pg plus-25/30/35/40 & 45 gas fired combination …...pg plus-25/30/35/40 & 45 gas fired...
TRANSCRIPT
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa-tion in order to gain warranty coverage.
When receiving the Delta Performance unit, any claims for damage or shortage in shipment must be filedimmediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
WARNING
* I N S * I N S TT AA LL LL AA TT I O N I O N AA N D M N D M AA I N I N TT E N E N AA N C E * N C E * M M AA N U N U AA LL
- Input from 100,000 to 199,000 Btu/hr -
NOTICE
2003-2 Manual PG PLUS11/2003
If the information in this manual is not followed exactly, a fire or explosion mayresult causing property damage, personal injury or death.
FOR YOUR SAFETY• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS- Do not try to light any appliance- Do not touch any electrical switch; do not use any phone in your building.- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or thegas supplier.
PG PLUS-25/30/35/40 & 45Gas Fired
Combination Heaters
Category IV Vented Appliance
The
CONFORMS TO�ANSI Z 21-10-3�CERTIFIED TO�
CGA CAN 1-4-3 M8590870
Table of Contents
i
PRODUCT AND SAFETY INFORMATION
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Product Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Operating Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Code Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION I - PRE-INSTALLATION ITEMS
Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Determining Product Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Boiler Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Recommended Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6Flooring and Foundation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Residential Garage Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SECTION II - COMBUSTION AIR AND VENTING
Combustion Air Contamination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Outside Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Air Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Methods of Accessing Combustion Air into a Space . . . . . . . . . . . . . . . . . 8-9Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Removal of an Existing Boiler from a Common Vent System . . . . . . . . . . 10Accessing Combustion Air Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION III - UNIT PREPARATION
Handling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Hydrostatic Pressure Test
Hydrostatic Test Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Hydrostatic Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-13Completion of Hydrostatic Test and Draining . . . . . . . . . . . . . . . . 13
SECTION IV - DOMESTIC PIPING
General Piping Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Domestic Supply Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Thermal Expansion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Water Hammer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Temperature / Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-15Thermostatic Mixing Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table of Contents
ii
U-Tube Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16Domestic Drain Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Multiple Units Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Storage Tank Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16TR/Smart Series Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Domestic Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-19
SECTION V - PRIMARY PIPING
General Piping RequirementsLow Water Cut-off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Backflow Preventer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Primary System Piping Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Expansion Tank and Makeup Water
Diaphragm (Bladder) Expansion Tank. . . . . . . . . . . . . . . . . . . . . . 20Closed-Type (Standard) Expansion Tank . . . . . . . . . . . . . . . . . . . . 20
Circulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Closet (Zero Clearance) Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Sizing Primary Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21System Piping - Zone Circulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21System Piping - Zone Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21System Piping - Radiant Heating with Mixing Valves . . . . . . . . . . . . . . . . 21-22System Piping - Multiple Units Installation. . . . . . . . . . . . . . . . . . . . . . . . 22Primary Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-26
SECTION VI - VENT / COMBUSTION AIR INSTALLATION
General Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Category IV Vent Termination - Guideline . . . . . . . . . . . . . . . . . . . . . . . . 27Category IV Vent Termination - Clearance . . . . . . . . . . . . . . . . . . . . . . . . 28Multiple Vent Terminations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Locatin the Combustion Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Venting Option - Non-Direct Vent / Vertical . . . . . . . . . . . . . . . . . . . . . . . 29Venting Option - Direct Vent / Vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Venting Option - Non-Direct Vent / Horizontal . . . . . . . . . . . . . . . . . . . . . 30Venting Option - Direct Vent / Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . 29Triangle Tube Thimble Box Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Excessive Horizontal Vent Runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vent Outlet Reducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vent Appliance Adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vent Condensate Tee. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Condensate Drain Tube. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
iii
Table of Contents
Determining Piping Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Venting Option Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
SECTION VII - GAS PIPING
Gas Supply Piping Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Natural Gas
Pipe sizing -Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Natural Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . . 38
Propane GasPipe Sizing - Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Propane Gas Supply Pressure Requirements . . . . . . . . . . . . . . . . . 39
SECTION VIII - INTERNAL WIRING
General Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Internal Control Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-42
SECTION IX - EXTERNAL WIRING
Installation Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Line Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Outdoor Temperature Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43External Control Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-46
SECTION X - START-UP PREPARATION
Check System and Domestic Water ChemistryWater pH Level 6.0 to 8.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Water Hardness Less Than 7 Grains . . . . . . . . . . . . . . . . . . . . . . . 47Chloride Concentration Less Than 80mg/L . . . . . . . . . . . . . . . . . . 47Chlorinated Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Flush Primary and Domestic System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Check and Test Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Use of Antifreeze in the Primary System . . . . . . . . . . . . . . . . . . . . . . . . . 48Filling the Inner (Domestic) Tank and System . . . . . . . . . . . . . . . . . . . . . 48Filling the Outer (Primary) Tank and System . . . . . . . . . . . . . . . . . . . . . . 48-49Check Low Water Cut-off Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Check for Gas Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Verify Correct Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
iv
Table of Contents
Verify Correct Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Check Thermostat Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
SECTION XI - START-UP PROCEDURES
Final Checks Before Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51PERFORMANCE PLUS Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51If PERFORMANCE PLUS Does Not Start Correctly . . . . . . . . . . . . . . . . 51Check the PERFORMANCE PLUS and System . . . . . . . . . . . . . . . . . . . . 51Start-Up / Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-53
SECTION XII - TEMPERATURE LIMITS
Setting Primary Thermostat Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Adjustment of Secondary Thermostat Limit . . . . . . . . . . . . . . . . . . . . . . . 54Setting the Thermostatic Mixing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
SECTION XIII - CHECK-OUT PROCEDURES
Check-out Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
SECTION XIV - INSTALLATION RECORD
Installation Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
SECTIONS XV - MAINTENANCE SCHEDULE
Service Technician - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Owner Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
SECTION XVI - MAINTENANCE PROCEDURES
Maintenance ProceduresReported Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Check Surrounding Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Inspect Burner Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Check System (Primary and Domestic) Piping . . . . . . . . . . . . . . . 59Check Combustion/Ventilation Air Operating . . . . . . . . . . . . . . . . 60Inspect Vent System and Combustion Air Piping . . . . . . . . . . . . . . 60Check Primary System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Check Domestic System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
v
Table of Contents
Check Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Check Boiler Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Check Temperature / Pressure Relief Valve . . . . . . . . . . . . . . . . . . 61Inspection of Ignition Electrode. . . . . . . . . . . . . . . . . . . . . . . . . . . 61Check Ignition Wiring and Ground Wiring . . . . . . . . . . . . . . . . . . 61Check Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Check Thermostat Limit Settings . . . . . . . . . . . . . . . . . . . . . . . . . 61Perform Start-Up and Checkout Procedure . . . . . . . . . . . . . . . . . . 61Check Burner Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Check Flame Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Check Combustion Levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Review with Owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
SECTION XVII - REPLACEMENT PARTS
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63-67
PRODUCT SPECIFICATIONS
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68-69
Product & Safety Information
1
Indicates the presence of a hazardoussituation which, if ignored, will resultin death, serious injury or substantialproperty damage.
Indicates a potentially hazardous situ-ation which, if ignored, can result indeath, serious injury or substantialproperty damage.
Indicates a potentially hazardous situ-ation which, if ignored, may result inminor injury or property damage.
Indicates special instructions on instal-lation, operation or maintenance,which are important to equipment butnot related to personal injury hazards.
Indicates recommendations made byTriangle Tube for the installers whichwill help to ensure optimum operationand longevity of the equipment
BEST PRACTICES
NOTICE
CAUTION
WARNING
DANGER
The following terms are used throughout this manual to bring attention to the presence ofpotential hazards or to important information concerning the product.
Triangle Tube reserves the right to modify the technical specifications and components ofits products without prior notice.
NOTICE
Product & Safety Information
2
Bacteria can develop in the domesticwater system if certain minimum watertemperatures are not maintained.
Water temperature over 125ºF can causesevere burns instantly or death fromscalds.
• Children, disabled and elderly are athighest risk of being scalded.
- Never leave them unattended in ornear shower, bathtub or sink.
- Never allow small children to use ahot water faucet or draw their ownbath.
• If any one using hot water in the buildingfits this description or codes require spe-cific water temperatures at hot waterfaucet, we recommend:a) ensure the factory installed thermosta-
tic mixing valve is working properly.b)to set the thermostatic mixing valve
for the lowest temperature which sat-isfies your hot water need.
.
Protection must be taken against excessivetemperature and pressure!
TO PROTECT AGAINST EXCESSIVETEMPERATURE AND PRESSURE
• Check if the Temperature andPressure (T&P) relief valve is in thelocation provided. (Domestic Water)
• Check if the 30 psi relief valve sup-plied is in the location provided.(Primary water)
• To avoid injury, install the reliefdevices to comply with local coderequirements.
CAUTION
DANGER
WARNING
HOT
BURN
3
Product & Safety Information
Do not use this appliance if any parthas been under water. Immediately calla qualified service technician to inspectthe appliance and to replace any part ofthe control system which has beenunder water.
WHAT TO DO IF YOU SMELL GAS- Do not try to light any appliance
- Do not touch any electrical switch; donot use any phone in your building.
- Immediately call your gas supplierfrom a neighbor’s phone. Follow thegas supplier’s instructions.
- If you cannot reach your gas suppli-er, call the fire department.
Installation and service must be per-formed by a qualified installer, serviceagency or the gas supplier.
Should overheating occur or the gassupply fails to shut off, turn OFF themanual gas control valve external tothe appliance.
To prevent damage to inner tank,installer must:
• Fill inner tank prior to outer tankduring start-up.
• Relieve primary system pressurebelow 15 psig prior to draininginner tank.
CAUTION
WARNING
DANGER
DANGER
Qualified Installer:
Prior to installing this product read allinstructions included in this manual.Perform all installation steps required in thismanual in the proper order given. Failure toadhere to the guidelines within this manualcan result in severe personal injury, death orsubstantial property damage.
Homeowner:
-This product should be maintained / ser-viced and inspected annually by a qual-ified service technician.
- This manual is intended for use by aqualified Installer/Service Technician.
Please reference the unit’s model num-ber and the serial number from the rat-ing label when inquiring about service ortroubleshooting.
Triangle Tube accepts no liability for anydamage resulting from incorrect instal-lation or from the use of components orfittings not specified by Triangle Tube.
NOTICE
NOTICEWARNING
4
Product & Safety Information
OPERATING RESTRICTIONS
• Maximum working pressure for inner(domestic water) tank is 150 psig.
• Maximum working pressure for outer(primary water) tank is 45 psig.
• Inner tank has factory installedTemperature & Pressure Relief Valvewith an AGA rating of 100,000 Btu/hrfor PG-25 and 200,000 Btu/hr for PG-30/35/40/45.
• Outer tank has a factory installed 30psig relief valve rated at 535,000 Btu/hr
• Electrical rating:120 V, 60 Hz, lessthan 12 amperes
• pH & chloride limits for the PERFOR-MANCE PLUS are:
- Chloride, less than 80 mg/l.- pH, 6.0 - 8.0.
Any water conditioning system must beinstalled and maintained in accordancewith manufacturer’s specifications.
• 180º Maximum operating temperature -primary side.
• 120º Maximum outlet/mixed tempera-ture - domestic side.
CODE RESTRICTIONS
Single wall heat exchanger in the PERFOR-MANCE PLUS complies with NationalStandard Plumbing Code, provided that:
- Outer tank water (including additives)is practically non-toxic, having toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products,
- Outer tank pressure is limited to maxi-mum 30 psig by approved relief valve.
Single wall heat exchangers are permitted underthe Uniform Plumbing code - Paragraph L3.2. ifthey satisfy all of the following requirements.
1. The heat transfer medium is potablewater or contains only substances whichare recognized as safe by the U.S. Foodand Drug Administration.
2. The pressure of the heat transfer mediumis maintained less than the normal mini-mum operating pressure of the potablewater system
3. The equipment is permanently labeledto indicate that only additives recog-nized as safe by the FDA shall be used inthe heat transfer medium.
Or, per Uniform Plumbing Code paragraph L3.3as follows:
Other heat exchanger designs may be permittedwhere approved by the Administrative Authority.
NOTICE
Pre-Installation Items
5
SECTION I - Pre-Installation Items
Code Compliance
This product must be installed in accor-dance to the following:
• All applicable local, state, national andprovincial codes, ordinances, regula-tions and laws.
• The National Fuel Gas Code NFPA54/ANSI Z332.1 - Latest edition.
• National Electric Code ANSI/NFPA 70.
• For installations in Canada -“InstallationCode for Gas Burning Equipment”CGA/B149.
Determining Product Location
Before locating the PERFORMANCE PLUScheck for convenient locations to:
- Domestic water supply piping
- Heating system piping
- Venting
- Gas supply piping
- Electrical service
Ensure the area chosen for the installation ofthe PERFORMANCE PLUS is free of anycombustible materials, gasoline and otherflammable liquids.
Failure to remove or maintain the areafree of combustible materials, gasolineand other flammable liquids or vaporscan result in severe personal injury,death or substantial property damage.
Ensure the PERFORMANCE PLUS and itscontrols are protected from dripping or spray-ing water during normal operation or service.
The PERFORMANCE PLUS should beinstalled in a location so that any waterleaking from the tank or piping connectionsor relief valves will not cause damage tothe area surrounding the unit or any lowerfloors in the structure.
- When such a location is unavoidable asuitable drain pan with adequatedrainage should be placed under theunit. The drain pan must not restrict theflow of combustion air to the unit.
Boiler Replacement
If the PERFORMANCE PLUS is replacing anexisting boiler / hot water heater system, thefollowing items should be checked and correct-ed prior to installation:
• Primary and domestic piping leaks andcorrosion.
• Improper location and sizing of theexpansion tank on the primary heatingloop.
• Improper sizing of the thermal expan-sion tank (if used) on the domestic sup-ply line.
• Vent condition and sizing.
Recommended Clearances
The PERFORMANCE PLUS is approved forzero clearance to combustibles, excluding thevent hood and vent piping.
Vent hood and vent piping - 2 inches fromcombustible materials unless otherwise statedby the vent pipe manufacturer.
Primary and domestic hot water piping - 1 inchfrom combustible material.
WARNING
Pre-Installation Items
To provide serviceability to the unit it isrecommended that the following clear-ances be maintained:
Top and vent hood area - 36 inches.
Front and burner area - 24 inches.
Rear and primary piping areas - 12inches.
When installing the PERFORMANCEPLUS in a confined space, sufficient airmust be provided for proper combustionand venting and to allow under normaloperating condition proper air flowaround the product to maintain ambienttemperatures within safe limits to com-ply with the National Fuel Gas CodeNFPA 54 - latest edition.
Flooring and Foundation
The PERFORMANCE PLUS is approved forinstallation on combustible floors, but never oncarpeting.
Do not install the PERFORMANCEPLUS on carpeting even with a metal orwood foundation base. Fire can resultcausing severe personal injury, death orsubstantial property damage.
Installer should provide a solid brick or con-crete foundation pad, at least 2 inches abovethe floor level if:
- There is a potential for the floor tobecome flooded. The height of thefoundation should be such to sufficient-ly elevate the unit.
- The floor is dirt, sand, gravel or otherloose material.
- The flooring is severely uneven orsloped.
The minimum foundation size required is 24inches x 23 inches.
Residential Garage Installations
When installing the PERFORMANCE PLUS ina residential garage the following special pre-cautions per NFPA 54/ANSI Z223.1 must betaken:
- Mount the unit with a minimum 18inches above the floor level of thegarage. Ensure the burner and ignitiondevices / controls are no less than 18inches above the floor level.
- Locate or protect the unit in a matterso it cannot be damaged by a movingvehicle.
WARNING
WARNING
BEST PRACTICES
6
Combustion Air and Venting
7
SECTION II - Combustion Air andVenting
Combustion Air Contamination
If the PERFORMANCE PLUS combus-tion air inlet is located in any area likelyto cause or contain contamination, or ifproducts, which would contaminate theair cannot be removed, the combustionair must be repiped and terminated to anoutside location. Contaminated combus-tion air will damage the unit and itsburner system, resulting in possiblesevere personal injury, death or substan-tial property damage.
Do not operate a PERFORMANCEPLUS if its combustion air inlet is takeninside in a laundry room or pool facility.These areas will always contain haz-ardous contaminants.
Pool and laundry products and commonhousehold and hobby products oftencontain fluorine or chlorine compounds.When these chemicals pass through theburner and vent system, they can formstrong acids. These acids can create cor-rosion of the outer tank, burner compo-nents and vent system, causing seriousdamage and presenting a possible threatof flue gas spillage or water leakage intothe surrounding area.
Please read the information listed below.If contaminating chemicals are locatednear the location of the combustion airinlet, the installer should pipe the com-bustion air inlet to an outside area perSECTION VI of this installation manual.
Potential contaminating products
- Spray cans containing chloro/fluorocar-bons
- Permanent Wave Solutions
- Chlorinated wax
- Chlorine - based swimming pool chem-icals / cleaners
- Calcium Chloride used for thawing ice
- Sodium Chloride used for water soften-ing
- Refrigerant leaks
- Paint or varnish removers
- Hydrochloric acid / muriatic acid
- Cements and glues
- Antistatic fabric softeners used inclothes dryers
- Chlorine-type bleaches, detergents, andcleaning solvents found in householdlaundry rooms
- Adhesives used to fasten building prod-ucts and other similar products
Areas likely to contain these products
- Dry cleaning / laundry areas and estab-lishments
- Beauty salons
- Metal fabrication shops
- Swimming pools and health spas
- Refrigeration Repair shops
- Photo processing plants
- Auto body shops
- Plastic manufacturing plants
- Furniture refinishing areas and estab-lishments
- New building construction
- Remodeling areas
- Garages with workshops
WARNING
WARNING
8
Combustion Air and Venting
Combustion Air Requirements
The PERFORMANCE PLUS can use insideair if no contaminants are present in the area ofinstallation. If contaminants are likely to bepresent in the area of installation, outside airmust be piped directly to the unit as referencedin Section VI Venting and Combustion AirPiping.
It is recommended to pipe combustionair directly from the outdoors to the unitas referenced in Section VI Venting andCombustion Air Piping.
Outside Combustion Air
Combustion air can be ducted directly from theoutside to the air inlet fitting of the PERFOR-MANCE PLUS using the following materials:
- PVC
- Galvanized metal vent
- Flexible metal vent
All seams and joints must be sealed withsealant or mechanical fasteners. Do not usetape as it is not considered a sealing material.
Air Openings
Air openings to the PERFORMANCE PLUSare always required even if the combustion air isobtained indoors or outdoors. These air open-ings provide ventilation to prevent overheatingof the PERFORMANCE PLUS and its controlas well as providing combustion air.
The air openings must be sized to handlethe requirements of all appliances and airmovers (exhaust fans, etc.) contained inthe same space using the same air supply.
Methods of Accessing Combustion Air Into ASpace
Indoor Combustion Air
The methods listed in this section foraccessing Indoor Combustion Airassume that the infiltration rate is ade-quate and not less than .40 ACH. Forinfiltration rates less than .40 ACH, ref-erence the NFPA 54 National Fuel GasCode for additional guidance.
Opening Size and Location
Openings used to connect indoor spaces shallbe sized and located in accordance with thefollowing:
- Combining spaces on the same story.Each opening shall have a minimumfree area of 1 sq. in./1000 Btu/hr of thetotal input rating of all gas utilizationequipment in the space, but not less than100 sq. inches. One opening shall com-mence within 12 inches of the top, andone opening shall commence within 12inches of the bottom of the enclosure.
- Combining spaces in different stories.The volumes of spaces in different sto-ries shall be considered as communicat-ing spaces where such spaces are con-nected by one or more openings indoors or floors having a total minimumfree area of 2 sq. in./1000 Btu/hr oftotal input rating of all gas utilizationequipment.
NOTICE
NOTICE
BEST PRACTICE
9
Combustion Air and Venting
Outdoor Combustion Air
Isolating the combustion appliance roomfrom the rest of the building and bring-ing in uncontaminated outside air forcombustion and ventilation is alwayspreferred.
Two Permanent Openings Method.
Two permanent openings, one commencingwithin 12 in. of the top and one commencingwithin 12 in. of the bottom of the enclosure,shall be provided. The openings shall commu-nicate directly, or by ducts, with the outdoorsor spaces that freely communicate with the out-doors, as follows:
- Where directly communicating with theoutdoors or where communication to theoutdoors is through vertical ducts, eachopening shall have a minimum free areaof 1 sq. in./4000 Btu/hr of total input rat-ing of all equipment in the enclosure.
- Where communicating with the out-doors is through horizontal ducts, eachopening shall have a minimum freearea of not less than 1 sq.in./2000Btu/hr of total input rating of all equip-ment in the enclosure.
One Permanent Opening Method.
One permanent opening, commencing within 12in. of the top of the enclosure, shall be provided.The equipment shall have clearances of at least 1inch from the sides and back and 6 in. from thefront of the appliance. The opening shall direct-ly communicate with the outdoors or shall com-municate through a vertical or horizontal duct tothe outdoors or spaces that freely communicatewith the outdoors and shall have a minimum freearea of the following:
- 1sq. in./3000 Btu/hr of the total inputrating of all equipment located in theenclosures, and
- Not less than the sum of the areas of allvent connectors in the space.
Combination of Indoor and OutdoorCombustion Air
Indoor Openings: Where used, openings con-necting the interior spaces shall comply withthe Indoor Combustion Air section on page 8.
Outdoor Opening(s) Location. Outdoor open-ing(s) shall be located in accordance with theOutdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s)shall be calculated in accordance with the fol-lowing:
- The ratio of the interior spaces shall bethe available volume of all communi-cating spaces divided by the requiredvolume.
- The outdoor size reduction factor shallbe 1 minus the ratio of interior spaces.
- The minimum size of outdoor open-ing(s) calculated in accordance with theabove outdoor air section multiplied bythe reduction factor. The minimumdimension of air openings shall not beless than 3 in.
Vent System
The PERFORMANCE PLUS is designedto vent as a Category IV appliance, whichrequires a special vent system.
Category IV Venting is described as a ventsystem that has a positive static pressureand a flue temperature that may causeexcessive condensate within the vent.
BEST PRACTICE
10
Combustion Air and Venting
Do not install the PERFORMANCEPLUS into a common vent with other gasappliances.. This may cause flue gasspillage or appliance malfunction, result-ing in possible severe personal injury,death or substantial property damage.
Removal of an Existing Boiler from aCommon Vent System
For installations in which the PERFOR-MANCE PLUS is replacing an existingboiler / hot water heater system, whichwas connected to a common vent systemwith other appliances, the following stepsshall be conducted with each remainingappliance connected to the common vent-ing system:
1. Any unused openings in the commonventing system must be sealed.
2. A visual inspection of the venting sys-tem must be conducted for proper siz-ing and horizontal pitch. The inspec-tion should ensure no blockage orrestriction is within the vent system,and there is no leakage, corrosion orother items, which could cause anunsafe condition.
3. To adequately test the venting system,close all exterior doors and windowsand all doors between the area contain-ing the remaining appliances connectedto the common vent system and otherareas of the building. Turn on anyclothes dryers and any other gas appli-ance not connected to the common ventsystem. Turn on all exhaust fans, i.e.range hoods and bathroom exhaustfans, preferably at maximum speed.Close any fireplace dampers.
4. Place in operation the first appliancebeing inspected that is connected to thecommon vent system. The remainingappliances should not be in operation.Follow the appliance’s lighting instruc-tions and adjust the thermostat to allowthe appliance to operate continuously.
5. Test for spillage at the draft hood reliefopening after 5 minutes of main burneroperation. Spillage can be detectedusing the flame of a match or candle orwith smoke from a cigarette.
6. Once it has been determined that eachremaining appliance connected to thecommon vent system is properly vent-ed, return doors, windows, exhaustfans, fireplace dampers and any operat-ing gas appliance to their previous con-dition.
Should any improper operation of the commonventing system be detected in the outline test,the condition should be corrected so the ventsystem conforms with the National Fuel GasCode, NFPA 54/ ANSI Z223.1 - latest edition.Canadian installations must conform withB149.1 or 149.2 Installation Code.
BEST PRACTICES
DANGER
11
Combustion Air and Venting
Equipment Located in ConfinedSpaces; All Air from inside thebuilding.
Fig. 1: Equipment Located in ConfinedSpaces; One Permanent Air Inlet
Fig. 2:
Equipment Located in ConfinedSpaces; All Air from Outdoors
Fig. 4: Equipment Located in ConfinedSpaces; All Air from OutdoorsThrough Ventilated Attic
Fig. 3:
12
Unit Preparation
SECTION III - Unit Preparation
Handling InstructionsThe PERFORMANCE PLUS is generally eas-ier to handle and maneuver once removed fromthe shipping carton and pallet.
To remove the shipping carton and pallet:
a. Remove the shipping straps and openthe top of the shipping carton to removethe wood shipment insert.
b. Lift the shipping carton over the unit toremove. If ceiling height is limited thecarton maybe cut open using care not todamage the exterior jacket of the unit.
c. Remove the front burner hood to pre-vent damage prior to lifting the unitfrom the shipping pallet.
When lifting or moving the unit do notuse the burner or its components as ameans of a handle. Hand-truck the unitfrom the rear only.
d. Discard all packing materials.
Hydrostatic Pressure Test
Prior to permanently connecting water,gas supply or electrical supply, performa pressure hydrostatic test of the outertank to ensure all piping connectionswere not damaged during shipment.
Hydrostatic Test Preparation
1. Mount the circulator on the supply pipe asshown in Figure 11 page 23.
2. Temporarily plug the primary return con-nections as shown in Figure 11 using a 1”NPT pipe plug. Use pipe dope sparingly toallow removal of the plugs upon comple-tion of the test.
3. On the outlet flange of the circulator pipeinstall a 1” NPT nipple and shut-off valve.Use pipe dope sparingly to allow removalof the fittings upon completion of the test.
To avoid getting water onto the unitand/or surrounding area additional pip-ing from the shut-off to a catch bucket ordrain may be required.
4. Connect a hose to the primary circuit drainvalve located per Figure 45 page 68, Item 2and connect the other end to a fresh watersupply. Ensure the hose can be used as adrain hose upon completion of the test.
Hydrostatic Test Procedures
1. Open the shut-off valve installed on theoutlet flange of the circulator.
2. Open the fresh water supply valve and thenopen slowly the primary circuit drain valveto fill the outer tank with water.
3. When the water within the outer tankreaches the shut-off on the primary supply,close the primary circuit drain valve.
4. Close the shut-off valve, on the top of thecirculator.
5. Slowly reopen the primary circuit drainvalve until the test pressure on the temper-ature / pressure gauge reaches 10 psigmaximum. Close the primary circuit drainvalve.
To prevent damage to the inner tank thetest pressure must not exceed 10 psig.
6. Allow the test pressure to remain for 10minutes.
CAUTION
NOTICE
BEST PRACTICES
WARNING
Unit Preparation
13
Do not leave the unit unattended whilepressurized. A cold water fill couldexpand and cause excessive pressure,resulting in severe personal injury, deathor substantial property damage.
7. Ensure constant gauge pressure has beenmaintained throughout the 10 minute test.Check for leaks at all fitting joints. Repairif found.
Leaks must be repaired immediatelywhen detected. Failure to repair leakscan damage the unit, resulting in sub-stantial property damage.
8. Check continuity using a voltmeter acrossthe terminals of the LWCO device. Thecontacts on the LWCO should be closed.See item 6 in Figure 40 page 64 for loca-tion of the LWCO.
Completion of Hydrostatic Test and Draining
1. Disconnect the fill hose from the freshwater source and direct the hose to a suit-able place of drainage.
2. Open the primary drain valve and complete-ly drain the unit. To aid in draining open theshut-off valve on the primary supply.
3. Remove the hose from the primary drainvalve when draining is complete.
4. Remove the plugs, nipple, shut-off valveand any other piping unless they willremain for use in the system piping.
WARNING
WARNING
Domestic Piping
SECTION IV - Domestic Piping
General Piping Requirements
• All plumbing must meet or exceed alllocal, state and national plumbing codes.
• Use pipe dope or tape suitable forpotable water.
• Use isolation valves to isolate systemcomponents.
• Install unions for easy removal of thePERFORMANCE PLUS from the sys-tem piping.
Domestic Supply Pressure
For applications in which the domestic sup-ply pressure exceeds 70 psig it is recom-mended to install a pressure reducing valveon the cold water supply.
Maintaining the cold water supply at orbelow 70 psig will prevent normal thermalexpansion from repeatedly forcing the T&Prelief valve open.
Thermal Expansion
If the cold water supply contains a backflowpreventer, check valve and / or a pressurereducing valve, the installer must install adomestic thermal expansion tank on the coldwater supply. (See Fig. 6 page 17)
Installing a thermal expansion tank willprevent normal thermal expansion fromrepeatedly forcing the T&P relief valveopen.
When installing a thermal expansion tankensure the charge pressure of the tank isequal to the cold water supply pressure atthe point of installation. Consult the ther-mal expansion tank manufacturer’s instruc-tions for further information on installationand sizing.
The Temperature / Pressure relief valveis not intended for constant duty, such asrelief of pressure due to normal thermalexpansion.
Water Hammer
Water hammer is the effect of sudden pres-sure changes occurring in the domestic pip-ing. These pressure changes are typicallythe result of “fast acting” positive shut-offvalves closing. These types of valves canbe typically found on dishwashers andclothes washers.
The effects of water hammering can causedamage to system components and tankwelds on the unit.
Installation of hammer arresters is recom-mended at these types of appliances, whichincorporate “fast-acting” positive shut-offvalves. Consult the manufacturer of waterhammer arresters for recommendation onsizing and installation requirements.
Temperature / Pressure Relief Valve
The PERFORMANCE PLUS has a factoryinstalled Temperature / Pressure Reliefvalve. Ensure the rating of the T&P reliefvalve is correctly sized as follows perAGA:
CAUTION
14
Model AGA RatingPG PLUS-25 100,000 Btu/hr
PG PLUS-30 200,000 Btu/hr
PG PLUS-35 200,000 Btu/hr
PG PLUS-40 200,000 Btu/hr
PG PLUS-45 200,000 Btu/hr
Domestic Piping
The installer must install discharge pipingonto the T&P relief valve. The dischargepiping must be:
• Made of material serviceable for tem-peratures of 250ºF or greater.
• Directed so that any hot water dis-charge flows away from all persons.
• Directed to a suitable place of drainage.
• Installed as to allow complete drainingof the T&P relief valve and the dis-charge piping.
• Terminated with a plain end, not withthreads.
Failure to properly direct the dischargepiping of the T&P relief valve may resultin flooding of the area adjacent to theunit and or lower floors in the structurecausing substantial property damage.
The installer must not install the T&Prelief valve discharge piping in a mannerthat is:
• Excessively long: Using more than 2elbows and/or 15 feet of discharge pip-ing can reduce the discharge capacity.
• Terminated directly into a drain: Thedischarge piping must terminate within6 inches of the drain. Check with localplumbing codes for termination guide-lines.
• The discharge piping is plugged, reducedin size or restricted in any manner.
• The discharge piping is subject to freez-ing.
DO NOT install any valves between theT&P relief valve and the discharge pip-ing. DO NOT plug the T&P relief valveor the discharge piping. Improper place-ment and piping of the T&P relief valvecan cause severe personal injury, deathor substantial property damage.
Thermostatic Mixing Valve
The PERFORMANCE PLUS contains a facto-ry installed thermostatic mixing valve withbuilt-in check valve.
The operating range of the thermostatic mixingis 90ºF to 120ºF.
For applications with a domestic recirculationloop, the recirculation pump should be con-trolled by an aquastat. The maximum recom-mended setting of the aquastat is 10ºF lowerthan the thermostatic mixing valve setting.
For proper operation of the thermostaticmixing valve and to prevent potentialscalding hazards, the recirculation loopshould be controlled by an aquastat. DONOT use continuous recirculation.
U-Tube Assembly
The PERFORMANCE PLUS is suppliedwith a U-Tube Assembly that directs coldwater to the thermostatic mixing valve.
To install the U-Tube Assembly theinstaller must:
1. Disconnect the cold inlet adapter/unionfrom the thermostatic mixing valve.
2. Using needle-nose pliers remove theplastic check valve assembly from theadapter.
DANGER
WARNING
CAUTION
15
Domestic Piping
3. Solder the U-Tube Assembly onto theadapter. (See Fig. 5)
4. Once the adapter has sufficientlycooled, re-insert the check valve assem-bly making sure of orientation andreconnect onto the mixing valve.
If the installation of the PERFORMANCEPLUS requires domestic hot water for acommercial dishwasher, the installer mayinsert a tee connection between the unit andthe mixing valve to provide 140ºF domes-tic hot water. The installer must referencelocal plumbing codes to ensure if this typeof application is permissible.
The thermostatic mixing valve MUST beinstalled and utilized on the PERFOR-MANCE PLUS. Removal of the thermo-static mixing valve will result in severepersonal injury or death.
The manual valve on the U-Tube assem-bly must remain in the full open positionfor proper operation of the thermostaticmixing valve.
Domestic Drain Valve
- The installer must install a drain valveand drain leg as shown in Fig. 6 page17 or Fig. 7 page 18.
- The drain valve should be positionedclose to the floor to aid in the siphonaction required to drain the inner tank.
Multiple Units Installation
For applications using multiple units thedomestic piping should be piped using a bal-anced manifold arrangement.
The installer should remove the thermostaticmixing valve from the units and install a singlethermostatic mixing valve at the outlet of thehot water manifold. The thermostatic mixingvalve should be sized according to the requiredflow rate and pressure drop. Refer to the ther-mostat mixing valve manufacturer specifica-tion and installation instructions for moredetails.
Reference Fig. 8, page 18 for piping diagram.
Storage Tank Application
For applications requiring large volumes ofdomestic hot water in a relative short period theinstaller may include a storage type tank (seeFig. 9 page 19) in the domestic piping. Theinstaller must:
1. Relocate the thermostatic mixing valvefrom the PERFORMANCE PLUS tothe outlet of the storage tank.
2. Provide recirculation from the storagetank back to the PERFORMANCEPLUS using a bronze type circulator.Maximum recommended flow rate is 5to 10 gpm.
CAUTION
DANGER
16
Cold
Hot
U-Tube AssemblyAdapter
Check Valve
Mixed
Fig. 5: Mixing Valve Assembly
17
Domestic Piping
TR/SMART Series Application
For applications requiring large volumes ofdomestic hot water over an extended period,the installer may include a Triangle TubeTR/SMART Indirect Water Heater in conjunc-tion with the PERFORMANCE PLUS. (SeeFig. 10 page 19)
The domestic system recirculation, if used, isdirected to the TR/SMART Series Tank. Thecirculator should be controlled by an aquastat.
The primary piping to the TR/SMART Seriestank must comply with the piping methodsdetails in SECTION V - Primary Piping or withother recognized piping methods.
Additional information regarding domestic andprimary piping can be found in the TR/SMARTInstallation Manual.
�
12" Heat trap
8
1
To dishwasher if�permitted by codes
3*�
Cold water inlet4 33
6
9
U-Tube�assembly
Fig. 6: PERFORMANCE PLUSWithout Recirculation
Note: All shut off valves shown inthis figure must be shut when siphondraining the PERFORMANCEPLUS.
Domestic Piping Diagrams
1. Mixing valve with check valve3. Shut off valve4. Backflow preventer or pressure reducing valve*
6. Thermal expansion tank 8. Domestic drain valve9. Vacuum breaker*
* Optional devices may be required by local Codes
18
Domestic Piping
7
8
1
To dishwasher if�permitted by codes
2 3
Optional recirculation line
3
12" Heat trap
Cold water inlet4 33
6
9
U-Tube assembly
Fig. 7: PERFORMANCE PLUSWith Recirculation
1. Mixing valve with check valve2. Flow check valve3. Shut off valve4. Backflow preventer or pressure reducing valve*
6. Thermal expansion tank 7. Circulator (controlled by aquastat)8. Domestic drain valve9. Vacuum breaker*
Note: All shut off valvesshown in this figure must beclosed when siphon drainingthe PERFORMANCE PLUS
* Optional devices may be required by local Codes
12" Heat trap
Optional recirculation line
8
1
Cold water inlet4 33
6
9
7 2 3
Fig. 8: Multiple Units Installation With Recirculation
19
12" Heat trap
Optional�Recirculation
8
1
3�
Cold water inlet4 3
3
3
6
9
27
27
To dishwasher if�permitted by codes
12" Heat trap
OptionalRecirculation
8
1
3
Cold water inlet4 3
3
3
6
9
27
To dishwasher ifpermitted by codes
Fig. 10: PERFORMANCE PLUS with TR/SMART Indirect Water Heater
Fig. 9 : PERFORMANCE PLUS with Storage Tank
1. Mixing valve with check valve2. Flow check valve3. Shut off valve4. Backflow preventer or pressure reducing valve*
6. Thermal expansion tank 7. Circulator (controlled by aquastat)8. Domestic drain valve9. Vacuum breaker*
Domestic Piping
* Optional devices may be required by local Codes
20
Primary Piping
SECTION V - Primary Piping
General Piping Requirements
Low Water Cutoff Device
- The PERFORMANCE PLUS is equippedwith a factory installed pressure switchstyle Low Water Cut Off device.
- The minimum operating system pressureallowable with this device is 10 psig.
- Check local codes which require a lowwater cutoff device for compliance ofthis device.
Backflow Preventer
- Use a backflow preventer valve in themake-up water supply to the unit asrequired by local codes.
Primary System Piping Applications
All piping applications shown in this instal-lation manual utilize a primary/ secondarypiping arrangement. This method is rec-ommended as a means to provide priorityto the production of domestic hot water.For other piping arrangements, consult theEngineering Department at Triangle Tubeor consult other approved/recognizeddesign arrangements.
On piping applications utilizing a singlezone or other recognized piping designarrangements it is recommended theinstaller uses flow/check valves withweighted seats at or near the appliance toprevent gravity circulation.
Expansion Tank and Makeup Water
Ensure the expansion tank is properly sizedfor the outer tank volume (20 gallons) andthe system volume and temperature.
Undersized expansion tanks will cause sys-tem water to be lost through the pressurerelief valve and cause additional makeupwater to be added to the system. Eventualprimary tank failure can result due to thisexcessive makeup water addition.
The expansion tank must be located asshown in Figure 11, 11A or 11B page 23 oras per recognized design methods. Refer tothe expansion tank manufacturer instruc-tions for additional installation details.
Connect the expansion tank to an air sepa-rator only if the air separator is located onthe suction side (inlet) of the system circu-lator. Always locate and install the systemfill connection at the same location as theexpansion tank connection to the system.
Diaphragm (Bladder) Expansion Tank
Always install an automatic air vent on thetop of the air separator to remove residualair from the system.
Closed-Type (Standard) Expansion Tank
It is recommended to pitch any horizontalpiping toward the expansion tank 1 inch per5 feet of piping. Use 3/4” piping for theexpansion tank to allow air within the sys-tem to rise.
For proper operation of the expansion tankand system, remove the factory installedautomatic air vent from the PERFOR-MANCE PLUS and plug the connection.(See Item 10, Fig. 46 page 68)
CAUTION
BEST PRACTICE
BEST PRACTICE
21
Primary Piping
DO NOT install automatic air vents on aclosed-type expansion tank system. Airmust remain in the system and bereturned to the expansion tank to pro-vide an air cushion. An automatic airvent would cause air to be vented fromthe system resulting in a water-loggedexpansion tank.
Circulator
The PERFORMANCE PLUS is suppliedwith a circulator that is pre-wired to allowfor domestic priority. Locate the circulatorin the return or supply piping as shown inthe piping diagrams included in this manual.
Closet (Zero Clearance) Applications
For applications in closets or zero clear-ances, the installer may use the upper prima-ry connection shown as Item 4 on page 70 asa primary return connection. The air elimi-nation, expansion tank and make-up watersystem should then be piped directly into theprimary loop of the space heating prior tothe system circulator.
Sizing Primary Piping
See Figure 12 through 15, pages 24 - 25,for recommended piping arrangementsbased on various applications. In all dia-grams, the space heating system is isolatedfrom the PERFORMANCE PLUS usingprimary / secondary piping connections.
Size the piping and system componentsrequired in the space heating system usingrecognized design methods.
System Piping - Zone Circulators
Connect the PERFORMANCE PLUS tothe system piping as shown in Fig. 12 page24 when zoning with zone circulators. Thecirculator supplied with the PERFOR-MANCE PLUS should not be used for aheat zone. It must supply only the prima-ry loop.
Install a separate circulator for each zone ofspace heating.
To control the zone circulators refer to Fig.34, page 45.
To ensure adequate flow rate throughthe PERFORMANCE PLUS, maintain aminimum 1 inch diameter on the systempiping connecting the unit to and fromthe primary / secondary connection.
System Piping - Zone Valves
Connect the PERFORMANCE PLUS to thesystem piping as shown in Fig. 13 page 24when zoning with zone valves. The prima-ry / secondary piping ensures the priority isgiven to the production of domestic hotwater.
To control the system circulator refer toFig. 33, page 44.
To ensure adequate flow rate throughthe PERFORMANCE PLUS, maintain aminimum 1 inch diameter on the systempiping connecting the unit to and fromthe primary / secondary connection.
System Piping - Radiant Heating with MixingValve
Connect the PERFORMANCE PLUS to thesystem piping as shown with a radiant sys-tem using a thermostatic mixing valve asshown in Fig. 14 page 25. The primary / sec-ondary piping ensures sufficient return tem-perature to the PERFORMANCE PLUS.
NOTICE
NOTICE
CAUTION
22
Primary Piping
If the radiant system tubing contains nooxygen barrier, a stainless steel heatexchanger must be used. Failure toinstall a heat exchanger could lead topremature failure of the outer tank andvoid any warranty claim.
Radiant heating system piping shouldinclude a means of regulating the boilerreturn water. The return water tempera-ture to the unit should be maintained at130ºF or higher. Failure to prevent lowreturn water temperature to the unitcould cause premature failure of the unitand it’s burner system resulting in severepersonal injury, death or substantialproperty damage.
Size the system piping and circulator to pro-vide the flow needed for the radiant system.
To control the zone circulators referenceFigure 34, page 45.
To ensure adequate flow rate throughthe PERFORMANCE PLUS, maintain aminimum 1 inch diameter on the systempiping connecting the unit to and fromthe primary / secondary connection.
System Piping - Multiple Units Installation
Use a balance manifold system as the pri-mary / secondary connection to the spaceheating piping as shown in Fig. 16 page 26.
Refer to Fig. 11 page 23 to install air elim-ination and expansion tank.
For the space heating piping refer to theapplications mentioned in this manual oruse recognized design methods.
NOTICE
WARNING
NOTICE
23
Primary Piping
1
2
12" Max.
Tosystem
4
7
5
22
3
2
From system
Cold Waterfill supply
Supplyflow
2
Returnflow
8
8
1
Tosystem
2
2
12" Max.
3
4
7
6
2
22
Supplyflow
Returnflow
From system
Cold Waterfill supply
Near Appliance Piping
1. Appliance Circulator2. Shut Off valve3. Expansion tank
4. Auto fill valve5. Tank fitting6. Automatic air vent
7. Air Separator8. Plug (by others)
To system
From system
Supplyflow
Returnflow
Cold Waterfill supply
2
1
7
6
8
2
12" Max.
3
4 2
22
Fig. 11 : Near Appliance PrimaryPiping with a DiaphragmType Expansion Tank
Fig. 11A : Near Appliance PrimaryPiping with Closed -Type Expansion Tank
Fig. 11B : Near Appliance Primary Pipingwith Diaphragm - Type ExpansionTank (Alternate Circulator Location)
24
Primary Piping
112" max.
2 2
3
6
2
3
6
2
3
2
3
2
2
2
5
LOAD
LOAD
1
2
2 2
22
5
2
4
6
4
12" max.
LOAD
LOAD
Fig. 12: Primary piping - Zoning with Circulators
Fig. 13: Primary Piping - Zoning with Zone Valves
1. Appliance circulator2. Shut-off valves3. Flow check valve4. Zone valve
5. System purge valve6. System circulator
Note: See page 23 for near appliance piping.
• Install balancing valves toadjust flow to distributeheat to all zones
• Size primary manifold fortotal flow of all circula-tors
• Size each circulator toindividual circuit require-ments
• Install balancing valves toadjust flow to distributeheat to all zones
25
Primary Piping
1
8
2
3 27
6
5
2
5H
M
C
LOAD
Fig. 14: Primary Piping - Low Temperature Radiant System
Note: Adjust system temperaturevalve to establish maximum sup-ply/return temperature differen-tial of 30ºF and a minimum130ºF return water temperatureto the PERFORMANCE PLUS
1. Circulator2. Shut Off valves3. Flow check valve4. Zone valve
5. Purge valve6. System circulator7. 3-way mixing valve8. System Temperature valve (See note above)
1
6Baseboard
Load
3
6
6
2
2
8
7
RadiantLoad
Air HandlerLoad
3
32
2
2
H
C
M
2
2
12" Max.
12" Max.
12" Max.
2
Fig. 15: Primary Piping - Multi Temperature System
26
Primary Piping
Rec
omm
ende
d pl
acem
ent
of e
xpan
sion
tank
and
mak
e up
wat
er s
uppl
y.
To th
e Sy
stem
From
the
Syst
em
12"
Max
.
12 3
12 3
4
22
2
12 3
Prim
ary
Hea
ting
Prim
ary
Tem
pera
ture
/Pre
ssur
eD
omes
ticH
eatin
g
Tria
ngle
Tube
Hot
Wat
er S
peci
alis
tsPush
But
to
n
To Reset
Sw
itch
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
Prim
ary
Hea
ting
Prim
ary
Tem
pera
ture
/Pre
ssur
eD
omes
ticH
eatin
g
Tria
ngle
Tube
Hot
Wat
er S
peci
alis
tsPush
But
to
n
To Reset
Sw
itch
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
Prim
ary
Hea
ting
Prim
ary
Tem
pera
ture
/Pre
ssur
eD
omes
ticH
eatin
g
Tria
ngle
Tube
Hot
Wat
er S
peci
alis
tsPush
But
to
n
To Reset
Sw
itch
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
Phase
III - PhaseIII
-PhaseIII-Phas
eIII
-
cit
semo
D
Space
heating
1.U
nit C
ircu
lato
r2.
Shut
Off
Val
ves
3.Fl
ow C
heck
Val
ve4.
Syst
em C
ircu
lato
r
Fig
. 16:
Pri
mar
y P
ipin
g -
Mul
ti U
nits
Ins
talla
tion
27
Venting and Combustion Air Installation
SECTION VI - Venting andCombustion Air Installation
General Requirements
- Installation must comply with localrequirements and with the NationalFuel Gas Code, NFPA 54/ ANSI Z223.1for U.S. installations and CSA B149.1or B149.2 for Canadian installations.
- The PERFORMANCE PLUS requiresa special vent system designed for pres-surized venting and is rated as ANSIZ21.13 Category IV (pressurized ventsystem, likely to condense within thevent system).
- The PERFORMANCE PLUS may bedirect vented with outside combustionair or non-direct vented using room air.
- The PERFORMANCE PLUS isapproved for the following vent manu-facturers:
• Heat Fab (Saf-T-Vent®)
• ProTech Systems (FasNSeal®)
• Flex-L (StaR-34)
• Z-Flex (Z-Vent III™)
DO NOT mix components from differentsystems. The vent system could fail orimproperly seal, causing leakage of flueproducts into the building.
Category IV Vent Termination - Guidelines
Locate the vent termination for direct or non-direct vent applications using the followingguidelines:
1. The total equivalent length of the ventshould not exceed 100 feet as given inTable 2, page 33.
2. The installer must consider the followingwhen determining the location of the venttermination:
- Locate the vent termination where fluevapors will not damage surroundingshrubs, plants or air conditioning equip-ment or be objectionable to the home-owner.
- The flue products will form a notice-able plume as they condense in colderair. Avoid terminating the vent in areaswhere the plume could obstruct win-dow views.
- Prevailing winds could cause freezingof flue condensation and a buildup ofwater / ice on surrounding plants, build-ing surfaces or combustion air inlet.
- Avoid locations of possible accidentalcontact of flue vapors with persons orpets.
- Avoid locations where prevailing windscould affect the performance of the unitor cause recirculation of the flue gases,such as inside corners of buildings ornear adjacent buildings or vertical sur-faces, window wells, stairwells,alcoves, courtyards, or other recessedareas.
- Do not terminate the vent above anydoors or windows; flue condensatecould freeze causing ice formations.
- Locate or guard the vent termination toprevent possible condensate damage toexterior finishes.
3. The vent termination and vent pipe mustnot extend more than 12 inches beyond theexterior wall.
4. Do not connect or terminate any otherappliance to the vent system or multipleunits into a common vent system.
WARNING
28
Venting and Combustion Air Installation
Category IV Vent Termination Clearances
Maintain the following clearances to the venttermination:
- At least 6 feet from adjacent walls
- No closer than 5 feet below roof over-hangs
- At least 7 feet above any public walk-ways
- At least 3 feet above any forced airintake (does not include the combustionair inlet) within 10 feet.
- The vent termination must be at least 4feet from any electric meters, gasmeter-regulators, relief valves or otherequipment. Never terminate the ventabove or below any of these items with-in 4 feet.
- Vent must terminate at least 12 inchesabove grade or common snow line.
In those applications in which the venttermination is below the projected snowline, the vent system can be routed verti-cally through an insulated chase or“riser box” and then terminated hori-zontally. The chase is to be constructedand insulated by the contractor, main-taining clearances for vertical and hori-zontal enclosures.
If the venting application is a horizontaldirect vent:
- Must maintain 12-inch clearancesbelow and horizontally from doors andwindows. See dimension A Fig. 17.
If the venting application is a horizontalnon-direct vent:
- Must maintain 4 feet of clearancebelow and horizontally from doors andwindows. See dimension A Fig. 17.
NOTICE
Fig.17: Termination of Vent system
Dimension ADirect Vent - 12 inchesNon-Direct Vent - 4 feet
29
Venting and Combustion Air Installation
If the venting application is a vertical director non-direct vent application:
- The vent must terminate at least 3 feetabove the roof and at least 2 feet higherthan any portion of the building within10 feet.
Multiple Vent Terminations
For multiple unit installation venting horizon-tally, it is recommended to vent as direct ventusing the Triangle Tube Thimble Box Kit. TheThimble Box terminations of the installationmust maintain the same horizontal centerline
and bespaced am i n i -mum 18i n c h e sf r o mcenter tocenter.
For multiple unit installation venting vertically,it is recommended to vent as direct vent usingTriangle Tube Vertical Vent Kit. The concen-tric vent / combustion air terminations mustmaintain a minimum 18 inch spacing from ventcenterline to vent centerline.
Locating the Combustion Air Inlet
When ducting outside combustion air directlyto the appliance the installer must use the fol-lowing guidelines:
1. The total equivalent length of the air inletduct should not exceed 100 feet as given inTable 2, page 33.
2. The installer must consider the followingwhen determining the location of the com-bustion air inlet:
- The air inlet must terminate at least 12inches above grade or projected snowline.
- The combustion air inlet must be locat-ed a minimum 12 inches from the venttermination. This does not apply on
direct vent applications using theThimble Box kit or the VerticalTermination Adapter of the VerticalVent kit.
- The combustion air inlet should not belocated above the vent terminationwhen direct venting.
- The combustion air inlet must be locat-ed in the same pressure zone as the venttermination.
Venting Option - Non Direct Vent / Vertical
In this vent application the PERFORMANCEPLUS is vented vertically through the roof oran unused chimney using 3 inch stainless ventmaterial and using room air for combustion.
The installer should consider the followingwhen choosing this vent option:
a. The vent system must contain a con-densate trap located no higher than 2feet above the unit. As shown in Fig. 19page 34.
b. The vent system must pitch back to theunit 1/4 inch per foot or as specified bythe vent manufacturer.
c. Clearance to combustibles must bemaintained per the vent manufacturer’srequirements. Refer to the vent manu-facturer’s installation instructions foradditional details.
d. At a minimum, a 3-inch elbow shouldbe placed on the combustion air inlet ofthe unit. This will prevent an acciden-tal blockage should anything be placedon top of the unit.
When using an unused chimney as ameans of a raceway for the 3 inch vent,the surrounding space cannot be used todraw combustion air.
NOTICE
PERFORMANCE Min. Recommended
Model Vent Connector
Diameter
PG-25/30 4 inches
PG-35/40/45 5 inches
TABLE 1: Vent Connector Diameter
30
Venting and Combustion Air InstallationVenting Option - Direct Vent / Vertical
In this vent application the PERFORMANCEPLUS is vented vertically through the roof oran unused chimney using the Triangle TubeVertical Vent Kit.
The installer should consider the followingwhen choosing this vent option:
a. The vent system should contain a conden-sate trap located no higher than 2 feetabove the unit as shown in Fig. 20, page 34.
b. The vent system must pitch back to the unit1/4 inch per foot as a minimum.
c. The vent system must maintain the follow-ing clearances to combustibles:
- 0 inches when there are no horizontaloffsets and fully enclosed by com-bustibles on all sides
- 1 inch when there are horizontal offsetsand fully enclosed by combustibles onall sides.
- 0 inches with or without offsets andunenclosed or with 1 side open and amaximum 3 sides enclosed with com-bustible materials.
- 0 inches with or without offsets andenclosed with non combustible materials.
Venting Option - Non-Direct Vent /Horizontal
In this vent application the PERFORMANCEPLUS is vented horizontally through a wallusing 3-inch stainless vent material and usingroom air for combustion.
The installer should consider the followingwhen choosing this vent option:
a. The vent system must contain a con-densate trap located near the unit asshown in Fig. 21 page 34.
b. The vent system must be pitched a min-imum 1/4 inch per foot or as specifiedby the vent manufacturer.
Although the vent system is allowed topitch away from the unit, it is recom-mended that the vent system pitchestoward the unit with a condensate draininstalled as close to the unit as possible.Opting to pitch the vent system awayposes potential damage to the buildingexterior or to the surrounding landscapeand/or potential risks of icing if conden-sate is formed.
c. Penetration at the wall requires a wallpenetration / thimble kit.
d. Clearance to combustibles must bemaintained per the vent manufacturer’srequirements. Reference the vent man-ufacturer’s installation instructions foradditional details.
Maintain a minimum 2-inch clearance tocombustible wall and 1-inch clearance tonon-combustible in the absence of amanufacturer’s recommended clearancewhen penetrating a sidewall.
e. At a minimum a 3-inch elbow shouldbe placed on the combustion air inlet ofthe unit. This will prevent an acciden-tal blockage should anything be placedon top of the unit.
NOTICE
BEST PRACTICE
31
Venting and Combustion Air Installation
Venting Option - Direct Vent /Horizontal
In this vent application the PERFORMANCEPLUS is vented horizontally through a wallusing 3-inch stainless vent material and usingoutside air for combustion.
The installer should consider the followingwhen choosing this vent option:
a. The vent system should contain a con-densate trap located near the unit asshown in Fig. 22, page 34.
b. The vent system must pitch back to theunit 1/4 inch per foot.
Although the vent system is allowed topitch away from the unit, it is recom-mended that the vent system pitchestoward the unit with a condensate draininstalled as close to the unit as possible.Opting to pitch the vent system awayposes potential damage to the buildingexterior or to the surrounding landscapeand/or potential risks of icing if conden-sate is formed.
c. Penetration at the wall requires a wallpenetration / thimble kit.
d. Clearance to combustibles must bemaintained per the vent manufacturer’srequirements. Refer to the vent manu-facturer’s installation instructions foradditional details.
Maintain a minimum 2-inch clearance tocombustible wall and 1-inch clearance tonon-combustible in the absence of amanufacturer’s recommended clearancewhen penetrating a sidewall.
d. For a zero clearance concentric termi-nation of the vent and inlet of the com-bustion air refer to the Triangle TubeThimble Box Kit.
There are two methods available for DirectVenting - Horizontal:
Separate: The vent and the combustion airinlet are run together and exit the structure sep-arately with different terminations. This methodcan be accomplished vertically or sidewallvented horizontally.
The combustion air inlet and the venttermination must reside in the samepressure zone area of the building forproper operation of the appliance.
Combination: The vent and combustion airinlet terminations are at a single concentric pointusing the Triangle Tube Wall Thimble Kit. Thisoption can only be done horizontally through thesidewall.
NOTICE
NOTICE
BEST PRACTICE
Combustion Test Port
Vent Outlet Reducer
Beveled End
PERFORMANCE PLUSFlue Hood
Fig.18: Installation of Vent Outlet Reducer
32
Venting and Combustion Air Installation
Triangle Tube Thimble Box Kit
- Requires a 5 1/2 inch x 5 1/2 inch penetra-tion through any type of wall.
- Allows zero clearance at the wall penetration.
- Maximum wall thickness is 11 inches.
- The use of a termination elbow or horizon-tal tee termination for the venting system isnot recommended when using the ThimbleBox Kit.
To prevent potential nuisance lock-outsor flue gas recirculation it is recom-mended to terminate the vent with a hor-izontal termination tee or side dischargevent hood.
Excessive Horizontal Vent Runs
If maintaining the 1/4 inch per foot pitchrequirement creates clearance problems withstructural obstacles, i.e. low ceilings, theinstaller may opt to installing the vent in amanner that pitches up to a high point from theunit and then pitches away from the high pointto the vent termination.
A condensate tee should be installed as close aspossible to the unit when venting in this manner.
The vent run from the high point to the venttermination should be as minimal in length aspossible to reduce the amount of potential con-densate that may form in the vent system.
The vent system must maintain the 1/4 inch perfoot pitch to the high point and from the highpoint to the vent termination.
Vent Outlet Reducer
Prior to installing the appliance adapter or anyvent system components, the installer mustinstall the vent outlet reducer as shown in Fig.18, page 31.
Failure to install the vent outlet reducermay create improper vent connectionand potential flue gas leakage into thebuilding.
Position the combustion test port towardsthe front of the unit for ease of access.
Vent Appliance Adapters
- The PERFORMANCE requires the use ofan appliance adapter as approved by the oneof vent manufacturers listed on page 27.
Failure to use an approved vent appli-ance adapter may create improper ventconnection and potential flue gas leak-age. Do not mix the manufacturer appli-ance adapter with other manufacturers’vent components, the vent system couldfail or improperly seal, causing leakageof flue products into the building.
Vent Condensate Tee
A vent condensate tee and drain tube should beinstalled on a horizontal run of vent near theappliance to prevent any potential condensatefrom entering the flue ways on the unit. SeeFigures 19, 20, 21 and 22 page 34.
Failure to provide a vent condensate teeclose to the appliance could allow acidicflue gas condensate to enter into theappliance flue ways causing prematurefailure of the appliance.
WARNING
WARNING
WARNING
BEST PRACTICES
33
Venting and Combustion Air Installation
Condensate Drain Tube
To prevent flue gases from entering into thebuilding it is important the drain tube is fash-ioned into a “pigtail” trap as shown in Figures19, 20, 21 and 22 page 34.
The drain tube must be filled with water to pre-vent flue gases from emitting into the buildingprior to operating the appliance.
Periodically inspect the water level in thecondensate drain tube. If low, add wateras needed to maintain trap level.
If water in drain tube evaporates rapidly due toambient conditions, propylene glycol may beadded or substituted to reduce evaporation.
Pipe the condensate drain tube to a suitableplace of drainage or to a condensate pump orsump. Consult local authorities regarding dis-posal of flue gas condensate into public wastewater system.
Determining Piping Lengths
Once the venting method and location for thevent termination has been determined theinstaller must select the vent componentsrequired for the system.
The maximum combined equivalent lengths forventing and combustion air inlet are as follows:
- Delta PERFORMANCE PLUS - 200feet (100 feet each)
The maximum equivalent length is thetotal length of the venting and the com-bustion air inlet combined. This includestermination fittings.
For Delta PERFORMANCE PLUSapplications that may exceed the 100 feetmaximum allowable equivalent lengthfor the venting system, contact TriangleTube Engineering Department for addi-tional information on how the appliancecan be adjusted to the application.
- For each elbow included in the system,the maximum allowable linear lengthmust be reduced as follows:
• Each 90º elbow within the system isthe equivalent of 10 linear feet.
• Each 45º elbow within the system isthe equivalent of 5 linear feet.
It is recommended that the installer uses thesame number of elbows and length of piping onthe venting system and the combustion airinlet.
NOTICE
NOTICE
NOTICE
Table 2- Allowable Equivalent Length (Combined Vent and Combustion Air)
MaximumAllowable for
Linear Length Combined 2 3 4 5 6 7
PERFORMANCE PLUS 180 170 160 150 140 130
Total Elbows within the Venting / Combustion Air System
34
Venting and Combustion Air Installation
Primary Heating
PrimaryTemperature/Pressure
DomesticHeating
TriangleTubeHot Water Specialists
Push Button
To
ResetSwitchPhase
III-
PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
PhaseIII
-PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
Refer to the vent manufacturer’s recommended clearances
Refer to the vent manufacturer’srecommended spacing of support Termination Tee
or Bird screen
HangerStrap
WallThimble
To DrainDispose of Condensate
According to Local Codes
Elbow
ApplianceAdaptor
DrainTee
CombustionAir Inlet
Fig. 21: Standard Horizontal Venting Installation
Primary Heating
PrimaryTemperature/Pressure
DomesticHeating
TriangleTubeHot Water Specialists
Push Button
To
ResetSwitchPhase
III-
PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
PhaseIII
-PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
Refer to ventmanufacturer’srecommended
clearances
Refer to vent manufacturer’srecommended clearances
To draindispose of condensate
according to local codes
DrainTee
StormCollar
Rain Cap
AdjustableFlashing
Roof Jack
FirestopSupportClamp
CombustionAir Inlet
2 Ft.Max.
Fig. 19: Standard Vertical Venting Installation
Primary Heating
PrimaryTemperature/Pressure
DomesticHeating
Push Button
To
Reset SwitchPhase
III-
PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
PhaseIII
-PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
HangerStrap
Triangle TubeWall Thimble
Kit
To DrainDispose of Condensate
According to Local Codes
ApplianceAdaptor
Elbow
DrainTeeRefer to the vent
manufacturer’s recommended
clearances
Refer to the vent manufacturer’srecommended spacing of support
Fig. 22: Horizontal - Direct Vent Combination
Refer to vent manufacturer’srecommended clearances
Refer to ventmanufacturer’srecommended
clearances
To draindispose of condensate
according to local codes
Triangle Tube’sVertical Direct
Vent System Kit
Primary Heating
PrimaryTemperature/Pressure
DomesticHeating
TriangleTubeHot Water Specialists
Push Button
To
ResetSwitchPhase
III-
PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
PhaseIII
-PhaseIII-Phase
III-
Pha
seIII -
citse mo D
Space
heating
DrainTee
2 Ft.Max.
Fig. 20: Vertical - Direct Vent Combination
35
Venting and Combustion Air Installation
Grade level
Flashing recommended
to direct exhaust away from wall
12" Min.
Vent Termination
Anchored fastners
Metal Plate
Caulk opening
Cement mortar
seal
1" Min.clearance
Fig. 24B: Vent Termination - Non-Combustible Wall
Grade level
Flashing recommended
to direct exhaustaway from wall
12" Min.
Anchored fastners
Anchoredfastners
Metal Plate
Caulk opening
2" Min.clearance
Vent Termination
Fig. 24A: Vent Termination CombustibleWall
Vent Termination Tee
Location of Air InletNot recommended forVertical Tee or HoodedVent Termination
Location of Air InletNot recommended forHorizontal Tee Vent Termination orhorizontal/straight-outscreened termination
Air Inlet Elbow
12" Recommendedminimum clearance
Fig. 23: Location of Air Inlet Termination
Vent Termination
Combustion Air�Inlet
Maximum 12"
Maintain Distance as�Close to Outside Wall�as Possible
36
Venting and Combustion Air Installation
Thi
mbl
eB
ox
Out
side
End
Cap
Atta
ch to
out
er w
all
usin
g ga
lvan
ized
scr
ews
Spl
it R
ing
may
be
used
to p
rovi
dead
ditio
n se
al
Term
inat
ion
Hoo
d-
mus
t ven
t hor
izon
tally
- at
tach
to O
utsi
de E
nd C
ap
3" to
4"
redu
ced
com
bust
ion
air
inle
t pip
ing
Insi
de E
nd C
apA
pply
hig
h te
mp.
silic
on b
ead
to s
eal
arou
nd v
ent p
ipe
No
te: U
se L
ocki
ng B
ands
insi
de th
e T
him
ble
Box
agai
nst t
he in
side
and
outs
ide
End
Cap
s to
pre
vent
mov
emen
t of t
he v
ent p
ipin
g.
Thi
mbl
eB
ox
Out
side
End
Cap
Atta
ch to
out
er w
all
usin
g ga
lvan
ized
scr
ews
Spl
it R
ing
may
be
used
to p
rovi
dead
ditio
n se
al
3" to
4"
redu
ced
com
bust
ion
air
inle
t pip
ing
Insi
de E
nd C
apA
pply
hig
h te
mp.
silic
on b
ead
to s
eal
arou
nd v
ent p
ipe
Ven
t Pip
ing
exte
nd th
roug
h th
imbl
e bo
xto
term
inat
ion
fittin
g
Term
inat
ion
Tee
- m
ust v
ent h
oriz
onta
lly-
mus
t ext
end
a m
inim
um 6
" be
yond
Out
side
End
Cap
. DO
NO
T e
xten
d m
ore
than
12"
Ven
t Pip
ing
exte
nd th
roug
h th
imbl
e bo
xto
term
inat
ion
fittin
g
Spl
itR
ing
No
te: U
se L
ocki
ng B
ands
insi
de th
e T
him
ble
Box
agai
nst t
he in
side
and
outs
ide
End
Cap
s to
pre
vent
mov
emen
t of t
he v
ent p
ipin
g.
Spl
itR
ing
Fig
. 25:
Tri
angl
e Tu
be T
him
ble
Box
Kit
- T
erm
inat
ion
Hoo
dF
ig. 2
6:T
rian
gle
Tube
Thi
mbl
e B
ox K
it -
Ter
min
atio
n Te
e
37
Gas Piping
SECTION VII - Gas Piping
Gas Supply Piping Connection
The gas supply piping must be installedin accordance to all applicable local,state and national codes and utilityrequirements.
1. Remove the burner jacket hood. Refer toFigure 27 to pipe gas supply to the burner.
a. Install a pipe union at the factory sup-plied gas nipple, for ease of service.
b. Install a manual shutoff valve in the gassupply piping as shown in Figure 27.For installations in Canada the installermust tag and identify the main shutoffvalve.
c. Install a drip leg on the gas supply lineprior to connecting to the PERFOR-MANCE PLUS gas train as shown inFigure 27.
2. Support the gas piping using hangers. Donot support the piping by the unit or itscomponents.
3. Purge all air from the gas supply piping.
4. Before placing the PERFORMANCEPLUS into operation, check and test allconnections for leaks.
Close the manual shutoff valve duringany pressure test with less than 13”w.c..
Disconnect the PERFORMANCEPLUS and its gas valve from the gassupply piping during any pressure testgreater than 13”w.c..
Do not check for gas leaks with an openflame. Use a gas detection device orbubble test. Failure to check for gasleaks can cause severe personal injury,death or substantial property damage.
5. Use pipe dope compatible with natural andpropane gases. Apply sparingly only to themale threads of pipe joints so that pipedope does not block gas flow.
Failure to apply pipe dope as detailedabove can result in severe personalinjury, death or substantial propertydamage.
Use a two-wrench method of tighteninggas piping near the unit and its gas valve.Use one wrench to prevent the gas valveline connection from turning and the sec-ond to tighten adjacent piping. Failureto support the gas valve connection pip-ing could damage the valve and the gasline components.
WARNING
WARNING
WARNING
NOTICE
Equipment Shutoff valve�(must be within 6' �
from the water heater)
Tee
Pipe Cap
Drip legBurner gas train
Male union
Pressure gauge port(1/8" NPT plugged)
Direction of flow
3" Minimum
Fig. 27: Recommended Gas Supply Piping
38
Gas Piping
NATURAL GAS
Pipe Sizing - Natural Gas
1. Refer to Table 3 for pipe length and diame-ter requirements. Based on rated PER-FORMANCE PLUS input (divide by 1,000to obtain cubic feet per hour).
- Table 3 is based on Natural Gas with aspecific gravity of 0.60 and a pressuredrop through the gas piping of0.30”w.c..
- For additional gas piping sizing infor-mation, refer to ANSI Z223.1. ForCanadian installations refer to B149.1or B149.2.
Natural Gas Supply Pressure Requirements
1. Pressure required at the gas valve inletsupply pressure port:
- Maximum 13”w.c. at flow or no flowconditions to the burner.
- Minimum 5”w.c. during flow condi-tions to the burner. Must be verifiedduring start up.
2. Install 100% lockup gas pressure regulatorin the gas supply line if inlet pressure canexceed 13”w.c at any time. Adjust the lock-up pressure regulator for 13”w.c maximum.
DO NOT adjust or attempt to measuregas valve outlet pressure. The gas valveis factory-set for the correct outlet pres-sure. This setting is suitable for naturalgas and propane and requires no fieldadjustment. Attempts by the installer toadjust or measure the gas valve outletpressure could result in damage to thevalve, causing potential severe personalinjury, death or substantial propertydamage.
WARNING
Length of Pipein Feet
SCH 40 1/2" 3/4" 1" 1-1/4" 1-1/2"10 132 278 520 1050 160020 92 190 350 730 110030 73 152 285 590 86040 63 130 245 500 76050 56 115 215 440 67075 45 93 175 360 545100 38 79 150 305 460150 31 64 120 250 380
Capacity of Pipe in Cubic Feet of Gas Per Hour(based on 0.60 specific gravity, 0.30" w.c. pressure drop)
Table 3: Gas piping sizing - Natural Gas
39
Gas Piping
PROPANE GAS
Pipe Sizing - Propane Gas
1. Contact the local propane gas supplier forrecommended sizing of piping, tanks and100% lockup gas regulator.
Propane Gas Supply Pressure Requirements
1. Adjust the propane supply regulator pro-vided by the gas supplier for 13”w.c. max-imum pressure
2. Pressure required at the gas valve inlet sup-ply pressure port:
- Maximum 13”w.c. at flow or no flowconditions to the burner
- Minimum 5”w.c. during flow condi-tions to the burner. Must be verifiedduring start up.
DO NOT adjust or attempt to measuregas valve outlet pressure. The gas valveis factory-set for the correct outlet pres-sure. This setting is suitable for naturalgas and propane and requires no fieldadjustment. Attempts by the installer toadjust or measure the gas valve outletpressure could result in damage to thevalve, causing potential severe personalinjury, death or substantial propertydamage.
Prior to start up ensure the unit is set tofire propane. Check the rating label forthe type of fuel. Check the gas valve andair inlet for propane conversion labels.If there is a conflict or doubt on theburner set up, remove the gas valve andcheck for the propane orifice. Failure toensure proper burner setup could resultin severe personal injury, death or sub-stantial property damage.
WARNING
WARNING
Venturi
Inlet SupplyPressure Port
PropaneOrifice
Gas ValveGasket
Gas ValvePipe Fitting
Gas Valve
Fig. 28: Gas Valve / Venturi Assembly
Internal Wiring
40
SECTION VIII - Internal Wiring
ELECTRICAL SHOCK HAZARD. Foryour safety, disconnect electrical powersupply to the unit before servicing ormaking any electrical connections toavoid possible electric shock hazard.Failure to do so can cause severe person-al injury or death.
All electrical contacts shown in Figures30 & 31 pages 41 & 42 do not have elec-trical power applied. Shown as “off-shelf” condition.
General Requirements
- Wiring must be N.E.C Class 1.
- If original wiring as supplied with theunit must be replaced, use only type90ºC wire or equivalent.
- The PERFORMANCE PLUS must beelectrically grounded as required byNational Electrical Code ANSI/NFPA70 - latest edition.
NOTICE
WARNING
ELECTRONICCONTROLS
ANSI Z21.20
IGNITORSPARKDIRECTSERIES1016-400
HV
L1 IND LED MV PS2 PS1 W FS R X C/COM
Black Gas Valve Plug
Red Snap-Set T2
RedSnap-Set
T1
Air SwitchTerminals
BlackGas Valve Plug
Bla
ck
Whi
teG
reen
BlowerMolex Plug
LEDIndicator
Snap-Set
L1N
Fig. 29 : Burner Control Wiring
41
Internal Wiring
Room T -StatSnap-Set LWCO
BurnerSnap-Set Circulator
TransformerRelay R2 Relay R1
C 1L1 N
1 3
4 6
1 3
4 6
BL
BL
BL
BL
BL
B BB
B
BL
B B
T T
T
T
R
V
W
G
Y
Y
YY
V
V B
BB
B
B
B
G
G G G
G G
W14 13 12 11 10 9 8 7 6 5 4 3 2 1
2C 1
2C 1
2C 1
OR P P
Manual ResetSafety Limit
Auto ResetSafety Limit
Primary T-Stat
On-OffSwitch
BurnerSnap-Set
T1 T2
Secondary T-Stat
120 V IncomingSupply Wiring
GNH
120V Field Wiring (By Others)
120V Factory Wiring
24V Factory Wiring
B� - �BlackBRN�- �BrownBL� - �BlueP� - �PinkV� - �VioletY� - �YellowR� -�RedOR� - �OrangeW� - �White
Wire Color Code
Fig. 30: Factory Wiring Schematic
42
Internal Wiring
JumperLWCO
Burner Control
Circulator
ManualResetLimit
R2A
R1A
120V
24V
Room T-statSnap-set
SecondaryT-stat
Gas Valve
AutoResetLimit
Burner Control
FactoryJumper
R2B
Air Switch
Blower
Alarm
EquipmentGround
On-OffSwitch
120 VAC
R2
B B B
B
B
B B
B
B
B
B
R
B
B
R
R
R
R
W
W
BL
BL
BL
BRN
T T V
VVP P
Y
Y
V BL BL
PrimaryT-Stat
CDM
C
C
PS1
PS2
MV
IND
L1
B� - �BlackBRN�- �BrownBL� - �BlueP� - �PinkV� - �VioletY� - �YellowR� -�RedOR� - �OrangeW� - �White
Wire Color Code
Fig. 31: Factory Internal Wiring
43
External Wiring
SECTION IX - External Wiring
Installation Compliance
All field wiring made during installation mustcomply with:
- National Electrical Code NFPA 70 andany other national, state, provincial orlocal codes or requirements.
- In Canada, CSA C22.1 CanadianElectrical Code Part 1, and any otherlocal codes.
Line Voltage Connections
1. Connect 120 VAC power wire to the linevoltage leads located behind the front con-trol panel.
2. Route the incoming 120 VAC power wirethrough the right side jacket panel.
3. Use the wire nuts provided to ensure a tightand secure connection.
4. The unit is provided with a service switch,check local code requirements for compli-ance.
If local electrical codes or conditionsrequire an additional service switch, theinstaller must provide and install a fuseddisconnect or 15 amp (minimum) serviceswitch.
Thermostat Wiring
1. Connect room thermostat or the end switch(isolated contact only) of a relay controlpanel to the Room Thermostat Snap-setlocated on the rear jacket panel.
2. Remove the snap-set cover and connect thethermostat wiring to terminals C and 1 perFigure 32.
3. For proper operation install the room ther-mostat on an inside wall away from influ-ences of heat and cold, i.e. water pipes,
areas of draft, lighting fixtures and fire-places.
4. Set the thermostat anticipator (if applica-ble) as follows:
- Set for 0.2 amps when wired directly tothe Room Thermostat Snap-set.
- Set to match the total electrical powerrequirements of the connected deviceswhen wired to zone relays or otherdevices. Refer to the relay manufactur-ers’ specifications and the thermostatinstructions for additional informationon the anticipator setting.
Outdoor Temperature Limit
1. The PERFORMANCE PLUS may operatewith a variable primary operating tempera-ture using an outdoor reset control provid-ed by the installer.
2. Remove the factory jumper across termi-nals 9 and 10 of the wiring terminal.Connect the outdoor limit control to thoseterminals.
3. Set the operating limits of the outdoor limitcontrol as follows:
- Maximum operating temperature of180ºF.
– Minimum operating temperature of150ºF.
4. Set the primary thermostat to the highestpossible setting.
NOTICE
Fig. 32: Room Thermostat Snap-set Wiring
External Wiring
To PERFORMANCE PLUS "Room Thermostat"
Snap Set
H H
High Voltage
120V.A.C.
24V.A.C.
RoomThermostat
RoomThermostat
Zone 1
Zone 2
Additional zones Additional zones maybe added as shown above
Transformer(Power)
ZoneValve
Zone Valve
* Isolation relay
1
C
44
4 Wire Zone Valve
Fig. 33: Multiple Zone Field Wiring Using Zone Valves
3 Wire Zone Valve
*Use isolation relay on 3-wirezone valve with non-isolatedend switch. Transformer andthe PERFORMANCE PLUScontrol can burn out if isolationrelay is not used.
H H
High Voltage
120V.A.C.
24V.A.C.
RoomThermostat
RoomThermostat
Zone 1
Zone 2
Additional zones Additional zones maybe added as shown above
To PERFORMANCE PLUS "Room Thermostat"
Snap Set
Transformer(Power)
ZoneValve
Zone Valve
C 1
45
External Wiring
T T
To PERFORMANCE PLUS " Room Thermostat"
Snap Set
CirculatorZone 1
Thermostatzone 1
HoneywellR845ARelay
120H
VACN
CirculatorZone 2
Thermostatzone 2
Additional zones may beadded as shown above
C 1
62 1 4 3 5
62 1 4 3 5
T T
T T
Fig. 34: Field wiring with zone circulators.
46
External Wiring
ThermostatZone 1
Zone 1Circulator
120VN
PERFORMANCE PLUS "Room Thermostat"
Snap-Set
Zone 2Circulator
Zone 3Circulator
ThermostatZone 2
ThermostatZone 3
R C T1 T1 T2T2 T3 T3
C3C3C2C2C1C1PRPRX2X1L1L2 ZC
HC 1
Fig. 35: Typical Zone Relay Panel Wiring
T T
BronzeCirculator
Storage TankThermostat
HoneywellR845ARelay
H
120VAC
62 1 4 3 5
T T
N
Fig. 36: Storage Tank Recirculation Wiring
47
Start-Up Preparations
SECTION X - Start Up PreparationCheck System and Domestic WaterChemistry
Do not use petroleum-base cleaning orsealing compounds in the primary sys-tem. Damage to seals and gaskets in thesystem components could occur, result-ing in substantial property damage.
System water including additives must bepractically non-toxic, having a toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products.
Water pH Level 6.0 to 8.0
Maintain the primary system water pHbetween 6.0 and 8.0. Check using litmuspaper or contact a water treatment compa-ny for a chemical analysis.
If the pH does not meet this requirement,do not operate the PERFORMANCEPLUS or leave the unit filled until the con-dition is corrected.
Water Hardness Less Than 7 Grains
For areas with unusually hard water (hard-ness above 7 grains) consult a water treat-ment company.
Chloride Concentration Less Than 80 mg/L
For those installations that use a water soft-ener or conditioner, consult the water treat-ment company.
Any water conditioning system mustbe installed and maintained in accor-dance with the water conditioner’smanufacturer’s specifications andwithin the operating guidelines of thePERFORMANCE PLUS.
Chlorinated Water
Do not use the PERFORMANCE PLUSinner or outer tank to heat a swimming poolor spa directly.
Maintain the chlorine level of the water inthe inner and outer tanks at levels consid-ered safe for drinking.
Flush Primary and Domestic System toRemove Sediment
The installer must flush both the primaryand domestic system to remove any sedi-ment to allow proper operation of the PER-FORMANCE PLUS.
Flush the systems until the water runs cleanand is free of sediment.
For primary zoned systems, each zoneshould be flushed through a purge valve.Purge valves and isolation valves should beinstalled on each zone to allow for properflushing of the system.
Check and Test Antifreeze
For primary systems containing antifreezesolutions, follow the antifreeze manufac-turer’s instructions in verifying theinhibitor level and to ensure the fluid char-acteristics are within specification require-ments.
Due to the degradation of inhibitors overtime, antifreeze fluids must be periodicallyreplaced. Refer to the manufacturer of theantifreeze for additional instructions.
NOTICE
NOTICE
WARNING
48
Start-Up Preparations
System water including additives must bepractically non-toxic, having a toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products.
Use of Antifreeze in the Primary System
NEVER use automotive or ethylene gly-col antifreeze or undiluted antifreeze inthe primary system as freeze protection.This can cause severe personal injury,death or substantial property damage ifignored.
Determine the antifreeze fluid quantityusing the system water content volume andfollowing the antifreeze manufacturerinstructions.
The primary outer tank volume of the PER-FORMANCE PLUS is 20 gallons.Remember to include the volume of theexpansion tank.
Check with local codes requirements forthe installation of back flow preventers oractual disconnect from the make up watersupply line.
Ensure the concentration of antifreeze towater does not exceed a 50/50 ratio.
System water including additives must bepractically non-toxic, having a toxicityrating or Class of 1, as listed in ClinicalToxicology of Commercial Products.
Filling the Inner (Domestic) Tank andSystem
Proceed with filling instructions for theinner and outer tanks only after ensur-ing the water meets the requirementslisted in this installation manual. Failureto comply could result in damage andimproper operation of the unit.
Never operate the PERFORMANCEPLUS unless both the inner and outertanks are completely filled.
Always fill the inner tank prior to fillingand pressurizing the outer tank. Failureto properly fill the inner tank couldresult in damage to the inner tank.
1. Ensure the domestic drain valve is closed.
2. Open the isolation valves on the domesticcold supply piping to the PERFOR-MANCE PLUS and on the domestic hotoutlet piping to the building.
3. Vent any air from the domestic piping sys-tem by opening faucets near the unit.Continue filling the domestic system untilthere is a constant flow of water from thefaucets.
4. Close the hot water faucets.
Filling the Outer (Primary) Tank andSystem
1. Close the primary drain valve locatedon the rear of the unit and any manualor automatic air vent in the system.
2. Open all system isolation valves.
CAUTION
CAUTION
WARNING
NOTICE
WARNING
NOTICE
49
Start-Up Preparations
3. Fill the outer tank to correct systempressure. Correct pressure will varywith each application.
Typical residential system fill pressure is12 psi. System pressure will increasewhen system temperature increases.Operating pressure of the system shouldnever exceed 25 psi.
4. Allow air to escape from the outer tank byopening the automatic air vent providedwith the PERFORMANCE PLUS.
5. Purge air in each zone of the primary sys-tem through the purge valve. Open airvents to allow air to be purged in the zones.
6. Once the system is completely filled andpurged of all air, check the system pressureand check for leaks.
Check Low Water Cut-Off Device
- The PERFORMANCE PLUS is pro-vided with a factory installed LowWater Cut-Off device that measuressystem pressure of more than 10 psi.
- Remove the front jacket panel and checkfor continuity across the low water cut-off device wire terminals. The contactsshould be closed when system pressureis greater than 10 psi.
Check For Gas Leaks
Prior to start-up and during initial opera-tion, smell near the floor and around theunit for gas odorant or any unusual odor.Do not proceed with the start-up if thereis any indication of a gas leak. Any leaksfound must be repaired immediately.
DO NOT adjust or attempt to measuregas valve outlet pressure. The gas valveis factory-set for the correct outlet pres-sure. This setting is suitable for naturalgas and propane and requires no fieldadjustment. Attempts by the installer toadjust or measure the gas valve outletpressure could result in damage to thevalve, causing potential severe personalinjury, death or substantial propertydamage.
Propane installations only - The propanesupplier mixes an odorant with thepropane to make its presence detectable.In some cases the odorant can fade andthe gas may no longer have an odor.
Prior to start-up of the unit and periodi-cally after start-up have the propanesupplier check and verify the odorantlevel.
WARNING
WARNING
WARNING
NOTICE
PG PLUS Natural Gas Propane
Model (inch w.c.) (inch w.c.)
PG PLUS-25 1.84 " w.c. (yellow) 1.84" w.c. (yellow)
PG PLUS-30 2.7" w.c. (red) 2.7" w.c. (red)
PG PLUS-35 2.7 " w.c. (red) 2.7" w.c. (red)
PG PLUS-40 2.7 " w.c. (red) 3.35" w.c. (blue)
PG PLUS-45 2.7 " w.c. (red) 3.35" w.c. (blue)
Table 3 : Pressure Switch Setting
50
Start-Up Preparations
Verify Correct Pressure Switch
1. Remove the burner hood and verify theburner pressure switch setting.
2. Check and compare the color of the out-line on the pressure switch label to Table 3page 49.
The PERFORMANCE PLUS isequipped with an air pressure switch,which provides a safe means of shuttingdown the unit due to a blockage of thecombustion air inlet. The switch is “nor-mally closed” and measures the changein the negative pressure (vacuum) creat-ed by the burner blower.
Verify Correct Air Shutter Setting
- Check and verify the air shutter settingas listed in Table 4.
- The air shutter is located inside the com-bustion air inlet adapter located in thetop /left jacket panel area. See Fig. 37.
Check Thermostat Circuit
- Unplug the Room Thermostat Snap-setlocated on the rear of the unit.
- Connect a voltmeter across the end ter-minals of the male half of the RoomThermostat Snap-set.
- Close each thermostat, zone valve andrelay in the external circuit one zone ata time and check the voltage readingacross the plug.
- There should NEVER be voltage mea-sured at the plug.
- If voltage is measured at the plug underany condition, check and correct theexternal wiring.
In systems using 3-wire zone valvesbackfeed of voltage to the unit is a com-mon problem. Use an isolation relay toprevent voltage from the external circuitentering the Room Thermostat Snap-set.
NOTICE
NOTICE
Model Natural Gas Propane
PG PLUS-25 2.5 2.5PG PLUS-30 2.5 2.5PG PLUS-35 1 2.0PG PLUS-40 N/R 0PG PLUS-45 N/R 0
Table 4 : Air Shutter Settings
NR- Air shutter not required.
Fig. 37: Air Shutter Adjustment
51
Start-Up Procedures
SECTION XI - Start-Up Procedures
Final Checks Before Start-up
Verify the PERFORMANCE PLUSand the primary and domestic systemsare full of water and all system compo-nents are correctly set for operation.
Verify Start-up Preparation items outlinedon pages 51 thru 53 have been completed.
Verify all electrical connections arecorrect and securely fasten.
Inspect vent piping and combustion airinlet piping for signs of deterioration fromcorrosion, physical damage or sagging.Verify combustion air piping and vent pip-ing are intact and correctly installed.
Verify Burner Configuration - PropaneOnly.
Check for proper labeling on the gasvalve, combustion air inlet and the rat-ing label for propane configuration.
If there is doubt on the burner configu-ration, remove the gas valve and checkfor proper propane orifice. Refer toPropane Conversion Instructions foradditional information on assembly ofthe gas valve.
Adjustment of the Secondary ThermostatLimit.
The Secondary (Domestic) Thermostatlocated on left side of the control panelmaintains the minimum domestic waterstorage temperature.
Set the thermostat knob as shown inFigure 38 page 54.
Maximum limit setting is 140ºF
PERFORMANCE PLUS Start-up
1. Turn the ON-OFF switch located on thefront control panel to the OFF position.Turn the electrical supply or any serviceswitch to the unit in the ON position.
2. Read and follow the Operating Instructionsoutlined on page 52.
If PERFORMANCE PLUS Does Not StartCorrectly
1. Check for loose electrical connections,blown fuse or open service switch.
2. Check continuity across the Low WaterCut-Off device for close circuit.
3. Is the manual limit control open? Ensure themanual limit is reset to the close position.
4. Is the gas supply valve open at the unit andmeter?
5. Is incoming gas supply pressure more than5”w.c. for natural or propane.
6. Are the heating thermostats set below roomtemperature?
If none of these conditions correct the problem,refer to the PERFORMANCE PLUS Trouble-shooting guide.
Check the PERFORMANCE PLUS andSystem
Check Domestic Piping.
Check domestic piping and systemcomponents for leaks. If found, shutdown the unit and repair immediately.
Check Primary Piping.
Check primary system piping and com-ponents for leaks. If found, shut downthe unit and repair immediately.
Purge any remaining air from the systempiping. Air in the system piping willinterfere with circulation creating heatdistribution problems and system noise.
Check Vent Piping and Combustion AirPiping.
Check for gas-tight seal at every con-nection and seam of the venting andcombustion air inlet.
52
Start-Up Procedures
FOR YOUR SAFETY READ BEFORE LIGHTING
OPERATING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
1. STOP! Read the safety information above.
2. Set the secondary thermostat to the lowestsetting.
3. Turn manual shutoff valve on the gas supplyline clockwise to “Close”
4. Set the unit’s “ON-OFF” switch to “OFF”
5. This appliance is equipped with an ignitiondevice which automatically lights the pilot.Do not try to light the pilot by hand.
6. Turn manual shutoff valve on the gas supplyline counter clockwise to “Open”
7. Wait five (5) minutes to clear out any gas. Ifyou smell gas, STOP! Follow “B” in the
safety information stated above. If you don’tsmell gas, go to next step.
8. Set the unit’s “ON-OFF” switch to “ON”
9. Set the secondary thermostat to the desired set-ting. See Page 54 for recommended thermostatsettings.
10. If the appliance will not operate, follow theinstructions “To Turn Off Gas To Appliance”and call your service technician or gas supplier.
WARNING The following instructions must be followed exactly, a fire orexplosion may result causing property damage, personal injuryor loss of life.
1. Set the system thermostat to lowest setting.
2. Turn the unit’s “ON-OFF” switch to “OFF”
3. Turn manual shut-off valve on the gas supplyline clockwise to “Close”.
A. This appliance is equipped with an electron-ic ignition system. Do not attempt to lightthe burner by hand.
B. BEFORE OPERATING, smell all around theappliance area for gas. Be sure to smell nextto the floor because some gas is heavier thanair and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.
• Do not touch any electric switch; do notuse any phone in your building
• Immediately call your gas supplier from anearby phone. Follow the gas supplier’sinstructions.
• If you cannot reach your gas supplier, callthe fire department.
C. Do not use this appliance if any part has beenunder water. Immediately call a qualifiedservice technician to inspect the applianceand to replace any part of the control systemand any gas control which has been underwater.
53
Start-Up Procedures
Venting system must be sealed gas-tightto prevent flue gas spillage and potentialcarbon monoxide emissions, which willresult in severe personal injury or death.
Check Gas Piping
1. Check around the unit for gas odor fol-lowing the procedure outlined in thismanual on Page 49.
If any gas leaks are found or suspected,shut the unit down immediately. Use agas detection device or bubble test tolocate the source of the gas leak andrepair at once. Do not operate the unituntil the leak is corrected. Failure tocomply with this procedure could resultin severe personal injury, death or sub-stantial property damage.
Verify Flame Pattern and Combustion
Check the flame pattern through theinspection port of the burner. Theflame should be blue and stable. Theflame should be the length of the burn-er head openings.
Remove the test plug located on the fluehood and insert a combustion test probe.
Test for CO2 or O2 and for CO. Thecombustion reading should be withinthe range listed in Table 5. The COlevel should not exceed 100 ppm whencombustion is correct.
To adjust the combustion level open orclose the air shutter by a 1/2 setting.
- Closing the air shutter will decreasethe O2 level and increase the CO2level.
- Opening the air shutter will increasethe O2 level and decrease the CO2level.
A combustion test must be performedafter any adjustments are made. Allowthe unit to operate for approximately 10minutes after adjustment before measur-ing any combustion levels. Failure tocomply with these procedures couldresult in severe personal injury, death orsubstantial property damage.
Replace the test port plug when the com-bustion test is completed to prevent fluegas spillage into the building. Failure tocomply with this procedure could resultin severe personal injury, death or sub-stantial property damage.
Measure Input - Natural Gas Only
1. Operate the unit for approximately 10minutes.
2. Turn off all gas appliances within thebuilding.
3. At the gas meter, record the timerequired to use one cubic foot of gas.
4. Calculate gas input using the followingequation:
3600 x 1000 / number of second record-ed for one cubic of gas = BTU/H.
5. The BTU/H calculated should approxi-mate the input rating listed on the unit.
WARNING
WARNING
WARNING
WARNING
Natural Gas Propane
O2 Min. 3.00% 3.00%
O2 Max. 5.00% 5.00%
CO2 Min 9.00% 10.50%
CO2 Max 10.00% 12.00%
Table 5: Recommended Combustion Levels
545
Temperature Limits
SECTION XII - Temperature Limits
Studies have indicated that dangerousbacteria can form in the potable waterdistribution system if certain minimumwater temperatures are not maintained.For prevention of this, it is recommend-ed that the Secondary Thermostat be setas shown in Figure 38 and maintained at130ºF to 140ºF.
Setting Primary Thermostat Limit.
- The Primary (Space Heating) Thermostatlocated on the right side of the controlpanel acts as the high limit during thespace heating function.
- Set the thermostat knob as shown inFigure 39.
- Maximum limit setting is 180ºF
To ensure proper function of the limitsthe Primary Thermostat must be sethigher than the Secondary Thermostat.
Adjustment of Secondary Thermostat Limit
- The Secondary (Domestic) Thermostatlocated on left side of the control panelmaintains the minimum domestic waterstorage temperature.
- Set the thermostat knob as shown inFigure 38.
- Maximum limit setting is 140ºF.
To adjust the thermostat settings:
- Turn thermostat knob clockwiseto increase water temperature
- Turn thermostat knob counter-clockwise to decrease watertemperature.
NOTICE
NOTICE
DANGER
PhaseIII
-Ph
ase
III
- Phase III
-Phase
III-
citsemoD
Spac
ehe
atin
g
Temperature UpTemperature Down
Temperature Indicator
BackPlate
Knob
Fig. 38: Recommended SecondaryThermostat Setting
Phase
III-
Phase III -
Phase
III-
PhaseIII-
citse
moD
Spaceheating
Temperature UpTemperature Down
Temperature Indicator
BackPlate
Knob
Fig. 39: Recommended Primary ThermostatSetting
55
Temperature Limits
Setting the Thermostatic Mixing Valve
The thermostatic mixing valve controlsthe outlet hot water temperature deliv-ered to the faucets.
POTENTIAL SCALD HAZARD Themixing valve must be installed on thePERFORMANCE PLUS. Removal ofthe mixing valve will create a potentialscald hazard resulting in severe personalinjury or death.
- Use a L-Key to remove the set screwsecuring the knob to the valve.
- Remove the knob and lock ring fromthe valve.
- Replace the knob and adjust the settemperature of the valve to the desiredtemperature.
To calibrate the outlet temperature,allow the water to run for approximately2 minutes and measure the water with athermometer. To adjust the valve setting,rotate the knob clockwise to decrease thewater temperature or counter-clockwiseto increase the water temperature.
- Once the desired temperature isachieved, remove the knob and refit thelock ring onto the valve aligning thering indicator mark with the valve’s“Mix” marking.
- Locate the tab on the inner face of theknob into the retainer in the lockingring. Secure the knob with setscrew.
- Record the valve performance on theInstallation Record included in thismanual.
For proper operation of the thermostaticmixing valve, the manual valve on the U-tube assembly MUST remain open toavoid a potential scald hazard.
DANGER
NOTICE
WARNING
NOTICE
56
Check-Out Procedures
SECTION XIII- Check-Out Procedures
Perform the following check-out proce-dures as outlined and check off items ascompleted. When procedures are com-pleted, the installer should complete theinstallation record on page 57.
Check-out Procedures
Both inner and outer tanks filled withwater.
Water chemistry checked and verifiedas outlined on page 47.
The automatic air vent on the unit andany place within the system are openone full turn.
Air is purged from the heating zonesand primary system.
Domestic piping is purged of air andhas been checked for leaks.
Burner has been confirmed as properlyconfigured for Propane application. (Ifapplicable).
Thermostat circuit wiring checked andverified that no voltage is present to theRoom Thermostat Snap-set as outlinedon page 50.
Operating Instructions on page 52 werefollowed during start-up.
Combustion levels and flame patternverified as outlined on page 53.
Measure the rate of input on NaturalGas as outlined on page 53.
Check the incoming gas pressure toensure a minimum pressure of 5”w.cduring flow conditions and a maximumpressure of 13”w.c during non-flowconditions for natural and propane.
Primary and Secondary Thermostatproperly set as shown in Figure 38 and39 page 54.
The thermostatic mixing valve adjustedto the desired domestic hot outlet tem-perature.
Adjusted balancing valves and systemlimit controls to provide design temper-atures to the primary space heating sys-tem.
In multiple zone applications, adjustedfor correct flow of primary heatingwater to each zone.
Check and verified room thermostatfunction properly and the thermostatheat anticipator (if used) was properlyset.
Observed several operating cycles forproper operation of the PERFOR-MANCE PLUS and the system.
Set the room thermostat(s) to thedesired room temperature.
Reviewed all instructions shipped withthe PERFORMANCE PLUS with thehomeowner or maintenance personnel.
Complete the Installation Record onpage 57.
Ensure all manuals and other documen-tation are returned to the Installationenvelope and given to the owner forsafekeeping.
NOTICE
57
Installation Record
SECTION XIV - Installation Record
PERFORMANCE Model Number:
Serial Number:
Date of Installation:
Fuel: Natural Gas Propane
Measured Rate of Input:
Thermostatic Mixing Valve Setting:
Measured Domestic Outlet Temperature:
Combustion Readings:
CO2
O2
CO
The following items were completed during installation:
�� Installation instructions have been followed and completed
�� Check-out procedures have been followed and completed
�� Information regarding the unit and installation received and left with owner / maintenance�� personal.
Installer Information
(Company)
(Address)
(Address)
(Phone Number)
Btu/hr
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
_________________________________________________________________
%
%
ppm
58
Maintenance Schedule
SECTION XV - Maintenance ScheduleService Technician
At least on an annual basis the following main-tenance should be performed by a qualified ser-vice technician:
General
• Attend to any reported problems.
• Inspect the interior of the combustionchamber; clean and vacuum if necessary.
• Clean the condensate trap in the ventsystem and fill with fresh water.
• Check for leaks; water, gas, flue andcondensate.
• Verify flue vent piping and air inlet pip-ing are in good condition and sealedtight.
• Check primary system water pressure/primary system piping/primary expan-sion tank.
• Check domestic water pressure/domes-tic system piping/domestic thermalexpansion tank.
• Check domestic and primary thermo-stat settings.
• Check ignition electrode (sand off anywhite oxide; clean and reposition).
• Check ignition wiring and groundwiring.
• Check all control wiring and connections.
• Check burner flame pattern (stable anduniform) and flame.
Additional items if combustion or performanceis poor:
• Clean baffles and flue ways.
• Remove burner assembly and cleanburner head using compressed air only.
Once the maintenance items are completed,review the service with the owner.
Owner Maintenance
Daily:
• Check the area around the unit.
• Check the combustion air inlet and ven-tilation openings for blockage.
• Check the temperature/pressure gauge.
Monthly:
• Check vent piping.
• Check combustion air inlet piping.
• Check the pressure relief valve.
• Check the temperature/pressure reliefvalve.
• Check the vent condensate drain system.
• Check the automatic air vents in the pri-mary system.
Every 6 months:
• Check both primary piping and gassupply piping for corrosion or potentialsigns of leakage.
• Operate the pressure relief valve.
• Operate the temperature/pressure reliefvalve.
Periodically:
• Check the operation of the domesticmixing valve.
Follow the maintenance proceduresgiven throughout this manual. Failureto perform the service and maintenanceor follow the directions in this manualcould result in damage to the PERFOR-MANCE PLUS or in system compo-nents, resulting in severe personalinjury, death or substantial propertydamage.
WARNING
59
Maintenance Procedures
SECTION XVI - MaintenanceProcedures
MAINTENANCE PROCEDURES
The PERFORMANCE PLUS should beinspected and serviced annually, prefer-ably at the start of the heating season, bya qualified service technician. In addi-tion, the maintenance and care of theunit as outlined on page 58 and furtherexplained on pages 59 through 62 shouldbe performed to assure maximum effi-ciency and reliability of the unit. Failureto service and maintain the PERFOR-MANCE PLUS and the system compo-nents could result in equipment failure,causing possible severe personal injury,death or substantial property damage.
The following information providesdetailed instruction for completing themaintenance items outline in the mainte-nance schedule on page 58. In additionto this maintenance, the PERFOR-MANCE PLUS should be serviced at thebeginning of the heating season by aqualified service technician.
Reported Problems
Any problems reported by the ownershould be checked, verified and correctedbefore proceeding with any maintenanceprocedures.
Check the Surrounding Area
Verify that the area surrounding the PER-FORMANCE PLUS is free of combustible/ flammable materials or flammable vaporsor liquids. Remove immediately if found.
Verify that air used for combustion is freeof any contaminates. Refer to the list ofpotential materials listed on page 7 of this
manual. If any of these products are in theroom from which the unit takes its com-bustion air, they must be removed immedi-ately or the combustion air intake must berelocated to another area.
Inspect the Burner Area
Remove the burner hood and inspect theappearance of the burner components.
Vacuum any dirt or debris from the burnercomponents.
Remove the venturi inlet elbow to check fordirt and debris. Remove any obstructions.
Do not use solvents to clean any of theburner components. The componentscould be damaged, resulting in unreli-able or unsafe operation.
Check System (Primary and Domestic)Piping
Inspect all piping on the Primary Heatingsystem and the Domestic system for leaksand verify that the piping is leak free.
Inspect the fittings and components on theunit and verify they are leak free.
Eliminate all primary water system leaks.Continual fresh make-up water willreduce the outer tank life causing tankfailure. Leaking water may also causesevere property damage to the surround-ing area.
WARNING
WARNING
NOTICE
WARNING
60
Maintenance Procedures
Check Combustion/ Ventilation Air Openings
Verify that all combustion air and ventila-tion openings to the mechanical room orbuilding are open and unobstructed. Checkthe operation and wiring of any automaticventilation dampers.
Check and verify the vent discharge and thecombustion air intake are free of debris andobstructions.
Inspect Vent System and Combustion AirPiping
Visually inspect the venting system andcombustion air piping (if installed) forblockage, deterioration or leakage. Repairany vent joints that show signs of deterio-ration as per the vent manufacturer’sinstructions.
When combustion air is ducted to the unit,verify that the air inlet piping is connectedand sealed. Inspect the air hose connectingthe air inlet adapter to the venturi elbow fordeterioration.
Failure to inspect the vent system andcombustion air inlet piping and have anyconditions repaired can result in severepersonal injury or death.
Check Primary System
Verify all system components are correctlyinstalled and operating correctly.
Check the cold fill pressure for the system,typical cold water fill pressure is 12 psig.
Verify the system pressure as the unit oper-ates at high temperature to ensure the pres-sure does not exceed 25 psig. Excessivepressure reading indicates expansion tanksizing is incorrect or system performanceproblems.
Inspect air vent and air separators in thesystem. Remove the caps on automatic airvents and briefly depress the valve stem toflush vent. Replace the cap when complet-ed. Ensure vents do not leak, replace anyleaking vents.
Check Domestic System
Verify all system components are correctlyinstalled and operating correctly.
Check the outlet domestic temperature ofthe mixing valve and compare with therecorded temperature made during start-up.
Check Expansion Tank
Refer to Section V - Primary Piping forrecommended location of the expansiontank and air eliminators.
Close -Type Tank:
- Ensure tank is partially filled withwater leaving an air gap as a cushion.Refer to the manufacturer’s instructionfor proper fill level.
- Ensure the tank is fitted with a devicethat reduces gravity circulation of air-saturated tank water back into the sys-tem. This device prevents air frombubbling up through the water as itreturns from the system.
- Ensure no automatic air vents are usedin the system. This will allow air toescape from the system instead ofreturning to the tank.
Diaphragm Tank:
- Ensure the system contains a minimumof one automatic air vent. Preferredlocation of the air vent should be atopan air eliminator.
- Remove the tank from the system andcheck the charge pressure. For residen-tial applications the charge pressure istypically 12 psig. If tank does not holda charge pressure, then the membrane isdamaged and the tank should bereplaced.
WARNING
61
Maintenance Procedures
Check Boiler Relief Valve
Inspect the relief valve and lift the lever toverify flow at least annually or as recom-mended on the warning tag of the valve.
Before manually operating the pressurerelief valve ensure the discharge piping isdirected to a suitable place of disposal toavoid a potential scald hazard. The dis-charge piping must be full size withoutrestriction and installed to permit com-plete drainage of both the valve and line.
If after closing the valve, the valve fails toseat properly or continually weeps, replacethe relief valve. Ensure the cause of therelief valve to weep is the valve itself, notdue to system over-pressurization causedby an expansion tank that is waterlogged orundersized.
Check Temperature / Pressure Relief Valve
Inspect the T&P relief valve and lift thelever to verify flow at least annually or asrecommended on the warning tag of thevalve.
Before manually operating the pressurerelief valve ensure the discharge piping isdirected to a suitable place of disposal toavoid a potential scald hazard. The dis-charge piping must be full size withoutrestriction and installed to permit com-plete drainage of both the valve and line.
If after closing the valve, the valve fails toseat properly or continually weeps, replacethe relief valve. Ensure the cause of theweeping is the valve itself, not due to ther-mal expansion or a faulty or under-pressur-ized thermal expansion tank.
Inspection of Ignition Electrode
Remove the ignition electrode from theburner mounting plate.
Remove any white oxides accumulated onthe electrode using fine grit sandpaper orsteel wool. If the electrode does not clean toa satisfactory condition, replace the ignitor.
When replacing the ignition electrode,ensure the gasket is in good condition andcorrectly positioned.
Check Ignition Wiring and Ground Wiring
Inspect the burner wiring from the burnercontrol module to the ground terminalbehind the control panel.
Ensure wiring is in good condition andsecurely connected.
Check ground continuity of the wiringusing a continuity meter.
Replace and correct ground wire if groundcontinuity is not completed and satisfactory.
Check Control Wiring
Inspect all control wiring located behindthe control panel and at the burner controlmodule. Ensure wiring is in good condi-tion and properly connected.
Check Thermostat Limit Settings
Check the position of the Secondary andPrimary Thermostat knobs, refer to Figure 38and 39 page 54 for recommended settings.
Perform Start-up and Checkout Procedures
Start the unit and perform the start-up pro-cedure as listed in this manual.
Verify the cold water fill pressure is correctand the operating pressure of the primarysystem is within normal operating range.
Complete the checkout procedures as refer-enced in this manual.
WARNING
WARNING
62
Maintenance Procedures
Check Burner Flame
Inspect the burner flame through the obser-vation port on the burner mounting plate.
If flame pattern is not fully blue and coversthe entire burner surface, shut the unitdown and allow it to cool thoroughly.
Close the manual gas valve on the gas sup-ply line and disconnect the gas piping toremove the burner assembly from the unit.
Remove the burner head mounting screwsand remove the burner head. Inspect thehead for deterioration. Use compressed airor a vacuum to clean the burner head.
Remove the venturi and gas valve assem-bly from the blower.
Use the vacuum cleaner or compressed airto clean the interior of the blower assembly.Inspect the blower blades to ensure they areclean and not damage.
Re-assemble the venturi and gas valve ontothe blower. Ensure the venturi gasket is ingood condition and positioned correctly.
Re-assemble the burner head onto themounting plate. Ensure the burner headgasket is in good condition and positionedcorrectly.
Re-assemble the gas supply connection andopen the manual gas valve placing the unitback into service.
Flame Signal
The flame signal should be at least 0.6µ Α.Refer to the PERFORMANCE PLUSTrouble-shooting Guide for information onchecking the flame signal.
Check the ignitor for fouling or damagedinsulation if a low flame signal is read.
Check ground wiring and continuity as acause for low flame signal. Replace ignitorif conditions are satisfactory.
Check Combustion Levels
Refer to page 53 of this manual for mea-suring combustion levels and burneradjustments.
Review With Owner
Ensure the owner understands the impor-tance to perform the maintenance schedulespecified in this manual.
Remind the owner of the importance to calla licensed contractor should the unit or sys-tem exhibit any unusual behavior.
63
Replacement Parts
SECTION XVII - Replacement Parts
Replacement Parts
Replacement parts can be ordered andpurchased through a local Triangle Tubedistributor. When ordering parts, spec-ify the Model Number and SerialNumber. Include a description of thepart and a replacement part number.Using modified or other manufacturerparts will not be covered by warrantyand may damage or cause improperfunction of the unit.
Refer to pages 64 and 67 for descriptionand replacement part numbers.
NOTICE
WARNING
Replacement Parts
64
5
1
3
4
2
6
Fig. 40: Jacket Components
Item Part No. Description Quantity required by Model
PG PLUS-25/ 30/35 PG PLUS-40/45
HMJKTF25 Complete Jacket Set 1
HMJKTF40 Complete Jacket Set 1
HMJKT25F Jacket, Front 1
HMJKT40F Jacket, Front 1
HMJKT25L Jacket, Left side 1
HMJKT40L Jacket, Left side 1
HMJKT25R Jacket, Right side 1
HMJKT40R Jacket, Right side 1
HMJKT25B Jacket , Back 1
HMJKT40B Jacket , Back 1
HMJKT25TOP Jacket, Top cover 1
HMJKT40TOP Jacket, Top cover 1
6 PGRKIT20 Low Water Cut-Off Device LWCO 1 1
HMHOO06 1 1Burner Jacket Hood5
1
2
3
4
65
Replacement Parts
Item Part No. Description
Operating Thermostat
Primary or Secondary
Manual Reset Hight Limit
Pre-set at 205ºF
Auto Reset High Limit
Pre-Set at 194ºF
Temperature / Pressure
Gauge
Control Panel
PGRKIT21
PGRKIT 22
HMCS01
PGRKIT23
HMGAU01
7
11
8
9
10
11
9
810
7
7
Fig. 41: Control Panel Components
66
Replacement Parts
Item Part No. Description
R1 Relay - Controls
Burner Function
R2 Relay - Controls
Domestic Priority & Circulator
120 V-24 V 40VA
Transformer13 PGRKIT18
12A PGRKIT19
12B PGRKIT 19
12A
12B
24V Circuit
13
120 V Circuit
14 13 1211 10 9 8 7 6 5
4 32 1 G
Fig. 42: Electrical Panel Components
Part No. Description
HMRLV01 Pressure Relief Valve 30 psi
P3AVT01 Air Vent
HMVLV07 Thermostatic Mixing valve 3/4"
HNSNP02 Snap sets Male / Female
HMTPV01 Temperature/Pressure Relief Valve (PG PLUS-30/35/40/45 only)
HMTPV03 Temperature/Pressure Relief Valve (PG PLUS-25 only)
67
Replacement Parts
16
19
17
15
14
Venturi
18
Burner InsulationGasket
Fig. 43: Burner Components
Item Part Number Description Where Used
14 PGRKIT01 Gas valve replacement kit ALL
PGRKIT02 PG PLUS-25 Blower / motor replacement kit PG PLUS-25
PGRKIT03 PG PLUS-30 Blower / motor replacement kit PG PLUS-30
PGRKIT04 PG PLUS-35 Blower / motor replacement kit PG PLUS-35
PGRKIT05 PG PLUS-40 Blower / motor replacement kit PG PLUS-40
PGRKIT06 PG PLUS-45 Blower / motor replacement kit PG PLUS-45
PGRKIT09 Burner head replacement kit PG PLUS-25/30/35
PGRKIT10 Burner head replacement kit PG PLUS-40/45
PGRKIT11 Pressure switch replacement kit with 1.84" w.c.
pressure switch
PGRKIT12 Pressure switch replacement kit with 2.7" w.c. See Table 3
pressure switch Page 49
PGRKIT13 Pressure switch replacement kit with 3.35" w.c.
pressure switch
PGRKIT14 Ignitor replacement kit PG PLUS-25/30/35
PGRKIT17 Ignitor replacement kit PG PLUS-40/45
19 PGRKIT16 UT Ignition control module replacement kit ALL
18
15
16
17
Specifications
68
22"
9"
15"
A
Fig. 45: Rear ViewFig. 44: Side View
5"11.5"
14"
21"
C
6
3
Domestic�cold Domestic�
hot
1
2
B
8"
5
410
1. Primary circuit, ø 1” NPT
2. Primary circuit drain valve connection, ø 1/2” NPT
3. Domestic temperature/pressure relief valve (150psi), ø 3/4” NPT
4. Primary circuit & pressure relief valve (30 psi), ø 1”NPT
5. Domestic cold water inlet, ø 3/4” NPT
6. Hot water outlet & secondary thermostat sensor, ø3/4” NPT
7. Manual reset safety sensor & pressure indicator sen-sor, ø 3/4” NPT
8. Primary thermostat sensor, temperature indicatorsensor and automatic reset safety sensor, ø 1/2”NPT
9. L.W.C.O. pressure sensor, ø 1/2” NPT (shown asitem 6 on page 66)
10. Primary circuit & air vent, ø 1” NPT
10
8
5
34
7
6
Fig. 46: Top View
Specifications
69
Table 7: PERFORMANCE PLUS Data
Table 6: Dimensional Data
Type PG PLUS-25 PG PLUS-30 PG PLUS-35 PG PLUS-40 PG PLUS-45Input Nat. Gas Btu/hr 100,000 120,000 140,000 165,000 199,000
Inner Tank Capacity Gal 17 17 17 22 22
Outer Tank Capacity Gal 20 20 20 18 18
Dimensions Inches
A 59 59 59 67 67
B 54 54 54 62.5 62.5
C 54.5 54.5 54.5 63.5 63.5
Vent outlet size 3 3 3 3 3
TP Valve (domestic) ø 3/4" 3/4" 3/4" 3/4" 3/4"
Domestic water ø 3/4" 3/4" 3/4" 3/4" 3/4"
Primary connection ø 1 " 1 " 1 " 1 " 1 "
Drain ø 1/2" 1/2" 1/2" 1/2" 1/2"
Empty weight lb 345 345 345 485 485
Heat exchanger surface Sq. Ft. 17 17 17 26.5 26.5
2
1
2
3
4
5
6
7
4 6 8 10 12 14 16
Hea
d L
oss
(Ft.
)
Flow Rate (gpm)
Graph 1: PERFORMANCE PLUS Pressure Loss - Primary Side
Model 10 Min. Peak 1st Hour Continuous Flow Combustion AFUE HeatingFlow Rating @ 80ºF Rise Efficiency Capacity
(gallons) (gallons) (gph) (%) (%) MBH
PG PLUS-25 54 162 130 86.3 86.1 86PG PLUS-30 59 187 155 85.7 85.6 102PG PLUS-35 64 212 180 85.5 85.2 119PG PLUS-40 75 250 210 86.0 85.7 141PG PLUS-45 80 290 255 85.5 85.2 170
Additional quality water heating equipment availablefrom
Triangle Tube/Phase III
- Exclusive “Tank-in-Tank” design- Stainless steel construction- Available in 8 sizes and 2 models- Limited LIFETIME residential warranty- 15 year limited commercial warranty- Self cleaning/self descaling design
- Construction of high quality corrosion resistant stain-less steel (AISI 316)
- Specially designed built-in flow restrictor to assuremaximum heat exchange
- Compact and light weight- Available in 5 sizes that can accommodate any size
pool or spa
TTP Brazed Plate Heat Exchangers
- For domestic water, snow melting, radiant floor,refrigeration
- Plates made of stainless steel, with a 99.9 % copperand brazed, ensuring a high resistance to corrosion
- Self cleaning and self descaling- Computerized sizing available from Triangle
Tube/Phase III- Available in capacities from 25,000 BTU/hr to
5,000,000 BTU/hr
Phase III Indirect Fired Water Heaters
Maxi-flo Pool and Spa Heat Exchangers
Freeway Center - 1 Triangle Lane - Blackwood, NJ 08012Tel: (856) 228 8881 - Fax: (856) 228 3584http://www.triangle tube.comE-mail: Info@triangle tube.com
Member of
Group