Page 1: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

+ 4 4 ( 0 ) 1 4 6 0 5 3 5 3 5i n f o @ p o w r m a t i c . c o . u kw w w . p o w r m a t i c . c o . u k

Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to change, amend or vary specifications without notice. Whilst the details contained herein are believed to be correct they do not form the basis of any contract and interested parties should contact the Company to confirm whether any material alterations have been made since publication of this brochure.

Ireland Office

Get in touch

Powrmatic LimitedHort BridgeIlminsterSomersetTA19 9PS

tel: +44 (0) 1460 53535fax: +44 (0) 1460 52341e-mail: [email protected]: www.powrmatic.co.uk

United Kingdom OfficePowrmatic Ireland

45 Broomhill CloseTallaght

Dublin 24

tel: +353 (0) 1452 1533fax: +353 (0) 1452 1764

e-mail: [email protected]: www.powrmatic.ie

F O R T H E L A T E S T N E W S , C A S E S T U D I E S , A N D T E C H N I C A L S U P P O R T F O L L O W U S O N

#keepingthenationwarm

Powrmatic are a leading British manufacturer of industrial and commercial heating equipment. With over 60 years of experience in the HVAC industry, our

products are built with integrity, and characterised by high quality and energy-saving designs, delivering exceptional performance and facilitating

compliance with energy and emission regulations.

Powrmatic are also a specialist British manufacturer of natural, powered and smoke ventilation products working closely with a wide range of architects and consultants whilst also a supplier of a range of air conditioning and evaporative

cooling equipment.

We provide a full product application advice service for architects, mechanical engineers, installers and end users to ensure the best products are selected to meet the required budget, design and regulatory requirements. Our heating and ventilation engineers are also supported by distribution partners and a network of installers who are knowledgeable

in the supply, installation and maintenance of all of our equipment.

ErP READY2 0 1 8 P O W R M A T I C P R O D U C T

EURO-AIRQUALITYICOM

Energy Association

Industrial & Commercial Heating SystemsOUH Suspended Oil Unit Heater

Page 2: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

Powrmatic CPxI N D U S T R I A L & C O M M E R C I A L W A R M A I R H E A T I N G S O L U T I O N

Lorem ipsum dolor s i t amet, consectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. Ut enim ad minim veniam, quis nostrud exercitat ion ul lamco laboris nis i ut a l iquip ex ea commodo consequat. Duis aute i rure dolor in reprehenderit in voluptate vel i t esse ci l lum dolore eu fugiat nul la par iatur. Excepteur s int occaecat cupidatat non proident, sunt in culpa qui off ic ia deserunt mol l i t anim id est laborum

C U S T O M E R B E N E F I T S

T Y P I C A L A P P L I C A T I O N S

• Warehouses• Factor ies• Garage Workshops• Distr ibut ion Centres• Aircraft Hangers

• Lorem ipsum dolor s i t amet

Lcon sectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. •Duis aute i rure dolor in reprehenderit in voluptate vel i t esse ci l lum •

Lorem ipsum dolor s i t amet, consectetur adipiscing el i t , •Lcon sectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. •

GAS

OIL

LPG

G20 - GROUP H / G25 GROUP L

35 SEC FUEL (STANDARD) 28 SEC FUEL (OPTIONAL)

PROPANE G31

I N D U S T R I A L & C O M M E R C I A L H E A T I N G S O L U T I O N S

Powrmatic OUHThe OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a stainless steel heat exchanger as standard and a downwards firing pressure jet oil burner. The OUH heater can be supplied in axial fan freeblowing format, to be installed directly into the space to be heated, or with centrifugal fan for ducted applications.

The OUH range of oil fired unit heaters is comprised of 4 models with outputs ranging from 20kW to 60kW.

Heaters are generally arranged for on/off operation however they may also be specified with high/low heat output. Freeblowing models are fitted with axial fan sets and discharge warmed air directly into the heated space via adjustable louvred horizontal louvres. Centrifugal fan models are fitted with a centrifugal fan close-coupled directly to the heater casing foruse on ducted applications.

OIL GAS OIL (35 SEC) / KEROSENE (28 SEC) / BIO FUEL

Models Available• OUH F - Freeblowing Oil Unit Heater• OUH C - Centrifugal Oil Unit Heater• OUH D - Ducted Oil Unit Heater

Installation Benefits• Compact in size• Stainless steel combustion chamber as standard• Bio fuels options• Standard models single phase

Peace Of Mind• More than sixty years experience in warm air• Two year parts and one year labour guarantee• Ten-year time related heat exchanger warranty• Full technical support

Working With The HVAC TradePowrmatic philosophy is to work in partnership with our customers establishing a long-term commitment to a relationship based on understanding the expectations of customers and a dedicated common goal.

By working with our customers we can deliver solutions that enable them to meet technical and regulatory challenges they face, fulfil their clients needs effectively and economically, and gain a competitive edge.

Efficiency and ErP ComplianceFrom 1st January 2018 all warm air heaters used to provide comfort for the occupants of a heated space are required to meet minimum standards of ‘seasonal’ efficiency as determined by the Ecodesign regulation (EU) 2015/1188, Directive 2009/125/EC - Lot 21 Tier 1. Compliance to the standard is mandatory.

The calculation for seasonal efficiency takes into account air flow, temperature rise across the heat exchanger, electrical power consumption as well as the usual thermal efficiencies.

OUH oil suspended unit heaters placed on the market after 1st January 2018 comply with the requirements of the standard.

Installers and customers will note that in pursuit of increased efficiency when ErP legislation is implemented OUH heaters will no longer be available in on/off configuration other than for non-personnel heating applications. For most space heating applications high/low heat output will be standard with modulation as an option..

ErP READY2 0 1 8 P O W R M A T I C P R O D U C T

ErP READY2 0 1 8 P O W R M A T I C P R O D U C T

2

Page 3: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

Powrmatic CPxI N D U S T R I A L & C O M M E R C I A L W A R M A I R H E A T I N G S O L U T I O N

Lorem ipsum dolor s i t amet, consectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. Ut enim ad minim veniam, quis nostrud exercitat ion ul lamco laboris nis i ut a l iquip ex ea commodo consequat. Duis aute i rure dolor in reprehenderit in voluptate vel i t esse ci l lum dolore eu fugiat nul la par iatur. Excepteur s int occaecat cupidatat non proident, sunt in culpa qui off ic ia deserunt mol l i t anim id est laborum

C U S T O M E R B E N E F I T S

T Y P I C A L A P P L I C A T I O N S

• Warehouses• Factor ies• Garage Workshops• Distr ibut ion Centres• Aircraft Hangers

• Lorem ipsum dolor s i t amet

Lcon sectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. •Duis aute i rure dolor in reprehenderit in voluptate vel i t esse ci l lum •

Lorem ipsum dolor s i t amet, consectetur adipiscing el i t , •Lcon sectetur adipiscing el i t , sed do eiusmod tempor incididunt ut labore et dolore magna al iqua. •

GAS

OIL

LPG

G20 - GROUP H / G25 GROUP L

35 SEC FUEL (STANDARD) 28 SEC FUEL (OPTIONAL)

PROPANE G31

C U S T O M E R B E N E F I T S

Energy efficient •Range of sizes and configurations •

Space saving ‘off-floor’ location • Bio fuel option available •

Colour (RAL) options •Manufactured in the UK •

A P P R O V E D P R O D U C T

T Y P I C A L A P P L I C A T I O N S

• Car Garages & Workshops• Warehouses• Factories• Distribution / Logistic Centres• Aircraft Hangars• Horticultural & Garden Centres• Showrooms• Retail Outlets

ConstructionThe heater is of unitary construction and complete with suspension mounting lugs for easy installation. The cabinet is finished with a durable epoxy powder coat stove baked paint.

Combustion Heat ExchangerFormed from folded and welded AISI430 grade stainless steel and comprising of a central combustion chamber and twin plate heat exchanger retort sections manifold to a common flue heater.

BurnersOUH heaters are specifically matched to Riello pressure jet oil burners. heaters are arranged, as standard, for operation on Class D light distillate fuel oil (35 second). Alternatively Kerosene (28 second) firing is available to order. Biofuel options are available, please consult with Powrmatic Technical Support.

Air MovementAxial fan heaters are fitted with a single fan set and discharge warmed air directly into the heated space via adjustable horizontal louvres. Vertical louvres are available as an option where lateral air discharge is required.

Centrifugal fan models benefit from a close coupled fan which discharges warmed air via a duct outlet spigot suitable for the onward connection of ductwork. A comprehensive range of accessories are available.

ControlsAs standard OUH heaters are supplied with approved safety controls including high limit protection and flame monitoring.

For comfort and fuel efficiency connection terminals are provided for independent time, temperature and ‘fan only’ control. Alternatively we recommend that heaters be connected to compatible Powrmatic digital control systems -

•MC200 (control of single units)•MC300 Multi (control of multiple units)

Note: Interconnecting wiring for all controls is the responsibility of the installer.

Approvals Heaters placed on the market subsequent to 1st January 2018 meet the seasonal efficiency requirements of ErP Lot 21 Tier 1.

3

Page 4: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

Technical Specification

Model 20 30 45 60

Output (nominal)High Fire (Max) kW 20 30 45 60

Low Fire (Min) kW 14 21 31 42

Airflow

Volume

OUH F / C m3/s 0.58 0.68 1.08 1.41

OUH DMin m3/s 0.37 0.56 0.83 1.11

Max m3/s 0.56 0.83 1.25 1.67

Throw OUH F m 8.5 16 25 34

Fan Static OUH C Pa 140 187 100 50

Electrics

SupplyStandard V/ph/Hz 230/1/50

Optional V/ph/Hz 415/3/50

OUH FStart Current amp 2.26 1.14 2.44 6.65

Run Current amp 0.94 0.50 1.06 2.90

OUH CStart Current amp 6.50 18.0 18.0 18.0

Run Current amp 4.20 7.20 7.20 7.20

Fuel OilConnection BSP/Rc ¼

Consumption l/h 2.17 3.19 4.89 6.51

Mounting Height OUH FMin m 2.50 3.00

Max m 3.00 5.00

OverallDimensions

Height mm 880 1117 1117 1117

Width mm 555 780 780 780

DepthOUH F mm 753 1106 1118 1140

OUH C mm 1038 1469 1469 1469

Installation Clearances

Top mm 1000

Side mm 500

Rear mm 400

Flue diameter mm ø 100 125

Combustion Air Spigot mm ø 150

Maximum Combustion Duct Length * m 120 100 81 21

Noise Level - OUH F models dB(A) 46 54 52 53

Nett WeightOUH F kg 53 126 126 126

OUH C kg 91.5 142 142 142

Notes:

• Fuel consumption and output figures based upon nett calorific value as follows: - Class D light distillate fuel oil Nett CV 36.28 MJ/l• OUH heaters have efficiency levels which comply with the requirements of United Kingdom Part L Building Regulations and the seasonal efficiency requirements of the Ecodesign regulation

(EU) 2015/1188, Directive 2009/125/EC – Lot 21 Tier 1 (Known as ErP and mandatory as from 1st January 2018) • Air handling data is assessed at room ambient conditions • Throw figures provide the distance to the point where the terminal velocity degrades to 0.25 m/s• Noise levels refer to OUH F axial fan models and measured 5m from appliance and in free field conditions• Where NVxD heaters are to be applied installers should be aware of both the minimum and maximum airflows as well as a need for fan over-run facilities to protect the heater. It is

recommended that you consult with Powrmatic Technical Support prior to product selection and installation• Motor, run and start amps apply to standard electrical supply as stated. For optional data contact sales • Combustion air spigot is an optional extra• For extended combustion duct lengths please contact Powrmatic Technical Support• For Installer guidance notes see page 7

4

Page 5: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

DimensionsOUH F 20 - Axial Freeblowing Fan

A

øD

B

CM

K

A

øD

B

CM

L

A LB

CM

A K

FEF

B

CM

FEF

H

J

H

J

50

50

G

G

235

235

G E F

G E F

ØD

ØD

Model A B C D E F G K M

OUH F 20 668 555 610 100 465 101 549 85 270

A

øD

B

CM

K

A

øD

B

CM

L

A LB

CM

A K

FEF

B

CM

FEF

H

J

H

J

50

50

G

G

235

235

G E F

G E F

ØD

ØD

OUH F 30/45/60 - Axial Freeblowing Fan

Model A B C D E F G K M

OUH F 30 975 780 847 125 490 276 490 131 270

OUH F 45 975 780 847 125 490 276 490 143 270

OUH F 60 975 780 847 125 490 276 490 165 270

5

Page 6: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

Dimensions

OUH C 30/45/60- Centrifugal Fan Unit

A

øD

B

CM

K

A

øD

B

CM

L

A LB

CM

A K

FEF

B

CM

FEF

H

J

H

J

50

50

G

G

235

235

G E F

G E F

ØD

ØD

Model A B C D E F G H J L M

OUH C 30 975 780 847 125 490 276 490 636 418 494 270

OUH C 45 975 780 847 125 490 276 490 636 418 494 270

OUH C 60 975 780 847 125 490 276 490 636 418 494 270

Model A B C D E F G H J L M

OUH C 20 668 555 610 100 465 101 549 410 340 370 270

A

øD

B

CM

K

A

øD

B

CM

L

A LB

CM

A K

FEF

B

CM

FEF

H

J

H

J

50

50

G

G

235

235

G E F

G E FØ

D

OUH C 20 - Centrifugal Fan Unit

6

Page 7: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

GeneralThe following notes are provided as a guide, however installers and users should fully acquaint themselves with the more detailed guidance provided in the relevant Installation, Operation and Maintenance Manual. For copies of such manuals please consult our technical department or visit our website - www.powrmatic.co.uk

StandardsOUH heaters must be installed, commissioned and operated with due regard to appropriate regulations including but not limited to relevant Codes of Practice, the possible requirements of Local Authorities, Fire Officers and insurers as the relevant Installation, Operation and Maintenance Manual.

Position & Location Powrmatic OUH heaters can be ‘drop rod’ suspended via purpose designed M10 suspension fixing points, attached to our optional wall support brackets or positioned on a level non-combustible base. In all cases it is important that all supporting structures have due regard to the relevant weight loadings.

Consideration should also be given to flue routes and points of exit, oil, electrical and control connections, the throw characteristics of the heater, issues of public access and the siting of environmental control stations and/or remote temperature sensors where the position needs to be representative of the zone temperature to which they refer.

Heaters should not be installed in hazardous areas or areas where there is a foreseeable risk of flammable or corrosion inducing particles, gases or vapours being drawn into the combustion air or main fan circuits

Areas where special consideration or advice may be required could include but is not limited to -

• Where de-greasing solvents are present, even in minute concentrations • Where paint spraying is carried out • Where styrenes or other laminating products are used • Where airborne silicone is present • Where petrol engined vehicles are stored or maintained • Where dust is present (ie wood working or joinery shops) • Where high levels of extract persist

Installation in such areas may be possible under specific conditions. Please consult our technical department or your local sales manager for further information.

Plant Room or Enclosure Locations It is possible to install centrifugal fan variants of the OUH heater within plant rooms or enclosures however specific requirements may need to be applied. Such requirements cover the provision of positive ductwork connections as well as ventilation for combustion air and general plant room or enclosure ventilation. It is recommended that you consult with our technical department or the Installation, Operation and Maintenance Manual.

Combustion Air & General Ventilation Our recommendation is that where a heater is installed directly within the heated space and where that heated space has a natural ventilation rate greater than 0.5 air changes per hour

then combustion air and general heater ventilation is probably not required.

If the heated space has a natural ventilation rate of less than 0.5 air changes per hour then either natural ventilator openings or mechanical ventilation may be required. Please consult the relevant Installation, Operation and Maintenance Manual for further details.

Installation ClearancesParticular clearances may be necessary for the correct and safe function of the heater as well as for maintenance purposes. Such clearances are confirmed in the relevant Installation, Operation and Maintenance Manual.

Flue OUH heaters are supplied with a 90° flue tee that has a flue gas analysis sample point. For internally located heaters each heater requires a separate flue system of the appropriate size. The flue should essentially be installed in the vertical plane and the number of bends kept to a minimum.

The flue must be adequately supported and terminated with a suitable cowl, with due regard to the point of exit and it’s proximity to any windows, doors or ventilation intakes.

External heaters are supplied complete with a primary flue section and cowl which provides the direct discharge of flue gases directly to atmosphere. Care should be taken to ensure that the flue discharge is not in anyway restricted or the exit point such that flue gases can enter a building.

If the application requires it may be possible to extend the flue of external heaters to enable the point of discharge to be reposi-tioned. However should this be necessary then the diameter of flue must not be less than stated in the data sections of this brochure.

DuctworkOUH heaters can be fitted with distribution ductwork and/or inlet or return air duct connections. In such circumstances the OUH C centrifugal fan model should be selected and install-ers must ensure that the combined duct resistances, including grilles, filters, dampers or other ductwork components are balanced to closely match the static pressure as shown on page 4 of this brochure. Insufficient or excessive duct resistance will compromise the performance of the heater. Please consult or technical department or your local area sales manager for further guidance.

Pipework Care should be taken when sizing pipework to ensure that maximum oil inlet pressures and flow rates are not compromised under dynamic load conditions. Isolating valves and service unions should be provided for each heater and pipework installed with due regard for relevant standards and Codes of Practice.

Guarantee Powrmatic heaters are provided with a comprehensive guarantee covering both the heater and the heat exchanger. For United Kingdom sales the heater has the benefit of a two year parts and one year labour guarantee. The combustion chamber/heat exchanger has a ten year time related sliding scale warranty. All guarantees are subject to terms and conditions.

Your Installer Guide

2 YEAR

1 YEAR

10 YEAR

PARTS WARRANTY

LABOUR WARRANTY

TIME RELATED HEAT EXCHANGER WARRANTY7

Page 8: OUH Suspended Oil Unit Heater - Powrmatic OUH Oil Unit Heaters are indirect oil fired suspended warm air heaters with a ... and in free field conditions • Where NVxD heaters are

+ 4 4 ( 0 ) 1 4 6 0 5 3 5 3 5i n f o @ p o w r m a t i c . c o . u kw w w . p o w r m a t i c . c o . u k

Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to change, amend or vary specifications without notice. Whilst the details contained herein are believed to be correct they do not form the basis of any contract and interested parties should contact the Company to confirm whether any material alterations have been made since publication of this brochure.

Ireland Office

Get in touch

Powrmatic LimitedHort BridgeIlminsterSomersetTA19 9PS

tel: +44 (0) 1460 53535fax: +44 (0) 1460 52341e-mail: [email protected]: www.powrmatic.co.uk

United Kingdom OfficePowrmatic Ireland

45 Broomhill CloseTallaght

Dublin 24

tel: +353 (0) 1452 1533fax: +353 (0) 1452 1764

e-mail: [email protected]: www.powrmatic.ie

F O R T H E L A T E S T N E W S , C A S E S T U D I E S , A N D T E C H N I C A L S U P P O R T F O L L O W U S O N

#keepingthenationwarm

Powrmatic are a leading British manufacturer of industrial and commercial heating equipment. With over 60 years of experience in the HVAC industry, our

products are built with integrity, and characterised by high quality and energy-saving designs, delivering exceptional performance and facilitating

compliance with energy and emission regulations.

Powrmatic are also a specialist British manufacturer of natural, powered and smoke ventilation products working closely with a wide range of architects and consultants whilst also a supplier of a range of air conditioning and evaporative

cooling equipment.

We provide a full product application advice service for architects, mechanical engineers, installers and end users to ensure the best products are selected to meet the required budget, design and regulatory requirements. Our heating and ventilation engineers are also supported by distribution partners and a network of installers who are knowledgeable

in the supply, installation and maintenance of all of our equipment.

ErP READY2 0 1 8 P O W R M A T I C P R O D U C T

EURO-AIRQUALITYICOM

Energy Association

Issue 5.5 ErP 2018