inspection, testing, and maintenance fire sprinkler system nfpa 25...

5
Property Information: Name: ___________________________________ Address: _________________________________ City: _____________________________________ Zip: ______________________________________ Contact: __________________________________ Phone: ___________________________________ Contractor Information: Name: ___________________________________ Address: _________________________________ City: _____________________________________ Zip: ______________________________________ Contact: __________________________________ Phone: ___________________________________ Main Drain Test Results: System Riser ID: __________ Initial Static Pressure: ____________________ (psi) Residual Static Pressure: ____________________ (psi) Restored Static Pressure: ____________________ (psi) Type of System: Wet Pipe Dry Pipe Preaction Deluge Abbreviation Key: I = Inspection T = Test M = Maintenance A-O = After Operation MI = Per Manufacturer’s Instructions CA Licence #: ________________________________________ Job#: _______________________________________________ Performed By: ________________________________________ Occupancy Use: ______________________ Construction Type: ____________________ No. Stories: __________________________ Year Constructed: ____________________ Date of Inspection, Testing, Maintenance: _________________ Number of System Risers: _____ Copy Sent To: Owner Date: ___________ Fire AHJ: Date: ___________ Contractor Date: ___________ Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Page 1 1) For specific inspection, testing and maintenance requirements and information, see NFPA 25, 2002 Edition as amended by California Code of Regulations, Title19, §901 to §906. 2) Inspection Items may be performed by the Owner in accordance with California Code of Regulations Title 19 §904.1(a). NOTES: Forms included with this report Automatic Sprinkler System Standpipe and Hose Systems Private Water Supply System Fire Pump Water Storage Tank Water Spray System Foam Water Sprinkler System * See “Deficiencies and Comments” section at the end of each respective form. NFPA 25 Chapter Number of Forms N/A FAIL* PASS Item 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 I I I I I I I I I I I I I I I I I Daily / Weekly Daily / Weekly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Quarterly Annually Preaction/Deluge Valves - Enclosure Temp. Dry Pip Valves - Enclosure Temp. Gauges (Dry, Preaction, Deluge Systems) 5.2.4.2 / 5.2.4.3 Control Valves Alarm Devices Gauges (Wet Pipe Systems) Hydraulic Nameplate Pipe and Fittings Sprinklers Spare Sprinklers Fire Department Connections Alarm Valves - Exterior Inspection Preaction/Deluge Valves - Exterior Inspection Pressure Reducing Valves Dry Pipe Valves - Exterior Inspection Backflow Preventers Buildings 12.4.3.1 12.4.4.1.1 12.3.2.1 5.2.6 5.2.4.1 5.2.7 5.2.2 5.2.1 5.2.1.3 12.7.1 12.4.1.1 12.4.3.1.6 12.5.1.1 12.4.4.1.4 12.6.1 5.2.5 Activity Frequency Description PASS FAIL N/A NFPA 25 Reference

Upload: vannhu

Post on 19-Oct-2018

232 views

Category:

Documents


1 download

TRANSCRIPT

Property Information:

Name: ___________________________________

Address: _________________________________

City: _____________________________________

Zip: ______________________________________

Contact: __________________________________

Phone: ___________________________________

Contractor Information:

Name: ___________________________________

Address: _________________________________

City: _____________________________________

Zip: ______________________________________

Contact: __________________________________

Phone: ___________________________________

Main Drain Test Results:

System Riser ID: __________ Initial Static Pressure: ____________________ (psi) Residual Static Pressure: ____________________ (psi) Restored Static Pressure: ____________________ (psi)

Type of System:

Wet Pipe Dry Pipe Preaction Deluge

Abbreviation Key:

I = InspectionT = TestM = MaintenanceA-O = After OperationMI = Per Manufacturer’s Instructions

CA Licence #: ________________________________________

Job#: _______________________________________________

Performed By: ________________________________________

Occupancy Use: ______________________

Construction Type: ____________________

No. Stories: __________________________

Year Constructed: ____________________

Date of Inspection, Testing, Maintenance: _________________

Number of System Risers: _____

Copy Sent To:

Owner Date: ___________ Fire AHJ: Date: ___________Contractor Date: ___________

Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Page 1

1) For specific inspection, testing and maintenance requirements and information, see NFPA 25, 2002 Edition as amended by California Code of Regulations, Title19, §901 to §906.

2) Inspection Items may be performed by the Owner in accordance with CaliforniaCode of Regulations Title 19 §904.1(a).

NOTES:

Forms included with this reportAutomatic Sprinkler System

Standpipe and Hose SystemsPrivate Water Supply System

Fire PumpWater Storage TankWater Spray System

Foam Water Sprinkler System

* See “Deficiencies and Comments” section at the end of each respective form.

NFPA 25 Chapter Number of Forms N/A FAIL* PASS

Item

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

1.10

1.11

1.12

1.13

1.14

1.15

1.16

1.17

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

Daily / Weekly

Daily / Weekly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Annually

Preaction/Deluge Valves - Enclosure Temp.

Dry Pip Valves - Enclosure Temp.

Gauges (Dry, Preaction, Deluge Systems) 5.2.4.2 / 5.2.4.3

Control Valves

Alarm Devices

Gauges (Wet Pipe Systems)

Hydraulic Nameplate

Pipe and Fittings

Sprinklers

Spare Sprinklers

Fire Department Connections

Alarm Valves - Exterior Inspection

Preaction/Deluge Valves - Exterior Inspection

Pressure Reducing Valves

Dry Pipe Valves - Exterior Inspection

Backflow Preventers

Buildings

12.4.3.1

12.4.4.1.1

12.3.2.1

5.2.6

5.2.4.1

5.2.7

5.2.2

5.2.1

5.2.1.3

12.7.1

12.4.1.1

12.4.3.1.6

12.5.1.1

12.4.4.1.4

12.6.1

5.2.5

Activity Frequency Description PASSFAILN/ANFPA 25Reference

Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Page 2

Item

1.18

1.19

1.20

1.21

1.22

1.23

1.24

1.25

1.26

1.27

1.28

1.29

1.30

2.1

2.2

2.3

2.4

I

I

I

I

I

I

I

I

I

I

I

I

I

T

T

T

T

Annually

Annually

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

5 Years

Annually

Annually

Annually

Annually

Hangers

Seismic Braces

Hangers (Accessible concealed spaces) 5.2.3.3

Seismic Braces (Accessible concealed spaces)Pipe and Fittings (Accessible concealed spaces)

Sprinklers (Accessible concealed spaces)

Alarm Valves - Interior Inspection

Alarm Valves - Strainers, filters, orifices

Check Valves - Interior Inspection

Preaction/Deluge Valves - Interior Inspection

Preaction/Deluge Valves - Strainers, filters, orifices

Dry Pipe Valves - Interior Inspection

Dry Pipe Valves - Strainers, filters, orifices

Alarm Devices (90 seconds)

Main Drain Test (Enter data on page 1)

Antifreeze Test

Control Valve - Position

5.2.3

5.2.3

5.2.3.3

5.2.2.3

5.2.1.1.4

12.4.1.2

12.4.1.2

12.4.2.1

12.4.3.1.7

12.4.4.1.8

12.4.4.1.5

12.4.4.1.6

5.3.3/12.2.7

12.2.6/12.2.6.1/12.3.3.4

5.3.4

12.3.3.1

Activity Frequency Description PASSFAILN/ANFPA 25Reference

2.6

2.7

2.8

2.9

2.10

2.11

2.12

2.13

2.14

2.15

2.16

2.17

2.18

2.19

2.20

2.21

2.22

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

Annually

Annually

Annually

Annually

Annually

Annually

Annually

Annually

Annually

3 Years

5 Years

5 Years

5 Years

5 Years

5 Years

10 Years

20 Years

Supervisory

Preaction Valve - Priming Water

Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10

Preaction Valve - Full Flow Trip Test

Dry Pipe Valve - Priming Water

Dry Pipe Valve - Low Aire Pressure Alarm

Dry Pipe Valve - Quick Opening Device

Dry Pipe Valve - Trip Test

Backflow Preventer Assemblies

Dry Pipe Valve - Full Flow Trip Test

Gauges

Pressure Reducing Valve

Fire Department Connection Backflush

Sprinklers - Extra High Temperature

Sprinklers - Corrosive environment orcorrosive water

Sprinklers - Dry

Sprinklers - Fast Response

12.3.3.5

12.4.3.2.1

12.4.3.2.2

12.4.4.2.1

12.4.4.2.6

12.4.4.2.4

12.4.4.2.2

12.6.2

12.4.4.2.2.2

5.3.2

12.5.1.2

12.7.4

5.3.1.1.1.3

5.3.1.1.2

5.3.1.1.1.5

5.3.1.1.1.2

2.5 T Annually Control Valve - Operation 12.3.3.1

2.23

2.24

2.25

3.1

3.2

3.3

3.4

3.5

T

T

T

M

M

M

M

M

50 Years

75 Years

Annually

Annually

Annually

Annually

5 Years

Sprinklers

Sprinklers 75 years in service

Sprinklers manufactured prior to 1920 - Replace

Control Valves

Preaction/Deluge Valves

Dry Pipe Valves/Quick-Opening Devices

Dry Pipe Valve - Low Point Drains

Obstruction Investigation

5.3.1.1.1

5.3.1.1.1.4

5.3.1.1.1.1

12.3.4

12.4.3.3.2

12.4.4.3.2

12.4.4.3.3

Chapter 13

Date of Inspection, Testing, Maintenance: _______________

Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Page 3

Date of Inspection, Testing, Maintenance: _______________

Deficiency List

Quarterly Annual 5 Year

Abbreviation Key:

INTERIORB = BedroomMB = Master BedroomMBA = Master BathMC = Master ClosetBA = BathK = KitchenLR = Living RoomDR = Dining RoomH = HallwayP = Patio/BalconyE = Entry Way

LO = LoftLC = Loft Closet2F = Second FloorC = ClosetL = LaundryB2 = Second BedroomB3 = Third BedroomUTIL = Furnace/Water Heater

EXTERIORPK = Parking/Car PortG = Gas RoomELEC = Electrical RoomM = Maintenance LR = Laundry RoomFC = Fitness CenterMR = Media RoomCH = Club HouseTH = TheaterGYM = GymLOB = LobbyO = Office

PL = Pool/Pool RoomPR = Pump RoomEL = Elevator RoomH = HallwayS = Stairs1 = First Floor2 = Second Floor3 = Third Floor4 = Fourth FloorMR = Men’s RestroomWR = Women’s RestroomESCT. = Escutcheon

Bldg./Apt. Item Painted Bent Esct. Corroded Loaded Recalled Comments

Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Continued

Bldg./Apt. Item Painted Bent Esct. Corroded Loaded Recalled Comments

Property Information:

Name: ___________________________________

Address: _________________________________

City: _____________________________________

Zip: ______________________________________

Contact: __________________________________

Phone: ___________________________________

Main Drain Test Results: (use if additional space is needed)

System Riser ID: _______________________ Initial Static Pressure: ______________________________________________________________________ (psi) Residual Static Pressure: ______________________________________________________________________ (psi) Restored Static Pressure: ______________________________________________________________________ (psi)

Type of System:

Date of Inspection, Testing, Maintenance: _________________

Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Page 4

Total Deficiency Breakdown:

Comments:

TOTAL SPRINKLER HEADS TO REPLACE

TOTAL SECTIONS OF PIPE TO STRIAGHTEN PER 15’TOTAL SECTIONS OF PIPE TO REPLACE PER 15’

TOTAL SIGNS NEEDED

TOTAL LOCKS NEEDEDTOTAL VALVES TO REPLACE

TOTAL FDC CAPS NEEDED

TOTAL FLOW SWITCHES TO REPLACETOTAL STANDPIPE CAPS NEEDED

TOTAL JUNCTION BOXES TO RELOCATETOTAL GAUGES TO REPLACETOTAL SPRINKLER ESCUTCHEONS TO REPLACE

Wet Pipe Dry Pipe Preaction Deluge

PASSFAIL Signature: ______________________________________ Date: _________________