Industrial Rental Trailer-MountedGenerator Set and Switchgear Power Control Systems
1500/2000 kW
Rental Power Control Systems
Standard Features
� These sophisticated Power Control Systems combine a
generator set and switchgear with paralleling capabilities
for up to eight other generator sets and/or a single utility
providing prime or standby power for critical situations.
� The design allows for automatically starting, stopping,
and paralleling the generator sets.
� The paralleling switchboard contains the operator
interface, controls, protective relays, and circuit
breaker(s) required for the generator set to operate in
parallel.
� Kohler Rental Power provides one-source responsibility
for the generator set and switchgear system.
TM
Generator Set
Air Inlet Louver
CableAccessDoor
FuelTank
Silencer
Roof Vent
Stairs
PD-150 Switchgear
G32-1 5/02
G32-1 5/02
Trailer
Trailer Features
� Premium sound-attenuated ISO container
� Internal fuel tank with external fuel inlet and fuel pump
� AC input connection (shore power) box for block heater
and battery charger
� Additional engine and generator features as listed on the
respective generator set specification sheet
� Easy access cable hatch with locking capabilities
� Fire extinguisher
� Work lights with timer
� Stowable stairs with safety railing
� Running lights with standard DOT 7-way receptacle
Trailer Specifications
Generator SetTrailer* Dimensions, mm (in.)
Generator Set Weight Trailer Gross Fuel Tank CapacityGenerator SetModel Length Width Height
Generator Set Weight,kg (lb.)
Trailer GrossWeight,� kg (lb.)
Fuel Tank Capacity,L (gal.)
1500ROZD-4 12292 (480) 2438 (96) 4064 (160) 13698 (30200) 26072 (57480) 3785 (1000)
2000ROZD-4 12192 (480) 2438 (96) 4064 (160) 15876 (35000) 27307 (60200) 3785 (1000)
* Trailer dimensions include the enclosure, chassis, and axle/wheels.� Trailer gross weight includes trailer (enclosure, chassis, and axle/wheels), generator set, switchgear, and fuel tank with no fuel.
Generator SetGenerator Set Features
� Battery, battery rack, and battery cables
� Electronic isochronous governor providing precise
frequency regulation
� Battery charger
� Engine block heater
� Exhaust silencer
Generator Set Specifications
Generator Set Generator130�C Standby Rating, 277/480 Volt, 3 Ph, 60 Hz
Sound Level dBA with NoGenerator SetModel Engine Model
GeneratorModel Amps kW/kVA
Sound Level dBA with NoLoad at 7 m (21 ft.)
1500ROZD-4 DDC Series 4000 7M4050 2255 1500/1875 80
2000ROZD-4 DDC Series 4000 7M4054 3007 2000/2500 82
Generator Set Generator130�C Standby 60 Hz. Rating, Fuel Consumption, Lph (gph)
Generator SetModel Engine Model
GeneratorModel 25% Load 50% Load 75% Load 100% Load
1500ROZD-4 DDC Series 4000 7M4050 108.6 (28.7) 215.8 (57.0) 284.3 (75.1) 382.8(101.1)
2000ROZD-4 DDC Series 4000 7M4054 142.7 (37.7) 260.4 (68.8) 375.1 (99.1) 508.8(134.5)
Note: See the respective specification sheets for generator set specifications not shown. Refer to the Additional Literature table.
Electrical Power Panel Specifications
Generator SetModel Load Lug Connections
Main Circuit Breakers,Amp Rating
Shore Power Electrical Service and Hookup forBattery Charger and Block Heater
1500ROZD-4 (8) 3/0--750 MCM 2500 40 Amp/240 Volt
2000ROZD-4 (9) 3/0--750 MCM 3000
40 Amp/240 VoltPower Cord Required
G32-1 5/02
PD-150 Switchgear
Switchgear Features
� Random-access automatic paralleling switchgear allows
unattended operation of paralleled Kohler� generator sets.
� The main bus is sized for the standby current rating. Bus
bracing is designed for fault current equal to the circuit
breaker fault current.
� The switchgear supports 277/480 VAC, 3-phase, 4-wire,
60 Hz electrical systems.
� UL-891listed and labeled
� Service entrance rated
� Metering setup, control, and monitoring via the door-
mounted digital paralleling controller
� Multifunction utility-grade intertie protective relay
� Full capacity neutral bus
� Modes of operation
� Prime power
� Emergency
� Isolate
� Import/export
� Base load generator
� Automatic synchronizer
Component Specifications
Environmental Requirements
Ambient operating temperature rating of --16�C to 70�C
(4�F to 158�F).
Cable Connections
Drilled bus bars and setscrew-type Cu/Al cable lugs are
standard for utility and load connections.
Circuit Breakers
Draw-out electrically operated power circuit breakers are
standard. The circuit breakers are UL listed and equipped with
shunt trip and a microprocessor-based, true RMS sensing trip
unit for overload and short circuit protection. Service
entrance-rated utility circuit breakers include ground fault
protection.
Generator Set Power Controller
A microprocessor-based generator set power controller contains
the system logic, automatic synchronizer, and generator load
control.
Generator Protective Relays
A microprocessor-based, multifunction generator power control
and management module provides all generator relaying and
control functions.
� Over/Undervoltage. Provides voltage protection by opening
the generator set circuit breaker when voltage strays outside
of preset parameters.
� Over/Underfrequency. Provides frequency protection by
opening the generator set circuit breaker when frequency
strays outside of preset parameters.
� Reverse Power. Provides reverse-power protection by
opening the generator circuit breaker when reverse power
exceeds a preset limit for a preset length of time.
� Loss of Excitation. Provides protection for the generator set
upon loss of field.
Intertie Protective Relays
The multifunction intertie protective relay offers the following
protection:
� Phase undervoltage
� Phase overvoltage
� Over/underfrequency
� Negative sequence current
� Dual setpoint negative sequence voltage
� Potential transformer fuse loss detection
� Phase directional overcurrent
� Rate of change frequency
Availability is subject tochangewithout notice.Kohler Co. reserves the rightto change the design or specifications without notice and without anyobligation or liability whatsoever. Contact your local Kohler�RentalPowerregional office for availability. � 2002 by Kohler Co.. All rights reserved.
DISTRIBUTED BY:
KOHLER CO., Kohler, Wisconsin 53044 USAPhone 920-459-1634; Fax 920-459-1846For the nearest sales and service outlet in the US andCanada, phone 1-888-769-3794 or KohlerRentalPower.com
TM
G32-1 5/02
PD-150 Modes of OperationSelect the operating mode locally with the keyswitch on the front
panel. Initiate operation locally with the Local Control Switch or
via remote contact closure.
Prime Power/Remote ATS Start
The system can parallel up to 8 generators in parallel on an
isolated bus.
Emergency
With utility power connected to the PD-150 utility circuit breaker,
the PD-150 operates as a self-contained emergency standby
switchgear system.
Base Load Generator
The generator set remains paralleled to the utility and is loaded
to a user-adjustable kW level. When generator output power
exceeds local load requirements, the surplus power is directed
to the utility grid. When local load requirements exceed the
generator base load level, the utility supplies the remaining load
requirement.
Isolate
Local load transfers from the utility grid to the generator set.
The system operates independently from the utility source until
an operator terminates Isolate operation.
Import/Export
The customer chooses between exporting power to the utility
grid and importing a user-adjustable level of power from the
utility.
When importing power, the system is configured so that a
constant, user-adjustable kW level flows in from the utility.
Generator output power fluctuates to meet differences between
the utility import level and actual system load.
When exporting power, the system is configured so that a
constant, user-adjustable kW level flows to the utility from the
generator set. Generator output power fluctuates to meet
differences between the export level and actual system load.
The system does not allow the generator set to ever exceed its
maximum capacity.
PD-150 System Configuration
Additional Literature
Generator Set Model
Generator SetSpec Sheet
Industrial Rental Trailer-MountedGenerator Set Spec Sheet
Generator SetController
ControllerSpec Sheet
SwitchgearSpec Sheet
1500ROZD-4 G5-196G5 186 Decision Maker� 550 G6 46 G11 84
2000ROZD-4 G5-198G5-186 Decision-Maker��550 G6-46 G11-84