
8.-REFRIGERANT LINES TO CONDENSING UNIT 3. SEE M301 FOR FURTHERINFORMATION.
9.-REFRIGERANT LINES TO CONDENSING UNIT 4. SEE M301 FOR FURTHERINFORMATION.
10.-REFRIGERANT LINES TO CONDENSING UNIT 5. SEE M301 FOR FURTHERINFORMATION.
11.-COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.COORDINATE PIPING WITH OTHER PIPING IN CHASE. SEE PIPINGCONTINUATION ON PLUMBING SHEET P200.
12.-NEW PRV STATION. SEE DETAIL 12 ON SHEET M502.
13.-CONNECT TO EXISTING 3" HIGH PRESSURE STEAM LINE. PROVIDE NEW 2-1/2"TAP ON EXISTING MAIN STEAM HEADER. PROVIDE A LINE SIZE GATE VALVEDOWNSTREAM TAP. COORDINATE DOWNTIME OF MAIN STEAM SYSTEMWITH VA FACILITIES STAFF PRIOR TO EXECUTING WORK. PROVIDE AMINIMUM OF A WEEK LEAD TIME PRIOR TO STEAM SYSTEM SHUTDOWN.
14.-STEAM AND CONDENSATE PIPING TO AHU-1. SEE M200 FOR MOREINFORMATION.
15.-CONNECT NEW 3" LOW PRESSURE RETURN INTO EXISTING LOW PRESSURERETURN LINE IN CRAWL SPACE.
16.-2" VENT FROM CONDENSATE PUMP. TERMINATE AT 24" ABOVE BUILDINGCONNECTOR ROOF LINE WITH 90° ELBOW DOWN. FASTEN PIPING TOEXTERIOR OF THE BUILDING.
17.-CONNECT TO NEW HOT WATER HEATER.
18.-PIPING SHALL BE RUN BELOW BASEMENT SLAB AND INTO
SUB-BASEMENT/CRAWL SPACE.
19.-NEW PRV STATION. SEE DETAIL 12 ON SHEET M502. PRV STATION TO BERECONNECTED TO EXISTING LOW PRESSURE STEAM SYSTEM LOCAL TO THEMECHANICAL ROOM SPACE.
20.-VENT FROM PRESSURE REDUCING STATIONS. TERMINATE AT 24" ABOVEBUILDING CONNECTOR ROOF LINE WITH 90° ELBOW DOWN. FASTEN PIPINGTO EXTERIOR OF THE BUILDING.
21.-REFRIGERANT LINES TO CONDENSING UNIT 6. SEE M301 FOR FURTHERINFORMATION.
22.-STEAM AND CONDENSATE LINES UP TO LEVEL 4 SERVING DOAS-1 UNIT, SEEDRAWING M304 FOR DETAILS. CONDENSATE LINE UP TO LEVEL 1 FAN COILUNITS, SEE M301 CODED NOTE 9 FOR DETAILS.
23.-REFRIGERANT LINES TO CONDENSING UNIT 5 / DOAS-1 UNIT. SEE DRAWINGSM301 AND M304 FOR FURTHER INFORMATION.
24.-REFRIGERANT LINES TO CONDENSING UNIT 1/LEVEL 3 FAN COIL UNITS. SEEDRAWINGS M301 AND M303 FOR FURTHER INFORMATION.
25.-REFRIGERANT LINES TO CONDENSING UNIT 2/LEVEL 1 FAN COIL UNITS. SEEDRAWING M301 FOR FURTHER INFORMATION.
26.-STEAM AND CONDENSATE LINES UP TO LEVEL 4 SERVING DOAS-2 UNIT, SEEDRAWING M304 FOR DETAILS.
27.-REFRIGERANT LINES TO CONDENSING UNIT 3/LEVEL 3 FAN COIL UNITS. SEEDRAWINGS M301 AND M303 FOR FURTHER INFORMATION.
28.-REFRIGERANT LINES TO CONDENSING UNIT 4/LEVEL 3 FAN COIL UNITS. SEEDRAWINGS M301 AND M303 FOR FURTHER INFORMATION.
29.-REFRIGERANT LINES TO CONDENSING UNIT 6 / DOAS-2 UNIT. SEE DRAWINGSM301 AND M304 FOR FURTHER INFORMATION.
PLAN NOTES
UP
DN
DN
UP
DN
UP
DN
DN
UP
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1
RL
RD
RS
1"
1"
1"
T
1
2
2
3
4
5
7
RL
RD
RS
6
1-1/4"
1-1/4" 1"
11
1111
RS RD RLRL RHGBP RS
RS RHGBP RL
RL RHGBP RSRS RHGBP RL
9
10
21 8
RS RD RL
12
12PRV-1
PRV-213
14
2"
C
15 PSI
15
PS
I
3"
CP-1
1-1/4"15
V
16
17
18
18 18
PRV-3
PRV-4 19
20
SW3
SW2
041
040A 040B
C-B-8
C-B-2
C-B-7C-B-6
C-B-1
C-B-4
028
001
UP
DN
DN
UP
DN
UP
DN
DN
UP
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1
CUH-1
FC-1
AH-1
SW3
SW2
041
040A 040B
C-B-8
C-B-2
C-B-7C-B-6
C-B-1
C-B-4
028
001
22 23 24 25
26
2728
2926
2-1/2" 1-1/2"
UP
UP
T S R Q
U
C-B-4
SW1
SW1B
C-B-5
UP
UP
T S R Q
U
C-B-4
SW1
SW1B
C-B-5
001 UNOCCUPIED
028 STORAGE 001CW STORAGE
040A ELECT RM 000WW ELECTRICAL
040B COMM RM 001WW COMMUNICATIONS
041 ENTRY 000CW VESTIBULE
- -
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
A. SLOPE ALL COOLING COIL CONDENSATE DRAIN PIPING AT MIN. 1/10 SLOPE INDIRECTION OF FLOW
B. ALL VRV SYSTEM REFRIGERANT PIPING TEES ARE TO BE REFNET JOINTS. REFNETJOINTS TO BE MIN. 40" FROM EACH OTHER.
C. SEE PIPING SCHEMATICS ON SHEETS M503 AND M504, FOR VRV SYSTEMREFRIGERANT PIPE SIZES. SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY.VRV SYSTEM MANUFACTURER IS RESPONSIBLE FOR PIPE SIZING OF INSTALLEDPIPE.
D. ALL COOLING COIL CONDENSATE DRAIN PIPING TO HAVE 45° WYE ELBOWS. 90°ELBOWS ARE NOT PERMITTED. PROVIDE CLEANOUTS AT ALL VERTICAL RISERSAND HORZONTAL CHANGES IN DIRECTION.
E. FURNISH AND INSTALL WALL-MOUNTED THERMOSTATS FOR ALL FAN COILUNITS.
F. COOLING COIL CONDENSATE DRAIN RUN-OUTS TO FAN COIL UNITS SHALL BEMIN. 1".
G.- REFER TO SCHEDULES ON SHEET M501.
PIPING PLANS GENERAL NOTES
HVAC PIPING PLAN BASEMENTSCALE: 1/8"=1'-0"
NORTH M300
BASEMENTHVAC PIPING PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.-MOUNT CONDENSING UNIT ON OUTDOOR EQUIPMENT PAD - SEE DETAIL 17
ON M502. PAD TO EXTEND 4" FROM EDGE OF UNIT/UNITS ON ALL SIDES.
2.-COVER WEATHER-EXPOSED PIPING WITH ALUMINUM JACKET. MOUNT PIPINGON EQUIPMENT SUPPORTS LOCATED AT 5'-0" O.C. AND AT CHANGES INDIRECTION. SEE DETAIL 16 ON SHEET M502 FOR EQUIPMENT SUPPORTDESIGN.
3.-REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.
4.-1" COOLING COIL CONDENSATE DRAIN LINE FROM FC UNIT DOWN THRUFLOOR. SEE FLOOR PLAN BELOW FOR CONTINUATION.
5.-1" COOLING COIL CONDENSATE DRAIN LINE DOWN TO MOP SINK BELOW.
6.- DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHERPIPING IN CHASE.
7.-REFRIGERANT PIPING DOWN TO CONDENSING UNIT 2. ALL FAN COILS ON THISLEVEL SHALL BE SERVED BY THIS CONDENSING UNIT. COORDINATE LOCATIONWITH CHASE OR WALLS ON FLOORS ABOVE AND BELOW.
8.-BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.
9.-COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.COORDINATE PIPING WITH OTHER PIPING IN CHASE.
10.-SEE BASEMENT PIPING PLAN FOR CONTINUATION.
11.-REGRADE AS NECESSARY. FURNISH AND INSTALL 6 INCH GRAVEL BEDCONFORMING TO AASHTO IN THIS AREA.
12.- FOOTPRINT FOR FUTURE UNITS TO SERVE ALL ADDITIONAL FLOORS. SHOWN
FOR REFERENCE ONLY (NOT INCLUDED IN CONTRACT).
13.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRUCHASE. SEE ADDITIONAL BASEMENT, SECOND, THIRD, AND ATTIC LEVELPIPING DRAWINGS FOR FURTHER INFORMATION. COORDINATE WITHDUCTWORK IN CHASE.
PLAN NOTES
DN
UP
UP
UP
DNDN
DN
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
NOT IN SCOPE
6.8
Prntr
Copy
Files
Camera
SCOPE OF WORK
A
1
9
8.3
6
TV
Bro
ch
ure
s
WHITEBOARD
WHITEBOARD
WHITEBOARD
WH
ITE
BO
AR
D
PROJSCREEN
OVERHEADPROJECTOR
OVERHEADPROJECTOR
PROJSCREEN
MOVEABLE PARTITION
6.1
TYP.
TYPICAL
TYPICAL
10
'-0
"
CU-6
10
'-0
"
1 1
T3(TYP.)
T
DN
UP
UP
UP
DNDN
DN
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
NOT IN SCOPE
6.8
Prntr
Copy
Files
Camera
SCOPE OF WORK
A
1
9
8.3
6
TV
Bro
ch
ure
s
WHITEBOARD
WHITEBOARD
WHITEBOARD
WH
ITE
BO
AR
D
PROJSCREEN
OVERHEADPROJECTOR
OVERHEADPROJECTOR
PROJSCREEN
MOVEABLE PARTITION
6.1
TYP.
TYPICAL
TYPICAL
CUH-2
FC-4
FC-8
FC-6
FC-6
FC-6
FC-5
FC-4
FC-7
FC-7
FC-5
FC-2
FC-1
FC-4
123
123A
122D
122A
120
102
101
122B
125
125A
144
143
C-1-1
C-1-2
C-1-4
122
C-1-6
121
118
120A
C-1-5
SW4
SW2
SW3
122G
C-1-3
102B
305 Connector
410 Connector
102A
T
T
T
T
T
T
T
T
T
3(TYP.)
3(TYP.)
6
4
6
4
8
RS
RD
RL
RS
RD
RL
10
'-0
"
CU-4
10
'-0
"
D
1"
D
D
1"
1"
1"
DD
1"
1"
1"
7910
10
10
11
5
12
1212
12
12
CU-5
CU-1
CU-2
RLRS
RL
RS
RL
RD
RS
RL
RD
RS
RHGBP
RH
GB
P
10'-0"
10'-0"
1
1
1
2
2
11
1212
8
8
8
8
8
99
9
1-1/4"
1-1/4"1"
RSRDRL
2
RLR
S
RLRS
RH
GB
P
RHGBP
CU-3
RSRDRL
8
123
123A
122D
122A
120
102
101
122B
125
125A
144
143
C-1-1
C-1-2
C-1-4
122
C-1-6
121
118
120A
C-1-5
SW4
SW2
SW3
122G
C-1-3
102B
305 Connector
410 Connector
102A
13
13
T
T
8
8
R Q
UP
DN
DN
7.5
8.2
T S
7
8
6.8
U
9
6
10
'-0
"
R Q
UP
DN
DN
7.5
8.2
T S
7
8
6.8
U
9
6
10
'-0
"
101 VESTIBULE 100CW VESTIBULE
102 WAITING 102CW WAITING
102A RECEPTION 102CW
102B REGISTER 133EW
118 CONFERENCE #4 132EW CONFERENCE
120 MEN 104CW MEN
120A JAN 103CW HAC CLOSET
121 WOMEN 105CW WOMEN
122 CYBER CAFE 106CW CAFE
122A VENDING 107CW VENDING
122B EMPLOYEE DINING 108CW DINING
122D CONFERENCE 3 109CW CONFERENCE
122G CANTEEN - -
123 CONFERENCE 1 111CW CONFERENCE
123A CONFERENCE 2 110CW CONFERENCE
125 COMM RM 112CW COMMUNICATIONS
125A ELECT RM 100WW ELECTRICAL
143 ENROLLMENT 113CW
144 PBS/STAFF 114CW
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
HVAC PIPING PLAN LEVEL 1SCALE: 1/8"=1'-0"
NORTH M301
LEVEL 1HVAC PIPING PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.- MOUNT PIPING AS HIGH AS POSSIBLE.
2.- COOLING COIL CONDENSATE DRAIN UP TO FLOOR ABOVE. COORDINATE
EXACT LOCATION WITH EQUIPMENT THAT DRAIN CONNECTS TO ON FLOORABOVE OR WALL OR CHASE THAT DRAIN IS CONCEALED IN ON FLOOR ABOVE.
3.- COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.
COORDINATE PIPING WITH OTHER PIPING IN CHASE.
4.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRU CHASE.SEE ADDITIONAL BASEMENT, THIRD, AND ATTIC LEVEL PIPING DRAWINGS FORFURTHER INFORMATION.
PLAN NOTES
Q
7.5
8.2
P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
6.1
UPDN
UPDN
UPDN
F.E.
1
1
2
2
2
2
222
22222 2
3
1"1"1" 1"
33
1" 1-1/4" 1" 1"
1-1/4"
1"
1"
1-1/4" 1"
4
4
SW3
SW2
SW4
231
231A
C-2-2
C-1-4 C-2-4
UP
DN
T S R Q
STAIR-2
U
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
231 COMM RM
231A ELECTR
200CW COMMUNICATIONS
200WW ELECTRICAL HVAC PIPING PLAN LEVEL 2SCALE: 1/8"=1'-0"
NORTH M302
LEVEL 2HVAC PIPING PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.- COOLING COIL CONDENSATE DRAIN LINE UP AND DOWN INSIDE WALL.COORDINATE PIPING WITH OTHER PIPING IN CHASE.
2.- REFRIGERANT PIPING UP TO ATTIC ABOVE. COORDINATE PIPING, DUCTWORKAND HOLE PENETRATIONS IN SAME AREA.
3.- REMOTE MOUNTED THERMOSTAT FOR VRV FAN COIL UNIT.
4.- 1" COOLING COIL CONDENSATE DRAIN LINE FROM FC UNIT DOWN THRUFLOOR. SEE FLOOR PLAN BELOW FOR CONTINUATION.
5.- 1" COOLING COIL CONDENSATE DRAIN LINE DOWN TO MOP SINK BELOW.
6.- DROP REFRIGERANT PIPING DOWN INSIDE FURRED WALL AND CONNECT TO
FAN COIL UNIT (FROM INSIDE WALL). COORDINATE PIPING WITH OTHERPIPING IN CHASE.
7.-REFRIGERANT LINES TO CONDENSING UNIT 1/LEVEL 3 (CENTER) FAN COILUNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.
8.- BRANCH SELECTOR BOX MANUFACTURED BY VRV SYSTEM MANUFACTURER.
9.- STEAM, CONDENSATE AND REFRIGERANT PIPING UP AND DOWN THRU CHASE.SEE ADDITIONAL BASEMENT, FIRST, SECOND AND ATTIC LEVEL PIPINGDRAWINGS FOR FURTHER INFORMATION..
10.- COOLING COIL CONDENSATE DRAIN LINE FROM DOAS UNITS ABOVE. ROUTEPIPING TO HOUSEKEEPING CLOSET MOP SINK.
11.-REFRIGERANT LINES TO CONDENSING UNIT 3/LEVEL 3 (NORTH EAST) FANCOIL UNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.
12.-REFRIGERANT LINES TO CONDENSING UNIT 4/LEVEL 3 (SOUTH EAST) FAN COILUNITS. SEE DRAWING M301 FOR FURTHER INFORMATION.
PLAN NOTES
A. SLOPE ALL COOLING COIL CONDENSATE DRAIN PIPING AT MIN. 1/10 SLOPE INDIRECTION OF FLOW
B. ALL VRV SYSTEM REFRIGERANT PIPING TEES ARE TO BE REFNET JOINTS. REFNETJOINTS TO BE MIN. 40" FROM EACH OTHER.
C. SEE PIPING SCHEMATICS ON SHEETS M503 AND M504 FOR VRV SYSTEMREFRIGERANT PIPE SIZES. SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY.VRV SYSTEM MANUFACTURER IS RESPONSIBLE FOR PIPE SIZING OF INSTALLEDPIPE.
D. ALL COOLING COIL CONDENSATE DRAIN PIPING TO HAVE 45° WYE ELBOWS. 90°ELBOWS ARE NOT PERMITTED. PROVIDE CLEANOUTS AT ALL VERTICAL RISERSAND HORIZONTAL CHANGES IN DIRECTION.
E. FURNISH AND INSTALL WALL-MOUNTED THERMOSTATS FOR ALL FAN COILUNITS.
F. COOLING COIL CONDENSATE DRAIN RUN-OUTS TO FAN COIL UNITS SHALL BEMIN. 1".
G.- REFER TO SCHEDULES ON SHEET M501.
PIPING PLANS GENERAL NOTES
DN
DN
DN
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1
FC-7
FC-4
FC-6
FC-5
FC-4
FC-1
FC-6
FC-1 FC-1 FC-1 FC-1
FC-1
FC-1
FC-1
FC-1
FC-3
FC-2FC-1FC-1
FC-8
FC-8 FC-8 FC-8
SW3
SW2
311
310
308
309
307
302A 302B 303 303A
305A304A
314315
305
302
301A
331
331A
318A
328
306
318
319
312
304
313A
313
316317
C-3-4
301
348
C-3-1
327
C-3-5
C-3-4
DN
DN
DN
UP
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
9
8.3
66.1
D
1"
5
D
1" 1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
46
8 8 8 8 8 8
8
8
8
8
8
8
RSRD RLRS RD RL
8
8
8
8
8
8
8
8
8
46
46 4
64
6
46
46
46
4
6
6
4
64
64
64
1
1
2
9
RS RD RL
C15 PSI
SW3
SW2
311
310
308
309
307
302A 302B 303 303A
305A
304A
314315
305
302
301A
331
331A
318A
328
306
318
319
312
304
313A
313
316
317
C-3-4
301
348
C-3-1
327
C-3-5
C-3-4
10
10
T
3
T
3
T
3
T
3
T 3
T3
T3
T3
T3
T3
T3
T
3
T3
3
T3
T3
3
T3
33
333
7
11
12
R Q
DN
7.5
8.2
T S
7
8
6.8
U
9
6
R Q
DN
7.5
8.2
T S
7
8
6.8
U
9
6
NO. NAME VA NO. VA NAME
ROOM SCHEDULE
301 WAITING 300EW PATIENT BUSINESSSERVICES
301A BREAK ROOM 301EW BREAK ROOM
302 PRIVACY OFFICER 302EW OFFICE
302A TUMOR REGISTRY 303EW OFFICE
302B CODING SUPERVISOR 304EW OFFICE
303 TRAINER 305EW OFFICE
303A COMPUTERCOORDINATOR
306EW OFFICE
304 RELEASE TECHS 308EW OPEN OFFICE
304A RELEASE SUPERVISOR 307EW OFFICE
305 STORAGE 309EW STORAGE
305A 310EW OFFICE
306 ELECTR 311EW ELECTRICAL
307 SCANNING STAGING 313EW
308 PBS CHIEF 314EW OFFICE
309 ADMINISTRATIVEASSISTANT
315EW OFFICE
310 ASSISTANT CHIEF 316EW OFFICE
311 CHIEF OF HIMS 317EW OFFICE
312 SCANING TECHS 318EW OPEN OFFICE
313 WORK ROOM 312 EW OFFICE
313A CORRIDOR
314 319EW OFFICE
315 320EW OFFICE
316 FEE BASIS TECHS - -
317 CODING TECHS 321EW OFFICE
317A RECEPTION 322EW RECEPTION
318 MEN 301CW MEN
318A JANITOR 300CW HAC CLOSET
319 WOMEN 302CW WOMEN
327 STORAGE 303CW STORAGE
328 STORAGE 304CW STORAGE
331 COMM RM 300WW COMMUNICATIONS
331A ELECTRICAL 301WW ELECTRICAL
348 CONFERENCE 305CW CONFERENCE
HVAC PIPING PLAN LEVEL 3SCALE: 1/8"=1'-0"
NORTH M303
LEVEL 3HVAC PIPING PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
1.-RUN 1-1/2" COOLING COIL CONDENSATE DRAIN PIPING FROM AIR HANDLER
HOUSEKEEPING CLOSET ON FLOOR BELOW. ROUTE DRAIN TO MOP SINK
LOCATED WITHIN THIS HOUSEKEEPING CLOSET.
2.-REFRIGERANT PIPING DOWN THRU ATTIC FLOOR. COORDINATE LOCATION
WITH WALL OR CHASE ON FLOOR BELOW.
3.-COORDINATE INSTALLATION AND LOCATIONS OF ALL NEW PIPING WITH
EXISTING SPRINKLER PIPING IN ATTIC.
4.-REFRIGERANT PIPING TO BE SIZED BY AIR HANDLING UNIT/CONDENSING UNIT
MANUFACTURER.
5.-MOUNT AIR HANDLER ON 4" BASE RAILS. PROVIDE VIBRATION ISOLATION PER
SPECIFICATION SECTION 23 05 41.
PLAN NOTES
7.5
8.2
Q P O N M.1 M L BCDEFGHH.9JK
7
8
5
4
3
2
6.8
A
1
8.3
AH-X
2
3 4
1
1
3 4
5
5
2
C15 PSI
C1
5 P
SI
DOAS-2
DOAS-1
2"
1-1/4"
1-1/4"
1-1/4"
2-1/2"
1-1/2"
T S R Q
U
6
9
AH-X
HVAC PIPING PLAN LEVEL 4SCALE: 1/8"=1'-0"
NORTH M304
LEVEL 4HVAC PIPING PLAN
DS
IC
1/8" = 1'-0"
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
A.- PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABORREQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS ASINDICATED ON THE DRAWINGS AND AS SPECIFIED.
B.- ALL WORK SHALL BE INSTALLED ACCORDING TO THE LATEST LOCAL, STATEAND NATIONAL CODES. ALL DUCTWORK SHALL BE INSTALLED ACCORDING TOTHE LATEST ASHRAE RECOMMENDATIONS AND SMACNA INSTALLATIONMANUALS.
C.- CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK AREDIAGRAMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERALARRANGEMENT ONLY.
D.- PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TOPREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
E.- PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TOAND WITHIN 50 FEET OF ISOLATED EQUIPMENT THROUGHOUT MECHANICALEQUIPMENT ROOMS.
F.- COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITHARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ONOTHER CONTRACT DOCUMENT DRAWINGS.
G.- MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS,CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES INMECHANICAL ROOMS.
H.- CAULK SPACE BETWEEN SLEEVES, DUCTS AND PIPES WHERE DUCTS AND PIPESPASS THROUGH WALLS. CAULKING TO BE AIRTIGHT.
I.- ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT ORPIPING INSULATION IS APPLIED.
J.- COORDINATE OPENINGS THROUGH OUTSIDE WALLS, LINTELS FOR LOUVERSWITH STRUCTURAL AND ARCHITECTURAL REQUIREMENTS.
K.- COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS'CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPINGTRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTONS TO FURNISHEDEQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPINGDIMENSIONS BEFORE FABRICATION.
L.- MINIMUM CONCRETE PAD THICKNESS SHALL BE 4 INCHES FOR INTERIOREQUIPMENT, 6 INCHES FOR EXTERIOR EQUIPMENT. PAD SHALL EXTEND BEYONDTHE EQUIPMENT A MINIMUM OF 4 INCHES ON EACH SIDE, WITH BEVELEDEDGES.
M.- PROVIDE INSULATED SUBBASES ON ALL THERMOSTATS/TEMPERATURESENSORS LOCATED ON EXTERIOR WALLS.
N.- INLET DUCTWORK TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK SIZEUNLESS NOTED OTHERWISE. INLET DUCTWORK TO AIR TERMINAL BOXES SHALLBE SAME SIZE AS BOX INLET UNLESS NOTED OTHERWISE.
O.- ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION
AND AS SHOWN IN DETAILS FOR PIPING, DUCTWORK AND EQUIPMENT (UNLESS
NOTED OTHERWISE) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
P.- ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURALSTEEL SHALL BE COORDINATED WITH STRUCTURAL REQUIREMENTS. ALLATTACHMENTS TO STEEL BAR JOISTS, TRUSSES OR JOIST GIRDERS SHALL BE ATPANEL POINTS. PROVIDE BEAM CLAMPS MEETING MSS STANDARDS. WELDINGTO STRUCTURAL MEMBERS SHALL NOT BE PERMITTED. THE USE OF C-CLAMPSSHALL NOT BE PERMITTED.
Q.- LOCATION AND SIZED OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BECOORDINATED WITH ALL OTHER TRADES INVOLVED.
R.- ALL OPENINGS IN FIRE RATED WALLS DUE TO DUCTWORK, PIPING, CONDUIT,ETC., SHALL BE FIRE STOPPED. SEE SPECIFICATIONS FOR REQUIREMENTS. FIRERATED WALL TO HAVE FIRE DAMPERS IN ALL DUCT PENETRATIONS.
S.- ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIRHANDLING UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITHP-TRAP, AND PIPED TO NEAREST DRAIN. PROVIDE CONDENSATE TRAP ASREQUIRED.
HVAC GENERAL NOTES
S SPACE TEMPERATURE SENSOR - MOUNTING HEIGHT 48"
SPACE HUMIDISTATH
SPACE MOTION SENSOR
T THERMOSTAT ELECTRIC - MOUNTING HEIGHT 48"
NEW EQUIPMENT REFERENCE SYMBOLH-1
NOTE SYMBOL2
CONNECT TO EXISTING SYMBOL
ROOM NUMBER105
APPROXIMATE ELEVATION FROM FLOOR TOBOTTOM OF DUCT, PIPE OR EQUIPCHMENT ITEM
9'-6"
SECTION "A" DESIGNATION, SHOWN ON SHEET H1M1-1
A
H3321
DETAIL REFERENCE SYMBOL, DETAIL "A" SHOWN ON SHEET H1
WALL OR DUCT MOUNTED AIR DEVICE, S1 AIR DEVICEDESIGNATION. REFER TO SCHEDULE. 10"x6" NECK SIZE,200-REQUIRED CFM, 7'-6" MOUNTING HEIGHT FROM FLOOR TOBOTTOM OF AIR DEVICE. BRANCH DUCT SIZE SAME AS NECK SIZEUNLESS INDICATED OTHERWISE.
S1-10"x6"200-7'-6"
MANUAL BALANCING VOLUME DAMPER WITH LOCKING DEVICE
U/C 1" DOOR UNDER CUT
DUCT RISE IN DIRECTION OF AIR FLOW 45° OFFSETR
DUCT DROP IN DIRECTION OF AIR FLOW 45° OFFSETD
FLEXIBLE DUCT CONNECTION
AIR TURNING VANES
FIRE DAMPER AND CONFIGURATION TYPEBE
EXISTING FIRE DAMPERB
SMOKE DAMPERSE
EXISTING SMOKE DAMPERS
COMBINATION SMOKE/FIRE DAMPER AND CONFIGURATION TYPES B
E EEXST. COMBINATION SMOKE/FIRE DAMPER AND CONFIG. TYPES B
MOTOR OPERATED DAMPER (OPPOSED)M
MOTOR OPERATED DAMPER (PARALLEL)M
TDUCT TEMPERATURE SENSOR
DUCT HUMIDITY SENSOR
DUCT HUMIDITY HIGH LIMIT SENSORL
DUCT AIR FLOW SENSORF
DUCT STATIC PRESSURE SENSOR
DOUBLE WALL DUCT WITH 1" INSULATION PERFORATED LINER
MEDIUM PRESSURE CONICAL LOW LOSS DUCT TEE
HVAC LEGEND
DEMOLITION OF DUCTWORK, PIPING, EQUIPMENT ETC.
EXISTING TO REMAIN
NEW WORK
(P-1)E EXISTING EQUIPMENT TAG
SINGLE LINE DUCT TRANSITION
RETURN, EXHAUST AND OR RELIEF AIR RISE
SUPPLY AND OR OUTSIDE AIR RISE
RETURN, EXHAUST AND OR RELIEF AIR DROP
LOW PRESSURE BELL MOUTH WITH LOCKING QUADRANT DAMPER
SUPPLY AND OR OUTSIDE AIR DUCT DROP
T THERMOSTAT PNEUMATIC - MOUNTING HEIGHT 48"
CARBON MONOXIDE SENSOR
P SPACE PRESSURE SENSOR
2-WAY SUPPLY DIFFUSER
AIR TRANSFER ASSEMBLY
(ALL MAY NOT APPLY)
CEILING MOUNTED AIR DEVICE, R1- AIR DEVICE DESIGNATION.REFER TO SCHEDULE. 22"x22" NECK SIZE, 1,200 REQUIRED CFM.DUCT SIZE SAME AS NECK SIZE UNLESS INDICATED OTHERWISE.
R1-22"x22"1200
CEILING MOUNTED AIR DEVICE, E1- AIR DEVICE DESIGNATION.REFER TO SCHEDULE. 22"x22" NECK SIZE, 1,200 REQUIRED CFM.DUCT SIZE SAME AS NECK SIZE UNLESS INDICATED OTHERWISE.
E1-22"x22"1200
REFRIGERATION MONITORING SYSTEM ALARM DEVICE
LINED DUCTWORK
HVAC LEGEND
TRIPLE DUTY VALVE
GLOBE VALVE
SOLENOID VALVES
OS&Y VALVE
PRESSURE REDUCING VALVE
3/4" NPT PETES PLUG
UNION
METER
S WATER TEMPERATURE SENSOR
A AUTOMATIC AIR VENT WITH SHUTOFF COCK, VENT TO DRAIN
M MANUAL AIR VENT WITH SHUTOFF COCK
THERMOSTATIC AIR VENTT
THERMOMETERT
PP PRESSURE GAUGE WITH SHUTOFF COCK SNUBBERREQUIRED FOR STEAM SERVICE
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
CHECK VALVE
COMBINATION BALANCING/SHUTOFF VALVE
SHUTOFF/ISOLATION VALVE
STRAINER WITH BLOW DOWN
CLEAN OUTCOCO
PIPE RISE
PIPE DROP
PIPE CAP
VENTURI FLOW METER
ECCENTRIC PIPE REDUCER
CONCENTRIC PIPE REDUCER
PIPE FLANGE
VACUUM BREAKERVB
FLOW SWITCHFS
FLOW CONTROL VALVE
AUTOMATIC FLOW CONTROL VALVE WITH SHUTOFFA
NEEDLE VALVE
CIRCUIT SETTER
PLUG VALVE
BUTTERFLY VALVE
BALL VALVE
FILL VALVE
PRESSURE RELIEF VALVE WITH INDICATED SETTING30
F&T TRAP
BUCKET TRAP
DIRECTION OF FLOW
PITCH DOWN
PRESSURE DIFFERENTIAL SWITCH WITH SHUTOFF COCKP
PIPE EXPANSION JOINT
PIPE GUIDE
PIPE ANCHOR
VALVE IN RISER
PRE ENGINEERED EXPANSION LOOP. SEE SPECIFICATIONS
PIPE TEE UP
PIPE TEE DOWN
(ALL MAY NOT APPLY)
VARIABLE SPEED PUMPING DIFFENTIAL PRESSURE SENSOR
FLEXIBLE CONNECTOR
HVAC LEGEND
(LPR)E EXISTING LOW PRESSURE RETURN
LPR LOW PRESSURE RETURN
(MPR)E EXISTING MEDIUM PRESSURE RETURN
MPR MEDIUM PRESSURE RETURN
EXISTING HIGH PRESSURE RETURN(HPR)E
HIGH PRESSURE RETURNHPR
REFRIGERANT DISCHARGERD
REFRIGERANT LIQUIDRL
REFRIGERANT HOT GAS BYPASS LINERHGBP
MAKE UP WATERMUW
EXISTING MAKE UP WATER(MUW)E
HOT WATER SUPPLYHWS
EXISTING HOT WATER SUPPLY(HWS)E
HOT WATER RETURNHWR
EXISTING HOT WATER RETURN(HWR)E
STEAM SUPPLY (VALUE INDICATES PRESSURE)15
EXISTING STEAM SUPPLY (VALUE INDICATES PRESSURE)(15)E
(C)E EXISTING STEAM CONDENSATE (GRAVITY RETURN)
C STEAM CONDENSATE (GRAVITY RETURN)
(CPD)E EXISTING PUMPED CONDENSATE
CPD PUMPED CONDENSATE
CHILLED WATER SUPPLYCWS
EXISTING CHILLED WATER SUPPLY(CWS)E
CHILLED WATER RETURNCWR
EXISTING CHILLED WATER RETURN(CWR)E
EXISTING CONDENSER WATER SUPPLY(CS)E
CONDENSER WATER RETURNCR
EXISTING CONDENSER WATER RETURN(CR)E
DRAIN PIPED
(ALL MAY NOT APPLY)
REFRIGERANT SUCTIONRS
CONDENSER WATER SUPPLYCS
T.- UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDEOF STRUCTURE OR SLAB, WITH SPACE FOR INSULATION WHERE REQUIRED INTHE SPECIFICATIONS.
U.- INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGESAND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
V.-PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMSMOUNTED GREATER THAN 7'-0" ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO7'-0" ABOVE FLOOR LEVEL.
W.-UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF
EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS (100 FEET OR MORE) TOPERMIT DISASSEMBLY FOR ALTERATIONS AND REPAIRS.
X.-ALL PIPING WORK AND DUCTWORK SHALL BE COORDINATED WITH ALLTRADES INVOLVED. OFFSETS IN PIPING AND DUCTS AROUND OBSTRUCTIONSSHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
Y.-CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS,VOLUME DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENTDRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALLNOT BE INTERPRETED AS THE EXTEND OF THE REQUIREMENTS FOR THESE ITEMS.
Z.-ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNALCLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FORDUCT LINING THICKNESS.
AA.- PROVIDE 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNINGVANES UNLESS OTHERWISE INDICATED. PROVIDE ACCESS DOORS UPSTREAM OFALL ELBOWS WITH TURNING VANES.
BB.- COORDINATE DIFFUSER, REGISTER AND GRILLE LOCATIONS WITHARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING AND OTHER CEILINGITEMS AND MAKE MINOR DUCT MODIFICATIONS TO SUIT.
CC.- PROVIDE MINIMUM 4" FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
(SUPPLY, RETURN AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANSAND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLECONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THEEQUIPMENT UNLESS OTHERWISE INDICATED.
DD.- UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THEUNDERSIDE OF STRUCTURE, WITH SPACE FOR INSULATION WHERE REQUIRED INTHE SPECIFICATIONS.
EE.- RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 7 FEET AND SHALL NOT BE USEDFOR 90 DEGREE BENDS.
FF.- PROVIDE ACCESS DO0RS IN DUCTWORK FOR ACCESS TO ALL SMOKEDETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, COILS AND
OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/ORINSPECTION.
GG.- SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICALCONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FORMOUNTING THE SMOKE DETECTOR IN THE DUCTWORK AS SHOWN ON THEDRAWINGS AND IN ACCORDANCE WITH MANUFACTURER'S PRINTEDINSTRUCTIONS.
HH.- CONTRACTOR TO PROVIDE FIRE STOPPING AT ALL RATED HORIZONTAL ANDVERTICAL ASSEMBLIES. CONTRACTOR SHALL NOT LEAVE OPENINGS UNPROTECTEDDURING THE CONSTRUCTION PERIOD EXCEPT FOR SHORT DURATIONS WHILE ITEMS AREBEING INSTALLED THROUGH OPENINGS
II.- ALL 12"x12" DIFFUSERS ARE TO BE INSTALLED IN CENTER OF CEILING TILE.
JJ.-ALL EXISTING HVAC EQUIPMENT, PIPING, AND DUCTWORK NOT SHOWN ONDRAWINGS IS TO BE REMOVED AS NECESSARY FOR COMLETION OF NEW WORK
(CONTRACTOR SHALL INCLUDE THIS COST IN BASE BID PRICE).
KK.-ALL EXISTING EQUIPMENT, PIPING,...ECT. THAT IS ABOVE CEILING THAT CONFLICTSWITH NEW DUCTWORK AND PIPING LAYOUT IS TO BE RELOCATED AS NECESSARY TO
ALLOW FOR NEW LAYOUT INSTALLATION (CONTRACTOR SHALL INCLUDE THIS COST IN
BASE BID PRICE).
LL.-FURNISH AND INSTALL ISOLATION VALVES AND PIPE CAPS IN PIPING AS REQUIREDFOR PHASING OF ALL WORK.
VRV SYSTEM BRANCH SELECTOR BOX
M500
HVAC LEGEND AND INDEX
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
REQ'D ACCY:
AIR DISTRIBUTION DEVICES
TAG DESCRIPTIONFINISH
E.C.L.CONSTRUCTION TYPE
ALUM. STEEL O.W.B.E. BY ARCH.SURFACEMOUNTING TYPELAY-IN TYPEMODULE SIZE
R3
R2
R1
S3
S2
S1
RETURN
RETURN
RETURN
SUPPLY
SUPPLY
SUPPLY
24"x12"
24"x12"
24"x24"
AS NOTED
24"x24"
12"x12"
1,3
1,3
1,3
1
-
2SQUARE - PLAQUE
1. OPPOSED BLADE DAMPER2. 12"x12" TRIM RING, RAPID MOUNT3. DAMPER TO BE ACCESSIBLE FROM FACE OF GRILLE.
OWBE - OFF WHITE BAKED ENAMEL FINISH ECL - ETCHED CLEAR LACQUER FINISH
REQ'DACCY
E1 EXHAUST 24"x12" 1,3
REQ'D ACCESS.
UNIT NUMBER
AREA SERVED
UNIT CONFIG.
CFM - FUTURE
WHEEL DIA.
WHEEL TYPE
MOTOR H.P.
SENSIBLE CL'G
ENT. AIR TEMP.
LVG. AIR TEMP.
CFM
-
TYPE - PRE
P.D. IN. W.C.
SU
PP
LY F
AN
EX
HA
US
T F
AN
CO
OLI
NG
CO
ILF
ILT
ER
OUTSIDE AIR - CFM
DB/WB
DB/WB
CLEAN/DIRTY
MAX. AIR P.D. - IN. W.C.
REQ'D ACCESS.
CUSTOM AIR HANDLING UNITS
ROWS
WHEEL TYPE
MOTOR H.P.
WHEEL DIA.
CFM - FUTURE
REFRIGERANT
FACE AREA S.F.
MBH
(MIN.)
DOAS-1
SOUTH WING
6,700
MERV 8
6,800
-
1,2
-
4,400
EAST WING
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.INSTALL UNIT ON SPRING ISOLATIONFURNISHED BY UNIT MFR.
2.POWER IS TO BE 208/3/60, MCA 25.1, MOP 35.0
3.POWER IS TO BE 208/3/60, MCA 21.4, MOP 30.0.
- PERFORMANCE SHALL BE EQUAL OR SUPERIOR TO SCHEDULED VALUES.
-- --
- - - -
SMACNA
DUCT CONSTRUCTION/SEALING
MEDIUM VELOCITY SUPPLY
OUTSIDE AIR
-
RETURN / RELIEF
GENERAL EXHAUST
DUCT SYSTEM
LOW VELOCITY SUPPLY
-0.5"
-
-0.5"
-1"
+1"
+3"
SP CONST
-
C
C
C
-
-
-
-
B
A
SEAL CL
-
-
NOTES
NOTES:
1. 15 PSI STEAM IS SUPPLIEDTO CONTROL VALVE. SIZESTEAM CONTROL VALVEFOR 10 PSI PRESSUREDROP.
2. IFB=INTEGRAL FACE ANDBYPASS COIL
R4 RETURN AS NOTED 1,3
TOTAL SP./EXT. SP. -IN. W.G.
SQUARE - PLAQUE
SUPPLY GRILLE
LOUVERED FILTER GRILLE
LOUVERED FILTER GRILLE
EGGCRATE RETURN GRILLE
LOUVERED RETURN GRILLE
LOUVERED RETURN GRILLE
MFG. - -
MODEL -
DOAS-2
HORIZ. HORIZ. -
10
AF-PLENUM
20 INCH
5.3/2.0
5,500
5
2.82/1.75
FACE AREA
CAP'Y - MBH
ENT. AIR TEMP.
LVG. AIR TEMP.
CFM
MAX. AIR P.D. -
DESCRIPTION
RE
-HE
AT
CO
IL
IN. W.C.
LB/HR
PRESSURE - PSISTEAM
-
IFB COIL IFB COIL
4,400
-
-
-
-
-
-
-
-
-
-
-
-
-
5
637
-
6,700
495
52/51
R410A
6
0.98
6,700
81/71
428
215
0.27/1.0
-
CONDENSING UNITS
REQ'D ACCESS.
- DISCONNECT BY ELECTRICAL CONTRACTOR
1. - COMPRESSOR TO BE MOUNTED ON RUBBER IN SHEAR ISOLATORS.2. - UNIT IS HEAT RECOVERY CONDENSING UNIT WITH INVERTER. INCLUDE R410A REFRIGERANT, HEATING OPERATION TO 0° F,VFD CONTROLLED OUTDOOR FAN MOTOR, CONTINUOUS HEATING DURING DEFROST, MANIFOLDING KIT3. - SINGLE POINT POWER CONNECTION.4. - CONDENSING UNIT IS A COMBINATION OF TWO CONDENSING UNITS. EACH INDIVIDUAL CONDENSING UNIT REQUIRES ANELECTRICAL FEED, WIRE PER MANUFACTUERS INSTRUCTIONS.5. - INCLUDE; HOT GAS BYPASS LINE, FIELD OUTLET CONNECTION, 4 SCROLL COMPRESSORS, 4-STEP CAPACITY CONTROL,BUILT-IN HAIL PROTECTION, PHASE FAILURE, GROUND FAULT PROTECTION, R410A REFRIGERANT.
6. - INSTALL UNIT ON VIBRATION ISOLATION PADS (MIN. 1/4" DEFLECTION) FURNISHED BY UNIT MANUFACTURER.
TAGREFRIG. LINE SIZES
SERVICELIQUID COOLINGBAL. TUBE HEATING
CAPACITY (BTU/Hr) REQ'DACCESS.SUCT.TEMP
ELECTRICAL DATAVOLTS PHASE MOCP
REFRIG. NO. OF CIRCUITSMCA
- R-410A REFRIGERANT
DISCH. SUCTION
- COOLING CAPACITY BASED ON INDOOR CONDITIONS OF 80.0°F DB / 67.0°F WB AND OUTDOOR CONDITIONS OF 95.0°F DB- HEATING CAPACITY BASED ON INDOOR CONDITIONS OF 70.0°F DB AND OUTDOOR CONDITIONS OF 0.0°F DB / 0.0°F WB
E2 EXHAUST 12"x12" 1,3
CU-1
CU-2
CU-6
- -
3,500 -
-
MERV 8 -
4,400
1,3
-
-
AF-PLENUM
113
30
- -
0.22/1.0 -
-
-
-
AF-PLENUM
-
-
5.39/2.0
-
AF-PLENUM
-
7.5
-
16 INCH
-
20 INCH
-
52/51
R410A
6
4,400
81/70
280
146
-
-
-
-
-
-
-
-
WINTER EA
84 -
-
-
-
PLA
TE
HE
AT
EX
CH
AN
GE
R
90/73
41.0
0.6DBWINTER LADBSUMMER EA
-
EX
HA
US
T A
IR
93/74
0
-
-
-
DB/WB
81/71SUMMER LADB/WB 82/71 -
OU
TS
IDE
AIR
WINTER EADBWINTER LADBSUMMER EADBSUMMER LADB
-
-
-
-
68
30
75
86
70
31
75
-
-
-
-
SOUTH WING THIRD FLOORSOUTH WINGFIRST FLOOR
CU-5
1
1
2
2
208 3
3,5,6
3,5,6
3
3
-
-
175
175
43.0
43.0
-
-275,000
MFR. TO SIZE
MFR. TO SIZE
MFR. TO SIZE
MFR. TO SIZE
REQ'D ACCESS
ELECTRIC HEATING UNITS
TAG DESCRIPTION HEATINGKW (MIN)MBH KW (MAX)
ELEC SERVICEAMP VOLT PHASE
SERVICE CFM
-
-
-
-
-
-
CUH-1
-
-
-
-
-
ELECT. CABINET UNIT HEATER
-
-
-
-
-
VESTIBULE
-
-
-
-
-
250
-
-
-
-
-
-
2
2
-
-
-
-
-
17
-
-
-
-
-
3
-
-
-
-
-
5
-
-
-
-
-
25
-
-
-
-
-
208
-
-
-
-
-
3
1. DUCT COLLAR FOR INLINE AIRFLOW (UNIT TO BE MOUNTED HORIZONTALLY,
BOTTOM IN/TOP OUT CONFIGURATION) , WALL-MOUNTED THERMOSTAT.PROVIDE VIBRATION ISOLATION PER SPEC SECTION 23 05 41.
2.FRONT INLET/TOP OUTLET CONFIGURATION. BUILT-IN THERMOSTAT.
- THREE (3) PHASE COIL LOADS SHALL BE DIVIDED EVENLY ACROSS EACH PHASE- ELEC SERVICE TO THREE (3) PHASE UNITS TO BE THREE (3) WIRE UNLESS NOTED
REQ'DACCESS
- VERIFY/COORDINATE CABINET DIMENSIONS MOUNTING AND RECESS REQUIREMENTSWITH ARCHITECTURAL DWGS PRIOR TO ORDERING
CUH-2 ELECT. CABINET UNIT HEATER VESTIBULE 250 17 3 5 25 3
- - - - - - - - -
CU-3 MFR. TO SIZEEAST WING THIRD FLOOR
DOAS-1SOUTH WING
DOAS-2EAST WING
11-
96,000 108,000
125
1,2,4,6
1,2,4,6
1,2,6
SUPPLY AIR
TYPE - FINAL
P.D. IN. W.C.
FIL
TE
R
CLEAN/DIRTY
FACE AREA S.F.
MERV 14
-
-
-
-
-
0.5/1.0
-
MERV 14 -
- -
0.44/1.0 -
SUPPLY AIR
P.D. IN. W.C.
FIL
TE
R
CLEAN/DIRTY
FACE AREA S.F.
-
-
-
-
-
0.21/1.0
-
0.21/1.0 -
TYPE - PREMERV 8 MERV 8 -EXHAUST AIR
DESCRIPTION PLEATED PANEL
PLEATED PANEL
--
DESCRIPTION -
DESCRIPTION PLEATEDPANEL
PLEATEDPANEL
--
- -
5
16 INCH
0.94
-
5
361
-
347
109
36
41.1
- - -
1.- LOUVER SIZES SHOWN ARE FOR BIDDING PURPOSES ONLY. CONTRACTORSHALL FIELD-VERIFY EXISTING OPENING SIZES AND SIZE LOUVERS TO FIT INEXISTING OPENINGS.2.- CONTRACTOR SHALL PROVIDE INSULATED SHEETMETAL PLENUM BEHINDALL LOUVERS.
3.- PROVIDE 1-1/4" DRAIN PIPING FROM ALL INTAKE LOUVERS. ROUTE TONEAREST FLOOR DRAIN.4.- COLOR OF LOUVER SELECTED BY THE ARCHITECT.5.- COORDINATE LOCATION AND SIZE WITH ARCHITECT AND OTHERCONTRACTORS.
LOUVERS
NOTES (APPLIES TO ALL LOUVERS)
TAGH
SIZEWDP
SERVICE NOTES
ALL
F.A.SQ.FT.IN
P.D.CFM
L-1
L-2
L-3
L-4
L-5
L-6
340030"INTAKE
48"ØINTAKE 3400
EXHAUST 48"Ø 6600
42"ØINTAKE
42"ØINTAKE
2200
2200
EXHAUST 48"Ø 4200
60"
ALL
ALL
ALL
ALL
ALL
4"
4"
4"
4"
4"
4"
-
-
-
-
-
0.06
0.10
0.25
0.05
0.12
0.05
4.81
4.81
4.81
6.28
6.28
6.25
160430,000 208
208
208
-
E3 EXHAUST AS NOTED EGGCRATE RETURN GRILLE
EGGCRATE RETURN GRILLE
4543.8
REQ'D ACCESS
DESCRIPTIONTAG GPMELECTRICAL DATA
VOLTAGE
CONDENSATE RECEIVER PUMP
RPMHP PHASE
CP-1 CONDENSATE RETURN 1,2,3,4,5120 1
1. INLET BASKET STRAINER2. DISCHARGE PRESSURE GAUGE3. MECHANICAL ALTERNATOR (FLOW SWITCH INSIDE RECEIVER)4. PUMP SUCTION ISOLATION VALVES
REQ'DACCESS
INLETSIZEPSI
NOTES
1. PUMP SHALL BE DUPLEX.
SIZE(IN) CAP(GAL)
18 20 3500 1" 2" 25 (2) 1/3
PRV-4
-
-
-
-
-
PRV-1
60
-
-
-
-
-
125
15
-
-
-
-
-
60
1609
-
-
-
-
-
3410
25
-
-
-
-
-
-
1,2
-
-
-
-
-
1,2,3
1. INCLUDE EXTERNAL STEAM PILOT CAPABLE OF +/- 1% ACCURACY.2. NOISE LEVEL TO BE MAX. 85 DB.
3. ADDITIONAL LOAD OF 523 LBS/HR ADDED TO THIS PRV STATION TO PICK UP THE LOAD OF A FUTURE DOAS-3 UNIT FOR THE WEST WING.
TAG
REQ'D ACCESS
STEAM PRESSURE REDUCING VALVE AND RELIEF VALVE
-
-
-
-
-
1-1/2
1-1/2
-
-
-
-
-
SPENCE
-
-
-
-
-
E
SPENCE
MFR MODEL
E
-
-
-
-
-
1856
-
-
-
-
-
-
2
-
-
-
-
-
-
12.60
14.28
STEAM PRESSURE REDUCING VALVE RELIEF VALVE
INLET PRESSURE(PSI)
OUTLET PRESS.(PSI)
CAP'Y
lb/hr
VALVESIZE (IN)
REQUIREDCV
VALVESIZE (IN)
RELIEF PRESSURESETTING (PSI)
CAP'Y
lb/hrREQ'D
ACCESS
PRV-2 60 15 3410 252 E 3941426.70
PRV-3 125 60 1609 -1,2E --6.74
1,2,3
- - -- - - - - --
L-7 42"INTAKE 1500 ALL4" 0.04 3.5
5. PROVIDE VIBRATION ISOLATION ASRECOMMENDED BY UNITMANUFACTURER.
TOTAL SP./EXT. SP. -IN. W.G. 3.03/1.75
-
FIRE DAMPER NOTES
GENERAL NOTES DETAILS SHOW INSTALL. OF FIRE DAMPER IN WALL. FIRE DAMPERIN FLOOR SIMILAR. INSTALL. OF FIRE DAMPERS SHALL CONFORM TO NFPA 90A,SMACNA AND MFR'S INSTRUCTIONS. ALL FIRE DAMPERS TO BE DYNAMIC.
DETAIL NOTES1.- FIRE DAMPER SHALL BE FOLDED BLADE TYPE, EXCEPT AS NOTED. VERTICALMOUNT; GRAVITY DROP, HORIZONTAL MOUNT; SPRING LOADED TO CLOSE.TYPE "A" - BLADES STORED IN AIR STREAM.TYPE "B" - BLADES STORED OUT OF THE AIR STREAM.TYPE "C" - HIGH VELOCITY TYPE, BLADES STORED OUT OF THE AIR STREAM,RECTANGULAR, ROUND OR OVAL CONNECTION.
2.- DUCT/SLEEVE CONNECTION, BREAK AWAY TYPE.
3.- SHEET METAL SLEEVE, 16 GAUGE MIN. SAME MATERIAL AS DUCT EXCEPTGALVANIZED FOR FIBER GLASS DUCTBOARD.
4.- DUCT ACCESS PANEL. REFER TO SPECIFICATIONS.
5.- RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MIN. OVERLAP OFWALL OPENING. BOLT OR TACK WELD TO WALL SLEEVE AS PER SMACNA.
6.- 10 GAUGE WALL SLEEVE WITH 1/2" WIDE LEG AT ALL SIDES ON OPPOSITE SIDEOF DUCT CONNECTION TO OVERLAP WALL OPENING.
7.- HIGH VELOCITY DUCT COUPLING
TYPE "B"3" MIN.
DUCT
5
1
2
4
2
6
5
FIRE DAMPER - TYPE B 1
SCALE: NONE
FIRE RATED WALLOR PARTITION
DUCT EXTENSIONTOP OF DAMPER
FIRE DAMPER - TYPE B (AT FLOOR) 2
SCALE: NONE
DUCT
2
5
4
TYPE "B" 1
35
2
6
FIRE RATEDFLOOR
4
(IF DOOR ABOVE ISNOT ACCESSIBLE,INSTALL DOORBELOW)
3
SPENCE
SPENCE
REQ'D ACCESS.
UNIT NUMBER
AREA SERVED
UNIT CONFIG.
CFM
WHEEL DIA.
WHEEL TYPE
MOTOR H.P.
-
SU
PP
LY F
AN
OUTSIDE AIR - CFM
REQ'D ACCESS.
MODULAR AIR HANDLING UNITS
(MIN.)
AH-1
CORRIDOR
1500
100
-
1,2 -
-
-
-
-
-
-
-
-
-
-
1.INSTALL UNIT ON SPRING ISOLATIONFURNISHED BY UNIT MFR.
2.POWER IS TO BE 208/3/60
- PERFORMANCE SHALL BE EQUAL OR SUPERIOR TO SCHEDULED VALUES.
NOTES:
1. 15 PSI STEAM IS SUPPLIEDTO CONTROL VALVE. SIZESTEAM CONTROL VALVEFOR 10 PSI PRESSUREDROP.
2. IFB=INTEGRAL FACE ANDBYPASS COIL
TOTAL SP./EXT. SP. -IN. W.G.
- - -
- -
HORIZ.
1.5
AF CENT.
9.50
1.89/1.00
FACE AREA
CAP'Y - MBH
ENT. AIR TEMP.
LVG. AIR TEMP.
CFM
MAX. AIR P.D. -
DESCRIPTION
HE
AT
ING
CO
IL
IN. W.C.
LB/HR
PRESSURE - PSISTEAM
2.48 SF
IFB COIL -
-
-
-
-
-
-
-
-
5
88.57
0.26
1500
83.70
114
63
P.D. IN. W.C.
FIL
TE
R
CLEAN/DIRTY
FACE AREA S.F.
-
-
-
-
-
0.18/0.59
5.6
TYPE - FINAL MERV 8 - 2"
DESCRIPTION PLEATED PANEL
-
S4 SUPPLY 16"Ø SUPPLY GRILLE
CONNECTOR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
AH-1 DETAIL 19
SCALE: NONE
COMPONENTS
1 INLET OPENING (LxW):16 x 362 PANEL FILTER3 IFB STEAM COIL4 FAN5 OUTLET
UNIT WEIGHT 986 LBS
PLAN VIEW
ELEVATION VIEW
1
2
3
5
5
3
6
6
2
1
6 ACCESS SECTION
4
4
2. DIRECT EXPANSION COIL PACKAGE WITH FACTORY MOUNTED THERMAL EXPANSION VALVE AND EQUALIZING TUBE.
- COOLING CAPACITY BASED ON INDOOR CONDITIONS OF 80.0°F DB / 67.0°F WB AND OUTDOOR CONDITIONS OF 95.0°F DB
1. ALL TEMPERATURE SENSORS AND FC CONTROLS SHALL BE PROVIDED BY THE UNIT MANUFACTURER.
5. UL LISTED
3. R-I-S VIBRATION ISOLATORS.
REQ'D ACCESS.
TAG CFMTYPEHEATINGCOOLING
CAPACITY (MBH)
GASLIQUID
REFRIG. LINE SIZES
MOCPWATTPHASEVOLT
ELECTRICAL DATA
VRV FAN COIL UNITS - MASTER SCHEDULE
REQ'DACCESS
SERVED BY
4. PROVIDE (1) SOLENOID VALVE KIT PER DX FAN COIL.
6. PROVIDE FACTORY MOUNTED CONDENSATE PUMP FOR FC-4 THRU 8 ONLY.7. WASHABLE FILTER
FC-1FLOOR MOUNTED
CONSOLE UNITSEE DWGS FOR
ASSOC. CU280/210 12.0 13.5 1/4 1/2 208 1 79 15 ALL
- HEATING CAPACITY BASED ON INDOOR CONDITIONS OF 70.0°F DB AND OUTDOOR CONDITIONS OF 0°F DB / 0°F WB
FC-2FLOOR MOUNTED
CONSOLE UNIT490/380 18.0 20.0 1/4 1/2 208 1 105 15 ALL
FC-3FLOOR MOUNTED
CONSOLE UNIT560/420 24.0 27.0 3/8 5/8 208 1 108 15 ALL
SEE DWGS FORASSOC. CU
SEE DWGS FORASSOC. CU
FC-4DUCTED
CONCEALED UNIT 636/530 18.0 20.0 1/4 208 1 214 15SEE DWGS FOR
ASSOC. CU ALL 1/2
FC-5DUCTED
CONCEALED UNIT 688/565 24.0 27.0 3/8 208 1 230 15SEE DWGS FOR
ASSOC. CU ALL5/8
FC-6DUCTED
CONCEALED UNIT 883/706 30.0 34.0 3/8 208 1 300 15SEE DWGS FOR
ASSOC. CU ALL5/8
FC-7DUCTED
CONCEALED UNIT 1130/812 36.0 40.0 3/8 208 1 375 15SEE DWGS FOR
ASSOC. CU ALL5/8
FC-8DUCTED
CONCEALED UNIT 1377/989 48.0 54.0 3/8 208 1 460 15SEE DWGS FOR
ASSOC. CU ALL5/8
CARTRIDGE CARTRIDGE
CU-4 MFR. TO SIZEEAST WING THIRD FLOOR 11- 1,2,4,6
24"
3
3
240,000 270,000
192,000 216,000
208
208 6041.328.8 40
6041.36041.3
120,000 135,000 208 3 5044.2
OA CFM -5270(CURRENT) 790 -
OA CFM -6700(FUTURE) 4400 -
EA CFM -3300(CURRENT) 640 -
EA CFM -5500(FUTURE) 3500
CFM - CURRENT 5,270
CFM - CURRENT 3,300 640
790
M501
HVAC SCHEDULES
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
LOW PRESSURE STEAM SUPPLY
SEDIMENT POCKET
F&T TRAP AND STRAINER
STRAINER
LOW PRESSURE CONDENSATERETURN.
AUTOMATIC CONTROL VALVE
VACUUM BREAKER
END OF MAIN DRIP
ECCENTRIC REDUCER
VB
SCALE: NONE
35
1 8
EMD
2
9
8
7
6
4
5
DOAS-1,2, AH-1 STEAM HEAT COIL
4 9 6 97
1
3
2
3
45° TEE
HOSE CLAMP (TYP. 2 PL)
CEILING PANEL
RETURN / EXHAUST GRILLE
5RETURN/EXHAUST CONNECTION
SCALE: NONE
EXTERNALINSULATION
RETURN / EXHAUSTAIR TRUNK DUCT (REF.PLAN FOR SIZE)
FLEX. DUCT (4'-0" MAX)EXTERNALLY INSULATED
SQUARE TO ROUNDADAPTOR
VOLUME DAMPER (IFDAMPER NOT PROVIDEDIN AIR DEVICE - SEEPLANS)TRANSITION
AS REQUIRED
HOSE CLAMPS (TYP)
FLEX DUCT (5'-0" MAX)EXTERNALLY INSULATED
SCALE: NONE
CEILING SUPPLY AIRDIFFUSER
SUPPLY AIR TRUNK REFER TO PLANS FOR SIZE
EXTERNALLY INSULATED DUCTWORK
CEILING DIFFUSER 4
SMOOTH RADIUSROUND ELBOW
FLEX TO BESAG FREE
BELLMOUTH FITTINGWITH MANUAL DAMPER
NOTE:1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.2. ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADESHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES.VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED ASRECOMMENDED BY SMACNA.
R>=W R>=1/3W R>=1/6W
STANDARDRADIUSELBOW
SHORT RADIUSELBOW WITHONE VANE
SHORT RADIUSELBOW WITHTWO VANES
DUCTWORK RADIUS ELBOWS
SCALE: NONE
2
7
6
5
4
3
2
1
34
6
1
7
5 5
LOW PRESSURE STEAM DRIP 6
SCALE: NONE
LOW PRESSURE STEAM MAIN(15-30 PSI)
"Y" STRAINER
F&T TRAP
STRAINER
SHUTOFF VALVE
COLLECTING POCKET ANDDIRT LEG SAME SIZE AS MAIN
LENGTH FROM INVERT OF
MAIN TO DRIP PIPE, 1 1/2 xMAIN PIPE DIA., 8"MINIMUM
1VRF FAN COIL BRANCH SELECTOR
SCALE: NONE
TO DX FAN COIL
TO OUTDOOR CONDENSOR
1
SHUT OFF BALL VALVE WITHINTEGRAL REFRIGERANTMAINTENANCE PORTS. TYP.
2
33
2 2 2
1
1
BRANCH SELECTOR4
4LIQUID LINE5
SUCTION LINE6
DISCHARGE LINE7
5 67
5
6
SHUT-OFF VALVE
BLOW DOWN5
STRAINER
CHECK VALVE
4
3
2
1
120H
1231
45
H= 10"
HIGH PRESSURE STEAM DRIP 7
SCALE: NONE
HPR
HPR THERMO-DYNAMICSTEAM TRAP
DOAS-2 DETAIL 15
SCALE: NONE
13
1
2 3
4 5 6 7
8
9
10
11
12
4 5 6 7
8
11
12
PLAN VIEW
ELEVATION VIEW
263"
77
"5
9"
6"
COMPONENTS1 INLET
(LxW):15 x 362 PANEL FILTER3 CARTRIDGE FILTER4 HEAT EXCHANGER5 DX COIL6 IFB STEAM COIL7 FAN8 OUTLET
(LxW):21 5/8 x 249 INLET
(LxW):14 x 3610 PANEL FILTER11 FAN12 OUTLET
(LxW):21 5/8 x 2413 CONTROL PANEL
UNIT WEIGHT 8,100 LBS
CLEARANCES:ACCCESS DOORS - 26 in
STEAM CONNECTIONS TO DOMESTIC WATER HEATER 8
CONTROL VALVE BYMANUFACTURER OF DOMESTICWATER HEATER,
FLOAT & THERMOSTATICTRAP ASSEMBLY
GRAVITY STEAM CONDENSATERETURN
DIELECTRIC FITTING
SCALE POCKET
STEAM SUPPLY
DOMESTIC WATER HEATER
1800 LB/HR @15 PSI STEAM
TRAP OR ORIFICED UNIONFITTING FURNISHED BYMANUFACTURER OF DOMESTICWATER HEATER, SEE PLUMBINGDWGS.
FLOOR
NOTES:
1. VERTICAL COIL TYPE DOMESTIC WATERHEATER IS SHOWN.
2. SEE PLUMBING DRAWINGS FOR PIPINGCONNECTIONS.
3. INSTALL ALL PIPING PER WATER HEATERMANUFACTURERS RECOMMENDATIONS.
LPS
DCW
DHWR
13CONDENSATE PUMP DETAIL
2"
2"
P
V
P
VENT TO OUTDOORS
2"1"
CP-1P
R
1"
2" 1"
ROUTE TOFLOOR DRAIN
TO LPR MAINALONG WALL
FROM DOM. HWHEATERS
9SAFETY VALVE DETAIL
PROVIDE UNION UNLESSSAFETY VALVE HASFLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TOPRESSURE VESSEL OR PIPE
VENT PIPE TO BUILDINGEXTERIOR. (NOTES 1, 2)
PIPE THREADED INTOELBOW (SAME SIZE ASELBOW)
DRIP PAN ELBOW(SECTIONAL VIEW)
3/4" [20mm] DRAIN TOFLOOR DRAIN OR OPENSIGHT DRAIN (NOTE 4)
[25
mm
]
24" MAX.[610mm]
[76mm]
ELEVATION
NOTES
1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM ISNOT BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHODCONTAINED IN ANSI B31.1. POWER PIPING CODE, APPENDIX II.
2. VENT PIPE SHALL TERMINATE AT EXTERIOR OF BUILDING WITH 90° ELBOW DOWN.3. DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS
WHICH PERSONNEL MAY OCCUPY.4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
FLEXIBLE CONNECTOR
P
TAPER PIPE
12PRV-1 AND PRV-2 STEAM PRESS. REDUCING STATION
SCALE: NONE
P
PRESSUREGAUGE WITHCOCK ANDSIPHON LOOP
BY-PASS PIPEWITH GLOBEVALVE
9" LONG NIPPLE SCREWEDINTO DRIP PAN ELBOW &INSERTED INTO RISER PIPE.SEE SAFETY VALVE DETAILCONTROL TUBING
WITH NEEDLEVALVE SAFETY RELIEF VALVE @ 25 PSI
DRIP PAN ELBOW
FULL SIZE DIRT LEG & 3/4"STEAM MAIN DRIPASSEMBLY
3"
4"PRV-1
PIPE SAFETY VALVEDISCHARGE TOEXTERRIOR OF BUILDINGAND TERMINATE WITH90° EL DOWN.
P
PRV-2
125 PSI
15 PSI LPS
2-1/2"60 PSI MPS NOTE:
1. FURNISH AND INSTALL ALL PRVASSOCIATED TUBING AND PERMANUFACTURER'SRECOMMENDATIONS.
20" MIN. 40" MIN.80" MIN.
TO FIRST TURN
40" MIN.
DOAS-1,2/CU-5,6 DX COIL PIPING SCHEMATIC 10
SCALE: NONE
COIL #2
COIL #1
S
4
5
32 6
AIR HANDLER
1
7
NOTE:1. THIS DETAIL IS TO BE USED FOR BIDDING PURPOSES ONLY.SIZING OF REFRIGERATION SYSTEM PIPING/EQUIPMENT SHALLBE THE RESPONSIBILITY OF THE AH/CU MANUFACTUER.(CONTRACTOR SHALL INCLUDE IN HIS PRICE ALL ITEMS ASREQUIRED BY AH/CU MANUFACTURER.)2. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OFREFRIGERATION SYSTEM LAYOUT DONE BY AIR HANDLINGUNIT/CONDENSING MANUFACTURER.3. CONTRACTOR IS TO FURNISH AND INSTALL ALLREFRIGERATION SPECIALTIES AND ITEMS AS REQUIRED BYAH/CU MANUFACTURER.
CONDENSING UNIT
8RL
RHGBP
RS
RL
RHGBP
RS
S
RL
RHGBP
RS
RL
RHGBP
RS
TYP. DOAS-1 AND 2TYP. CU-5 AND 6
AUX SIDE CONNECTOR (INTRODUCES HOT GAS INTODISTRIBUTER
EXPANSION VALVE
SIGHT GLASS
SOLENOID VALVE
EQUALIZING LINE
FILTER/DRYER
HOT GAS BYPASS VALVE
HOT GAS BYPASS SOLENOID VALVE
1
2
3
4
5
6
7
8
2
3/16"
1/2" x 5-1/2" x 5-1/2" PLATE 3/16"
MC6x12.0 CHANNEL
CLEVIS HANGERS
4" SCHEDULE 40 STEEL PIPE
REFRIGERANT PIPING SUPPORT
SCALE: NONE
16
EXTERIOR
12" SONO-TUBE FORM 30" BELOWGRADE
1/2" x 8" x 8" PLATE W/ (2) 3/4"Ø x8" AB
SCALE: NONE
OUTDOOR EQUIPMENT PAD 17
FURNISH AND INSTALL OUTDOORCONCRETE EQUIPMENT PAD FOR ALLOUTDOOR EQUIPMENT
1'-0"
#5 @ 12' EW
(2 ) #5 CONTINUOUS
1'-
0"EQ
EQ
2'-
6"
MIN
GRADE
#4 W / 1'-8" LEGS@ 2'-0"
24
" M
IN.
NOTE: ADJUST SIZES OF SUPPORTSSHOWN ABOVE AS REQUIRED TOADEQUATLEY SUPPORT PIPING.
GRAVEL
DOAS-1 DETAIL 14
SCALE: NONE
13
1
2 3
4 5 6 7
8
9
10
11
12
282"
95
"
COMPONENTS
1 INLET(LxW):20 x 42
2 PANEL FILTER3 CARTRIDGE FILTER4 HEAT EXCHANGER5 DX COIL6 IFB STEAM COIL7 FAN8 OUTLET
(LxW):20 1/8 x 369 INLET
(LxW):16 x 4210 PANEL FILTER11 FAN12 OUTLET
(LxW):20 1/8 x 3613 CONTROL PANEL
UNIT WEIGHT 10,500 LBS
CLEARANCES:ACCCESS DOORS - 26 in
PLAN VIEW
4 5 6 7
8
11
12
ELEVATION VIEW
65
"
6"
P
TAPER PIPE
18PRV-3 AND PRV-4 STEAM PRESS. REDUCING STATION
SCALE: NONE
P
PRESSUREGAUGE WITHCOCK ANDSIPHON LOOP
BY-PASS PIPEWITH GLOBEVALVE
9" LONG NIPPLE SCREWEDINTO DRIP PAN ELBOW &INSERTED INTO RISER PIPE.SEE SAFETY VALVE DETAILCONTROL TUBING
WITH NEEDLEVALVE SAFETY RELIEF VALVE @ 25 PSI
DRIP PAN ELBOW
FULL SIZE DIRT LEG & 3/4"STEAM MAIN DRIPASSEMBLY
3"
2"PRV-3
PIPE SAFETY VALVEDISCHARGE TOEXTERRIOR OF BUILDINGAND TERMINATE WITH90° EL DOWN.
P
PRV-4
125 PSI HPS
15 PSI LPS
1-1/2"60 PSI MPS NOTE:
1. FURNISH AND INSTALL ALL PRVASSOCIATED TUBING AND PERMANUFACTURER'SRECOMMENDATIONS.
20" MIN. 40" MIN.80" MIN.
TO FIRST TURN
40" MIN.
POLYSULFIDE SEALANT
PIPE
PIPE SLEEVE
WALL LINE
PIPE DETAIL FOR VENT LINES 20
SCALE: NONE
PIPE JACKET &INSULATION
3/4" THICKINSULATION
SADDLE SUPPORTANCHOR TO EXISTING WALL
REDUCER REDUCERHPS
M502
HVACDETAILS
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
VARIABLE REFRIGERANT VOLUME SYSTEM INSTALLATION NOTES
1. ENTIRE VRV SYSTEM INCLUDING FAN COIL UNITS, BRANCH
SELECTOR BOXES, CONDENSING UNITS AND ALL CONTROLSSHALL BE MANUFACTURED BY ONE MANUFACTURER.
2. FOR CLARIFICATION PURPOSES ALL REFRIGERATION VALVES
AND SPECIALTIES ARE NOT SHOWN ON THE ABOVE SCHEMATIC.CONTRACTOR IS TO FURNISH AND INSTALL ALL VALVES,REFRIGERATION SPECIALTIES AND ACCESSORIES AS REQUIRED
BY VRV SYSTEM MANUFACTURER AND PROJECTSPECIFACATIONS.
3. PIPING LAYOUT MAY VARY FROM MANUFACTURER TOMANUFACTURER. CONTRACTOR SHALL INSTALL PER
MANUFACTURER RECOMMENDATIONS AND ALLREQUIREMENTS SHALL BE INCLUDED IN CONTRACTORS BIDPRICE.
bacnet gateway
L1, L2
I-TOUCH (WITH WEB
& PPD OPTIONS)
CU-2
CU-1
CU-3
CU-4
F1/F2
L1, L2
OUT F1/F2
OUT F1/F2
COUT F1/F2
OUT F1/F2
CU-1
115.0ft [6]
KHRP25A33T
3/8"x7/8"x3/4"
BS-14
7.0ft [3]
3/8"x5/8"x1/2"
FC-5
4.0ft [2]
3/8"x5/8"
30.0ft [4]
KHRP25A33T
3/8"x7/8"x3/4"
BS-15
3.0ft
3/8"x5/8"x1/2"
FC-4
24.0ft [3]
1/4"x1/2" *
5.0ft
KHRP25A33T
3/8"x7/8"x3/4"
BS-16
3.0ft
3/8"x5/8"x1/2"
FC-6
12.0ft [4]
3/8"x5/8"
17.0ft
KHRP25A22T
3/8"x3/4"x5/8"
BS-17
2.0ft
3/8"x5/8"x1/2"
FC-7
8.0ft [2]
3/8"x5/8"
BS-18
16.0ft [2]
3/8"x5/8"x1/2"
FC-4
C22.0ft [4]
1/4"x1/2" *
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
BS-14L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-5
L1, L2 1.8A 1ph
BRC1E71P1/P2
BS-15L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-4
L1, L2 1.6A 1ph
BRC1E71P1/P2
BS-16L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-6
L1, L2 2.3A 1ph
BRC1E71P1/P2
BS-17L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-7
L1, L2 2.9A 1ph
BRC1E71P1/P2
BS-18L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-4
L1, L2 1.6A 1ph
BRC1E71P1/P2
11A 1ph
REFRIGERANT PIPING SCHEMATIC - CU-1 - THIRD FLOOR CENTER CORE UNITS
WIRING SCHEMATIC - CU-1 - THIRD FLOOR CENTER CORE UNITS
CENTRALIZED CONTROL WIRING SCHEMATIC
CU-1
L1, L2, L3 20A 3ph
IN F1/F2OUT F1/F2
to centralized controller
REFRIGERANT PIPING SCHEMATIC - CU-2 - BASEMENT AND FIRST FLOOR UNITS
WIRING SCHEMATIC - CU-2 - BASEMENT AND FIRST FLOOR UNITS
CU-2
REYQ240PYDNR
REMQ120PYDNR REMQ120PYDNR
1/2"x1 1/8"x3/4" 1/2"x1 1/8"x3/4"
BHFP26P90U 3/4"
50.0ft [4]
KHRP25M73TU
5/8"x1 3/8"x1 1/8" *
BS-1
BSVQ36PVJU
75.0ft [1]
3/8"x5/8"x1/2"
FC-1
FXLQ12MVJU
18.0ft [2]
1/4"x1/2" *
35.0ft [4]
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
3.0ft [4]
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-2
BSVQ36PVJU
2.0ft [2]
3/8"x5/8"x1/2"
FC-5
FXMQ24PVJU
6.0ft [3]
3/8"x5/8"
11.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-3
BSVQ60PVJU
3.0ft
3/8"x5/8"x1/2"
FC-8
FXMQ48PVJU
6.0ft [4]
3/8"x5/8"
10.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-4
BSVQ36PVJU
2.0ft [1]
3/8"x5/8"x1/2"
FC-7
FXMQ36PVJU
12.0ft [2]
3/8"x5/8"
24.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-5
BSVQ36PVJU
4.0ft [1]
3/8"x5/8"x1/2"
FC-6
FXMQ30PVJU
8.0ft [2]
3/8"x5/8"
FC-6
FXMQ30PVJU
8.0ft [2]
3/8"x5/8"
14.0ft [4]
KHRP25M72TU
1/2"x1 1/8"x3/4"
BS-7
BSVQ36PVJU
2.0ft [1]
3/8"x5/8"x1/2"
FC-7
FXMQ36PVJU
12.0ft [2]
3/8"x5/8"
10.0ft
KHRP25A33T
3/8"x7/8"x3/4"
BS-8
BSVQ36PVJU
2.0ft [1]
3/8"x5/8"x1/2"
FC-4
FXMQ24PVJU
6.0ft [3]
3/8"x5/8"
8.0ft
KHRP25A22T
3/8"x3/4"x5/8"
BS-9
BSVQ36PVJU
4.0ft [1]
3/8"x5/8"x1/2"
FC-6
FXMQ30PVJU
3.0ft [4]
3/8"x5/8"
BS-10
BSVQ36PVJU
14.0ft [5]
3/8"x5/8"x1/2"
FC-5
FXMQ24PVJU
6.0ft [4]
3/8"x5/8"
30.0ft [2]
KHRP25A22T
3/8"x3/4"x5/8"
BS-43
BSVQ36PVJU
35.0ft [3]
3/8"x5/8"x1/2"
FC-4
FXMQ18PVJU
5.0ft
1/4"x1/2" *
40.0ft [4]
KHRP25A22T
3/8"x5/8"x1/2"
BS-11
BSVQ36PVJU
2.0ft [1]
3/8"x5/8"x1/2"
FC-4
FXMQ18PVJU
12.0ft [3]
1/4"x1/2" *
8.0ft
KHRP25A22T
3/8"x5/8"x1/2"
BS-12
BSVQ36PVJU
8.0ft [1]
3/8"x5/8"x1/2"
FC-1
FXLQ12MVJU
25.0ft [2]
1/4"x1/2" *
BS-13
BSVQ36PVJU
12.0ft [2]
3/8"x5/8"x1/2"
FC-2
FXLQ18MVJU
17.0ft [2]
1/4"x1/2" *
CU-2
REYQ240PYDNR
REMQ120PYDNR
REMQ120PYDNR
Q1/Q2
Q1/Q2
L1, L2, L3
21A 3ph
L1, L2, L3
21A 3ph
OUT F1/F2
IN F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
BS-1
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
FXLQ12MVJU
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-2
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-5
FXMQ24PVJU
L1, L2 1.8A 1ph
BRC1E71P1/P2
BS-3
BSVQ60PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-8
FXMQ48PVJU
L1, L2 3.4A 1ph
BRC1E71P1/P2
BS-4
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-7
FXMQ36PVJU
L1, L2 2.9A 1ph
BRC1E71P1/P2
BS-5
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-6
FXMQ30PVJU
L1, L2 2.3A 1ph
BRC1E71P1/P2
F1/F2IN F1/F2
FC-6
FXMQ30PVJU
L1, L2 2.3A 1ph
BRC1E71P1/P2
BS-7
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-7
FXMQ36PVJU
L1, L2 2.9A 1ph
BRC1E71P1/P2
BS-8
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-5
FXMQ24PVJU
L1, L2 1.8A 1ph
BRC1E71P1/P2
BS-9
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-6
FXMQ30PVJU
L1, L2 2.3A 1ph
BRC1E71P1/P2
BS-10
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-5
FXMQ24PVJU
L1, L2 1.8A 1ph
BRC1E71P1/P2
BS-43
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-4
FXMQ18PVJU
L1, L2 1.6A 1ph
BRC1E71P1/P2
BS-11
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-4
FXMQ18PVJU
L1, L2 1.6A 1ph
BRC1E71P1/P2
BS-12
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
FXLQ12MVJU
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-13
BSVQ36PVJU
L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-2
FXLQ18MVJU
L1, L2 0.6A 1ph
BRC1E71P1/P2
28A 1ph
OUT F1/F2
to centralized controller
M503
HVACSCHEMATICS
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
CU-3
3/8"x7/8"x3/4" 3/8"x7/8"x3/4"
BHFP26P90U 3/4"
120.0ft [8]
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-19
21.0ft
3/8"x5/8"x1/2"
FC-1
23.0ft [4]
1/4"x1/2" *
5.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-20
21.0ft
3/8"x5/8"x1/2"
FC-1
23.0ft [4]
1/4"x1/2" *
10.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-21
6.0ft
3/8"x5/8"x1/2"
FC-8
10.0ft [2]
3/8"x5/8"
8.0ft [4]
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-22
22.0ft
3/8"x5/8"x1/2"
FC-1
26.0ft [2]
1/4"x1/2" *
10.0ft
KHRP25M73TU
5/8"x1 1/8"x1 1/8"
BS-23
22.0ft
3/8"x5/8"x1/2"
FC_1
19.0ft [2]
1/4"x1/2" *
6.0ft
KHRP25M72TU
1/2"x1 1/8"x3/4"
BS-24
22.0ft
3/8"x5/8"x1/2"
FC-1
25.0ft [4]
1/4"x1/2" *
FC-8
46.0ft [2]
3/8"x5/8"
27.0ft
KHRP25A33T
3/8"x7/8"x3/4"
BS-26
22.0ft
3/8"x5/8"x1/2"
FC-1
19.0ft [2]
1/4"x1/2" *
10.0ft
KHRP25A33T
3/8"x7/8"x3/4"
BS-27
11.0ft
3/8"x5/8"x1/2"
FC-6
9.0ft [2]
3/8"x5/8"
FC-8
62.0ft [4]
3/8"x5/8"
CU-4
210.0ft [12]
KHRP25M72TU
5/8"x1 1/8"x3/4" *
BS-39
6.0ft
3/8"x5/8"x1/2"
FC-1
20.0ft [3]
1/4"x1/2" *
10.0ft
KHRP25M72TU
1/2"x1 1/8"x3/4"
BS-40
10.0ft
3/8"x5/8"x1/2"
FC-1
16.0ft [2]
1/4"x1/2" *
13.0ft
KHRP25M72TU
1/2"x1 1/8"x3/4"
BS-41
6.0ft [2]
3/8"x5/8"x1/2"
FC-8
5.0ft [3]
3/8"x5/8"
30.0ft
KHRP25A33T
3/8"x7/8"x3/4"
BS-42
15.0ft [2]
3/8"x5/8"x1/2"
FC-2
13.0ft [4]
1/4"x1/2" *
15.0ft [1]
KHRP25A22T
3/8"x3/4"x5/8"
BS-35
4.0ft [2]
3/8"x5/8"x1/2"
FC-3
20.0ft [4]
3/8"x5/8"
13.0ft
KHRP25A22T
3/8"x5/8"x1/2"
BS-36
4.0ft
3/8"x5/8"x1/2"
FC-1
12.0ft [2]
1/4"x1/2" *
4.0ft
KHRP25A22T
3/8"x5/8"x1/2"
BS-37
5.0ft
3/8"x5/8"x1/2"
FC-1
16.0ft [2]
1/4"x1/2" *
BS-38
21.0ft [2]
3/8"x5/8"x1/2"
FC-1
16.0ft [2]
1/4"x1/2" *
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
BS-19L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-20L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-21L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-8
L1, L2 3.4A 1ph
BRC1E71P1/P2
BS-22L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-23L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC_1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-24L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
F1/F2IN F1/F2
FC-8
L1, L2 3.4A 1ph
BRC1E71P1/P2
BS-26L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-27L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-6
L1, L2 2.3A 1ph
BRC1E71P1/P2
F1/F2
FC-8
L1, L2 3.4A 1ph
BRC1E71P1/P2
16A 1ph
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
OUT F1/F2
BS-39L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-40L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-41L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-8
L1, L2 3.4A 1ph
BRC1E71P1/P2
BS-42L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-2
L1, L2 0.6A 1ph
BRC1E71P1/P2
BS-35L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-3
L1, L2 0.6A 1ph
BRC1E71P1/P2
BS-36L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-37L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
BS-38L1, L2 0.1A 1ph
F1/F2IN F1/F2
FC-1
L1, L2 0.5A 1ph
BRC1E71P1/P2
7.9A 1phREFRIGERANT PIPING SCHEMATIC - CU-3 - THIRD FLOOR EAST UNITS
CU-3
REYQ192PAYD
Q1/Q2
Q1/Q2
L1, L2, L3
20A 3ph
L1, L2, L3
20A 3ph
IN F1/F2OUT F1/F2
to centralized controller
WIRING SCHEMATIC - CU-3 - THIRD FLOOR EAST UNITS
REFRIGERANT PIPING SCHEMATIC - CU-4 - THIRD FLOOR EAST UNITS
CU-4
L1, L2, L3 21A 3ph
IN F1/F2OUT F1/F2
to centralized controller
WIRING SCHEMATIC - CU-4 - THIRD FLOOR EAST UNITS
VARIABLE REFRIGERANT VOLUME SYSTEM INSTALLATION NOTES
1. ENTIRE VRV SYSTEM INCLUDING FAN COIL UNITS, BRANCH
SELECTOR BOXES, CONDENSING UNITS AND ALL CONTROLS
SHALL BE MANUFACTURED BY ONE MANUFACTURER.
2. FOR CLARIFICATION PURPOSES ALL REFRIGERATION VALVES
AND SPECIALTIES ARE NOT SHOWN ON THE ABOVE SCHEMATIC.
CONTRACTOR IS TO FURNISH AND INSTALL ALL VALVES,
REFRIGERATION SPECIALTIES AND ACCESSORIES AS REQUIRED
BY VRV SYSTEM MANUFACTURER AND PROJECT
SPECIFACATIONS.
3. PIPING LAYOUT MAY VARY FROM MANUFACTURER TO
MANUFACTURER. CONTRACTOR SHALL INSTALL PER
MANUFACTURER RECOMMENDATIONS AND ALL
REQUIREMENTS SHALL BE INCLUDED IN CONTRACTORS BID
PRICE.
IN F1/F2
M504
HVACSCHEMATICS
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
th inkchampl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098
SEQUENCE OF OPERATIONS
THE VARIABLE REFRIGERANT FLOW (VRF) SYSTEM SHALL CONSIST OF AN
OUTDOOR CONDENSING UNIT WITH VARIABLE SPEED COMPRESSOR(S) ANDMULTIPLE INDOOR FAN COILS. VRF CONTROL SYSTEM SHALL BE BY THE SAMEMANUFACTURER AS VRF SYSTEM. THE SYSTEM SHALL BE CONTROLLED ON AN
OCCUPIED/UNOCCUPIED TIME SCHEDULE AS DEFINED AT THE OPERATORWORKSTATION. THE VRF SYSTEM SHALL HAVE CENTRALIZED CONTROLLERS. THEBUILDING AUTOMATION SYSTEM SHALL INTERFACE TO THE VRF SYSTEMCONTROLLER TO ADJUST SETPOINTS, OCCUPY ZONES, AND MONITOR THESYSTEM.
THE VRF CONDENSING UNIT SHALL MODULATE TO MATCH THE LOAD OF THECONNECTED INDOOR UNITS.
OCCUPIED MODETHE INDIVIDUAL FAN COILS SHALL CYCLE THE FAN UPON A CALL FOR
COOLING OR HEATING. THE FAN COIL SHALL OPERATE AT REDUCED LOAD AND VARY THE REFRIGERANT FLOW TO FULL COOLING OR HEATING UNTIL THESPACE IS AT THE OCCUPIED COOLING OR HEATING SETPOINT. FAN COIL UNITCONTROLLER SHALL COMMUNICATE WITH THE BRANCH SELECTOR BOX TO
CONTROL THE MODE OF OPERATION (HEATING OR COOLING).
UNOCCUPIED MODETHE FAN AND DX COOLING COIL SHALL BE CYCLED TO MAINTAIN AN
INCREASED UNOCCUPIED SPACE TEMPERATURE SETPOINT.
IN, HEATING MODE, THE FAN AND DX COIL SHALL BE CYCLED TO MAINTAIN DECREASED UNOCCUPIED SPACE TEMPERATURE SETPOINT.
THE UNIT SHALL BE CONTROLLED ON ITS OWN OCCUPIED/UNOCCUPIED TIMESCHEDULE AS DEFINED AT THE OPERATOR WORKSTATION.
SYSTEM POINTS:TYPE DESCRIPTION QUANTITY
AI SPACE TEMPRATURE 1 (PER FAN COIL)
AD SPACE OCCUPIED SETPOINT 1 (PER FAN COIL)
AD SPACE UNOCCUPIED SETPOINT 1 (PER FAN COIL)
DO OCCUPIED COMMAND 1 (PER FAN COIL)
AO VRF CONDENSING UNIT COMMAND 1 (PER COND. UNIT)
AI VRF SYSTEM LOAD % 1 (PER COND. UNIT)
DI VRF CONDENSING UNIT STATUS 1 (PER COND. UNIT)
DI FAN COIL FAULT 1 (PER FAN COIL)
DI VRF CONDENSING UNIT FAULT 1 (PER COND. UNIT)
AIREXHAUST
LL-T
DA-2
EAT
DOAS-1 & 2 OPERATION
SEQUENCE OF OPERATIONS
SAFETIES - ALL CONTROLS SHALL INCORPORATE THE FOLLOWING HARDWIREDSAFETIES. THE FOLLOWING SAFETIES SHALL BE PROVEN TO BE OPERATIONALUPON FINAL CHECKOUT. LOW TEMPERATURE LIMIT "FREEZESTAT" SHALL STOPTHE AIR HANDLING UNIT FAN IF A TEMPERATURE BELOW 38 DEG F. IS DETECTED.SMOKE DETECTORS SHALL STOP THE AIR HANDLING UNIT FAN WHEN SMOKE ISDECTECTED.
MODE CONTROL - THE AIR HANDLING UNIT SHALL BE CAPABLE OF OPERATING INTHE FOLLOWING MODES: OCCUPIED, AND UNOCCUPIED MODES. THE UNITSHALL BE AUTOMATICALLY INTIATED THROUGH TIME-OF-DAY SCHEDULES
(APPLICATION PROGRAMS).
OCCUPIED MODE - THE SUPPLY AND EXHAUST FANS SHALL BE INDEXED TO START.THE TEMPERATURE CONTROLS SHALL FUNCTION AS SPECIFIED BELOW DURINGTHE OCCUPIED OPERATION.
UNOCCUPIED - THE AIR HANDLING UNIT SHALL BE DE-ENERGIZED. SEE BELOW FORDESCRIPTION OF DE-ENERGIZING AIR HANDLER.
FAN CONTROL - WHENEVER THE UNIT IS INDEXED TO START, THE FOLLOWINGSEQUENCE SHALL BE EXECUTED: THE DDC SYSTEM SHALL ENABLE THE ELECTRICRELAY. THIS RELAY SHALL OPEN THE OUTSIDE AND EXHAUST DAMPERS. UPONCONFIRMATION OF THE OUTSIDE AIR DAMPER BEING FULLY OPEN, ASINDICATED BY ELECTRIC END SWITCH, THE SUPPLY AND EXHAUST FANS SHALL BESTARTED. ONCE THE FAN STATUS HAS BEEN PROVEN, THE DISCHARGE AIRCONTROL SHALL BE ENABLED. WHENEVER THE UNIT IS DE-ENERGIZED, DUE TOEITHER A SCHEDULED SHUTDOWN OR A SAFETY TRIP, THE FOLLOWINGSEQUENCE SHALL BE EXECUTED: THE SUPPLY AND EXHAUST FANS SHALL STOP.THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL FULLY CLOSE. THE DXCOOLING SHALL BE DISABLED. THE REHEAT COIL VALVE SHALL REMAIN UNDERCONTROL. IF THE LOW TEMPERATURE LIMIT SAFETY "FREEZESTAT" HASTRIPPED, THE HEATING COIL VALVE SHALL FULLY OPEN TO THE COIL. IF EITHERFAN IS ENABLED BY THE MANUAL SWITCH AT THE DRIVE, THE ASSOCIATEDDAMPERS SHALL OPEN TO ALLOW FAN OPERATION.
REHEAT CONTROL -IF THE OUTSIDE AIR TEMPERATURE IS AT OR ABOVE 40 DEG F. THE FOLLOWING
SHALL OCCUR: THE FACE AND BYPASS DAMPER SHALL BE POSITIONED TOALLOW FULL AIR FLOW THROUGH THE FACE OF THE STEAM COIL. THEDISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED THROUGH THEMODULATION OF THE STEAM OR DX COOLING IN SEQUENCE.
IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40 DEG F. THE FOLLOWING SHALLOCCUR: THE STEAM VALVE SHALL BE OPEN TO PROVIDE FULL STEAM FLOWTHROUGH THE STEAM COIL. THE DISCHARGE AIR TEMPERATURE SHALL BEMAINTAINED THROUGH THE MODULATION OF THE FACE AND BYPASS DAMPERSTO MAINTAIN SETPOINT.
DOAS-1 & 2 CONTROLLER POINTS
TAG TYPE NOTES
DP-1
DA-1
EHXT
OAT
DI
DO
AI
AI
OUTSIDE
HEAT EXCHANGER ENT
OUTSIDE AIR
-
-
-
-
DESCRIPTION
TYPE: AI - ANALOG INPUT AO - ANALOG OUTPUT DI - DIGITAL INPUT DO - DIGITAL OUTPUT PI - PULSED INPUT
FEATURES:D - DISPLAYED ON WORKSTATION GRAPHICS
M - MODIFIED/OVERRIDDEN FROM WORKSTATION GRAPHICSA - ALARMS AT WORKSTATION
L - LOGGED/TRENDED AT WORKSTATIONS - TIME SCHEDULED AT WORKSTATIONG - GLOBALLY SHARED TO ALL CONTROLLERS
QTY
HE-1 AI DISCHARGE AIR -
PRE-FILTER DIFF.
FEATURESD M A L S G
1
1
1
1
1
EF-C DOFAN START/STOP
-1
DAMPER CONTROL
TEMPERATURE
TEMPERATURE
HUMIDITY SENSOR
PRESSURE
COMMAND
X
X
X
X
X
X
-
X
-
-
-
X
X
-
-
-
X
-
-
-
X
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
SF-C DO FAN START/STOP -1COMMAND X X - - - -
SF
EF
DOAS-1 & 2 OPERATION
SEQUENCE OF OPERATIONS (PART 2)
HEAT RECOVERY CONTROL - HEAT RECOVERY IS FIXED PLATE TYPE WITH NOMOVABLE PART OR CONTROLS.
DISCHARGE AIR CONTROL - DURING THE OCCUPIED MODE THE UNIT SHALLMAINTAIN DISCHARGE AIR SETPOINT. THE HEATING AND COOLING CONTROLSSHALL BE MODULATED IN SEQUENCE TO MAINTAIN A DISCHARGE AIR
TEMPERATURE BETWEEN 68° AND 75° DRY BULB (ADJUSTABLE).
DEHUMIDIFACATION CONTROL - DURING THE OCCUPIED CYCLE, A SUPPLY AIRHUMIDITY SENSOR SHALL ENERGIZE THE COOLING SYSTEM AND REHEAT COIL TO
MAINTAIN MAXIMUM 60 PERCENT RELATIVE HUMIDITY (ADJUSTABLE).
C
(STM)
(COND)
ST
VA
-1
FB-D
C
C
VA-1 AO HEATING -1VALVE CONTROL X X - - - -
NO
- - - --- - - - - - -
DA-2 -1 X X - - - -
DAT
SD-1
SF-S
SF-C
EF-S DI FAN STATUS -1 X - - - - -
SF-S DI FAN STATUS -1 X - - - - -
CCT AI COOLING COIL -1TEMPERATURE X - - X - -
DAT AI DISCHARGE AIR -1TEMPERATURE X - - X - -
EAT AI EXHAUST AIR TEMP -1ENTERING UNIT X - - X - -
LHXT AI HEAT EXCHANGER LVG -1TEMPERATURE X - - X - -
AIREXHAUST
DP-2 DI FINAL-FILTER DIFF. -1PRESSURE X - X - - -
DP-3 DI PANEL-FILTER DIFF. -1PRESSURE X - X - - -
EF-S
EF-C
DP-1
OUTSIDEAIR
DA-1
HXLHXT
DP-2
CCT
LAT
DP-3
EXHAUSTDAMPER CONTROLDO
DX1-C
DX2-C
R-X
R-X
DX1-C DO DX COOLING -1STAGE 1 COMMAND X X - - - -
DX2-C DO DX COOLING -1STAGE 2 COMMAND X X - - - -
CONDENSING UNIT
SD-1 DI -SMOKE DETECTOR 1STATUS X - X - - -
OUTSIDE WALLOAT
WEATHER SHIELD
HE-1
DI LOW TEMPERATURE -1LIMIT SENSOR X - X - - -LL-T
LAT AI EXHAUST AIR TEMP -1LEAVING UNIT X - - X - -
DOAS-1 & 2 CONTROLS SCHEMATIC DIAGRAM
DISCHARGEAIR
VARIABLE REFRIGERANT FLOW -SYSTEM
EHXT
AHU-1 OPERATION
SEQUENCE OF OPERATIONS
SAFETIES - ALL CONTROLS SHALL INCORPORATE THE FOLLOWING HARDWIREDSAFETIES. THE FOLLOWING SAFETIES SHALL BE PROVEN TO BE OPERATIONALUPON FINAL CHECKOUT. LOW TEMPERATURE LIMIT "FREEZESTAT" SHALL STOPTHE AIR HANDLING UNIT FAN IF A TEMPERATURE BELOW 38 DEG F. IS DETECTED.SMOKE DETECTORS SHALL STOP THE AIR HANDLING UNIT FAN WHEN SMOKE ISDECTECTED.
MODE CONTROL - THE AIR HANDLING UNIT SHALL BE CAPABLE OF OPERATING INTHE FOLLOWING MODES: OCCUPIED, AND UNOCCUPIED MODES. THE UNITSHALL BE AUTOMATICALLY INTIATED THROUGH TIME-OF-DAY SCHEDULES
(APPLICATION PROGRAMS).
OCCUPIED MODE - THE SUPPLY SHALL BE INDEXED TO START. THE TEMPERATURECONTROLS SHALL FUNCTION AS SPECIFIED BELOW DURING THE OCCUPIEDOPERATION.
UNOCCUPIED - THE AIR HANDLING UNIT SHALL BE DE-ENERGIZED. SEE BELOW FORDESCRIPTION OF DE-ENERGIZING AIR HANDLER.
FAN CONTROL - WHENEVER THE UNIT IS INDEXED TO START, THE FOLLOWINGSEQUENCE SHALL BE EXECUTED: THE DDC SYSTEM SHALL ENABLE THE ELECTRICRELAY. THIS RELAY SHALL OPEN THE OUTSIDE AIR DAMPER. UPONCONFIRMATION OF THE OUTSIDE AIR DAMPER BEING FULLY OPEN, ASINDICATED BY ELECTRIC END SWITCH, THE SUPPLY FAN SHALL BE STARTED.ONCE THE FAN STATUS HAS BEEN PROVEN, THE ROOM TEMPERATURE CONTROLSHALL BE ENABLED. WHENEVER THE UNIT IS DE-ENERGIZED, DUE TO EITHER ASCHEDULED SHUTDOWN OR A SAFETY TRIP, THE FOLLOWING SEQUENCE SHALLBE EXECUTED: THE SUPPLY FAN SHALL STOP. THE OUTSIDE AIR DAMPER SHALLFULLY CLOSE. THE REHEAT COIL VALVE SHALL REMAIN UNDER CONTROL. IF THELOW TEMPERATURE LIMIT SAFETY "FREEZESTAT" HAS TRIPPED, THE HEATINGCOIL VALVE SHALL FULLY OPEN TO THE COIL. IF EITHER FAN IS ENABLED BY THEMANUAL SWITCH AT THE DRIVE, THE ASSOCIATED DAMPERS SHALL OPEN TOALLOW FAN OPERATION.
REHEAT CONTROL -IF THE OUTSIDE AIR TEMPERATURE IS AT OR ABOVE 40 DEG F. THE FOLLOWING
SHALL OCCUR: THE FACE AND BYPASS DAMPER SHALL BE POSITIONED TOALLOW FULL AIR FLOW THROUGH THE FACE OF THE STEAM COIL. THE ROOMAIR TEMPERATURE SHALL BE MAINTAINED THROUGH THE MODULATION OF THESTEAM IN SEQUENCE.
IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40 DEG F. THE FOLLOWING SHALLOCCUR: THE STEAM VALVE SHALL BE OPEN TO PROVIDE FULL STEAM FLOWTHROUGH THE STEAM COIL. THE ROOM AIR TEMPERATURE SHALL BEMAINTAINED THROUGH THE MODULATION OF THE FACE AND BYPASS DAMPERSTO MAINTAIN SETPOINT.
ROOM TEMPERATURE CONTROL - DURING THE OCCUPIED MODE THE UNIT SHALLMAINTAIN ROOM TEMPERATURE SETPOINT CONTROLLED BY THERMOSTATLOCATED IN THE SPACE. THE HEATING CONTROLS SHALL BE MODULATED IN
SEQUENCE TO MAINTAIN ROOM SETPOINT (ADJUSTED). SETPOINT IS TO BEADJUSTABLE THROUGH CENTRAL DDC SYSTEM.
AIRRETURN
OUTSIDEAIR TO ASSOCIATED SPACES
DISCHARGE AIR
AH-1 CONTROLLER POINTS
TAG TYPE NOTES
TE-2
TE-1
AI
AI
SPACE
DISCHARGE AIR
-
-
DESCRIPTION
TYPE: AI - ANALOG INPUT AO - ANALOG OUTPUT DI - DIGITAL INPUT DO - DIGITAL OUTPUT PI - PULSED INPUT
FEATURES:D - DISPLAYED ON WORKSTATION GRAPHICS
M - MODIFIED/OVERRIDDEN FROM WORKSTATION GRAPHICSA - ALARMS AT WORKSTATION
L - LOGGED/TRENDED AT WORKSTATIONS - TIME SCHEDULED AT WORKSTATIONG - GLOBALLY SHARED TO ALL CONTROLLERS
QTYFEATURES
D M A L S G
1
1
TEMPERATURE
TEMPERATURE
X
X
-
-
-
-
X
X
-
-
-
-
SF-C DO FAN START/STOP -1COMMAND X X - - - -
SF
C
(STM)
(COND)
ST
VA
-1
VA-1 AO HEATING -1VALVE CONTROL X X - - - -
LL-T DI LOW TEMPERATURE -1LIMIT SENSOR X X - - - -
NO
R-X
SF-S
SF-C
SF-S DI -SUPPLY FAN 1STATUS X - X - - -
TE-1
TE-2
OAD-ES
OAD-C DO OUTSIDE AIR DAMPER -1COMMAND X X - - - -
OAD-ES DI -OUTSIDE AIR DAMPER 1END SWITCH STATUS X - X - - -
LL-T
OAD-C
M505
HVACVENTILATION
SCHEDULES ANDCONTROL
DIAGRAMS
DS
IC
NONE
DAYTON VAMC
RENOVATE
BUILDING 409
VA PROJECT
NO.552-10-256
02-21-2011
t h i n k c h a m pl in.com
424 East Fourth Street
Cincinnati, OH 45202
T 513.241.4474 F 513.241.0081
556-4098