Page 1: Intouch 9.0 v

Configuration Manual For SCADAIntouch v9.0

Page 2: Intouch 9.0 v

Configuration Manual for SCADA Table of Contents

2

Table of Contents

Chapter 1 Intouch v9.0 .................................................................................................... 3 1-1 OPC Server ............................................................................................................ 4 1-2 Connect OPC Client to OPC Server through Intouch v9.0 ..................................... 5 

Page 3: Intouch 9.0 v

Chapter 1

Intouch v9.0

Page 4: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

4

1-1 OPC Server Please create tags according to the Configuration Manual.

Later, click [ File ] [ Make Active ] to activate new created configuration file.

Page 5: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

5

1-2 Connect OPC Client to OPC Server through Intouch v9.0 Start OPCLink. [ Start ] [ Program ] [ Wonderware ] [ IO Servers ] [ OPCLink ]

[ Configure ] [ Topic Definition ]

Click [ New ] to add new Topic

Page 6: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

6

OPC Link Topic DefinitionDescription

Column Description Topic Name Topic Name Node Name Remote OPC Server

(IP or name of Remote PC/ Please skip this column if there is no remote pc be connected with.)

OPC Server Name The OPC Server to be connected with OPC Path Group of OPC Server

Page 7: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

7

Here takes Modbus as an example First, Define the Topic Name as ”Test_Modbus”.

Please select ”OPCTechs.Modbus30DA.3”.

Page 8: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

8

Click ”Browse” on “OPC Path” to choose the Data Item, and then click [ OK ].

Click [ OK ]

Page 9: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

9

Click [ Done ].

Do not close OPClink, Please continue the following issue without closing OPClink.

Page 10: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

10

Start InTouch program. [ Start ] [ Programs ] [ Wonderware ] [ InTouch ] create a new project. Select [ Access Names ] on the tree view.

Click [ Add ] to create a new “ Access Names”.

Page 11: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

11

Description of Access Name Configuration

Column Description Access Access name Node Name Remote OPC Server

(IP or name of Remote PC/ Please skip this column if there is no remote pc be connected with.)

Application Name Application name Topic Name Topic name of the application Which protocol to use When to advise server

Page 12: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

12

The configuration of OPC Link connection. Please select [ OK ].

Column Description Access Test Node Name Please skip this column if there is no

remote pc be connected with. Application Name OPCLINK Topic Name Test_Modbus (Topic Name of

OPCLINK) Which protocol to use Suite Link When to advise server Advise only active items

A “test” project will be created.

Page 13: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

13

Select [ Tagname Dictionary ] to create new tags connected to Access Names.

Create a new Tag.

Type in “AI01” in [ Tagname ]; then click [ Type ] to select the Tag Type.

Page 14: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

14

Please select “source “.

Click [ Access Name ] to select the Access Name you need.

Select the “test” to be connected, and then click [ Close ].

Page 15: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

15

Type in the Tag connected to OPC Server. The format of Tag name must follow: {Tag Type}+{Tag Name} D:Discrete Value、I:Integer Value、R:Real Value、M:Message Value

IAI_01

Click [ Save ].

Page 16: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

16

Select [ Text ] and type ”####”.

Press the right key of the mouse selecting [ Animation Links ].

Page 17: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

17

Click [ Analog ] to select the data source.

Double click on the “ Tagname”.

Page 18: Intouch 9.0 v

Configuration Manual for SCADA Intouch v9.0

18

Please select “AI01 “.

Click [ OK ].

Page 19: Intouch 9.0 v

Intouch v9.0 Configuration Manual for SCADA

19

Start Intouch program.