Page 1: Kelvin

KELVIN S.r.l. ITALY Street Enrico Fermi ZAI 46040 Ponti sul Mincio (MN)

Tel. ++39 0376 809651 Fax ++39 0376 809648www.kelvinitaly.it

KELVIN

Release 05/2001

AIR CONDITIONING SYSTEMS FOR ENCLOSURES

COOLING POWER

CE

I N D U S T R I A L D I V I S I O N

www.erdin

cklim

a.com

Page 2: Kelvin

A conditioned enclosure absorb or dissipate heat through its walls according to its material, dimensions and the difference between internal enclosures and ambient temperature (t). This value is determinate by a simple calculation

2(m x t x5)W, (as assuming the enclosure made in steel, transfer coefficient = 5), see the selection chart below for a quick reference:

First question to ask in order to select the appropriate cooling equipment is: “Can the internal enclosure temperature be higher than the external ambient temperature ?

, we will choose between an air conditioner and a water to air heat exchanger. In this case, the heat absorbed by the enclosure, at specified limit conditions, has to be added to the heat dissipated by the internal components. Using an air conditioner can be maintained constant the internal enclosure temperature, independently from the variation of outside ambient temperature. If an air conditioner is used, it is suggested to keep the internal temperature to a minimum of 30°C to avoid condensate water production when an operator will open the enclosure door. Temperatures lower than 30°C may cause the installed components to be covered of condensate water when warmer external air enter in the enclosure.

, we will choose an air to air heat exchanger or a forced ventilation system, that uses filtered primary air. In this case the heat absorbed by the enclosure, at specified limit conditions, has to be removed from the heat dissipated by the installed components. Air to air heat exchanger cooling capacity is measured in W/K, this value indicates how many Watt the heat exchanger can remove for every degree of temperature difference between internal enclosure temperature and external ambient temperature. For example, a 30 W/K cooling capacity heat exchanger can remove 450W of heat, if ambient temperature is 35°C and internal enclosure temperature is 50°C (i.e. 50-35 = 15 difference of temperature x 30 = 450W).Only as an indication, heat dissipation by components can be calculated using the below table:

transformers drivers, PLC, numerical controls , inverters suppliers moving-coils relay, contactors incandescent lamps heaters

If the answer is NO

If the answer is YES

Help

30

25

20

15

10

0

0 125 250 375 500 625 750 875 1000 1125 1250 1375 1500 1625 1750 1875 2000 2125 2250

∆t °C m²

W

5

2 3 4 5 6 7 8 9 10 11 12 13 14 15

Above table only give approximate values for components. Particular attention should be given to high power components and it is suggested to consult the component's manufacturer in order to obtain an accurate value and to avoid wrong calculations of heat dissipation.

AVAILABLE POWER SUPPLIES

ABCDELTPQRVW

230 1 50230 1 60230 1 50 / 60110 - 115 1 50 / 60440 - 480 3 60415 3 60400 - 415 3 50400 2 50400 2 60440 - 480 2 6024 V DC48 V DC

from 2 to 5%5%

10%3%

100%100%

www.erdin

cklim

a.com

Page 3: Kelvin

Air conditioners

Air to water heat exchangers

Air to air heat exchangers

Anticondensation heaters

Accessories

From pag. 10 to pag. 29

From pag. 36 to pag. 39

pag. 40

Pag. 42

Index

Ventilation

Pag. 41

LOW MAINTENANCE Units marked with this symbol require only air filter cleaning and no other periodical maintenance.

ANTI-CONDENSATE DEVICEThis device collects condensate and evaporates this off into the ambient atmosphere, thus ensuring that the air left inside the machine is dry and the surfaces are moisture-free.

From pag. 30 to pag. 35

Sales network

Pag. 43

NO MAINTENANCE Units marked with this symbol do not require any periodical maintenance.

ENERGY SAVING This symbol indicates that the product has been designed to optimise its energy consumption according to the provided working conditions. (DIN3168L35L35).

OZON FRIEND Is the symbol that represents Kelvin's permanent commitment in preserving the environment around us. All refrigeration techniques take environmental protection into consideration by using cloro-fluoro-carbon-free (CFC) refrigerants, which are not harmful to the ozone layer.

www.erdin

cklim

a.com

Page 4: Kelvin

10

KMV

Standard Optionals

he KMV is a very compact air conditioner for vertical installation on the outside face of the door or wall of an enclosure, especially designed for applications where space is limited, like small control panels. It is suitable for low cooling capacities. The condensate drain is positioned on the Tbottom of the air conditioner. Four M6 threaded inserts will enable easy screw-on installation.

CE

MODEL:

Standard power supply (C)Running currentStarting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 self adhesive gasket

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

Internal control thermostat set at 35° C.

Polyurethane air filter

Aluminium air filter

User manual in five languages

KMV 03

230 - 50/601,2 / 1,46,2 / 6,2

2330 / 347248 / 257216 / 247

R134a27

20 - 5554346217

C, D

V - HzAAAWWW

bar°CIPIP

dB (A)kg

50

0

170 280

www.erdin

cklim

a.com

Page 5: Kelvin

KUR

Standard Optionals

CE

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Internal terminal board for wiring

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

User manual in five languages

Protected terminal board IP30

Non standard painting

3 meters power supply cableconnected in therminal board

Aluminium or

polyurethane air filter

Inlet 3 pole connector

Free voltage contact for dirty filter and max temperature alarm

Noise filter for power supply line

he KUR05 and KUR09 are two compact air conditioners designed to be installed on the outside face of the door or wall of an enclosure. These can also be installed internally or semi-concealed using an optional mounting frame. They are made from galvanised steel with an easily removable Tcover with rounded edges. KUR05 and KUR09 are both designed to operate without an air filter, available as an option and recommended if the

working environment is particularly dusty or oily. The condensate drain is positioned at the bottom of the air conditioners. Six M6 threaded inserts will enable easy screw-on installation.

11

KUR 05

2,1 / 2,57,9 / 9,3

4600 / 630450 / 480395 / 461

6728

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KUR 09

2,8 / 3,311,3 / 12,3

4850 / 892637 / 663525 / 611

6829

60

5

215 305

SE

MI-

CO

NC

EA

LE

D A

SS

EM

BLY

INT

ER

NA

L A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

230 - 50/60

R134a27

20 - 555434

C, D

www.erdin

cklim

a.com

Page 6: Kelvin

12

he KUJ05 and 09 are two air conditioners designed to be installed on the outside face of the door or wall of an enclosure. These can also be installed semi-concealed using an optional frame. The large distance between the inlet and outlet of the internal circuit (enclosure side) helps to keep an even Ttemperature in the cabinet. KUJ models are made from galvanised steel with an easily removable cover with rounded edges. On the front, an

aluminium grid conceals the air filter and gives the air conditioner a pleasant look thanks to its design. The condensate drain is positioned at the bottom. Six M6 threaded inserts will enable easy screw-on installation.

KUJ

Standard Optionals

Protected terminal board IP30

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Non standard painting

Internal terminal board for wiring

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

3 meters power supply cableconnected in therminal board

Aluminium air filter

Inlet 3 pole connector

Free voltage contact for dirty filter and max temperature alarm

Noise filter for power supply line

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

70

0

190 350

CO

VE

R F

OR

IN

TE

RN

AL

AS

SE

MB

LY

SE

MI-

CO

NC

EA

LE

D A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

INT

ER

NA

L A

SS

EM

BLY

KUJ 05

2,2 / 2,78,2 / 9,7

4600 / 630450 / 480445 / 516

6725

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KUJ 09

2,9 / 3,511,6 / 12,7

6850 / 892637 / 663570 / 666

6829

230 - 50/60

C,D

R134a27

20 - 555434

www.erdin

cklim

a.com

Page 7: Kelvin

KUN

User manual in five languages

Standard

Non standard painting

Optionals

IP54 protected electrical parts

Protection for voltage peaks

CE

Electrical control board

- keeps temperature at set point- visualises temperature inside the control board- provides voltage free contacts for dirty filter and high temperature alarms- protected programming access (within 1' from power-on)

he KUN series of air conditioners are designed to be installed on the outside face of the door or wall of an enclosure.These can be also installed internally or semi-concealed using an optional frame. They are made from galvanised steel with an easily removable cover with rounded edges. On Tthe front, an aluminium grid conceals the air filter and gives the air conditioners a pleasant look thanks to its design.This product line is provided

with a water condensate dissipater and emergency condensate drain at the bottom. Six M6 threaded inserts will enable easy screw-on installation.

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 self adhesive gasket

Polyurethane air filter

Lifting eyebolts

Internal terminal board for wiring

Inlet 3 pole connector

Noise filter for power supply line

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Compressor start delay timer

OPTION: KUN10 and KUN20 230/1/50-60 without electronic diagnostic card are available on cCSAus comply version.

10

00

230 400

VE

RS

ION

WIT

H E

LE

CT

RO

NIC

CO

NT

RO

LL

ER

SE

MI-

CO

NC

EA

LE

D A

SS

EM

BLY

INT

ER

NA

L A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

ON

LY

WIT

H E

LE

CT

RO

NIC

CO

NT

RO

LL

ER

VE

RS

ION

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

13

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KUN 10

2,9 / 3,511,6 / 12,7

41050 / 1102778 / 819570 / 666

45

KUN 15

4,2 / 5,216,6 / 17,2

61360 / 14281020 / 1060830 / 1014

48

KUN 17

5,4 / 6,620,4 / 21,1

101720 / 18061290 / 13421050 / 1278

49

KUN 20

5 / 6,123,6 / 24,2

102000 / 21001500 / 15601045 / 1272

52C,D,E,P,Q,R,T

230 - 50/60

R134a27

20 - 55543470

C,D,P,Q,RC,D,P,Q,R C,D,P,Q,R

www.erdin

cklim

a.com

Page 8: Kelvin

14

KUN

Optionals

IP54 protected electrical parts

StandardStandard

CE

MODEL:

Standard power supply (A)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Non standard painting

Protection for voltage peaks

Inlet 3 pole connector

Noise filter for power supply line

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Compressor start delay timer

IP54 self adhesive gasket

Polyurethane air filter

Lifting eyebolts

Internal terminal board for wiring

User manual in five languages

OPTION: KUN40 400/3/50 and 440-460/3/60 without electronic diagnostic card are available on cCSAus comply version.

he KUN series of air conditioners are designed to be installed on the outside face of the door or wall of an enclosure.These can be also installed internally or semi-concealed using an optional frame. They are made from galvanised steel with an easily removable cover with rounded edges. On Tthe front, an aluminium grid conceals the air filter and gives the air conditioners a pleasant look thanks to its design.This product line is provided

with a water condensate dissipater and emergency condensate drain at the bottom. Six M6 threaded inserts will enable easy screw-on installation.

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KUN 40

6,8 / 33,2 /

3800 / 2850 / 1405 /

87

8,342,6

399029641744

KUN 30

6,7 / 37,2 /

2800 / 2100 / 1155 /

83

8,344,6

294021841444

230 - 50

10

R134a

2720 - 55

543472

A,B,E,T ( )60Hz

12

05

305 500

EX

TE

RN

AL

AS

SE

MB

LY

VE

RS

ION

WIT

HO

UT

EL

EC

TR

ON

IC C

ON

TR

OL

LE

R

SE

MI-

CO

NC

EA

LE

D A

SS

EM

BLY

Electrical control board

- keeps temperature at set point- visualises temperature inside the control board- provides voltage free contacts for dirty filter and high temperature alarms- protected programming access (within 1' from power-on)

www.erdin

cklim

a.com

Page 9: Kelvin

KUS

Standard

Noise filter for power supply line

Optionals

Internal control thermostat set at 35° C.

Compressor start delay timer

IP54 protected electrical parts

Aluminium air filter

he KUSs are designed for outdoor installations on walls or control board doors. With a depth of only 115mm, a painted cowling with rounded edges and the particular design of the aluminium front grill supporting the air filter, the KUS has all the features that offer an elegant cooling solution. The Tcompressor is positioned in the lower part of the air conditioner and provision must be made behind the door for the extra intrusion of the

compressor body beyond the depth of the KUS. Four M6 threaded inserts are provided for installation. The condensate outlet is positioned on the lower part of the air-conditioner.

Gasket roll

User manual in five languages

CEInternal terminal board for wiring

MODEL:

Standard power supply (C)Running currentStarting currentProtection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Inlet 3 pole connector

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

Protection for voltage peaks

15

15

10

115+60 400

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KUS 10

3,3 / 412,3 / 13,7

41000 / 1050

750 / 780645 / 756

43

KUS 15

4,3 / 5,216,9 / 17,4

61450 / 15221088 / 1131860 / 1014

48

KUS 17

5,5 / 6,720,7 / 21,2

81700 / 17851275 / 13261080 / 1278

49

KUS 20

5,1 / 6,223,9 / 24,4

82000 / 21001500 / 15601075 / 1272

46

230 - 50/60

R134a27

20 - 55

543470

C,D

EX

TE

RN

AL

AS

SE

MB

LY

www.erdin

cklim

a.com

Page 10: Kelvin

16

KSL

Standard Optionals

CE

he KSL “slim line” air-conditioners are designed to be installed vertically inside and outside the control board. This new product line represents the latest technical innovation from Kelvin's research and development department. All parts are accessible by simply removing the front panel, so Teliminating the need to remove the unit from the control board. This model can be used with or without an air filter. The condensate is collected and

then dissipated into the external ambient. This unit can be installed outdoors without worrying about associated air pollutants.

NEW

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Inlet 3 pole connector

Free voltage contact for dirty filter and max temperature alarm

3 meters power supply cableconnected in therminal board

Aluminium air filter

Noise filter for power supply line

Non standard painting

IP54 protected electrical parts

Internal terminal board for wiring

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

Slim line

15

00

190 400

INT

ER

NA

L A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

VE

RS

ION

WIT

H A

IR F

ILT

ER

V - HzAAAWWW

bar°CIPIP

dB (A)kg

230 - 50/60

R134a27

20 - 55

543469

KSL 10

2,4 / 2,812 / 13

41050 / 1102778 / 819425 / 465

KSL 15

3,6 / 4,215 / 18

61490 / 15451150 / 1200650 / 715

C,D,P,Q,R50

Electrical control board (KUN)

www.erdin

cklim

a.com

Page 11: Kelvin

KSL Slim line

Standard Optionals

CE

he KSLs are designed for simple installation. The drilling template is common to all models, thus allowing interchangeability of unit sizes if the need to increase cooling power became necessary. In the internal mounted version the air-conditioner's front side, 20 mm thick, is leaned on the Tcontrol board's panel covering so possible aesthetic defects.

NEW

MODEL:

Standard power supply Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 protected electrical parts

Internal terminal board for wiring

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

Inlet 3 pole connector

Free voltage contact for dirty filter and max temperature alarm

Electrical control board (KUN)

3 meters power supply cableconnected in therminal board

Aluminium air filter

Noise filter for power supply line

Non standard painting

15

00

220 400

VE

RS

ION

E S

EN

ZA

FIL

TR

O A

RIA

INT

ER

NA

L A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

17

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KSL 20

230 - 50/60 (C)4,7 / 5,622 / 24,2

82100 / 22001500 / 1560870 / 1050

20 -55

56C,D,E,P,Q,R,T

KSL 40

230 - 50 (A)8,5 / 29 /

103300 / 2450 / 1220 /

20 - 50

65A,B,E,T ( )

9,334,8

349025201464

60Hz

KSL 30

230 - 50 (A)5,6 / 26 /

102900 / 2190 / 1055 /

R134a27

20 - 5554347065

A,B,E,T ( )

6,231

302022651344

60Hz

www.erdin

cklim

a.com

Page 12: Kelvin

KZM

18

Standard Optionals

Compressor start delay timer

IP54 protected electrical parts Protection for voltage peaks

Lifting eyeboltsElectric module (KUN)

he KZM60 and 80 air conditioners are designed for side panel mounting. They are made from steel and painted and measure 2000mm high by either 600mm or 800mm wide respectively. These units are designed so that one unit can provide conditioned air to up to 6 cabinet modules in a Trow, supplying the air via a channel in the floor. Particular care has been taken when designing the KZM range of products to give the optimum

performance/consumption ratio. The water condensate drain is positioned at the bottom. Eight M6 threaded inserts will enable easy screw-on installation.

Gasket roll

CE

Internal terminal board for wiring

MODEL:

Standard power supply (T)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Polyurethane air filter

Internal control thermostat set at 35° C.

User manual in five languages

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

Aluminium air filter

KZM 60

6 / 21,4 /

85700 / 4275 /2340 /

150

6,923,2

5985 44462928

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KZM 80

7,6 / 30,4 /

107500 / 5625 / 3140 /

160

8,532,2

78755850 3828

20

00

380600 KZM60

800 KZM80

400 - 3 - 50

3454

20 - 5527

R407C

72

E,L,T ( )60Hz

EX

TE

RN

AL

AS

SE

MB

LY

EX

TE

RN

AL

AS

SE

MB

LY

KZM60 KZM80

www.erdin

cklim

a.com

Page 13: Kelvin

19

KB

Standard

Inlet 3 pole connector

noise filter for power supply line

Optionals

he KB 04 is a very compact air-conditioner and is particularly suitable for fitting on the top of small control boards which require minimal cooling within limited room conditions. The internal recycled cooled air is parallel to KB04s longitudinal axis. Four M6 threaded inserts are provided for Tinstallation. The condensate outlet is positioned on the unit's rear side.

CE

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 self adhesive gasket

Polyurethane air filter

Internal control thermostat set at 35° C.

User manual in five languages

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

KB 04

230 - 50/601,9 / 2,26,8 / 6,9

4490 / 515368 / 382360 / 419

R134a27

20 - 5554346722

C,D

V - HzAAAWWW

bar°CIPIP

dB (A)kg

25

0

500350

www.erdin

cklim

a.com

Page 14: Kelvin

20

KBhe KBs are air-conditioners designed to be fitted on the roof of control boards requiring a transverse cooled air path when compared to the KBs longitudinal axis. The supporting structure is made from galvanised steel sheet and an elegant aluminium grid supports the standard polyurethane Tair filter. Four M6 threaded inserts are provided for installation. The condensate outlet is positioned laterally on its right side.

Standard Optionals

CE

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Lifting eyebolts

Internal terminal board for wiring

Antifreeze thermostat

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

Inlet 3 pole connector

Noise filter for power supply line

Non standard painting

Condensate overflow safety

device (Acquablock)

Electrical control board (KUN)

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Compressor start delay timer

Protection for voltage peaks

IP54 protected electrical parts

30

0

600400

KB 10

2,9 / 3,511,6 / 12,7

61000 / 1050

750 / 780570 / 666

37

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KB 17

5,2 / 6,220 / 20

81650 / 17321237 / 12871005 / 1188

41

KB 15

230 - 50/604 / 4,8

16,2 / 16,46

1450 / 1522 1087 / 1131

785 / 924R134a

2720 - 55

54347041

C,D,P,Q,R

www.erdin

cklim

a.com

Page 15: Kelvin

KB

Standard

Lifting eyebolts

Inlet 3 pole connector

Noise filter for power supply line

Non standard painting

Optionals

Condensate overflow safety

device (Acquablock)

IP54 protected electrical parts

CE

Internal terminal board for wiring

Antifreeze thermostat

MODEL:

Standard power supply Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Compressor start delay timer

Protection for voltage peaks

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

21

KB 20

230 - 50/60 (C)5 / 6,1

23,7 / 24,28

2000 / 21001500 / 15601050 / 1272

54C,D,E,P,Q,R,T

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KB 40

230 - 50 (A)6,8 /

33,2 / 10

3800 / 2850 / 1405 /

63A,B,T,E ( )

8,342,6

399029641744

60Hz

KB 30

230 - 50 (A)6,9 /

37,6 / 10

2800 / 2100 / 1115 /

R134a27

20 - 5554346560

A,B,T,E ( )

8,945,8

294021841370

60Hz

40

0

800400

Electrical control board (KUN)

www.erdin

cklim

a.com

Page 16: Kelvin

22

KT

Standard Optionals

CE

he KTs are a range of air-conditioners designed to be fitted on the roof of a cabinet with a cold air recycle path parallel to its longitudinal axis. Its supporting structure is made from galvanised steel sheet and an elegant aluminium grid supports the standard polyurethane air filter. Four M6 Tthreaded inserts are provided for installation. The condensate outlet is positioned on the unit's rear side.

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Lifting eyebolts

IP54 protected electrical parts

Internal terminal board for wiring

Antifreeze thermostat

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

Inlet 3 pole connector

Noise filter for power supply line

Non standard painting

Condensate overflow safety

device (Acquablock)

Electrical control board (KUN)

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

Compressor start delay timer

Protection for voltage peaks

35

0

400 600

KT 10

2,9 / 3,511,6 / 12,7

61000 / 1050

750 / 780570 / 666

37C,D,P,Q,R

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KT 17

5,2 / 6,220 / 20,2

81700 / 17851275 / 13261005 / 1188

41C,D,E,P,Q,R,T

230 - 50/60

R134a27

20 - 55543467

www.erdin

cklim

a.com

Page 17: Kelvin

KT

Standard

Noise filter for power supply line

Non standard painting

Optionals

Compressor start delay timer

Protection for voltage peaks

Electrical control board (KUN)

Condensate overflow safety device (Acquablock)

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 protected electrical parts

Internal terminal board for wiring

Antifreeze thermostat

IP54 self adhesive gasket

Internal control thermostat set at 35° C.

Polyurethane air filter

User manual in five languages

Inlet 3 pole connector

3 meters power supply cableconnected in therminal board

Aluminium air filter

Free voltage contact for dirty filter and max temperature alarm

23

MODEL:

Standard power supply (A)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

KT 35

230 - 506,8 /

33,2 / 10

3500 / 2625 / 1350 /

R134a27

20 - 5554347264

A,B,E,T ( )

8,342,6

365027301700

60Hz

V - HzAAAWWW

bar°CIPIP

dB (A)kg

45

0

460 800

Lifting eyebolds

www.erdin

cklim

a.com

Page 18: Kelvin

KCN

24

Standard

Inlet 3 pole connector

Optionals

he KCN is an air conditioner for 19” rack cabinets. It has an aluminium front panel 6U high. Two handles on the front provide easy installation into an enclosure. Both the air intake and outlet of the external circuit are located on the front of the unit and so there is no need for cutouts through the Tenclosure side panels. The condensate drain is positioned on the front side of the unit.

Compressor start delay timer

IP54 protected electrical parts

Washable aluminium air filter

CE

Antifreeze thermostat

MODEL:

Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Internal control thermostat set at 35° C.

User manual in five languagesNon standard painting

Internal terminal board for wiring

Protection for voltage peaks

Noise filter for power supply line

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

26

6

545 445

KCN 05

2,2 / 2,78,2 / 9,7

4600 / 630450 / 480445 / 516

25

V - HzAAAWWW

bar°CIPIP

dB (A)kg

KCN 10

230 - 50/602,9 / 3,5

11,6 / 12,76

850 / 892637 / 663570 / 666

R134a27

20 - 5554346737

KCN 15

4 / 4,816,2 / 16,4

61450 / 1522 1087 / 1131

785 / 924

41

483

C,D

www.erdin

cklim

a.com

Page 19: Kelvin

KWS

30

Standard Optionals

he air-water heat exchanger KWS20 KELVIN is unique in representing the best in compactness and design. It is silent, long lasting and totally free of ordinary maintenance. It represents an optimised product designed to reach elevated performances. This offers the best choice when it comes to Tprohibitive working temperatures. Four M6 threaded inserts are provided for fixing onto the cabinet.

CE

NEW

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

Internal control thermostat set at 35° C.

Internal terminal board for wiring

User manual in five languages

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

IP54 self adhesive gasket

MODEL:

Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies

V - HzWW AA

m³/hbar°CIP

dB (A)kg

KWS 20

230 - 50/6029 / 28

635 - 250 lit/h0,2 / 0,4

1330

5-5 +70IP551/2”5012

C,D,V,W

60

0

110250

www.erdin

cklim

a.com

Page 20: Kelvin

KWS

31

Optionals

he KWS air to water heat exchangers can reach high cooling capacities with small dimensions. They represent the best choice if the working environment is particularly dusty, oily or hot. KWS offer IP55 protection rating and are very silent and reliable, with almost no maintenance Trequired. Six M6 threaded inserts will enable easy screw-on installation.

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

MODEL:

Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies

Standard

Internal control thermostat set at 35° C.

Internal terminal board for wiring

User manual in five languages

IP54 self adhesive gasket

V - HzWWAA

m³/hbar°CIP

dB (A)kg

KWS 30

230 - 50/6080 / 98

1600 - 200 lit/h0,36 / 0,44

2550

5-5 +70IP551/2”6015

C,D,W

60

0

160300

www.erdin

cklim

a.com

Page 21: Kelvin

KWS

32

Optionals

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

MODEL:

Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies

Standard

Internal control thermostat set at 35° C.

Internal terminal board for wiring

User manual in five languages

IP54 self adhesive gasket

V - HzWWAA

m³/hbar°CIP

dB (A)kg

10

00

200400

KWS 70

230 - 50/6085 / 90

3400 - 400 lit/h0,38 / 0,4

2850

5-5 +70IP551/2”6529

C,D,W

he KWS air to water heat exchangers can reach high cooling capacities with small dimensions. They represent the best choice if the working environment is particularly dusty, oily or hot. KWS offer IP55 protection rating and are very silent and reliable, with almost no maintenance Trequired. Six M6 threaded inserts will enable easy screw-on installation.

www.erdin

cklim

a.com

Page 22: Kelvin

KWS

Optionals

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard painting

MODEL:

Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies

Standard

Internal control thermostat set at 35° C.

Internal terminal board for wiring

User manual in five languages

IP54 self adhesive gasket

33

V - HzWWAA

m³/hbar°CIP

dB (A)kg

12

00

250450

KWS 90

230 - 50/60130 / 180

5400 - 600 lit/h0,57 / 0,80

21230

5-5 +70IP551/2”6834

C,D,W

www.erdin

cklim

a.com

Page 23: Kelvin

KWS

34

Standard Optionals

Internal control thermostat set at 35° C.

he air-water heat exchangers KWS 100 and 120 are designed to reach elevated cooling performances. They are realized inside carpentry modules planned on purpose to be placed side by side to the cabinets, obtaining so an optimal aesthetic integration. Due to their functional characteristics Tthese products are very simple, silent, long lasting and completely free of ordinary maintenance and represent the best choice in cases of prohibitive

working temperatures. Eight M6 threaded inserts are provided for fixing on the control board.

Internal terminal board for wiring

Gasket roll

NEW

MODEL:

Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

Free voltage contact for dirty filter and max temperature alarm

Non standard paintingUser manual in five languages

V - HzWWAA

m³/hbar°CIP

dB (A)kg

KWS 100

15012500 - 2000 lit/h

0,66

125

380600 KWS100

20

00

800 KWS120

KWS 120

30014000 - 2000 lit/h

1,3

135

230 - 50/60

42340

5-5 +70IP55

1”69

C,P,T

KWS100 KWS120

CE

www.erdin

cklim

a.com

Page 24: Kelvin

36

MODEL:

Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies

KSAhe KSAs 18-19 are air-air heat exchangers, which are particularly suitable for side or door installations on small control boards and other small enclosures which require minimal cooling within limited room conditions. These two models use four axial fans, which provide improved air Tcirculation and temperature distribution. The external circuit fans can be controlled by a DIN bar thermostat, saving energy and reducing noise.

The control board circuit fans have to run permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.

Standard

Adjustable DIN bar thermostat to control external circuit fans

3 meters power supply cableconnected in therminal board

Optionals

External air path deflector

Inlet 3 pole connector

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP54 self adhesive gasket

User manual in five languages

Internal air path deflector

Non standard painting

38

0

134 316

INT

ER

NA

L A

SS

EM

BLY

EX

TE

RN

AL

AS

SE

MB

LY

KSA 18

12360,21

24024036

-10 +55IP54

8

V - HzW/KWAA

m³/hm³/h

dB(A)°CIPkg

KSA 19

23570,31

38038048

-10 +55IP54

8C,D,V,W

230 - 50/60www.erdin

cklim

a.com

Page 25: Kelvin

KSAhe KSAs 20-23 are air air heat exchangers designed to be fitted on the side, the door or the roof of control boards. The reduced depth to high performance ratio makes this one of the best product lines that the market can offer. Thanks to their high flow rate and head pressure , the radial fans Tensure a correct air circulation and an unvarying temperature distribution. The external circuit fan can be controlled by a DIN bar thermostat,

saving energy and reducing noise. The inside circuit fan runs permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.

Standard Optionals

IP55 protection degreeIP55

CE

MODEL:

Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

3 meters power supply cableconnected in therminal board

External air path deflector

IP54 self adhesive gasket

User manual in five languages

Adjustable DIN bar thermostat to control external circuit fans

Inlet 3 pole connector

Internal air path deflector

Non standard painting

86 3187

82

EX

TE

RN

AL

AS

SE

MB

LY

INT

ER

NA

L A

SS

EM

BLY

37

KSA 20

371600,71

55055065

-5 +55IP5410

V - HzW/KWAA

m³/hm³/h

dB(A)°CIPkg

KSA 23

471600,71

55055065

-5 +55IP5411

C,D,V,W

230 - 50/60www.erdin

cklim

a.com

Page 26: Kelvin

38

KSA

Standard Optionals

IP55

CE

MODEL:

Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP55 protection degree

3 meters power supply cableconnected in therminal board

External air path deflector

IP54 self adhesive gasket

User manual in five languages

Adjustable DIN bar thermostat to control external circuit fans

Inlet 3 pole connector

Internal air path deflector

Non standard painting

86 3187

82

DIM

A M

ON

TA

GG

IO E

ST

ER

NO

DIM

A M

ON

TA

GG

IO IN

CA

SS

O

V - HzW/KWAA

m³/hm³/h

dB(A)°CIPkg

KSA 42

371600,71

55055065

-5 +55IP5410

KSA 43

471600,71

55055065

-5 +55IP5411

C,D,V,W

230 - 50/60

he KSAs 42-43 and 21 are air air heat exchangers designed to be fitted on the side, the door or the roof of control boards. The reduced depth to high performance ratio makes this one of the best product lines that the market can offer. Thanks to their high flow rate and head pressure , the radial fans Tensure a correct air circulation and an unvarying temperature distribution. The external circuit fan can be controlled by a DIN bar thermostat,

saving energy and reducing noise. The inside circuit fan runs permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.

www.erdin

cklim

a.com

Page 27: Kelvin

KSA

Standard Optionals

IP55

CE

MODEL:

Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

IP55 protection degree

3 meters power supply cableconnected in therminal board

External air path deflector

IP54 self adhesive gasket

User manual in five languages

Adjustable DIN bar thermostat to control external circuit fans

Inlet 3 pole connector

Internal air path deflector

Non standard painting

107 318

12

50

EX

TE

RN

AL

AS

SE

MB

LY

INT

ER

NA

L A

SS

EM

BLY

39

KSA 21

230 - 50/6080

1700,75

185085073

-5 +55IP5418

C,D,V,W

V - HzW/KWAA

m³/hm³/h

dB(A)°CIPkg

www.erdin

cklim

a.com

Page 28: Kelvin

40

MODELLO:

Power supply (C)Air flow rateDissipation powerFrontal air speedAbsorption Current absorptionProtection degreeNoise levelColorsPower supply cableDimension W D HWeight Available power supplies

KEA 60 / 100

KEA 200

VENTILATORShe KEA ventilation systems offer a wide range of functional solutions to cool control boards with primary air. There are two types available: the wall mounted version and the mini-tower for roof mount installations on control boards. They have a particularly high air flow rate. Ventilation Twith filtration represents an efficient solution in those cases in which the working ambient air is clean and the temperature inside the cabinet can

be higher than the external one. KELVIN offers with the KEA product line a solution panoramic suitable to satisfy any applicative, aesthetic and technical need. The new and exclusive KEA200 has a wide filtering area. This highly efficient design practically eliminates the need to clean the filters and represents a perfect example of KELVIN's continual commitment to developing new and innovative designs for the future.

KEA 200

230 - 50/60700210

185 / 90

0,38 / 0,4IP3368

RAL70323

30090

150014

C,D,V,W

KEA 100

230 - 50/60700210

85 / 900,38 / 0,4

IP3368

RAL 70323

375295915,9

C,D,V,W

KEA 60

230 - 50/60450135

80 / 980,36 / 0,44

IP3360

RAL70323

375295915,6

C,D,V,W

V - Hzm³/hW/KMsWAIP

dB (A)

mmmmmmmKg

CE

All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space

www.erdin

cklim

a.com

Page 29: Kelvin

nti-condensate heaters are indispensable to avoid condensate from forming inside the cabinet during a unit's standstill and in instances of very low ambient temperatures or very high humidity. Since hot air tends to rise they have to be positioned in the lower part and possibly beneath Athose components that require protection. Maximum efficiency is reached installing the heater in a vertical position and orientating the supply

cable downwards. In case of large cabinets it is advisable to use multiple low rate heaters to obtain an unvarying temperature distribution. All KELVIN heaters are provided with a snapping fitment for the DIN EN 5002 conform 35 mm bar.

ANTICONDENSATIONHEATINGS

MAXI VENTILATED

Power supply

Heating capacity (W)

Maximum amperage (A)

Superficial temperature (°C)

Protection class

Protection degree

Approvals

Mounting

Dimensions (mm)

K5R035

250

1,5

75

I

20

VDE, UL

80 x 80 x178

K5R036

400

2,2

75

I

20

VDE, UL

80 x 80 x252

MINI

Power supply

Heating capacity(W)

Maximum amperage (A)

Superficial temperature (°C)

Protection class

Protection degree

Mounting

Approvals

K5R037

10

0,8

70

II

54

VDE, UL

AC/DC 110 - 250 max. 265V

CR TERM. + VENTIL.

Power supply

Air flow rate (m³/h)

Heating capacity (W)

Maximum amperage (A)

Protection class

Protection degree

Approvals

Mounting

Range of regulation (C°)

Dimensions (mm)

K5R040

35

350

7,5

20

UL

0 - 60

K5R041

35

350

11

20

UL

0 - 60

K5R042

45

550

8,5

20

UL

0 - 60

Bar 35mm. DIN EN 50022

K5R043

45

550

12

20

UL

0 - 60

II ( double isolation)

AC 220-230 / 50-60Hz

MIDI

Power supply

Heating capacity (W)

Maximum amperage (A)

Superficial temperature (°C)

Protection class

Protection degree

Approvals

Mounting

K5R028

15

0,5

165

I test 1600V

20

-

AC/DC 110-250V max. 265V

AC 110-120 / 50-60Hz

K5R029

30

1

190

I test 1600V

20

-

K5R030

45

1

105

I test 1600V

20

-

K5R031

60

1,5

110

I test 1600V

20

-

K5R032

75

1,8

110

I test 1600V

20

-

K5R033

100

2,4

130

I test 1600V

20

-

K5R034

150

4,5

140

I test 1600V

20

-

K5R038

20

1

110

II

54

VDE, UL

K5R039

30

1,5

120

II

54

VDE, UL

41

AC 220-230 / 50-60Hz

100 x 128 x 165

Bar 35mm. DIN EN 50022

Bar 35mm. DIN EN 50022

Bar 35mm. DIN EN 50022

www.erdin

cklim

a.com

Page 30: Kelvin

MODEL:

Range of regulationContact capacityPrecisionProtection degreeAmbient temperatureDimensions (HxWxD)

K9S.022

from 50 to 100% UR5 A to 230V

+/- 3%IP20

from 0° to 60°67x50x38 mm

MODEL:

Range of regulationContact capacityAssemblyDifferential commutationProtection degreeApprovationBoxDimensions (HxWxD)

K7H.020 - K7H.021

from 0° to +60°C6A (1) 250 V ACDIN bar 35 mm

7KIP30

VDE, ULPlastic (UL94V0)

60x33x35 mm

7H.020 and K7H.021 are two electro-mechanical bimetal thermostats with contactors, which are normally open (with a blue regulation screw) and normally closed (with a red regulation screw) respectively. The former is suitable in controlling cooling devices (air-conditioners, air-water Kheat exchangers, air-air heat exchangers, and fans) or to provide high temperature alarms. The latter is suitable in controlling heating or

anticondensate devices (anticondensate heaters) K9S.022 is a humidistat with a 35 mm DIN bar (EN 5002) mount and generally used to control the anticondensate heaters.

K7H.020 K7H.021 K9S.022

Functional scheme of K7H.021 e del K9S.022.

Functional scheme of K7H.020.

42

ACCESSORIES