Next step in IEC 61850: Large applications and process bus applications José Roberto Moreira Rodrigues Clemens Hoga

Upload: hoanghuong

Post on 18-Jun-2018

227 views

Category:

Documents


2 download

TRANSCRIPT

Next step in IEC 61850:

Large applications and process bus applicationsJosé Roberto Moreira Rodrigues

Clemens Hoga

Agenda

• Process bus application

• Large Applications

IEC 61850 Overview

To be harmonized

with CIM

IEC 61970*Control Center

IEC 61850IEC 61850

IEC 61850 (Ethernet)

Protection & Control

Firewall

Router

Digital Instrument Transformer

Data via IEC61850-9-2

IEC61850 Station Bus

Merging

Unit

IED IED

communication

to other

substatons*

IEC61850 Process Bus

*standardization

in work

CT

VT

CBC

x

Circuit

Breaker

Controller

Benefits of IEC 61850-9-2 Process Bus

• Standardized communication interface on Ethernet

• Enabling Non Conventional Instrument Transformer Technology

• Saves cables and other hardware structures

• Saving engineering efforts

• Eases installation and maintenance

• Basis for intelligent switchgear and extended monitoring

features

Prototype Merging Unit

IEC 61850-9-2 Prototypes

Merging Unit

9-2 LE

Process Bus

InterfaceProcess/Station

Bus Interface

Off the shelve switches or

Ethernet Switch Prototypes

with Real Time availability

7SA 525

Distance Protection

Hall

sensor

Siprotec

as CB

Controller

Lopo

Conventional

..other

types

Prototype Merging Unit

IEC 61850-9-2

Merging Unit OverviewSV 60...250Vdc

4x I (1A)

IEC 60044-1

IEC 60044-2

IEC 60044-7/-8

4x LoPo +/-10V

4x U (100/110V 3)

SPI

NCT

Optical / Hall/..

z.B. ISH

PS-1

PS-2

SV 60...250Vdc

PPS

Life

2x IEC61850

Communication ExtensionSYNC

Kontroll-LEDs

DC/AC

I

B

redundant

• Samples Must not get lost

• Samples blocking free

• Trip signal, non blocking, highly redundant

• < 1µs Time Sync via the Ethernet

• Client Server for e.g. monitoring

and SV/GOOSE on the same wire/fiber

Requirements for a Process Bus

Communication

Cycle 1 Cycle 2 Cycle n

RTE channel

Openchannel

(IP)

RTE channel

Openchannel

(IP)

E.g. 1 ms control cycle

IP dataRTE data

Deterministic communication Open communicationSynchro-nization

Communication system scheduling

- separate time domains for real-time and non-real-time -

Why not a Real Time Ethernet Solution ?

• Principle of the bandwidth reservation

– Preprogrammed noninteruptable Data

transfer inside

the IRT Channel

– Unlimited TCP/IP-traffic in the open Channelreserved lane for IRT

TCP/IP

TCP/IP

TCP/IP

Exit

TCP/IP TCP/IP

TCP/IP TCP/IP

IRTIRTIRTIRTIRTIRT

Bandwidth Reservation

TCP/IP

IEC 61850 Protocol Stack combined with RTE

ISO /IEC 8802.3

ISO/IEC 8802.3 Ethertype

Sampled

ValuesGOOSE

UDP/IP

SNTP

TCP/IP

MMS

Protocol suite

Priority Tagging IEEE 802.1Q

RTE IEC 61784-2 CP3/6

TR

IP o

ve

r b

us

Minor extensions, maximum effectT

ime

syn

c o

ve

r b

us

Digitized CT/VT

valuesIED to IED

Interlocking

1ms station

bus time sync

Station Controller

to IED communication

Merging

Unit 1

Merging

Unit 2

Demonstration use of Real time Ethernet

Process Bus incl. Access Switch

Lo

Po

HA

LL

CT

1 A

Lo

Po

OMICRON

CPC 100(AC / DC source)

SICAM PAS

Control: CB onSampled ValuesReport of measured valuesTrip - GOOSEReport CB off

IRT Access

Switch

Clock, e.g. GPS

x

Protection

RelayCB-Control

3rd party

device

IRT Access

Switch

IEEE 1588 Time sync via the Bus

Merging

Unit 1

Merging

Unit 2

Lo

Po

HA

LL

CT

1 A

Lo

Po

Protection

Relay

flicker free

redundant

Ethernet

CB-control

1µs time sync

Ethernet

Bay Switch

Master Clock

Output

Slave Clock

Output

Clock, e.g. GPS

Research and Development Project

„intelligent Switchgear“

Station Nehden

Source: Jochen Haude, RWE

RWE Westfalen-Weser-Ems Netzservice 5.5.2008 SEITE 15

110 kVT412380 kV

Source: Jochen Haude, RWE

110 kVT412380 kV

MergingUnit

Transf. Monitoring

OLTCMonitoring LS IED

Merging UnitOLTC IED

samples

no samples

MU

Sensor-data

Station control/

Remote control

I >(30 kV)

Disturb.

recorder

Messung

Diff.-Prot.

Disturb.

recorder

I >Buchholz

Disturb.

recorder

Measur.

HMIDistanz.

Sync.

Disturb.

recorder

Measur.

TesttoolU-control

CT / VT

alarms

Baycontroller

MUMU

MergingUnit

LS IED

CT / VT

alarms

Merging Unit

Baycontroller

Centralunit

IEC 61850

Service-PCprinter

Remote service

1 ppsSNTP

Source: Jochen Haude, RWE

• Bandwidth Reservation

Guaranteed response times

• Bumpless Redundancy

In the case of interruption not even one telegram gets lost

• < 1µs Time Sync via the Ethernet

IEEE 1588 Precision Time Protocol Redundancy for the time sync

• Real Time and non-Real-Time (TCP/IP) on the same wire/fiber

All signals available at each port

• Conversion IEC 61850-9-2 LE to RTE in a external switch possible

• Other domains have the same requirements and discuss similar solutions

IEEE 802.1avb

• Bumpless redundancy and use of IEEE 1588 is now

discussed in IEC and IEEE PSRC

Real-Time Ethernet add-on advantages

Large Applications

SICAM PAS CCIHM2

IEC-101 sobre

TCP/IP

PAS2

„Full Server“

16 x 7SJ64/ 16 x 6MD64 x (7SA61+7SD52)4 x 7SA618 x 7UT6119 x 7SJ621 x 7SS5216 x medidoresNota: Inclusos relés do contrato da SE GRU

Anhanguera Substation

Control Center Control Center Control Center Control Center Control Center

„Full Server“ „Full Server“ „Full Server“

„Full Server“ „Full Server“

SICAM PAS CCIHM1

Sw1 Sw2

10 x 7SJ64/ 10 x 6MD64 x (7SA6+7SD52)4 x 7SA612 x 7SJ622 x 7UT611 x 7SS528 x medidores

Estação Engenharia (DIGSI/ Recpro)

PAS1

PAS3 PAS4 PAS5 PAS6

PAS7 PAS8

Setor 1 – 345kV Setor 2 – 230kVSetor 3 – 88kV

16 x 7SJ64/ 16 x 6MD68 x 7SA616 x 7SJ621 x 7SS5214 x medidores1 x Sistema paralelismo e Cj. Sensores Temperatura TREE TECH

GerenciadorVídeo Wall

IEC-101

Sw3

SICAM PAS CCIHM345

IEC-61850

SICAM PAS CCIHM230

Sw4 Sw5 Sw6

SICAM PAS CCIHM88

Sw7 Sw8

TS2TS1

PAS2

„Full Server“

Anhanguera – HMI’s

„Full Server“ „Full Server“ „Full Server“ „Full Server“ „Full Server“

Sw1 Sw2

HMI 1 - SCCSICAM PAS CC

HMI 2 - SCCSICAM PAS CC Estação Engenharia

(DIGSI/ Recpro)

PAS1

PAS4 PAS5 PAS6 PAS7 PAS8

Setor 1 – 345kV Setor 2 – 230kV Setor 3 – 88kV

Sw3

GerenciadorVídeo Wall

HMI 3 – SCS-345SICAM PAS CC

HMI 4 – SCS 230SICAM PAS CC

HMI 5 – SCS 88SICAM PAS CC

Sw5 Sw6

Sw7

IEC-101 sobre TCP/IP

Sw4

Sw8

PAS3

„Full Server“ „Full Server“

IEC-101 sobre TCP/IP

Control Center Communication

Control Center Control Center Control Center Control Center Control Center

Sw1 Sw2

Sw4

Sw8

Sw5

IEC-101

TS800-2TS800-1

Modem Modem Modem Modem Modem ModemModem

Modem

Modem Modem Modem Modem

Modem Modem

Modem Modem

Modem Modem

Modems6-10

Modems1-5

IEC-101

Modems11-12

Modems13-14

Modems15-16

Modems17-18

Modems19-20

Nota: deve ser confirmado meio de comunicação.

PAS1 PAS2

ModemModem

Sw3 Sw6

Sw7

Petrobras Substation Automation Solution